Det-Tronics Instructions IR Flame Detector X9800
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
IR Flame Detector
X9800
13.1
Rev: 1/16
95-8554
Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . 14
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . 15
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3
oi Plate Removal and Replacement . . . . . . . . . 15
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Periodic Checkout Procedure . . . . . . . . . . . . . . 15
Integral Wiring Compartment . . . . . . . . . . . . . . . 3
Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SIGNAL PROCESSING OPTIONS . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
GENERAL APPLICATION INFORMATION . . . . . . . . 4
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Response Characteristics . . . . . . . . . . . . . . . . . . 4
False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 4
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 18
Factors Inhibiting Detector Response . . . . . . . . . 5
Replacement Parts List . . . . . . . . . . . . . . . . . . . 18
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 5
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . . 18
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 18
Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 6
X9800 Model Matrix . . . . . . . . . . . . . . . . . . . . . 19
Protection Against Moisture Damage . . . . . . . . . 7
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 7
Setting Device Network Addresses
(EQ and EQP Models Only) . . . . . . . . . . . . 13
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 20
APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 23
STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 14
Fire Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . 14
APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 24
APPENDIX D – IECEx APPROVAL . . . . . . . . . . . . . 26
APPENDIX E – EN54 APPROVALS . . . . . . . . . . . . 27
APPENDIX F – ADDITIONAL APPROVALS . . . . . . 28
INSTRUCTIONS
IR Flame Detector
X9800
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X9800 includes the Automatic oi ® (Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
DESCRIPTION
The X9800 Single Frequency IR Flame Detector meets the
most stringent requirements worldwide with advanced
detection capabilities and immunity to extraneous
sources, combined with a superior mechanical design.
The detector is equipped with both automatic and manual
oi test capability. The detector has Division and Zone
explosion-proof ratings and is suitable for use in indoor
and outdoor applications.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
The X9800 housing is available in copper-free aluminum
or stainless steel, with NEMA/Type 4X and IP66/IP67
rating.
OUTPUTS
Relays
The standard output configuration includes fire, fault and
auxiliary relays. Output options include:
––
0 to 20 mA output (in addition to the three relays)
––
––
Pulse output for compatibility with existing Detector
Electronics Corporation (Det-Tronics) controller
based systems (with fire and fault relays)
Eagle Quantum Premier® (EQP) compatible model
––
HART communication
13.1
The standard detector is furnished with fire, fault, and
auxiliary relays. All three relays are rated 5 amperes at
30 Vdc.
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or non-latching
operation.
(no analog or relay outputs)
©Detector Electronics Corporation 2016
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
1
Rev: 1/16
95-8554
The Auxiliary relay has normally open / normally
closed contacts, and is configurable for energized or
de-energized operation, and latching or non-latching
operation.
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions. Table 2 indicates the condition of the
LED for each status.
0 to 20 mA Output
A 0 to 20 mA output is available as an option (in addition
to the three relays). This option provides a 0 to 20 mA dc
current output for transmitting detector status information
to other devices. The circuit can be wired in either an
isolated or non-isolated configuration and can drive
a maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table 1
indicates the detector status conditions represented by
the various current levels. The output is calibrated at the
factory, with no need for field calibration. A model with
relays and 0-20 mA with HART is also available. Refer to
Addendum number 95-8637 for complete details.
Table 2—Detector Status Indicator
Power Fault
2 mA
oi Fault
4 mA
Normal Operation
16 mA
Pre-Alarm
20 mA
Fire Alarm
Green, flashing off for
0.5 sec. every 5 sec.
Low IR Sensitivity
Medium IR Sensitivity
High IR Sensitivity
Very High IR Sensitivity
Quick Fire/TDSA IR Signal
TDSA only IR Signal
Yellow
Red, flashing on for
1 sec. and off for 1 sec.
Steady Red
One Green Flash
Two Green Flashes
Three Green Flashes
Four Green Flashes
One Yellow Flash
Two Yellow Flashes
oi (OPTICAL INTEGRITY)
Automatic oi
The X9800 includes the Automatic oi feature — a
calibrated performance test that is automatically
performed once per minute to verify complete detector
operation capabilities. No testing with an external test
lamp is required. The detector automatically performs
the same test that a maintenance person with a test
lamp would perform — once every minute, 60 times per
hour. However, a successful Automatic oi test does not
produce an alarm condition.
The X9800 signals a fault condition when less than half
of the detection range remains. This is indicated by the
Fault output and is evident by the yellow color of the LED
on the face of the detector. See the "Troubleshooting"
section for further information.
LON/SLC Output
The EQP model is designed for use exclusively with
the Det-Tronics Eagle Quantum Premier system. The
detector communicates with the system controller over
a digital communication network or LON/SLC (Local
Operating Network / Signaling Line Circuit). The LON/
SLC is a fault tolerant, two wire digital communication
network arranged in a loop configuration. Analog and
relay outputs are not available on this model.
13.1
Power On/Normal Man oi
On Power-Up, The LED Flashes in Sequence as Follows,
Indicating Sensitivity and Signal Processing Status
Detector Status
General Fault
Green
Fire (Alarm)
Table 1—Detector Status Conditions Indicated by Current Level
1 mA
Power On/Normal Auto oi
(no fault or fire alarm)
Pre-Alarm/Background IR
An alarm condition will normally over-ride a fault
condition, unless the nature of the fault condition
impairs the ability of the detector to generate or
maintain an alarm output, i.e., loss of operating power.
0 mA
LED Indicator
Fault
NOTE
The output of the 0 to 20 mA current loop is not
monitored by the fault detection circuitry of the
X9800. Therefore, an open circuit on the loop will
not cause the fault relay to change state or the
detector status LED to indicate a fault. The status of
the LED always follows the status of the relays.
Current Level (±0.3 mA)
Detector Status
Magnetic oi / Manual oi
The detector also incorporates both Magnetic oi
(Mag oi) and Manual oi (Man oi) features that provide
the same calibrated test as the Automatic oi, and in
addition actuates the Alarm output to verify operation
for preventive maintenance requirements. These
features can be performed at any time and eliminate
the need for testing with a non-calibrated external test
lamp.
2
95-8554
INTEGRAL WIRING COMPARTMENT
CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
All external wiring to the device is connected within
the integral junction box. The detector is furnished with
four conduit entries, with either 3/4 inch NPT or M25
threads.
The Mag oi test is performed by placing a magnet at the
location marked "MAG OI" on the outside of the detector
(see Figure 2). The Man oi test is accomplished by
connecting the oi lead (terminal 22) to power supply
minus via an external switch. The magnet or switch
must be held in place for a minimum of 6 seconds
to complete the test. Either of these test methods
activates the calibrated IR emitter. If the resulting signal
meets the test criteria, indicating that greater than half
of the detection range remains, the fire alarm output of
the detector is activated. This condition remains until the
magnet is removed or the switch is released, regardless of
whether the detector has been configured for latching or
non-latching operation.
SIGNAL PROCESSING OPTIONS
The X9800 features signal processing options. These
options determine the type of logic that the detector will
use for processing fire signals to customize the X9800
to the application. Two signal processing options are
available for the X9800:
TDSA enabled
––
Both TDSA and Quick Fire enabled (either initiates
fire alarm).
Time Domain Signal Analysis (TDSA)
If less than half of the detection range remains, no alarm
is produced and a fault is generated. The fault indication
can be reset by momentarily applying the Mag oi or
Man oi switch. In this case, the detector's optics should
be cleaned and the oi tests should be repeated. See the
"Cleaning Procedure" section of this manual for details.
The TDSA signal processing technique analyzes the
input signal in real time, requiring the IR signal to flicker
randomly in order to recognize it as a fire condition.
Using TDSA signal processing, the X9800 ignores
regularly chopped blackbody sources (occurring in areas
where moving conveyors and hot objects in proximity
to one another result in a regularly chopped IR signal),
because it looks for a less uniform signal. However, in the
presence of a regularly chopped signal, the detector is
more susceptible to false alarms due to sporadic IR that
functions as a trigger when occurring in conjunction with
the regularly chopped signal.
NOTE
Refer to Appendix A for FM verification of
Det-Tronics’ o i function.
COMMUNICATION
The X9800 is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 supports MODBUS protocol, with
the detector configured as a slave device.
Quick Fire (High Speed)
The Quick Fire (High Speed) feature can be used in
conjunction with the TDSA signal processing method.
This method overrides TDSA requirements in the event
of a sudden and intense signal, such as the result of a
flash fire. When Quick Fire is activated, the detector is
capable of responding to an intense fire signal in less
than 30 milliseconds (0.030 seconds). Using the Quick
Fire feature in conjunction with TDSA signal processing
allows the detector to provide a high speed response to
a large, non-flickering fire (such as in high pressure gas
applications). Additionally, when the Quick Fire feature
and TDSA signal processing are used in conjuction, the
detector maintains an ability to respond to fires that start
very small and grow in size and intensity over time.
For HART communication, connect a HART communicator
across a 250 ohm resistor in the 0-20 mA loop.
NOTE
The EQP model uses LON/SLC communication.
RS-485 and HART communication are not
available on the EQP model.
DATA LOGGING
Data logging capability is also provided. Status
conditions such as normal, power down, general and
oi faults, pre-alarm, fire alarm, time and temperature
are recorded. Each event is time and date stamped,
along with the temperature and input voltage. Event
data is stored in non-volatile memory when the event
becomes active, and again when the status changes.
Data is accessible using the Inspector Connector
accessory, RS-485, or the EQP Controller.
13.1
––
3
95-8554
GENERAL APPLICATION
INFORMATION
EMI/RFI Interference
The X9800 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE marked. It will
not respond to a 5 watt walkie-talkie at distances greater
than 1 foot (0.3 m).
RESPONSE CHARACTERISTICS
Response is dependent on the detector's sensitivity
setting, distance, type of fuel, temperature of the fuel,
and time required for the fire to come to equilibrium. As
with all fire tests, results must be interpreted according to
an individual application.
Non-Carbon Fires
The response of the X9800 is limited to carbonaceous
fuels. It should not be used to detect fires from fuels that
do not contain carbon, such as hydrogen, sulfur, and
burning metals.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics.
Welding
FALSE ALARM SOURCES
It is recommended that the system be bypassed during
welding operations in situations where the possibility of a
false alarm cannot be tolerated. Gas welding mandates
system bypass, since the gas torch is an actual fire. Arc
welding rods can contain organic binder materials in
the flux that burn during the welding operation and are
detectable by the X9800. Welding rods with clay binders
do not burn and will not be detected by the X9800.
However, system bypass is always recommended, since
the material being welded may be contaminated with
organic substances (paint, oil, etc.) that will burn and
possibly cause the X9800 to alarm.
The detector has been designed to ignore steady state
infrared sources that do not have a flicker frequency
characteristic of a fire, however, it should be noted that
if these steady state infrared sources are hot enough
to emit adequate amounts of infrared radiation in the
response range of the IR sensor and if this radiation
becomes interrupted from the view of the detector in a
pattern characteristic of a flickering flame, the IR sensor
can respond.
Any object having a temperature greater than 0° Kelvin
(–273°C) emits infrared radiation. The hotter the object,
the greater the intensity of the emitted radiation. The
closer the infrared source is to the detector, the greater
the potential for a false alarm. The IR sensor can respond
to IR radiation sources that can meet the amplitude and
flicker requirements of the detector such as vibrating hot
objects.
Artificial Lighting
The X9800 should not be located within 3 feet (0.9 m)
of artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
13.1
4
95-8554
IMPORTANT SAFETY NOTES
FACTORS INHIBITING DETECTOR RESPONSE
Windows
WARNING
Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage.
Glass and Plexiglas windows significantly attenuate
radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Det-Tronics for recommendations regarding window
materials that will not attenuate radiation.
Obstructions
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be done
by a properly trained person.
Radiation must be able to reach the detector in order
for it to respond. Care must be taken to keep physical
obstructions out of the line of view of the detector.
Smoke
Smoke will absorb radiation. If accumulations of dense
smoke can be expected to precede the presence of a flame,
then detectors that are used in enclosed areas should be
mounted on the wall approximately 3 feet (0.9 m) from the
ceiling where the accumulation of smoke is reduced.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing detection system tests or maintenance.
Detector Viewing Windows
It is important to keep the detector viewing windows as
free of contaminants as possible in order to maintain
maximum sensitivity. Commonly encountered substances
that can significantly attenuate IR radiation include, but
are certainly not limited to, the following:
––
Dust and dirt buildup
––
Paint overspray
––
Water and ice
CAUTION
The IR flame detectors are to be installed in places
where the risk of mechanical damage is low.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.
13.1
5
95-8554
INSTALLATION
NOTE
The recommended lubricant for threads and
O‑rings is a silicone free grease (p/n 005003001) available from Detector Electronics. Under
no circumstances should a lubricant containing
silicone be used.
•
Dense fog, rain as well as certain gases and vapors
can absorb IR radiation and reduce the sensitivity of
the detector.
•
If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
•
For ATEX/IECEx installations, the X9800 Flame
Detector housing must be electrically connected to
earth ground.
DETECTOR POSITIONING
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:
•
Identify all high risk fire ignition sources.
•
Be sure that enough detectors are used to adequately
cover the hazardous area.
•
Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
•
Verify that all detectors in the system are properly
located and positioned so that any fire hazards are
within both the Field of View (FOV) and detection
range of the detector. Det-Tronics' Q1201C Laser
Aimer is recommended for establishing the detector's
FOV. Refer to Appendix A for specific information
regarding detector range and FOV.
•
The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain (see
Figure 1). The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.
•
DETECTOR ORIENTATION
Refer to Figure 2 and ensure that the oi plate will be
oriented as shown when the X9800 is mounted and
sighted. This will ensure proper operation of the oi
system and will also minimize the accumulation of
moisture and contaminants between the oi plate and the
viewing windows.
IMPORTANT
If removed, the o i plate must be securely
tightened to ensure proper operation of the oi
system (40 oz./inches [28.2 N . cm] recommended).
oi PLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
The detector must be mounted on a rigid surface in
a low vibration area.
IR VIEWING WINDOW
oi MAGNET
B2174
DETECTOR
STATUS INDICATOR
Figure 2—Front View of the X9800
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
INCORRECT
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
D1974
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon
13.1
6
95-8554
PROTECTION AGAINST MOISTURE DAMAGE
NOTE
R e f e r t o “ Po w e r C o n s u m p t i o n” i n t h e
“Specifications” section of this manual.
It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
operation and is the responsibility of the installer.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures 7
through 12, and Figure 15. Consult the factory if not using
shielded cable.
If conduit is used, we recommend installing drains,
according to local codes, at water collection points
to automatically drain accumulated moisture. It is
also recommended to install at least one breather,
according to local codes, at upper locations to provide
ventilation and allow water vapor to escape.
In applications where the wiring cable is installed in
conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate disconnect
capability must be provided.
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
WARNING
All entries must contain appropriately rated plugs
or fittings. It is required that each plug or fitting be
wrench-tightened to an appropriate installation
torque and meet the minimum thread engagement
requirements per the applicable local standards,
codes, and practices in order to retain the defined
ratings. PTFE sealant or equivalent should be used
on NPT threads.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are
highly recommended to prevent water ingress in
outdoor applications. Units with M25 threads must use
an IP66/IP67 washer to prevent water ingress.
IMPORTANT
Devices certified for hazardous locations shall be
installed in accordance with EN/IEC 60079-14 and
NEC 505.
WIRING PROCEDURE
CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.
Wire Size and Type
The system should be wired according to local
codes. The wire size selected should be based on the
number of detectors connected, the supply voltage
and the cable length. Typically 16 AWG or 2.5 mm2
shielded cable is recommended. Wires should be
stripped 3/8 inch (9 mm). A minimum input voltage of
18 Vdc must be present at the X9800.
4X ø0.42
(1.1)
3.0
(7.6)
4.0
(10.2)
13.1
(33.3)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
3.0
(7.6)
4.0
(10.2)
10.6
(27.0)
F2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
13.1
7
95-8554
Detector Installation
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 inch (M9) bolts with a length
of at least 1 inch (25 mm). The surface must also have
sufficient capacity to hold the detector and mounting
arm weights (See "Specifications" section). Refer to the
Q9033 Mounting Arm manual (95-8686) for additional
installation information. See Figure 3 for dimensions.
3. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
Relay and 0-20 mA Output Models
EOL Resistors (Not Used with EQP Model)
Follow the instructions below to install the X9800.
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
by EOL resistors, observe the following guidelines when
installing the resistors.
1. Make field connections following local ordinances
and guidelines in this manual. Refer to Figures 4
through 12.
1. Required EOL resistor power rating must be 5 watts
minimum.
2. Check all field wiring to be sure that the proper
connections have been made.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies to
ATEX/IECEx installations only.
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3. Bend the leads and install the EOL resistor as shown
in Figure 6.
4. Maintain a 3/8 inch (10 mm) minimum gap between
the resistor body and the terminal block or any other
neighboring parts.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused conduit
entries shall be closed with suitable blanking
elements.
Figure 4—X9800 Terminal Block
3/8 INCH (10 MM) GAP MINIMUM
9
mA +
19
mA –
29
SPARE
8
mA + REF
18
mA – REF
28
SPARE
7
COM FIRE
17
COM FIRE
27
COM AUX
6
NO FIRE
16
NO FIRE
26
NO AUX
5
NC FIRE
15
NC FIRE
25
NC AUX
4
COM FAULT
14
COM FAULT
24
RS485 A
3
NO FAULT
13
NO FAULT
23
RS485 B
2
+Vin
12
+Vin
22
MAN Oi
1
–Vin
11
–Vin
21
–Vin
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
E2061
Figure 5—Wiring Terminal Identification
13.1
Figure 6—EOL Resistor Installation
8
95-8554
X9800 DETECTOR
FIRE ALARM PANEL
SHIELD
ALARM
+
24 VDC
–
9
mA +
19
mA –
SPARE
29
8
mA + REF
18
mA – REF
SPARE
28
7
COM FIRE2
COM AUX
27
6
NO FIRE2
NO AUX
26
NC AUX
25
COM FIRE
17
NO FIRE
16
5
NC FIRE2
4
COM FAULT1
3
NO FAULT1
2
+Vin
12
1
–Vin
11
EOL
DEVICE4
NC FIRE
15
COM FAULT
14
RS485 A
24
NO FAULT
13
RS485 B
23
+Vin
MAN Oi
22
–Vin
–Vin
21
oi TEST 3
WIRING NOTES:
C2176
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 7—Ex d Wiring Option
SHIELD
X9800 DETECTOR
FIRE ALARM PANEL
ALARM
EOL
DEVICE 4
ALARM
+
24 VDC
–
9
mA +
19
mA –
SPARE
29
8
mA + REF
18
mA – REF
SPARE
28
7
COM FIRE2
COM FIRE
17
COM AUX
27
6
NO FIRE2
NO FIRE
16
NO AUX
26
5
NC FIRE2
NC FIRE
15
NC AUX
25
4
COM FAULT1
COM FAULT
14
3
NO FAULT1
13
NO FAULT
2
+Vin
12
1
–Vin
11
RS485 A
24
RS485 B
23
+Vin
MAN Oi
22
–Vin
–Vin
21
oi TEST 3
C2177
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 8—Ex e Wiring Option
13.1
9
95-8554
X9800 DETECTOR
X9800 DETECTOR
PLC
PLC
600 Ω MAX
AT 24 VDC
9
mA +
19 mA –
29
+
8
mA + REF
18
28
+
–
7
17
27
–
mA
24 VDC
600 Ω MAX
AT 24 VDC
9
+
6
16
26
5
15
25
mA
24 VDC
+Vin
12
–Vin
11
–
16
26
5
15
25
4
14
24
2
+Vin
12
–Vin
21
1
–Vin
11
23
13
MAN Oi
22
D2179
–Vin 21
Figure 10—X9800 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sinking)
24 VDC
+
–
X9800 DETECTOR
PLC
9
mA +
19 mA –
29
X9800 DETECTOR
19 mA –
29
+
8
18
28
+
8
18
28
–
7
17
27
–
7
17
27
6
16
26
6
16
26
5
15
25
5
15
25
4
14
24
4
14
24
+
–
9
600 Ω MAX
AT 24 VDC
mA
24 VDC
+
–
23
3
2
+Vin
12
MAN Oi
22
2
1
–Vin
11
–Vin
21
13
3
D2180
1
13
+Vin
12
–Vin
11
23
MAN Oi
22
–Vin 21
Oi TEST1
Figure 12—X9800 Detector Wired for Isolated 0 to 20 mA
Current Output (Sinking)
Figure 11—X9800 Detector Wired for Isolated 0 to 20 mA
Current Output (Sourcing)
NOTES: 1.
mA +
D2181
Oi TEST1
13.1
27
6
Oi TEST1
24 VDC
+
–
mA
24 VDC
28
17
3
Figure 9—X9800 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sourcing)
600 Ω MAX
AT 24 VDC
18 mA – REF
7
22
Oi TEST1
PLC
8
23
D2178
1
29
MAN Oi
13
3
2
24
14
4
–
+
19 mA –
mA +
INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE
INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.
10
95-8554
5. Check all field wiring to be sure that the proper
connections have been made.
EQP Model
1. Connect external wires to the appropriate terminals
inside the device junction box, shown in Figure 13.
See Figure 14 for terminal identification.
6. Replace the device cover and apply input power.
2. Connect the shield of the power cable to earth
ground at the power source.
7. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
3. Connect shields for the LON cable as indicated.
See Figure 15.
NOTE
Refer to the Eagle Quantum Premier system
manual (95-8533) for information regarding power
requirements, network communication cable
requirements, and configuration.
NOTE
DO NOT ground any shields at the detector
housing.
4. With input power disconnected, set the device
network address. (See “Setting Device Network
Addresses” section of this manual for switch setting
procedure.)
Figure 13—X9800 Terminal Block (EQP Model)
6
SHIELD
16
SHIELD
5
COM 1 A
15
COM 2 A
4
COM 1 B
14
COM 2 B
3
PWR SHIELD
13
PWR SHIELD
2
+Vin
12
+Vin
1
–Vin
11
–Vin
C2089
Figure 14—Wiring Terminal Identification for X9800 EQP Model
13.1
11
95-8554
13.1
C 45
12
9 3+
RELAY 5
RELAY 6
RELAY 7
C 42
NO 43
NC 44
31 NO
32 NC
NC 41
29 NC
RELAY 3
30 C
C 39
NO 40
28 NO
NC 38
26 NC
RELAY 2
27 C
C 36
NO 37
25 NO
NC 35
23 NC
RELAY 1
24 C
NO 34
22 NO
P5
C 33
DIGITAL INPUTS
21 C
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
P3
1
2
CH 3
P4
8– 20
8+ 19
CH 7
12 4–
11 4+
7– 18
7+ 17
A
4
P4
B
5
3
COM1
SHIELD
6
COM2
1
4
P2
2
24 VDC –
24 VDC +
5
3
SHIELD
6
P1
EQP3700DCIO
CH 2
10 3–
6– 16
6+ 15
5– 14
5+ 13
P3
A 56
B 55
CH 6
8 2–
7 2+
6 1–
5 1+
P2
59 TxD
58 RxD
57 GND GND 54
P8
NC 47
FAULT NO 46
CH 5
DB-9
CONNECTION
TO COM PORT
OF PC
TXD 3
RXD 2
GND 5
50
A
53
P9
49
B
52
P6
48
COM1
SHIELD
51
COM2
1
3
P7
2
24 VDC –
24 VDC +
4
P1
CONTROLLER
CH 1
CH 4
CH 8
RELAY 4
RELAY 8
95-8554
–
–
24 VDC
BATTERY
+
H
N
AC LINE
24 VDC
SUPPLY
+
+
+
–
–
POWER
–
–
+ DISTRIBUTION +
+
–
+ –
+ –
2
B
N
H
AC LINE
COM2
15
14
16
A
B
5
4
6
COM1
SHIELD
Figure 15—A Typical EQP System
4
3
1
2
C
A
10
3
P3
B
11
1
BUS BAR
SHIELD
12
COM1
12 24 VDC + 2
8
5
COM2
11 24 VDC – 1
7
24 VDC –
24 VDC +
3
6
SHIELD
EQPX9800
13
SHIELD
4
9
EQP2100PSM
COM2
15
14
16
A
B
SHIELD
5
4
6
COM1
2
15
14
16
COM2
A
B
SHIELD
5
4
6
COM1
12 24 VDC + 2
3
11 24 VDC – 1
SHIELD
EQPX9800
13
12 24 VDC +
3
11 24 VDC – 1
SHIELD
EQPX9800
13
3
B
A
14
15
5
4
6
COM1
SHIELD
16
COM2
12 24 VDC + 2
11 24 VDC – 1
SHIELD
EQPX9800
13
A2210
ADDRESS SWITCHES
SENSOR MODULE
REMOVED FROM HOUSING
A2191
Figure 16—Location of Address Switches
The address number is binary encoded with each
switch having a specific binary value with switch 1
being the LSB (Least Significant Bit), see Figure 17.
The device’s LON address is equal to the added value
of all closed rocker switches. All “Open” switches are
ignored.
SETTING DEVICE NETWORK ADDRESSES
(EQ and EQP Models Only)
Overview of Network Addresses
Each device on the LON must be assigned a unique
address. Addresses 1 to 4 are reserved for the
controller. Valid addresses for field devices are from 5
to 250.
Example: for node No. 5, close rocker switches 1 and
3 (binary values 1 + 4); for node No. 25, close rocker
switches 1, 4 and 5 (binary values 1 + 8 + 16).
IMPORTANT
If the address is set to zero or an address above
250, the switch setting will be ignored.
NOTE
The field device sets the LON address only when
power is applied to the device. Therefore, it is
important to set the switches before applying
power. If an address is ever changed, system
power must be cycled before the new address will
take effect.
Duplicated addresses are not automatically detected.
Modules given the same address will use the number
given and report to the controller using that address.
The status word will show the latest update, which
could be from any of the reporting modules using that
address.
After setting address switches, record the address
number and device type.
Setting Field Device Addresses
Selection of the node address is done by setting rocker
switches on an 8 switch “DIP Switch Assembly” within
the detector’s housing. Refer to Figure 16 for switch
location.
WARNING
The network address switches are located within
the detector housing. Disassembly of the detector
head that contains powered electrical circuits is
required to gain access to the network address
switches. For hazardous areas, the area must be
de-classified before attempting disassembly of the
device. Always observe precautions for handling
electrostatic sensitive devices.
ON
BINARY
VALUE
1
2
3
4
5
1
2
4
8
16 32 64 128
6
7
8
NODE ADDRESS EQUALS THE ADDED VALUE
OF ALL CLOSED ROCKER SWITCHES
OPEN = OFF
CLOSED = ON
A2190
Figure 17—Address Switches for X9800
13.1
13
95-8554
STARTUP PROCEDURE
Table 3—Current Level Output Troubleshooting Guide
When installation of the equipment is complete, perform
the “Fire Alarm Test” below.
FIRE ALARM TEST
1. Disable any extinguishing
connected to the system.
equipment
that
is
2. Apply input power to the system.
3. Initiate an oi test. (See “Magnetic oi / Manual oi”
under Optical Integrity in the "Description" section of
this manual.
Current Level
(±0.3 mA)
Status
Action
0 mA
Power Fault
Check system wiring.
1 mA
General Fault
Cycle power.1
2 mA
oi Fault
Clean windows.2
4 mA
Normal Operation
16 mA
Hi Background IR
Fault
20 mA
Fire Alarm
Remove IR source or
aim detector away
from IR source.
1If fault continues, return device to factory for repair.
2See “Maintenance” section for cleaning procedure.
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (Det-Tronics'
Q1201C Laser Aimer is recommended for this
purpose.)
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
6. Enable extinguishing equipment when the test is
complete.
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
high levels of background IR radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears, extreme
background IR radiation is present. Re-adjust the
view of the detector away from the IR source or
relocate the detector.
TROUBLESHOOTING
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
1. Disable any extinguishing
connected to the unit.
equipment
that
If none of these actions corrects the problem, return the
detector to the factory for repair.
is
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
MAINTENANCE
3. Check input power to the unit.
IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
4. If the fire system has a logging function, check the
fire panel log for output status information. See Table
3 for information regarding 0 to 20 mA output.
WARNING
To avoid a potential electrostatic discharge (ESD),
the painted surface of the detector should only be
cleaned with a damp cloth.
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
13.1
14
95-8554
NOTE
Refer to the X9800 Safety manual, number
9 5 - 8 6 7 2 , fo r s p e c i fi c re q u i re m e n t s a n d
recommendations applicable to the proper
installation, operation, and maintenance of all SILCertified X9800 Flame Detectors.
LOOSEN TWO CAPTIVE SCREWS
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X9800 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.
GRASP VISOR AND
REMOVE oi PLATE
CLEANING PROCEDURE
B2175
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
Figure 18—oi Plate Removal
To clean the windows and oi plate, use the Det-Tronics
window cleaner (p/n 001680-001) and a soft cloth, cotton
swab or tissue and refer to the following procedure:
4. Recalibrate the detector's oi system. Refer to the
Inspector Monitor manual, number 95-8581, for
instructions regarding oi plate replacement and oi
system recalibration.
1. Disable any extinguishing equipment that is
connected to the unit.
CAUTION
Do not replace the oi reflector plate without also
recalibrating the oi system.
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.
Recalibration of the oi system requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.
2. Clean the viewing window and reflective surfaces
of the oi plate using a clean cloth, cotton swab or
tissue, and Det-Tronics' window cleaning solution.
Use Isopropyl alcohol for contaminations that the
Det-Tronics window cleaning solution can not
remove. If a fault condition is still indicated after
cleaning, remove and clean the oi plate using the oi
Plate Removal and Replacement procedure.
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the system
using the Mag oi or Man oi feature should performed
regularly to ensure that the system is operating properly.
Refer to Table 1 in the X9800 Safety manual (95-8672) for
frequency of proof tests. To test the system, perform the
“Fire Alarm Test” as described in the “Startup Procedure”
section of this manual.
IMPORTANT
When used in extreme environments, the reflective
surface of the detector oi plate may eventually
deteriorate, resulting in reoccurring oi faults and
the need for oi plate replacement.
CLOCK BATTERY
The real time clock has a backup battery that will
operate the clock with no external power. Return the
device to the factory for battery replacement if needed.
oi PLATE REMOVAL AND REPLACEMENT
1. Disable any extinguishing equipment that is
connected to the unit.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
2. Loosen the two captive screws, then grasp the oi
plate by the visor and remove it from the detector.
See Figure 18.
3. Install the new (or cleaned) oi plate.
13.1
15
95-8554
FEATURES
SPECIFICATIONS
•
Responds to a fire in the presence of modulated
blackbody radiation (i.e., heaters, ovens, turbines)
without false alarm.
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
•
High speed capability — 30 milliseconds
•
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms)
•
Microprocessor controlled heated optics
increased resistance to moisture and ice
•
Automatic, manual or magnetic oi testing
•
Easily replaceable oi plate
•
Fire, fault and auxiliary relays standard
•
0 to 20 mA isolated output (optional)
POWER CONSUMPTION—
Without heater: 2.1 watts at 24 Vdc nominal;
3.5 watts at 24 Vdc in alarm.
2.2 watts at 30 Vdc nominal;
4.0 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power:
16.5 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
Eagle Quantum Premier LON/SLC output (optional)
For HART model, refer to Addendum number 95-8637.
•
HART communication (optional)
•
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
•
Operates under adverse weather conditions
•
Mounting arm allows easy sighting
•
Integral wiring compartment for ease of installation
•
Explosion-proof/flame-proof
detector
housing.
Meets FM, CSA, ATEX, and IECEx certification
requirements.
for
•
Class A wiring per NFPA-72
•
Meets NFPA-33 response requirement for under
0.5 second (available when model selected)
•
3 year warranty
•
Advanced signal processing (TDSA)
•
RFI and EMC Directive compliant
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault Alarm relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open / normally
closed contacts, normally energized or
de-energized operation, and latching or nonlatching operation.
CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
Associated Manuals
List of X9800 related manuals:
TITLE
Pulse
EQP
SIL 2 (Safety)
HART Addendum
FORM NUMBER
95-8555
95-8533
95-8672
95-8637
Q9033 Mounting Arm
and Collar Attachment
95-8686
Inspector Monitor Software for
X-Series Flame Detectors
95-8581
13.1
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
16
95-8554
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
VIEWING ANGLE
15°
30°
0°
100
15°
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
30°
90
80
45°
45°
70
60
DETECTION
DISTANCE
(PERCENT)
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
50
40
30
SHIPPING WEIGHT (Approximate)—
Aluminum:
7 pounds (3.2 kilograms).
Stainless Steel:
14.6 pounds (6.7 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).
20
10
C1288
Figure 19—Detector Cone of Vision
WARRANTY PERIOD—
3 years
CERTIFICATION—
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 19.
®
RESPONSE TIME—
32 inch methane plume: < 10 seconds.
1 foot x 1 foot n-Heptane: < 15 seconds.
(See Appendix A for details.)
VdS
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).
For complete approval details, refer to the appropriate
Appendix:
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - EN54
Appendix F - Additional Approvals
DIMENSIONS—
See Figure 20.
4.7
(11.9)
B2223
10.2
(25.9)
4.8
(12.2)
Figure 20—Dimensions in Inches (cm)
13.1
17
95-8554
REPLACEMENT PARTS
ORDERING INFORMATION
The detector is not designed to be repaired in the field. If
a problem should develop, refer to the "Troubleshooting"
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the
factory for repair.
When ordering, please specify:
X9800 IR Flame Detector
Refer to the X9800 Model Matrix below for details
Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel detectors
REPLACEMENT PARTS LIST
Part Number
Description
009208-002
oi Replacement kit for X52/X22/X98 (5 Reflector Plates)
with Inspector Connector and Monitor
Replacement oi Reflector Plate for X52/X22/X98
(requires Inspector Connector to calibrate)
007307-002
ACCESSORIES
Part Number
Description
000511-029
103881-001
Converter RS485 to RS232
Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
Flame Inspector Monitor CD
Model 475 HART Communicator
Magnet
Magnet and Adapter for Extension Pole
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
Q1120A1001 Paint Shield mounting ring (AL)
Q1201 Laser
Laser Battery, 3V Lithium (laser)
Q1201C1001 X-Series Laser Holder (AL/Plastic)
Q2000A1001 X-Series Weather Shield (AL)
Q9033B Stainless Steel Mounting Arm Assembly is for
aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum
detectors only
Q9033 Collar Attachment
Stop Plug, 3/4” NPT, AL
Stop Plug, 3/4” NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4”NPT, AL
Stop Plug, 20 Pack, 3/4”NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
Window cleaner (6 pack)
O-ring - Rear Cover (Viton) - black or brown
1 oz grease for detectors (silicone-free)
O-ring - Rear Cover (Fluorosilicone) - blue
1 oz PTFE silicone-free lubricant
007819-001
007819-002
009207-001
103922-001
102740-002
008082-001
007739-001
007240-001
007818-001
007818-002
009177-001
006097-001
102871-001
007255-001
007338-001
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure.
007290-001
007290-002
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
001680-001
107427-040
005003-001
104346-154
012549-001
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.
Return all equipment transportation prepaid to the factory
in Minneapolis.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
13.1
18
95-8554
X9800 MODEL MATRIX
MODEL DESCRIPTION
X9800
Single Frequency IR Flame Detector
TYPE
MATERIAL
A
Aluminum
S
Stainless Steel (316)
TYPE
THREAD TYPE
4M
4 PORT, METRIC M25
4N
4 PORT, 3/4" NPT
TYPE
OUTPUTS
11
Relay
13
Relay and 0-20 mA
14
Eagle Quantum Premier (EQP)
15
Relay and Pulse
16
Addressable Module Only (Third Party Type)*
23
HART, Relay and 0-20 mA
TYPE
APPROVALS**
T
SIL/FM/CSA/ATEX/IECEx
W
FM/CSA/ATEX/IECEx
S
SIL
R
VNIIPO/VNIIFTRI (Russia)
TYPE
CLASSIFICATION
1
Division/Zone Ex d e
2
Division/Zone Ex d
*The Addressable Module Only (Type 16) is not FM approved.
**Type Approvals can use one or more letters to designate
the approvals of the product.
13.1
19
95-8554
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:
•
Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615.
•
Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T5) Hazardous (Classified) Locations per FM 3615.
•
Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611.
•
Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
•
Enclosure rating NEMA/Type 4X per NEMA 250.
•
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
•
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
CL I, ZONE 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
CL I, ZONE 1, AEx db IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
The following accessories are FM approved for use with the X9800 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector
was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.
13.1
20
95-8554
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
Size / Flow Rate
Distance
feet (m)
Typical Response Time
(seconds)*
TDSA
Quick Fire
n-Heptane
1 x 1 foot
85 (25.9)
15
On
Off
Methane
32 inch plume
60 (18.3)
5
On
Off
Propane
Torch
2 (0.6)
0.04
On
On
*Add 2 seconds for EQP model.
High Sensitivity
Fuel
Size / Flow Rate
Distance
feet (m)
Typical Response Time
(seconds)*
TDSA
Quick Fire
n-Heptane
1 x 1 foot
50 (15.2)
8
On
Off
Methane
32 inch plume
35 (10.7)
3
On
Off
Pyrodex
40 grams
10 (3)
0.1
On
On
Black Powder
40 grams
10 (3)
0.04
On
On
n-Heptane
1 x 1 foot
50 (15.2)
6
On
On
*Add 2 seconds for EQP model.
Low Sensitivity
Fuel
Size / Flow Rate
Distance
feet (m)
Typical Response Time
(seconds)*
TDSA
Quick Fire
n-Heptane
1 x 1 foot
15 (4.6)
8
On
Off
*Add 2 seconds for EQP model.
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
High Sensitivity, TDSA On, Quick Fire Off
Distance
feet (m)
Fire Source
Distance
feet (m)
Typical Response Time
(seconds)*
Sunlight, direct, modulated/unmodulated
—
2 inch dia Heptane
10 (3)
< 30
Sunlight, reflected, modulated/unmodulated
—
2 inch dia Heptane
10 (3)
< 30
70 w sodium vapor lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
70 w sodium vapor lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
250 w mercury vapor lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
250 w mercury vapor lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
300 w incandescent lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
300 w incandescent lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
500 w shielded quartz halogen lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
500 w shielded quartz halogen lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
1500 w electric radiant heater, unmodulated
10 (3)
2 inch dia Heptane
5 (1.5)
3
1500 w electric radiant heater, modulated
10 (3)
2 inch dia Heptane
3 (0.9)
13
Two 34 w fluorescent lamps, unmodulated
3 (0.9)
2 inch dia Heptane
10 (3)
3
Two 34 w fluorescent lamps, modulated
3 (0.9)
2 inch dia Heptane
10 (3)
5
Arc welding
15 (4.6)
2 inch dia Heptane
5 (1.5)
N/A
False Alarm Souce
*Add 2 seconds for EQP model.
13.1
21
95-8554
FM Approval and Performance Report – Continued
FALSE ALARM IMMUNITY
High Sensitivity, TDSA On, Quick Fire Off
False Alarm Souce
Distance feet
(m)
Modulated Response
Unmodulated Response
—
No alarm
No alarm
Sunlight, direct, reflected
NA
No alarm
No alarm
Arc welding
15 (4.6)
No alarm
No alarm
70 w sodium vapor lamp
3 (0.9)
No alarm
No alarm
250 w mercury vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
10 (3)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Vibration
FIELD OF VIEW
Very High Sensitivity, Quick Fire Off
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
n-Heptane
1 x 1 foot
42.5
(13)
+45
–45
12
14
+45
–30
10
16
Methane
32 inch plume
30
(9.1)
+45
–45
7
4
+45
–30
6
4
*Add 2 seconds for EQP model.
High Sensitivity, TDSA On, Quick Fire Off
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
n-Heptane
1 x 1 foot
25
(7.6)
+45
–45
7
7
+45
–30
6
5
Methane
32 inch plume
17.5
(5.3)
+45
–45
6
3
+45
–30
4
4
*Add 2 seconds for EQP model.
High Sensitivity, TDSA On, Quick Fire On
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
Black
Powder
40 Grams
5
(1.5)
+45
–45
0.04
0.03
+45
–30
0.04
0.04
*Add 2 seconds for EQP model.
13.1
22
95-8554
APPENDIX B
CSA APPROVAL
DIVISION CLASSIFICATION:
Infrared Flame Detector/Controller X9800 series, rated 18-30 Vdc, 2.1 Watts to 16.5 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);
Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3);
Class III; Enclosure NEMA/Type 4X;
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91
–
General requirements - Canadian Electrical Code, Part II
CAN/CSA-C22.2 No. 25-1966
–
Enclosures for use in Class II Groups E, F & G Hazardous Locations.
CAN/CSA-C22.2 No. 30-M1986
–
Explosion-Proof Enclosures for use in Class I Hazardous Locations.
CAN/CSA C22.2 No. 94-M91
–
Special Purpose Enclosures.
CAN/CSA-C22.2 No. 142-M1987
–
Process Control Equipment.
CAN/CSA-C22.2 No. 213-M1987
–
Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations.
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex db eb IIC T6...T5
T6 (Tamb = -50°C to +60°C)
T5 (Tamb = -50°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -50°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
Ex db IIC T6...T5
T6 (Tamb = -55°C to +60°C)
T5 (Tamb = -55°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -55°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0: 2007
–
Electrical apparatus for explosive atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1: 2011
–
Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7: 2012
–
Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
CAN/CSA-C22.2 No. 60079-31: 2012
–
Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure "t"
The following accessories are CSA approved for use with the X9800 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
13.1
23
95-8554
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 02 ATEX 132195X
Increased Safety Model
FM
APPROVED
Flameproof Model
II 2 G
II 2 G
FM
0539
II 2 D
II 2 D
Ex db eb IIC T6...T5
Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
0539
®
®
APPROVED
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-31: 2009
EN 60529:1991+A1:2000+A2:2013
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG, 2.5-0.2 mm2.
The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e." They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Infrared (IR) flame detector type X9800 is to be installed in places where there is a low risk of mechanical
damage.
•
See the "Maintenance" section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual for
more information on conducting repairs.
13.1
24
95-8554
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.
NOTE
For ATEX installations, the X9800 detector housing must be electrically connected to earth ground.
The following accessories are ATEX approved for use with the X9800 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
13.1
25
95-8554
APPENDIX D
IECEx APPROVAL
CERTIFICATE OF CONFORMITY
IECEx ULD 06.0018X
Ex db eb IIC T6...T5
Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
or
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
Compliance with:
IEC 60079-0: 2011, Ed. 6
IEC 60079-1: 2014, Ed. 7
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
IEC 60529: 2013, Ed. 2.2
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG, 2.5-0.2 mm2.
The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e." They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Infrared (IR) flame detector type X9800 is to be installed in places where there is a low risk of mechanical
damage.
•
See the "Maintenance" section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual for
more information on conducting repairs.
The following accessories are IECEx approved for use with the X9800 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
13.1
26
95-8554
APPENDIX E
EN54 APPROVALS
Conventional Output
Certification Bodies
VdS –
Construction Product Regulation
Certificate/Approval Number
Basis of Approval
0786 – CPR – 20779
EN 54-10 + A1
—
—
G 203084
VdS 2344
VdS 2504
EN 54-10 + A1
G212021
VdS 2344
VdS 2504
EN 54-10
EN 54-17
S 212002*
VdS 2344
EN 54-13
S 212002*
VdS 2344
EN 54-13
—
—
0832 – CPD – 1377
EN 54-10 + A1
EN 54-17
973e/01
EN 54-10 + A1
973a/01
EN 54-10 + A1
EN 54-17
VdS
BRE –
Construction Product Directive
LPCB
LON Output
Certificate/Approval
Number
Basis of Approval
* Approved for use in conjunction with the EN54-13 compliant EQP System.
INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM
The installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view
angle in this direction is <90°.
The IR-flame detector corresponds to class 1.
The following accessories are EN54-10 and EN54-17 approved for use with the X9800 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
13.1
27
95-8554
APPENDIX F
ADDITIONAL APPROVALS
SIL 2
IEC 61508
Certified SIL 2 Capable.
Applies to specific models – refer to the SIL 2 Certified X9800 Safety Manual, number 95-8672, for details.
RUSSIA & KAZAKHSTAN
VNIIFTRI
CERTIFICATE OF CONFORMITY TO TP TC 012/2011
TC RU C-US. ГБ06.B.00158
2ExdeIICT6/T5 IP66
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
– OR –
1ExdIICT6/T5IP66
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
RUSSIA
VNIIPO
CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS, GOST R 53325-2012
C-US.ПБ01.B.02841
FRANCE
AFNOR Identification No: LIR 011 A0.
For specific information regarding the X9800 Flame Detector's conformity to NF EN54-10, reference Addendum number
95-8699.
13.1
28
95-8554
95-8554
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2016 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.