Endress + Hauser Operating Instructions Liquisys M CLM223/253 Transmitter for Conductivity
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
BA00193C/07/EN/15.15
71300836
Products
Solutions
Operating Instructions
Liquisys M CLM223/253
Transmitter for Conductivity
Services
Liquisys M CLM223/253
Table of contents
Table of contents
1
Document information . . . . . . . . . . . . . . 5
6.3
1.1
1.2
1.3
1.4
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols on the device . . . . . . . . . . . . . . . . . . .
Electrical symbols . . . . . . . . . . . . . . . . . . . . . .
Local operation . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.1 Automatic/manual mode . . . . . . . . . . 29
6.3.2 Operating concept . . . . . . . . . . . . . . . 30
7
Commissioning . . . . . . . . . . . . . . . . . . . . 32
2
Basic safety instructions . . . . . . . . . . . . 7
2.1
2.2
2.3
2.4
2.5
Requirements for personnel . . . . . . . . . . . . . . .
Designated use . . . . . . . . . . . . . . . . . . . . . . . .
Occupational safety . . . . . . . . . . . . . . . . . . . . .
Operational safety . . . . . . . . . . . . . . . . . . . . . .
Product safety . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.1 State of the art . . . . . . . . . . . . . . . . . .
2.5.2 IT security . . . . . . . . . . . . . . . . . . . . . .
7.1
7.2
7.3
7.4
3
Incoming acceptance and product
identification . . . . . . . . . . . . . . . . . . . . . . . 9
3.1
3.2
3.3
Incoming acceptance . . . . . . . . . . . . . . . . . . . .
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . .
Product identification . . . . . . . . . . . . . . . . . . .
3.3.1 Nameplate . . . . . . . . . . . . . . . . . . . .
3.3.2 Product identification . . . . . . . . . . . .
Certificates and approvals . . . . . . . . . . . . . . .
3.4.1 mark . . . . . . . . . . . . . . . . . . . . . .
3.4.2 CSA General Purpose . . . . . . . . . . . . .
7.5
Function check . . . . . . . . . . . . . . . . . . . . . . .
Switching on . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . .
Device configuration . . . . . . . . . . . . . . . . . . .
7.4.1 Setup 1 (conductivity) . . . . . . . . . . . .
7.4.2 Setup 2 (temperature) . . . . . . . . . . . .
7.4.3 Current input . . . . . . . . . . . . . . . . . .
7.4.4 Current outputs . . . . . . . . . . . . . . . . .
7.4.5 Alarm . . . . . . . . . . . . . . . . . . . . . . . .
7.4.6 Check . . . . . . . . . . . . . . . . . . . . . . . .
7.4.7 Relay configuration . . . . . . . . . . . . . .
7.4.8 Temperature compensation with
table . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.9 Concentration Measurement . . . . . . .
7.4.10 Service . . . . . . . . . . . . . . . . . . . . . . .
7.4.11 E+H Service . . . . . . . . . . . . . . . . . . . .
7.4.12 Interfaces . . . . . . . . . . . . . . . . . . . . .
7.4.13 Communication . . . . . . . . . . . . . . . . .
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Diagnostics and troubleshooting . . . 81
8.1
8.2
8.3
8.4
Trouble shooting instructions . . . . . . . . . . . . .
System error messages . . . . . . . . . . . . . . . . . .
Process-specific errors . . . . . . . . . . . . . . . . . .
Device-specific errors . . . . . . . . . . . . . . . . . . .
9
Maintenance . . . . . . . . . . . . . . . . . . . . . . 90
9.1
Maintenance of the entire measuring point . .
9.1.1 Cleaning the transmitter . . . . . . . . . .
9.1.2 Cleaning the conductivity sensors . . .
9.1.3 Simulation of conductive sensors for
device testing . . . . . . . . . . . . . . . . . .
9.1.4 Simulation of inductive sensors for
device testing . . . . . . . . . . . . . . . . . .
9.1.5 Checking conductive sensors . . . . . . .
9.1.6 Checking inductive sensors . . . . . . . .
9.1.7 Assembly . . . . . . . . . . . . . . . . . . . . .
9.1.8 Connecting cables and junction
boxes . . . . . . . . . . . . . . . . . . . . . . . .
3.4
5
5
5
6
7
7
7
8
8
8
8
9
9
10
10
10
10
10
10
4
Installation . . . . . . . . . . . . . . . . . . . . . . . 11
4.1
4.4
Installation at a glance . . . . . . . . . . . . . . . . . .
4.1.1 Measuring system . . . . . . . . . . . . . . .
Installation conditions . . . . . . . . . . . . . . . . . .
4.2.1 Field device . . . . . . . . . . . . . . . . . . . .
4.2.2 Panel-mounted device . . . . . . . . . . . .
Installation instructions . . . . . . . . . . . . . . . . .
4.3.1 Field device . . . . . . . . . . . . . . . . . . . .
4.3.2 Panel-mounted device . . . . . . . . . . . .
Post-installation check . . . . . . . . . . . . . . . . . .
5
Electrical connection . . . . . . . . . . . . . . 18
5.1
5.2
5.3
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1 Wiring diagram . . . . . . . . . . . . . . . . .
5.1.2 Measuring cables and sensor
connection . . . . . . . . . . . . . . . . . . . .
Alarm contact . . . . . . . . . . . . . . . . . . . . . . . .
Post-connection check . . . . . . . . . . . . . . . . . .
6
Operation options . . . . . . . . . . . . . . . . . 25
6.1
6.2
Quick operation guide . . . . . . . . . . . . . . . . . .
Display and operating elements . . . . . . . . . . .
6.2.1 Display . . . . . . . . . . . . . . . . . . . . . . .
6.2.2 Operating elements . . . . . . . . . . . . . .
6.2.3 Key functions . . . . . . . . . . . . . . . . . .
4.2
4.3
Endress+Hauser
11
12
13
13
14
15
15
17
17
18
18
21
24
24
25
25
25
27
27
10
32
32
34
37
37
39
42
45
49
50
53
69
70
73
75
76
76
77
81
81
84
88
90
90
91
91
92
93
94
94
94
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
10.1 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . 95
10.2 Disassembling the panel-mounted device . . . . 95
10.3 Disassembling the field device . . . . . . . . . . . . 98
10.4 Replacing the central module . . . . . . . . . . . . 102
10.5 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
10.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
3
Table of contents
11
Accessories . . . . . . . . . . . . . . . . . . . . . . 104
11.1
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.1.1 Sensors with conductive
measurement of conductivity . . . . . .
11.1.2 Sensors with inductive measurement
of conductivity . . . . . . . . . . . . . . . .
11.2 Connection accessories . . . . . . . . . . . . . . . . .
11.3 Installation accessories . . . . . . . . . . . . . . . .
11.4 Software and hardware add-ons . . . . . . . . . .
11.5 Calibration solutions . . . . . . . . . . . . . . . . . .
12
104
104
104
105
105
106
107
Technical data . . . . . . . . . . . . . . . . . . . 108
12.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.2 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.3 Power supply . . . . . . . . . . . . . . . . . . . . . . . .
12.4 Performance characteristics . . . . . . . . . . . . .
12.5 Environment . . . . . . . . . . . . . . . . . . . . . . . .
12.6 Mechanical construction . . . . . . . . . . . . . . .
13
Liquisys M CLM223/253
108
108
112
113
113
114
Appendix . . . . . . . . . . . . . . . . . . . . . . . . 115
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
4
Endress+Hauser
Liquisys M CLM223/253
Document information
1
Document information
1.1
Warnings
Structure of information
LDANGER
Causes (/consequences)
Consequences of non-compliance
(if applicable)
‣ Corrective action
LWARNING
Causes (/consequences)
Consequences of non-compliance
(if applicable)
‣ Corrective action
LCAUTION
Causes (/consequences)
Consequences of non-compliance
(if applicable)
‣ Corrective action
NOTICE
Cause/situation
Consequences of non-compliance
(if applicable)
‣ Action/note
1.2
Meaning
This symbol alerts you to a dangerous situation.
Failure to avoid the dangerous situation will result in a fatal or serious
injury.
This symbol alerts you to a dangerous situation.
Failure to avoid the dangerous situation can result in a fatal or serious
injury.
This symbol alerts you to a dangerous situation.
Failure to avoid this situation can result in minor or more serious injuries.
This symbol alerts you to situations which may result in damage to
property.
Symbols used
Additional information, tips
Permitted or recommended
Forbidden or not recommended
1.3
Symbol
Symbols on the device
Meaning
Reference to device documentation
Endress+Hauser
5
Document information
Liquisys M CLM223/253
1.4
Electrical symbols
Symbol
Meaning
A0027423
A0027424
A0027425
A0027426
Direct current
A terminal at which DC is present or through which DC flows.
Alternating current
A terminal to which alternating voltage (sine-wave) is applied or through
which alternating current flows.
Direct current or alternating current
A terminal at which direct voltage or alternating voltage is present or
through which direct current or alternating current flows.
Ground connection
A terminal which, from the user's point of view, is already grounded via a
grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any
other connections.
A0027427
Class II equipment
Reinforced or double insulation
A0019929
Alarm relay
A0027420
Input
A0027428
Output
A0027429
DC voltage source
A0027430
Temperature sensor
A0027431
6
Endress+Hauser
Liquisys M CLM223/253
Basic safety instructions
2
Basic safety instructions
2.1
Requirements for personnel
• Installation, commissioning, operation and maintenance of the measuring system may
be carried out only by specially trained technical personnel.
• The technical personnel must be authorized by the plant operator to carry out the
specified activities.
• The electrical connection may be performed only by an electrical technician.
• The technical personnel must have read and understood these Operating Instructions
and must follow the instructions contained therein.
• Measuring point faults may be repaired only by authorized and specially trained
personnel.
Repairs not described in the Operating Instructions provided may only be carried out
directly by the manufacturer or by the service organization.
2.2
Designated use
Liquisys M is a transmitter for determining the conductivity and resistivity of liquid media.
The transmitter is particularly suited for use in the following areas:
• Ultrapure water
• Water treatment
• Cooling water desalination
• Condensate treatment
• Municipal wastewater treatment plants
• Chemical industry
• Food industry
• Pharmaceutical industry
Use of the device for any purpose other than that described, poses a threat to the safety of
people and of the entire measuring system and is therefore not permitted.
The manufacturer is not liable for damage caused by improper or non-designated use.
2.3
Occupational safety
As the user, you are responsible for complying with the following safety conditions:
• Installation guidelines
• Local standards and regulations
Electromagnetic compatibility
• The product has been tested for electromagnetic compatibility in accordance with the
applicable European standards for industrial applications.
• The electromagnetic compatibility indicated applies only to a product that has been
connected in accordance with these Operating Instructions.
Endress+Hauser
7
Basic safety instructions
Liquisys M CLM223/253
2.4
Operational safety
1.
Before commissioning the entire measuring point, verify that all connections are
correct. Ensure that electrical cables and hose connections are undamaged.
2.
Do not operate damaged products, and safeguard them to ensure that they are not
operated inadvertently. Label the damaged product as defective.
3.
If faults cannot be rectified:
Take the products out of operation and safeguard them to ensure that they are not
operated inadvertently.
2.5
Product safety
2.5.1
State of the art
The product is designed to meet state-of-the-art safety requirements, has been tested, and
left the factory in a condition in which it is safe to operate. The relevant regulations and
European standards have been observed.
2.5.2
IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
8
Endress+Hauser
Liquisys M CLM223/253
Incoming acceptance and product identification
3
Incoming acceptance and product
identification
3.1
Incoming acceptance
1.
Verify that the packaging is undamaged.
Notify your supplier of any damage to the packaging.
Keep the damaged packaging until the matter has been settled.
2.
Verify that the contents are undamaged.
Notify your supplier of any damage to the delivery contents.
Keep the damaged products until the matter has been settled.
3.
Check the delivery for completeness.
Check it against the delivery papers and your order.
4.
Pack the product for storage and transportation in such a way that it is protected
against impact and moisture.
The original packaging offers the best protection.
The permitted ambient conditions must be observed (see "Technical data").
If you have any questions, please contact your supplier or your local sales center.
3.2
Scope of delivery
The delivery of the field device comprises:
• 1 transmitter CLM253
• 1 plug-in screw terminal, 3-pin
• 1 cable gland Pg 7
• 1 cable gland Pg 16 reduced
• 2 cable glands Pg 13.5
• 1 set of Operating Instructions
• For versions with HART communication:
1 set of Operating Instructions: Field communication with HART
• For versions with PROFIBUS interface:
1 set of Operating Instructions: Field communication with PROFIBUS PA/DP
The delivery of the panel-mounted device comprises:
• 1 transmitter CLM223
• 1 set of plug-in screw terminals
• 2 tensioning screws
• 1 set of Operating Instructions
• For versions with HART communication:
1 set of Operating Instructions: Field communication with HART
• For versions with PROFIBUS interface:
1 set of Operating Instructions: Field communication with PROFIBUS PA/DP
Endress+Hauser
9
Incoming acceptance and product identification
3.3
Product identification
3.3.1
Nameplate
Liquisys M CLM223/253
The nameplate provides you with the following information on your device:
• Manufacturer identification
• Order code
• Extended order code
• Serial number
• Ambient and process conditions
• Input and output values
• Safety information and warnings
Compare the data on the nameplate with your order.
3.3.2
Product identification
The order code and serial number of your product can be found in the following locations:
• On the nameplate
• In the delivery papers
Obtaining information on the product
1.
Go to the product page for your product on the Internet.
2.
In the navigation area on the right-hand side, select "Check your device features"
under "Device support".
An additional window opens.
3.
Enter the order code from the nameplate into the search field.
You will receive information on each feature (selected option) of the order code.
3.4
Certificates and approvals
3.4.1
mark
The product meets the requirements of the harmonized European standards. As such, it
complies with the legal specifications of the EC directives. The manufacturer confirms
successful testing of the product by affixing to it the mark.
3.4.2
CSA General Purpose
The following device versions meet the requirements of CSA and ANSI/UL for Canada and
the US:
• CLM253-**2/3/7***
• CLM223-**2/3/7***
10
Endress+Hauser
Liquisys M CLM223/253
Installation
4
Installation
4.1
Installation at a glance
Proceed as follows to completely install the measuring point:
• Install the transmitter (see the "Installation instructions" section).
• If the sensor is not yet installed in the measuring point, install it (see Technical
Information of the sensor).
• Connect the sensor to the transmitter as illustrated in the "Electrical connection" section.
• Connect the transmitter as illustrated in the "Electrical connection" section.
• Commission the transmitter as explained in the "Commissioning" section.
Endress+Hauser
11
Installation
Liquisys M CLM223/253
4.1.1
Measuring system
A complete measuring system comprises:
• Transmitter Liquisys M CLM223 or CLM253
• sensor with or without an integrated temperature sensor
• If necessary, Measuring cable: CYK71 or CPK9 (conductive) or CLK6 (inductive)
Optionally:
• Eintaucharmatur, z.B. CLA111
• Extension cable, junction box VBM
• Weather protection cover CYY101 for field housing
1
2
ENDRESS+HAUSER
LIQUISYS S
7
ENDRESS+HAUSER
LIQUISYS S
6
5
3
4
A0024642
1
1
2
3
4
5
6
7
12
Complete measuring systems
Conductive sensor CLS15
Liquisys M CLM253
Liquisys M CLM223
Inductive sensor CLS54
Inductive sensor CLS50
Conductive sensor CLS21
Immersion assembly CLA111
Endress+Hauser
Liquisys M CLM223/253
Installation
4.2
Installation conditions
4.2.1
Field device
Pg 13.5
Pg 7
Pg 16
247 (9.72)
Ø 6 (0.24)
70 (2.76)
157 (6.18)
M5
11 (0.43)
115 (4.53)
70 (2.76)
154 (6.06)
170 (6.69)
A0024637
2
Field device, dimensions in mm (inch)
There is a hole in the perforation for the cable entry (connection of supply voltage). It
serves as a pressure balance during air shipment. Make sure no moisture penetrates
the inside of the housing before the cable installation. The housing is completely airtight after cable installation.
Endress+Hauser
13
Installation
Liquisys M CLM223/253
1
4
3
2
A0024640
3
1
2
3
4
View into the field housing
Removable electronics box
Terminals
Partition plate
Fuse
4.2.2
Panel-mounted device
96 (3.78)
6 (0.24)
149.5 (5.89)
139 (5.47)
92 (3.62)
90 (3.54)
A0024641
4
14
Panel-mounted device, dimensions in mm (inch)
Endress+Hauser
Liquisys M CLM223/253
Installation
4.3
Installation instructions
4.3.1
Field device
There are several ways of securing the field housing:
• Wall mounting with fixing screws
• Post mounting to cylindrical pipes
• Post mounting to a square securing mast
NOTICE
Effect of climatic conditions (rain, snow, direct sunlight etc.)
Impaired operation to complete transmitter failure
‣ When installing outside, always use the weather protection cover (accessory).
Transmitter wall mounting
2
Ø 6 (0.24)
1
154 (6.06)
A0024638
5
1
2
Field device wall mounting
Fixing bore holes
Plastic caps
Proceed as follows to mount the transmitter on the wall:
• Create the bore holes as shown in → 5.
• Drive two fixing screws through the fixing bore holes (1) from the front.
• Mount the transmitter on the wall as shown.
• Cover the bores with plastic caps (2).
Transmitter post mounting
You require a post mounting kit to secure the field device to horizontal and vertical
posts or pipes (max. Ø 60 mm (2.36")). This can be acquired as an accessory (see the
"Accessories" section).
Endress+Hauser
15
Installation
Liquisys M CLM223/253
1
1
2
Ø max. 60 (2.36)
3
1
3
A0024635
6
1
2
3
Field device on horizontal or vertical pipes
Securing screws
Fixing screws
Securing plate
Proceed as follows to mount the transmitter on a post:
1.
Guide the two securing screws (1) of the mounting kit through the openings on the
securing plate (3).
2.
Screw the securing plate onto the transmitter using the four fixing screws (2).
3.
Secure the bracket with the field device on the post or pipe using the clip.
You can also secure the field device to the Flexdip CYH112 bracket in conjunction with the
weather protection cover. These can be acquired as accessories, see the "Accessories"
section.
A0027433
7
16
Field device on Flexdip CYH112 bracket with weather protection cover
Endress+Hauser
Liquisys M CLM223/253
Installation
4.3.2
Panel-mounted device
The panel-mounted device is secured with the tensioning screws supplied → 8
The necessary installation depth is approx. 165 mm (6.50").
+0.5
(3.62
+0.02
)
92+0.5 (3.62+0.02)
92
1
max. 45 (1.77)
139 (5.47)
~ 25 (0.98)
3
96 (3.78)
92 (3.62)
57 (2.24)
3
33 (1.30)
90 (3.54)
2
3
6 (0.24)
~ 165 (6.50)*
A0024639
8
1
2
3
*
Dimensions in mm (inch)
Mounting plate
Seal
Tensioning screws
Necessary installation depth
4.4
Post-installation check
• After installation, check the transmitter for damage.
• Check whether the transmitter is protected against moisture and direct sunlight (e.g. by
the weather protection cover).
Endress+Hauser
17
Electrical connection
Liquisys M CLM223/253
5
Electrical connection
LWARNING
Device is live
Incorrect connection may result in injury or death.
‣ The electrical connection may be performed only by an electrical technician.
‣ The electrical technician must have read and understood these Operating Instructions
and must follow the instructions contained therein.
Prior
to commencing connection work, ensure that no voltage is present on any cable.
‣
5.1
Wiring
LWARNING
Risk of electric shock!
‣ At the supply point, the power supply must be isolated from dangerous live cables by
double or reinforced insulation in the case of devices with a 24 V power supply.
NOTICE
The device does not have a power switch
‣ The customer must provide a protected circuit breaker in the vicinity of the device.
‣ The circuit breaker must be a switch or power switch, and you must label it as the
circuit breaker for the device.
5.1.1
Wiring diagram
The wiring diagram shows the connections of a device equipped with all the options. The
connection of the sensors to the various measuring cables is explained in more detail in
the "Measuring cables and sensor connection" section.
18
Endress+Hauser
Liquisys M CLM223/253
Electrical connection
PE
84
85+
15 V
15
A
86 _
16
H
83
41
42
84
15
B
I
43
16
47
83
48
49
S
C
11
57
12
58
13
59
mA
32
52
54
mA
55
34
23 +
24 -
10-50 V
82
N
mA
~
=
L1 L+
93
G
M
56
81
F
L
53
Lf
33
E
K
51
31
D
J
N L–
10-50 V
94
O
PE
A0008920
9
Endress+Hauser
Electrical connection of the transmitter
A
Sensor (conductive)
I
Alarm (current-free contact position)
B
Sensor (inductive)
J
Relay 1 (current-free contact position)
C
Temperature sensor
K
Relay 2 (current-free contact position)
D
Signal output 1, conductivity
L
Relay 3 (current-free contact position)
E
Signal output 2, user-definable variable
M
Relay 4 (current-free contact position)
F
Binary input 1 (hold)
N
Current input 4 to 20 mA
G
Binary input 2 (Chemoclean)
O
Power connection
H
Auxiliary voltage output
19
Electrical connection
Liquisys M CLM223/253
Please note the following:
• The device is approved for protection class II and is generally operated without a
protective ground connection.
• To guarantee measuring stability and functional safety, you must connect the outer
shield of the sensor cable:
– Inductive sensors: terminal "S"
– Conductive sensors: PE distributor rail
This is on the cover frame in the case of panel-mounted devices, and in the connection
compartment in the case of field devices. Ground this PE distributor rail or the ground
terminal directly on site wherever possible.
• Circuits "E" and "H" are not galvanically isolated from each other.
Field device connection
Guide the measuring cables through the PG glands into the housing. Connect the
measuring cables in accordance with the terminal assignment.
SENSOR
REL 4
REL 3
REL 2
REL 1
Contacts:
max. 2A
AC: 250V/500VA
DC: 30V/60W
54 55 56 51 52 53 57 58 59 47 48 49 41 42 43
Mains
Hilfsenergie
YE
83 13 84 15
NC
L1 N (AC)
+
- (DC)
NC 31 32 33 34 NC 85 86 93 94 81 82 23 24 NC
+ - + + - +
- +
- +
4..20mA
Binär/
1
Binary
Binär/
2
Binary
+15V
10mA
13
Temp.
(opt.)
Lf
16 11 12 S
GN WH
1
131095-4F
11 12
PE
A0008915
10
1
Field device connection compartment sticker
PE distributor rail for CD/CS device version (conductive sensors)
Panel-mounted device connection
20
Endress+Hauser
Liquisys M CLM223/253
Electrical connection
49
Sensor
31 +
COM 48
32 -
59
1
33 +
15
Lf
84
12
WH
YE
GN
57
34 -
Temp.
(opt.) 13
COM 58
NC
11
REL2
REL3
53
85 +
51
86 -
COM 52
56
54
REL4
COM 55
+15V
10mA
16
83
93 +
Binary 2
94 -
S
81 +
Binary 1
82 -
43
- 24
NC
+ 23
NC
42
41
AC DC
L1 +
4..20mA
N
-
Mains
47
REL1
Contacts: max. 2A, AC:250V/500VA, DC:30V/60W
131081-4E
131084-4C
A0008912
11
1
Panel-mounted device connection sticker
Ground terminal
5.1.2
Measuring cables and sensor connection
You require shielded special measuring cables to connect conductivity sensors to the
transmitter. The following multi-core, pre-terminated cable types can be used:
Sensor type
Cable
Extension
Two-electrode sensor with or without
temperature sensor Pt 100
CYK71
CPK9* (for CLS16)
VBM box + CYK71 cable
Inductive sensor CLS50, CLS52
Fixed cable on sensor
VBM box + CLK6 cable
* High-temperature version without PML
Maximum cable length
Conductive measurement of
conductivity
Max. 100 m (328 ft) with CYK71
Resistance measurement
Max 15 m (49.2 ft) with CYK71
Inductive measurement of conductivity
Max. 55 m ( 180 ft) with CLK5 (incl. sensor cable)
Structure and termination of the measuring cables
Endress+Hauser
21
Electrical connection
Liquisys M CLM223/253
83
84
83
semiconductor
screen
semiconductor
screen
16 screen
white
red
screen 15
84
screen
black
green 11
green 11
white 12
white 12
yellow 13
brown (nc)
yellow 13
brown (nc)
CYK71
CLK6
A0008938-EN
12
A
sc
Structure of the special measuring cables
Semi-conductor layer
Shield
For further information on the cables and junction boxes, please refer to the
"Accessories" section.
Field device measuring cable connection
Proceed as follows to connect a conductivity sensor to the field device:
1.
Open the housing cover to access the terminal block in the connection compartment.
2.
Break through the perforation for a cable gland, mount a cable gland and guide the
cable through this gland.
3.
Connect the cable in accordance with the terminal assignment (see connection
compartment sticker).
4.
Tighten the cable gland.
Panel-mounted device measuring cable connection
22
Endress+Hauser
Liquisys M CLM223/253
Electrical connection
To connect a conductivity sensor, connect the measuring cable in accordance with the
terminal assignment to the terminals on the rear of the device (see connection sticker).
PE 11 12 13
83 16 15 84
S
GN WH YE
11 12 13
GN WH YE
83 16 15 84
BU RD RD BU
BK
RD
WH
CYK71/CPK9
CLK6
GN WH YE
3
1
BK
2
A0008918
A0008919
13
Endress+Hauser
Connection of conductive sensors
14
Connection of inductive sensors
23
Electrical connection
Liquisys M CLM223/253
5.2
Alarm contact
A
B
41
41
42
42
43
43
A0006415
15
A
B
Recommended fail-safe switching for the alarm contact
Normal operating status
Alarm condition
Normal operating status
Alarm condition
Device in operation and no error message
present (alarm LED off):
• Relay energized
• Contact 42/43 closed
Error message present (alarm LED red) or device
defective or de-energized (alarm LED off):
• Relay de-energized
• Contact 41/42 closed
5.3
Post-connection check
Carry out the following checks once you have made the electrical connection:
Device state and specifications
Notes
Are the devices and cables free from damage on the outside?
Visual inspection
Electrical connection
Notes
Are the mounted cables strain relieved?
Are the connected cables provided with strain relief?
Is the cable run correct, without loops and cross-overs?
Are the power cable and signal cables connected correctly and in
accordance with the wiring diagram?
Are all the screw terminals tightened?
Are all the cable entries fitted, tightened and leak-proof?
Are the PE distributor blocks grounded (if present)?
24
Grounding is carried out at the point of
installation.
Endress+Hauser
Liquisys M CLM223/253
Operation options
6
Operation options
6.1
Quick operation guide
You have the following ways of operating the transmitter:
• On site via the key field
• Via the HART interface (optional, with corresponding order version) with:
– HART handheld terminal
– PC with HART modem and the Fieldcare software package
• Via PROFIBUS PA/DP (optional, with corresponding order version) by PC with a
corresponding interface and the Fieldcare software package or via a programmable logic
controller (PLC).
For operation via HART or PROFIBUS PA/DP, please read the relevant sections in the
additional Operating Instructions:
• PROFIBUS PA/DP, field communication for Liquisys M CXM223/253,
BA00209C/07/EN
• HART, field communication for Liquisys M CXM223/253, BA00208C/07/EN
The following section only explains operation via the keys.
6.2
Display and operating elements
6.2.1
Display
LED displays
Indicates the current operating mode, "Auto" (green LED) or
"Manual" (yellow LED)
A0027220
Indicates the activated relay in the "Manual" mode (red LED)
The status of relays 3 and 4 is indicated on the LC display.
A0027222
A0027221
A0027218
Endress+Hauser
Indicates the working status of relay 1 and 2
LED green: measured value within the permitted limit, relay
inactive
LED red: measured value outside the permitted limit, relay active
Alarm display, e.g. in event of continuous limit value overshoot,
temperature sensor failure or system error (see error list)
25
Operation options
Liquisys M CLM223/253
LC display
1
2
11
5
mS/cm
6
12 15 R232
13
12
4
3
7
Setpoint
10
8
9
A0008922-EN
26
16
Transmitter LC display
1
Indicator for measuring mode (normal operation)
2
Indicator for calibration mode
3
Indicator for setup mode (configuration)
4
Indicator for "Hold" mode (current outputs remain at last current state)
5
Indicator for receipt of a message on devices with communication
6
Indicator of working status of relays 3/4:
7
Function code
inactive,
active
8
In measuring mode: measured variable - in setup mode: configured variable
9
In measuring mode: secondary measured value - in setup/calibr. mode: e.g. set value
10
Indicator for autom. Temperature compensation
11
Indicator for man. Temperature compensation
12
"Error": error display
13
Sensor symbol (see the "Calibration" section)
Endress+Hauser
Liquisys M CLM223/253
Operation options
6.2.2
Operating elements
The display shows the current measured value and the temperature simultaneously, which
means you have an overview of the most important process data at once. Help text in the
configuration menu helps users configure the device parameters.
1
2
7
3
4
6
5
A0024632-EN
17
1
2
3
4
5
6
7
Operating elements
LC display for displaying the measured values and configuration data
Key to switch relays in manual mode and to display the active contact
LED for alarm function
Changeover switch for automatic/manual mode
LEDs for limit contactor relay (switch status)
Main operating keys for calibration and device configuration
Field for user-defined information
6.2.3
Key functions
CAL key
A0027235
When you press the CAL key, the device first prompts you for the
calibration access code:
• Code 22 for calibration
• Code 0 or any other code for reading the last calibration data
Use the CAL key to accept the calibration data or to switch from
field to field within the calibration menu.
ENTER key
A0027236
When you press the ENTER key, the device first prompts you for the
setup mode access code:
• Code 22 for setup and configuration
• Code 0 or any other code for reading all the configuration data.
The ENTER key has several functions:
• Calls up the Setup menu from the measuring mode
• Saves (confirms) data entered in the setup mode
• Moves on within function groups
Endress+Hauser
27
Operation options
Liquisys M CLM223/253
PLUS key and MINUS key
A0027240
In the Setup mode, the PLUS and MINUS keys have the following
functions:
• Selection of function groups.
Press the MINUS key to select the function groups in the order
given in the "System configuration" section.
• Configuration of parameters and numerical values
• Operation of the relays in manual mode
In the measuring mode, the following sequence of functions is
accessed by repeatedly pressing the PLUS key:
• Temperature displayed in °F
• Temperature is hidden
• Current input signal in %
• Current input signal in mA
• Uncompensated conductivity value is displayed
• Return to basic settings
In the measuring mode, the following sequence of information is
displayed by repeatedly pressing the MINUS key:
• The current errors are displayed consecutively (max. 10).
• Once all the errors have been displayed, the standard
measurement display appears. In the function group F, an alarm
can be defined separately for each error code.
A0027241
A0027234
REL key
In the manual mode, you can use the REL key to switch between the
relay and the manual start of cleaning.
In automatic mode, you can use the REL key to read out the switchon points (for limit contactor) or set points (for PID controller)
assigned to the relay in question.
Press the PLUS key to jump to the settings of the next relay. Use the
REL key to get back to the display mode (automatic return after
30 s).
AUTO key
Use the AUTO key to switch between automatic mode and manual
mode.
Escape function
If you press the PLUS and MINUS key simultaneously, you return to
the main menu, or are taken to the end of calibration if calibrating.
If you press the PLUS and MINUS key again, you return to the
measuring mode.
A0027237
Locking the keyboard
Press the PLUS and ENTER key simultaneously for at least 3 s to
lock the keyboard against any unauthorized data entry. All the
settings can continue to be read.
The code prompt displays the code 9999.
A0027238
Unlocking the keyboard
Press the CAL and MINUS key simultaneously for at least 3 s to
unlock the keyboard.
The code prompt displays the code 0.
A0027239
28
Endress+Hauser
Liquisys M CLM223/253
Operation options
6.3
Local operation
6.3.1
Automatic/manual mode
The transmitter normally operates in automatic mode. Here, the relays are triggered by
the transmitter. In the manual mode, you can trigger the relays manually using the REL
key or start the cleaning function.
How to change the operating mode:
1.
The transmitter is in automatic mode. The top LED (green)
next to the AUTO key is lit.
2.
Press the AUTOMATIC key.
3.
To enable the manual mode, enter the code 22 via the PLUS
and MINUS keys and press ENTER to confirm.
The lower LED (manual mode) is lit.
4.
Select the relay or the function.
You can use the REL key to switch between the relays. The
relay selected and the switch status (ON/OFF) is displayed on
the second line of the display.
In the manual mode, the measured value is displayed
continuously (e.g. for measured value monitoring for dosing
functions).
5.
Switch the relay. The relay is switched on with PLUS and
switched off with MINUS.
The relay remains in this switched state until it is switched
again.
6.
Press the AUTOMATIC key to return to the measuring mode,
i.e. to the automatic mode.
All the relays are triggered again by the transmitter.
A0027242
A0027243
A0027240
A0027241
A0027240
A0027234
• The operating mode remains in effect even after a power failure. The relays assume
the quiescent state, however.
• The manual mode has priority over all other automatic functions.
• Hardware locking is not possible in the manual mode.
• The manual settings are kept until they are actively reset.
• Error code E102 is signaled during manual operation.
Endress+Hauser
29
Operation options
Liquisys M CLM223/253
6.3.2
Operating concept
Operating modes
Measuring mode:
standard mode of
operation, displaying
current measured values
Setup mode
access to all
configuration
settings
Calibration mode:
execution of
calibration routine
Code
The function groups
are selected with the
PLUS or MINUS key.
A0027244-EN
18
Description of the possible operating modes
If no key is pressed in the setup mode for approx. 15 min, the device automatically
returns to the measuring mode. Any active hold (hold during setup) is canceled.
Access codes
All device access codes are fixed and cannot be altered. When the device requests the
access code, it distinguishes between different codes.
• CAL key + code 22: access to Calibration and Offset menu
• ENTER key + code 22: access to the menus for the parameters which make
configuration and user-specific settings possible
• PLUS + ENTER keys simultaneously (min. 3 s): lock the keyboard
• CAL + MINUS keys simultaneously (min. 3 s): unlock the keyboard
• CAL or ENTER key + any code: access to read mode, i.e. all the settings can be read but
not modified.
The device continues measuring in the read mode. It does not shift to the "Hold" status.
The current output and the controllers remain active.
30
Endress+Hauser
Liquisys M CLM223/253
Operation options
Menu structure
The configuration and calibration functions are arranged in function groups.
• In the setup mode, select a function group with the PLUS and MINUS keys.
• In the function group itself, switch from function to function with the ENTER key.
• Within the function, select the desired option with the PLUS and MINUS keys or edit the
settings with these keys. Then confirm with the ENTER key and continue.
• Press the PLUS and MINUS keys simultaneously (Escape function) to exit programming
(return to the main menu).
• Press the PLUS and MINUS keys simultaneously again to switch to the measuring mode.
If a modified setting is not confirmed by pressing ENTER, the old setting is retained.
An overview of the menu structure is provided in the Appendix to these Operating
Instructions.
1
-
2
3
E
E
E
E
E
A0027245
19
1
2
3
Menu structure
Functions (selection of parameters, entry of numbers)
Function groups, scroll backwards and forwards with the PLUS and MINUS keys
Switch from function to function with the ENTER key
Hold function: "freeze" the outputs
In both the setup mode and during calibration, the current output can be "frozen" (factory
setting), i.e. it constantly retains its current status. "HOLD" appears on the display. If the
controller actuating variable (steady control 4 to 20 mA) is output via current output 2, it
is set to 0/4 mA during a hold.
• Hold settings can be found in the "Service" function group.
• During a hold, all contacts assume a quiescent state.
• An active hold has priority over all other automatic functions.
• With every hold, the I-component of the controller is set to "0".
• Any alarm delay is reset to "0".
• This function can also be activated externally via the hold input (see Wiring diagram;
binary input 1).
• A manual hold (field S3) remains active even after a power failure.
Endress+Hauser
31
Commissioning
Liquisys M CLM223/253
7
Commissioning
7.1
Function check
LWARNING
Incorrect connection, incorrect supply voltage
Safety risks for staff and device malfunctions
‣ Check that all connections have been established correctly in accordance with the
wiring diagram.
‣ Ensure that the supply voltage matches the voltage indicated on the nameplate.
7.2
Switching on
Familiarize yourself with the operation of the transmitter before it is first switched on. In
particular please read the "Basic safety instructions" and "Operation options" sections. After
power-up, the device performs a self-test and then goes to the measuring mode.
Now calibrate the sensor in accordance with the instructions in the "Calibration" section.
During initial commissioning, the sensor must be calibrated so that the measuring
system can return precise measurement data.
Then perform the first configuration in accordance with the instructions in the "Quick
setup" section. The values set by the user are kept even in the event of a power failure.
The following function groups are available in the transmitter (the groups that are only
available in the Plus Package are marked accordingly in the functional description):
Setup mode
• SETUP 1 (A)
• SETUP 2 (B)
• CURRENT INPUT (Z)
• CURRENT OUTPUT (O)
• ALARM (F)
• CHECK (P)
• RELAY (R)
• TEMPERATURE COMPENSATION (T)
• CONCENTRATION MEASUREMENT (K)
• SERVICE (S)
• E+H SERVICE (E)
• INTERFACE (I)
Calibration mode
CALIBRATION (C)
A detailed explanation of the function groups available in the transmitter can be
found in the "Device configuration" section.
2
s
F3
Err.delay
Function display:
The displayed code indicates
the function position in the
function group.
Additional information
A0025560-EN
20
32
Information for the user on the display
Endress+Hauser
Liquisys M CLM223/253
Commissioning
C131
C132
C133
C121
C
C1
C111
To make it easier for you to select and find function
groups and functions, a code for the corresponding
field is displayed for each function → 20
The structure of this code is illustrated in → 21.
The function groups are indicated as letters in the first
column (see the names of the function groups). The
functions of the individual groups are displayed
incrementally by row and by column.
A0027502
21
Function code
Factory settings
The first time the device is switched on, the factory setting is set for all the functions. The
table below provides an overview of the most important settings.
All other factory settings can be found in the description of the individual function groups
in the "System configuration" section (the factory setting is highlighted in bold).
Function
Factory setting
Type of measurement
Conductive measurement of conductivity,
Temperature measurement in °C
Type of temperature compensation
Linear with reference temperature 25 °C (77 °F)
Temperature compensation
Automatic (ATC on)
Limit value for controller 1
9999 mS/cm
Limit value for controller 2
9999 mS/cm
Hold
Active during configuration and calibration
Measuring range
0 μS/cm to 2000 mS/cm (no measuring ranges to be
configured).
The setting is flowing and depends on the sensors
connected.
Current outputs 1 and 2*
4 to 20 mA
Current output 1: measured value for 4 mA signal
current
0 μS/cm
Current output 1: measured value for 20 mA signal
current
2000 mS/cm
Current output 2: temperature value for 4 mA signal
current*
-35.0 °C (-31 °F)
Current output 2: temperature value for 20 mA
signal current*
250.0 °C (482 °F)
* with appropriate version
Endress+Hauser
33
Commissioning
Liquisys M CLM223/253
7.3
Quick Setup
After power-up, you must make some settings to configure the most important functions
of the transmitter which are required for correct measurement. The following section gives
an example of this.
User entry
1.
Press the ENTER key
2.
Enter the code 22 to open access to the
menus. Press the ENTER key.
3.
Press the MINUS key until you get to the
"Service" function group.
4.
Press ENTER to be able to make your settings.
Range of adjustment
(factory settings in
bold)
Display
S
SERVICE
A0008408-EN
5.
Select your language in S1, e.g. "ENG" for
English.
Press ENTER to confirm your entry.
ENG = English
GER = German
FRA = French
ITA = Italian
NEL = Dutch
ESP = Spanish
ENG
S1
Language
A0008409-EN
6.
Press the PLUS and MINUS key simultaneously
to exit the "Service" function group.
7.
Press the MINUS key until you get to the
"Setup 1" function group.
8.
Press ENTER to be able to make your settings
for "Setup 1".
A
SETUP 1
A0007824-EN
9.
In A1, select the desired mode of operation,
e.g. "cond" = conductive.
Press ENTER to confirm your entry.
cond = conductive
ind = inductive
MOhm = resistance
Conc = concentration
cond A1
Oper.Mode
A0009002-EN
10.
In A2, press ENTER to accept the factory
%
setting. (Only if A1 = conc, otherwise continue ppm
with Step 12)
mg/l
TDS = total dissolved
solids
None
% A2
Conc.Unit
A0009003-EN
11.
In A3, press ENTER to accept the standard
setting.
XX.xx
X.xxx
XXX.x
XXXX
XX.xx A3
Format
A0009004-EN
12.
In A4, press ENTER to accept the standard
setting.
auto, μS/cm, mS/cm,
S/cm, μS/m, mS/m, S/ m
auto A4
Unit
A0009005-EN
34
Endress+Hauser
Liquisys M CLM223/253
Commissioning
User entry
Range of adjustment
(factory settings in
bold)
13.
cond: 1.000 cm-1
ind: 1.98 cm-1
MOhm: 0.01 cm-1
0.0025 to 99.99 cm-1
In A5, enter the exact cell constant of the
sensor. The cell constant is provided on the
sensor quality certificate.
Display
1/cm
1.000 A5
Cellconst
A0009006-EN
14.
In A6, enter the cable resistance (only applies
to conductive sensors).
0Ω
0 to 99.99 Ω
@
0 A6
Cable-Res
A0009007-EN
15.
16.
In A7, enter the measured value damping.
1
Measured value damping causes the measured 1 to 60
value to be averaged over the specified number
of individual measured values (if A7 = 1, no
damping takes place).
Press ENTER to confirm your entry.
The display returns to the initial display of the
"Setup 1" function group.
Press the MINUS key until you get to the
"Setup 2" function group.
Press ENTER to make your settings for "Setup
2".
1 A7
Damping
A0001960-EN
B
SETUP 2
A0007830-EN
17.
In B1, select the temperature sensor.
Press ENTER to confirm your entry.
Pt100
Pt1k = Pt 1000
NTC30
Fixed
Pt100 B1
ProcTemp.
A0009010-EN
18.
19.
In B2, select the appropriate type of
temperature compensation for your process,
e.g. "lin" = linear.
Press ENTER to confirm your entry.
Detailed information is provided in the "Setup
2" section.
In B3, enter the temperature coefficient α.
Press ENTER to confirm your entry.
None
Lin = linear
NaCl = table salt (IEC
746)
Pure = ultrapure water
NaCl
PureH = ultrapure water
HCl
Tab = table
2.1 %/K
0.0 to 20.0 %/K
lin B2
TempComp.
A0009011-EN
%/K
2.10 B3
Alpha val
A0009012-EN
20.
The current temperature is displayed in B5. If Actual value displayed
necessary, adjust the temperature sensor to an and entered
external measurement.
-35.0 to 250.0 °C
Press ENTER to confirm your entry.
¡C
0.0 B5
RealTemp.
A0009014-EN
Endress+Hauser
35
Commissioning
Liquisys M CLM223/253
User entry
Range of adjustment
(factory settings in
bold)
21.
0.0 °C
-5.0 to 5.0 °C
The difference between the measured and
entered temperature is displayed.
Press the ENTER key.
The display returns to the initial display of the
"Setup 2" function group.
Display
¡C
0.0 B6
TempOffs.
A0009015-EN
22.
Press the MINUS key to get to the "Current
output" function group.
Press ENTER to make your settings for the
current outputs.
O
OUTPUT
A0025026-EN
23.
In O1, select your current output, e.g. "Out 1" =
output 1.
Press ENTER to confirm your entry.
Out 1
Out 2
Out1
O1
Sel.Out
A0025027-EN
24.
In O3, select the linear characteristic.
Press ENTER to confirm your entry.
Lin = linear (1)
Lin = linear (1)
Tab = table
lin
O3
Sel.Type
A0025029-EN
25.
In O311, select the current range for your
current output, e.g. 4 to 20 mA.
Press ENTER to confirm your entry.
4 to 20mA
0 to 20 mA
4-20
O311
Sel.Range
A0025030-EN
26.
In O312, specify the conductivity at which the
minimum current value is applied at the
transmitter output, e.g. 0 μS/cm.
Press ENTER to confirm your entry.
Cond/ind: 0.00 μS/cm
MOhm: 0.00 kΩ·cm
Conc: 0.00 %
Temp: 0.00 °C
mg/l
0.00 O312
0/4 mA
A0025031-EN
27.
In O313, specify the conductivity at which the
maximum current value is applied at the
transmitter output, e.g. 2000 mS/cm.
Press ENTER to confirm your entry.
The display returns to the initial display of the
"Current output" function group.
Cond/ind: 2000 mS/cm
MOhm: 500 kΩ·cm
Conc: 99.99 %
Temp: 150 °C
mg/l
10.00 O313
20 mA
A0025032-EN
28.
Press PLUS and MINUS simultaneously to
switch to the measurement mode.
You must perform an air set before installing the inductive sensor. See the
"Calibration" section for more information.
36
Endress+Hauser
Liquisys M CLM223/253
Commissioning
7.4
Device configuration
7.4.1
Setup 1 (conductivity)
In the SETUP 1 function group, you can change the settings for the measuring mode and
the sensor.
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
A
Configuration of basic
functions
SETUP 1
function group
A
SETUP 1
A0007824-EN
A1
Select the
operating mode
auswählen
cond = conductive
ind = inductive
MOhm =
resistance
conc=
concentration
cond A1
Oper.Mode
A0009002-EN
A2
Select the
concentration unit
to be displayed
(only for Plus
Package)
%
ppm
mg/l
TDS = total
dissolved solids
None
Display varies depending on
the device:
• Cond/resistance/conc
• Ind/conc
the operating
When
mode is changed, all
user settings are
automatically reset.
A2 is only active if A1 = conc
% A2
Conc.Unit
A0009003-EN
A3
Select the display
format for the
concentration unit
(only for Plus
Package)
XX.xx
X.xxx
XXX.x
XXXX
A3 is only active if A1 = conc
XX.xx A3
Format
A0009004-EN
A4
Select the unit to
be displayed
auto, μS/cm,
mS/cm, S/cm, μS/
m, mS/m, S/m,
kΩ·cm, MΩ·cm,
kΩ·m
auto A4
If "auto" is selected, the
highest possible resolution is
automatically selected.
A4 is not active if A1 = conc
Unit
A0009005-EN
A5
Enter the cell
constant for the
connected sensor
cond:1.000 cm-1
ind:1.98 cm-1
MOhm:0.01 cm-1
0.0025 to 99.99
cm-1
1/cm
1.000 A5
The exact cell constant is
provided on the sensor
quality certificate.
Cellconst
A0009006-EN
Endress+Hauser
37
Commissioning
Liquisys M CLM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
A6
0Ω
0 to 99.99 Ω
Enter the cable
resistance
Display
Info
@
0 A6
Cable-Res
Only for conductive sensors.
The standardized line
resistance must be multiplied
by the actual cable length.
CYK71: 0.165 Ω/m
A0009007-EN
A7
Enter the value
for measured
value damping
1
1 to 60
1 A7
Damping
A0009008-EN
38
Measured value damping
causes averaging over the
specified number of
individual measured values.
This is used, for example, to
stabilize the display if the
measurement is unstable.
There is no damping if “1” is
entered.
Endress+Hauser
Liquisys M CLM223/253
Commissioning
7.4.2
Setup 2 (temperature)
Temperature coefficient α indicates the change in the conductivity per degree of
temperature change:
k(T) = k(T0) . (1+ a . (T - T0))
A0009163
Where
κ(T) = conductivity at process temperature T
κ(T0) = conductivity at reference temperature T0
The temperature coefficient depends both on the chemical composition of the solution and
the temperature itself.
To determine the level of dependency, four different types of compensation can be selected
in the transmitter:
• Linear temperature compensation
• NaCl compensation
• NaCl ultrapure water compensation (neutral compensation)
• HCl ultrapure water compensation (acid compensation)
• Temperature compensation with table
Linear temperature compensation
The change between two temperature points is taken
to be constant, i.e. α = const. The α value can be edited
for linear compensation. The reference temperature
can be edited in the B7 field. The default setting is 25
°C.
k*
a
1
T
A0008945
22
NaCl compensationIn the case of NaCl compensation
(as per IEC 60746), a fixed non-linear curve specifying
the relationship between the temperature coefficient
and temperature is saved in the device. This curve
applies to low concentrations of up to approx. 5 %
NaCl.
a [%/K]
*
Linear temperature compensation
Uncompensated conductivity
2.7
2.5
2.3
2.1
0
48
96
144
T [°C]
A0008939
23
Endress+Hauser
NaCl compensation
39
Commissioning
Liquisys M CLM223/253
Ultrapure water compensation (for conductive sensors)
For pure and ultrapure water, algorithms are saved in the transmitter that consider the
self-dissociation of ultra pure water and its strong temperature dependency. They are used
for conductivity levels of approx. 100 μS/cm.
Two types of compensation are available:
• NaCl ultrapure water compensation: this is optimized for pH-neutral contamination.
• HCl ultrapure water compensation: this is optimized for measuring the acid conductivity
downstream of a cation exchanger. It is also suitable for ammonia (NH3) and caustic
soda (NaOH).
• The ultrapure water compensation types always refer to a reference temperature of
25 °C (77 °F).
• The lowest conductivity displayed is the theoretical limit value of ultrapure water at
25 °C (77 °F) of 0.055 μS/cm.
Temperature compensation with table
For devices with the Plus Package, it is possible to enter a table with temperature
coefficients α as a function of the temperature. The following conductivity data of the
medium under measurement are required to use the alpha table function for temperature
compensation:
Value pairs comprising the temperature T and conductivity κ with:
• κ(T0) for the reference temperature T0
• κ(T) for the temperatures that occur in the process
A
B
a
k
k1
a2
k(T0)
a1
k2
T1
T0
T2
T1 T2
T
T
A0008944
24
A
B
Determination of the temperature coefficient
Required data
Calculated α values
Use the following formula to calculate the α values for the temperatures that are relevant
in your process:
a=
100%
k(T0)
.
k(T) - k(T0)
T - T0
; T ¹ T0
A0009162
Enter the α-T value pairs obtained in this way in the T4 and T5 fields of the ALPHA TABLE
function group.
Use this function group to change the settings for temperature measurement.
40
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory settings in
bold)
Display
Info
B
Settings for temperature
measurement
SETUP 2 function
group
B
SETUP 2
A0007830-EN
B1
Select the
temperature
sensor
Pt100
Pt1k = Pt 1000
NTC30
Fixed
Pt100 B1
ProcTemp.
"fixed":
Manual temperature
compensation (MTC), no
temperature measurement.
Instead a fixed temperature
value is defined in B4.
A0009010-EN
B2
B3
Select the type of
temperature
compensation
None
Lin = linear
NaCl = table salt
(IEC 746)
Pure = ultrapure
water NaCl
PureH = ultrapure
water HCl
Tab = Table
Enter temperature 2.10 %/K
coefficient α
0.00 to 20.00 %/K
lin B2
TempComp.
This option does not
appear for concentration
measurement.
"Pure" and "PureH" are only
displayed for conductive
devices.
A0009011-EN
%/K
2.10 B3
Only if B2 = lin.
With other settings in B2,
field B3 does not have any
effect.
Alpha val
A0009012-EN
B4
Enter the process
temperature
25.0 °C
-35.0 to 250.0 °C
¡C
25.0 B4
Only if B1 = fixed.
The value entered can only
be in °C.
ProcTemp.
A0009013-EN
B5
Display the
temperature and
adjust the
temperature
sensor
Actual value
displayed and
entered
-35.0 to 250.0 °C
¡C
0.0 B5
RealTemp.
With the value entered
here, the temperature
sensor can be adjusted to
an external measurement.
Affects B6.
Omitted if B1 = fixed.
A0009014-EN
B6
Enter the
temperature
differential
(offset)
Current offset
-5.0 to 5.0 °C
¡C
0.0 B6
TempOffs.
The offset is the difference
between the actual value
entered and the measured
temperature.
Omitted if B1 = fixed.
A0009015-EN
B7
Enter reference
temperature
25.0 °C
-5.0 to 100 °C
°C
25.0 B7
ref temp.
A0009016-EN
Endress+Hauser
41
Commissioning
Liquisys M CLM223/253
7.4.3
Current input
For the "Current input" function group, you require a relay card with a current input which
is not available in the basic device version. With this function group, you can monitor
process parameters and use them for feedforward control. For this purpose, you must
connect the current output of an external measured variable (e.g. flowmeter) to the 4 to
20mA input of the transmitter. The following assignment applies:
Flow in main stream
Current signal in mA
Current input signal in %
Flowmeter start of measuring range
4
0
Flowmeter end of measuring range
20
100
Flow monitoring in the main stream
This arrangement is particularly practical if the sample flow through a flow assembly in an
open outlet is independent of the flow in the main stream.
This permits signaling of an alarm condition in the main stream (flow too low or has
completely stopped) and triggers dosing switch-off even if the medium flow is maintained
due to the method of installation.
1
A
0
1
B
Z2
Z3
0
1
C
0
E
F
D
A0008923
25
Alarm signaling and dosing switch-off by the main stream
A Flow in main stream
F
Flow restoration
B
Relay contacts of PID controller
Z2
Delay for controller switch-off, see field Z2
C
Alarm relay
Z3
Delay for controller switch-on, see field Z3
D
Flow below switch-off limit Z 4 or flow failure
0
Off
E
Flow alarm
1
On
Feedforward control to PID controller
You can optimize control on control systems with very short response times by measuring
the medium flow rate in addition to the oxygen content. Then apply this flow rate value (4
to 20 mA) as feedforward control to the PID controller.
Feedforward control is a multiplying function as illustrated in the figure below (example
with factory setting):
42
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Y
1.5
1
0.5
0
20
40
Z7
60
80
100
X
A0008942
26
Y
X
Endress+Hauser
Multiplying feedforward control
Gain Kinfl
Current input signal in [%]
43
Commissioning
Liquisys M CLM223/253
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory
settings in
bold)
Display
Info
Z
Current input settings
CURRENT INPUT
function group
Z
CUR.INPUT
A0024903-EN
Z1
Select flow
monitoring of main
stream (with
controller switchoff)
Off
On
Off Z1
Cont.stop
Flow monitoring may only be
switched on if the flowmeter is
connected in the main stream. If
Z1 = off, fields Z2 to Z5 are not
available.
A0024904-EN
Z2
Enter the delay for
controller switchoff through current
input
0s
0 to 2000 s
s
0 Z2
Off Delay
Brief flow shortfalls can be
suppressed by this delay and do
not result in controller switchoff.
A0024905-EN
Z3
Enter the delay for
controller switchon through current
input
0s
0 to 2000 s
s
0 Z3
On Delay
In the case of a controller, a
delay until the reception of a
representative measured value
is recommended after a long
period without flow.
A0024934-EN
Z4
Enter the switch-off 50 %
limit value for the
0 to 100 %
current input
%
50 Z4
A.Thresh
0 to 100% corresponds to 4 to
20 mA at the current input.
Observe measured value
assignment to the current
output of the flowmeter.
A0024935-EN
Z5
Enter the switch-off Low
direction for the
High
current input
Low Z5
Stop Dir
The controller is switched off if
the value entered in Z4 is
undershot or overshot.
A0024939-EN
Z6
Select feedforward
control to PID
controller
Off
Lin = linear
Basic
Off Z6
PID influ
A0024940-EN
Z7
Enter value for
50 %
feedforward control 0 to 100 %
at which gain = 1
applies
%
50 Z7
Kinflu=1
If Z6 = off, the field Z7 is not
available.
Z6 = basic: disturbance variable
only affects the basic load
(alternatively dosing in
proportion to quantity, if usual
PID controller not possible, e.g.
defective sensor).
When the value is set, the
controller actuating variable is
the same size when feedforward
control is switched on as when
feedforward control is switched
off.
A0024941-EN
44
Endress+Hauser
Liquisys M CLM223/253
Commissioning
7.4.4
Current outputs
Use the "Current output" function group to configure the individual outputs. You can enter
either a linear characteristic (O3 (1)) or a user-defined current output characteristic in
conjunction with the Plus Package (O3 (3)). Exception: if you have chosen a "continuous
controller" for current output 2, you cannot enter a user-defined current output
characteristic for this current output.
In addition, you can also simulate a current output value (O3 (2)) to check the current
outputs.
If a second current output is present, you can output the controller actuating variable via
the current output in accordance with field R237/O2.
c[mS/cm]
2000
1500
D Signal
1000
500
0
4
8
12
16
D I [mA]
20
I [mA]
A0008943
27
User-defined current output characteristic (example)
The current output characteristic must increase or decrease very monotonically.
The distance per mA between two table value pairs must be greater than:
• Conductivity: 0.5 % of measuring range
• Temperature: 0.25 °C
The values for the sample characteristic → 27 are entered in the following table. The
distance per mA is calculated from Δ signal / Δ mA.
Current output 1
Endress+Hauser
Current output 2
Value pair
[mS/cm]
[%] [°C]
Current
[mA]
Distance
per mA
1
500
4
2
1000
16
41.66
3
2000
20
250
[mS/cm]
[%] [°C]
Current
[mA]
Distance
per mA
45
Commissioning
Liquisys M CLM223/253
First enter the desired current output configuration into the following blank table with a
pencil. Calculate the resulting signal distance per mA to observe the necessary minimum
slope. Then enter the values in the device.
Current output 1
Value pair
[mS/cm]
[%] [°C]
Current
[mA]
Current output 2
Distance
per mA
[mS/cm]
[%] [°C]
Current
[mA]
Distance
per mA
1
2
3
4
5
6
7
8
9
10
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
O
CURRENT
OUTPUT
function group
O
Configuration of the current
output (does not apply for
PROFIBUS).
OUTPUT
A0025026-EN
O1
Select current
output
Out 1
Out 2
Out1
A characteristic can be
selected for every output.
O1
Sel.Out
A0025027-EN
O2
Select measured
variable for 2nd
current output
°C
mS/cm, MΩ, %
Contr
¡C O2
Parameter
R237=curr (current output 2)
can only be selected if
O2=Contr (controller) is
selected (relay card required).
A0025028-EN
O3 (1)
Enter the
characteristic
type
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
lin
O3
Sel.Type
A0025029-EN
46
The characteristic can have a
positive or negative slope for
the measured value output.
In the case of actuating
variable output (O2 = Contr),
an increasing current
corresponds to an increasing
actuating variable.
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
O311
4 to 20mA
0 to 20 mA
Select current
range
Display
Info
4-20
O311
Sel.Range
A0025030-EN
O312
0/4 mA value:
Enter the
associated
measured value
Cond/ind: 0.00
μS/cm
MOhm:
0.00kΩ*cm
Conc: 0.00 %
Temp: 0.00 °C
0.00
µS/cm
O312
0/4 mA
A0025034-EN
O313
20 mA value:
Enter the
associated
measured value
Cond/ind: 2000
μS/cm
MOhm: 500
kΩ*cm
Conc: 99.99 %
Temp: 150 °C
2000
mS/cm
O313
20 mA
A0025035-EN
O3 (2)
Simulate current
output
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
sim
O3
Sel.Type
Here you can enter the
measured value at which the
min. current value (0/4 mA)
is applied at the transmitter
output (not for controller).
(Turndown see Technical
data.)
Here you can enter the
measured value at which the
max. current value (20 mA) is
applied at the transmitter
output (not for controller).
(Turndown see Technical
data.)
Simulation is not ended until
O3(1) or O3(3) is selected.
For further characteristics, see
O3 (1), O3 (3).
A0025039-EN
O321
Enter simulation
value
Current value
0.00 to 22.00 mA
mA
10.20 O321
Simulat.
Entering a current value
results in this value being
directly output at the current
output.
A0025040-EN
O3 (3)
Enter current
output table
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
table O3
Sel.Type
A0025041-EN
O331
Select table
option
Read
Edit
Only for Plus Package
Values can also be
subsequently added or
modified. The values entered
are automatically sorted by
increasing current value.
For further characteristics, see
O3 (1), O3 (2).
read O331
Sel.Table
A0025042-EN
O332
Enter number of
table value pairs
1
1 to 10
1 O332
Enter the number of pairs of x
and y values (measured value
and current value) here.
No.Elem.
A0025043-EN
Endress+Hauser
47
Commissioning
Liquisys M CLM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
O333
1
1 to no. elem.
Assign
Select table value
pair
Display
Info
1 O333
Sel.Elem.
The system runs through the
O333 to O335 function chain
as often as indicated in O332.
"Assign" appears as the last
step. The display goes to
O336 after confirmation.
A0025044-EN
O334
Enter x value
Cond/ind: 0.00
μS/cm
MOhm:
0.00kΩ*cm
Conc: 0.00 %
Temp: 0.00 °C
µS/cm
0.00 O334
x value = measured value
specified by user.
Meas.val.
A0025045-EN
O335
Enter y value
0.00 mA
0.00 to 20.00 mA
mA
0.00 O335
y value = user-defined current
value pertaining to O334.
Return to O333 until all
values are entered.
mA value
A0025048-EN
O336
Message as to
whether table
status is OK
Yes
No
yes O336
Status ok
Back to O3.
If status = no, correct the table
(all settings made up until
now remain intact) or go back
to the measuring mode (table
is deleted).
A0025049-EN
48
Endress+Hauser
Liquisys M CLM223/253
Commissioning
7.4.5
Alarm
You can use the "Alarm" function group to define various alarms and configure output
contacts.
Each individual error can be defined to be effective or not (at the contact or as an error
current).
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory
settings in
bold)
Display
Info
F
Alarm function settings.
ALARM
function group
F
ALARM
A0025141-EN
F1
Select contact
type
Latch =
latching
contact
Momen =
momentary
contact
Latch F1
The option selected only applies
for the fault-signaling contact, not
for the error current.
Cont.Type
A0025142-EN
F2
Select the time
unit for the
alarm delay
s
min
s F2
Time Unit
A0025143-EN
F3
Enter alarm
delay
0 s (min)
0 to 2000 s
(min)
s
0 F3
Depending on the option selected
in F2, the alarm delay can be
entered in s or min.
Err.Delay
A0025144-EN
F4
Select error
current
22 mA
2.4 mA
22mA
"0-20 mA" was selected in
IfO311,
"2.4 mA" may not be
F4
used.
Err.Curr
A0025145-EN
F5
Select the error
number
1
1 to 255
1 F5
Sel.error
A0025146-EN
F6
Set alarm
Yes
contact to be
No
effective for the
selected error
yes F6
Rel.Assg
Here you can select all the errors
which should trigger an alarm. The
errors are selected by the error
numbers. Please refer to the table
in the "System error messages"
section for the meaning of the
individual error numbers. The
factory settings remain in effect
for all errors that are not edited.
If “no” is selected, all the other
alarm settings are deactivated (e.g.
alarm delay). The settings
themselves are maintained. This
setting only applies to the error
currently selected in F5.
A0025147-EN
Endress+Hauser
49
Commissioning
Liquisys M CLM223/253
Coding Field
F7
Range of
adjustment
(factory
settings in
bold)
Display
Info
Set error
No
current to be
Yes
effective for the
selected error
no F7
Curr.Assg
The option selected in F4 is
effective or not effective in the
event of an error.
This setting only applies to the
error currently selected in F5.
A0025148-EN
F8
Automatic
cleaning
function start
No
Yes
no F8
This field is not available for
certain errors, see the
"Troubleshooting and fault
elimination" section.
CleanTrig
A0025149-EN
F9
Select return to Next = next
menu or next
error number
error
←R
next F9
If ←R is selected, you return to F. If
Next is selected, you go to F5.
Select
A0025150-EN
7.4.6
Check
The CHECK function group is only available for devices with a Plus Package.
In the CHECK function group, you can select different monitoring functions for the
measurement.
Polarization detection (field P1)
In the case of conductive sensors, the effects of polarization in the boundary layer between
the sensor and medium restrict the measuring range. The transmitter can detect
polarization effects by using a smart signal analysis process. Error message E071 is
displayed.
Alarm threshold monitoring (fields P2 to P5)
You can use this function to monitor the measured value for permissible upper and lower
limits and trigger an alarm (error messages E154, E155).
PCS alarm (process check system), (fields P6 to P9)
AC (alternation check; sensor activity monitoring): The function AC (field P6) is used to
check measuring signals for deviations. An alarm (E152) is triggered if the measuring
signal remains constant within the space of one hour. The reason for such sensor behavior
can be contamination, cable open circuit or similar.
CC (controller check): You can monitor the controller activity with the CC function . This
function is primarily suited to batch operation and single-sided limit switches. A
malfunction of the controller is detected and reported thanks to freely adjustable
monitoring times (E156, E157).
50
Endress+Hauser
Liquisys M CLM223/253
Commissioning
A
t
A0025196
28
A
PCS alarm (live check)
Constant measuring signal = alarm triggered after PCS alarm time has elapsed
Any PCS alarm pending is automatically deleted as soon as the sensor signal changes.
Endress+Hauser
51
Commissioning
Liquisys M CLM223/253
You can use the "Check" function group to monitor the measured value for permissible
upper and lower limits and trigger an alarm.
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
P
Settings for sensor and
process monitoring
CHECK function
group
P
CHECK
A0009045-EN
P1
Switch
Off
polarization
On
detection on or off
(only for
conductive
sensors)
Off P1
Pol.Detec
Polarization only occurs with
conductive sensors.
Any polarization that may
occur is detected but is not
compensated for. (Error no.:
E071)
A0009046-EN
P2
P3
Select alarm
threshold
monitoring
Enter alarm delay
Off
Low
High
LoHi = low and
high
Lo!
Hi!
LoHi!
0 min (s)
0 to 2000 min (s)
Off P2
A.Tresh
A0009048-EN
s
0 P3
Err.Delay
A0009049-EN
P4
Enter lower alarm 0 µS/cm
threshold
0 to 9999 mS/cm
Alarm possible with or
without controller switch-off.
xxxx = without controller
switch-off
xxxx! = with controller
switch-off
(Error no.: E154, E155)
Depending on the option
selected in F2, the alarm
delay can be entered in s or
min.
This delay must first elapse
before undershooting/
overshooting in accordance
with fields P4/P5 results in
an alarm.
µS/cm
0.00 P4
LowAlarm
A0009050-EN
P5
Enter upper alarm 9999 µS/cm
threshold
0 to 9999 mS/cm
mS/cm
9999 P5
HighAlarm
A0009051-EN
P6
52
Select process
monitoring
Off
AC
CC
AC+CC
AC!
CC!
AC+CC!
Off P6
ProcMonit
A0009052-EN
AC = sensor activity
monitoring (E152)
CC = controller monitoring
(E156, E157)
Alarm possible with or
without simultaneous
controller switch-off.
xxxx = without controller
switch-off
xxxx! = with controller
switch-off
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Coding Field
P7
Range of
adjustment
(factory settings
in bold)
Enter maximum
60 min
permissible
0 to 2000 min
duration for lower
CC setpoint limit
violation (field
P9)
Display
Info
Only if P6=CC or AC CC.
min
60 P7
Tmax Low
A0009053-EN
P8
Enter maximum
120 min
permissible
0 to 2000 min
duration for upper
CC setpoint limit
violation (field
P9)
Only if P6=CC or AC CC.
min
120 P8
Tmax High
A0009054-EN
P9
Enter CC set point
(for P7/P8)
1000 µS/cm
0 to 9999 mS/cm
µS/cm
1000 P9
Setpoint
Set value is an absolute value.
This function is primarily
suited to batch operation and
single-sided limit switches.
A0009055-EN
7.4.7
Relay configuration
For the "RELAY" function group, you require a relay card which is not available in the basic
device version.
The following relay contacts can be selected and configured as desired (max. four contacts,
depending on options installed):
• Limit contactor for conductivity measured value: R2 (1)
• Limit contactor for temperature: R2 (2)
• PID controller: R2 (3)
• Timer for cleaning function: R2 (4)
• Chemoclean function: R2 (5)
• USP/EP: R2 (6) and R2 (7) (for Plus Package, only conductive sensors)
Limit contactor for conductivity measured value and temperature
The transmitter has different ways of assigning a relay contact. Switch-on and switch-off
points and pickup and dropout delays can be assigned to the limit contactor. In addition,
you can configure an alarm threshold to output an error message and to start a cleaning
function in conjunction with this.
These functions can be used both for the primary value and for temperature measurement.
Please refer to the switch states in → 29 for a clear illustration of the relay contact
states.
• When the measured values increase (maximum function), the relay contact is closed as
of t2 after the switch-on point (t1) has been exceeded and the pickup delay has elapsed
(t2-t1).
The alarm contact switches if the alarm threshold (t3) is reached and the alarm delay
(t4-t3) has also elapsed (errors E067 to E070).
• When the measured values decrease, the alarm contact is reset when the value falls
below the alarm threshold (t5) again, as is the relay contact (t7) after the dropout delay
(t7-t6).
• If the pickup and dropout delays are set to 0 s, the switch-on and switch-off points are
also switch points of the contacts.
The same settings can also be made for a minimum function in the same way as for the
maximum function.
Endress+Hauser
53
Commissioning
Liquisys M CLM223/253
5
6
1
4
A
2
3
7
t1
t2
t3
t4
t5
t6 t7
t
7
B
3
2
4
6
1
5
t1
t2
t3
t4
t5
t6 t7
t
A0025215
29
A
B
1
2
3
4
5
6
7
54
Illustration of the alarm and limit value functions
Switch-on point > switch-off point: Max. function
Switch-on point < switch-off point: Min. function
Alarm threshold
Switch-on point
Switch-off value
Contact ON
Alarm ON
Alarm OFF
Contact OFF
Endress+Hauser
Liquisys M CLM223/253
Commissioning
P(ID) controller
You can define various controller functions for the transmitter. On the basis of the PID
controller, P, PI, PD and PID controllers can be implemented. For an optimum control
system, use the controller that best suits your application.
• P controller
Used for simple linear control purposes with small system deviations. Where major
changes are to be controlled, overshooting may occur. In addition, a lasting control
deviation must be expected.
• PI controller
Is used for control systems where overshooting is to be avoided and no lasting control
deviation should occur.
• PD controller
Is used for processes that require quick changes and where peaks must be corrected.
• PID controller
Is used for processes where a P, PI or PD controller does not control sufficiently.
Configuration options of the P(ID) controller
The following configuration options are available for a PID controller:
• Change control gain Kp (P influence)
• Set integral action time Tn (I influence)
• Set derivative action time Tv (D influence)
Basic load dosing (basic)
You can set a constant dosage amount (field R2311) with basic load dosing (field R231).
PID control plus basic load dosing
If you have selected this function (PID + Basic) in field R231, the PID-controlled dosage
amount does not drop below the basic load value entered in field R2311.
A
100 %
B
100 %
C
A0025221
30
A
B
C
Control characteristic of PID controller with basic load dosing
PID plus basic load
Basic load
PID
Commissioning
If you do not yet have any experience for setting the control parameters, set the values
that yield the greatest possible stability in the control circuit. Proceed as follows to
optimize the control circuit further:
• Increase the control gain Kp until the controlled variable just starts to overshoot.
• Reduce Kp slightly again and then reduce the integral action time Tn so that the shortest
possible correction time without overshooting is achieved.
• To reduce the response time of the controller, also set the derivative action time Tv.
Control and fine optimization of the set parameters with a recorder
Endress+Hauser
55
Commissioning
Liquisys M CLM223/253
A
A
2
1
B
B
A
A
4
3
B
B
A
5
B
A0025218
31
A
B
1
2
3
4
5
Optimization of settings Tn and Kp
Actual value
Time
Tn too small
Tn too large
Kp too large
Kp too small
Optimum setting
Actuating signal outputs via contacts (R237 to R2310)
Each control contact outputs a cyclical signal whose intensity corresponds to the
controller's actuating value. A distinction is made according to the type of signal cycle:
• Pulse length modulation
The bigger the calculated manipulated variable is, the longer the contact affected
remains picked up. The period T can be set to be between 0.5 and 99 s (field R238).
Outputs with pulse length modulation are used to activate solenoid valves.
• Pulse frequency modulation
The bigger the calculated manipulated variable is, the higher the switching frequency of
the contact affected. The maximum switching frequency 1/T can be set to be between 60
and 180 min-1 (field R239). The on-time ton is constant. It depends on the set maximum
frequency and is approx. 0.5 s for 60 min-1 and approx. 170 ms for 180 min-1. 170 ms.
Outputs with pulse frequency modulation are used to activate directly controlled
solenoid dosing pumps.
56
Endress+Hauser
Liquisys M CLM223/253
Commissioning
A
t1
A
t2
t1
1
1
0
0
t [s]
T
T1
T2
t [s]
A0025219
32
Signal of a pulse-length modulated controller contact (left) and of a pulse frequency-modulated controller
contact (right)
Contact:
1 = on, 0 = off
T
Period
Time (s):
t1 = ton t2 = toff
T1 T2
Impulse period length ( 1/T1 and 1/T2)
Constant controller
The controller can also control the second analog current output (if provided). This is
configured in fields R237 and O2.
Control characteristic for direct and inverse control action
You can choose between two control characteristics in the R236 field:
• Direct control action = maximum function
• Inverse control action = minimum function
Y
100 %
A
XW
– XW
Y
100 %
B
– XW
XW
A0025222
33
A
B
XW
Y
Control characteristic of a proportional controller with direct and inverse control action
Direct = maximum function
Inverse = minimum function
Control deviation
Current output signal = controller actuating variable
Timer for cleaning function
This function includes a simple cleaning option. You can set the time interval after which
cleaning should start. Therefore you can only select a constant interval sequence.
Other cleaning functions are available for selection in conjunction with the Chemoclean
function (device version with four contacts required, see the "Chemoclean function"
section).
The timer and Chemoclean do not work independently of one another. While one of
the two functions is active, the other cannot be started.
Endress+Hauser
57
Commissioning
Liquisys M CLM223/253
1
A
0
t
1
B
0
t0
t1
t2
t3
t4
t
A0025223
34
Connection between cleaning time, pause time and hold dwell period
A
Wiper and/or spray cleaning system
B
Hold function
0
Inactive
1
active
t0 Normal operation
t1 cleaning start
t2-t1Cleaning time
t3-t2Clean hold dwell period (0 to 999 s)
t4-t3Pause time between two cleaning intervals (1 to 7200 min)
Chemoclean function
Just like the timer function, Chemoclean can also be used to start a cleaning cycle.
However, Chemoclean also gives you the added option of defining various cleaning and
rinsing intervals and of dosing cleaning agent.
Therefore, it is possible to clean irregularly with different repeat cycles and to separately
set the cleaning times with post rinse times.
Please note the following:
• To use the Chemoclean function the transmitter has to be equipped with a designated
relay board (see product structure or chapter "accessories").
• The timer and Chemoclean are mutually dependent. While one of the two functions is
active, the other cannot be started.
• For the Chemoclean function, the relays 3 (water) and 4 (cleaner) are used.
• If the cleaning is prematurely aborted, a post rinse time always follows.
• If the setting is "Economy", cleaning only takes place with water.
58
Endress+Hauser
Liquisys M CLM223/253
Commissioning
1
A
0
1
B
0
1
C
0
t0
t1
t2
t4
t3
t5
A0025216
35
Sequence of a cleaning cycle
A
Hold function
B
Water valve is triggered
C
Cleaning valve is triggered
0
Contact off
1
Contact on
t0 Normal operation
t1 cleaning start
t2-t1Pre-rinse time
t3-t2Cleaning time
t4-t3Post rinse time
t5-t4Hold dwell period
Limit values for pharmaceutical water according to United States Pharmacopoeia
(USP) and European Pharmacopoeia (EP) (only for conductive sensors)
In the case of conductive sensors, the transmitter has functions for monitoring "Water for
Injection" (WFI), "Highly Purified Water" (HPW) and "Purified Water" (PW) according to the
United States Pharmacopoeia (USP) Part 645 and European Pharmacopoeia (EP)
standards.
USP function: The temperature-dependent limit values in the following table apply for
"Water for Injection" (WFI) according to USP and EP and for "Highly Purified Water" (HPW)
according to EP. The table is programmed into the transmitter.
Endress+Hauser
Temperature [°C]
Conductivity [µS/cm]
Temperature [°C]
Conductivity [µS/cm]
0
0.6
55
2.1
5
0.8
60
2.2
10
0.9
65
2.4
15
1.0
70
2.5
20
1.1
75
2.7
25
1.3
80
2.7
30
1.4
85
2.7
35
1.5
90
2.7
40
1.7
95
2.9
45
1.8
100
3.1
50
1.9
59
Commissioning
Liquisys M CLM223/253
The measurement is performed in the following steps:
• The transmitter determines the uncompensated conductivity and the water temperature.
• The transmitter rounds the temperature off to the nearest 5 °C and compares the
measured conductivity with the associated value in the table.
• If the measured value is larger than the value in the table, an alarm is triggered (E151).
EP-PW function: The following table lists the temperature-dependent limit values for
"Purified Water" (PW) in accordance with EP; this table is also programmed into the
transmitter.
Temperature [°C]
Conductivity [µS/cm]
Temperature [°C]
Conductivity [µS/cm]
0
2.4
60
8.1
10
3.6
70
9.1
20
4.3
75
9.7
25
5.1
80
9.7
30
5.4
90
9.7
40
6.5
100
10.2
50
7.1
The measurement is performed in the following steps:
• The transmitter determines the uncompensated conductivity and the water temperature.
• If the temperature is between two table entries, the limit value for the conductivity is
determined by interpolation of the two neighboring points.
• If the measured value is larger than the limit value, an alarm is triggered (E151).
Early warning: A USP early warning is also available. This is activated at a configurable
switch-on point (e.g. 80 % of USP/EP limit value). This means that the user is alerted to be
able to regenerate the plant in time. Der Voralarm wird in Feld R262 bzw. R272
eingestellt.
Please note the following:
• The device must be equipped with a relay card and the Plus Package to be able to use the
USP and EP function.
• To output an alarm, enable the fault-signaling contact or the error current in field F5 F7 (error code E151 and E153).
• The switch-off point of the pre-alarm is 1 % below of the switch-on point (R262 /
R272), related to the main limit value.
• The transmitter also uses the uncompensated values for the USP and EP function when
it displays temperature-compensated values.
• The limit value of 100 °C (212 °F) is used for temperatures over 100 °C (212 °F).
60
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
R
Relay contact settings
RELAY
R
RELAIS
A0009058-EN
R1
Select the contact Rel1
to be configured Rel2
Rel3
Rel4
Rel1 R1
Sel.Relay
A0009059-EN
R2 (1)
R211
Configure limit
contactor for
conductivity,
resistance or
concentration
measurement
Switch function
of R2 (1) off or
on
LC PV = limit
contactor
conductivity (1)
LC °C = limit
contactor T (2)
PID controller (3)
Timer (4)
Clean=
Chemoclean (5)
USP (6)
EP PV(7)
Off
On
LC PV
R2
Sel.Type
A0009060-EN
Rel3 (water) and Rel4
(cleaner) are only available
with the relevant version of
the transmitter.
If Chemoclean is used as the
cleaning method, Rel4 is not
available.
PV = process value
If Rel4 is selected in the R1
field, Clean = Chemoclean
cannot be selected. By
confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
All the settings are retained.
off
R211
Function
A0009067-EN
R212
Enter the switch- Cond/ind: 9999
on point of the
mS/cm
contact
MOhm: 200
MΩ·cm
Conc: 9999 %
9999
mS/cm
R212
On value
Never set the switch-on point
and the switch-off point to the
same value! (Only the
operating mode selected in A1
is displayed.)
A0009068-EN
R213
Enter the switch- Cond/ind: 9999
off point of the
mS/cm
contact
MOhm: 200
MΩ·cm
Conc: 9999 %
9999
mS/cm
R213
Off value
A0009069-EN
R214
Enter pickup
delay
0s
0 to 2000 s
0
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact
(switch-off point > switch-on
point), thereby implementing a
hysteresis that is constantly
required (see "Illustration of
the alarm and limit functions"
figure).
s
R214
On Delay
A0009070-EN
Endress+Hauser
61
Commissioning
Liquisys M CLM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
R215
0s
0 to 2000 s
Enter dropout
delay
Display
Info
0
s
R215
Off Delay
A0009071-EN
R216
Enter alarm
threshold
Cond/ind: 9999
mS/cm
MOhm: 200
MΩ·cm
Conc: 9999 %
9999
mS/cm
R216
A.Thresh
A0009072-EN
R217
Display status for MAX
limit contactor
MIN
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the
error message (E067 to E070)
and an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
Display only
MAX R217
LC State
A0009073-EN
R2 (2)
R221
Configure limit
contactor for
temperature
measurement
Switch function
of R2 (2) off or
on
LC PV = limit
contactor
conductivity (1)
LC °C = limit
contactor T (2)
PID controller (3)
Timer (4)
Clean=
Chemoclean (5)
USP (6)
EP PV(7)
Off
On
LC ¡C
R2
Sel.Type
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
A0009061-EN
off
R221
Function
A0009074-EN
R222
Enter switch-on
temperature
250.0 °C
-35.0 to 250.0 °C
°C
250.0 R222
Never set the switch-on point
and the switch-off point to the
same value!
On value
A0009075-EN
R223
Enter switch-off
temperature
250.0 °C
-35.0 to 250.0 °C
°C
250.0 R223
Off value
A0009076-EN
62
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact
(switch-off point > switch-on
point), thereby implementing a
hysteresis that is constantly
required (see "Illustration of
the alarm and limit functions"
figure).
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
R224
0s
0 to 2000 s
Enter pickup
delay
Display
Info
0 R224
s
On Delay
A0009077-EN
R225
Enter dropout
delay
0s
0 to 2000 s
0 R225
s
Off Delay
A0009078-EN
R226
Enter alarm
threshold (as
absolute value)
250.0 °C
-35.0 to 250 °C
°C
250.0 R226
A.Thresh
A0009079-EN
R227
Display status for MAX
limit contactor
MIN
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the
error message (E067 to E070)
and an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
Display only
MAX R227
LC State
A0009080-EN
R2 (3)
R231
Configure P(ID)
controller
Switch function
of R2 (3) off or
on
LC PV = limit
contactor
conductivity (1)
LC °C = limit
contactor T (2)
PID controller
(3)
Timer (4)
Clean=
Chemoclean (5)
USP (6)
EP PV(7)
Off
On
Basic
PID+B
PID R2
Sel.Type
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
A0009062-EN
off
R231
On = PID controller
Basic = basic load dosing
PID+B = PID controller + basic
load dosing
Function
A0009081-EN
R232
Enter set point
Cond/ind: 0.00
μS/cm
MOhm: 0.00
kΩ·cm
Conc: 0.00 %
µS/cm
0.00 R232
Setpoint
The set point is the value to be
maintained by the control
system. Using this control
process, this value is restored
when an upwards or
downwards deviation occurs.
A0009084-EN
Endress+Hauser
63
Commissioning
Liquisys M CLM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
R233
1.00
0.01 to 20.00
Enter control
gain KP
Display
Info
1.00 R233
See the "P(ID) controller"
section.
Kp
A0009085-EN
R234
Enter integral
action time Tn
(0.0 = no Icomponent)
0.0 min
0.0 to 999.9 min
0.0
min
R234
Time Tn
A0009086-EN
R235
Enter derivative
action time Tv
(0.0 = no Dcomponent)
0.0 min
0.0 to 999.9 min
0.0
min
See the "P(ID) controller"
section.
With every hold, the Icomponent is set to zero.
Although the hold can be
deactivated in field S2, this
does not apply for Chemoclean
and timer!
See the "P(ID) controller"
section.
R235
Time Tv
A0009087-EN
R236
Select controller
characteristic
Dir = direct
Inv = inverse
dir
R236
Direction
The setting is required
depending on the control
deviation (upward or
downward deviation, see the
"P(ID) controller" section).
A0009088-EN
R237
Select pulse
length or pulse
frequency
Len = pulse
length
Freq = pulse
frequency
Curr = current
output 2
len
R237
Oper.Mode
A0009089-EN
R238
Enter pulse
interval
10.0 s
0.5 to 999.9 s
s
10.0 R238
PulsePer.
Pulse length e.g. for solenoid
valve, pulse frequency e.g. for
solenoid dosing pump, see the
"Actuating signal outputs"
section.
Curr = current output 2 can
only be selected if O2 = Contr.
This field only appears if pulse
length is selected in R237.
If pulse frequency is selected,
R238 is skipped and entries
continue with R239.
A0009090-EN
R239
Enter maximum
pulse frequency
of the adjuster
min-1
120
60 to 180 min-1
120
1/min
R239
Max.PFreq
This field only appears if pulse
frequency is selected in R237.
If pulse length is selected,
R239 is skipped and entries
continue with R2310.
A0009091-EN
R2310
Enter minimum
switch-on time
tON
0.3 s
0.1 to 5.0 s
s
0.3 R2310
This field only appears if pulse
length is selected in R237.
Min.PTime
A0009082-EN
64
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
R2311
0%
0 to 40 %
Enter basic load
Display
Info
%
0 R2311
BasicLoad
A0009083-EN
R2 (4)
R241
Configure
LC PV = limit
cleaning function contactor
(timer)
conductivity (1)
LC °C = limit
contactor T (2)
PID controller (3)
Timer (4)
Clean=
Chemoclean (5)
USP (6)
EP PV(7)
Switch function
of R2 (4) off or
on
Off
On
Timer R2
Sel.Type
A0009063-EN
off
When you select the basic load,
you enter the desired dosing
quantity.
100% basic load would
correspond to:
• Constantly on if R237 = len
• Fmax if R237 = freq (field
R239)
• 20 mA if R237 = curr
Only one cleaning agent
(generally water) is used for
the cleaning.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
R241
Function
A0009092-EN
R242
Enter rinsing/
cleaning time
30 s
0 to 999 s
s
30 R242
Settings for hold and relay are
active for this time.
RinseTime
A0009093-EN
R243
Enter pause time
360 min
1 to 7200 min
min
360 R243
The pause time is the time
between two cleaning cycles
(see the "Timer for cleaning
function" section).
PauseTime
A0009094-EN
R244
Enter minimum
pause time
120 min
1 to R243
min
120 R244
The minimum pause time
prevents constant cleaning if a
cleaning trigger is pending.
Min.Pause
A0009095-EN
R2 (5)
Endress+Hauser
Configure
cleaning with
Chemoclean (for
version with four
contacts,
Chemoclean
option and
contacts 3 and 4
assigned)
LC PV = limit
contactor
conductivity (1)
LC °C = limit
contactor T (2)
PID controller (3)
Timer (4)
Clean=
Chemoclean (5)
USP (6)
EP PV(7)
Clean R2
Sel.Type
A0009064-EN
See the "Chemoclean function"
section.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
65
Commissioning
Liquisys M CLM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
R251
Off
On
Switch function
of R2 (5) off or
on
Display
Info
off R251
Function
A0009096-EN
R252
R253
Select type of
start pulse
Enter pre-rinse
time
Int = internal
(timecontrolled)
Ext = external
(digital input 2)
I+ext = internal +
external
I+stp = internal,
suppressed by
external
20 s
0 to 999 s
int
R252
CleanTrig
A0009097-EN
s
20 R253
The cycle for the "int" function
is started when the pause time
ends (R257).
No real time clock is available.
External suppression is
required for irregular time
intervals (e.g. weekends).
Rinsing is performed with
water.
PreRinse
A0009098-EN
R254
Enter cleaning
time
10 s
0 to 999 s
s
10 R254
Cleaning is performed with
cleaning agent and water.
CleanTime
A0009099-EN
R255
Enter post rinse
time
20 s
0 to 999 s
s
20 R255
Rinsing is performed with
water.
PostRinse
A0009100-EN
R256
Enter number of
repeat cycles
0
0 to 5
R253 to R255 is repeated.
0 R256
Rep.Rate
A0009101-EN
R257
Enter pause time
360 min
1 to 7200 min
min
360 R257
PauseTime
The pause time is the time
between two cleaning cycles
(see the "Chemoclean function"
section).
A0009102-EN
R258
Enter minimum
pause time
120 min
1 to R257
min
120 R258
Min.Pause
The minimum pause time
prevents constant cleaning if
an external cleaning start is
pending.
A0009103-EN
66
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
R259
Enter number of
cleaning cycles
without cleaning
agent (economy
function)
0
0 to 9
Configure USP
contact (only for
Plus Package
with relay card)
LC PV = limit
contactor
conductivity (1)
LC °C = limit
contactor T (2)
PID controller (3)
Timer (4)
Clean=
Chemoclean (5)
USP (6)
EP PV(7)
Display
Info
0 R259
EconomyCl
After cleaning with cleaner, up
to 9 cleaning sessions can be
carried out with water only
until the next cleaning session
with cleaner takes place.
A0009104-EN
R2 (6)
R261
Switch function
of R2 (6) off or
on
Off
On
USP
R2
Sel.Type
A0009065-EN
Off
The USP contact can be
configured as an early warning
alarm, i.e. it alerts the user
before the actual limit value is
reached.
Error no. E151 appears in the
event of an alarm.
WFI according to USP; HPW
according to EP
R261
Function
A0009105-EN
R262
Early warning
threshold: enter
switch-on point
80.0 %
0.0 to 100.0 %
%
80.0 R262
On Value
A0009106-EN
R264
Early warning
threshold: enter
pickup delay
0s
0 to 2000 s
The early warning triggers the
contact.
When the alarm value is
reached (100%), the alarm
relay is also triggered.
Example: Given 15 °C and 1.0
μS/cm, a USP early warning
alarm is triggered at 0.8 μS/cm
when the setting is 80%.
s
0 R264
On Delay
A0009107-EN
R265
Early warning
threshold: enter
dropout delay
0s
0 to 2000 s
s
0 R265
Off Delay
A0009108-EN
R2 (7)
Endress+Hauser
Configure EP PV
contact (only for
Plus Package
with relay card)
LC PV = limit
contactor
conductivity (1)
LC °C = limit
contactor T (2)
PID controller (3)
Timer (4)
Clean=
Chemoclean (5)
USP (6)
EP PV(7)
EP PW R2
Sel.Type
A0009066-EN
The EP PV contact can be
configured as an early warning
alarm, i.e. it alerts the user
before the actual limit value is
reached.
Error no. E151 appears in the
event of an alarm.
PV according to EP
67
Commissioning
Liquisys M CLM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
R271
Off
On
Switch function
of R2 (7) off or
on
Display
Info
Off
R271
Function
A0009109-EN
R272
Early warning
threshold: enter
switch-on point
80.0 %
0.0 to 100.0 %
%
80.0 R272
On Value
A0009110-EN
R274
Early warning
threshold: enter
pickup delay
0s
0 to 2000 s
The early warning triggers the
contact.
When the alarm value is
reached (100%), the alarm
relay is also triggered.
Example: Given 15 °C and 1.0
μS/cm, an EP PV early warning
alarm is triggered at 0.8 μS/cm
when the setting is 80%.
s
0 R274
On Delay
A0009111-EN
R275
Early warning
threshold: enter
dropout delay
0s
0 to 2000 s
s
0 R275
Off Delay
A0009112-EN
68
Endress+Hauser
Liquisys M CLM223/253
Commissioning
7.4.8
Temperature compensation with table
The "ALPHA TABLE" function group is not available in the basic device version. You require
the Plus Package to access this function group. With this function group, you can perform
temperature compensation using a table (field B2).
Enter the α-T value pairs (see SETUP 2) in the T4 and T5 fields.
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
Display
adjustment
(factory
settings in bold)
Info
T
Settings for temperature
compensation.
ALPHA TABLE
function group
T
ALPHA TAB
A0009123-EN
T1
Select table
option
Read
Edit
read T1
Sel.Table
A0009125-EN
T2
Enter number of
table value pairs
1
1 to 10
1 T2
No. Elem.
In the α-table, you can enter a
maximum of 10 value pairs.
These pairs are saved under
numbers 1 to 10 and can be
changed individually or
consecutively.
A0009126-EN
T3
Select table
value pair
1
1 to number of
table value pairs
Assign
1 T3
Sel.Elem.
A0009127-EN
T4
Enter
temperature
value
0.0 °C
-35.0 to 250.0 °C
°C
0.0 T4
Temp.val.
The system automatically runs
through the T3 to T5 function
chain as often as corresponds to
the value indicated in T2.
"Assign" appears as the last
value.
The display goes to T6 once the
process is finished.
The temperature values must be
at least 1 K apart.
Factory setting for the
temperature value in the table
value pairs:
0.0 °C; 10.0 °C; 20.0 °C; 30.0 °C ...
A0009128-EN
T5
Enter
temperature
coefficient α
2.10 %/K
0.00 to 20.00
%/K
%/K
2.10 T5
alpha val
A0009129-EN
T6
Message as to
whether table
status is OK
Yes
No
yes T6
Status ok
A0009130-EN
Endress+Hauser
Display only
If status = "no", you must set
correct values in the table (all
settings made up until now
remain intact) or go back to the
measuring mode (then the table
is not valid).
69
Commissioning
Liquisys M CLM223/253
7.4.9
Concentration Measurement
The CONCENTRATION function group is only available for devices with a Plus Package.
The transmitter can convert from conductivity values to concentration values. For this
purpose, the operating mode is first set to concentration measurement (see field A1).
Afterwards, in the measuring device you must specify the basic data on the basis of which
the concentration is to be calculated. You require the conductivity characteristic curves of
the medium for this.
In the case of conductive sensors, the effects of polarization in the boundary layer between
the sensor and medium restrict the measuring range. The transmitter can detect
polarization effects by using a smart signal analysis process. Error message E071 is
displayed.
You can either refer to your data sheets for these characteristic curves or determine the
characteristic curves yourself.
1. Create samples of the medium in the concentrations that occur in the process.
2. Then measure the uncompensated conductivity of these samples at temperatures that
also occur in the process.
• For variable process temperatures:
If variable process temperatures are to be taken into consideration, you must
measure the conductivity for at least two temperatures (ideally the minimum and
maximum process temperature) for the samples created. The temperature values of
the various samples must be identical in each case. The temperatures must be at
least 0.5 °C apart.
At least two samples of different concentrations, taken at two different
temperatures in each case, are required as the transmitter needs at least four points
in the table (this must include the minimum and maximum concentration values).
• For constant process temperatures:
Measure the differently concentrated samples at this temperature. At least two
samples are required.
At the end you should have measuring data which resemble those shown in the following
figures.
2
k
k
T3
1
2
T3
1
T2
T2
T1
Cmin
Cmax
T1
C
Cmin
Cmax
C
A0008926
36
κ
C
T
1
2
70
Example of measured data for variable temperatures
Conductivity
Concentration
Temperature
Measuring point
Measuring range
Endress+Hauser
Liquisys M CLM223/253
Commissioning
k
k
1
1
T
Cmin
Cmax
C
Cmin
T
C
Cmax
A0008925
37
κ
C
T
1
Example of measured data for constant temperatures
Conductivity
Concentration
Constant temperature
Measuring range
The characteristic curves received from the measuring
points
must increase or decrease very monotonically in
k
k
the range of the process conditions, i.e. neither
maximum points, nor minimum points, nor ranges
with a constant behavior can occur. The curve profiles
opposite are therefore not permitted.
C
C
A0008927
38
κ
C
Impermissible curve profiles
Conductivity
Concentration
Value entry
Enter the three characteristic values for each measured sample in the fields K6 to K8
(value triplets of uncompensated conductivity, temperature and concentration).
• Variable process temperature:
Enter at least the four value triplets needed.
• Constant process temperature:
Enter at least the two value triplets needed.
Please note the following:
If the measured values of the process are outside the range of your sample values, this
considerably reduces the level of accuracy and the error message E078 or E079 will be
displayed. Therefore, take the limit values of your process into consideration when
determining the characteristic curves. Wird bei aufsteigender
If you enter an additional value triplet of 0 μS/cm and 0% for every temperature used
when the characteristic curve is increasing, you can work from the start of the measuring
range with sufficient accuracy and without an error message.
Enter the values in order of increasing concentration (see the following example).
Endress+Hauser
mS/cm
%
°C
240
96
60
380
96
90
220
97
60
340
97
90
120
99
60
200
99
90
71
Commissioning
Liquisys M CLM223/253
As the temperature is already processed in the concentration tables, the settings for
temperature compensation in the Setup 2 menu (fields B2 and B3) are ineffectual for
concentration measurement.
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory
settings in
bold)
Display
Info
K
CONCENTRATION
function group
K
Four different
concentration fields can be
entered in this function
group.
CONCENTRA
A0009113-EN
K1
Select the active
1
concentration curve on 1 to 4
which the calculation of
the display value is
based
1 K1
The curves are
independent of one
another. Four different
curves can be defined.
act.curve
A0009114-EN
K2
Select the curve to be
edited
1
1 to 4
1 K2
editCurve
A0009115-EN
K3
Select table option
Read
Edit
read K3
If a curve is being edited,
another curve should be
used to calculate the
current display values.
Example: If curve 2 is
being edited, either curve
1, curve 3 or curve 4
should be active (see K1).
This option is valid for all
concentration curves.
Table
A0009116-EN
K4
Enter number of
reference triplets
1
1 to 10
1 K4
Each triplet consists of
three numeric values.
No. Elem.
A0009117-EN
K5
Select triplet
1
1 to number of
triplets in K4
Assign
1 K5
Any triplet can be edited.
"Assign" takes the user to
K9
Sel.Elem.
A0009118-EN
K6
Enter uncompensated
conductivity value
0.0 mS/cm
0.0 to 9999
mS/cm
mS/cm
0.0 K6
conduct.
The system automatically
runs through the K5 to K6
function chain as often as
corresponds to the value
indicated in K4. The
display then goes to K9.
A0009119-EN
72
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Coding Field
Range of
adjustment
(factory
settings in
bold)
K7
0.00 %
0.00 to 99.99 %
Enter concentration
value for K6
Display
Info
Engineering unit as
selected in A2.
Format as selected in A3.
%
0.00 K7
concentr.
A0009120-EN
K8
Enter temperature value 0.0 °C
for K6
-35.0 to 250.0
°C
°C
0.0 K8
Temp.val.
A0009121-EN
K9
Message as to whether
table status is OK
Yes
No
yes K9
Status ok
A0009122-EN
7.4.10
Read only.
If "No", then set correct
values in the table (all
settings made up until
now remain intact) or go
back to the measuring
mode (then the table is
not valid).
Service
Coding Field
Range of
adjustment
(factory settings in
bold)
Display
Info
S
Service function settings.
SERVICE
function group
S
SERVICE
A0008408-EN
S1
Select language
ENG = English
GER = German
FRA = French
ITA = Italian
NL = Dutch
ESP = Spanish
ENG
S1
The option selected only
applies for the faultsignaling contact, not for the
error current.
Language
A0008409-EN
S2
S3
Configure a hold S+C = hold during
configuration and
calibration
Cal = hold during
calibration
Setup = hold during
configuration
None = no hold
Manual hold
Off
On
S+C
S = setup
C = calibration
S2
Auto HOLD
A0008413-EN
off
S3
The setting is retained even
in the event of a power
failure.
Man. HOLD
A0008414-EN
Endress+Hauser
73
Commissioning
Liquisys M CLM223/253
Coding Field
S4
Range of
adjustment
(factory settings in
bold)
Display
Info
Enter hold dwell 10 s
period
0 to 999 s
10
s
S4
Cont.Time
A0008415-EN
S5
Enter SW
upgrade release
code (Plus
Package)
0000
0000 to 9999
0000
S5
PlusCode
A0008416-EN
S6
Enter SW
upgrade release
code for
Chemoclean
0000
0000 to 9999
0000 S6
CleanCode
A0008417-EN
S7
Order number is
displayed
order
S7
The code can be found on the
nameplate.
If an incorrect code is
entered, you are taken back
to the measurement menu.
The number is edited with
the PLUS or MINUS key and
confirmed with the ENTER
key. "1" is displayed if the
code is active.
The code can be found on the
nameplate.
If an incorrect code is
entered, you are taken back
to the measurement menu.
The number is edited with
the PLUS or MINUS key and
confirmed with the ENTER
key. "1" is displayed if the
code is active.
If the device is upgraded, the
order code is changed
automatically.
PR0005
A0008418-EN
S8
Serial number is
displayed
SerNo
S8
12345678
A0008420-EN
S9
Reset the device
to the basic
settings
No
Sens = sensor data
Facty = factory
settings
no
S9
S.Default
Sens = last calibration is
deleted and is reset to factory
setting.
Facty = all data (apart from
A1 and S1) are deleted and
reset to the factory setting!
A0008421-EN
S10
Perform device
test
No
Displ = display test
no
S10
Test
A0008410-EN
74
Endress+Hauser
Liquisys M CLM223/253
Commissioning
7.4.11
E+H Service
Coding Field
Range of adjustment
(factory settings in
bold)
Display
Info
E
Information on the
device version
E+H SERVICE
function group
E
E+H SERV
A0007857-EN
E1
Select module
Contr = controller
(central module) (1)
Trans = transmitter (2)
Main = power unit (3)
Rel = relay module (4)
Sens = sensor (5)
Contr E1
Select
A0007858-EN
E111
E121
E131
E141
E151
Software version is
displayed
E112
E122
E132
E142
E152
Hardware version
is displayed
xx.xx
E111
SW-Vers.
If E1 = contr: device
software
If E1 = trans, main, rel:
module firmware
If E1 = sens: sensor
software
A0007859-EN
Info display
xx.xx
E112
HW-Vers.
A0007861-EN
E113
E123
E133
E143
E153
Serial number is
displayed
Info display
SerNo
E113
12345678
A0007860-EN
E114
E124
E134
E144
E154
Module ID is
displayed
Info display
LSG
E114
Modul-ID
A0007862-EN
Endress+Hauser
75
Commissioning
Liquisys M CLM223/253
7.4.12
Interfaces
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
I
INTERFACE
function group
I
Communication settings (only
for HART or PROFIBUS device
version).
INTERFACE
A0007863-EN
I1
Enter bus
address
Address
HART: 0 to 15
or
PROFIBUS: 0 to
126
126
I1
Address
A0007864-EN
I2
The tag name is
displayed
Each address may only be
assigned once in a network. If a
device address ≠ 0 is selected for
a HART device, the current
output is automatically set to 4
mA and the device prepares for
multi-drop operation.
Tag I2
@@@@@@@@
A0007865-EN
7.4.13
Communication
For devices with a communication interface, please also refer to the separate Operating
Instructions BA00208C/07/EN (HART®) or BA00209C/07/DE (PROFIBUS®).
76
Endress+Hauser
Liquisys M CLM223/253
Commissioning
7.5
Calibration
Use the CAL key to access the calibration function group.
Use this function group to calibrate and adjust the transmitter. The calibration can be
performed in two different ways:
• By measuring in a calibration solution of known conductivity.
• By entering the exact cell constant of the conductivity sensor.
Please note the following:
• During initial commissioning of inductive sensors, an air set is absolutely essential for
residual coupling compensation (from field C111) so that the measuring system can
return precise measurement data.
• If the calibration procedure is aborted by pressing the PLUS and MINUS keys at the same
time (return to C114, C126 or C136) or if the calibration is faulty, then the previous
calibration data are reinstated. A calibration error is indicated by “ERR” and the sensor
symbol flashes on the display.
Repeat calibration!
• For each calibration, the device automatically switches to hold (factory setting).
• On completion of the calibration, the device returns to the measurement mode. The
"hold" symbol appears on the display during the hold dwell period (field S4).
• Only items C121 to C126 are relevant for conductive sensors.
Coding
Field
Range of
adjustment
(factory
settings in
bold)
Display
Info
C
CALIBRATION
function group:
Airs and InstF do not apply
for conductive
measurement.
C
CALIBRAT
A0009141-EN
C1(1)
Calibration of
inductive sensors
with annular
opening
Airs = air set
(1)
Cellc = cell
constant (2)
InstF =
installation
factor (3)
AirS C1
Calibrat
When commissioning
inductive sensors, an air set
is mandatory. The sensor
air set must be performed in
air and in a dry state.
A0009142-EN
Take the inductive sensor out of the liquid and
dry it fully.
A0025597
C111
Residual coupling
start calibration
(air set)
Current
measured value
µS/cm
0.0 C111
Press CAL to start the
calibration.
AirSet
A0009145-EN
Endress+Hauser
77
Commissioning
Liquisys M CLM223/253
Coding
Field
Range of
adjustment
(factory
settings in
bold)
C112
The residual
coupling is
displayed (air set)
-80.0 to 80.0
μS/cm
Display
Info
µS/cm
5.3 C112
Residual coupling of
measuring system (sensor
and transmitter).
AirSetVal
A0009146-EN
C113
Calibration status
is displayed
o.k.
E xxx
o.k. C113
If the calibration status is
not o.k., a reason for the
error is provided on the
second line of the display.
Status
A0009147-EN
C114
Store calibration
result?
Yes
No
New
yes C114
Store
If C113 = E xxx, then only
No or New.
If New, return to C.
If Yes/No, return to
"Measurement".
A0009148-EN
C1(2)
Cell constant
calibration
Airs = air set (1)
Cellc = cell
constant (2)
InstF =
installation
factor (3)
Cellc C1
Calibrat
The sensor should be
immersed in such a way
that there is sufficient
distance to the vessel wall
(the installation factor has
no influence if a > 15 mm).
A0009143-EN
Immerse the sensor in the calibration solution.
following section describes calibration
The
with the temperature-compensated
conductivity value of the reference solution.
If calibration is to be performed with the
uncompensated conductivity value, you
must set the temperature coefficient α to
zero.
A0025598
C121
Enter calibration
25 °C
temperature (MTC) -35.0 to 250.0 °C
Only available if B1 = fixed.
C122
Enter the α value
of the calibration
solution
The value is given in the
Technical Information for
all E+H calibration
solutions. You can also use
the printed-on table to
calculate the value.
Set α to 0 for calibration
with uncompensated values.
2.10 %/K
0.00 to 20.00
%/K
2.10 C122
%/K
alpha val
A0009150-EN
C123
Enter the correct
conductivity value
of the calibration
solution
Current
measured value
0.0 μS/cm to
9999 mS/cm
mS/cm
10.30 C123
A value close to the
subsequent operating range
should be selected.
Real. val
A0009151-EN
78
Endress+Hauser
Liquisys M CLM223/253
Commissioning
Coding
Field
Range of
adjustment
(factory
settings in
bold)
C124
The calculated cell
constant is
displayed
0.0025 to 99.99
cm-1
Display
Info
1/cm
1.000 C124
The calculated cell constant
is displayed and accepted in
A5.
Cellconst
A0009152-EN
C125
Calibration status
is displayed
o.k.
E xxx
o.k. C125
If the calibration status is
not o.k., a reason for the
error is provided on the
second line of the display.
Status
A0009153-EN
C126
Store calibration
result?
Yes
No
New
yes C126
Store
If C125 = E xxx, then only
No or New.
If New, return to C.
If Yes/No, return to
"Measurement".
A0009154-EN
C1(3)
Calibration with
sensor adjustment
for inductive
sensors (only for
Plus Package)
Airs = air set (1)
Cellc = cell
constant (2)
InstF =
installation
factor (3)
InstF C1
Calibrat
A0009144-EN
The inductive sensor is mounted at the place of
installation.
Sensor adjustment with
compensation for wall
effects.
In the case of inductive
sensors, the measured value
is influenced by the distance
between the sensor and the
pipe wall and by the
material of the pipe
(conductive or insulating).
The installation factor
indicates these
dependencies. See the
Technical Information of
the sensor used for more
information
A0025599
C131
Enter the process
25 °C
temperature (MTC) -35.0 to 250.0 °C
Only available if B1 = fixed.
25.0
°C
C131
MTC temp.
A0009155-EN
C132
Enter the α value of 2.10 %/K
the calibration
0.00 to 20.00
solution
%/K
2.10 C132
%/K
alpha val
A0009156-EN
C133
Enter the correct
conductivity value
of the calibration
solution
Current
measured value
0.0 μS/cm to
9999 mS/cm
mS/cm
10.30 C133
The value is given in the TI
for all E+H calibration
solutions. You can also use
the printed-on table to
calculate the value.
Set α to 0 for calibration
with uncompensated values.
A value close to the
subsequent operating range
should be selected.
Real val.
A0009157-EN
Endress+Hauser
79
Commissioning
Liquisys M CLM223/253
Coding
Field
Range of
adjustment
(factory
settings in
bold)
C134
Calculated
installation factor
is displayed
1
0.10 to 5.00
Display
Info
1 C134
InstFact
A0009158-EN
C135
Calibration status is o.k.
displayed
E xxx
o.k. C135
The installation factor
indicates the dependency
between the measured
value and the distance
between the sensor and
pipe wall. See the Technical
Information of the sensor
used for more information.
If the calibration status is
not o.k., a reason for the
error is provided on the
second line of the display.
Status
A0009159-EN
C136
Store calibration
result?
Yes
No
New
yes C136
Store
If C135 = E xxx, then only
No or New.
If New, return to C.
If Yes/No, return to
"Measurement".
A0009160-EN
80
Endress+Hauser
Liquisys M CLM223/253
Diagnostics and troubleshooting
8
Diagnostics and troubleshooting
8.1
Trouble shooting instructions
The transmitter continuously monitors its functions itself. If an error occurs which the
device recognizes, this is indicated on the display. The error number is shown below the
display of the main measured value. If more than one error occurs, you can call these up
with the MINUS key.
Refer to the "System error messages" table for the possible error numbers and remedial
measures.
Should a malfunction occur without any transmitter error message, please refer to the
"Process-specific errors" or the "Device-specific errors" tables to localize and rectify the error.
These tables provide you with additional information on any spare parts required.
8.2
System error messages
You can display and select the error messages with the MINUS key.
Error
No.
E001
E002
E003
E004
E007
E008
E010
Endress+Hauser
Display
Tests/remedial action
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
• Switch off device and
switch it on again.
• Load software
compatible with
Device not calibrated,
hardware
calibration data
invalid, no user data or • Load measurementparameter specific
user data invalid
device software.
(EEPROM error),
• If the error persists,
device software not
send in the device for
suitable for hardware
repair to your local
(controller)
sales center or replace
the device.
Yes
No
X
0C
X
0C
X
0C
X
0C
Download error
Invalid configuration.
Repeat download.
Yes
No
0C
Load software compatible
with hardware
Load measurementparameter specific device
software.
Yes
EEPROM memory
error
Device software
version not compatible
with module hardware
version
Transmitter
malfunction, device
software not
compatible with
transmitter version
Yes
No
No
0C
No
No
0C
0C
Yes
Sensor or sensor
connection faulty
Check sensor and sensor
connection
Yes
Temperature sensor
defective, not
connected or shortcircuited
(measurement
continues with 25 °C)
Check temperature sensor Yes
and connections; check
the measuring device and
measuring cable with a
temperature simulator if
necessary.
Check that correct option
is selected in field B1
No
No
X
0C
X
0C
Yes
0C
0C
No
No
80
0C
81
Diagnostics and troubleshooting
Error
No.
E025
E036
E037
E045
E049
E050
E055
E057
E059
E061
E063
E064
E065
E066
E067
E068
E069
E070
E071
82
Liquisys M CLM223/253
Display
Tests/remedial action
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
No
No
80
Limit value for air set
offset exceeded
Perform air set again (in
air) or replace sensor. Dry
sensor.
No
Calibration range of
sensor exceeded
Clean sensor and
recalibrate; if necessary,
check sensor and
connections.
No
Below calibration
range of sensor
Calibration aborted
Calibration range of
installation factor
exceeded
80
No
Repeat the calibration
Check pipe diameter,
clean sensor and perform
calibration again.
No
No
Below main parameter Check measurement,
measuring range
control and connections
Yes
Main parameter
measuring range
exceeded
Yes
Below temperature
measuring range
Yes
Temperature
measuring range
exceeded
Yes
No
No
80
No
No
No
No
X
80
X
80
X
80
X
80
X
80
X
80
No
44
80
No
No
44
80
No
No
80
44
No
No
80
44
Check measured value
and current assignment
Yes
No
No
80
80
Current output range 1
exceeded
Yes
Below current output
range 2
Yes
Current output range 2
exceeded
Yes
No
No
80
80
No
No
80
80
No
No
80
80
Check configuration
Yes
No
No
80
80
Set point exceeded
limit contactor 2
Yes
Set point exceeded
limit contactor 3
Yes
Set point exceeded
limit contactor 4
Yes
Incorrect
measurement /
polarization
80
80
No
Set point exceeded
limit contactor 1
No
80
Below calibration
range of installation
factor
Below current output
range 1
No
No
No
80
80
No
No
80
80
No
No
80
80
Clean sensor; check table;
select suitable sensor.
Yes
No
No
44
80
Endress+Hauser
Liquisys M CLM223/253
Diagnostics and troubleshooting
Error
No.
E077
E078
E079
E080
E081
E085
E100
E101
E102
E106
E116
E150
E151
Display
Temperature outside α
value table range
Tests/remedial action
Clean sensor; check tables
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
Yes
No
No
44
80
Temperature outside
concentration table
Yes
Conductivity outside
concentration table
Yes
Current output 1 range Increase range in "Current
too small
outputs" menu.
Yes
Current output 2 range
too small
Yes
Incorrect setting for
error current
Download error
Distance between
temp. values in α value
table too small or not
monotonously
increasing
44
No
No
44
80
If the current range "0 to
20 mA" was selected in
field O311, the error
current may not be set to
"2.4 mA".
Yes
No
No
No
No
Switch off service function No
or switch device off and
then on again.
No
No
No
Wait for download to
finish.
No
Repeat download.
Yes
No
No
Enter correct α value table No
(temperatures must be
entered at intervals of at
least 1 K)
No
Yes
No
USP-EP error
X
80
X
80
X
80
X
80
No
80
80
Yes
Manual mode active
Download active
No
80
Current simulation
active
Service function active
No
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
0C
X
0C
No
44
80
No
44
80
E152
E153
E154
E155
E156
Endress+Hauser
PCS alarm
Check sensor and
connection.
USP-EP temperature
error
Below lower alarm
threshold for period
exceeding alarm delay
Above upper alarm
threshold for period
exceeding alarm delay
Actual value
undershoots alarm
threshold for longer
Yes
No
No
44
44
Yes
No
No
80
44
Perform manual
comparison measurement
if necessary. Service
sensor and recalibrate.
Yes
No
No
X
X
Yes
No
No
X
X
Yes
No
No
X
83
Diagnostics and troubleshooting
Error
No.
Liquisys M CLM223/253
Display
Tests/remedial action
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
than the set
permissible maximum
period
E157
E162
E171
E172
E173
X
Actual value exceeds
alarm threshold for
longer than the set
permissible maximum
period
Dosage stop
Flow in main stream
too low or zero
Yes
No
No
X
X
Check settings in the
CURRENT INPUT and
CHECK function groups.
Yes
Restore flow.
Yes
No
No
X
X
No
No
X
X
Switch-off limit for
Check process variables at Yes
current input exceeded sending measuring device.
Change range assignment
Current input < 4 mA if necessary.
Yes
No
No
X
X
No
No
X
X
E174
Current input > 20 mA
Yes
No
No
X
X
1)
8.3
PV = process variable, primary value
Process-specific errors
Use the following table to localize and rectify any errors occurring.
84
Error
Possible cause
Tests/remedial action
Tools, spare parts
Incorrect reading
compared to
comparison
measurement
Device calibrated
incorrectly
Calibrate the device according to
Kap. the "Calibration" section
Calibration solution or cell
certificate
Sensor fouled
Clean sensor
See the "Cleaning of
conductivity sensors"
section
Incorrect temperature
measurement
Check temperature measured
value in measuring device and
reference device
Temperature measuring
device, precision
thermometer
Temperature
compensation incorrect
Check compensation method
(none / ATC / MTC) and
compensation type (linear/
substance/user table)
Please note: the
transmitter has separate
calibration and operating
temperature coefficients
Reference device is
calibrated incorrectly
Calibrate reference device or use
verified device
Calibration solution,
Operating Instructions of
reference device
Incorrect ATC setting in
reference device
Compensation method and
compensation type must be
identical on both devices.
Operating Instructions of
reference device
Polarization errors
Use suitable sensor:
• Use larger cell constant
• Use graphite instead of
stainless steel (check
resistance)
Measuring range tables
e.g. in SI "Conductivity" or
technical data of
conductivity sensors
Endress+Hauser
Liquisys M CLM223/253
Diagnostics and troubleshooting
Error
Implausible
measured values
in general:
• Continuous
measured value
overflow
• Measured value
constantly 000
• Measured value
too low
• Measured value
too high
• Measured value
frozen
• Current output
value not as
expected
Possible cause
Tests/remedial action
Tools, spare parts
Incorrect line resistance
in field A6
Enter correct value
CYK71: 165 Ω/km
Short-circuit/moisture in
sensor
Check sensor
See the "Checking
inductive conductivity
sensors" section.
Short-circuit in cable or
socket
Check cable and socket
See the "Connecting lines
and junction boxes"
section.
Disconnection in sensor
Check sensor
See the "Checking
inductive conductivity
sensors" section.
Disconnection in cable or
socket
Check cable and socket
See the "Connecting lines
and junction boxes"
section.
Incorrect cell constant
setting
Check cell constant
Sensor nameplate or
certificate
Incorrect output
assignment
Check assignment of measured
value to current signal
Incorrect output function
Check preset value (0-20 / 4 -20
mA) and curve shape (linear /
table)
Air pockets in assembly
Check assembly and installation
position
Grounding short at or in
device
Measure in insulated device
Plastic vessel, calibration
solutions
Transmitter module
defective
Check with new module
See the "Spare parts"
section
Device in impermissible
Switch off device and switch it on
operating condition (does again
not respond when key
pressed)
Incorrect
conductivity
measured value in
the process
EMC problem: if this
persists, check the
grounding, shields and
line routing or have
checked by E+H Service.
No/incorrect temperature ATC: select type of compensation;
compensation
if linear, set suitable coefficients.
MTC: set process temperature.
Incorrect temperature
measurement
Check temperature measured
value.
Bubbles in medium
Suppress formation of bubbles by:
• Gas bubble trap
• Creating counterpressure
(orifice plate)
• Measurement in bypass
Polarization effects (only
with conductive sensors)
Use suitable sensor:
• Use larger cell constant
• Use graphite instead of
stainless steel (check
resistance)
Reference device,
thermometer
Measuring range tables
e.g. in SI "Conductivity" or
technical data of
conductivity sensors
Flow rate too high (can
Reduce flow rate or select less
lead to bubble formation) turbulent mounting location.
Endress+Hauser
Voltage potential in
medium (only for
conductive)
Ground medium close to sensor.
Problem mainly occurs in
plastic lines and tanks
Sensor fouling or buildup
on sensor
Clean the sensor (see the
For heavily contaminated
"Cleaning the conductivity sensors" media:
section).
Use spray cleaning
Incorrect line resistance
in field A6
Enter correct value
CYK71: 165 Ω/km
85
Diagnostics and troubleshooting
Error
Possible cause
Tests/remedial action
Tools, spare parts
Incorrect
temperature value
Incorrect sensor
connection
Check connections using wiring
diagram. Three-wire connection
always required.
Wiring diagram in
"Electrical connection"
section
Measuring cable
defective
Check cable for interruptions/
short-circuit/shunt.
Ohmmeter
Incorrect sensor type
Set type of temperature sensor at
the device (field B1).
Interference on
measuring cable
Connect cable shield as per wiring
diagram
See the "Electrical
connection" section
Interference on signal
output cable
Check cable routing, possibly
route cable separately
Route signal output and
measuring input lines
separately
Interference potential in
medium
Eliminate source of interference
or ground medium as close as
possible to sensor.
Electromagnetic
interference on signal
lines with conductive
sensors
Use shielded cables and ground
the cable shield
Fluctuations in
measured value
Controller or timer No relay module
cannot be
available
activated
Install LSR1-2 or LSR1-4 module
Controller/limit
contact does not
work
Controller switched off
Activate controller
See fields R2xx
Controller in operating
mode "Manual off"
Select "Auto" or "Manual on" mode
Keyboard, REL key
Pickup delay setting too
long
Switch off or shorten pickup delay See fields R2xx
time
"Hold" function active
“Auto hold” for calibration,
“Hold” input activated;
“Hold” active via keyboard
See fields S2 to S5
Controller in operating
mode "Manual on"
Select "Auto" or "Manual off" mode
Keyboard, REL and AUTO
keys
Dropout delay setting too
long
Shorten dropout delay time
See fields R2xx
Control loop interruption
Check measured value, current
output value, actuators, chemical
supply
No conductivity
current output
signal
Cable disconnected or
short-circuited
Disconnect cable and measure
directly at device
Output defective
See the "Device-specific errors"
section
Fixed conductivity
current output
signal
Current simulation active
Switch off simulation.
See field O3
Impermissible operating
state of processor system
Disconnect line voltage for
approx. 10 seconds
Possibly EMC problem: if
problem persists, check
grounding and wire
routing.
Incorrect current
output signal
Incorrect current
assignment
Check current assignment: 0–20
mA or 4–20 mA?
Field O311
Total load in the current
loop too high (> 500 Ω)
Disconnect output and measure
directly at device
mA meter for 0–20 mA
DC
EMC (interference
coupling)
Disconnect both output cables and Use shielded cables,
measure directly at device
ground shields at both
ends, where necessary
route cable in another
cable duct
Controller/limit
contact works
continuously
86
Liquisys M CLM223/253
mA meter 0–20 mA
Endress+Hauser
Liquisys M CLM223/253
Diagnostics and troubleshooting
Error
Possible cause
Tests/remedial action
Current output
table is not
accepted
Value interval too small
Select practical intervals
No temperature
output signal
Device does not have a
second current output
Check version using nameplate, if
necessary replace the LSCH-x1
module
Device with PROFIBUSPA
PA device has no current output!
Chemoclean
function not
available
No relay module (LSR1x) installed or only
LSR1-2 available
Additional function not
enabled
Install LSR1-4 module.
Chemoclean is enabled using the
release code supplied by the
manufacturer in the Chemoclean
retrofit kit.
To check the version, see the
nameplate
Plus Package
functions not
available
Plus Package not enabled • For Plus Package retrofit: code For a detailed description,
(enable by entering a
is supplied by E+H → enter this see the "Replacement of
code which depends on
code.
central module" section.
the serial number and
• After replacing a defective
which is supplied by E+H
LSCH/LSCP module: first enter
when a Plus Package is
device serial number manually
ordered)
(see nameplate), then enter the
existing code number.
No HART
communication
No HART central module
Verify using nameplate: HART = xxx5xx and -xxx6xx
No or incorrect DD
(device description)
For further information, see
BA00208C/07/EN, "HART field
communication with Liquisys
CxM223/253”
HART interface missing
Tools, spare parts
LSCH-x2 module, see the
"Spare parts" section
LSR1-4 module, see the
"Spare parts" section
Upgrade to LSCH-H1 / H2
Current output < 4 mA
Load too small (must be
> 230 Ω)
HART receiver (e.g. FXA
191) not connected via
load but via power supply
Incorrect device address
(addr. = 0 for single
operation, addr. > 0 for
multidrop operation)
Line capacitance too high
Interference on line
No PROFIBUS
communication
Several devices set to
same address
Assign addresses correctly
No communication
possible if several devices
set to the same address
No PA/DP central
module
Verify using the nameplate: PA =
-xxx3xx /DP = xxx4xx
Upgrade to LSCP module,
see the "Spare parts"
section
Incorrect device software
version (without
PROFIBUS)
For further information, see
BA00209C/07/EN "PROFIBUS
PA/DP - Field communication for
Liquisys CxM223/253".
Information about
PROFIBUS configuration is
provided in Technical
Information TI00260F,
while detailed information
about instrumentation
and accessories is provided
in Operating Instructions
BA00198F
With Commuwin (CW) II:
CW II version and device
software version
incompatible
No or incorrect DD/DLL
Incorrect baud rate
setting for segment
coupler in DPV-1 server
Endress+Hauser
87
Diagnostics and troubleshooting
Liquisys M CLM223/253
Error
Possible cause
Tests/remedial action
Tools, spare parts
Bus user (master) has
wrong address or address
assigned twice
Bus user (slave) has
wrong address
Bus line not terminated
Line problems (too long,
cross-section too small,
not shielded, shield not
grounded, wires not
twisted)
Bus voltage too low
The voltage at the device's PA/DP
(Bus voltage typ. 24 V DC connector must be at least 9 V
for non-Ex)
8.4
Device-specific errors
The following table helps you during the diagnosis and points to any spare parts required.
Depending on the degree of difficulty and the measuring equipment present, diagnosis is
carried out by:
• Trained operator personnel
• The user's trained electrical technicians
• Company responsible for system installation/operation
• Endress+Hauser Service
Information on the exact spare part designations and on how to install these parts can be
found in the "Spare parts" section.
88
Error
Possible cause
Tests/remedial action
Execution, tools, spare
parts
Device cannot be
operated, display
value 9999
Operation locked
Press CAL and MINUS keys
simultaneously.
See the "Key functions"
section
Display dark, no
light-emitting
diode active
No line voltage
Check whether line voltage is
present
Electrical technician / e.g.
multimeter
Supply voltage
wrong/too low
Compare actual line voltage
and nameplate data
User (data for energy supply
company or multimeter)
Connection faulty
• Terminal not tightened
• Insulation jammed
• Wrong terminals used
Electrical technician
Device fuse defective
Compare line voltage and the
nameplate data and replace
fuse
Electrical technician/suitable
fuse; see exploded drawing in
the the "Spare parts" section
Power unit defective
Replace power unit, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Central module defective
Replace central module, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Field device: ribbon cable
loose or defective
Check ribbon cable, replace if
necessary
See the "Spare parts" section
Display dark, light- Central module defective
emitting diode
(module: LSCH/LSCP)
active
Replace central module, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Endress+Hauser
Liquisys M CLM223/253
Diagnostics and troubleshooting
Error
Possible cause
Tests/remedial action
Values appear on
display but:
• Display does not
change and / or
• Device cannot
be operated
Device or module in
device not correctly
mounted
Panel-mounted device: reinstall Perform with the aid of the
insert.
installation drawings in the
Field device: remount display
the "Spare parts" section
module
Impermissible operating
system condition
Disconnect line voltage for
approx. 10 seconds
Possibly Possible EMC
problem: if this persists,
check the installation or have
checked by Endress+Hauser
Service
Device gets hot
Voltage wrong/too high
Compare line voltage and
nameplate data
User, electrical technician
Power unit defective
Replace power unit
Diagnosis only by Endress
+Hauser Service
Conductivity/MΩ
measured value
and/or
temperature
measured value
incorrect
Transmitter module
defective (module:
MKIC), please first carry
out tests and take
measures as per the
"Process-specific errors"
section
Measuring input test:
• Connect a resistor instead of
the conductivity sensor
• 100 Ω resistance at
terminals 11/ 12 + 13 =
display 0 °C
If the test is negative: replace
module (note version).
Perform with the aid of the
exploded drawings in the
"Spare parts" section.
Current output,
incorrect current
value
Incorrect adjustment
Check with integrated current
simulation, connect mA meter
directly to current output.
If simulation value incorrect:
adjustment in factory or new
LSCH module required.
If simulation value correct:
check current loop for load
and shunts.
Load too large
Shunt / short to ground
in current loop
Endress+Hauser
Execution, tools, spare
parts
Incorrect mode of
operation
Check whether 0–20 mA or 4–
20 mA is selected.
No current output
signal
Current output stage
defective (only for LSCH
module; LSCP has no
current output)
Check with integrated current
simulation, connect mA meter
directly to current output
If test negative:
Replace central module (note
version)
Additional relays
not working
Field device: ribbon cable
loose or defective
Check ribbon cable seating,
replace cable if required.
See the "Spare parts" section
Only 2 additional
relays can be
triggered
LSR1-2 relay module
with 2 relays is installed
Upgrade to LSR1-4 with 4
relays.
User or Endress+Hauser
Service
Additional
functions (Plus
Package) missing
No or incorrect release
code used
If retrofitting: check whether
the correct serial number was
quoted when ordering the Plus
Package.
Handled by Endress+Hauser
Sales
Incorrect device serial
number saved in LSCH/
LSCP module
Check whether serial number
on the nameplate matches SNR
in LSCH/ LSCP (field S 8).
The serial number of the
device is definitive for the
Plus Package.
Additional
functions (Plus
Package and/or
Chemoclean)
missing after
LSCH/LSCP
module
replacement
Replacement modules
LSCH or LSCP have the
device serial number
0000 when they leave
the factory. The Plus
Package or Chemoclean
are not enabled on
leaving the factory.
In the case of LSCH/LSCP with
SNR 0000, a device serial
number can be entered once in
fields E115 to E117.
Then enter the release codes
for the Plus Package and/or
Chemoclean if necessary.
For a detailed description,
see the "Replacement of
central module" section.
No HART or
PROFIBUS PA/DP
interface function
Incorrect central module
HART: LSCH-H1 or H2 module,
PROFIBUS-PA: LSCP-PA
module,
PROFIBUS-DP: LSCP-DP
module,
see field E112.
Replace central module;
User or Endress+Hauser
Service.
89
Maintenance
Liquisys M CLM223/253
Error
9
Possible cause
Tests/remedial action
Wrong software
SW version, see field E111.
Bus problem
Remove some devices and
repeat the test.
Execution, tools, spare
parts
Contact Endress+Hauser
Service.
Maintenance
LWARNING
Process pressure and temperature, contamination, electrical voltage
Risk of serious or fatal injury
‣ If the sensor has to be removed during maintenance work, avoid hazards posed by
pressure, temperature and contamination.
Make
sure the device is de-energized before you open it.
‣
Power
can be supplied to switching contacts from separate circuits. De-energize these
‣
circuits before working on the terminals.
Take all the necessary precautions in time to ensure the operational safety and reliability
of the entire measuring point.
The maintenance of the measuring point comprises:
• Calibration
• Cleaning the controller, assembly and sensor
• Checking the cables and connections
When performing any work on the device, bear in mind any potential impact this may
have on the process control system or on the process itself.
NOTICE
Electrostatic discharge (ESD)
Risk of damaging the electronic components
‣ Take personal protective measures to avoid ESD, such as discharging beforehand at PE
or permanent grounding with a wrist strap.
For
your own safety, only use genuine spare parts. With genuine parts, the function,
‣
accuracy and reliability are also ensured after maintenance work.
9.1
Maintenance of the entire measuring point
9.1.1
Cleaning the transmitter
Clean the front of the housing using commercially available cleaning agents only.
The front of the housing is resistant to the following in accordance with DIN 42 115:
• Ethanol (for a short time)
• Diluted acids (max. 2% HCl)
• Diluted alkaline solutions (max. 3% NaOH)
• Soap-based household cleaning agents
When performing any work on the device, bear in mind any potential impact this may
have on the process control system or on the process itself.
90
Endress+Hauser
Liquisys M CLM223/253
Maintenance
NOTICE
Prohibited cleaning agents
Damage to the housing surface or housing seal
‣ Never use concentrated mineral acids or alkaline solutions for cleaning.
‣ Never use organic cleaners such as benzyl alcohol, methanol, methylene chloride,
xylene or concentrated glycerol cleaner.
‣ Never use high-pressure steam for cleaning purposes.
9.1.2
Cleaning the conductivity sensors
LCAUTION
Risk of injury from cleaning agents, damage to clothing and equipment
‣ Wear protective goggles and safety gloves.
‣ Clean away splashes on clothes and other objects.
‣ Pay particular attention to the information provided in the safety data sheets for the
chemicals used.
Clean away fouling on the sensor as follows depending on the type of fouling:
• Oily and greasy films:
Clean with grease remover, e.g. alcohol, acetone, possibly hot water and dishwashing
detergent.
• Lime and metal hydroxide buildup:
Dissolve buildup with diluted hydrochloric acid (3 %) and then rinse thoroughly with
plenty of clear water.
• Sulfidic buildup (from flue gas desulfurization or sewage treatment plants):
Use a mixture of hydrochloric acid (3 %) and thiocarbamide (commercially available) and
then rinse thoroughly with plenty of clear water.
• Buildup containing proteins (e.g. food industry):
Use a mixture of hydrochloric acid (0.5 %) and pepsin (commercially available) and then
rinse thoroughly with plenty of clear water.
9.1.3
Simulation of conductive sensors for device testing
You can test the transmitter for conductive conductivity by replacing the measurement
section and temperature sensor with resistors. The accuracy of the simulation will depend
on the accuracy of the resistors.
Temperature
If a temperature offset is not set at the transmitter, the temperature values of the
following table apply:
Pt 100 equivalent resistors
Endress+Hauser
Temperature
Resistance value
-20 °C (-4 °F)
92.13 Ω
-10 °C (14 °F)
96.07 Ω
0 °C (32 °F)
100.00 Ω
10 °C (50 °F)
103.90 Ω
20 °C (68 °F)
107.79 Ω
25 °C (77 °F)
109.73 Ω
50 °C (122 °F)
119.40 Ω
80 °C (176 °F)
130.89 Ω
100 °C (212 °F)
138.50 Ω
200 °C (392 °F)
175.84 Ω
91
Maintenance
Liquisys M CLM223/253
With the Pt 1000 type of temperature sensor, all the resistance values are increased by a
factor of 10.
Attach the temperature equivalent resistor in a three-wire system.
Conductivity
If the cell constant k is set to the value in column 2 of the following table, then the
conductivity values of this table apply.
Otherwise the following applies: Conductivity [mS/cm] = k[cm-1] ⋅ 1 / R[kΩ]
Resistance R
10 Ω
Cell constant k
1
100 mS/cm
cm-1
1000 mS/cm
10
100 Ω
1000 Ω
10 kΩ
1 mS/cm
1 cm-1
10 mS/cm
10 cm-1
100 mS/cm
0.1 cm-1
0.1 mS/cm
1 cm-1
1 mS/cm
10 cm-1
10 mS/cm
0.01 cm-1
1 μS/cm
1 MΩ ⋅ cm
0.1 cm-1
10 μS/cm
100 kΩ ⋅ cm
cm-1
100 μS/cm
cm-1
1 mS/cm
10
1
0.1 μS/cm
10 MΩ ⋅ cm
1 μS/cm
1 MΩ ⋅ cm
10 MΩ
0.01 μS/cm
100 MΩ ⋅ cm
cm-1
0.1 μS/cm
10 MΩ ⋅ cm
cm-1
1 μS/cm
cm-1
0.001 μS/cm
cm-1
0.01 μS/cm
0.01
0.1
10 μS/cm
cm-1
0.01
1
10 kΩ ⋅ cm
cm-1
cm-1
0.1
1 kΩ ⋅ cm
cm-1
0.01
0.1
1 MΩ
Display for MΩ
0.1 cm-1
1
100 kΩ
Display for conductivity
cm-1
100 MΩ ⋅ cm
The MΩ measurement is normally used for pure and ultrapure water and therefore
only makes sense for cell constants k= 0.01 cm-1 or k = 0.1 cm-1.
9.1.4
Simulation of inductive sensors for device testing
The inductive sensor cannot be simulated.
However, the overall system comprising the transmitter and inductive sensor can be tested
using equivalent resistors. Note the cell constant k (e.g. knominal = 1.98 cm-1 for CLS50,
knominal = 5.9 cm-1 for CLS52, knominal = 6.3 cm-1 for CLS54).
For accurate simulation, the actual cell constant used (visible in field C124) must be used
to calculate the display value.
The formula for calculation also depends on the type of sensor:
• CLS50 and CLS52: conductivity reading [mS/cm] = k[cm-1] ⋅1/R[kΩ]
• CLS54: conductivity reading [mS/cm] = k[cm-1] ⋅1/R[kΩ] ⋅ 1.21
92
Endress+Hauser
Liquisys M CLM223/253
Maintenance
Values for simulation with CLS50 at 25 °C (77 °F):
Simulation resistance R
Default cell constant k
Conductivity reading
1.98
cm-1
990 mS/cm
1.98
cm-1
198 mS/cm
1.98
cm-1
19.8 mS/cm
1.98 cm-1
1.98 mS/cm
Simulation resistance R
Default cell constant k
Conductivity reading
10 Ω
6.3 cm-1
520 mS/cm
26 Ω
6.3 cm-1
200 mS/cm
100 Ω
6.3 cm-1
52 mS/cm
260 Ω
6.3 cm-1
20 mS/cm
2.6 kΩ
6.3 cm-1
2 mS/cm
26 kΩ
6.3 cm-1
200 μS/cm
52 kΩ
cm-1
100 μS/cm
2Ω
10 Ω
100 Ω
1 kΩ
Simulation with CLS54 at 25 °C (77 °F):
6.3
Conductivity simulation:
Pull a cable through the sensor opening and then connect it to a decade resistor, for
instance.
9.1.5
Checking conductive sensors
• Measuring surface connection:
The measuring surfaces are directly connected to the connections of the sensor
connector. Check with ohmmeter for < 1 Ω.
• Measuring surface shunt:
A shunt is not permitted between the measuring surfaces. Check with ohmmeter for >
20 MΩ.
• Temperature sensor shunt:
A shunt is not permitted between the measuring surfaces and the temperature sensor.
Check with ohmmeter for > 20 MΩ.
• Temperature sensor:
See the sensor nameplate for information on the type of the temperature sensor being
used.
The sensor can be checked at the sensor connector with an ohmmeter:
– Pt 100 at 25 °C (77 °F) = 109.79 Ω
– Pt 1000 at 25 °C (77 °F) = 1097.9 Ω
– NTC 30 k at 25 °C (77 °F) = 30 kΩ
• Terminal:
For sensors with a terminal connection (CLS12/13) check the assignment of the
terminals to ensure they have not been inadvertently interchanged. Check the tightness
of the terminal screws.
Endress+Hauser
93
Maintenance
Liquisys M CLM223/253
9.1.6
Checking inductive sensors
The following applies to the CLS50, CLS52 and CLS54 sensors.
The sensor cables must be disconnected at the device or junction box for all tests described
here!
• Testing the transmitting and receiving coils:
Perform the measurement at the white and red coaxial cables, between the inner
conductor and shield in each case.
– Ohmic resistance
CLS50/52: approx. 0.5 to 2 Ω
CLS54: approx. 1 to 3 Ω
– Inductance approx. 180 to 500 mH (for 2 kHz, series circuit as equivalent circuit
diagram)
CLS50: approx. 250 to 450 mH
CLS52/54: approx. 180 to 550 mH
• Testing the coil shunt:
A shunt is not permitted between the two sensor coils (from red coax to white coax). The
measured resistance must be > 20 MΩ.
Test with the ohmmeter from the red coax cable to the white coax cable.
• Temperature sensor test:
Use the table in the "Simulation of conductive sensors for device testing" section to check
the Pt 100 / Pt 1000 in the sensor.
Measure between the green and white wires and between the green and yellow wires.
The resistance values must be identical.
• Temperature sensor shunt test:
Shunts are not permitted between the temperature sensor and the coils. Check with
ohmmeter for > 20 MΩ
Measure between the temperature sensor wires (green + white + yellow) and the coils
(red and white coax).
9.1.7
Assembly
Refer to the assembly operating manual for information on servicing and troubleshooting
the assembly. The assembly operating manual describes the procedure for mounting and
disassembling the assembly, replacing the sensors and seals, and contains information on
the material resistance properties, as well as on spare parts and accessories.
9.1.8
Connecting cables and junction boxes
• Use the methods described in chapters "Simulation of conductive/inductive sensors for
device test" to perform a quick functional check from the conductivity sensor (sensor
connector) to the measuring instrument via an extension. The easiest way to connect
resistor decades is with the "Conductivity testing adapter" service kit, order number:
51500629
• Check junction boxes for:
– Moisture (influence at low conductivity or for MΩ measurement, where necessary dry
box, replace seals, insert dehydrating bag)
– Correct connection of all lines
– Connection of the outer shields
– Tightness of the terminal screws
94
Endress+Hauser
Liquisys M CLM223/253
Repair
10
Repair
10.1
Spare parts
Please order spare parts from your local Sales Office. For this purpose, use the order
numbers listed in the "Spare part kits" section.
For safety, you should always provide the following additional data when ordering spare
parts:
• Device order code
• Serial number
• Software version, if possible
You can take the order code and serial number from the nameplate.
The software version is provided in the device software provided that the device processor
system is still working.
For more detailed information on spare parts kits, please refer to the "Spare Part Finding
Tool" on the Internet:
www.endress.com/spareparts_consumables
10.2
Disassembling the panel-mounted device
Please note the effects on the process if the device is taken out of service!
See the exploded drawing for the item numbers.
1.
Disconnect the terminal block (item 420 b) from the rear of the device to de-energize
the device.
2.
Then disconnect the terminal blocks (item 420 a and 430 where applicable) from the
rear of the device. Now you can disassemble the device.
3.
Press in the latches of the end frame (item 340) and remove the frame from the rear.
4.
Release the special screw (item 400) by turning it counter-clockwise.
5.
Remove the entire electronics block from the housing. The modules are only
mechanically connected and can be easily separated:
6.
Simply remove the processor/display module towards the front.
7.
Pull out the brackets of the rear plate (item 320) slightly.
8.
Now you can remove the side modules.
9.
Remove the conductivity transmitter (item 240) as follows:
10. Using a fine wire cutter, nip off the heads of the synthetic distance holders.
11. Then remove the module from above.
Assembly is the reverse of the disassembly sequence. Tighten the special screw fingertight without using a tool.
Endress+Hauser
95
Repair
Liquisys M CLM223/253
420a
345
420b
340
400
240
15/20
40 ... 91
330
320
310
430
290/300
15
A
230V
B
115V
100V
A0008913
39
96
Exploded drawing of panel-mounted device
Endress+Hauser
Liquisys M CLM223/253
Repair
The exploded drawing contains the components and spare parts of the panel-mounted
device. You can take the spare parts and the corresponding order number from the
following section using the item numbers.
Item
Kit description
Name
Function/contents
Order no.
15
Power unit (main module)
LSGA
100/115/230 V AC
51500317
20
Power unit (main module)
LSGD
24 V AC + DC
51500318
40
Central module (contr.),
conductive
LSCH-S1
1 current output
51501210
50
Central module (contr.),
conductive
LSCH-S2
2 current outputs
51501212
60
Central module (contr.),
conductive
LSCH-H1
1 current output + HART
51501213
70
Central module (contr.),
conductive
LSCH-H2
2 current outputs + HART
51501214
80
Central module (contr.),
conductive
LSCP-PA
PROFIBUS PA/no current output
51501215
90
Central module (contr.),
conductive
LSCP-DP
PROFIBUS DP/no current output
51502502
90
Kit for CLM2x3
conductivity central
module, conductive,
PROFIBUS DP
LSCP-DP
PROFIBUS DP central module
Relay module + 2 relays
Current inp. + DP terminals
Hardware version 2.10 and higher
71134726
41
Central module (contr.),
inductive
LSCH-S1
1 current output
51501216
51
Central module (contr.),
inductive
LSCH-S2
2 current outputs
51501218
61
Central module (contr.),
inductive
LSCH-H1
1 current output + HART
51501219
71
Central module (contr.),
inductive
LSCH-H2
2 current outputs + HART
51501220
81
Central module (contr.),
inductive
LSCP-PA
PROFIBUS PA/no current output
51501221
91
Central module (contr.),
inductive
LSCP-DP
PROFIBUS DP/no current output
51502501
91
Kit for CLM2x3
conductivity central
module, inductive,
PROFIBUS DP
LSCP-DP
PROFIBUS DP central module
Relay module + 2 relays
Current inp. + DP terminals
Hardware version 2.10 and higher
71134727
240
Conductivity transmitter
(hazardous area version)
MKIC
Conductivity + temperature input
71161137
Conductivity transmitter
MKIC
Conductivity + temperature input
71161133
290
Relay module
LSR1-2
2 relays
51500320
290
Relay module
LSR2-2i
2 relays + 4-20 mA current input
51504304
290
Kit for Cxm2x3 relay
module
PROFIBUS DP
LSR2-DP
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134732
300
Relay module
LSR1-4
4 relays
51500321
300
Relay module
LSR2-4i
4 relays + 4-20 mA current input
51504305
310
Side panel
Kit with 10 parts
51502124
Rear plate, side panel, end frame,
special screw
51501076
310, 320, Housing mechanical parts
340, 400
Endress+Hauser
97
Repair
Liquisys M CLM223/253
Item
Kit description
330, 400
Function/contents
Order no.
Housing module
Housing with front membrane, sensory
tappets, seal, special screw, tensioning
dogs, connection plates and nameplates
51501075
340
End frame
PROFIBUS-DP
Rear frame for PROFIBUS DP, with Dsubmin plug connector
51502513
345
Grounding terminal strip
PE and shielding terminals
51501086
420a,
420b
Terminal strip set
Complete terminal strip set, standard +
HART
51501203
420a,
420b
Terminal strip set
Complete terminal strip set
PROFIBUS PA
51502126
420a,
420b
Terminal strip set
Complete terminal strip set
PROFIBUS DP
51502493
Terminal strip
Terminal strip for relay module
51501078
A
Fuse
Part of power unit, item 15
B
Choice of line voltage
Position of jumper on power unit, item
15 depending on line voltage
430
10.3
Name
Disassembling the field device
Please note the effects on the process if the device is taken out of service!
See the exploded drawing for the item numbers.
You require the following tools to disassemble the field device:
• Standard set of screwdrivers
• Torx screwdriver, size TX 20
Proceed as follows to disassemble the field device:
1.
Open and remove the cover of the connection compartment (item 420).
2.
Disconnect the supply terminal (item 470) to de-energize the device.
3.
Open the display cover (item 410) and release the ribbon cables (item 310/320) on
the central module side (item 40 to 91) .
4.
To remove the central module (item 40) release the screw in the display cover (item
450 b).
5.
Proceed as follows to remove the electronics box (item 330):
6.
Turn the screws in the housing base (item 450 a) by two revolutions to release them.
7.
Then push the entire box backwards and remove it from above while making sure
that the module locks do not open.
8.
Release the ribbon cables (item 310/320).
9.
Bend the module locks out and remove the modules.
10. To remove the docking module (item 340) remove the screws in the housing base
(item 450 c) and remove the entire assembly from above.
11. To remove the conductivity transmitter (item 240) nip off the heads of the synthetic
distance sleeves using a fine wire cutter.
12. Then remove the module from above.
98
Endress+Hauser
Liquisys M CLM223/253
Repair
To assemble, carefully push the modules into the guide rails of the electronics box and let
them engage in the side box noses.
It is not possible to mount the modules incorrectly. Modules inserted in the electronics
box incorrectly are not operable since the ribbon cables cannot be connected.
Make sure the cover seals are intact to guarantee IP 65 ingress protection.
Endress+Hauser
99
Repair
Liquisys M CLM223/253
A
B
Pos. 10
Netzteil 100 – 230 V AC
15
C
Sicherung
410
230 V
370
D
460b
115 V
100 V
40 ... 91
450b
330
450a
310/320
400
460a
240
430
420
15/20
290/300
403
340
480
450c
470
A0008916
40
100
Field device exploded drawing
Endress+Hauser
Liquisys M CLM223/253
Repair
The exploded drawing contains the components and spare parts of the field device. You
can take the spare parts and the corresponding order number from the following section
using the item numbers.
Item
Endress+Hauser
Kit description
Name
Function/contents
Order no.
15
Power unit (main module)
LSGA
100/115/230 V AC
51500317
20
Power unit (main module)
LSGD
24 V AC + DC
51500318
40
Central module (contr.),
conductive
LSCH-S1
1 current output
51501210
50
Central module (contr.),
conductive
LSCH-S2
2 current outputs
51501212
60
Central module (contr.),
conductive
LSCH-H1
1 current output + HART
51501213
70
Central module (contr.),
conductive
LSCH-H2
2 current outputs + HART
51501214
80
Central module (contr.),
conductive
LSCP-PA
PROFIBUS PA/no current output
51501215
90
Central module (contr.),
conductive
LSCP-DP
PROFIBUS DP/no current output
51502502
90
Kit for CLM2x3 conductivity
central module, conductive,
PROFIBUS DP
LSCP-DP
PROFIBUS DP central module
Relay module + 2 relays
Current inp. + DP terminals
Hardware version 2.10 and higher
71134726
41
Central module (contr.),
inductive
LSCH-S1
1 current output
51501216
51
Central module (contr.),
inductive
LSCH-S2
2 current outputs
51501218
61
Central module (contr.),
inductive
LSCH-H1
1 current output + HART
51501219
71
Central module (contr.),
inductive
LSCH-H2
2 current outputs + HART
51501220
81
Central module (contr.),
inductive
LSCP-PA
PROFIBUS PA/no current output
51501221
91
Central module (contr.),
inductive
LSCP-DP
PROFIBUS DP/no current output
51502501
91
Kit for CLM2x3 conductivity
central module, inductive,
PROFIBUS DP
LSCP-DP
PROFIBUS DP central module
Relay module + 2 relays
Current inp. + DP terminals
Hardware version 2.10 and higher
71134727
240
Conductivity transmitter
(hazardous area version)
MKIC
Conductivity + temperature input
71161137
Conductivity transmitter
MKIC
Conductivity + temperature input
71161133
290
Relay module
LSR1-2
2 relays
51500320
290
Relay module
LSR2-2i
2 relays + 4-20 mA current input
51504304
290
Kit for Cxm2x3 relay module
PROFIBUS DP
LSR2-DP
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134732
300
Relay module
LSR1-4
4 relays
51500321
300
Relay module
LSR2-4i
4 relays + 4-20 mA current input
51504305
370, 410, Complete housing cover
420, 430
Display cover, hinges, connection
compartment cover, front membrane
51501068
400, 480
Base, threaded joint
51501072
Housing base (mechanics)
101
Repair
Liquisys M CLM223/253
Item
Kit description
Name
Function/contents
Order no.
330, 340, Inner housing fittings
450
Docking module, empty electronics
box, small parts
51501073
310, 320
Ribbon cable lines
2 ribbon cable lines
51501074
430
Hinges
2 pairs of hinges
51501069
470
Terminal strip power supply
2-pin terminal strip
51501079
420a,
420b
Terminal strip set
Complete terminal strip set
PROFIBUS DP
51502493
403
PE terminal strip
PE and shielding terminals
51501087
A
Electronics box with relay
module LSR-1 (bottom) and
power unit LSGA/LSGD (top)
B
Fuse also accessible if
electronics box installed
C
Fuse
Part of power unit, item 15
D
Choice of line voltage
Position of jumper on power unit,
item 15 depending on line voltage
10.4
Replacing the central module
Generally, when a central module has been replaced, all data which can be changed
are set to the factory setting.
If possible, note the customized settings of the device, such as:
• Calibration data
• Current assignment, main parameter and temperature
• Relay function selections
• Limit value/controller settings
• Cleaning settings
• Monitoring functions
• Interface parameters
Proceed as described below if a central module is replaced:
1.
Disassemble the device as explained in the "Dismantling the panel-mounted
instrument" or "Dismantling the field instrument" section.
2.
Use the part number on the central module to check whether the new module has
the same part number as the previous module.
3.
Reassemble the device with the new module.
4.
Put the device back into operation and check the basic functions (e.g. measured value
and temperature display, operation via keyboard).
5.
Read the serial number (“ser-no.”) off the nameplate of the device (e.g.
6A345605G00) and enter this number in fields E115 (1st digit = year, one-digit (6
in the example)), E116 (2nd digit: month, one-digit (A in the example)), E117 (digits
3-6 cons. number, four-digit (3456 in the example)).
In the field E118, the complete number is displayed again so you can check it is
correct.
You can only enter the serial number for new modules with the serial number 0000.
This can only be done once! For this reason, make sure the number entered is correct
before you press ENTER to confirm!
If an incorrect code is entered, the additional functions are not enabled. An incorrect
serial number can only be corrected at the factory!
102
Endress+Hauser
Liquisys M CLM223/253
Repair
1.
Press ENTER to confirm the serial number or cancel the entry to enter the number
again.
2.
If available, enter the release codes for the Plus Package and/or Chemoclean in the
"Service" menu.
3.
Check the Plus Package release (e.g. by opening the function group CHECK / Code P)
or the Chemoclean function.
4.
Make the customized device settings again.
10.5
Return
The product must be returned if repairs or a factory calibration are required, or if the
wrong product was ordered or delivered. As an ISO-certified company and also due to legal
regulations, Endress+Hauser is obliged to follow certain procedures when handling any
returned products that have been in contact with medium.
To ensure swift, safe and professional device returns, please read the return procedures
and conditions at www.endress.com/support/return-material.
10.6
Disposal
The device contains electronic components and must therefore be disposed of in
accordance with regulations on the disposal of electronic waste.
Observe the local regulations.
Endress+Hauser
103
Accessories
Liquisys M CLM223/253
11
Accessories
11.1
Sensors
11.1.1
Sensors with conductive measurement of conductivity
Condumax CLS12
• Conductive conductivity sensor
• For pure water, Ex and high-temperature applications
• Product Configurator on the product page: www.endress.com/CLS12
Technical Information TI00082C
Condumax CLS13
• Conductive conductivity sensor
• For pure water, Ex and high-temperature applications
• Product Configurator on the product page: www.endress.com/CLS13
Technical Information TI00083C
Condumax CLS15
• Conductive conductivity sensor
• For pure water applications, ultrapure water applications and Ex applications
• Product Configurator on the product page: www.endress.com/CLS15
Technical Information TI00109C
Condumax CLS16
• Hygienic, conductive conductivity sensor
• For pure water applications, ultrapure water applications and Ex applications
• With EHEDG and 3A approval
• Product Configurator on the product page: www.endress.com/CLS16
Technical Information TI00227C
Condumax CLS19
• Cost-effective, conductive conductivity sensor
• For applications with pure and ultrapure water
• Product Configurator on the product page: www.endress.com/CLS19
Technical Information TI00110C
Condumax
• Two-electrode sensor in plug-in head version version
• Product Configurator on the product page: www.endress.com/CLS21
Technical Information TI00085C
11.1.2
Sensors with inductive measurement of conductivity
Indumax CLS50
• High-durability inductive conductivity sensor
• For standard and hazardous area applications
• Product Configurator on the product page: www.endress.com/cls50
Technical Information TI00182C
104
Endress+Hauser
Liquisys M CLM223/253
Accessories
Indumax CLS52
• Inductive conductivity sensor
• Short response times for the food industry
• Product Configurator on the product page: www.endress.com/CLS52
Technical Information TI00167C
Indumax CLS54
• Inductive conductivity sensor
• For standard and hazardous area applications, available with hygienic design for food,
beverages, pharmaceuticals and biotechnology
• Product Configurator on the product page: www.endress.com/CLS54
Technical Information TI00400C
11.2
Connection accessories
Measuring cable CYK71
• Unterminated cable for connecting analog sensors and for extending sensor cables
• Sold by the meter, order numbers:
– Non-Ex version, black: 50085333
– Ex-version, blue: 50085673
Measuring cable CLK6
• Extension cable for inductive conductivity sensors, for extension via VBM junction box
• Sold by the meter, order number: 71183688
VBM
• Junction box for cable extension
• 10 terminal strips
• Cable entries: 2 x Pg 13.5 or 2 x NPT ½"
• Material: aluminum
• Degree of protection: IP 65
• Order numbers
– Cable entries Pg 13.5 : 50003987
– Cable entries NPT ½": 51500177
11.3
Installation accessories
CYY101
• Weather protection cover for field devices
• Absolutely essential for field installation
• Material: stainless steel 1.4301 (AISI 304)
• Order No. CYY101-A
270 (10.6)
320 (12.6)
300 (11.8)
A0024627
41
Endress+Hauser
Dimensions in mm (inch)
105
Accessories
Liquisys M CLM223/253
Flexdip CYH112
• Modular holder system for sensors and assemblies in open basins, channels and tanks
• For Flexdip CYA112 water and wastewater assemblies
• Can be affixed anywhere: on the ground, on the capstone, on the wall or directly onto
railings.
• Stainless steel version
• Product Configurator on the product page: www.endress.com/cyh112
Technical Information TI00430C
30 (1.18)
Ø max. 60 (2.36)
M6
60 (2.36)
90 (3.54)
70 (2.76)
Ø 8 (0.31)
90 (3.54)
70 (2.76)
Ø 8 (0.31)
Post mounting kit
• For securing the field housing to horizontal and vertical posts and pipes
• Material: stainless steel 1.4301 (AISI 304)
• Order No. 50086842
Ø 6 (0.24)
70 (2.76)
90 (3.54)
A0024660
42
11.4
Dimensions in mm (inch)
Software and hardware add-ons
The add-ons can only be ordered by quoting the serial number of the device in question.
• Plus Package
Order No. 51500385
• Chemoclean function (requires four-relay card)
Order No. 51500963
• Two-relay card
Order No. 51500320
• Four-relay card
Order No. 51500321
• Two-relay card with current input
Order No. 51504304
• Four-relay card with current input
Order No. 51504305
106
Endress+Hauser
Liquisys M CLM223/253
Accessories
11.5
Calibration solutions
Conductivity calibration solutions CLY11
Precision solutions referenced to SRM (Standard Reference Material) by NIST for qualified
calibration of conductivity measuring systems in accordance with ISO 9000
CLY11-B, 149.6 μS/cm (reference temperature 25 °C (77 °F)), 500 ml (16.9 fl.oz)
Order No. 50081903
Technical Information TI00162C
Endress+Hauser
107
Technical data
Liquisys M CLM223/253
12
Technical data
12.1
Input
Measured variables
Conductivity
Resistivity
Temperature
Measuring range
Conductivity (conductive)
Conductivity (inductive)
Resistance
Concentration
Temperature
0 to 600 mS/cm (uncompensated)
0 to 2000 mS/cm (uncompensated)
0 to 200 MΩcm
0 to 9999 (%, ppm, mg/l, TDS)
-35 to +250 °C (can also be displayed in °F)
Cell constant
Configurable cell constant
k = 0.0025 to 99.99 cm-1
Connectable temperature
sensors
Pt 100, Pt 1000, NTC 30K
Measuring frequency
Conductivity, resistance (conductive) 170 Hz to 2 kHz
Conductivity (inductive)
2 kHz
Binary inputs
Voltage
Current consumption
Current input
4 to 20 mA, galvanically isolated
10 to 50 V
Max. 10 mA
Load: 260 Ω for 20 mA (voltage drop 5.2 V)
12.2
Output signal
Output
HART
Signal encoding
Frequency Shift Keying (FSK) + 0.5 mA via current output signal
Data transmission rate
1200 baud
Galvanic isolation
Yes
PROFIBUS PA
108
Signal encoding
Manchester Bus Powered (MBP)
Data transmission rate
31.25 kBit/s, voltage mode
Galvanic isolation
Yes (IO modules)
Endress+Hauser
Liquisys M CLM223/253
Technical data
PROFIBUS DP
Signal encoding
RS485
Data transmission rate
9.6 kBd, 19.2 kBd, 93.75 kBd, 187.5 kBd, 500 kBd, 1.5 MBd
Galvanic isolation
Yes (IO modules)
Signal on alarm
2.4 or 22 mA in the event of an error
Load
Max. 500 Ω
Transmission range
Conductivity
Resistivity
Concentration
actuating variable
Temperature
Signal resolution
Max. 700 digits/mA
Minimum turndown of
output signal
Conductivity
Measured value 0 to 1.999 μS/cm
Measured value 0 to 19.99 μS/cm
Measured value 20 to 199.9 μS/cm
Measured value 200 to 1999 μS/cm
Measured value 2 to 19.99 mS/cm
Measured value 20 to 2000 mS/cm
Resistance
Measured value 0 to 199.9 kΩcm
Measured value 200 to 1999 kΩcm
Measured value 2 to 19.99 MΩcm
Measured value 20 to 200 MΩcm
Concentration
Temperature
Configurable
Configurable
Configurable
Configurable
Configurable
0.2 μS/cm
2 μS/cm
20 μS/cm
200 μS/cm
2 mS/cm
20 mS/cm
20 kΩcm
200 kΩcm
2.0 MΩcm
20 MΩcm
No minimum turndown
15 °C
Separation voltage
Max. 350 VRMS / 500 V DC
Auxiliary voltage output
Output voltage
Output current
15 V ± 0.6 V
Max. 10 mA
Contact outputs
Switching current with ohmic load (cos φ = 1)
Switching current with inductive load (cos φ =
0.4)
Switching voltage
Switching power with ohmic load (cos φ = 1)
Switching power with inductive load (cos φ =
0.4)
Max. 2 A
Max. 2 A
Pickup/dropout delay
0 to 2000 s
Limit contactors
Endress+Hauser
Max. 250 V AC, 30 V DC
Max. 500 VA AC, 60 W DC
Max. 500 VA AC, 60 W DC
109
Technical data
Controller
Liquisys M CLM223/253
Function (configurable)
Controller behavior
Control gain Kp
Integral action time Tn
Derivative action time Tv
Period length for pulse length controller
Frequency for pulse frequency controller
Basic load
Alarm
Function (switchable)
Alarm threshold adjustment range
Alarm delay
Monitoring time for lower limit violation
Monitoring time for upper limit violation
Protocol-specific data
Pulse length/pulse frequency controller,
continuous controller
P, PI, PD, PID, basic load dosing
0.01 to 20.00
0.0 to 999.9 min
0.0 to 999.9 min
0.5 to 999.9 s
60 to 180 min-1
0 to 40 % of max. actuating variable
Latching/momentary contact
Conductivity/resistance/concentration/
temperature/USP/EP: entire range
0 to 2000 s
0 to 2000 min
0 to 2000 min
HART
Manufacturer ID
11h
Device type
0092h (inductive measurement), 0093h
(conductive measurement)
Transmitter-specific revision
0001h
HART version
5.0
Device description files (DD)
www.endress.com/hart
HART load (communication resistor)
250 Ω
Device variables
None (only dynamic variables PV and SV)
Supported features
-
PROFIBUS PA
Manufacturer ID
11h
Device type
1515h
Device revision
0001h
Profile version
2.0
GSD files
www.endress.com/profibus
GSD version
110
Output values
Primary value, temperature
Input variables
PCS display value
Supported features
Device lock: The device can be locked
using the hardware or software.
Endress+Hauser
Liquisys M CLM223/253
Technical data
PROFIBUS DP
Manufacturer ID
11h
Device type
1521h
Profile version
2.0
GSD files
www.endress.com/profibus
GSD version
Endress+Hauser
Output values
Primary value, temperature
Input variables
PCS display value
Supported features
Device lock: The device can be locked
using the hardware or software.
111
Technical data
Liquisys M CLM223/253
12.3
Supply voltage
Power supply via fieldbus
Power supply
Depending on order version:
• 100/115/230 V AC +10/-15 %, 48 to 62 Hz
• 24 V AC/DC +20/-15 %
HART
Supply voltage
Not applicable, active current outputs
Reverse polarity protection
Not applicable, active current outputs
PROFIBUS PA
Supply voltage
9 V to 32 V, max. 35 V
Sensitivity to reverse polarity
No
FISCO/FNICO compliant according to IEC
60079-27
No
PROFIBUS DP
Supply voltage
9 V to 32 V, max. 35 V
Sensitivity to reverse polarity
Not applicable
FISCO/FNICO compliant according to IEC
60079-27
No
Power consumption
Max. 7.5 VA
Mains fuse
Fine-wire fuse, semi-delay 250 V/3.15 A
Circuit breaker
NOTICE
The device does not have a power switch
‣ The customer must provide a protected circuit breaker in the vicinity of the device.
‣ The circuit breaker must be a switch or power switch, and you must label it as the
circuit breaker for the device.
‣ At the supply point, the power supply for the 24 V versions must be isolated from
dangerous live cables by double or reinforced insulation.
Cable specification
Cable length (conductive)
Cable length (inductive)
CYK71 cable resistance
Overvoltage protection
112
Conductivity: max. 100 m (330 ft) (CYK71)
Resistance: max. 15 m (49 ft) (CYK71)
Max. 55 m (180 ft) (CLK5)
165 Ω/km (conductivity measurement)
According to EN 61000-4-5
Endress+Hauser
Liquisys M CLM223/253
Technical data
12.4
Performance characteristics
Reference operating
conditions
Reference temperature:
25 ˚C (77 ˚F)
Measured value resolution
Conductivity
Depends on measured value; 0.001 μS/cm up to a
measured value of 1.999 μS/cm and k ≤ 0.5 cm-1
0.1 °C
Temperature
Maximum measured error
Display
Conductivity
Resistance
Temperature
Signal output
Conductivity
Resistance
Temperature
Max. 0.5 % of measured value ± 4 digits
Max. 0.5 % of measured value ± 4 digits
Max. 1.0 % of measuring range
Max. 0.75 % of current output range
Max. 0.75 % of current output range
Max. 1.25 % of measuring range
Measured errors in accordance with DIN IEC 746 Part 1, at rated operating conditions
Repeatability
Max. 0.2% of measured value ± 2 digits
Temperature compensation
Range
Types of compensation
-35 to +250 °C (-30 to 480 °F)
Uncompensated, linear, NaCl, table
Conductive only: ultrapure water NaCl, ultrapure
water HCl
Offset
Temperature
±5 °C for adjusting the temperature display
12.5
Environment
Ambient temperature
range
-10 to +55 °C (+10 to +130 °F)
Storage temperature
–25 to +65 °C (-10 to +150 °F)
Electromagnetic
compatibility
Interference emission and interference immunity as per EN 61326-1:2006, EN
61326-2-3:2006
Degree of protection
Field device
Panel-mounted device
Electrical safety
As per EN/IEC 61010-1:2010, overvoltage category II for installations up to
2000 m (6500 ft) above MSL
CSA
Device versions with CSA General Purpose approval are certified for indoor use.
Endress+Hauser
IP 65 / integrity according to NEMA 4X
IP 54 (front), IP 30 (housing)
113
Technical data
Liquisys M CLM223/253
Relative humidity
10 to 95%, not condensing
Degree of contamination
The product is suitable for pollution degree 2.
12.6
Mechanical construction
Field device
L x B x D: 96 x 96 x 145 mm (3.78" x 3.78" x 5.71")
Installation depth: approx. 165 mm (6.50 ")
L x B x D: 247 x 170 x 115 mm (9.72" x 6.69" x 4.53")
Weight
Panel-mounted device
Field device
Max. 0.7 kg (1.54 lbs.)
Max. 2.3 kg (5.07 lbs.)
Materials
Panel-mounted device housing
Field housing
Front membrane
Polycarbonate
ABS PC FR
Polyester, UV-resistant
Terminals
Cable cross-section
Max. 2.5 mm2 (14 AWG)
Dimensions
114
Panel-mounted device
Endress+Hauser
Liquisys M CLM223/253
Appendix
13
Endress+Hauser
Appendix
115
Appendix
Liquisys M CLM223/253
Calibration temperature
entry (MTC)
Calibration
InstF
= Installation factor C1 (3)
25.0 °C
–35.0 ... +250.0 °C
Cellc
= Cell constant
Calibration temperature
entry
(if B1 = fixed)
C1 (2)
.
25.0 °C
–35.0 ... +250.0 °C
Function group
CALIBRATION
C131
C121
C1 (1)
C
Entry of correct
conductivity value of
calibration solution
Display of calculated
installation factor
2.10 %/K
0.00 ... 20.00 %/K
.
1.0
0.10 ... 5.0
C132
Entry of a α value of
calibration solution
.
2.10 %/K
0.00 ... 20.00 %/K
Current meas. value C133
0.0 µS/cm ... 9999 mS/cm
Entry of correct
Calibration status
is displayed
C134
C123
0.0025 ... 99.99 1/cm
C124
Calibration status
is displayed
o.k.;
E---
C135
Calibration status
is displayed
Display of calculated
cell constant
C122
Display of residual coupling
(Airset)
Residual coupling
Start calibration
AirS = Airset
Entry of α value of
calibration solution
o.k.;
E---
C125
Store calibration
results
.
0.0 µS
Current meas. value
C112
C111
o.k.
E---
C113
yes; no; new
C114
Edit mode:
Code 22
Read mod:
any code
MEAS. VALUE DISPLAY
Temperature display
Temperature display
Measured value display
Measured value display
in °F
suppressed
Current output in %
Current output in mA
1st error is displayed
Other errors are displayed
(if present)
(up to 10 errors)
Selection of unit
displayed
Display format selection
(if A1 = conc)
Uncompensated
measured value
is displayed
with
TEMPERATURE DISPLAY
in °C
Edit mode:
Code 22
Read mode:
any code
Selection of operation mode
Function group
SETUP 1
cond = conductive
ind = inductive
MOhm = resistance
conc = concentration
A
ppm; mg/l; %; TDS; none
(% only if A1 = conc)
Selection of temperature
Selection of temperature
measurement
Function group
SETUP 2
XX.xx; X.xxx; XXX.x; XXXX
A2
A1
.
Pt100
Pt1k (= Pt 1000)
NTC30 (= NTC 30 kΩ)
fixed
B
A3
Entry of a value
(if B2 = linear)
2.10 %/K
0.00 ... 20.00 %/K
B1
Cont. switch-off
by current input
Function group
CURRENT INPUT
Selection of unit
displayed
Off; Input
0s
ZZ
Delay for cont.
switch-on current input
0s
0 ... 2000 s
Z1
auto; µS/cm; mS/cm; S/cm;
µS/m; mS/m; S/m
autoΩ; kΩ×cm; MΩ×cm; kΩ×m
(omitted if A1 = conc)
A4
0.00 Ω
0.00 ... 99.99 Ω
A6
Enter temperature
difference (omitted
if B1 = fixed)
25.0 °C
–35.0 °C ... +250.0 °C
Display of actual value
–35.0 ... +250.0 °C
Current offset
–5.0 ... 5.0 °C
B4
50%
B5
Switch-off direction
for current input
0 ... 100%
Off; lin = linear
Table option selection
table
read
edit
Z6
Z5
Z4
Characteristic selection
B6
Feedforward control
to PID controller
Low; High
Z3
O3 (3)
Entry of cable
resistance
(if A1 = cond)
Temperature sensor
calibration (omitted
if B1 = fixed)
Switch-off limit value
for current input
0 ... 2000 s
Z2
cond / ind / MOhm
1.000 / 1.98 / 0.01 1/cm
0.0025 ... 99.99 1/cm for
cond; ind; MOhm
A5
Entry of correct
process temperature
(if B1 = fixed)
B3
B2
Delay for cont.
switch-off current input
Entry of cell constant
Entry of number of
value pairs in table
Selection of
value pair in table
1
1 ... 10
1
1 ... number of value pairs
asign
O333
O332
O331
Simulation value entry
sim = simulation
O3 (2)
current value
0 ... 22.00 mA
O321
Select measured variable
for 2nd current output
Current output selection
Function group
CURRENT OUTPUT
lin = linear
Out1; Out2
O3 (1)
Current range selection
Entry of 0/4 mA value
Entry of 20 mA value
4–20 mA; 0–20 mA
0 µS/cm / 0 kΩ·cm /
0 % / 0 °C
entire measuring range
2000 mS/cm / 500 kΩ·cm /
9999 % / 150.0 °C
entire measuring range
°C; mS/cm; Contr
O2
O1
O
Select contact type
Function group
ALARM
Select alarm
delay unit
Stead = steady contact;
Fleet = fleeting contact
F
Switch polarisation
detection on or off
Function group
CHECK
P
off; on
P1
F2
0 s (min)
0 s ... 2000 s (min)
(depends on F2)
Set alarm threshold
Enter alarm delay
Off; Low: High; Lo+Hi;
Lo!; Hi!; LoHi!
P2
0 s (min)
0 … 2000 s (min)
F3
22 mA
2.4 mA
F4
0 µS/cm
0 … 9999 mS/cm
1
1 ... 255
P4
9999 µS/cm
0 … 9999 mS/cm
O313
Set alarm contact
to be effective
yes; no
F6
F5
Set upper
alarm threshold
Set lower
alarm threshold
P3
O312
Error number
selection
Error current
setting
Alarm delay
s; min
F1
O311
Select process
monitoring
P5
Off; AC; CC; AC+CC
AC!; CC!; ACCC!
P6
A0027482-EN
116
Endress+Hauser
Liquisys M CLM223/253
Appendix
Store calibration
results
yes; no; new
C136
Store calibration
results
yes; no; new
C126
Entry of measured
value damping
1 (no damping)
1 ... 60
A7
Entry of
reference temperature
25 °C
–35 ... 250 °C
B7
Feedforward control = 1
at
50%
0 … 100%
Z7
x value entry
(measured value)
y value entry
(current value)
0 µS/cm / 0 kΩ×cm /
0 % / 0 °C
entire measuring range
0.00 mA
0 ... 20.00 mA
entire measuring range
Table status ok
yes; no
O236
O235
O334
Field for customer settings
Activate error current
for previously set
error
no; yes
F7
Automatic start of
cleaning function
no; yes
(not always displayed,
see error messages)
Set max. perm. period
for lower limit exceeded
Set max. perm. period
for upper limit exceeded
60 min
120 min
0 ... 2000 min
P7
0 ... 2000 min
Select “next error”
or return to menu
F8
next = next error;
¬R
F9
Set monitoring
value
P8
1000 µS/cm
0 ... 9999 mS/cm
P9
A0027483-EN
Endress+Hauser
117
Appendix
Liquisys M CLM223/253
Limit contactor
configuration
EP PW
R2 (7)
Function of R2 (7)
Switch off or on
Entry of alarm threshold
(switch-on point)
Pickup delay
entry
Off
On
80 %
0.0 ... 100.0 %
0
0 ... 2000 s
R271
USP
Function of R2 (6)
Switch off or on
Entry of alarm threshold
(switch-on point)
Pickup delay
entry
Off
On
80 %
0.0 ... 100.0 %
0
0 ... 2000 s
R2 (6)
R261
Function of R2 (5)
Switch off or on
Off; On
Clean
= Chemoclean
(only with rel. 3)
R251
R2 (5)
Function of R2 (4)
Switch off or on
Off; On
Timer
LC °C
= T limit contactor
Function group
T
T1
Selection of concentration
curve for calculation of
display value
Function group
CONCENTRATION
Curve 1 ... 4
K
1
1 ... 10
Language selection
SERVICE
ENG; GER
ITA; FRA
ESP; NEL
S
S1
Module selection
Relay
MainB
= mainboard
E1 (4)
E1 (3)
E1 (2)
R242
1.00
0.01 ... 20.00
R232
0.0 min
0.0 ... 999.9 min
Pickup delay
setting
0s
0 ... 2000 s
Select contact
switch-on point
Select contact
switch-off point
Pickup delay
setting
9999 mS/cm / 200 MΩ×cm /
9999 %
entire meas. range
R212
9999 mS/cm / 200 MΩ×cm /
9999 %
entire meas. range
R213
0s
0 ... 2000 s
Entry of temperature
value (x value)
Entry of temperature
coefficient a (y value)
Table status o.k.
0.0 °C
–35.0 ... +250.0 °C
2.10 %/K
0.00 ... 20.00 %/K
T3
T5
T4
Set number of
value pairs
Select value pair
read
edit
1
1 ... 10
1
1 ... number of value pairs
in K4
K3
Manual hold
Software
version
Hardware
version
SW version
HW version
E141
Hardware
version
HW version
Software
version
Hardware
version
SW version
HW version
E121
S4
S3
Serial number
is displayed
E142
K5
0000
0000 ... 9999
Serial number
is displayed
0.0 µS/cm
0.0 ... 9999 mS/cm
K6
S5
0000
0000 ... 9999
S6
E144
Module name
is displayed
E133
Serial number
is displayed
E122
Entry of
uncompensated
conductivity value
Module name
is displayed
E143
E132
T6
Entry of SW upgrade
release code
Chemoclean
Entry of SW upgrade
release code
(plus package)
Entry of
hold dwell period
10 s
0 ... 999 s
SW version
E131
K4
off; on
Software
version
R214
yes; no
Table option
selection
Hold configuration
- none = no hold
- s+c = during setup
and calibration
- CAL = during calibration
- Setup = during setup S2
R224
R223
1
1 ... 4
K2
R234
R233
R222
R221
R244
Entry of integral action time
Tn (0.0 = no I component)
Entry of
control gain Kp
250.0 °C
–35.0 ... +250.0 °C
1
1 ... number of
table value pairs
asign
120 min
1...3600 min
R243
Entry of switch-off
temperature
Off; On
Set minimum
pause time
Selection of table
to be edited
K1
Function group
T2
360 min
1 ... 7200 min
250.0 °C
–35.0 ... +250.0 °C
Selection of table value
read
edit
Pause time setting
30 s
0 ... 999 s
Entry of switch-on
temperature
R211
Entry of number of
table value pairs
Table option selection
ALPHA TABLE
Rinse time setting
R254
R253
Off; On
R1
Function group
10 s
0 ... 999 s
Function of R2 (2)
Switch off or on
R2 (2)
R2 (1)
LC PV
= cond. limit contactor
Entry of cleaning time
20 s
0 ... 999 s
0 µS/cm / 0 kΩ×cm /
0%
entire meas. range
Function of R2 (1)
Switch off or on
Rel1; Rel2; Rel3; Rel4
R
Entry of pre-rinse time
R231
R2 (3)
Select contact to be
configured
RELAY
Start pulse selection
int = internal
ext = external
i+ext = internal + external
i+stp = internal,
suppr. by ext R252
Entry of set point
Off; On; Basic; PID+B
R264
R262
R241
R2 (4)
Function of R2 (3)
Switch off or on
PID controller
R274
R272
E134
Module name
is displayed
E123
E124
Function group
E + H SERVICE
Contr = controller
E1 (1)
E
Function group
INTERFACE
I
Software
version
Hardware
version
SW version
HW version
E111
Module name
is displayed
Serial number
is displayed
E112
E113
E114
Tag description
Entry of address
HART: 0 ... 15
or Profibus 1 ... 126
@@@@@@@@
I1
I2
A0027484-EN
118
Endress+Hauser
Liquisys M CLM223/253
Appendix
Dropout delay
entry
0
0 ... 2000 s
R275
Dropout delay
entry
0
0 ... 2000 s
R265
Entry of post-rinse time
Number of repeat cycles
20 s
0 ... 999 s
0
0 ... 5
R256
R255
Entry of derivative
action time Tv
(0.0 = no D component)
0.0 min
0.0 ... 999.9 min
360 min
1 ... 7200 min
R257
len = pulse length
freq = pulse frequency
curr = current input 2
dir = direct;
inv = inverted
R236
R235
Dropout delay
setting
Setting of
alarm threshold
0s
0 ... 2000 s
250.0 °C
–35.0 ... +250.0 °C
Display of LC status
9999 mS/cm / 200 MΩ×cm /
9999 %
entire meas. range
R216
MAX
MIN
Entry of
associated
temperature value
K7
0.0 °C
–35.0 ... 250.0 °C
S7
Entry of max.
pulse frequency
Entry of min. ON time
tON
Enter basic load
10.0 s
0.5 ... 999.9 s
120 1/min
60 ... 180 1/min
0.3 s
0.1 ... 5.0 s
40%
0 ... 40%
R238
R239
R2310
R2311
R217
Table status o.k.
yes; no
K8
Serial number is
displayed
Order number is
displayed
Entry of
pulse interval
R227
0s
0 ... 2000 s
0.00 %
0 ... 99.99 %
R259
MAX
MIN
Setting of alarm threshold
(as an absolute value)
Entry of associated
concentration value
0
0 ... 9
Display of LC status
Dropout delay
setting
R215
R258
R237
R226
R225
120 min
1 ... R357 min
Selection
Selection of
control characteristic
Number of cleaning
cycles without
cleaning agent
Set minimum pause
time
Set interval between
two cleaning cycles
(pause time)
K9
Reset instrument
(restore default values)
S8
no;
Sens = sensor data;
Facty = factory settings S9
Perform instrument test
no;
Displ = display
S10
A0027485-EN
Endress+Hauser
119
Index
Liquisys M CLM223/253
Index
A
Access codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Alarm contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Automatic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
C
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Calibration solutions . . . . . . . . . . . . . . . . . . . . . . . . 107
Central module replacement . . . . . . . . . . . . . . . . . . 102
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Conductive sensors . . . . . . . . . . . . . . . . . . . . . . . . 93
Inductive sensors . . . . . . . . . . . . . . . . . . . . . . . . . 94
Cleaning
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Concentration Measurement . . . . . . . . . . . . . . . . . . . 70
Conductive sensors
Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Connecting cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Current outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
D
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Device configuration . . . . . . . . . . . . . . . . . . . . . . . . . 37
Device-specific errors . . . . . . . . . . . . . . . . . . . . . . . . . 88
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Disassembling
Field device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Panel-mounted device . . . . . . . . . . . . . . . . . . . . . 95
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
E
E+H Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . 18
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
EP-PW function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
F
Feedforward control . . . . . . . . . . . . . . . . . . . . . . . . . 42
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . 13
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . 15
Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
J
Junction boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
K
Key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
L
Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Maintenance of the entire measuring point . . . . . . . . 90
Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mechanical construction . . . . . . . . . . . . . . . . . . . . . 114
Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
N
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
O
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
P
P(ID) controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Performance characteristics . . . . . . . . . . . . . . . . . . . 113
Post mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . 24
Post-installation check . . . . . . . . . . . . . . . . . . . . . . . 17
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Process-specific errors . . . . . . . . . . . . . . . . . . . . . . . . 84
Product identification . . . . . . . . . . . . . . . . . . . . . . . . . 9
Q
Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
R
Hold function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
H
Relay configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Replacing the central module . . . . . . . . . . . . . . . . . . 102
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
I
S
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Inductive sensors
Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
120
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sensor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Endress+Hauser
Liquisys M CLM223/253
Index
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Setup 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Setup 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Simulation
Conductive sensors . . . . . . . . . . . . . . . . . . . . . . . . 91
Inductive sensors . . . . . . . . . . . . . . . . . . . . . . . . . 92
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Switching on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System error messages . . . . . . . . . . . . . . . . . . . . . . . 81
T
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Temperature compensation with table . . . . . . . . . . . . 69
Trouble shooting instructions . . . . . . . . . . . . . . . . . . 81
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
U
Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
USP function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
W
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Endress+Hauser
121
*71300836*
71300836
www.addresses.endress.com