Endress + Hauser Operating Instructions Liquisys M CCM223/253 Transmitter for free chlorine, chlorine dioxide and total chlorine
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
BA00214C/07/EN/15.15
71300499
Products
Solutions
Services
Operating Instructions
Liquisys M CCM223/253
Transmitter for free chlorine, chlorine dioxide and total
chlorine
Liquisys M CCM223/253
Table of contents
Table of contents
1
Document information . . . . . . . . . . . . . . 5
1.1
1.2
1.3
1.4
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols on the device . . . . . . . . . . . . . . . . . . .
Electrical symbols . . . . . . . . . . . . . . . . . . . . . .
2
Basic safety instructions . . . . . . . . . . . . 7
2.1
2.2
2.3
2.4
2.5
Requirements for personnel . . . . . . . . . . . . . . .
Designated use . . . . . . . . . . . . . . . . . . . . . . . .
Occupational safety . . . . . . . . . . . . . . . . . . . . .
Operational safety . . . . . . . . . . . . . . . . . . . . . .
Product safety . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.1 State of the art . . . . . . . . . . . . . . . . . .
2.5.2 IT security . . . . . . . . . . . . . . . . . . . . . .
3
Incoming acceptance and product
identification . . . . . . . . . . . . . . . . . . . . . . . 9
3.1
3.2
3.3
Incoming acceptance . . . . . . . . . . . . . . . . . . . .
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . .
Product identification . . . . . . . . . . . . . . . . . . .
3.3.1 Nameplate . . . . . . . . . . . . . . . . . . . .
3.3.2 Product identification . . . . . . . . . . . .
Certificates and approvals . . . . . . . . . . . . . . .
3.4.1 mark . . . . . . . . . . . . . . . . . . . . . .
3.4.2 CSA General Purpose . . . . . . . . . . . . .
3.4
5
5
5
6
7
7
7
8
8
8
8
9
9
10
10
10
10
10
10
4
Installation . . . . . . . . . . . . . . . . . . . . . . . 11
4.1
4.4
Installation at a glance . . . . . . . . . . . . . . . . . .
4.1.1 Measuring system . . . . . . . . . . . . . . .
Installation conditions . . . . . . . . . . . . . . . . . .
4.2.1 Field device . . . . . . . . . . . . . . . . . . . .
4.2.2 Panel-mounted device . . . . . . . . . . . .
Installation instructions . . . . . . . . . . . . . . . . .
4.3.1 Field device . . . . . . . . . . . . . . . . . . . .
4.3.2 Panel-mounted device . . . . . . . . . . . .
Post-installation check . . . . . . . . . . . . . . . . . .
5
Electrical connection . . . . . . . . . . . . . . 19
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical connection, version 1 . . . . . . . . . . .
Electrical connection, version 2 . . . . . . . . . . .
Device connection . . . . . . . . . . . . . . . . . . . . .
Measuring cables and sensor connection . . . .
Three-point step controller for Cl2 / ClO2 /
total chlorine . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm contact . . . . . . . . . . . . . . . . . . . . . . . .
Post-connection check . . . . . . . . . . . . . . . . . .
6
Operation options . . . . . . . . . . . . . . . . . 30
6.1
Quick operation guide . . . . . . . . . . . . . . . . . .
4.2
4.3
Endress+Hauser
11
12
14
14
15
16
16
18
18
19
19
21
22
24
28
29
29
30
6.2
6.3
Display and operating elements . . . . . . . . . . .
6.2.1 Display . . . . . . . . . . . . . . . . . . . . . . .
6.2.2 Operating elements . . . . . . . . . . . . . .
6.2.3 Key functions . . . . . . . . . . . . . . . . . .
Local operation . . . . . . . . . . . . . . . . . . . . . . .
6.3.1 Automatic/manual mode . . . . . . . . . .
6.3.2 Operating concept . . . . . . . . . . . . . . .
30
30
32
32
35
35
36
7
Commissioning . . . . . . . . . . . . . . . . . . . . 38
7.1
7.2
7.3
7.4
7.5
Function check . . . . . . . . . . . . . . . . . . . . . . .
Switching on . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . .
Device configuration . . . . . . . . . . . . . . . . . . .
7.4.1 Setup 1 (chlorine/chlorine dioxide) . .
7.4.2 Setup 2 (temperature or pH/ORP) . . .
7.4.3 Current input . . . . . . . . . . . . . . . . . .
7.4.4 Current outputs . . . . . . . . . . . . . . . . .
7.4.5 Alarm . . . . . . . . . . . . . . . . . . . . . . . .
7.4.6 Check . . . . . . . . . . . . . . . . . . . . . . . .
7.4.7 Relay configuration . . . . . . . . . . . . . .
7.4.8 Service . . . . . . . . . . . . . . . . . . . . . . .
7.4.9 E+H Service . . . . . . . . . . . . . . . . . . . .
7.4.10 Interfaces . . . . . . . . . . . . . . . . . . . . .
7.4.11 Communication . . . . . . . . . . . . . . . . .
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Diagnostics and troubleshooting . . . 85
8.1
8.2
8.3
8.4
Trouble shooting instructions . . . . . . . . . . . . .
System error messages . . . . . . . . . . . . . . . . . .
Process-specific errors . . . . . . . . . . . . . . . . . .
Device-specific errors . . . . . . . . . . . . . . . . . . .
9
Maintenance . . . . . . . . . . . . . . . . . . . . . . 95
9.1
Maintenance of the entire measuring point . .
9.1.1 Cleaning the transmitter . . . . . . . . . .
9.1.2 Cleaning the pH/mV sensors
(EP version) . . . . . . . . . . . . . . . . . . .
9.1.3 Maintenance of chlorine sensors . . . .
9.1.4 Assembly . . . . . . . . . . . . . . . . . . . . .
9.1.5 Maintenance of pH connecting
cables and junction boxes (EP
version) . . . . . . . . . . . . . . . . . . . . . .
Test and simulation . . . . . . . . . . . . . . . . . . . .
9.2.1 Chlorine sensors . . . . . . . . . . . . . . . .
9.2.2 Temperature measurement . . . . . . . .
9.2.3 pH/ORP measurement . . . . . . . . . . . .
9.2.4 Flow monitoring . . . . . . . . . . . . . . . .
9.2
10
38
38
40
42
42
44
47
51
55
56
60
77
79
80
80
81
85
85
89
93
95
95
96
97
97
98
98
98
99
99
99
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.1 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . .
10.2 Disassembling the panel-mounted device . . .
10.3 Disassembling the field device . . . . . . . . . . .
10.4 Replacing the central module . . . . . . . . . . . .
101
101
104
107
3
Table of contents
Liquisys M CCM223/253
10.5 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
10.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
11
Accessories . . . . . . . . . . . . . . . . . . . . . . 109
11.1
11.2
11.3
11.4
11.5
11.6
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection accessories . . . . . . . . . . . . . . . . .
Installation accessories . . . . . . . . . . . . . . . .
Software and hardware add-ons . . . . . . . . . .
Metering system . . . . . . . . . . . . . . . . . . . . .
Calibration accessories . . . . . . . . . . . . . . . . .
12
Technical data . . . . . . . . . . . . . . . . . . . 113
12.1
12.2
12.3
12.4
12.5
12.6
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply . . . . . . . . . . . . . . . . . . . . . . . .
Performance characteristics . . . . . . . . . . . . .
Environment . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical construction . . . . . . . . . . . . . . .
13
Appendix . . . . . . . . . . . . . . . . . . . . . . . . 119
109
109
110
111
111
112
113
113
116
117
117
118
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
4
Endress+Hauser
Liquisys M CCM223/253
Document information
1
Document information
1.1
Warnings
Structure of information
LDANGER
Causes (/consequences)
Consequences of non-compliance
(if applicable)
‣ Corrective action
LWARNING
Causes (/consequences)
Consequences of non-compliance
(if applicable)
‣ Corrective action
LCAUTION
Causes (/consequences)
Consequences of non-compliance
(if applicable)
‣ Corrective action
NOTICE
Cause/situation
Consequences of non-compliance
(if applicable)
‣ Action/note
1.2
Meaning
This symbol alerts you to a dangerous situation.
Failure to avoid the dangerous situation will result in a fatal or serious
injury.
This symbol alerts you to a dangerous situation.
Failure to avoid the dangerous situation can result in a fatal or serious
injury.
This symbol alerts you to a dangerous situation.
Failure to avoid this situation can result in minor or more serious injuries.
This symbol alerts you to situations which may result in damage to
property.
Symbols used
Additional information, tips
Permitted or recommended
Forbidden or not recommended
1.3
Symbol
Symbols on the device
Meaning
Reference to device documentation
Endress+Hauser
5
Document information
Liquisys M CCM223/253
1.4
Electrical symbols
Symbol
Meaning
A0027423
A0027424
A0027425
A0027426
Direct current
A terminal at which DC is present or through which DC flows.
Alternating current
A terminal to which alternating voltage (sine-wave) is applied or through
which alternating current flows.
Direct current or alternating current
A terminal at which direct voltage or alternating voltage is present or
through which direct current or alternating current flows.
Ground connection
A terminal which, from the user's point of view, is already grounded via a
grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any
other connections.
A0027427
Class II equipment
Reinforced or double insulation
A0019929
Alarm relay
A0027420
Input
A0027428
Output
A0027429
DC voltage source
A0027430
Temperature sensor
A0027431
6
Endress+Hauser
Liquisys M CCM223/253
Basic safety instructions
2
Basic safety instructions
2.1
Requirements for personnel
• Installation, commissioning, operation and maintenance of the measuring system may
be carried out only by specially trained technical personnel.
• The technical personnel must be authorized by the plant operator to carry out the
specified activities.
• The electrical connection may be performed only by an electrical technician.
• The technical personnel must have read and understood these Operating Instructions
and must follow the instructions contained therein.
• Measuring point faults may be repaired only by authorized and specially trained
personnel.
Repairs not described in the Operating Instructions provided may only be carried out
directly by the manufacturer or by the service organization.
2.2
Designated use
Liquisys M CCM223/253 is a transmitter for determining the amount of free chlorine,
chlorine dioxide or total chlorine dissolved in water.
The transmitter is particularly suited for use in the following areas:
• Drinking water
• Water treatment
• Cooling water
• Gas scrubbers
• Reverse osmosis
• Food processing
• Swimming pool and bathing pool water
Use of the device for any purpose other than that described, poses a threat to the safety of
people and of the entire measuring system and is therefore not permitted.
The manufacturer is not liable for damage caused by improper or non-designated use.
2.3
Occupational safety
As the user, you are responsible for complying with the following safety conditions:
• Installation guidelines
• Local standards and regulations
Electromagnetic compatibility
• The product has been tested for electromagnetic compatibility in accordance with the
applicable European standards for industrial applications.
• The electromagnetic compatibility indicated applies only to a product that has been
connected in accordance with these Operating Instructions.
Endress+Hauser
7
Basic safety instructions
Liquisys M CCM223/253
2.4
Operational safety
1.
Before commissioning the entire measuring point, verify that all connections are
correct. Ensure that electrical cables and hose connections are undamaged.
2.
Do not operate damaged products, and safeguard them to ensure that they are not
operated inadvertently. Label the damaged product as defective.
3.
If faults cannot be rectified:
Take the products out of operation and safeguard them to ensure that they are not
operated inadvertently.
2.5
Product safety
2.5.1
State of the art
The product is designed to meet state-of-the-art safety requirements, has been tested, and
left the factory in a condition in which it is safe to operate. The relevant regulations and
European standards have been observed.
2.5.2
IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
8
Endress+Hauser
Liquisys M CCM223/253
Incoming acceptance and product identification
3
Incoming acceptance and product
identification
3.1
Incoming acceptance
1.
Verify that the packaging is undamaged.
Notify your supplier of any damage to the packaging.
Keep the damaged packaging until the matter has been settled.
2.
Verify that the contents are undamaged.
Notify your supplier of any damage to the delivery contents.
Keep the damaged products until the matter has been settled.
3.
Check the delivery for completeness.
Check it against the delivery papers and your order.
4.
Pack the product for storage and transportation in such a way that it is protected
against impact and moisture.
The original packaging offers the best protection.
The permitted ambient conditions must be observed (see "Technical data").
If you have any questions, please contact your supplier or your local sales center.
3.2
Scope of delivery
The delivery of the field device comprises:
• 1 transmitter
• 1 plug-in screw terminal, 3-pin
• 1 cable gland Pg 7
• 1 cable gland Pg 16 reduced
• 2 cable glands Pg 13.5
• 1 set of Operating Instructions
• For versions with HART communication:
1 set of Operating Instructions: Field communication with HART
• For versions with PROFIBUS interface:
1 set of Operating Instructions: Field communication with PROFIBUS PA/DP
The delivery of the panel-mounted device comprises:
• 1 transmitter
• 1 set of plug-in screw terminals
• 2 tensioning screws
• Also for EP version: 1 BNC connector (solder-free)
• 1 set of Operating Instructions
• For versions with HART communication:
1 set of Operating Instructions: Field communication with HART
• For versions with PROFIBUS interface:
1 set of Operating Instructions: Field communication with PROFIBUS PA/DP
Endress+Hauser
9
Incoming acceptance and product identification
3.3
Product identification
3.3.1
Nameplate
Liquisys M CCM223/253
The nameplate provides you with the following information on your device:
• Manufacturer identification
• Order code
• Extended order code
• Serial number
• Ambient and process conditions
• Input and output values
• Safety information and warnings
Compare the data on the nameplate with your order.
3.3.2
Product identification
The order code and serial number of your product can be found in the following locations:
• On the nameplate
• In the delivery papers
Obtaining information on the product
1.
Go to the product page for your product on the Internet.
2.
In the navigation area on the right-hand side, select "Check your device features"
under "Device support".
An additional window opens.
3.
Enter the order code from the nameplate into the search field.
You will receive information on each feature (selected option) of the order code.
3.4
Certificates and approvals
3.4.1
mark
The product meets the requirements of the harmonized European standards. As such, it
complies with the legal specifications of the EC directives. The manufacturer confirms
successful testing of the product by affixing to it the mark.
3.4.2
CSA General Purpose
The following device versions meet the requirements of CSA and ANSI/UL for Canada and
the US:
• CCM253-**2/3/7***
• CCM223-**2/3/7***
10
Endress+Hauser
Liquisys M CCM223/253
Installation
4
Installation
4.1
Installation at a glance
Proceed as follows to completely install the measuring point:
• Install the transmitter (see the "Installation instructions" section).
• If the sensor is not yet installed in the measuring point, install it (see Technical
Information of the sensor).
• Connect the sensor to the transmitter as illustrated in the "Electrical connection" section.
• Connect the transmitter as illustrated in the "Electrical connection" section.
• Commission the transmitter as explained in the "Commissioning" section.
Endress+Hauser
11
Installation
Liquisys M CCM223/253
4.1.1
Measuring system
Version 1: free chlorine and chlorine dioxide
A complete measuring system comprises:
• Transmitter Liquisys M CCM223 or CCM253
• A membrane covered sensor CCS140/141 for Cl2 or CCS240/241 for ClO2 an open
sensor 963 for Cl2
• Flow assembly CCA250 (not required for sensor 963)
Optionally:
• pH or ORP electrode
• Proximity switch INS for flow monitoring (not with sensor 963)
• Extension cable CMK for chlorine measurement
• Extension cable CYK71 for pH/ORP measurement
• An extension cable MK for proximity switch INS
• Junction box VBC
8
9
4
5
6
7
3
2
1
A0024088
1
1
2
3
4
5
6
7
8
9
Measuring system for the measurement of free chlorine or chlorine dioxide in flow operation (example)
Flow assembly CCA250
Medium inflow
Proximity switch INS
Mounting location for pH/ORP sensors
Chlorine sensor
Medium outlet
Sampling tap
Measuring cable
Transmitter CCM253
Version 2: total chlorine
A complete measuring system comprises:
• Transmitter Liquisys M CCM223 or CCM253
• Total chlorine sensor CCS120
• Flow assembly CCA250 or immersion assembly CYA611
• Measuring cable CPK9 with internal PML
12
Endress+Hauser
Liquisys M CCM223/253
Installation
Optionally:
• pH or ORP electrode
• Proximity switch INS for flow monitoring (only with flow assembly)
• Extension cable CPK9 with internal PML for chlorine measurement
• Extension cable CYK71 for pH/ORP measurement
• An extension cable MK for proximity switch INS
• Junction box VBC
• Weather protection cover CYY101 for field housing
1
2
4
3
6
5
A0024089
2
1
2
3
4
5
6
Endress+Hauser
Measuring system for the measurement of total chlorine in immersion operation (example)
Junction box
Transmitter CCM253
Measuring cable
Immersion assembly CYA611
Chlorine sensor CCS120
Assembly adapter G1
13
Installation
Liquisys M CCM223/253
4.2
Installation conditions
4.2.1
Field device
Pg 13.5
Pg 7
Pg 16
247 (9.72)
Ø 6 (0.24)
70 (2.76)
157 (6.18)
M5
11 (0.43)
115 (4.53)
70 (2.76)
154 (6.06)
170 (6.69)
A0024637
3
Field device, dimensions in mm (inch)
There is a hole in the perforation for the cable entry (connection of supply voltage). It
serves as a pressure balance during air shipment. Make sure no moisture penetrates
the inside of the housing before the cable installation. The housing is completely airtight after cable installation.
14
Endress+Hauser
Liquisys M CCM223/253
Installation
1
4
3
2
A0024640
4
1
2
3
4
View into the field housing
Removable electronics box
Terminals
Partition plate
Fuse
4.2.2
Panel-mounted device
96 (3.78)
6 (0.24)
149.5 (5.89)
139 (5.47)
92 (3.62)
90 (3.54)
A0024641
5
Endress+Hauser
Panel-mounted device, dimensions in mm (inch)
15
Installation
Liquisys M CCM223/253
4.3
Installation instructions
4.3.1
Field device
There are several ways of securing the field housing:
• Wall mounting with fixing screws
• Post mounting to cylindrical pipes
• Post mounting to a square securing mast
NOTICE
Effect of climatic conditions (rain, snow, direct sunlight etc.)
Impaired operation to complete transmitter failure
‣ When installing outside, always use the weather protection cover (accessory).
Transmitter wall mounting
2
Ø 6 (0.24)
1
154 (6.06)
A0024638
6
1
2
Field device wall mounting
Fixing bore holes
Plastic caps
Proceed as follows to mount the transmitter on the wall:
• Create the bore holes as shown in → 6.
• Drive two fixing screws through the fixing bore holes (1) from the front.
• Mount the transmitter on the wall as shown.
• Cover the bores with plastic caps (2).
Transmitter post mounting
You require a post mounting kit to secure the field device to horizontal and vertical
posts or pipes (max. Ø 60 mm (2.36")). This can be acquired as an accessory (see the
"Accessories" section).
16
Endress+Hauser
Liquisys M CCM223/253
Installation
1
1
2
Ø max. 60 (2.36)
3
1
3
A0024635
7
1
2
3
Field device on horizontal or vertical pipes
Securing screws
Fixing screws
Securing plate
Proceed as follows to mount the transmitter on a post:
1.
Guide the two securing screws (1) of the mounting kit through the openings on the
securing plate (3).
2.
Screw the securing plate onto the transmitter using the four fixing screws (2).
3.
Secure the bracket with the field device on the post or pipe using the clip.
You can also secure the field device to the Flexdip CYH112 bracket in conjunction with the
weather protection cover. These can be acquired as accessories, see the "Accessories"
section.
A0027433
8
Endress+Hauser
Field device on Flexdip CYH112 bracket with weather protection cover
17
Installation
Liquisys M CCM223/253
4.3.2
Panel-mounted device
The panel-mounted device is secured with the tensioning screws supplied → 9
The necessary installation depth is approx. 165 mm (6.50").
+0.5
(3.62
+0.02
)
92+0.5 (3.62+0.02)
92
1
max. 45 (1.77)
139 (5.47)
~ 25 (0.98)
3
96 (3.78)
92 (3.62)
3
33 (1.30)
90 (3.54)
57 (2.24)
2
3
6 (0.24)
~ 165 (6.50)*
A0024639
9
1
2
3
*
Dimensions in mm (inch)
Mounting plate
Seal
Tensioning screws
Necessary installation depth
4.4
Post-installation check
• After installation, check the transmitter for damage.
• Check whether the transmitter is protected against moisture and direct sunlight (e.g. by
the weather protection cover).
18
Endress+Hauser
Liquisys M CCM223/253
Electrical connection
5
Electrical connection
LWARNING
Device is live
Incorrect connection may result in injury or death.
‣ The electrical connection may be performed only by an electrical technician.
‣ The electrical technician must have read and understood these Operating Instructions
and must follow the instructions contained therein.
Prior
to commencing connection work, ensure that no voltage is present on any cable.
‣
5.1
Wiring
LWARNING
Risk of electric shock!
‣ At the supply point, the power supply must be isolated from dangerous live cables by
double or reinforced insulation in the case of devices with a 24 V power supply.
NOTICE
The device does not have a power switch
‣ The customer must provide a protected circuit breaker in the vicinity of the device.
‣ The circuit breaker must be a switch or power switch, and you must label it as the
circuit breaker for the device.
The electrical connection of the transmitter depends on the sensor:
• If you are using the membrane-covered sensor CCS140 / 141 / 240 / 241 or the open
sensor 963, follow the instructions and illustrations in the "Electrical connection, version
1" section.
• If you are using the total chlorine sensor CCS120, follow the instructions and
illustrations in the "Electrical connection, version 2" section.
5.2
Electrical connection, version 1
The wiring diagram shows the connections of a device equipped with all the options. The
connection of the sensors to the various measuring cables is explained in more detail in
the "Measuring cables and sensor connection" section.
Endress+Hauser
19
Electrical connection
Liquisys M CCM223/253
pH/
Redox
A
pH
Ref.
Red.
PA/
PM
S
B
GN 11
NTC
BN 12
K 90
K
RD
A
41
A 91
Cl2
42
ClO2
43
J
BU
A
47
48
RD 92
K
K
C
49
31
Cl2
ClO2
D
32
33
57
58
mA
L
59
51
52
mA
M
E
*
F
G
BK
10–50 V
53
81
82
54
55
56
93
23
H
85
I
N
24
94
BN
BU
34
O
mA
~ =
L1L+
15 V
N L–
P
86
A0001903
10
Electrical connection of the transmitter (version 1)
A
pH/ORP input (optional)
I
Auxiliary voltage output
B
Sensor CCS140/141/240/241
J
Alarm (current-free contact position)
C
Sensor 963 (alternative)
K
Relay 1 (current-free contact position)
D
Signal output 1, chlorine / chlorine dioxide
L
Relay 2 (current-free contact position)
E
Signal output 2, temperature, pH or ORP
M
Relay 3 (current-free contact position)
F
Binary input 1 (hold/cleaning)
N
Relay 4 (current-free contact position)
G
Proximity switch INS
O
Current input 4 to 20 mA
H
Binary input 2
P
Power connection
*
Auxiliary voltage of terminal 85/86 can be used
The device is approved for protection class II and is generally operated without a
protective ground connection. Circuits "E" and "I" are not galvanically isolated from each
other.
20
Endress+Hauser
Liquisys M CCM223/253
Electrical connection
5.3
Electrical connection, version 2
The wiring diagram shows the connections of a device equipped with all the options. The
connection of the sensors to the various measuring cables is explained in more detail in
the "Measuring cables and sensor connection" section.
pH/
Redox
A
pH
Ref.
Red.
PA/
PM
S
B
YE 11
WH
BK 12
CCS
120
90
Cl2
41
42
ClO2
85
GN
C
43
47
48
15 V
86
D
32
33
57
58
mA
Cl2
ClO2
F
G
BK
10–50 V
mA
34
53
81
82
54
55
56
93
23
H
BN
BU
24
94
85
C
L
59
51
52
E
*
K
49
BN
31
J
M
N
O
mA
15 V
~ =
L1L+
N L–
86
P
A0001904
11
Endress+Hauser
Electrical connection of the transmitter (version 2)
A
pH/ORP input (optional)
*
Auxiliary voltage of terminal 85/86 can be used
B
Sensor CCS120
J
Alarm (current-free contact position)
C
Auxiliary voltage output
K
Relay 1 (current-free contact position)
D
Signal output 1, total chlorine
L
Relay 2 (current-free contact position)
E
Signal output 2, temperature, pH or ORP
M
Relay 3 (current-free contact position)
F
Binary input 1 (hold/cleaning)
N
Relay 4 (current-free contact position)
21
Electrical connection
Liquisys M CCM223/253
G
Proximity switch INS
O
Current input 4 to 20 mA
H
Binary input 2
P
Power connection
The device is approved for protection class II and is generally operated without a
protective ground connection. Circuits "E" and "C" are not galvanically isolated from
each other.
5.4
Device connection
Field device connection
Proceed as follows to connect the field device:
1.
Open the housing cover to access the terminal block in the connection compartment.
2.
Break through the perforation for a cable gland, mount a Pg gland and guide the
cable through this Pg gland.
3.
Connect the cable in accordance with the terminal assignment.
4.
Tighten the Pg gland again.
NOTICE
Non-observance could cause incorrect measurement.
‣ Make absolutely sure to protect the cable ends and terminals from moisture.
‣ Terminals marked NC may not be connected.
‣ Unmarked terminals may not be connected.
REL 4
pH / Redox
SENSOR
REL 2
REL 1
Contacts:
max. 2A
AC: 250V/500VA
DC: 30V/60W
54 55 56 51 52 53 57 58 59 47 48 49 41 42 43
Mains
Hilfsenergie
REF
90 12
PA/PM
BN BN
REL 3
NC
NC 31 32 33 34 NC 85 86 93 94 81 82 23 24 NC
+ - + + - +
- +
- +
4..20mA
Digital 1
Digital 2
(INS)
11
+15V
10mA
91/A
Temp.
pH/Redox
(opt.)
12
(963:92/K)
90/K
Cl 2
ClO 2
91 11 92 S
(BU) GN (RD)
L1 N (AC)
+
- (DC)
CCM 253
131194-4D
A0002276
12
Field device connection compartment sticker
Please label the sensor terminal block with the sticker provided.
Panel-mounted device connection
To connect the panel-mounted device, connect the cables in accordance with the terminal
assignment to the terminals on the rear of the device.
22
Endress+Hauser
Liquisys M CCM223/253
Electrical connection
Sensor
BNC: pH/Redox + REF
47
31 +
COM 48
32 -
REL1
59
33 +
57
34 -
COM 58
REL2
Cl2
ClO2
Temp.
pH
Redox
(opt.)
(REF)
92 K 963 RD
12
BN
GN
NC
11
53
85 +
91 A
51
86 -
COM 52
93 +
REL3
REL4
56
94 -
54
81 +
82 -
24
NC
+ 23
NC
4..20mA
Digital 2
(INS)
963 BU
CCS..
90 K
S
42
43
Digital 1
COM 55
-
+15V
10mA
BN
PA/PM
Contacts: max. 2A, AC:250V/500VA, DC:30V/60W
49
131192-4C
41
AC DC
L1 +
N
-
Mains
131084-4C
A0002277
13
Panel-mounted device connection sticker
NOTICE
Non-observance could cause incorrect measurement.
‣ Make absolutely sure to protect the cable ends and terminals from moisture.
‣ Terminals marked NC may not be connected.
‣ Unmarked terminals may not be connected.
Please label the sensor terminal block with the sticker provided.
Endress+Hauser
23
Electrical connection
Liquisys M CCM223/253
5.5
Measuring cables and sensor connection
Sensor type
Cable
Extension
Chlorine/chlorine dioxide sensors
CCS140 / 141 / 240 / 241
3 m (9.8 ft) CMK, permanently connected VBC box + CMK
Chlorine sensor 963
-
Temperature sensor for chlorine sensor 963
CPK1
Total chlorine sensor CCS120
CPK9-N*A1B
VBC box + CYK71
pH or ORP sensor without temperature
sensor
CPK1 for sensors with GSA plug-in head
CPK9 for sensors with ESA plug-in head
VBC box + CYK71
VBC box + MK
Connecting the chlorine sensors CCS140 / 141 / 240 /241
The sensors are equipped with a 3 m (9.8 ft) fixed cable. Connect the sensors to the
transmitter according to the following diagram:
Sensor with 3 m fixed cable
Transmitter
Assignment
Core
Outer shield
Terminal
S
Anode
[A] red
91
Cathode
[K]
90
NTC temperature sensor
green
11
NTC temperature sensor
brown
12
Connecting the total chlorine sensor CCS120
Connect the sensor with the measuring cable CPK9-N*A1B (with internal PML) according
to the following connection diagram:
Cable with TOP68 connection
Transmitter
Pin
Assignment
Core
Terminal
1
TC signal
Coax, inside (white)
90
2
AGND
Coax, outside (black)
12
4
+UB (15 V)
green
85
5
NTC1
yellow*
11
NTC1
white*
11
6
NTC2/AGND
brown
86
S
Shielding
S
S
3
* The white and yellow wires are interconnected in the TOP68 connector.
24
Endress+Hauser
Liquisys M CCM223/253
Electrical connection
5
4
4
5
6
3
2
1
3
6
1
2
A0026048
14
TOP68 connection; pin arrangement of connector and coupling (shown from contact side)
Connecting the chlorine sensor 963
The chlorine sensor 963 is supplied without a temperature sensor ex factory. Connect the
chlorine sensor to the transmitter as follows:
• Without temperature measurement:
Connect the 10 kΩ equivalent resistor supplied to terminals 11 and 12. The measured
value display will then constantly show 25 °C (77 °F).
• With temperature measurement:
Mount an NTC temperature sensor 10 kΩ / 25 °C (77 °F) (120 mm installation version
TSP 3692) in the chlorine sensor 963. Use the CPK1 connecting able to connect the
temperature sensor to terminals 11 and 12.
• Chlorine sensor:
Connect the red cable to terminal 92 (cathode) and the blue cable to terminal 91
(anode).
Connection of pH or ORP sensors
Connect the pH or ORP sensor always symmetrically to prevent a mutual interference of
several sensors mounted in the CCA250 assembly.
Symmetrical connection requires a potential matching pin. The pin is integrated as
standard in the CCA250 flow assembly and is connected by a PML to the PA/PM terminal.
CPK1
PM
pH / Redox
Coax Ref.
pH or Redox
BN PM
PM
CPK9
pH + Pt 100 / Pt 1000
Coax BK Ref.
inner pH
GN Temp.
WH Temp.
YE Temp.
BN PM
A0002330-EN
15
Endress+Hauser
Connection of the pH or ORP sensor to the field instrument with the cables CPK1 or CPK9
25
Electrical connection
Liquisys M CCM223/253
If you are using glass electrodes with the panel-mounted device, you have to terminate the
measuring cable with a BNC connector. A solder-free BNC connector is supplied with the
device. To do this, proceed as follows:
1.
Cut off end ferrules 2 and 3 of the coaxial cable.
2
3
1
4
A0005744
16
1
2
3
4
2.
Push the cable gland 5 and the washer 6 onto the
coaxial cable.
3.
Remove the insulation (13 mm (0.51")) and screw the
clamping ring 7 onto the insulation.
Coax cable
Inner shield BK (ref)
Inner coax (pH / mV)
Strand BN (PA)
Parts 5 to 7 are supplied with the BNC
connector for cable diameters 3.2 mm and
5 mm.
4.
Fold the braided shield 8 of the shield over the
clamping ring and cut off the excess material.
5.
There is a semiconductor layer 14 (conductive
membrane) between the inner insulation and the
braided shield 8. Strip this semiconductor layer as far
as the braided shield.
Cable CPK1: device connection
5
6
5
6
7
13 (0.51)
16 (0.63)
14
8
A0005745
17
6.
Terminating the pH connecting cable for
mounting the BNC elbow plug. Dimensions in
mm (inch)
Remove the inner insulation (4 mm (0.16")), fit end
ferrule 13 on the stripped inner conductor and secure
the end ferrule with a crimping pliers.
13
4 (0.16)
A0005746
18
7.
Push the BNC connector housing 9 over the cable. The
inner conductor must be located on the clamping
surface 10 of the connector.
8.
Tighten the cable gland 5.
9.
Insert the clamp element 11 and screw in the
connector cover 12. This creates a safe connection
between the inner conductor and the connector pin.
Terminating the pH connecting cable for
mounting the BNC elbow plug. Dimensions in
mm (inch)
9
5
10
11
12
A0005747
19
26
Mounting the pH connecting cable in the BNC
elbow plug
Endress+Hauser
Liquisys M CCM223/253
Electrical connection
Sensor
Maximum cable length
Chlorine/chlorine dioxide sensors CCS140/141/240/ 241
Max. 30 m (98.4 ft) with cable CMK
Chlorine sensor 963
Max. 30 m (98.4 ft) with cable MK
Total chlorine sensor CCS120
Max. 15 m (49.2 ft) with cable CYK71
pH/ORP measurement
Max. 50 m (164 ft) with cable CYK71
Use the junction box VBC and the appropriate extension cable to extend the measuring
cable.
5 x Pg 7
52 (2.05)
B
A
B
2 x Pg 7
2 x Pg 11
113 (4.45)
125 (4.92)
54 (2.13)
A0005740
20
A
B
Junction box VBC with grounding point
View in arrow direction
2 fixing bore holes Ø 4.5 mm (0.18")
1
3
2
4
2
1
3
BN
GN
8
5
7
7
6
5
4
6
A0002332
A0002331
21
1
2
3
4
5
6
7
8
Structure of cable CMK
Outer shield
Inner shield, anode
Semi-conductor layer
Inner insulation
Inner conductor, measuring signal
Temperature sensor connection
2nd insulation
Outer insulation
22
1
2
3
4
5
6
7
Structure of cable CYK71
Outer shield
Inner shield, reference signal
Inner insulation
Inner conductor, measuring signal
Semi-conductor layer
2nd insulation
Outer insulation
NOTICE
Incorrect measurement due to short-circuit
‣ Make sure to remove the black semiconductor layer as far as the inner shield when
connecting cable CMK and CYK71.
Endress+Hauser
27
Electrical connection
Liquisys M CCM223/253
5.6
Three-point step controller for Cl2 / ClO2 / total
chlorine
Connect the continuously variable motor valves as follows:
28
1.
Connect the NO contact of the motor valve to relay 3.
2.
Connect the NC contact of the motor valve to relay 4.
Endress+Hauser
Liquisys M CCM223/253
Electrical connection
5.7
Alarm contact
A
B
41
41
42
42
43
43
A0006415
23
A
B
Recommended fail-safe switching for the alarm contact
Normal operating status
Alarm condition
Normal operating status
Alarm condition
Device in operation and no error message
present (alarm LED off):
• Relay energized
• Contact 42/43 closed
Error message present (alarm LED red) or device
defective or de-energized (alarm LED off):
• Relay de-energized
• Contact 41/42 closed
5.8
Post-connection check
Carry out the following checks once you have made the electrical connection:
Device state and specifications
Notes
Are the devices and cables free from damage on the outside?
Visual inspection
Electrical connection
Notes
Are the mounted cables strain relieved?
Are the connected cables provided with strain relief?
Is the cable run correct, without loops and cross-overs?
Are the power cable and signal cables connected correctly and in
accordance with the wiring diagram?
Are all the screw terminals tightened?
Are all the cable entries fitted, tightened and leak-proof?
Endress+Hauser
29
Operation options
Liquisys M CCM223/253
6
Operation options
6.1
Quick operation guide
You have the following ways of operating the transmitter:
• On site via the key field
• Via the HART interface (optional, with corresponding order version) with:
– HART handheld terminal
– PC with HART modem and the Fieldcare software package
• Via PROFIBUS PA/DP (optional, with corresponding order version) by PC with a
corresponding interface and the Fieldcare software package or via a programmable logic
controller (PLC).
For operation via HART or PROFIBUS PA/DP, please read the relevant sections in the
additional Operating Instructions:
• PROFIBUS PA/DP, field communication for Liquisys M CXM223/253,
BA00209C/07/EN
• HART, field communication for Liquisys M CXM223/253, BA00208C/07/EN
The following section only explains operation via the keys.
6.2
Display and operating elements
6.2.1
Display
LED displays
Indicates the current operating mode, "Auto" (green LED) or
"Manual" (yellow LED)
A0027220
Indicates the activated relay in the "Manual" mode (red LED)
The status of relays 3 and 4 is indicated on the LC display.
A0027222
A0027221
A0027218
30
Indicates the working status of relay 1 and 2
LED green: measured value within the permitted limit, relay
inactive
LED red: measured value outside the permitted limit, relay active
Alarm display, e.g. in event of continuous limit value overshoot,
temperature sensor failure or system error (see error list)
Endress+Hauser
Liquisys M CCM223/253
Operation options
LC display
1
2
13
11
5
4
042
14
12
3
mg/l
R242
Setpoint
10
6
7
8
9
A0001924-EN
Endress+Hauser
24
Transmitter LC display
1
Indicator for measuring mode (normal operation)
2
Indicator for calibration mode
3
Indicator for setup mode (configuration)
4
Indicator for "Hold" mode (current outputs remain at last current state)
5
Indicator for receipt of a message on devices with communication
6
Indicator of working status of relays 3/4:
7
Function code
inactive,
active
8
In measuring mode: measured variable - in setup mode: configured variable
9
In measuring mode: secondary measured value - in setup/calibr. mode: e.g. set value
10
Indicator for autom. Temperature compensation
11
Indicator for man. Temperature compensation
12
"Error": error display
13
Temperature offset
14
Sensor symbol (see the "Calibration" section)
31
Operation options
Liquisys M CCM223/253
6.2.2
Operating elements
The display shows the current measured value and the temperature simultaneously, which
means you have an overview of the most important process data at once. Help text in the
configuration menu helps users configure the device parameters.
1
2
7
3
4
6
5
A0024631-EN
25
1
2
3
4
5
6
7
Operating elements
LC display for displaying the measured values and configuration data
Key to switch relays in manual mode and to display the active contact
LED for alarm function
Changeover switch for automatic/manual mode
LEDs for limit contactor relay (switch status)
Main operating keys for calibration and device configuration
Field for user-defined information
6.2.3
Key functions
CAL key
A0027235
When you press the CAL key, the device first prompts you for the
calibration access code:
• Code 22 for calibration
• Code 0 or any other code for reading the last calibration data
Use the CAL key to accept the calibration data or to switch from
field to field within the calibration menu.
ENTER key
A0027236
When you press the ENTER key, the device first prompts you for the
setup mode access code:
• Code 22 for setup and configuration
• Code 0 or any other code for reading all the configuration data.
The ENTER key has several functions:
• Calls up the Setup menu from the measuring mode
• Saves (confirms) data entered in the setup mode
• Moves on within function groups
32
Endress+Hauser
Liquisys M CCM223/253
Operation options
PLUS key and MINUS key
A0027240
In the Setup mode, the PLUS and MINUS keys have the following
functions:
• Selection of function groups.
Press the MINUS key to select the function groups in the order
given in the "System configuration" section.
• Configuration of parameters and numerical values
• Operation of the relays in manual mode
In the measuring mode, the following sequence of functions is
accessed by repeatedly pressing the PLUS key:
• Temperature displayed in °F
• Temperature is hidden
• pH measured value or ORP (only for EP version)
• pH sensor signal in mV (only for EP version)
• Sensor current of chlorine/chlorine dioxide sensor in nA
• Zero current of sensor CCS120
• Current input signal in %
• Current input signal in mA
• Return to basic settings
In the measuring mode, the following sequence of information is
displayed by repeatedly pressing the MINUS key:
• The current errors are displayed consecutively (max. 10).
• Once all the errors have been displayed, the standard
measurement display appears. In the function group F, an alarm
can be defined separately for each error code.
A0027241
A0027234
REL key
In the manual mode, you can use the REL key to switch between the
relay and the manual start of cleaning.
In automatic mode, you can use the REL key to read out the switchon points (for limit contactor) or set points (for PID controller)
assigned to the relay in question.
Press the PLUS key to jump to the settings of the next relay. Use the
REL key to get back to the display mode (automatic return after
30 s).
AUTO key
Use the AUTO key to switch between automatic mode and manual
mode.
Escape function
If you press the PLUS and MINUS key simultaneously, you return to
the main menu, or are taken to the end of calibration if calibrating.
If you press the PLUS and MINUS key again, you return to the
measuring mode.
A0027237
Endress+Hauser
33
Operation options
Liquisys M CCM223/253
Locking the keyboard
Press the PLUS and ENTER key simultaneously for at least 3 s to
lock the keyboard against any unauthorized data entry. All the
settings can continue to be read.
The code prompt displays the code 9999.
A0027238
Unlocking the keyboard
Press the CAL and MINUS key simultaneously for at least 3 s to
unlock the keyboard.
The code prompt displays the code 0.
A0027239
34
Endress+Hauser
Liquisys M CCM223/253
Operation options
6.3
Local operation
6.3.1
Automatic/manual mode
The transmitter normally operates in automatic mode. Here, the relays are triggered by
the transmitter. In the manual mode, you can trigger the relays manually using the REL
key or start the cleaning function.
How to change the operating mode:
1.
The transmitter is in automatic mode. The top LED (green)
next to the AUTO key is lit.
2.
Press the AUTOMATIC key.
3.
To enable the manual mode, enter the code 22 via the PLUS
and MINUS keys and press ENTER to confirm.
The lower LED (manual mode) is lit.
4.
Select the relay or the function.
You can use the REL key to switch between the relays. The
relay selected and the switch status (ON/OFF) is displayed on
the second line of the display.
In the manual mode, the measured value is displayed
continuously (e.g. for measured value monitoring for dosing
functions).
5.
Switch the relay. The relay is switched on with PLUS and
switched off with MINUS.
The relay remains in this switched state until it is switched
again.
6.
Press the AUTOMATIC key to return to the measuring mode,
i.e. to the automatic mode.
All the relays are triggered again by the transmitter.
A0027242
A0027243
A0027240
A0027241
A0027240
A0027234
• The operating mode remains in effect even after a power failure. The relays assume
the quiescent state, however.
• The manual mode has priority over all other automatic functions.
• Hardware locking is not possible in the manual mode.
• The manual settings are kept until they are actively reset.
• Error code E102 is signaled during manual operation.
Endress+Hauser
35
Operation options
Liquisys M CCM223/253
6.3.2
Operating concept
Operating modes
Measuring mode:
standard mode of
operation, displaying
current measured values
Setup mode
access to all
configuration
settings
Calibration mode:
execution of
calibration routine
Code
The function groups
are selected with the
PLUS or MINUS key.
A0027244-EN
26
Description of the possible operating modes
If no key is pressed in the setup mode for approx. 15 min, the device automatically
returns to the measuring mode. Any active hold (hold during setup) is canceled.
Access codes
All device access codes are fixed and cannot be altered. When the device requests the
access code, it distinguishes between different codes.
• CAL key + code 22: access to Calibration and Offset menu
• ENTER key + code 22: access to the menus for the parameters which make
configuration and user-specific settings possible
• PLUS + ENTER keys simultaneously (min. 3 s): lock the keyboard
• CAL + MINUS keys simultaneously (min. 3 s): unlock the keyboard
• CAL or ENTER key + any code: access to read mode, i.e. all the settings can be read but
not modified.
The device continues measuring in the read mode. It does not shift to the "Hold" status.
The current output and the controllers remain active.
36
Endress+Hauser
Liquisys M CCM223/253
Operation options
Menu structure
The configuration and calibration functions are arranged in function groups.
• In the setup mode, select a function group with the PLUS and MINUS keys.
• In the function group itself, switch from function to function with the ENTER key.
• Within the function, select the desired option with the PLUS and MINUS keys or edit the
settings with these keys. Then confirm with the ENTER key and continue.
• Press the PLUS and MINUS keys simultaneously (Escape function) to exit programming
(return to the main menu).
• Press the PLUS and MINUS keys simultaneously again to switch to the measuring mode.
If a modified setting is not confirmed by pressing ENTER, the old setting is retained.
An overview of the menu structure is provided in the Appendix to these Operating
Instructions.
1
-
2
3
E
E
E
E
E
A0027245
27
1
2
3
Menu structure
Functions (selection of parameters, entry of numbers)
Function groups, scroll backwards and forwards with the PLUS and MINUS keys
Switch from function to function with the ENTER key
Hold function: "freeze" the outputs
In both the setup mode and during calibration, the current output can be "frozen" (factory
setting), i.e. it constantly retains its current status. "HOLD" appears on the display. If the
controller actuating variable (steady control 4 to 20 mA) is output via current output 2, it
is set to 0/4 mA during a hold.
• Hold settings can be found in the "Service" function group.
• During a hold, all contacts assume a quiescent state.
• An active hold has priority over all other automatic functions.
• With every hold, the I-component of the controller is set to "0".
• Any alarm delay is reset to "0".
• This function can also be activated externally via the hold input (see Wiring diagram;
binary input 1).
• A manual hold (field S3) remains active even after a power failure.
Endress+Hauser
37
Commissioning
Liquisys M CCM223/253
7
Commissioning
7.1
Function check
LWARNING
Incorrect connection, incorrect supply voltage
Safety risks for staff and device malfunctions
‣ Check that all connections have been established correctly in accordance with the
wiring diagram.
‣ Ensure that the supply voltage matches the voltage indicated on the nameplate.
7.2
Switching on
Familiarize yourself with the operation of the transmitter before it is first switched on. In
particular please read the "Basic safety instructions" and "Operation options" sections. After
power-up, the device performs a self-test and then goes to the measuring mode.
Now calibrate the sensor in accordance with the instructions in the "Calibration" section.
During initial commissioning, the sensor must be calibrated so that the measuring
system can return precise measurement data.
Then perform the first configuration in accordance with the instructions in the "Quick
setup" section. The values set by the user are kept even in the event of a power failure.
The following function groups are available in the transmitter (the groups that are only
available in the Plus Package are marked accordingly in the functional description):
Setup mode
• SETUP 1 (A)
• SETUP 2 (B)
• CURRENT INPUT (Z)
• CURRENT OUTPUT (O)
• ALARM (F)
• CHECK (P)
• RELAY (R)
• SERVICE (S)
• E+H SERVICE (E)
• INTERFACE (I)
Calibration and offset mode
CALIBRATION (C)
A detailed explanation of the function groups available in the transmitter can be
found in the "Device configuration" section.
2
s
F3
Err.delay
Function display:
The displayed code indicates
the function position in the
function group.
Additional information
A0025560-EN
28
38
Information for the user on the display
Endress+Hauser
Liquisys M CCM223/253
Commissioning
C131
C132
C133
C121
C
C1
C111
To make it easier for you to select and find function
groups and functions, a code for the corresponding
field is displayed for each function → 28
The structure of this code is illustrated in → 29.
The function groups are indicated as letters in the first
column (see the names of the function groups). The
functions of the individual groups are displayed
incrementally by row and by column.
A0027502
29
Function code
Factory settings
The first time the device is switched on, the factory setting is set for all the functions. The
table below provides an overview of the most important settings.
All other factory settings can be found in the description of the individual function groups
in the "System configuration" section (the factory setting is highlighted in bold).
Function
Factory setting
Type of measurement
Concentration of free chlorine/total chlorine in
mg/l
Temperature measurement in °C
pH value (EP version)
Sensor setting
CCS140 for free chlorine
Alarm contact
Steady contact
Alarm delay
Setting in minutes
Error current for alarm
22 mA
Check functions*
Off. Can be switched on if required
Limit value 1 and 2 for chlorine/chlorine dioxide
0.5 mg/l
Limit value 1 and 2 for pH*
pH 7.2
Limit value 1 and 2 for ORP*
750 mV
Limit value 1 and 2 for temperature
50 °C
Current outputs 1 and 2
4 to 20 mA
Current output 1: measured value for 4 mA signal current
0.00 mg/l
Current output 1: measured value for 20 mA signal current
2.00 mg/l
Current output 2: temperature value for 4 mA signal current*
0 °C
Current output 2: temperature value for 20 mA signal current* 50 °C
* with appropriate version
Endress+Hauser
39
Commissioning
Liquisys M CCM223/253
7.3
Quick Setup
After power-up, you must make some settings to configure the most important functions
of the transmitter which are required for correct measurement. The following section gives
an example of this.
User entry
1.
Press the ENTER key
2.
Enter the code 22 to open access to the menus.
Press the ENTER key.
3.
Press the MINUS key until you get to the "Service"
function group.
4.
Press ENTER to be able to make your settings.
Range of
adjustment
(factory settings in
bold)
Display
S
SERVICE
A0008408-EN
5.
Select your language in S1, e.g. "ENG" for English.
Press ENTER to confirm your entry.
ENG = English
GER = German
FRA = French
ITA = Italian
NEL = Dutch
ESP = Spanish
ENG
S1
Language
A0008409-EN
6.
Press the PLUS and MINUS key simultaneously to
exit the "Service" function group.
7.
Press the MINUS key until you get to the "Setup 1"
function group.
8.
Press ENTER to be able to make your settings for
"Setup 1".
A
SETUP 1
A0007824-EN
9.
In A1, select the desired sensor type.
Press ENTER to confirm your entry.
120 = CCS120
140 = CCS140
141 = CCS141
240 = CCS240
241 = CCS241
963
140 A1
Sensor
A0001954-EN
10.
In A2, select the desired engineering unit.
Press ENTER to confirm your entry.
mg/l
ppm
ppb
mg/l A2
Unit
A0024894-EN
11.
If you have connected the INS proximity switch, you Off
can switch on flow monitoring of the sample
INS
stream through the CCA250 assembly in A3.
Press ENTER to confirm your entry.
Off A3
Cont.stop
A0001956-EN
12.
If flow briefly falls below the threshold value, you
can suppress controller switch-off by entering a
delay time in A4.
Press ENTER to confirm your entry.
0s
0 to 2000 s
s
0 A4
Off Delay
A0001957-EN
40
Endress+Hauser
Liquisys M CCM223/253
Commissioning
User entry
Range of
adjustment
(factory settings in
bold)
13.
In A5, enter the delay time for controller switchon.
In the case of chlorine/chlorine dioxide control, a
delay until the reception of a representative
measured value is recommended after a long
period without flow.
Press ENTER to confirm your entry.
0s
0 to 2000 s
In A6, select the binary input.
Press ENTER to confirm your entry.
Hold = external
hold
Clean = cleaning
trigger
14.
Display
s
0 A5
On Delay
A0001958-EN
Hold A6
Digital 1
A0001959-EN
15.
16.
Endress+Hauser
In A7, enter the measured value damping.
Measured value damping causes the measured
value to be averaged over the specified number of
individual measured values (if A7 = 1, no damping
takes place).
Press ENTER to confirm your entry.
The display returns to the initial display of the
"Setup 1" function group.
1
1 to 60
1 A7
Damping
A0001960-EN
Press PLUS and MINUS simultaneously to switch to
the measurement mode.
41
Commissioning
Liquisys M CCM223/253
7.4
Device configuration
7.4.1
Setup 1 (chlorine/chlorine dioxide)
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
A
Configuration of basic
functions
SETUP 1 function
group
A
SETUP 1
A0007824-EN
A1
Select the connected
sensor type
120 = CCS120
140 = CCS140
240 = CCS240
241 = CCS241
963
Select the display
unit
mg/l
ppm
ppb
140 A1
Sensor
If the device is reset in
field S9, the configured
sensor type is not
modified.
A0001954-EN
A2
mg/l A2
Unit
A0001955-EN
A3
A4
Select flow
Off
monitoring of the
INS
sample flow through
the CCA250
assembly (with
controller switchoff)
Enter the delay for
controller switch-off
by the sample flow
0s
0 to 2000 s
Enter the delay for
controller switch-on
by the sample flow
0s
0 to 2000 s
Off A3
Cont.stop
May only be switched on
when the INS proximity
switch is connected.
A0001956-EN
s
0 A4
Off Delay
Brief flow shortfalls can
be suppressed by this
delay and do not result in
controller switch-off.
A0001957-EN
A5
s
0 A5
On Delay
A0001958-EN
A6
Select binary input 1
Hold = external
hold
Clean = cleaning
trigger
In the case of chlorine/
chlorine dioxide control, a
delay until the reception
of a representative
measured value is
recommended after a
long period without flow.
Hold A6
Digital 1
A0001959-EN
A7
Enter the value for
measured value
damping
1
1 to 60
1 A7
Damping
A0001960-EN
42
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Flow monitoring in the sample stream
If the flow falls below 30 l/h or if sample flow through the CCA250 assembly fails
completely, this causes an alarm to be signaled when an INS proximity switch is connected.
This alarm becomes active when the switch-off delay time elapses (A4 field). The alarm is
canceled immediately as soon as the necessary rate of flow is restored. The device
automatically stops the dosing of chemicals and the Chemoclean cleaning function for the
duration of the alarm. All the relays assigned to the PID controller or to a cleaning function
go to the quiescent state. The NO contact closes in the case of the three-point step
controller. Dosing and cleaning actions are only resumed once the switch-on delay time
has elapsed (A5 field).
1
A
0
1
B
A4
A5
0
1
A4
A5
C
0
1
D
0
E
F
G
A0002018
30
A
B
C
D
E
F
G
0
1
A4
A5
Endress+Hauser
Alarm signaling and dosing switch-off by the sample stream
Flow in sample stream
Relay contacts of PID controller
NO contact on three-point step controller
Alarm relay
Flow < 30 l/h or flow failure
Flow alarm
Flow restored
Off
On
Field A4 (controller switch-off delay)
Field A5 (controller switch-on delay)
43
Commissioning
Liquisys M CCM223/253
7.4.2
Setup 2 (temperature or pH/ORP)
Use this function group to change the settings for temperature measurement and pH/ORP
measurement.
You already made all the settings for this function group during initial commissioning.
However, you can change the values chosen at any time.
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
B
Initial display screen in the
SETUP 2 function group
SETUP 2
function group
B
SETUP 2
A0007830-EN
B1
Select operating
mode
Off
pH
ORPmV
Off B1
Oper.Mode
A0001963-EN
B2
Select pH
compensation
Off
Manu
Auto
Off B2
pH comp.
Field only available for EP
version.
ORPmV = ORP (oxidationreduction potential) in mV.
When the operating mode is
changed, all user settings are
automatically reset to the basic
settings.
If the device is reset in field
S9, the configured operating
mode is not modified.
Field only available for ES and
EP versions. (operation with
CCS140/141)
A0001964-EN
B3
Enter the value
for manual pH
compensation
Last
compensation
value
pH 4.00 to 9.00
pH
7.20 B3
Manu.Comp
The field is only displayed if »
manual« (Manu) was selected
in the B2 field.
The measured pH value is
displayed as the secondary
parameter.
A0001965-EN
B4
Enter the
process
temperature
Current
measured value
0 to 50 °C
¡C
0.0 B4
RealTemp.
A0001966-EN
B5
Enter the
temperature
differential
(offset)
Current offset
-5.0 to 5.0 °C
¡C
0.0 B5
Temp.Offs
You can edit the displayed
value.
The value can be changed by a
maximum of ±5 °C.
As the measurements are very
accurate, the value generally
does not need to be adjusted.
The offset is the difference
between the actual value
entered and the measured
temperature.
A0007835-EN
Types of chlorine
A distinction is made between free chlorine and combined chlorine.
Free chlorine
44
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Free chlorine is understood as the sum of elementary chlorine (Cl2), hypochlorous acid
(HOCl) and hypochlorite ions (OCl–). These forms of chlorine are able to kill bacteria,
inactivate viruses and oxidize organic substances within a short period of time.
Combined chlorine
Combined chlorine refers to the forms of chlorine in water and consists of chemical
compounds made up of chlorine and ammonia (NH3) or ammonium (NH4 +) entstehen.
Combined chlorine still has a disinfectant property, but far less than that of free chlorine.
Total chlorine
Total chlorine is the sum of free chlorine and combined chlorine.
Measuring free chlorine with the CCS140 and CCS141 sensors
Molecular chlorine (Cl2) is present at pH values < 4. Consequently, hypochlorous acid
(HOCl) and hypochlorite (OCl– remain as components of free chlorine within the range of
pH 4 to 11.
As hypochlorous acid splits up (dissociates) with an increasing pH value to form
hypochlorite ions (OCl–) and hydrogen ions (H+), the amounts of the individual
components of free effective chlorine change with the pH value. For example, if the
amount of hypochlorous acid is 97% at pH 6, it drops to approx. 3% at pH 9.
100
A
0
%
80
20
60
40
OCl-
HOCl
C
40
60
B
20
80
%
100
0
4
5
6
7
8
pH
9
10
11
A0002017
31
A
B
C
Basic representation of pH compensation
Measured value with pH compensation
Measured value without pH compensation
pH compensation
The CCS140 or CCS141 chlorine sensors selectively measure the amount of hypochlorous
acid in amperometric measurement.. This works as a powerful disinfectant in a watery
solution. In contrast to this, hypochlorite is an extremely weak disinfectant. Therefore,
when used as a disinfectant at higher pH values, the effectiveness of chlorine is limited. As
hypochlorite ions cannot permeate the sensor membrane, the sensors do not record this
value.
Measuring total chlorine with the CCS120 sensor
If, in addition to free available chlorine, ammonium is also present in the medium preferably water - chloramines (ClnNHm) form quickly. This compound is formed in various
Endress+Hauser
45
Commissioning
Liquisys M CCM223/253
degrees of dimerization. It is known as "combined chlorine". Combined chlorine has a lower
disinfecting effect but it forms larger depots compared to free chlorine. This means:
• Significantly slower elimination of existing germs.
• Disinfectant effect over considerably longer periods.
• Disinfectant effect over considerably longer transport distances.
The CCS120 amperometric sensor measures the total chlorine content, i.e. free chlorine as
well as chloramine components.
This type of measurement is only slightly pH dependent.
pH compensation of the chlorine sensor signal during free chlorine measurement
(only for ES and EP versions, for CCS140/141 sensors)
To calibrate and verify the chlorine measuring system, a colorimetric reference
measurement must be carried out using the DPD method. Free chlorine reacts with
diethyl-p-phenylendiamine to form a red dye. The intensity of the red color increases
proportionally to the chlorine content. With the DPD method, the water under
measurement is constantly buffered to a pH value of approx. 6.3. Therefore, the pH value
of the water under measurement is not included in the DPD measurement here. Due to the
buffer function in the DPD method, all components of free effective chlorine are recorded
and thus the total free chlorine is measured.
If you select pH compensation in fields B2 or B3, the sum of hypochlorous acid and
hypochlorite corresponding to the DPD measurement is calculated from the hypochlorous
acid measured by the sensor and the pH value in the region of pH 4 to 9. For this
calculation, the curve is stored in the transmitter.
When free chlorine is measured with pH compensation switched on, always perform
calibration in pH-compensated mode.
When you use pH compensation, the measured chlorine value that is displayed and applied
to the device output corresponds to the DPD measured value even if the pH values
fluctuate. If you do not use pH compensation, the measured chlorine value corresponds to
the DPD measurement only if the pH value remains unchanged compared with the
calibration. Without pH compensation, the chlorine measuring system must be
recalibrated when the pH value changes.
pH compensation can be performed both automatically using the connected pH electrode
(EP version) and manually (ES version) by entering the pH value in the B3 field.
Chlorine dioxide and total chlorine measurement is largely or entirely independent of the
pH value and therefore no pH compensation is required.
Accuracy of pH compensation when measuring free chlorine
The accuracy of the pH-compensated measured chlorine value is derived from the sum of
several individual deviations (chlorine, pH, temperature, DPD measurement etc.).
High levels of hypochlorous acid (HOCl) during chlorine calibration have a positive effect
on accuracy, whereas low levels of hypochlorous acid have a negative effect.
The inaccuracy of the pH-compensated measured chlorine value increases the greater the
pH difference between measuring mode and chlorine calibration or the more inaccurate
the underlying individual measured values are.
Calibration of free chlorine taking the pH value into consideration
The reference measurement (DPD method, photometer) determines the total free chlorine
by buffering to pH 6.2. In contrast to this, amperometric measurement determines only
the HOCl component.
During operation, pH compensation is effective up to a pH value of 9. However, there is
hardly any HOCl left at this pH value, and the measured current is very low. At this point,
pH compensation has the effect of increasing the measured HOCl value to the actual value
of the free chlorine.
46
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Calibration of the complete measuring system makes sense only up to a pH value of the
medium of 8 or 8.2.
Sensor
pH value
HOCl content
Uncompensated value
Compensated value
CCS141
8.2
15 %
12 nA
80 nA
CCS140
8
20 %
4 nA
20 nA
Above these pH values, the total error of the measuring system is unacceptably high.
7.4.3
Current input
For the "Current input" function group, you require a relay card with a current input which
is not available in the basic device version. With this function group, you can monitor
process parameters and use them for feedforward control. For this purpose, you must
connect the current output of an external measured variable (e.g. flowmeter) to the 4 to
20mA input of the transmitter. The following assignment applies:
Flow in main stream
Current signal in mA
Current input signal in %
Flowmeter start of measuring range
4
0
Flowmeter end of measuring range
20
100
Flow monitoring in the main stream
This arrangement is particularly practical if the sample flow through the CCA250 assembly
is completely independent of the flow in the main stream.
This permits signaling of an alarm condition in the main stream (flow too low or has
completely stopped) and triggers dosing switch-off even if the medium flow is maintained
due to the method of installation.
This monitoring method corresponds to monitoring the flow rate in the sample stream
(see SETUP 1).
1
A
0
1
B
Z2
Z3
0
1
Z2
Z3
C
0
1
D
0
E
F
G
A0002019
32
Endress+Hauser
Alarm signaling and dosing switch-off by the main stream
A Flow in main stream
F
Flow alarm
B
G
Flow restoration
Relay contacts of PID controller
47
Commissioning
Liquisys M CCM223/253
C
NO contact on three-point step controller
Z2
Delay for controller switch-off, see field Z2
D
Alarm relay
Z3
Delay for controller switch-on, see field Z3
E
Flow below switch-off limit Z 4 or flow failure
0
Off
1
On
Feedforward control to PID controller
You can optimize control on control systems with very short response times by measuring
the medium flow rate in addition to the oxygen content. Then apply this flow rate value (4
to 20 mA) as feedforward control to the PID controller.
1
2
4
3
F
6
ENDRESS+HAUSER
LIQUISYS S
5
Cl2
pH
4 ... 20 mA
A0025120
33
Sample arrangement for feedforward control of the flow in the main stream to the PID controller
1
Medium tapping point
5
Flow assembly CCA250
2
Static mixer
6
Liquisys CCM253
3
Injection points
4
Flowmeter
Feedforward control is a multiplying function as illustrated in the figure below (example
with factory setting):
48
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Y
1.5
1
0.5
0
20
40
Z7
60
80
100
X
A0008942
34
Y
X
Endress+Hauser
Multiplying feedforward control
Gain Kinfl
Current input signal in [%]
49
Commissioning
Liquisys M CCM223/253
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory
settings in
bold)
Display
Info
Z
Current input settings
CURRENT INPUT
function group
Z
CUR.INPUT
A0024903-EN
Z1
Select flow
monitoring of main
stream (with
controller switchoff)
Off
On
Off Z1
Cont.stop
Flow monitoring may only be
switched on if the flowmeter is
connected in the main stream. If
Z1 = off, fields Z2 to Z5 are not
available.
A0024904-EN
Z2
Enter the delay for
controller switchoff through current
input
0s
0 to 2000 s
s
0 Z2
Off Delay
Brief flow shortfalls can be
suppressed by this delay and do
not result in controller switchoff.
A0024905-EN
Z3
Enter the delay for
controller switchon through current
input
0s
0 to 2000 s
s
0 Z3
On Delay
In the case of a controller, a
delay until the reception of a
representative measured value
is recommended after a long
period without flow.
A0024934-EN
Z4
Enter the switch-off 50 %
limit value for the
0 to 100 %
current input
%
50 Z4
A.Thresh
0 to 100% corresponds to 4 to
20 mA at the current input.
Observe measured value
assignment to the current
output of the flowmeter.
A0024935-EN
Z5
Enter the switch-off Low
direction for the
High
current input
Low Z5
Stop Dir
The controller is switched off if
the value entered in Z4 is
undershot or overshot.
A0024939-EN
Z6
Select feedforward
control to PID
controller
Off
Lin = linear
Basic
Off Z6
PID influ
A0024940-EN
Z7
Enter value for
50 %
feedforward control 0 to 100 %
at which gain = 1
applies
%
50 Z7
Kinflu=1
If Z6 = off, the field Z7 is not
available.
Z6 = basic: disturbance variable
only affects the basic load
(alternatively dosing in
proportion to quantity, if usual
PID controller not possible, e.g.
defective sensor).
When the value is set, the
controller actuating variable is
the same size when feedforward
control is switched on as when
feedforward control is switched
off.
A0024941-EN
50
Endress+Hauser
Liquisys M CCM223/253
Commissioning
7.4.4
Current outputs
Use the "Current output" function group to configure the individual outputs. You can enter
either a linear characteristic (O3 (1)) or a user-defined current output characteristic in
conjunction with the Plus Package (O3 (3)). Exception: if you have chosen a "continuous
controller" for current output 2, you cannot enter a user-defined current output
characteristic for this current output.
In addition, you can also simulate a current output value (O3 (2)) to check the current
outputs.
Cl
[mg/l]
2
Δ Signal
1
0
4
8
12
16
Δ[mA]
20
[mA]
A0002021
35
User-defined current output characteristic (example)
The current output characteristic must increase or decrease very monotonically.
The distance per mA between two table value pairs must be greater than:
Sensor/measurement parameter
Minimum distance per mA
CCS120
0.005 mg/l
CCS140/240
0.01 mg/l
CCS141/241 and 963
0.003 mg/l
pH
pH 0.03
ORP
5 mV
Temperature
0.25 °C
The values for the sample characteristic → 35 are entered in the following table. The
distance per mA is calculated from Δ signal / Δ mA.
Current output 1
Endress+Hauser
Current output 2
Value pair
Cl[mg/l]
Current
[mA]
Distance
per mA
1
0
4
2
0.5
14
0.05
3
2
20
0.25
.....[]
Current
[mA]
Distance
per mA
51
Commissioning
Liquisys M CCM223/253
First enter the desired current output configuration into the following blank table with a
pencil. Calculate the resulting signal distance per mA to observe the necessary minimum
slope. Then enter the values in the device.
Current output 1
Value pair
.....[]
Current
[mA]
Current output 2
Distance
per mA
.....[]
Current
[mA]
Distance
per mA
1
2
3
4
5
6
7
8
9
10
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
O
CURRENT
OUTPUT
function group
O
Configuration of the current
output (does not apply for
PROFIBUS).
OUTPUT
A0025026-EN
O1
Select current
output
Out 1
Out 2
Out1
A characteristic can be selected
for every output.
O1
Sel.Out
A0025027-EN
O2
Select measured °C
variable for 2nd Contr
current output
¡C O2
Parameter
A0025028-EN
O3 (1)
Enter the
characteristic
type
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
lin
O3
Sel.Type
A0025029-EN
52
pH or ORPmV only with EP
version and depending on
option selected in B1. R247 or
R257 =curr (current output 2)
can only be selected if
O2=Contr (controller output) is
selected.
The characteristic can have a
positive or negative slope for
the measured value output.
In the case of actuating
variable output (O2 = Contr),
an increasing current
corresponds to an increasing
actuating variable.
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
O311
4 to 20mA
0 to 20 mA
Select current
range
Display
Info
4-20
O311
Sel.Range
A0025030-EN
O312
O313
0/4 mA value:
Enter the
associated
measured value
20 mA value:
Enter the
associated
measured value
0 ppb
0 to 20000 ppb
0.00 ppm
0 to 20 ppm
0.00 mg/l
0 to 20 (5) mg/l
pH 4.00
pH 4 to 9
0 mV
0 to 1500 mV
0 °C
0 to 50 °C
2000 ppb
0 to 20000 ppb
2.00 ppm
0 to 20 ppm
2.00 (0.50) mg/l
0 to 20 (5) mg/l
pH 9.00
pH 4 to 9
1000 mV
0 to 1500 mV
50 °C
0 to 50 °C
mg/l
0.00 O312
0/4 mA
A0001944-EN
mg/l
2.00 O313
20 mA
A0001946-EN
Here you can enter the
measured value at which the
min. current value (0/4 mA) is
applied at the transmitter
output (not for controller).
For the minimum distance
between the 0/4 mA and 20
mA value, see field O313
This field is not displayed if O2
= Contr.
Here you can enter the
measured value at which the
max. current value (20 mA) is
applied at the transmitter
output.
The minimum distance
between the 0/4 mA and 20
mA value must be as follows:
•
•
•
•
•
•
140/240: 0.2 mg/l
141/241/963: 0.05 mg/l
120: 0.1 mg/l
pH: pH 0.5
ORP: 100 mV
Temperature: 5 °C
This field is not displayed if O2
= Contr.
O3 (2)
Simulate
current output
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
sim
O3
Sel.Type
Simulation is not ended until
O3(1) or O3(3) is selected.
For further characteristics, see
O3 (1), O3 (3).
A0025039-EN
O321
Enter
simulation
value
Current value
0.00 to 22.00 mA
mA
10.20 O321
Simulat.
Entering a current value
results in this value being
directly output at the current
output.
A0025040-EN
O3 (3)
Enter current
output table
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
table O3
Sel.Type
A0025041-EN
Endress+Hauser
Only for ES and EP versions.
Values can also be
subsequently added or
modified. The values entered
are automatically sorted by
increasing current value.
For further characteristics, see
O3 (1), O3 (2).
53
Commissioning
Liquisys M CCM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
O331
Read
Edit
Select table
option
Display
Info
read O331
Sel.Table
A0025042-EN
O332
Enter number of 1
table value pairs 1 to 10
1 O332
Enter the number of pairs of x
and y values (measured value
and current value) here.
No.Elem.
A0025043-EN
O333
Select table
value pair
1
1 to no. elem.
Assign
1 O333
Sel.Elem.
The system runs through the
O333 to O335 function chain
as often as indicated in O332.
"Assign" appears as the last
step. The display goes to O336
after confirmation.
A0025044-EN
O334
O335
Enter x value
Enter y value
0 ppb
0 to 20000 ppb
0.00 ppm
0 to 20 ppm
0.00 mg/l
0 to 20 (5) mg/l
pH 4.00
pH 4 to 9
0 mV
0 to 1500 mV
0 °C
0 to 50 °C
0.00 mA
0.00 to 20.00 mA
mg/l
0.00 O334
x value = measured value
specified by user.
Meas.val.
A0025046-EN
mA
0.00 O335
y value = user-defined current
value pertaining to O334.
Return to O333 until all values
are entered.
mA value
A0025048-EN
O336
Message as to
whether table
status is OK
Yes
No
yes O336
Status ok
Back to O3.
If status = no, correct the table
(all settings made up until now
remain intact) or go back to
the measuring mode (table is
deleted).
A0025049-EN
54
Endress+Hauser
Liquisys M CCM223/253
Commissioning
7.4.5
Alarm
You can use the "Alarm" function group to define various alarms and configure output
contacts.
Each individual error can be defined to be effective or not (at the contact or as an error
current).
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory
settings in
bold)
Display
Info
F
Alarm function settings.
ALARM
function group
F
ALARM
A0025141-EN
F1
Select contact
type
Latch =
latching
contact
Momen =
momentary
contact
Latch F1
The option selected only applies
for the fault-signaling contact, not
for the error current.
Cont.Type
A0025142-EN
F2
Select the time
unit for the
alarm delay
min
s
s F2
Time Unit
A0025143-EN
F3
Enter alarm
delay
0 min (s)
0 to 2000 s
(min)
s
0 F3
Depending on the option selected
in F2, the alarm delay can be
entered in s or min.
Err.Delay
A0025144-EN
F4
Select error
current
22 mA
2.4 mA
22mA
"0-20 mA" was selected in
IfO311,
"2.4 mA" may not be
F4
used.
Err.Curr
A0025145-EN
F5
Select the error
number
1
1 to 255
1 F5
Sel.error
A0025146-EN
F6
Set alarm
Yes
contact to be
No
effective for the
selected error
yes F6
Rel.Assg
Here you can select all the errors
which should trigger an alarm. The
errors are selected by the error
numbers. Please refer to the table
in the "System error messages"
section for the meaning of the
individual error numbers. The
factory settings remain in effect
for all errors that are not edited.
If “no” is selected, all the other
alarm settings are deactivated (e.g.
alarm delay). The settings
themselves are maintained. This
setting only applies to the error
currently selected in F5.
A0025147-EN
Endress+Hauser
55
Commissioning
Liquisys M CCM223/253
Coding Field
F7
Range of
adjustment
(factory
settings in
bold)
Set error
No
current to be
Yes
effective for the
selected error
Display
Info
no F7
Curr.Assg
The option selected in F4 is
effective or not effective in the
event of an error.
This setting only applies to the
error currently selected in F5.
A0025148-EN
F8
Automatic
cleaning
function start
No
Yes
no F8
This field is not available for
certain errors, see the
"Troubleshooting and fault
elimination" section.
CleanTrig
A0025149-EN
F9
Select return to Next = next
menu or next
error number
error
←R
next F9
If ←R is selected, you return to F. If
Next is selected, you go to F5.
Select
A0025150-EN
7.4.6
Check
The CHECK function group is only available for devices with the Plus Package (ES and EP
versions).
In the CHECK function group, you can select different monitoring functions for the
measurement.
By default all monitoring functions are switched off. The Sensor Check System is adapted
to the current application conditions by adding and setting the suitable functions.
Alarm threshold monitoring
When you perform chlorine or chlorine dioxide measurements without chemical dosage
control, sensor errors lead to a measured value error, but have no impact on the process
medium (examples: monitoring measurements in water works). Sensor errors generally
cause implausibly high or low readings. This is detected and signaled by user-definable
alarm thresholds.
Controller monitoring
When you perform chlorine or chlorine dioxide measurements with simultaneous chemical
dosage control, sensor errors not only result in incorrect measured values but also directly
impact the state of the process medium.
Particularly in the case of regulated water disinfection, due to the closed control loop there
is the risk that chemical dosing will not switch on if the measured value is constantly too
high. This poses a considerable danger to process stability, and could even pose a serious
health hazard for humans. On the other hand, if the measured value is constantly too low
this results in higher operating costs and a risk of corrosion due to the continuous dosing
of chemicals.
These cases are detected and signaled using user-definable monitoring times for
maximum permitted limit value overshoot and undershoot.
Sensor activity monitoring
The effect of the process medium on the sensor can also result in incorrect measured
values. For example, severe deposit buildup on the sensor membrane can cause the
56
Endress+Hauser
Liquisys M CCM223/253
Commissioning
measuring signal to be very sluggish or not even change at all (constant signal). This
passive behavior is detected and signaled by constantly monitoring the signal activity.
Overview of SCS monitoring functions
Mode of operation
Alarm threshold
monitoring
(P111 to P114)
(P121 to P124)
Possible
setting
• User-definable lower Off
alarm threshold (AS)
• User-definable upper Only lower
alarm threshold (AS) alarm
threshold
Only upper
alarm
threshold
Alarm event
Use
-
Applications with
or without
chemical dosage
control
Lower alarm threshold
reached or undershot
Upper alarm threshold
reached or exceeded
Lower and
Lower alarm threshold
upper alarm reached or undershot or
threshold
upper alarm threshold
reached or exceeded
Endress+Hauser
Controller monitoring
(CC: controller check,
P115 to P118
P125 to P128)
• Switch-on duration
monitoring
• Switch-off duration
monitoring
Off
-
On
Set maximum duration
for permanent switch-on
or switch-off exceeded
Sensor activity
monitoring
(AC: alternation
check,
P115 to P118
P125 to P128)
Signal change
monitoring
Off
-
On
Change within 1 hour
less than
• ±0.01 mg/l
(CCS140/240, sensor
963)
• ±0.005 mg/l
(CCS141/241)
• pH ±0.01
• ±1 mV
Applications with
chemical dosage
control
Applications with
or without
chemical dosage
control
57
Commissioning
Liquisys M CCM223/253
You can use the "Check" function group to monitor the measured value for permissible
upper and lower limits and trigger an alarm.
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
Display
adjustment
(factory settings in
bold)
Info
P
Settings for sensor and process
monitoring
CHECK
function
group
P
CHECK
A0009045-EN
P1(1)
Cl2
ClO2
P1
Cl2 if A1 = "120", "140", "141",
"963"
ClO2 if A1 = "240", "241"
Parameter
A0001988-EN
P111
P112
Select alarm
threshold
monitoring
Enter alarm
delay
Off
Low
High
LoHi = low and high
Lo!
Hi!
LoHi!
0 min (s)
0 to 2000 min (s)
Off P111
A.Thresh
A0001989-EN
min
0 P112
Err.Delay
A0001990-EN
P113
Enter lower
alarm
threshold
0 ppb
0 to 20000 ppb
0.00 ppm
0 to 20 ppm
0.00 mg/l
0 to 20 (5) mg/l
Alarm possible with or without
controller switch-off.
xxxx = without controller
switch-off
xxxx! = with controller switchoff
Depending on the option
selected in F2, the alarm delay
can be entered in s or min.
This delay must first elapse
before undershooting/
overshooting in accordance
with fields P113/P114 results
in an alarm.
Not applicable when P111 = off
mg/l
0.00 P113
LowAlarm
A0001991-EN
P114
Enter upper
alarm
threshold
20000 ppb
0 to 20000 ppb
20.00 ppm
0 to 20 ppm
20.00 (5.00) mg/l
0 to 20 (5) mg/l
Not applicable when P111 = off
mg/l
20.00 P114
HighAlarm
A0001992-EN
P115
58
Select process
monitoring
Off
AC
CC
AC+CC
AC!
CC!
AC+CC!
mg/l
Off P115
ProcMonit
A0001993-EN
AC = sensor activity monitoring
CC = controller monitoring
Alarm possible without or with
simultaneous controller switchoff.
xxxx = without controller
switch-off
xxxx! = with controller switchoff
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
Range of
Display
adjustment
(factory settings in
bold)
Info
P116
Enter
maximum
permissible
duration for
alarm
threshold
undershoot
60 min
0 to 2000 min
Only if P115 = CC or AC+CC
Enter
maximum
permissible
duration for
alarm
threshold
overshoot
120 min
0 to 2000 min
Enter limit
value
500 ppb
0 to 20000 ppb
0.5 ppm
0 to 20 ppm
0.5 (0.1) mg/l
0 to 20 (5) mg/l
P117
P118
min
60 P116
Tmax Low
A0002006-EN
Only if P115 = CC or AC+CC
min
120 P117
Tmax High
A0002007-EN
mg/l
0.5 P118
Setpoint
A0002008-EN
P1(2)
pH
ORPmV
pH P1
Parameter
Limit value for monitoring
according to fields P116 and
P117.
performing
When
external control from a
process control system
with an external set point,
make sure that the setting
matches that in field
P118.
Only for EP version
pH or ORPmV is displayed
depending on the mode of
operation selected in field B1.
A0001997-EN
P121
P122
Select alarm
threshold
monitoring
Enter alarm
delay
Off
Low
High
LoHi = low and high
Lo!
Hi!
LoHi!
0 min (s)
0 to 2000 min (s)
Off P121
A.Thresh
A0001998-EN
min
0 P122
Err.Delay
A0001999-EN
P123
Enter lower
alarm
threshold
pH 4.00
pH 4 to 8.9
0 mV
0 to 1490 mV
Alarm possible with or without
controller switch-off.
xxxx = without controller
switch-off
xxxx! = with controller switchoff
Depending on the option
selected in F2, the alarm delay
can be entered in s or min.
This delay must first elapse
before undershooting/
overshooting in accordance
with fields P123/P124 results
in an alarm.
Not applicable when P121 = off
pH
4.00 P123
LowAlarm
A0002000-EN
P124
Enter upper
alarm
threshold
pH 9.00
pH 4.1 to 9
1500 mV
10 to 1500 mV
Not applicable when P121 = off
pH
9.00 P124
HighAlarm
A0002001-EN
Endress+Hauser
59
Commissioning
Liquisys M CCM223/253
Coding Field
Range of
Display
adjustment
(factory settings in
bold)
Info
P125
Off
AC
CC
AC+CC
AC!
CC!
AC+CC!
AC = sensor activity monitoring
CC = controller monitoring
Alarm possible without or with
simultaneous controller switchoff.
xxxx = without controller
switch-off
xxxx! = with controller switchoff
Options CC, AC+CC, CC! and AC
+CC! can only be selected if pH
is selected in field P1(2).
P126
P127
P128
Select process
monitoring
Enter
maximum
permissible
duration for
alarm
threshold
undershoot
60 min
0 to 2000 min
Enter
maximum
permissible
duration for
alarm
threshold
overshoot
120 min
0 to 2000 min
Enter limit
value
pH 7.20
pH 4 to 9
Off P125
ProcMonit
A0002002-EN
Only if P125 = CC or AC+CC
min
60 P126
Tmax Low
A0002003-EN
Only if P125 = CC or AC+CC
min
120 P127
Tmax High
A0002004-EN
pH
7.20 P128
Setpoint
A0002005-EN
7.4.7
Limit value for monitoring
according to fields P126 and
P127.
performing
When
external control from a
process control system
with an external set point,
make sure that the setting
matches that in field
P128.
Relay configuration
For the "RELAY" function group, you require a relay card which is not available in the basic
device version.
The following relay contacts can be selected and configured as desired (max. four contacts,
depending on options installed):
• Limit contactor for chlorine/chlorine dioxide measured value: R2 (1)
• Limit contactor for pH/ORP measured value: R2 (2)
• Limit contactor for temperature: R2 (3)
• PID controller for chlorine/chlorine dioxide: R2 (4)
• PID controller for pH: R2 (5)
• Timer for cleaning function: R2 (6)
• Chemoclean function: R2 (7)
• Three-point step controller for chlorine/chlorine dioxide: R2 (8)
Only one function can be assigned to each relay. If a relay function is already switched on
(R211 to R281), it is switched off automatically when you select another function and
press ENTER to confirm (R2(1) to R2(8)).
Pressing the REL key allows you to display the corresponding setpoint of every relay
function.
60
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Limit contactors for chlorine/chlorine dioxide/total chlorine measured value and
temperature or pH or ORP measured value
The transmitter has different ways of assigning a relay contact. Switch-on and switch-off
points and pickup and dropout delays can be assigned to the limit contactor. In addition,
you can configure an alarm threshold to output an error message and to start a cleaning
function in conjunction with this.
These functions can be used both for the primary value and for temperature measurement.
Please refer to the switch states in → 36 for a clear illustration of the relay contact
states.
• When the measured values increase (maximum function), the relay contact is closed as
of t2 after the switch-on point (t1) has been exceeded and the pickup delay has elapsed
(t2-t1).
The alarm contact switches if the alarm threshold (t3) is reached and the alarm delay
(t4-t3) has also elapsed (errors E067 to E070).
• When the measured values decrease, the alarm contact is reset when the value falls
below the alarm threshold (t5) again, as is the relay contact (t7) after the dropout delay
(t7-t6).
• If the pickup and dropout delays are set to 0 s, the switch-on and switch-off points are
also switch points of the contacts.
The same settings can also be made for a minimum function in the same way as for the
maximum function.
5
6
1
4
A
2
3
7
t1
t2
t3
t4
t5
t6 t7
t
7
B
3
2
4
6
1
5
t1
t2
t3
t4
t5
t6 t7
t
A0025215
36
A
B
1
2
3
4
5
6
7
Endress+Hauser
Illustration of the alarm and limit value functions
Switch-on point > switch-off point: Max. function
Switch-on point < switch-off point: Min. function
Alarm threshold
Switch-on point
Switch-off value
Contact ON
Alarm ON
Alarm OFF
Contact OFF
61
Commissioning
Liquisys M CCM223/253
P(ID) controller
You can define various controller functions for the transmitter. On the basis of the PID
controller, P, PI, PD and PID controllers can be implemented. For an optimum control
system, use the controller that best suits your application.
• P controller
Used for simple linear control purposes with small system deviations. Where major
changes are to be controlled, overshooting may occur. In addition, a lasting control
deviation must be expected.
• PI controller
Is used for control systems where overshooting is to be avoided and no lasting control
deviation should occur.
• PD controller
Is used for processes that require quick changes and where peaks must be corrected.
• PID controller
Is used for processes where a P, PI or PD controller does not control sufficiently.
Configuration options of the P(ID) controller
The following configuration options are available for a PID controller:
• Change control gain Kp (P influence)
• Set integral action time Tn (I influence)
• Set derivative action time Tv (D influence)
Basic load dosing (basic)
You can set a constant dosage amount (field R2411) with basic load dosing (field R241).
PID control plus basic load dosing
If you have selected this function (PID + Basic) in field R241, the PID-controlled dosage
amount does not drop below the basic load value entered in field R2411.
A
100 %
B
100 %
C
A0025221
37
A
B
C
Control characteristic of PID controller with basic load dosing
PID plus basic load
Basic load
PID
Commissioning
If you do not yet have any experience for setting the control parameters, set the values
that yield the greatest possible stability in the control circuit. Proceed as follows to
optimize the control circuit further:
• Increase the control gain Kp until the controlled variable just starts to overshoot.
• Reduce Kp slightly again and then reduce the integral action time Tn so that the shortest
possible correction time without overshooting is achieved.
• To reduce the response time of the controller, also set the derivative action time Tv.
Control and fine optimization of the set parameters with a recorder
62
Endress+Hauser
Liquisys M CCM223/253
Commissioning
A
A
2
1
B
B
A
A
4
3
B
B
A
5
B
A0025218
38
A
B
1
2
3
4
5
Optimization of settings Tn and Kp
Actual value
Time
Tn too small
Tn too large
Kp too large
Kp too small
Optimum setting
Actuating signal outputs via contacts (R247 to R2410 and R257 to R2510)
Each control contact outputs a cyclical signal whose intensity corresponds to the
controller's actuating value. A distinction is made according to the type of signal cycle:
• Pulse length modulation
The bigger the calculated manipulated variable is, the longer the contact affected
remains picked up. The period T can be adjusted between 0.5 and 99 s (field R248 or
R258). Outputs with pulse length modulation are used to activate solenoid valves.
• Pulse frequency modulation
The bigger the calculated manipulated variable is, the higher the switching frequency of
the contact affected. The maximum switching frequency 1/T can be set between 60 and
180 min-1 (field R249 or R259). The on-time ton is constant. It depends on the set
maximum frequency and is approx. 0.5 s for 60 min-1 and approx. 170 ms for 180 min-1.
170 ms. Outputs with pulse frequency modulation are used to activate directly controlled
solenoid dosing pumps.
Endress+Hauser
63
Commissioning
Liquisys M CCM223/253
A
t1
A
t2
t1
1
1
0
0
t [s]
T
T1
t [s]
T2
A0025219
39
Signal of a pulse-length modulated controller contact (left) and of a pulse frequency-modulated controller
contact (right)
Contact:
1 = on, 0 = off
T
Period
Time (s):
t1 = ton t2 = toff
T1 T2
Impulse period length ( 1/T1 and 1/T2)
Constant controller
The controller can also control the second analog current output (if provided). You can
configure the constant controller in the fields R247 or R257 and O2.
Control characteristic for direct and inverse control action
You can choose between two control characteristics in the R246 and R256 field:
• Direct control action = maximum function
• Inverse control action = minimum function
Y
100 %
A
XW
– XW
Y
100 %
B
– XW
XW
A0025222
40
A
B
XW
Y
Control characteristic of a proportional controller with direct and inverse control action
Direct = maximum function
Inverse = minimum function
Control deviation
Current output signal = controller actuating variable
Timer for cleaning function
This function includes a simple cleaning option. You can set the time interval after which
cleaning should start. Therefore you can only select a constant interval sequence.
Other cleaning functions are available for selection in conjunction with the Chemoclean
function (device version with four contacts required, see the "Chemoclean function"
section).
The timer and Chemoclean do not work independently of one another. While one of
the two functions is active, the other cannot be started.
64
Endress+Hauser
Liquisys M CCM223/253
Commissioning
1
A
0
t
1
B
0
t0
t1
t2
t3
t4
t
A0025223
41
Connection between cleaning time, pause time and hold dwell period
A
Wiper and/or spray cleaning system
B
Hold function
0
Inactive
1
active
t0 Normal operation
t1 cleaning start
t2-t1Cleaning time
t3-t2Clean hold dwell period (0 to 999 s)
t4-t3Pause time between two cleaning intervals (1 to 7200 min)
Chemoclean function
Just like the timer function, Chemoclean can also be used to start a cleaning cycle.
However, Chemoclean also gives you the added option of defining various cleaning and
rinsing intervals and of dosing cleaning agent.
Therefore, it is possible to clean irregularly with different repeat cycles and to separately
set the cleaning times with post rinse times.
Please note the following:
• To use the Chemoclean function the transmitter has to be equipped with a designated
relay board (see product structure or chapter "accessories").
• The timer and Chemoclean are mutually dependent. While one of the two functions is
active, the other cannot be started.
• For the Chemoclean function, the relays 3 (water) and 4 (cleaner) are used.
• If the cleaning is prematurely aborted, a post rinse time always follows.
• If the setting is "Economy", cleaning only takes place with water.
Endress+Hauser
65
Commissioning
Liquisys M CCM223/253
1
A
0
1
B
0
1
C
0
t0
t1
t2
t3
t4
t5
A0025216
42
Sequence of a cleaning cycle
A
Hold function
B
Water valve is triggered
C
Cleaning valve is triggered
0
Contact off
1
Contact on
t0 Normal operation
t1 cleaning start
t2-t1Pre-rinse time
t3-t2Cleaning time
t4-t3Post rinse time
t5-t4Hold dwell period
66
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Three-point step controller
With this type of controller, you can control motorized valves for metering chlorine gas.
• If the controller activates relay 3, the motorized valve closes.
• If the controller activates relay 4, the motorized valve opens.
measuring signal
C
overdosed
X
underdosed
B
XW
A
R4 mark-tospace ratio
B
R3 mark-tospace ratio
C
relay output
A0025217-EN
43
A
B
C
W
X
Function of the three-point step controller
Measured value is in set point window
Measured value is smaller than the set point
Measured value is larger than the set point
Set point
Measured value
• Measured value is in set point window (A)
Relays 3 and 4 are not activated. The motorized valve does not change.
• Measured value is smaller than the set point (B)
Not enough chlorine gas is metered. Relay 4 is activated (pulse control). The motorized
valve is opened further and the dosage metered is increased.
• Measured value is larger than the set point (C)
Too much chlorine gas is metered. Relay 3 is activated (pulse control). The motorized
valve is closed further and the dosage metered is reduced.
Endress+Hauser
67
Commissioning
Liquisys M CCM223/253
Functions marked in italics are not supported by the basic device version.
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
R
Relay contact settings
RELAY
R
RELAIS
A0009058-EN
R1
Select the
contact to be
configured
Rel1
Rel2
Rel3
Rel4
Rel1 R1
Sel.Relay
A0009059-EN
R2 (1)
R211
Configure limit
contactor for
Cl2/ClO2
Switch function
of R2 (1) off or
on
LC PV= limit
contactor
Cl2/ClO2 (1)
LC °C = limit
contactor pH (2)
LC °C = limit
contactor T (3)
PID controller
Cl2/ClO2 (4)
PID controller pH
(5)
Timer (6)
Clean=
Chemoclean (7)
Three-point step
controller
Off
On
LC PV
R2
Sel.Type
A0009060-EN
Rel3 (water) and Rel4 (cleaner)
are only available with the
relevant version of the
transmitter.
If Chemoclean is used as the
cleaning method, Rel4 is not
available.
PV = process value
If Rel4 is selected in the R1
field, Clean = Chemoclean
cannot be selected. By
confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
All the settings are retained.
off
R211
Function
A0009067-EN
R212
Enter the
switch-on point
of the contact
20000 ppb
0 to 20000 ppb
20 ppm
0 to 20 ppm
20 (5) mg/l
0 to 20 (5) mg/l
Enter the
switch-off point
of the contact
20000 ppb
0 to 20000 ppb
20 ppm
0 to 20 ppm
20 (5) mg/l
0 to 20 (5) mg/l
mg/l
20 R212
On Value
Never set the switch-on point
and the switch-off point to the
same value! (Only the operating
mode selected in A1 is
displayed.)
A0002033-EN
R213
mg/l
20 R213
Off Value
A0002034-EN
68
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact (switchoff point > switch-on point),
thereby implementing a
hysteresis that is constantly
required (see "Illustration of the
alarm and limit functions"
figure).
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
R214
0s
0 to 2000 s
Enter pickup
delay
Display
Info
0
s
R214
On Delay
A0009070-EN
R215
Enter dropout
delay
0s
0 to 2000 s
0
s
R215
Off Delay
A0009071-EN
R216
Enter alarm
threshold (as
absolute value)
20000 ppb
0 to 20000 ppb
20 ppm
0 to 20 ppm
20 (5) mg/l
0 to 20 (5) mg/l
mg/l
20 R216
A.Thresh
A0002038-EN
R217
Display status
for limit
contactor
MAX
MIN
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the error
message (E067 to E070) and
an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
Display only
MAX R217
LC State
A0009073-EN
R2 (2)
Configure limit
contactor for pH
or ORP mV
LC pH= limit
contactor pH
LVORP = limit
contactor ORP
mV
LC pH R2
Function
A0002025-EN
R221
Switch function
of R2 (2) off or
on
Off
On
off
R221
Only for EP version.
Measurement is configured for
pH or ORP depending on the
mode of operation selected in
field B1.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
Any settings made for the limit
contactor are not deleted if the
function is switched off.
Function
A0009074-EN
R222
Enter the switch- pH 9
on point of the
pH 4 to 9
contact
1500 mV
0 to 1500 mV
pH
9.00 R222
On Value
Never set the switch-on point
and the switch-off point to the
same value!
A0002041-EN
Endress+Hauser
69
Commissioning
Liquisys M CCM223/253
Coding Field
R223
Range of
adjustment
(factory settings
in bold)
Enter the switch- pH 9
off point of the
pH 4 to 9
contact
1500 mV
0 to 1500 mV
Display
Info
pH
9.00 R223
Off Value
A0002042-EN
R224
Enter pickup
delay
0s
0 to 2000 s
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact (switchoff point > switch-on point),
thereby implementing a
hysteresis that is constantly
required (see "Illustration of the
alarm and limit functions"
figure).
0 R224
s
On Delay
A0009077-EN
R225
Enter dropout
delay
0s
0 to 2000 s
0 R225
s
Off Delay
A0009078-EN
R226
Enter alarm
threshold (as
absolute value)
pH 9
pH 0 to 9
1500 mV
0 to 1500 mV
pH
9.00 R226
A.Thresh
A0005998-EN
R227
Display status
for limit
contactor
MAX
MIN
Configure limit
contactor for
temperature
LC °C = limit
contactor T
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the error
message (E067 to E070) and
an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
Display only
MAX R227
LC State
A0009080-EN
R2 (3)
LC ¡C
R2
Sel.Type
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
A0009061-EN
R231
Switch function
of R2 (3) off or
on
Off
On
off
R231
Any settings made for the limit
contactor are not deleted if the
function is switched off.
Function
A0009081-EN
R232
Enter switch-on
temperature
50 °C
0 to 50 °C
°C
50.0 R232
On Value
Never set the switch-on point
and the switch-off point to the
same value!
A0006003-EN
70
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
R233
50 °C
0 to 50 °C
Enter switch-off
temperature
Display
Info
¡C
50.0 R233
Off Value
A0002049-EN
R234
Enter pickup
delay
0s
0 to 2000 s
Entering a switch-off point
selects either a Max contact
(switch-off point < switch-on
point) or a Min contact (switchoff point > switch-on point),
thereby implementing a
hysteresis that is constantly
required (see "Illustration of the
alarm and limit functions"
figure).
s
0 R234
On Delay
A0002050-EN
R235
Enter dropout
delay
0s
0 to 2000 s
s
0 R235
Off Delay
A0002051-EN
R236
Enter alarm
threshold (as
absolute value)
50 °C
0 to 50 °C
¡C
50.0 R236
A.Thresh
A0002052-EN
R237
Display status
for limit
contactor
MAX
MIN
Configure P(ID)
controller for
Cl2/ClO2
PIDPV
If the alarm threshold is
undershot/overshot, this
triggers an alarm with the error
message (E067 to E070) and
an error current at the
transmitter (note alarm delay
in field F3).
If defined as a Min contact, the
alarm threshold must be <
switch-off point.
Display only
MAX R237
LC State
A0002053-EN
R2 (4)
PIDPV R2
Function
A0002027-EN
R241
Switch function
of R2 (4) off or
on
Off
On
Basic
PID+B
Enter set point
500 ppb
0 to 20000 ppb
0.5 ppm
0 to 20 ppm
0.5 (0.1) mg/l
0 to 20 (5) mg/l
Off R241
Function
PV = process value of main
measuring parameter
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
On = PID controller
Basic = basic load dosing
PID+B = PID controller + basic
load dosing
A0002054-EN
R242
mg/l
0.50 R242
Setpoint
The set point is the value to be
maintained by the control
system. Using this control
process, this value is restored
when an upwards or
downwards deviation occurs.
A0002057-EN
Endress+Hauser
71
Commissioning
Liquisys M CCM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
R243
1.00
0.01 to 20.00
Enter control
gain KP
Display
Info
1.00 R243
See the "P(ID) controller"
section.
Kp
A0002058-EN
R244
Enter integral
action time Tn
(0.0 = no Icomponent)
0.0 min
0.0 to 999.9 min
min
0.0 R244
Time Tn
A0002059-EN
R245
Enter derivative
action time Tv
(0.0 = no Dcomponent)
0.0 min
0.0 to 999.9 min
min
0.0 R245
Time Tv
See the "P(ID) controller"
section.
With every hold, the Icomponent is set to zero.
Although the hold can be
deactivated in field S2, this
does not apply for Chemoclean
and timer!
See the "P(ID) controller"
section.
A0002060-EN
R246
Select controller
characteristic
Inv = inverse
(initial setting
for sodium
hypochlorite
Dir = direct
inv R246
Direction
See the "P(ID) controller"
section.
This setting is required
depending on the desired
dosing direction (dosing above
or below the set point).
A0002061-EN
R247
Select pulse
length or pulse
frequency
Len = pulse
length
Freq = pulse
frequency
Curr = current
output 2
len R247
Oper.Mode
A0002062-EN
R248
Enter pulse
interval
10.0 s
0.5 to 999.9 s
s
10.0 R248
PulsePer.
Pulse length e.g. for solenoid
valve, pulse frequency e.g. for
solenoid dosing pump, see the
"Actuating signal outputs"
section.
Curr = current output 2 can
only be selected if O2 = Contr.
This field only appears if pulse
length is selected in R247.
If pulse frequency is selected,
R248 is skipped and entries
continue with R249.
A0002063-EN
R249
Enter maximum
pulse frequency
of the adjuster
min-1
120
60 to 180 min-1
1/min
120 R249
Max.PFreq
This field only appears if pulse
frequency is selected in R247. If
pulse length is selected, R249 is
skipped and entries continue
with R2410.
A0002064-EN
R2410
Enter minimum
switch-on time
tON
0.3 s
0.1 to 5.0 s
s
0.3 R2410
Min.PTime
This field only appears if pulse
length is selected in R247.
A0002055-EN
72
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
R2411
0%
0 to 40 %
Enter basic load
Display
Info
%
0 R2411
BasicLoad
A0002056-EN
R2 (5)
Configure P(ID) PIDpH
controller for pH
PIDpH R2
Function
When you select the basic load,
you enter the desired dosing
quantity.
100% basic load would
correspond to:
• Constantly on if R247 = len
• Fmax if R247 = freq (field
R249)
• 20 mA if R247 = curr
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
A0002028-EN
R251
Switch function
of R2 (5) off or
on
Off
On
Basic
PID+B
Off R251
Function
On = PID controller
Basic = basic load dosing
PID+B = PID controller + basic
load dosing
A0002084-EN
R252
Enter set point
pH 7.20
pH 4 to 9
pH
7.20 R252
Setpoint
The set point is the value to be
maintained by the control
system. Using this control
process, this value is restored
when an upwards or
downwards deviation occurs.
A0002087-EN
R253
Enter control
gain KP
1.00
0.01 to 100.00
See the "P(ID) controller" section
1.00 R253
Kp
A0002088-EN
R254
Enter integral
action time Tn
(0.0 = no Icomponent)
0.0 min
0.0 to 999.9 min
min
0.0 R254
Time Tn
A0002089-EN
R255
Enter derivative
action time Tv
(0.0 = no Dcomponent)
0.0 min
0.0 to 999.9 min
See the "P(ID) controller" section
With every hold, the Icomponent is set to zero.
Although the hold can be
deactivated in field S2, this
does not apply for Chemoclean
and timer!
See the "P(ID) controller" section
min
0.0 R255
Time Tv
A0002090-EN
R256
Select controller
characteristic
Inv = inverse
Dir = direct
(Initial setting for
acid)
dir R256
Direction
See the "P(ID) controller" section
This setting is required
depending on the desired
dosing direction (dosing above
or below the set point).
A0002091-EN
Endress+Hauser
73
Commissioning
Liquisys M CCM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
R257
Len = pulse
length
Freq = pulse
frequency
Curr = current
output 2
Select pulse
length or pulse
frequency
Display
Info
len R257
Oper.Mode
Pulse length e.g. for solenoid
valve
Pulse frequency e.g. for
solenoid dosing pump
Curr = current output 2 can
only be selected if O2 = Contr.
A0002092-EN
R258
Enter pulse
interval
10.0 s
0.5 to 999.9 s
Enter maximum
pulse frequency
of the adjuster
120 min-1
60 to 180 min-1
Enter minimum
switch-on time
tON
0.3 s
0.1 to 5.0 s
Enter basic load
0%
0 to 40 %
s
10.0 R258
PulsePer.
This field only appears if pulse
length is selected in R257.
If pulse frequency is selected,
R258 is skipped and entries
continue with R259.
A0002093-EN
R259
1/min
120 R259
Max.PFreq
This field only appears if pulse
length is selected in R257.
If pulse length is selected, R259
is skipped and entries continue
with R2510.
A0002094-EN
R2510
s
0.3 R2510
Min.PTime
This field only appears if pulse
length is selected in R257.
A0002085-EN
R2511
%
0 R2511
BasicLoad
A0002086-EN
R2 (6)
Configure
cleaning
function (timer)
Timer (6)
Timer R2
Sel.Type
A0009063-EN
R261
Switch function
of R2 (6) off or
on
Off
On
This field only appears for the
EP version.
When you select the basic load,
you enter the desired dosing
quantity.
100% basic load would
correspond to:
• Constantly on if R257 = len
• Fmax if R257 = freq (field
R259)
• 20mA if R257 = curr
Only one cleaning agent
(generally water) is used for the
cleaning.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
Off R261
Function
A0002095-EN
R262
Enter rinsing/
cleaning time
30 s
0 to 999 s
s
30 R262
RinseTime
Settings for hold and relay are
active for this time.
A0002096-EN
74
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
R263
Range of
adjustment
(factory settings
in bold)
Enter pause time 360 min
1 to 7200 min
Display
Info
min
360 R263
PauseTime
The pause time is the time
between two cleaning cycles
(see the "Timer for cleaning
function" section).
A0002097-EN
R264
Enter minimum
pause time
120 min
1 to 3600 min
min
120 R264
Min.Pause
The minimum pause time
prevents constant cleaning if a
cleaning trigger is pending.
A0002098-EN
R2 (7)
R271
Configure
Clean=
cleaning with
Chemoclean (7)
Chemoclean (for
version with four
contacts,
Chemoclean
option and
contacts 3 and 4
assigned)
Switch function
of R2 (7) off or
on
Off
On
Select type of
start pulse
Int = internal
(timecontrolled)
Ext = external
(digital input 2)
I+ext = internal +
external
I+stp = internal,
suppressed by
external
Clean R2
Sel.Type
A0009064-EN
See the "Chemoclean function"
section.
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
Off R271
Function
A0002099-EN
R272
R273
Enter pre-rinse
time
20 s
0 to 999 s
int R272
CleanTrig
No real time clock is available.
External suppression is required
for irregular time intervals (e.g.
weekends).
A0002100-EN
s
20 R273
PreRinse
Rinsing is performed with
water.
A0002101-EN
R274
Enter cleaning
time
10 s
0 to 999 s
s
10 R274
CleanTime
Cleaning is performed with
cleaning agent and water.
A0002102-EN
R275
Enter post rinse
time
20 s
0 to 999 s
s
20 R275
PostRinse
Rinsing is performed with
water.
A0002103-EN
Endress+Hauser
75
Commissioning
Liquisys M CCM223/253
Coding Field
Range of
adjustment
(factory settings
in bold)
R276
0
0 to 5
Enter number of
repeat cycles
Display
Info
R273 to R275 is repeated.
0 R276
Rep. Rate
A0002104-EN
R277
Enter pause time 360 min
1 to 7200 min
min
360 R277
PauseTime
The pause time is the time
between two cleaning cycles
(see the "Chemoclean function"
section).
A0002105-EN
R278
Enter minimum
pause time
120 min
1 to R277
min
120 R278
Min.Pause
The minimum pause time
prevents constant cleaning if an
external cleaning start is
pending.
A0002106-EN
R279
Enter number of 0
cleaning cycles
0 to 9
without cleaning
agent (economy
function)
0 R279
EconomyCl
After cleaning with cleaner, up
to 9 cleaning sessions can be
carried out with water only
until the next cleaning session
with cleaner takes place.
A0002107-EN
R2 (8)
Configure threepoint step
controller for
Cl2/ClO2
3 PSt (8)
3PSt R2
Function
Only with relays 3 and 4..
By confirming with ENTER,
another relay function already
switched on is switched off and
its settings are reset to the
factory settings.
A0002031-EN
R281
Switch function
of R2 (8) off or
on
Off
On
Off R281
Function
A0002108-EN
R282
Enter set point
500 ppb
0 to 20000 ppb
0.5 ppm
0 to 20 ppm
0.5 (0.1) mg/l
0 to 20 (5) mg/l
mg/l
0.50 R282
Setpoint
The set point is the value to be
maintained by the control
system. Using this control
process, this value is restored
when an upwards or
downwards deviation occurs.
A0002109-EN
R283
Enter control
gain KP
1.00
0.10 to 100.00
See the "P(ID) controller" section
1.00 R283
Kp
A0002110-EN
R284
Enter integral
action time Tn
0.0 min
0.0 to 999.9 min
See the "P(ID) controller" section
min
0.0 R284
Time Tn
A0002111-EN
76
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
Range of
adjustment
(factory settings
in bold)
R285
0.3 s
0.1 to 5.0 s
Enter minimum
switch-on time
tON
Display
Info
s
0.3 R285
Min.PTime
A0002112-EN
R286
Enter motor run
time
60 s
10 to 999 s
Enter neutral
zone
10 %
0 to 40 %
s
60 R286
MotorTime
Motor run time from "fully
closed" state to "fully open"
state.
A0002113-EN
R287
%
10 R287
NeutrZone
A0002114-EN
7.4.8
Service
Coding Field
Range of
adjustment
(factory settings in
bold)
Display
Info
S
Service function settings.
SERVICE
function group
S
SERVICE
A0008408-EN
S1
Select language
ENG = English
GER = German
FRA = French
ITA = Italian
NL = Dutch
ESP = Spanish
ENG
S1
The option selected only
applies for the faultsignaling contact, not for the
error current.
Language
A0008409-EN
S2
S3
Configure a hold S+C = hold during
configuration and
calibration
Cal = hold during
calibration
Setup = hold during
configuration
None = no hold
Manual hold
Off
On
S+C
S = setup
C = calibration
S2
Auto HOLD
A0008413-EN
off
S3
The setting is retained even
in the event of a power
failure.
Man. HOLD
A0008414-EN
Endress+Hauser
77
Commissioning
Liquisys M CCM223/253
Coding Field
S4
Range of
adjustment
(factory settings in
bold)
Display
Info
Enter hold dwell 10 s
period
0 to 999 s
10
s
S4
Cont.Time
A0008415-EN
S5
Enter SW
upgrade release
code (Plus
Package)
0000
0000 to 9999
0000
S5
PlusCode
A0008416-EN
S6
Enter SW
upgrade release
code for
Chemoclean
0000
0000 to 9999
0000 S6
CleanCode
A0008417-EN
S7
Order number is
displayed
The code can be found on the
nameplate.
If an incorrect code is
entered, you are taken back
to the measurement menu.
The number is edited with
the PLUS or MINUS key and
confirmed with the ENTER
key. "1" is displayed if the
code is active.
The code can be found on the
nameplate.
If an incorrect code is
entered, you are taken back
to the measurement menu.
The number is edited with
the PLUS or MINUS key and
confirmed with the ENTER
key. "1" is displayed if the
code is active.
If the device is upgraded, the
order code is changed
automatically.
order S7
EK0005
A0006005
S8
Serial number is
displayed
SerNo
S8
12345678
A0008420-EN
S9
Reset the device
to the basic
settings
No
Sens = sensor data
Facty = factory
settings
no
S9
S.Default
Sens = last calibration is
deleted and is reset to factory
setting.
Facty = all data (apart from
A1 and S1) are deleted and
reset to the factory setting!
A0008421-EN
S10
Perform device
test
No
Displ = display test
no
S10
Test
A0008410-EN
78
Endress+Hauser
Liquisys M CCM223/253
Commissioning
7.4.9
E+H Service
Coding Field
Range of adjustment
(factory settings in
bold)
Display
Info
E
Information on the
device version
E+H SERVICE
function group
E
E+H SERV
A0007857-EN
E1
Select module
Contr = controller
(central module) (1)
Trans = transmitter (2)
Main = power unit (3)
Rel = relay module (4)
Sens = sensor (5)
Contr E1
Select
A0007858-EN
E111
E121
E131
E141
E151
Software version is
displayed
E112
E122
E132
E142
E152
Hardware version
is displayed
xx.xx
E111
SW-Vers.
If E1 = contr: device
software
If E1 = trans, main, rel:
module firmware
If E1 = sens: sensor
software
A0007859-EN
Info display
xx.xx
E112
HW-Vers.
A0007861-EN
E113
E123
E133
E143
E153
Serial number is
displayed
Info display
SerNo
E113
12345678
A0007860-EN
E114
E124
E134
E144
E154
Module ID is
displayed
Info display
LSG
E114
Modul-ID
A0007862-EN
Endress+Hauser
79
Commissioning
Liquisys M CCM223/253
7.4.10
Interfaces
Coding Field
Range of
adjustment
(factory settings
in bold)
Display
Info
I
INTERFACE
function group
I
Communication settings (only
for HART or PROFIBUS device
version).
INTERFACE
A0007863-EN
I1
Enter bus
address
Address
HART: 0 to 15
or
PROFIBUS: 0 to
126
126
I1
Address
A0007864-EN
I2
The tag name is
displayed
Each address may only be
assigned once in a network. If a
device address ≠ 0 is selected for
a HART device, the current
output is automatically set to 4
mA and the device prepares for
multi-drop operation.
Tag I2
@@@@@@@@
A0007865-EN
7.4.11
Communication
For devices with a communication interface, please also refer to the separate Operating
Instructions BA00208C/07/EN (HART®) or BA00209C/07/DE (PROFIBUS®).
80
Endress+Hauser
Liquisys M CCM223/253
Commissioning
7.5
Calibration
Use the CAL key to access the calibration function group.
Use this function group to calibrate the transmitter.
When calibrating the "Free chlorine" measurement mode, make sure to pay attention
to the pH value and the temperature of the medium. The limit values are provided in
the following table:
Sensor
pHmin
pHmax
Tmin
Tmax
CCS140
4
8
10 °C (50 °F)
45 °C (113 °F)
CCS141
4
8.2
2 °C (36 °F)
45 °C (113 °F)
CCS240
-
-
2 °C (36 °F)
45 °C (113 °F)
CCS241
-
-
2 °C (36 °F)
45 °C (113 °F)
CCS120
5.5
9.5
5 °C (41 °F)
45 °C (113 °F)
Please note the following:
• You require a photometer, e.g. PF-3 (see "Accessories") to calibrate chlorine and chlorine
dioxide. A photometer with a higher accuracy rating and lower detection limit is required
for calibration in the trace range (<0.1 mg/l).
• If the calibration is aborted by simultaneously pressing the PLUS and MINUS keys
(return to C15, C29 or C35), or if the calibration is incorrect, the original calibration data
are used again. A calibration error is indicated by “ERR” and the sensor symbol flashes
on the display.
Repeat calibration!
• For each calibration, the device automatically switches to hold (factory setting).
• On completion of the calibration, the device returns to the measurement mode. The
"hold" symbol appears on the display during the hold dwell period (field S4).
Coding Field
Range of
adjustment
(factory
settings in
bold)
C(1)
Cl2
ClO2
CALIBRATION
function group:
Calibration Cl2/
ClO2
Display
Info
Cl2 C
CALIBRAT
Cl2 if A1 = 120/140/141/963
ClO2 if A1 = 240/241
A0006351-EN
C11
Enter DPD
calibration value
Value of last
calibration
mg/l
0.50 C11
DPD value
Minimum values for the
calibration:
• For CCS120/140/240 and
sensor 963: 0.05 mg/l
• For CCS141/241: 0.01 mg/l
A0002420-EN
C12
Zero point
calibration?
No
Yes
no C12
Zero cal
A0002421-EN
Endress+Hauser
Only if A1 = 963
Zero point calibration:
1. Pass unchlorinated water
through the assembly.
2. Wait for 10 minutes.
3. Accept by selecting YES and
pressing ENTER
81
Commissioning
Liquisys M CCM223/253
Coding Field
Range of
adjustment
(factory
settings in
bold)
C13
100 %
Minimum 25%
(3%)
Maximum
500%
Slope is displayed
Display
Info
%
100 C13
Slope
A0002422-EN
C14
Calibration status
is displayed
o. k.
E xxx
Minimum permitted slope:
• For CCS140/141 with pH
compensation and for
CCS240/241: 25%
• For CCS120/140/141 without
pH compensation and for
sensor 963: 3%
o.k. C14
Status
A0002423-EN
C15
Store calibration
result
Yes
No
New
yes C15
Store
If C14 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
A0002424-EN
C(2)
pH
CALIBRATION
function group:
pH calibration
pH C
CALIBRAT
A0002418-EN
C21
Calibration status
is displayed
25 °C
0 to 50 °C
¡C
25.0 C21
MTC-Temp
This field is only for recording
the calibration temperature. An
entry must not be made.
A0002425-EN
C22
Enter pH value of
the first buffer
solution
Buffer value of
the last
calibration
pH 3.50 to 9.50
pH
7.00 C22
Buffer 1
Press the ENTER key to display
the current measured value.
Press the ENTER key again as
soon as the measured value has
adjusted to the buffer value.
A0002427-EN
C23
Calibration is
performed
pH
7.00 C23
Buffer 1
Stability check:
The value is accepted if the
stability level is ≤pH ±0.05 for
more than 10 seconds.
A0002428-EN
C24
Enter pH value of
the second buffer
solution
Buffer value of
the last
calibration
pH 3.50 to 9.50
pH
4.00 C24
Buffer 2
Buffer 2 must have a different
value to buffer 1. A plausibility
check is performed.
Press the ENTER key and
proceed as in field C22.
A0002429-EN
C25
Calibration is
performed
pH
4.00 C25
Buffer 2
Stability check:
The value is accepted if the
stability level is ≤pH ±0.05 for
more than 10 seconds.
A0002430-EN
82
Endress+Hauser
Liquisys M CCM223/253
Commissioning
Coding Field
Range of
adjustment
(factory
settings in
bold)
C26
59.16 mV/pH
38.00 to 65.00
mV/pH
Slope is displayed
Display
Info
mV/pH
59.16 C26
Slope
A0002431-EN
C27
Zero point is
displayed
pH 7.00
pH 5.00 to 9.00
pH
7.00 C27
Zero
A0002432-EN
C28
Calibration status
is displayed
o. k.
E xxx
o.k. C28
Status
A0002452-EN
C29
Store calibration
result?
Yes
No
New
yes C29
Store
If C28 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
A0002434-EN
C(3)
ORPmV
CALIBRATION
function group:
ORP mV
calibration
ORPmV C
CALIBRAT
A0002419-EN
C31
Enter the value of
the ORP buffer
Buffer value of
the last
calibration
0 to 1500 mV
mV
225 C31
mV Buffer
Press the ENTER key to display
the current measured value.
Press the ENTER key again as
soon as the measured value has
adjusted to the buffer value.
A0002435-EN
C32
Calibration is
performed
mV
225 C32
CAL mV
Stability check:
The value is accepted if the
stability level is ≤pH ± 1 mV for
more than 10 seconds.
A0002436-EN
C33
Zero point is
displayed
-100 to +100
mV
mV
0 C33
Zero
A0002437-EN
C34
Calibration status
is displayed
o. k.
E xxx
o.k. C34
Status
A0002438-EN
Endress+Hauser
83
Commissioning
Liquisys M CCM223/253
Coding Field
Range of
adjustment
(factory
settings in
bold)
C35
Yes
No
New
Store calibration
result?
Display
Info
yes C35
Store
If C34 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
A0002439-EN
C(4)
Zero point
CALIBRATION
function group:
Zero point
CCS120
Zero C
CALIBRAT
Zero point calibration for
CCS120
A0006376-EN
C12
Zero point
calibration?
No
Yes
no C12
Zero cal
A0002421-EN
C14
Calibration status
is displayed
o. k.
E xxx
Only if A1 = 120
Zero point calibration:
1. Pass unchlorinated water
through the assembly.
2. Wait for 10 minutes.
3. Accept by selecting YES and
pressing ENTER
o.k. C14
Status
A0002423-EN
C15
Store calibration
result?
Yes
No
New
yes C15
Store
If C14 = E xxx, then only No or
New. If New, then return to C.
If Yes/No, then return to
"Measurement".
A0002424-EN
84
Endress+Hauser
Liquisys M CCM223/253
Diagnostics and troubleshooting
8
Diagnostics and troubleshooting
8.1
Trouble shooting instructions
The transmitter continuously monitors its functions itself. If an error occurs which the
device recognizes, this is indicated on the display. The error number is shown below the
display of the main measured value. If more than one error occurs, you can call these up
with the MINUS key.
Refer to the "System error messages" table for the possible error numbers and remedial
measures.
Should a malfunction occur without any transmitter error message, please refer to the
"Process-specific errors" or the "Device-specific errors" tables to localize and rectify the error.
These tables provide you with additional information on any spare parts required.
8.2
System error messages
You can display and select the error messages with the MINUS key.
Error
No.
E001
E002
E003
E004
E007
E010
E032
E033
Endress+Hauser
Display
Tests/remedial action
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
• Switch off device and
switch it on again.
• Load software
compatible with
Device not calibrated,
hardware
calibration data
invalid, no user data or • Load measurementparameter specific
user data invalid
device software.
(EEPROM error),
• If the error persists,
device software not
send in the device for
suitable for hardware
repair to your local
(controller)
sales center or replace
the device.
Yes
No
X
0C
X
0C
X
0C
X
0C
Download error
Invalid configuration.
Repeat download.
Yes
X
0C
X
0C
Load software compatible
with hardware
Load measurementparameter specific device
software.
Yes
X
0C
X
0C
X
0C
X
0C
No
80
EEPROM memory
error
Device software
version not compatible
with module hardware
version
Transmitter
malfunction, device
software not
compatible with
transmitter version
Yes
Yes
Temperature sensor
defective, not
connected or shortcircuited
(measurement
continues with 25 °C)
Check temperature sensor Yes
and connections; check
the measuring device and
measuring cable with a
temperature simulator if
necessary.
Upper or lower pH
slope range exceeded
No
Repeat calibration and
replace buffer solution; if
necessary, replace sensor
pH value zero point too and check the device and
low or too high
No
No
No
No
No
No
0C
No
No
X
80
X
80
X
80
85
Diagnostics and troubleshooting
Error
No.
E034
E035
E038
E041
E042
E043
E044
E045
E055
E056
E057
E058
E059
86
Liquisys M CCM223/253
Display
ORP offset range
exceeded or below
range
Tests/remedial action
measuring cable with a
simulator.
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
No
44
No
Sensor 963 zero point
signal outside
permitted range
• Service the sensor (in
accordance with sensor
manual).
• Check connections.
• Check activated carbon
filter.
No
Cl sensor signal
outside permitted
range during slope
calibration
• Service the sensor (in
accordance with sensor
manual).
• Check connections.
• Check DPD measuring
device.
• Do not use organic
chlorination agent.
No
Calculation of
calibration parameters
aborted
Repeat calibration and
replace buffer solution;
replace sensor if
necessary, check device
and measuring cable.
No
Distance between
buffer value and zero
point (pH7) too small
(single-point
calibration)
For slope calibration, use
a buffer solution which
has at least a distance of
ΔpH = 2 to the electrode
zero point.
No
Distance between
buffer 1 and buffer 2
calibration values too
small (two-point
calibration)
Use buffer solutions
which differ by at least
Δ pH = 2.
No
Stability requirement
not met during
calibration
Repeat calibration and
replace buffer solution; if
necessary, replace sensor
and check the device and
measuring cable with a
simulator.
No
Check measurement and
connections; if necessary,
check device and
measuring cable with a
simulator.
Yes
Calibration aborted
Lower Cl/ClO2
measuring range
exceeded
Lower pH/mV
measuring range
exceeded
No
No
No
No
No
No
No
No
No
No
80
Yes
No
No
44
80
Upper Cl/ClO2
measuring range
exceeded
Yes
Upper pH/mV
measuring range
exceeded
Yes
Below temperature
measuring range
Yes
No
No
44
80
No
No
44
80
No
No
80
44
Endress+Hauser
Liquisys M CCM223/253
Diagnostics and troubleshooting
Error
No.
E061
E063
E064
E065
E066
E067
E068
E069
E070
E080
E081
E085
E100
E101
E102
E106
E116
E152
Endress+Hauser
Display
Tests/remedial action
Temperature
measuring range
exceeded
Below current output
range 1
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
Yes
No
No
80
44
Check measured value
and current assignment
Yes
Yes
Below current output
range 2
Yes
Current output range 2
exceeded
Yes
Check configuration
Yes
Set point exceeded
limit contactor 4
Yes
Current output 1 range Increase range in "Current
too small
outputs" menu.
Yes
Current output 2 range
too small
Yes
No
No
80
No
No
80
No
No
80
No
No
80
80
No
No
80
80
No
No
80
80
If the current range "0 to
20 mA" was selected in
field O311, the error
current may not be set to
"2.4 mA".
Current simulation
active
Yes
No
No
No
No
Switch off service function No
or switch device off and
then on again.
No
No
No
Wait for download to
finish.
No
Repeat download.
Yes
• Check and service the
sensor and connection,
and replace if
necessary.
X
80
X
80
X
80
X
80
No
80
80
Yes
Manual mode active
Measuring signal of
Cl/ClO2 parameter
delayed or frozen
80
80
Yes
Download error
No
80
Set point exceeded
limit contactor 3
Download active
No
80
Yes
Service function active
80
80
Set point exceeded
limit contactor 2
Incorrect setting for
error current
No
80
Current output range 1
exceeded
Set point exceeded
limit contactor 1
No
No
No
No
No
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
80
X
0C
X
0C
No
44
44
87
Diagnostics and troubleshooting
Error
No.
E153
E154
E155
E156
E157
E158
E159
E160
E161
E162
E163
88
Liquisys M CCM223/253
Display
Tests/remedial action
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
No
44
Measuring signal of
pH/mV parameter
delayed or frozen
• Check whether medium No
has really changed or
not.
No
Cl/ClO2 below lower
alarm threshold for
period exceeding
alarm delay
• Perform manual
comparison
measurement if
necessary.
• Service the sensor (in
accordance with sensor
manual).
• Recalibrate the
measuring system.
• Check the flow.
• Check the chemical
supply.
• Check dosing devices.
No
Cl/ClO2 above upper
alarm threshold for
period exceeding
alarm delay
Actual Cl/ClO2 value
undershoots alarm
threshold for longer
than the set
permissible maximum
period
Yes
Yes
X
No
No
X
X
Yes
No
No
X
X
Yes
pH/mV below lower
alarm threshold for
period exceeding
alarm delay
Yes
pH/mV above upper
alarm threshold for
period exceeding
alarm delay
Yes
Actual pH/mV value
undershoots alarm
threshold (CC
setpoint) for longer
than the set
permissible maximum
period
Yes
Actual pH/mV value
exceeds alarm
threshold (CC
setpoint) for longer
than the set
permissible maximum
period
Yes
Uncompensated
chlorine value too
imprecise since pH
value > 9
No
X
Actual Cl/ClO2 value
exceeds alarm
threshold for longer
than the set
permissible maximum
period
Dosage stop
44
No
No
X
X
No
No
X
X
No
No
X
X
No
No
X
X
No
No
X
X
Check settings in the
CURRENT INPUT and
CHECK function groups.
Yes
Check pH value and adjust Yes
according to system
requirements. If pH values
> 9, the disinfection effect
is questionable since the
chlorine now exists as the
less effective OCl-.
No
No
X
X
No
No
X
X
Endress+Hauser
Liquisys M CCM223/253
Diagnostics and troubleshooting
Error
No.
E170
E171
E172
E173
Display
Tests/remedial action
Alarm
contact
Error
current
Autom.
cleaning
start
PROFIBU
S
Status
Facty
Facty
Facty
PV 1)
User
User
User
Temp
No
No
X
Flow through
assembly too low or
zero
Restore flow. Check
medium pipe.
Yes
Flow in main stream
too low or zero
Restore flow.
Yes
X
No
No
X
X
Switch-off limit for
Check process variables at Yes
current input exceeded sending measuring device.
Change range assignment
Current input < 4 mA if necessary.
Yes
No
No
X
X
No
No
X
X
E174
Current input > 20 mA
Yes
No
No
X
X
1)
8.3
PV = process variable, primary value
Process-specific errors
Use the following table to localize and rectify any errors occurring.
Error
Possible cause
Tests/remedial action
Tools, spare parts
Replace fuse
Fine-wire fuse, M 250 V /
3.15 A
No power supply
Establish power supply
Check with voltmeter
Automatic controller
switch-off due to alarm
Determine cause according to
error code Exxx and eliminate.
Current output simulation
End the simulation
Chlorine
measurement:
Slope too low
Sensor was in chlorinefree water or in air.
Short conditioning over (not in!) Chlorine bleach / chlorine
chlorine bleach, wait for
parent solution
conditioning time in water
before calibration.
No match with
DPD control
measurement
Measurement takes place Measure chlorine value pHwithout pH compensation, compensated
while DPD measurement is
always buffered to pH 6.3.
Select CCM223/253 with
ES option (manual
compensation) or EP
(automatic compensation).
DPD measured
value much too
high
Organic chlorination agent Use free (gaseous) chlorine or
used (may also be used
chlorine from inorganic chlorine
only at times or for shock compounds.
chlorination). In this case,
no correlation between
actual free chlorine, DPD
measurement and
amperometric
measurement. DPD value
too high by a factor of up
to 5.
If organic chlorination
agent was used previously,
the entire system must be
evacuated and carefully
cleaned!
Chlorine value too
high
Membrane defective
Replace membrane cap.
Replacement cartridges
CCY 14-WP
Polarization not complete
Wait for polarization time to
finish
Be patient
Foreign oxidizing agent
Analyze medium
Detailed knowledge of the
process
No device function Device fuse defective
Display flashes
Endress+Hauser
89
Diagnostics and troubleshooting
Error
Chlorine value too
low
Chlorine value
wrong/cannot be
calibrated; zero
current too large
pH/mV
measurement:
Measuring chain
zero-point cannot
be adjusted
No or slow change
of readings
Measuring chain
slope not
adjustable/
slope too low
Measuring chain
slope not
adjustable/
No slope
Liquisys M CCM223/253
Possible cause
Tests/remedial action
Tools, spare parts
Shunt in chlorine sensor
Replace sensor
Replacement sensor
Measuring chamber not
closed
Refill and screw closed carefully
Electrolyte
Air cushion outside in
front of membrane
Remove air bubble, possibly
select better installation
position
Air cushion inside
membrane
Refill and screw closed so that it Electrolyte
is bubble-free
Wrong polarization
voltage
Measure polarization voltage,
replace MKC1 module if
necessary.
Wrong sensor type
selected
Check sensor selection
Contaminated reference
system
Test with new sensor
pH/mV sensor
Membrane clogged
Clean or grind membranes (not
with TEFLON® membranes)
HCl 3%, needle file (only
file in one direction); new
sensor
Measuring line open
Short-circuit pH input and
connect to PM -> reading pH 7
Asymmetric sensor
voltage too high
Clean junction or test with
another sensor
HCl 3%, needle file (only
file in one direction); new
sensor
Potential matching of
Liquisys -> medium
incorrect
Always connect CCM223/253
symmetrically with PM.
Wiring diagrams
Sensor fouled
Clean sensor
Cleaning agent
Sensor old
Replace sensor
New sensor
Sensor defective
(reference lead)
Replace sensor
New sensor
Connection not at high
impedance
(moisture, dirt)
Check cable, plug connector and pH simulator, insulation
junction boxes
tester
Device input defective
pH measurement directly at
device
pH simulator
Sensor old
Replace sensor
pH sensor
Hair-line crack in the glass Replace sensor
membrane
pH sensor
Connection not at high
impedance
Constant, incorrect Sensor does not immerse
measured value
properly or protection cap
not removed
Check cable, plug connector and pH simulator, insulation
junction boxes
tester
Check installation position,
remove protection cap
Air pockets in assembly
Check assembly and installation
position
Grounding short at or in
device
Perform test measurement in
insulated vessel, perform with
buffer solution if required.
Hair-line crack in the glass Replace sensor
membrane
90
DVM (+) at S or 90, DVM
(-) at 91
CCS140/141: -20 mV
CCS240/241: +120 mV
Plastic vessel, buffer
solutions
pH sensor
Endress+Hauser
Liquisys M CCM223/253
Diagnostics and troubleshooting
Error
Incorrect
temperature value
Incorrect pH
measured value in
the process
Fluctuations in
measured value
Tests/remedial action
Tools, spare parts
Device in impermissible
operating condition (does
not respond when key
pressed)
Disconnect line voltage for
approx. 10 seconds
Possibly EMC problem: if
problem persists, check
grounding and wire
routing.
Incorrect sensor
connection
Check connections using wiring Wiring diagram in
diagram. Three-wire connection "Electrical connection"
always required
section
Sensor or measuring cable
defective
Check sensor and cable
Flow too high
Reduce flow or measure in a
bypass.
Potential in medium
Possibly ground with or/at PM
pin (connect PA/PM with PE).
Problem mainly occurs in
plastic lines.
Sensor fouling or buildup
on sensor
Clean sensor
For heavily contaminated
media: use spray cleaning
Ohmmeter
Interference on measuring Connect cable shield as per
cable
wiring diagram
See the "Electrical
connection" section
Interference on signal
output cable
Check cable routing, possibly
route cable separately
Route signal output and
measuring input lines
separately
Interference potential in
medium
Eliminate source of interference
or ground medium as close as
possible to sensor.
No potential matching on
symmetrical input
Connect PM pin in assembly to
device terminal PA/PM.
Controller or timer No relay module available
cannot be
activated
Install LSR1-2 or LSR1-4
module
Controller/limit
contact does not
work
Controller switched off
Activate controller
See fields R2xx
Controller in operating
mode "Manual off"
Select "Auto" or "Manual on"
mode
Keyboard, REL key
Pickup delay setting too
long
Switch off or shorten pickup
delay time
See fields R2xx
"Hold" function active
“Auto hold” for calibration,
“Hold” input activated;
“Hold” active via keyboard
See fields S2 to S4
Controller in operating
mode "Manual on"
Select "Auto" or "Manual off"
mode
Keyboard, REL and AUTO
keys
Dropout delay setting too
long
Shorten dropout delay time
See fields R2xx
Control loop interruption
Check measured value, current
output value, actuators,
chemical supply
Cable disconnected or
short-circuited
Disconnect cable and measure
directly at device
Output defective
See the "Device-specific errors"
section
Fixed current
output signal
Current simulation active
Switch off simulation.
See field O3
Impermissible operating
state of processor system
Disconnect line voltage for
approx. 10 seconds
Possibly EMC problem: if
problem persists, check
grounding and wire
routing.
Incorrect current
output signal
Incorrect current
assignment
Check current assignment: 0–
20 mA or 4–20 mA?
Field O311
Controller/limit
contact works
continuously
No current output
signal
Endress+Hauser
Possible cause
mA meter 0–20 mA
91
Diagnostics and troubleshooting
Error
Current output
table is not
accepted
Liquisys M CCM223/253
Possible cause
Tests/remedial action
Tools, spare parts
Total load in the current
loop too high (> 500 Ω)
Disconnect output and measure
directly at device
mA meter for 0–20 mA DC
EMC (interference
coupling)
Disconnect both output cables
and measure directly at device
Use shielded cables, ground
shields at both ends, where
necessary route cable in
another cable duct
Value interval too small
Select practical intervals
No output signal
Device does not have a
for temperature or second current output
pH/mV
Check version using nameplate,
if necessary replace the LSCHx1 module
LSCH-x2 module, see the
"Spare parts" section
Device with PROFIBUS-PA
PA device has no current
output!
Chemoclean
function not
available
No relay module (LSR1-x)
installed or only LSR1-2
available
Install LSR1-4 module.
Chemoclean is enabled using
the release code supplied by the
manufacturer in the
Chemoclean retrofit kit.
Plus Package
functions not
available
Plus Package not enabled • For Plus Package retrofit:
(enable by entering a code
code is supplied by E+H →
which depends on the
enter this code.
serial number and which is • After replacing a defective
supplied by E+H when a
LSCH/LSCP module: first
Plus Package is ordered)
enter device serial number
manually (see nameplate),
then enter the existing code
number.
No HART
communication
No HART central module
Verify using nameplate: HART = Upgrade to LSCH-H1 / -H2
-xxx5xx and -xxx6xx
No or incorrect DD (device
description)
For further information, see
BA00208C/07/EN, "HART field
communication with Liquisys
CxM223/253”
HART interface missing
LSR1-4 module, see the
"Spare parts" section
For a detailed description,
see the "Replacement of
central module" section.
Load too small (must be >
230 Ω)
HART receiver (e.g. FXA
191) not connected via
load but via power supply
Incorrect device address
(addr. = 0 for single
operation, addr. > 0 for
multidrop operation)
Line capacitance too high
Interference on line
No PROFIBUS
communication
Several devices set to same Assign addresses correctly
address
No communication possible
if several devices set to the
same address
No PA/DP central module
Verify using the nameplate: PA
= -xxx3xx /DP = xxx4xx
Upgrade to LSCP module,
see the "Spare parts" section
Incorrect device software
version (without
PROFIBUS)
For further information, see
BA00209C/07/EN "PROFIBUS
PA/DP - Field communication
for Liquisys CxM223/253".
Information about
PROFIBUS configuration is
provided in Technical
Information TI00260F,
while detailed information
about instrumentation and
accessories is provided in
Operating Instructions
BA00198F
With Commuwin (CW) II:
CW II version and device
software version
incompatible
No or incorrect DD/DLL
92
Endress+Hauser
Liquisys M CCM223/253
Diagnostics and troubleshooting
Error
Possible cause
Tests/remedial action
Tools, spare parts
Incorrect baud rate setting
for segment coupler in
DPV-1 server
Bus user (master) has
wrong address or address
assigned twice
Bus user (slave) has wrong
address
Bus line not terminated
Line problems (too long,
cross-section too small,
not shielded, shield not
grounded, wires not
twisted)
Bus voltage too low
(Bus voltage typ. 24 V DC
for non-Ex)
8.4
The voltage at the device's
PA/DP connector must be at
least 9 V
Device-specific errors
The following table helps you during the diagnosis and points to any spare parts required.
Depending on the degree of difficulty and the measuring equipment present, diagnosis is
carried out by:
• Trained operator personnel
• The user's trained electrical technicians
• Company responsible for system installation/operation
• Endress+Hauser Service
Information on the exact spare part designations and on how to install these parts can be
found in the "Spare parts" section.
Endress+Hauser
Error
Possible cause
Tests/remedial action
Execution, tools, spare
parts
Device cannot be
operated, display
value 9999
Operation locked
Press CAL and MINUS keys
simultaneously.
See the "Key functions"
section
Display dark, no
light-emitting
diode active
No line voltage
Check whether line voltage is
present
Electrical technician / e.g.
multimeter
Supply voltage
wrong/too low
Compare actual line voltage
and nameplate data
User (data for energy supply
company or multimeter)
Connection faulty
• Terminal not tightened
• Insulation jammed
• Wrong terminals used
Electrical technician
Device fuse defective
Compare line voltage and the
nameplate data and replace
fuse
Electrical technician/suitable
fuse; see exploded drawing in
the the "Spare parts" section
Power unit defective
Replace power unit, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Central module defective
Replace central module, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Field device: ribbon cable
loose or defective
Check ribbon cable, replace if
necessary
See the "Spare parts" section
93
Diagnostics and troubleshooting
Error
Liquisys M CCM223/253
Possible cause
Tests/remedial action
Execution, tools, spare
parts
Display dark, light- Central module defective
emitting diode
(module: LSCH/LSCP)
active
Replace central module, note
version
Onsite diagnosis by Endress
+Hauser Service, test module
necessary
Values appear on
display but:
• Display does not
change and / or
• Device cannot
be operated
Device or module in
device not correctly
mounted
Panel-mounted device: reinstall Perform with the aid of the
insert.
installation drawings in the
Field device: remount display
the "Spare parts" section
module
Impermissible operating
system condition
Disconnect line voltage for
approx. 10 seconds
Possibly Possible EMC
problem: if this persists,
check the installation or have
checked by Endress+Hauser
Service
Device gets hot
Voltage wrong/too high
Compare line voltage and
nameplate data
User, electrical technician
Power unit defective
Replace power unit
Diagnosis only by Endress
+Hauser Service
Cl/ClO2 measured
value and/or
temperature
measured value
incorrect
Transmitter module
defective (module:
MKIC), please first carry
out tests and take
measures as per the
"Process-specific errors"
section
Measuring input test:
• Chlorine input open = display
0.00 mg/l
• 10 kΩ resistance at terminals
11 + 12 = display 25 °C
If test negative: replace
module (note version)
Perform with the aid of the
exploded drawings in the
"Spare parts" section.
Current output,
incorrect current
value
Incorrect adjustment
Check with integrated current
simulation, connect mA meter
directly to current output.
If simulation value incorrect:
adjustment in factory or new
LSCH module required.
If simulation value correct:
check current loop for load
and shunts.
Load too large
Shunt / short to ground
in current loop
Incorrect mode of
operation
Check whether 0–20 mA or 4–
20 mA is selected.
No current output
signal
Current output stage
defective (only for LSCH
module; LSCP has no
current output)
Check with integrated current
simulation, connect mA meter
directly to current output
If test negative:
Replace central module (note
version)
Additional relays
not working
Field device: ribbon cable
loose or defective
Check ribbon cable seating,
replace cable if required.
See the "Spare parts" section
Only 2 additional
relays can be
triggered
LSR1-2 relay module
with 2 relays is installed
Upgrade to LSR1-4 with 4
relays.
User or Endress+Hauser
Service
Additional
functions (Plus
Package) missing
No or incorrect release
code used
If retrofitting: check whether
the correct serial number was
quoted when ordering the Plus
Package.
Handled by Endress+Hauser
Sales
Incorrect device serial
number saved in LSCH/
LSCP module
Check whether serial number
on the nameplate matches SNR
in LSCH/ LSCP (field S 8).
The serial number of the
device is definitive for the
Plus Package.
Replacement modules
LSCH or LSCP have the
device serial number
0000 when they leave
the factory. The Plus
Package or Chemoclean
are not enabled on
leaving the factory.
In the case of LSCH/LSCP with
SNR 0000, a device serial
number can be entered once in
fields E115 to E117.
Then enter the release codes
for the Plus Package and/or
Chemoclean if necessary.
For a detailed description,
see the "Replacement of
central module" section.
Additional
functions (Plus
Package and/or
Chemoclean)
missing after
LSCH/LSCP
module
replacement
94
Endress+Hauser
Liquisys M CCM223/253
Maintenance
Error
Possible cause
Tests/remedial action
Execution, tools, spare
parts
No HART or
PROFIBUS PA/DP
interface function
Incorrect central module
HART: LSCH-H1 or H2 module,
PROFIBUS-PA: LSCP-PA
module,
PROFIBUS-DP: LSCP-DP
module,
see field E112.
Replace central module;
User or Endress+Hauser
Service.
Wrong software
SW version, see field E111.
Bus problem
Remove some devices and
repeat the test.
9
Contact Endress+Hauser
Service.
Maintenance
LWARNING
Process pressure and temperature, contamination, electrical voltage
Risk of serious or fatal injury
‣ If the sensor has to be removed during maintenance work, avoid hazards posed by
pressure, temperature and contamination.
‣ Make sure the device is de-energized before you open it.
‣ Power can be supplied to switching contacts from separate circuits. De-energize these
circuits before working on the terminals.
Take all the necessary precautions in time to ensure the operational safety and reliability
of the entire measuring point.
The maintenance of the measuring point comprises:
• Calibration
• Cleaning the controller, assembly and sensor
• Checking the cables and connections
When performing any work on the device, bear in mind any potential impact this may
have on the process control system or on the process itself.
NOTICE
Electrostatic discharge (ESD)
Risk of damaging the electronic components
‣ Take personal protective measures to avoid ESD, such as discharging beforehand at PE
or permanent grounding with a wrist strap.
‣ For your own safety, only use genuine spare parts. With genuine parts, the function,
accuracy and reliability are also ensured after maintenance work.
9.1
Maintenance of the entire measuring point
9.1.1
Cleaning the transmitter
Clean the front of the housing using commercially available cleaning agents only.
The front of the housing is resistant to the following in accordance with DIN 42 115:
• Ethanol (for a short time)
• Diluted acids (max. 2% HCl)
• Diluted alkaline solutions (max. 3% NaOH)
• Soap-based household cleaning agents
When performing any work on the device, bear in mind any potential impact this may
have on the process control system or on the process itself.
Endress+Hauser
95
Maintenance
Liquisys M CCM223/253
NOTICE
Prohibited cleaning agents
Damage to the housing surface or housing seal
‣ Never use concentrated mineral acids or alkaline solutions for cleaning.
‣ Never use organic cleaners such as benzyl alcohol, methanol, methylene chloride,
xylene or concentrated glycerol cleaner.
‣ Never use high-pressure steam for cleaning purposes.
9.1.2
Cleaning the pH/mV sensors (EP version)
LCAUTION
Cleaning not switched off during calibration or maintenance activities
Risk of injury due to medium or cleaning agent
‣ If a cleaning system is connected, switch if off before removing a sensor from the
medium.
‣ If you wish to check the cleaning function and have therefore not switched off the
cleaning system, please wear protective clothing, goggles and gloves or take other
appropriate measures.
LCAUTION
Risk of injury from cleaning agents
‣ When using the following cleaning agents, make sure to protect your hands, eyes and
clothing.
Please clean contamination on the glass electrodes as follows:
• Oily and greasy films:
Clean with hot water or temperature-controller detergent (grease remover, e.g. alcohol,
acetone, possibly dishwashing detergent).
• Lime and metal hydroxide buildup:
Dissolve buildup with diluted hydrochloric acid (3 %) and then rinse thoroughly with
plenty of clear water.
• Sulfidic buildup (from flue gas desulfurization or sewage treatment plants):
Use a mixture of hydrochloric acid (3 %) and thiocarbamide (commercially available) and
then rinse thoroughly with plenty of clear water.
• Buildup containing proteins (e.g. food industry):
Use a mixture of hydrochloric acid (0.5 %) and pepsin (commercially available) and then
rinse thoroughly with plenty of clear water.
• Fibers, suspended substances:
Pressurized water, surface-active agents if necessary
• Light biological buildup:
Pressurized water
ORP electrodes:
Carefully clean the metal pins or surfaces mechanically.
After mechanical cleaning, the ORP sensor can require several hours conditioning
time. For this reason, check the calibration after one day.
ISFET sensors
• Never use acetone to clean ISFET sensors as this could damage the material.
• After being cleaned with compressed air, ISFET sensors require approx. 5 to 8 minutes
until the closed-control loop is re-established and the measured value has adjusted to
the real value.
Clogged membranes can be cleaned mechanically under certain circumstances (does not
apply to ISFET sensors, Teflon membranes and open ring junction electrodes):
• Use a small warding file.
• Only file in one direction.
96
Endress+Hauser
Liquisys M CCM223/253
Maintenance
Air bubbles in the electrode:
• Air bubbles can indicate incorrect mounting. For this reason check the orientation.
• The range 15° to 165° to the horizontal is allowed (ISFET sensors are the exception).
• Not permitted: horizontal installation or installation with the plug-in head pointing
downwards.
> 15°
> 15°
A0027183
44
Permitted angle of installation for glass electrodes
Check for reference system reduction
The inner reference lead of the reference system (Ag/AgCl) of a combination electrode or
a separate reference electrode is usually brownish and matt. A silver-colored reference
system is reduced and therefore defective. This is caused by a current flowing through the
reference element.
Possible causes for the current flow:
• Incorrect measuring device operating mode selected (PML pin connected, but operating
mode asymmetrical ("without PML"). See also the function description for "Selecting the
connection type".
• Shunt in measuring cable (e.g. due to moisture) between reference line and grounded
shield or PM line.
• Measuring device defective (shunt in reference input or entire input amplifier
downstream of PE).
9.1.3
Maintenance of chlorine sensors
Please refer to the Operating Instructions for your sensor for sensor maintenance and
troubleshooting:
CCS120
BA00388C/07/EN
CCS140/141
BA00058C/07/EN
CCS240/241
BA00114C/07/EN
963
BA00039C/07/EN
The Operating Instructions contain detailed information including:
• Sensor design and function
• Mounting and installation
• Electrical connection
• Commissioning and calibration
• Calculation examples and tables for verification of measured values
• Maintenance, regeneration, cleaning
• Troubleshooting table
• Accessories and spare parts
• Technical data and ordering information
9.1.4
Assembly
Refer to the assembly operating manual for information on servicing and troubleshooting
the assembly. The assembly operating manual describes the procedure for mounting and
disassembling the assembly, replacing the sensors and seals, and contains information on
the material resistance properties, as well as on spare parts and accessories.
Endress+Hauser
97
Maintenance
Liquisys M CCM223/253
9.1.5
Maintenance of pH connecting cables and junction boxes (EP
version)
Check the cables and connections for moisture. Moisture is indicated by a sensor slope that
is too small. If nothing more can be displayed or if the display is fixed at pH 7, please check
the following components:
• Sensor head
• Sensor plug
• Junction box, if fitted
• Extension cable
NOTICE
Incorrect measurements caused by moisture in the measuring cable
‣ If there is moisture in the measuring cable, the cable must be replaced!
A shunt in the cable of > 20 MΩ cannot be measured with normal multimeters but is
damaging for the pH measurement. Connect a pH simulator instead of the sensor. The
value that is displayed on the transmitter must match the value set at the simulator. The
value can differ at the second decimal place at the very maximum.
If you do not have a pH simulator, you can test the cable with a commercially available
megohmmeter. Please note the following when performing the test:
• Make sure to disconnect the pH measuring cable from the sensor and device!
• If you are using a junction box, you should check the infeed and outfeed measuring cable
separately.
• Check the cable with 1000 V DC (at least with 500 V DC) testing voltage.
• If the cable is intact, the insulation resistance is > 100 GΩ.
• If the cable is defective (moist), there is flashover.
The cable must be replaced.
You can clean (desalinate) the sensor head and junction box with de-ionized water
and dry them with a hot air dryer.
9.2
Test and simulation
9.2.1
Chlorine sensors
Chlorine sensors work according to the amperometric principle and supply very small
direct currents as the measuring signal.
A chlorine sensor can be simulated by a DC source. Due to the small currents, however, the
simulation is highly sensitive. Use shielded cables and ground the simulator. Typical slope
values are provided in the table below:
98
Sensor
Typical slope value
CCS120
Approx. 115 nA per mg Cl/l
CCS140
Approx. 25 nA per mg Cl/l
CCS141
Approx. 80 nA per mg Cl/l
CCS240
Approx. 100 nA per mg ClO2/l
CCS241
Approx. 350 nA per mg ClO2/l
963
Approx. 20 μA per mg Cl/l
Endress+Hauser
Liquisys M CCM223/253
Maintenance
9.2.2
Temperature measurement
The transmitter uses the NTC sensor of the chlorine sensor to measure the temperature.
Due to the relatively high sensor resistance, a two-wire connection is sufficient.
Simulation can be performed with a normal decade resistor. The table below contains
some simulation values:
Temperature
NTC simulation value
0 °C (32 °F)
29.490 kΩ
10 ° C (50 °F)
18.787 kΩ
20 °C (68 °F)
12.268 kΩ
25 °C (77 °F)
10.000 kΩ
30 °C (86 °F)
8.197 kΩ
40 °C (104 °F)
5.594 kΩ
9.2.3
pH/ORP measurement
Simulation is performed with a pH/mV simulator or an mV voltage source.
In the case of the CCM223/253, the pH or mV must always be measured
symmetrically. For this reason, each simulation requires potential matching with the
simulator. Connect the reference signal of the simulator (normal shield of the pH
coaxial measuring line) to the PA/PM terminal of the transmitter.
Zero point rapid test
• In the case of the panel-mounted device, connect the BNC inner conductor to the BNC
receptacle and the PM terminal.
• In the case of the field device, connect the pH terminal, the Ref terminal and the PM
terminal.
• For pH the reading must be approx. 7, and for ORP approx. 0 mV.
Test with DC supply point
pH value
Simulation
2
295 mV
4
177 mV
7
0 mV
9
-118 mV
12
-295 mV
9.2.4
Flow monitoring
Flow is monitored by an inductive proximity switch (INS) in the CCA250 assembly. This
switch is powered by 15 V from the auxiliary voltage output of the transmitter.
Function of the INS
Flow
INS
INS output
Yes
damped
low impedance
No
not damped
high-impedance
Test or emergency mode
Endress+Hauser
99
Maintenance
Liquisys M CCM223/253
If you connect terminal 93 to terminal 85 and terminal 94 to terminal 86, this simulates
an active proximity switch and thus a correct flow.
Do not run the measuring system continuously in this state. Reestablish flow
monitoring as soon as possible!
100
Endress+Hauser
Liquisys M CCM223/253
Repair
10
Repair
10.1
Spare parts
Please order spare parts from your local Sales Office. For this purpose, use the order
numbers listed in the "Spare part kits" section.
For safety, you should always provide the following additional data when ordering spare
parts:
• Device order code
• Serial number
• Software version, if possible
You can take the order code and serial number from the nameplate.
The software version is provided in the device software provided that the device processor
system is still working.
For more detailed information on spare parts kits, please refer to the "Spare Part Finding
Tool" on the Internet:
www.endress.com/spareparts_consumables
10.2
Disassembling the panel-mounted device
Please note the effects on the process if the device is taken out of service!
See the exploded drawing for the item numbers.
1.
Disconnect the terminal block (item 150 to 180) from the rear of the device to deenergize the device.
2.
Press in the latches of the end frame (item 340) and remove the frame from the rear.
3.
Release the special screw (item 400) by turning it counter-clockwise.
4.
Remove the entire electronics block from the housing. The modules are only
mechanically connected and can be easily separated:
5.
Simply remove the processor/display module towards the front.
6.
Pull out the brackets of the rear plate (item 320) slightly.
7.
Now you can remove the side modules.
8.
Remove the Cl transmitter (item 110/120) as follows:
9.
Using a fine wire cutter, nip off the heads of the synthetic distance holders.
10. Then remove the module from above.
Assembly is the reverse of the disassembly sequence. Tighten the special screw fingertight without using a tool.
Endress+Hauser
101
Repair
Liquisys M CCM223/253
150 -170
340
400
210
200
110/120
10/20
50 - 100
C
130
320
310
180
30 - 45
10
15
A
230 V
B
115 V
100 V
A0001912
45
102
Exploded drawing of panel-mounted device
Endress+Hauser
Liquisys M CCM223/253
Repair
The exploded drawing contains the components and spare parts of the panel-mounted
device. You can take the spare parts and the corresponding order number from the
following section using the item numbers.
Item
Kit description
Name
Function/contents
Order no.
10
Power unit (main
module)
LSGA
100/115/230 V AC
51500317
15
Jumper
20
Power unit (main
module)
LSGD
24 V AC + DC
51500318
30
Relay module
LSR1-2
2 relays
51500320
35
Relay module
LSR2-2i
2 relays + 4-20 mA current input
51504304
35
Kit for Cxm2x3 relay
module
PROFIBUS DP
LSR2-DP
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134732
40
Relay module
LSR1-4
4 relays
51500321
45
Relay module
LSR2-4i
4 relays + 4-20 mA current input
51504305
50
Central module
LSCH-S1
1 current output
51502467
50
Kit for CCM2x3 central
module
PROFIBUS DP
LSCP
PROFIBUS DP central module
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134731
60
Central module
LSCH-S2
2 current outputs
51502468
70
Central module
LSCH-H1
1 current output + HART
51502497
80
Central module
LSCH-H2
2 current outputs + HART
51502496
90
Central module
LSCP-PA
PROFIBUS PA/no current output
51502495
100
Central module
LSCP-DP
PROFIBUS DP/no current output
51502498
110
Cl transmitter
MKC1
Input Cl and temperature
51502466
120
Cl/pH transmitter
MKC1
Input Cl, pH/mV, temperature
51502465
Housing module
Housing with front membrane, sensory
tappets, seal, special screw, tensioning
dogs, connection plates and nameplates
51501075
150
Complete terminal strip
set
Standard + HART
Terminal strip set, inputs/outputs,
power supply, alarm relay
51502463
160
Complete terminal strip
set
PROFIBUS-PA
Terminal strip set, inputs/outputs,
power supply, alarm relay
51502464
170
Complete terminal strip
set
PROFIBUS-DP
Terminal strip set, inputs/outputs,
power supply, alarm relay
51502490
180
Terminal strip
Terminal strip for relay modules
51501078
200
pH input socket
Socket with screen plate
51501070
210
BNC connector
BNC easy solder-free, angled
50074961
Rear plate, side panel, end frame, special
screw
51501076
End frame
PROFIBUS-DP
Rear frame for PROFIBUS DP, with Dsubmin plug connector
51502513
A
Fuse
Part of power unit, item 10
B
Choice of line voltage
Position of jumper on power unit, item 10
depending on line voltage
C
End frame latches
Part of the end frame
130, 400
310, 320, Housing mechanical
340, 400 parts
340
Endress+Hauser
Part of power unit, item 10
103
Repair
Liquisys M CCM223/253
10.3
Disassembling the field device
Please note the effects on the process if the device is taken out of service!
See the exploded drawing for the item numbers.
You require the following tools to disassemble the field device:
• Standard set of screwdrivers
• Torx screwdriver, size TX 20
Proceed as follows to disassemble the field device:
1.
Open and remove the cover of the connection compartment (item 420).
2.
Disconnect the supply terminal (item 270)) to de-energize the device.
3.
Open the display cover (item 410) and release the ribbon cables (item 250) on the
central module side (item 50 to 100) .
4.
To remove the central module (item 50) release the screw in the display cover (item
450 b).
5.
Proceed as follows to remove the electronics box (item 230) :
6.
Turn the screws in the housing base (item 450 a) by two revolutions to release them.
7.
Then push the entire box backwards and remove it from above while making sure
that the module locks do not open.
8.
Release the ribbon cables (item 250) .
9.
Bend the module locks out and remove the modules.
10. To remove the docking module (item 240) remove the screws in the housing base
(item 450 c) and remove the entire assembly from above.
11. To remove the CI transmitter (item 110/120) on devices with a pH/mV input, bend
the shielding plate up.
12. Disconnect the connected strand (pH input, strand comes from the BNC connection
jack) and nip off the heads of the synthetic distance sleeves using a fine wire cutter.
13. Then remove the module from above.
To assemble, carefully push the modules into the guide rails of the electronics box and let
them engage in the side box noses.
It is not possible to mount the modules incorrectly. Modules inserted in the electronics
box incorrectly are not operable since the ribbon cables cannot be connected.
Make sure the cover seals are intact to guarantee IP 65 ingress protection.
104
Endress+Hauser
Liquisys M CCM223/253
Repair
A
B
10
15
C
410
370
230 V
D
115 V
50 - 100
100 V
450b
460b
230
450a
250
400
460a
430
420
110/120
280
30 - 45
10/20
240
450c
480
270
A0001915
46
Field device exploded drawing
Endress+Hauser
105
Repair
Liquisys M CCM223/253
The exploded drawing contains the components and spare parts of the field device. You
can take the spare parts and the corresponding order number from the following section
using the item numbers.
Item
Kit description
Function/contents
Order no.
51500317
10
Power unit (main module) LSGA
100/115/230 V AC
15
Jumper
Part of power unit, item 10
20
Power unit (main module) LSGD
24 V AC + DC
51500318
30
Relay module
LSR1-2
2 relays
51500320
35
Relay module
LSR2-2i
2 relays + 4-20 mA current input
51504304
35
Kit for Cxm2x3 relay
module
PROFIBUS DP
LSR2-DP
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134732
40
Relay module
LSR1-4
4 relays
51500321
45
Relay module
LSR2-4i
4 relays + 4-20 mA current input
51504305
50
Central module
LSCH-S1
1 current output
51502467
50
Kit for CCM2x3 central
module
PROFIBUS DP
LSCP
PROFIBUS DP central module
Relay module + 2 relays
Curr. input + DP terminals
Hardware version 2.10 and higher
71134731
60
Central module
LSCH-S2
2 current outputs
51502468
70
Central module
LSCH-H1
1 current output + HART
51502497
80
Central module
LSCH-H2
2 current outputs + HART
51502496
90
Central module
LSCP-PA
PROFIBUS PA/no current output
51502495
100
Central module
LSCP-DP
PROFIBUS DP/no current output
51502498
110
Cl transmitter
MKC1
Input Cl and temperature
51502466
120
Cl/pH transmitter
MKC1
Input Cl, pH/mV, temperature
51502465
Inner housing fittings
Docking module, empty electronics box,
small parts
51501073
250
Ribbon cable lines
2 ribbon cable lines
51501074
270
Terminal strip
Terminal strip for connection to power
supply
51501079
280
pH terminal
pH terminal with shielding plate
51501071
370, 410, Housing cover
420, 430,
460
Display cover, connection compartment
cover, front membrane, hinges, cover
screws, small parts
51501068
400, 480
Base, threaded joints
51501072
Rear plate, side panel, end frame, special
screw
51501076
230, 240
Housing base
310, 320, Housing mechanical parts
340, 400
106
Name
A
Electronics box with relay
module LSR1-x (bottom)
and power unit LSGA/
LSGD (top)
B
Fuse also accessible if
electronics box installed
C
Fuse
Part of power unit, item 10
D
Choice of line voltage
Position of jumper on power unit, item
10 depending on line voltage
Endress+Hauser
Liquisys M CCM223/253
Repair
10.4
Replacing the central module
Generally, when a central module has been replaced, all data which can be changed
are set to the factory setting.
If possible, note the customized settings of the device, such as:
• Calibration data
• Current assignment, main parameter and temperature
• Relay function selections
• Limit value/controller settings
• Cleaning settings
• Monitoring functions
• Interface parameters
Proceed as described below if a central module is replaced:
1.
Disassemble the device as explained in the "Dismantling the panel-mounted
instrument" or "Dismantling the field instrument" section.
2.
Use the part number on the central module to check whether the new module has
the same part number as the previous module.
3.
Reassemble the device with the new module.
4.
Put the device back into operation and check the basic functions (e.g. measured value
and temperature display, operation via keyboard).
5.
Read the serial number (“ser-no.”) off the nameplate of the device (e.g.
6A345605G00) and enter this number in fields E115 (1st digit = year, one-digit (6
in the example)), E116 (2nd digit: month, one-digit (A in the example)), E117 (digits
3-6 cons. number, four-digit (3456 in the example)).
In the field E118, the complete number is displayed again so you can check it is
correct.
You can only enter the serial number for new modules with the serial number 0000.
This can only be done once! For this reason, make sure the number entered is correct
before you press ENTER to confirm!
If an incorrect code is entered, the additional functions are not enabled. An incorrect
serial number can only be corrected at the factory!
1.
Press ENTER to confirm the serial number or cancel the entry to enter the number
again.
2.
If available, enter the release codes for the Plus Package and/or Chemoclean in the
"Service" menu.
3.
Check the Plus Package release (e.g. by opening the function group CHECK / Code P)
or the Chemoclean function.
4.
Make the customized device settings again.
10.5
Return
The product must be returned if repairs or a factory calibration are required, or if the
wrong product was ordered or delivered. As an ISO-certified company and also due to legal
regulations, Endress+Hauser is obliged to follow certain procedures when handling any
returned products that have been in contact with medium.
To ensure swift, safe and professional device returns, please read the return procedures
and conditions at www.endress.com/support/return-material.
Endress+Hauser
107
Repair
Liquisys M CCM223/253
10.6
Disposal
The device contains electronic components and must therefore be disposed of in
accordance with regulations on the disposal of electronic waste.
Observe the local regulations.
108
Endress+Hauser
Liquisys M CCM223/253
Accessories
11
Accessories
11.1
Sensors
CCS120
• Amperometric sensor for total chlorine
• Measuring range 0.1 to 10 mg/l
• Product Configurator on the product page: www.endress.com/ccs120
Technical Information TI00388C
CCS140
• Membrane-covered amperometric sensor for free chlorine
• Measuring range 0.05 to 20 mg/l
• Product Configurator on the product page: www.endress.com/ccs140
Technical Information TI00058C
CCS141
• Membrane-covered amperometric trace sensor for free chlorine
• Measuring range 0.01 to 5 mg/l
• Product Configurator on the product page: www.endress.com/ccs141
Technical Information TI00058C
CCS240
• Membrane-covered amperometric sensor for chlorine dioxide
• Measuring range 0.05 to 20 mg/l
• Product Configurator on the product page: www.endress.com/ccs240
Technical Information TI00114C
CCS241
• Membrane-covered amperometric trace sensor for chlorine dioxide
• Measuring range 0.01 to 5 mg/l
• Product Configurator on the product page: www.endress.com/ccs241
Technical Information TI00114C
11.2
Connection accessories
Measuring cable CYK71
• Unterminated cable for connecting analog sensors and for extending sensor cables
• Sold by the meter, order numbers:
– Non-Ex version, black: 50085333
– Ex-version, blue: 50085673
CPK1
For pH/ORP electrodes with GSA plug-in head
Ordering information is available from your sales office or at www.endress.com.
CPK9
• Terminated measuring cable for connecting analog sensors with TOP68 plug-in head
• Selection in accordance with product structure
For more information and to order, please contact your sales office.
Endress+Hauser
109
Accessories
Liquisys M CCM223/253
MK extension cable
• Twin-core signal cable with additional shielding and PVC insulation
• Particularly for the transmission of output signals of transmitters or input signals of
controllers and for temperature measurement.
• Order number: 50000662
VBC junction box
• For cable extension (for chlorine measuring systems)
• Dimensions (B x D x H): 125 x 80 x 54 mm (4.92 x 3.15 x 2.13 ")
• 10 terminal strips
• Cable entries: 7 x Pg 7, 2 x Pg 11
• Material: aluminum
• Degree of protection: IP 65 (i NEMA 4x)
• Order No. 50005181
VBM
• Junction box for cable extension
• 10 terminal strips
• Cable entries: 2 x Pg 13.5 or 2 x NPT ½"
• Material: aluminum
• Degree of protection: IP 65
• Order numbers
– Cable entries Pg 13.5 : 50003987
– Cable entries NPT ½": 51500177
11.3
Installation accessories
CYY101
• Weather protection cover for field devices
• Absolutely essential for field installation
• Material: stainless steel 1.4301 (AISI 304)
• Order No. CYY101-A
270 (10.6)
320 (12.6)
300 (11.8)
A0024627
47
Dimensions in mm (inch)
Flexdip CYH112
• Modular holder system for sensors and assemblies in open basins, channels and tanks
• For Flexdip CYA112 water and wastewater assemblies
• Can be affixed anywhere: on the ground, on the capstone, on the wall or directly onto
railings.
• Stainless steel version
• Product Configurator on the product page: www.endress.com/cyh112
Technical Information TI00430C
110
Endress+Hauser
Liquisys M CCM223/253
Accessories
30 (1.18)
Ø max. 60 (2.36)
M6
60 (2.36)
90 (3.54)
70 (2.76)
Ø 8 (0.31)
90 (3.54)
70 (2.76)
Ø 8 (0.31)
Post mounting kit
• For securing the field housing to horizontal and vertical posts and pipes
• Material: stainless steel 1.4301 (AISI 304)
• Order No. 50086842
Ø 6 (0.24)
70 (2.76)
90 (3.54)
A0024660
48
Dimensions in mm (inch)
11.4
Software and hardware add-ons
The add-ons can only be ordered by quoting the serial number of the device in question.
• Plus Package
Order No. 51502242
• Chemoclean function (requires four-relay card)
Order No. 51502871
• Two-relay card
Order No. 51500320
• Four-relay card
Order No. 51500321
• Two-relay card with current input
Order No. 51504304
• Four-relay card with current input
Order No. 51504305
• pH package for EK version
Order No. 51502460
• pH package for ES version
Order No. 51503526
11.5
Metering system
Compact measuring station CCE10/CCE11
• Fully assembled and wired panel for one or three transmitters, with CCA250-A1 flow
assembly
• Product Configurator on the product page: www.endress.com/cce10 or
www.endress.com/cce11
Technical Information TI00440C
Endress+Hauser
111
Accessories
Liquisys M CCM223/253
11.6
Calibration accessories
Photometer PF-3
• Compact hand-held photometer for determining free available chlorine
• Color-coded reagent bottles with clear dosing instructions
• Order No.: 71257946
112
Endress+Hauser
Liquisys M CCM223/253
Technical data
12
Technical data
12.1
Input
Measured variables
Total chlorine
Free available chlorine
Chlorine dioxide
Temperature
pH value or ORP (optional)
Cl2/ClO2 signal input
CCS120/140/141/240/241:
Sensor 963:
0 to 5000 nA
-100 to 500 µA
Temperature measurement
Temperature sensor for
CCS120/140/141/240/241:
Display range:
NTC, 10 kΩ at 25 °C (77 °F)
pH and ORP measurement
pH measuring range:
ORP measuring range:
Zero point adjustment:
Slope adjustment
pH 3.5 to 9.5
0 to 1500 mV
±100 mV
38 to 65 mV/pH
Binary inputs
Voltage
Current consumption
10 to 50 V
Max. 10 mA
Current input
4 to 20 mA, galvanically isolated
0 to 50 °C (32 to 122 °F)
Load: 260 Ω for 20 mA (voltage drop 5.2 V)
12.2
Output signal
Output
HART
Signal encoding
Frequency Shift Keying (FSK) + 0.5 mA via current output signal
Data transmission rate
1200 baud
Galvanic isolation
Yes
PROFIBUS PA
Endress+Hauser
Signal encoding
Manchester Bus Powered (MBP)
Data transmission rate
31.25 kBit/s, voltage mode
Galvanic isolation
Yes (IO modules)
113
Technical data
Liquisys M CCM223/253
PROFIBUS DP
Signal encoding
RS485
Data transmission rate
9.6 kBd, 19.2 kBd, 93.75 kBd, 187.5 kBd, 500 kBd, 1.5 MBd
Galvanic isolation
Yes (IO modules)
Signal on alarm
2.4 or 22 mA in the event of an error
Load
Max. 500 Ω
Transmission range
Cl2/ClO2
CCS120
CCS140/240
CCS141/241 and 963
Temperature
pH
ORP
0 to 10 mg/l
0 to 20 mg/l
0 to 5 mg/l
0 to 50 °C (32 to 120 °F)
4 to 9
0 to 1500 mV
Signal resolution
Max. 700 digits/mA
Separation voltage
Max. 350 VRMS / 500 V DC
Auxiliary voltage output
Output voltage
Output current
15 V ± 0.6 V
Max. 10 mA
Contact outputs
Switching current with ohmic load (cos φ = 1)
Switching current with inductive load (cos φ =
0.4)
Switching voltage
Switching power with ohmic load (cos φ = 1)
Switching power with inductive load (cos φ =
0.4)
Max. 2 A
Max. 2 A
Limit contactors
Pickup/dropout delay
0 to 2000 s
Controller
Function (configurable)
114
Max. 250 V AC, 30 V DC
Max. 500 VA AC, 60 W DC
Max. 500 VA AC, 60 W DC
Pulse length/pulse frequency controller,
continuous controller
Three-point step controller for Cl2/ClO2
Controller behavior
P, PI, PD, PID, basic load dosing
Control gain Kp
0.01 to 20.00
Integral action time Tn
0.0 to 999.9 min
Derivative action time Tv
0.0 to 999.9 min
Period length for pulse length controller
0.5 to 999.9 s
Frequency for pulse frequency controller
60 to 180 min-1
Basic load
0 to 40 % of max. actuating variable
Motor run time for three-point step controller 10 to 999 s
Neutral zone for three-point step controller 0 to 40 %
Endress+Hauser
Liquisys M CCM223/253
Alarm
Technical data
Function (switchable)
Alarm threshold adjustment range
Alarm delay
Monitoring time for lower limit violation
Monitoring time for upper limit violation
Protocol-specific data
Latching/momentary contact
Cl2/ClO2/pH/ORP/temperature: entire
range
0 to 2000 s
0 to 2000 min
0 to 2000 min
HART
Manufacturer ID
11h
Device type
0094h
Transmitter-specific revision
0001h
HART version
5.0
Device description files (DD)
www.endress.com/hart
HART load (communication resistor)
250 Ω
Device variables
None (only dynamic variables PV and SV)
Supported features
-
PROFIBUS PA
Manufacturer ID
11h
Device type
1518h
Device revision
0001h
Profile version
2.0
GSD files
www.endress.com/profibus
GSD version
Output values
Primary value, temperature
Input variables
PCS display value
Supported features
Device lock: The device can be locked
using the hardware or software.
PROFIBUS DP
Manufacturer ID
11h
Device type
151Eh
Profile version
2.0
GSD files
www.endress.com/profibus
GSD version
Endress+Hauser
Output values
Primary value, temperature
Input variables
PCS display value
Supported features
Device lock: The device can be locked
using the hardware or software.
115
Technical data
Liquisys M CCM223/253
12.3
Supply voltage
Power supply via fieldbus
Power supply
Depending on order version:
• 100/115/230 V AC +10/-15 %, 48 to 62 Hz
• 24 V AC/DC +20/-15 %
HART
Supply voltage
Not applicable, active current outputs
Reverse polarity protection
Not applicable, active current outputs
PROFIBUS PA
Supply voltage
9 V to 32 V, max. 35 V
Sensitivity to reverse polarity
No
FISCO/FNICO compliant according to IEC
60079-27
No
PROFIBUS DP
Supply voltage
9 V to 32 V, max. 35 V
Sensitivity to reverse polarity
Not applicable
FISCO/FNICO compliant according to IEC
60079-27
No
Power consumption
Max. 7.5 VA
Mains fuse
Fine-wire fuse, semi-delay 250 V/3.15 A
Circuit breaker
NOTICE
The device does not have a power switch
‣ The customer must provide a protected circuit breaker in the vicinity of the device.
‣ The circuit breaker must be a switch or power switch, and you must label it as the
circuit breaker for the device.
‣ At the supply point, the power supply for the 24 V versions must be isolated from
dangerous live cables by double or reinforced insulation.
Cable specification
Cable length (CCS140/141/240/241)
Cable length (chlorine sensor 963)
Cable length (CCS120)
Cable length (pH/ORP)
Overvoltage protection
According to EN 61000-4-5
116
Max. 30 m (98 ft) with CMK cable
Max. 30 m (98 ft) with CMK cable
Max. 15 m (49 ft) with CPK9 cable
Max. 50 m (160 ft) with cable CYK71
Endress+Hauser
Liquisys M CCM223/253
Technical data
12.4
Performance characteristics
Reference operating
conditions
Reference temperature:
25 ˚C (77 ˚F)
Measured value resolution
CCS120/140/240 and 963
CCS141/241
pH value
ORP
Temperature
0.01 mg/l
0.001 mg/l
0.01 pH
1 mV
0.1 °C
Maximum measured error
Display(pH, T = const.)
CCS140/141/240/241
CCS120 and 963
Temperature
Signal output
CCS140/141/240/241/
CCS120/963
pH
ORP
Temperature
Max. 0.5 % of measured value ± 4 digits
Max. 1 % of measured value ±4 digits
0.03 pH
3 mV
±0.3 K
Max. 0.75 % of measuring range
Max. 1.25 % of current output range
Max. 1.25 % of current output range
Max. 1.25 % of measuring range
Measured errors in accordance with DIN IEC 746 Part 1, at rated operating conditions
Repeatability
Max. 0.2 % of measuring range
12.5
Environment
Ambient temperature
range
-10 to +55 °C (+10 to +130 °F)
Storage temperature
–25 to +65 °C (-10 to +150 °F)
Electromagnetic
compatibility
Interference emission and interference immunity as per EN 61326-1:2006, EN
61326-2-3:2006
Degree of protection
Field device
Panel-mounted device
Electrical safety
As per EN/IEC 61010-1:2010, overvoltage category II for installations up to
2000 m (6500 ft) above MSL
CSA
Device versions with CSA General Purpose approval are certified for indoor use.
Endress+Hauser
IP 65 / integrity according to NEMA 4X
IP 54 (front), IP 30 (housing)
117
Technical data
Liquisys M CCM223/253
Relative humidity
10 to 95%, not condensing
Degree of contamination
The product is suitable for pollution degree 2.
12.6
Mechanical construction
Field device
L x B x D: 96 x 96 x 145 mm (3.78" x 3.78" x 5.71")
Installation depth: approx. 165 mm (6.50 ")
L x B x D: 247 x 170 x 115 mm (9.72" x 6.69" x 4.53")
Weight
Panel-mounted device
Field device
Max. 0.7 kg (1.54 lbs.)
Max. 2.3 kg (5.07 lbs.)
Materials
Panel-mounted device housing
Field housing
Front membrane
Polycarbonate
ABS PC FR
Polyester, UV-resistant
Terminals
Cable cross-section
Max. 2.5 mm2 (14 AWG)
Dimensions
118
Panel-mounted device
Endress+Hauser
Liquisys M CCM223/253
Appendix
13
Endress+Hauser
Appendix
119
Appendix
Liquisys M CCM223/253
Zero calibration
(only if A1 = 120)
CALIBRATION
zero
(CCS120)
Calibration status is
displayed
no; yes
o.k.
CALIBRAT
Cl2 / ClO2
C14
Zero calibration
(only if A1 = 120 or 963)
Enter
DPD value
no; yes
Value of last cal.
C
C11
Operating matrix versions EK and ES
yes; no; new
Exxx
C15
Store calibration
result
C15
Slope is
displayed
100% min. 25% (3%)
max. 500%
C12
Calibration status
is displayed
o.k.
Store
calibration
Exxx
yes; no; new
C13
C14
C15
Edit:
Code 22
Read:
any code
MEAS. VALUE
DISPLAY
with
TEMPERATURE
READING
in °C
Meas. value display
Meas. value display
Meas. value display
Meas. value display
Meas. value display
Temperature reading in °F
no temp. display
Sensor current in nA
Current input in mA
Current input in %
1st error displayed
Other errors are
displayed
(up to max. 10 errors)
(if present)
Only display switchover!
Edit:
Code 22
Read:
any code
Select sensor
140; 141; 240; 241;
963; 120
SETUP 1
A
mg/l; ppm; ppb
Off; INS
B2
Cont. switch-off
by current input
Off; Input
B3
0s
Z
0 ... 2000 s
Sw.-off direction
for current input
0 ... 100%
read
O
Output1; Output2
°C; mg/l; ppm; ppb; Contr
O1
Select contact type
F
F1
lin = linear
min; s
F2
Select
table pairs
1
1 ... no. Table pair
asign
1 ... 10
O332
O333
O321
Select current range
Enter 0/4 mA value
Enter 20 mA value
4–20 mA; 0–20 mA
0.00; 0 ... 20 (5) mg/l
0 °C; 0 ... 50 °C
2.0 (0.5); 0 ... 20 (5) mg/l
50 °C; 0 ... 50 °C
O3(1)
O311
Define
error current
Alarm delay
0 min (s)
0 ... 2000 min (s)
(dep. on F2)
Select unit of alarm
delay
Latch = latching c.
Momen = momentary c.
ALARM
O2
1
O331
O3(2)
CURRENT OUTPUT
Z6
Enter simulation
val.
current value
0 ... 22.0 mA
sim = Simulation
Select meas. unit for
2nd current output
Off; lin = linear
Z5
Enter no. of
table pairs
edit
O3(3)
Feedforward control
to PID cont.
Low; High
Z4
Select table
options
Select current output
A6
B5
Z3
Tab = Table
Clean trig.
A5
Enter temperature
difference (offset)
current offset
–5.0 ... + 5.0 °C
50%
0 ... 2000 s
Z2
Select
digital input 1
ext.Hold
0 ... 2000 s
0s
Sw.-off limit value
for current input
Delay for cont.
sw.-on current input
Delay for contr.
swi.-on sam. stream
A4
B4
0s
Z1
0 ... 2000 s
A3
Enter correct
process temperature
current meas. value
0 ... 50 °C
Delay for cont.
switch-off curr. input
Delay for controller
switch-off sam. stream
0s
A2
Manual
pH compensation
last comp. value
pH 4.00 ... 9.00
Off; Manu
B
CURRENT INPUT
Controller switch-off
by sample stream
A1
PH compensation
SETUP 2
Select display unit
Select error number
22 mA; 2.4 mA
F3
O312
1
F4
1 ... 255
O313
Enable alarm
contact
yes; no
F5
F6
A0002633-EN
120
Endress+Hauser
Liquisys M CCM223/253
Appendix
Enter meas.
value damping
1 (no damping)
1 ... 60
A7
Feedforward control
gain = 1 at
50%
0 ... 100%
Z7
Enter x value (meas. val.)
Enter y value (current)
Table status o.k.
0.00; 0 ... 20 (5) mg/l
0 °C; 0 ... 50 °C
4.00 mA 0 ... 20.00 mA
yes; no
O334
O335
Enable error current
for error just entered
Automatic start
of cleaning function
no; yes
no; yes
F7
F8
O336
Select “next error”
or return to menu
next = next error
<---R
F9
A0002634-EN
Endress+Hauser
121
Appendix
Liquisys M CCM223/253
CHECK
Chlorine / ClO2
P
P1(1)
P111
Switch function R2(8)
on or off
int = internal
ext = external
Off; On
R2(7)
Timer
Off; On; Basic; PID+B
R2(4)
RELAY
Rel1; Rel2; Rel3; Rel4
Switch function R2(3)
on or off
Off; On; Basic; PID+B
S+C = for param. + cal.
Setup = for param.
S
Hardware version
SW Version
HW Version
E1(4)
Main (= mainboard)
E141
Trans (= transmitter)
Hardware version
SW Version
HW Version
E131
E+H SERVICE
Contr (= controller)
E
Hardware version
SW Version
HW Version
E121
SW Version
HW Version
E111
E112
0s
Select switch-off point
of contact
20 (5) mg/l
0 ... 20 (5) mg/l
R234
Set pick-up
delay
0s
0 ... 2000 s
R213
10 s
Serial number
is displayed
0 ... 2000 s
R233
Enter Hold
dwell time
S3
R244
Set pick-up
delay
0 ... 50 °C
R212
Off; On
0.0 min 0.0 ... 999.9 min
R243
R232
Select switch-on point
of contact
20 (5) mg/l
0 ... 20 (5) mg/l
R264
R214
Enter SW upgrade
release code (Plus pack.)
0
0 ... 999 s
S4
0 ... 9999
S5
Module identification
is displayed
E143
E144
Module identification
is displayed
Serial number
is displayed
E133
E134
Module identification
is displayed
Serial number
is displayed
E123
E124
Module identification
is displayed
Serial number
is displayed
E113
E114
Tag description
HART: 0 ... 15 or
PROFIBUS: 1 ... 126
I
Hardware version
0.01 ... 100.00
50 °C
0 ... 50 °C
E122
Instrument software
E1(1)
Enter address
INTERFACE
50 °C
R273
Enter integral action time
Tn (0.0 = no I comp.)
Enter switch-off
temperature
Enter switch-on
temperature
E132
Module software
E1(2)
1.00
R242
E142
Module software
E1(3)
Enter control
gain Kp
0.5 (0.1) mg/l
0 ... 20 (5) mg/l
S2
Module software
0 ... 999 s
R263
Enter setpoint
Manual Hold
CAL = with Cal.
no = no Hold
S1
Rel (= relay)
360 min
1 ... 7200 min
R262
R211
Configure Hold
Select language
ENG; GER; FRA;
ITA; NEL; ESP
SERVICE
Off; On
R2(1)
20 s
Define minimum
pause time
120 min
1 ... 3600 min
Define pause time
0 ... 999 s
R231
Switch contact R2(1)
on or off
LC PV =
limit contactor
Cl2 / ClO2
R1
R
Define rinse time
R241
R2(3)
Select contact to
be configured
i+ext = internal + external
i+stp = int. w. suppression by ext.
R261
Switch function R2(4)
on or off
R284
Enter pre-rinse time
R272
30 s
Off; On
R2(6)
0.0 min 0.0 ... 999.9 min
R283
R271
Switch function R2(6)
on or off
LC °C =
Limit contactor
T
0.01 ... 100.00
1.00
P115
Enter integral action time
Tn (0.0 = no I comp.)
Select start pulse
Switch function R2(7)
on or off
Clean =
Chemoclean
(only with Rel3 and Rel4)
Enter control
gain Kp
R282
R281
Select process
monitoring
Off; AC; CC; AC CC
AC!; CC!; ACCC!
P114
Enter setpoint
0.5 (0.1) mg/l
0 ... 20 (5) mg/l
Off; On
R2(8)
PID controller
Cl2 / ClO2
P113
P112
3-point step controller
Cl2 / ClO2
(only with Rel3 and Rel4)
Set upper
alarm threshold
20.00 (5.00) mg/l
0.1 ... 20 (5) mg/l
Set lower
alarm threshold
0.00 mg/l
0 ... 19.9 (4.9) mg/l
Alarm delay
0 min (s)
0 ... 2000 min (s)
(dep. on F2)
Select alarm threshold
monitoring
Off; Low; High
LoHi; Lo!; Hi!; LoHi!
@@@@@@@@
I1
I2
A0002635-EN
122
Endress+Hauser
Liquisys M CCM223/253
Set max. perm. period of
lower limit exceeding
60 min
0 ... 2000 min
Appendix
Set max. perm. period of
upper limit exceeding
120 min
0 ... 2000 min
P117
P116
Enter min. switch-on
time tON
0.3 s
0.1 ... 5.0 s
Motor run time
60 s
10 s
10%
20 s
0 ... 999 s
R274
3-p. step contr.: assigns 2 contacts,
only permitted for contacts 3+4
0 ... 40%
R286
Enter post-rinse time
0 ... 999 s
P118
Neutral zone
10 ... 999 s
R285
Enter cleaning
time
Set
limit value
0.5 (0.1) mg/l
0 ... 20 (5) mg/l
R287
Define period between
two cleaning cycles
(pause time)
360 min 1 ... 7200 min
Define repeat
times
0
0 ... 5
R275
R276
Define min.
pause time
120 min 1 ... R277 min
Number of cleaning
cycles without
cleaning agent
0 0 ... 9
R278
R277
R279
Chemoclean: assigns 2 contacts,
only permitted for contacts 3+4
Enter deriv. action time
Tv (0.0 = no D comp.)
Select
control characteristic
0.0 min 0.0 ... 999.9 min
inv; dir
R245
Set drop-out
delay
0s
50 °C
R235
0 ... 2000 s
R215
Enter SW upgrade
release code Chemocl.
0
R247
Enter
pulse period
10.0 s
0.5 ... 999.9 s
R249
R248
Enter min switch-on
time tON
0.3 s
0.1 ... 5.0 s
R2410
Enter basic load
0%
0 ... 40%
R2411
Display LC status
R236
R216
Order number
is displayed
R237
Display LC status
MAX; MIN
R217
R216
Serial number
is displayed
Reset instrument
0 ... 9999
Start instrument test
no; sens; factory
S6
Enter
max. pulse frequency
120 1/min
60 ... 180 1/min
MAX; MIN
0 ... 50 °C
Set alarm
threshold (as abs. value)
20 (5) mg/l
0 ... 20 (5) mg/l
Set dropout
delay
0s
R246
Set alarm
threshold (as abs. value)
0 ... 2000 s
Select
len = pulse length
freq = pulse frequency
curr = current output 2
S7
S8
no; display
S9
S10
A0002636-EN
Endress+Hauser
123
Appendix
Liquisys M CCM223/253
Zero calibration
(only if A1 = 120)
CALIBRATION
zero
(CCS120)
Calibration status is
displayed
no; yes
o.k.
Enter value of ORP
buffer
Buffer value of last cal.
0 ... 1500 mV
CALIBRATION
ORP mV
(dep. on B1)
C14
Enter calibration
temperature
CALIBRATION
pH
(dep. on B1)
25.0 °C –10 ... +60 °C
Enter pH value
of first buffer solution
Buffer value of last cal.
pH 3.50 ... 9.50
Adopt if stable
pH ±0.05 (> 10 s)
C23
C12
C35
Calibrating
Calibration status is
displayed
C25
C26
Store calibration
result
yes; no; new
Exxx
o.k.
Slope is
displayed
59.16 mV/pH
38.00 ... 65.00 mV/pH
Adopt if stable
pH ±0.05 (> 10 s)
C24
Slope is
displayed
100% min. 25% (3%)
max. 500%
no; yes
C11
C34
Enter pH value
of second buffer solution
Buffer value of last cal.
pH 3.50 ... 9.50
Calibrating
Enter calibration
results
yes; no; new
Exxx
o.k.
C33
C22
Value of last cal.
C
–100 ... +100 mV
Zero calibration
(only if A1 = 963)
Enter DPD
calibration value
Calibration status is
displayed
C32
C21
CALIBRATION
Cl2 / ClO2
C15
Zero point is
displayed
Calibrating
Adopt if stable
±1 mV (> 10 s)
C31
Operating matrix version EP
yes; no; new
Exxx
C15
Store calibration
result
C13
C14
C15
Edit:
Code 22
Read:
any code
MEAS. VALUE
DISPLAY
with
TEMPERATURE
DISPLAY
in °C
Meas. value display
Meas. value display
Meas. value display
Meas. value display
Meas. value display
Temperature display in °F
No temp. display
pH; ORP (dep. on B1)
pH signal in mV
Sensor current in nA
1st error is displayed
Other errors are
displayed
(up to max. 10 errors)
Delay for contr.
sw.-off by sample stream
Delay for contr.
sw.-on by sample stream
Select
digital input 1
(if present)
Edit:
Code 22
Read:
any code
Display unit
Select sensor
140; 141; 240; 241;
963; 120
SETUP 1
A
SETUP 2
Controller switch-off
by sample stream
mg/l; ppm; ppb
Off; INS
Select operating mode
pH compensation
Off; pH; ORP mV
Off; Manu; Auto
B
0s
A2
A1
B1
0 ... 2000 s
A3
Enter correct
process temperature
current meas. value
0 ... 50 °C
Manual
pH compensation
last comp. value
pH 4.00 ... 9.00
B2*
ext.Hold
0 ... 2000 s
0s
A6
Enter temperature
difference (offset)
current offset
–5.0 ... + 5.0 °C
B4
B3
Clean Trig.
A5
A4
B5
* field B2 not available for CCS240/241
Controller switch-off
by current input
Off; Input
CURRENT INPUT
0s
Z1
Z
Delay for controller
sw.-off current input
Delay for controller
sw.-on current input
0 s 0 ... 2000 s
50%
0 ... 2000 s
Z2
Switch-off direction
for current input
Switch-off limit
for current input
Low; High
0 ... 100%
Z3
read
O3(3)
sim = simulation
O3(2)
Select current output
Select meas. parameter
for 2nd current output
Output1; Output2
°C; pH; ORPmV; Contr
O
O1
O2
edit
1
O331
1 ... 10
Z6
Select table
pairs
1
1 ... No. of table pairs
asign
O332
O333
Enter simulation
value
current value
0 ... 22.0 mA
O321
Select current range
lin = linear
O3(1)
Z5
Enter number of
table pairs
4–20 mA; 0–20 mA
CURRENT OUTPUT
Off; lin = linear
Z4
Select table
options
Tab = Table
Feedforward control
to PID controller
O311
Enter 0/4-mA value
0.00 mg/l; 0 ... 20 (5) mg/l
0.00 ppm; 0 … 20 ppm
0 ppb; 0 … 20000 ppb
pH 4.00; pH 4 ... 9
0 mV; 0 ... 1500 mV
0 °C; 0 ... 50 °C
O312
Enter 20-mA value
2.0 (0.5); 0 ... 20 (5) mg/l
2.0 ppm; 0 … 20 ppm
2000 ppb; 0 … 20000 ppb
pH 9.00; pH 4 ... 9
1000 mV; 0 ... 1500 mV
50 °C; 0 ... 50 °C
O313
A0002637-EN
124
Endress+Hauser
Liquisys M CCM223/253
Appendix
Calibration status is
displayed
Zero point is
displayed
pH 7.00
pH 5.00 ... 9.00
o.k.
C27
Store calibration
results
yes; no; new
Exxx
C28
Meas. value display
Meas. value display
Current input in mA
Current input in %
C29
Only LCD switchover!
Enter meas.
value damping
1 (no damping)
1 ... 60
A7
Feedforward control
gain = 1 at
50%
0 ... 100%
Z7
Enter x value (meas. val.)
0.,00; 0 ... 20 (5) mg/l
pH 4.00; pH 4 ... 9
0 mV; 0 ... 1500 mV
0 °C; 0 ... 50 °C
Enter y value (current)
Table status o.k.
4.00 mA 0 ... 20.00 mA
yes; no
O334
O335
O336
A0002638-EN
Endress+Hauser
125
Appendix
Liquisys M CCM223/253
Select contact type
ALARM
F
min; s
F1
F2
Select alarm threshold
monitoring
Off; Low; High; Lo Hi
Low!; High!; LoHi!
ORP mV
(dep. on B1)
P1(2)
CHECK
Select alarm threshold
monitoring
Off; Low; High
Lo Hi; Low!; High!; LoHi!
Chlorine / ClO2
P
3-point step controller
Cl2 / ClO2
(only with Rel3 and Rel4)
Alarm delay
0 min (s)
0 ... 2000 min (s)
(depending on F2)
Alarm delay
0 min (s)
0 ... 2000 min (s)
(depending on F2)
Switch function R2(8)
on or off
Off; On
Off; On; Basic; PID+B
Off; On; Basic; PID+B
R2(4)
Switch function R2(3)
on or off
Off; On
R
R1
R2(1)
pH 4.1 ... 9
P124
Switch function R2(2)
on or off
Off; On
Off; On
R211
Select process
monitoring
Off; AC; CC; AC CC
AC!; CC!; ACCC!
P115
Enter control
gain Kp
Enter integral action time
Tn (0.0 = no I comp.)
0.01 ... 100.00
1.00
0.0 min 0.0 ... 999.9 min
R283
R284
Select start pulse
Enter pre-rinse time
i+ext = internal + external
i+stp = int. w. suppression of ext.
20 s
0 ... 999 s
R273
R272
Define rinse time
0 ... 999 s
360 min
1 ... 7200 min
R263
pH 4 ... 9
0.0 min 0.0 ... 999.9 min
R253
Enter setpoint
R254
Enter integral action time
Tn (0.0 = no I comp.)
Enter control
gain Kp
1.00
0.0 min 0.0 ... 999.9 min
0.01 ... 100.00
R242
Set switch-on
temperature
Enter integral action time
Tn (0.0 = no I comp.)
0.01 ... 100.00
1.00
R252
0.5 (0.1) mg/l; 0 ... 20 (5) mg/l
0.5 ppm; 0 … 20 ppm
500 ppb; 0 … 20000 ppb
R264
Enter control
gain Kp
Enter setpoint
pH 7.20
Define min. pause
time
120 min
1 ... 3600 min
Define pause time
R262
R243
R244
Set switch-off
temperature
0 ... 50 °C
R232
Select contact
switch-on point
1500 mV
0 ... 1500 mV
R222
Select contact
switch-on point
pH 9
pH 4 ... 9
R221
Switch function R2(1)
on or off
P125
P114
R282
R221
R2(2)
RELAY
pH 9.00
Enter setpoint
R231
Switch function R2(2)
on or off
P125
Select process
monitoring
Off; AC; CC; AC CC
AC!; CC!; ACCC!
Set upper
alarm threshold
20.00 mg/l; 0 ... 20 mg/l
20.00 ppm; 0 … 20 ppm
20000 ppb; 0 … 20000 ppb
0.5 (0.1) mg/l; 0 ... 20 (5) mg/l
0.5 ppm; 0 … 20 ppm
500 ppb; 0 … 20000 ppb
50 °C
Off; On
R2(2)
LC PV =
Limit contactor
Cl2 / ClO2
Off; AC; AC!
P124
P113
R241
R2(3)
Rel1; Rel2; Rel3; Rel4
1500 mV 10 ... 1500 mV
Set upper
alarm threshold
0.00 mg/l; 0 ... 20 mg/l
0.00 ppm; 0 … 20 ppm
0 ppb; 0 … 20000 ppb
R251
Switch function R2(4)
on or off
Select contact to
be configured
Set lower
alarm threshold
R261
R2(5)
LC pH =
Limit contactor
pH
(dep. on B1)
Select process
monitoring
P123
30 s
Switch function R2(5)
on or off
LCORP =
Limit contactor
ORP
(dep. on B1)
pH 4 ... 8.9
F6
Set upper
alarm threshold
R271
R2(6)
LC °C =
Limit contactor
T
pH 4.00
int = internal
ext = external
Off; On
PID controller
Cl2 / ClO2
Set lower
alarm threshold
Switch function R2(7)
on or off
Off; On
yes; no
F5
P123
R281
Switch function R2(6)
on or off
PID controller
pH
0 ... 1490 mV
P112
R2(7)
Timer
0 mV
P122
R2(8)
Clean =
Chemoclean
(only with Rel3 and Rel4)
Set lower
alarm threshold
Enable alarm
contact
1 ... 255
1
F4
P122
P111
P1(1)
22 mA; 2.4 mA
Alarm delay
0 min (s)
0 ... 2000 min (s)
(depending on F2)
P121
P1(2)
Select error number
F3
P121
Select alarm threshold
monitoring
Off; Low; High; Lo Hi
Low!; High!; LoHi!
pH
(dep. on B1)
Define
error current
Alarm delay
0 min (s)
0 ... 2000 min (s)
(depending on F2)
Select unit for
alarm delay
Latch = latching c.
Momen = momentary c.
R222
50 °C
Set pick-up
delay
0 ... 50 °C
0s
R234
Set pick-up
delay
Select contact
switch-off point
1500 mV
0 ... 1500 mV
0s
0 ... 2000 s
R223
R224
Set pick-up
delay
Select contact
switch-off point
pH 9
pH 4 ... 9
0s
0 ... 2000 s
R223
R224
Select contact
switch-off point
Select contact
switch-on point
0 ... 2000 s
R233
20 (0.5) mg/l; 0 ... 20 (5) mg/l
20 ppm; 0 … 20 ppm
20000 ppb; 0 … 20000 ppb
20 (0.5) mg/l; 0 ... 20 (5) mg/l
20 ppm; 0 … 20 ppm
20000 ppb; 0 … 20000 ppb
R212
R213
Set pick-up
delay
0s
0 ... 2000 s
R214
A0002639-EN
126
Endress+Hauser
Liquisys M CCM223/253
Appendix
Enable error current for
error just selected
Automatic start
of clean function
no; yes
no; yes
Select “next error”
or return to menu
next = next error
<---R
F7
F8
Set max. perm. period
for lower alarm threshold
Set max. perm. period
for upper alarm threshold
60 min
0 ... 2000 min
0 ... 2000 min
120 min
60 min
0 ... 2000 min
Set max. perm. period
for lower limit exceeding
0 ... 2000 min
120 min
0.3 s
0.1 ... 5.0 s
Motor run time
10 ... 999 s
60 s
R285
Enter cleaning
time
10 s
0 ... 999 s
pH 7.20
pH 4 ... 9
P128
Set limit value
0.5 (0.1) mg/l; 0 ... 20 (5) mg/l
0.5 ppm; 0 … 20 ppm
500 ppb; 0 … 20000 ppb
P117
P116
Enter min. switch-on
time tON
Set limit
value
P127
P126
Set max. perm. period
for lower limit exceeding
F9
P118
10%
0 ... 40%
R286
Enter post-rinse time
0 ... 999 s
20 s
R274
3-p. step controller: assigns 2 contacts, only permitted for contacts 3+4
Neutral zone
R287
Define period between
two cleaning cycles
(pause time)
360 min 1 ... 7200 min
Define repeat
cycles
0
0 ... 5
R275
R276
R277
Define minimum
pause time
120 min 1 ... R277 min
Number of cleaning
cycles without
cleaning agent
0 0 ... 9
R278
R279
Chemoclean: assigns 2 contacts,
only permitted for contacts 3 (+4)
Enter deriv. action time
Tv (0.0 = no D comp.)
Select control
characteristic
0.0 min 0.0 ... 999.9 min
dir; inv
R255
R256
Enter deriv. action time
Tv (0.0 = no D comp.)
Select control
characteristic
0.0 min 0.0 ... 999.9 min
inv; dir
R245
Set drop-out
delay
0s
0 ... 2000 s
Set drop-out
delay
50 °C
0 ... 2000 s
0 ... 2000 s
R225
MAX; MIN
R226
0 ... 2000 s
R215
20 (5) mg/l; 0 ... 20 (5) mg/l
20 ppm; 0 … 20 ppm
20000 ppb; 0 … 20000 ppb
R216
Enter
pulse period
10.0 s
0.5 ... 999.9 s
R248
R259
Enter max.
pulse frequency
120 1/min
60 ... 180 1/min
R249
0.1 ... 5.0 s
0%
R2510
Enter min. switch-on
time tON
0.3 s
0.1 ... 5.0 s
R2410
0 ... 40%
R2511
Enter basic load
0%
0 ... 40%
R2411
R227
Display of LC status
MAX; MIN
R226
Set alarm threshold
Set drop-out
delay
R258
0.3 s
Enter basic load
R237
1500 mV 0 ... 1500 mV
pH 0 ... 9
0.5 ... 999.9 s
Enter min. switch-on
time tON
MAX; MIN
Display of LC status
pH 9.00
10.0 s
Enter max.
pulse frequency
120 1/min
60 ... 180 1/min
Display of LC status
Set alarm threshold
Set alarm threshold
Set drop-out
delay
0s
0 ... 50 °C
R247
R236
R225
0s
Select
len = pulse length
freq = pulse frequency
curr = current output 2
Set alarm threshold
Enter
pulse period
R257
R246
R235
0s
Select
len = pulse length
freq = pulse frequency
curr = current output 2
R227
Display of LC status
MAX; MIN
R217
A0002640-EN
Endress+Hauser
127
Appendix
Liquisys M CCM223/253
Configure Hold
Select language
S+C = for param. + cal.
Setup = for param.
ENG; GER; FRA;
ITA; NEL; ESP
SERVICE
S
S1
Rel (= relay)
Module software
Hardware version
SW Version
HW Version
Main (= mainboard)
E141
Hardware version
SW Version
HW Version
E131
E1(3)
Trans (= transmitter)
Hardware version
SW Version
HW Version
E121
E1(2)
Contr (= controller)
E
E1(1)
Enter address
I
HW Version
E112
0 ... 999 s
0
S4
0 ... 9999
S5
E144
Module identification
is displayed
Serial number
is displayed
E133
E134
Module identification
is displayed
Serial number
is displayed
E123
E124
Module identification
is displayed
Serial number
is displayed
E113
E114
Tag description
HART: 0 ... 15 or
PROFIBUS: 1 ... 126
INTERFACE
Hardware version
SW Version
Enter SW upgrade
release code (Plus pack.)
Module identification
is displayed
E143
E122
Instrument software
E111
Serial number
is displayed
E132
Module software
10 s
S3
E142
Module software
Enter Hold
dwell time
Off; On
S2
E1(4)
E+H SERVICE
Manual Hold
CAL = for Cal.
no = no Hold
I1
@@@@@@@@
I2
A0002641-EN
128
Endress+Hauser
Liquisys M CCM223/253
Control SW upgrade
release code Chemocl.
0
Appendix
Order number
is displayed
Serial number
is displayed
Reset instrument
0 ... 9999
Start instrument test
no; sens; factory
S6
S7
S8
no; display
S9
S10
A0002642-EN
Endress+Hauser
129
Index
Liquisys M CCM223/253
Index
A
Access codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Alarm contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Automatic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
C
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Central module replacement . . . . . . . . . . . . . . . . . . 107
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Cleaning
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Connecting cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Current outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
D
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Device configuration . . . . . . . . . . . . . . . . . . . . . . . . . 42
Device-specific errors . . . . . . . . . . . . . . . . . . . . . . . . . 93
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Disassembling
Field device . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Panel-mounted device . . . . . . . . . . . . . . . . . . . . 101
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
E
E+H Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . 19
Version 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Version 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
F
Feedforward control . . . . . . . . . . . . . . . . . . . . . . . . . 48
H
Hold function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
I
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . 16
Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
J
Junction boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
130
K
Key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
L
Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Maintenance of the entire measuring point . . . . . . . . 95
Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mechanical construction . . . . . . . . . . . . . . . . . . . . . 118
Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
N
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
O
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
P
P(ID) controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Performance characteristics . . . . . . . . . . . . . . . . . . . 117
Post mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . 29
Post-installation check . . . . . . . . . . . . . . . . . . . . . . . 18
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Process-specific errors . . . . . . . . . . . . . . . . . . . . . . . . 89
Product identification . . . . . . . . . . . . . . . . . . . . . . . . . 9
Q
Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
R
Relay configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Replacing the central module . . . . . . . . . . . . . . . . . . 107
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
S
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SCS monitoring functions . . . . . . . . . . . . . . . . . . . . . . 57
Sensor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Setup 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Setup 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Switching on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System error messages . . . . . . . . . . . . . . . . . . . . . . . 85
Endress+Hauser
Liquisys M CCM223/253
Index
T
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Test
Chlorine sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Flow monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . 99
pH/ORP measurement . . . . . . . . . . . . . . . . . . . . . 99
Temperature measurement . . . . . . . . . . . . . . . . . 99
Test and simulation . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Three-point step controller . . . . . . . . . . . . . . . . . 28, 67
Trouble shooting instructions . . . . . . . . . . . . . . . . . . 85
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
U
Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
W
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Endress+Hauser
131
*71300499*
71300499
www.addresses.endress.com