Endress + Hauser Operating Instructions Liquisys M CCM223/253 Transmitter for free chlorine, chlorine dioxide and total chlorine
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
BA00214C/07/EN/15.15 71300499 Products Solutions Services Operating Instructions Liquisys M CCM223/253 Transmitter for free chlorine, chlorine dioxide and total chlorine Liquisys M CCM223/253 Table of contents Table of contents 1 Document information . . . . . . . . . . . . . . 5 1.1 1.2 1.3 1.4 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . Symbols on the device . . . . . . . . . . . . . . . . . . . Electrical symbols . . . . . . . . . . . . . . . . . . . . . . 2 Basic safety instructions . . . . . . . . . . . . 7 2.1 2.2 2.3 2.4 2.5 Requirements for personnel . . . . . . . . . . . . . . . Designated use . . . . . . . . . . . . . . . . . . . . . . . . Occupational safety . . . . . . . . . . . . . . . . . . . . . Operational safety . . . . . . . . . . . . . . . . . . . . . . Product safety . . . . . . . . . . . . . . . . . . . . . . . . . 2.5.1 State of the art . . . . . . . . . . . . . . . . . . 2.5.2 IT security . . . . . . . . . . . . . . . . . . . . . . 3 Incoming acceptance and product identification . . . . . . . . . . . . . . . . . . . . . . . 9 3.1 3.2 3.3 Incoming acceptance . . . . . . . . . . . . . . . . . . . . Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . Product identification . . . . . . . . . . . . . . . . . . . 3.3.1 Nameplate . . . . . . . . . . . . . . . . . . . . 3.3.2 Product identification . . . . . . . . . . . . Certificates and approvals . . . . . . . . . . . . . . . 3.4.1  mark . . . . . . . . . . . . . . . . . . . . . . 3.4.2 CSA General Purpose . . . . . . . . . . . . . 3.4 5 5 5 6 7 7 7 8 8 8 8 9 9 10 10 10 10 10 10 4 Installation . . . . . . . . . . . . . . . . . . . . . . . 11 4.1 4.4 Installation at a glance . . . . . . . . . . . . . . . . . . 4.1.1 Measuring system . . . . . . . . . . . . . . . Installation conditions . . . . . . . . . . . . . . . . . . 4.2.1 Field device . . . . . . . . . . . . . . . . . . . . 4.2.2 Panel-mounted device . . . . . . . . . . . . Installation instructions . . . . . . . . . . . . . . . . . 4.3.1 Field device . . . . . . . . . . . . . . . . . . . . 4.3.2 Panel-mounted device . . . . . . . . . . . . Post-installation check . . . . . . . . . . . . . . . . . . 5 Electrical connection . . . . . . . . . . . . . . 19 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical connection, version 1 . . . . . . . . . . . Electrical connection, version 2 . . . . . . . . . . . Device connection . . . . . . . . . . . . . . . . . . . . . Measuring cables and sensor connection . . . . Three-point step controller for Cl2 / ClO2 / total chlorine . . . . . . . . . . . . . . . . . . . . . . . . . Alarm contact . . . . . . . . . . . . . . . . . . . . . . . . Post-connection check . . . . . . . . . . . . . . . . . . 6 Operation options . . . . . . . . . . . . . . . . . 30 6.1 Quick operation guide . . . . . . . . . . . . . . . . . . 4.2 4.3 Endress+Hauser 11 12 14 14 15 16 16 18 18 19 19 21 22 24 28 29 29 30 6.2 6.3 Display and operating elements . . . . . . . . . . . 6.2.1 Display . . . . . . . . . . . . . . . . . . . . . . . 6.2.2 Operating elements . . . . . . . . . . . . . . 6.2.3 Key functions . . . . . . . . . . . . . . . . . . Local operation . . . . . . . . . . . . . . . . . . . . . . . 6.3.1 Automatic/manual mode . . . . . . . . . . 6.3.2 Operating concept . . . . . . . . . . . . . . . 30 30 32 32 35 35 36 7 Commissioning . . . . . . . . . . . . . . . . . . . . 38 7.1 7.2 7.3 7.4 7.5 Function check . . . . . . . . . . . . . . . . . . . . . . . Switching on . . . . . . . . . . . . . . . . . . . . . . . . . Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . Device configuration . . . . . . . . . . . . . . . . . . . 7.4.1 Setup 1 (chlorine/chlorine dioxide) . . 7.4.2 Setup 2 (temperature or pH/ORP) . . . 7.4.3 Current input . . . . . . . . . . . . . . . . . . 7.4.4 Current outputs . . . . . . . . . . . . . . . . . 7.4.5 Alarm . . . . . . . . . . . . . . . . . . . . . . . . 7.4.6 Check . . . . . . . . . . . . . . . . . . . . . . . . 7.4.7 Relay configuration . . . . . . . . . . . . . . 7.4.8 Service . . . . . . . . . . . . . . . . . . . . . . . 7.4.9 E+H Service . . . . . . . . . . . . . . . . . . . . 7.4.10 Interfaces . . . . . . . . . . . . . . . . . . . . . 7.4.11 Communication . . . . . . . . . . . . . . . . . Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Diagnostics and troubleshooting . . . 85 8.1 8.2 8.3 8.4 Trouble shooting instructions . . . . . . . . . . . . . System error messages . . . . . . . . . . . . . . . . . . Process-specific errors . . . . . . . . . . . . . . . . . . Device-specific errors . . . . . . . . . . . . . . . . . . . 9 Maintenance . . . . . . . . . . . . . . . . . . . . . . 95 9.1 Maintenance of the entire measuring point . . 9.1.1 Cleaning the transmitter . . . . . . . . . . 9.1.2 Cleaning the pH/mV sensors (EP version) . . . . . . . . . . . . . . . . . . . 9.1.3 Maintenance of chlorine sensors . . . . 9.1.4 Assembly . . . . . . . . . . . . . . . . . . . . . 9.1.5 Maintenance of pH connecting cables and junction boxes (EP version) . . . . . . . . . . . . . . . . . . . . . . Test and simulation . . . . . . . . . . . . . . . . . . . . 9.2.1 Chlorine sensors . . . . . . . . . . . . . . . . 9.2.2 Temperature measurement . . . . . . . . 9.2.3 pH/ORP measurement . . . . . . . . . . . . 9.2.4 Flow monitoring . . . . . . . . . . . . . . . . 9.2 10 38 38 40 42 42 44 47 51 55 56 60 77 79 80 80 81 85 85 89 93 95 95 96 97 97 98 98 98 99 99 99 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 10.1 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . 10.2 Disassembling the panel-mounted device . . . 10.3 Disassembling the field device . . . . . . . . . . . 10.4 Replacing the central module . . . . . . . . . . . . 101 101 104 107 3 Table of contents Liquisys M CCM223/253 10.5 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 10.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 11 Accessories . . . . . . . . . . . . . . . . . . . . . . 109 11.1 11.2 11.3 11.4 11.5 11.6 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connection accessories . . . . . . . . . . . . . . . . . Installation accessories . . . . . . . . . . . . . . . . Software and hardware add-ons . . . . . . . . . . Metering system . . . . . . . . . . . . . . . . . . . . . Calibration accessories . . . . . . . . . . . . . . . . . 12 Technical data . . . . . . . . . . . . . . . . . . . 113 12.1 12.2 12.3 12.4 12.5 12.6 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power supply . . . . . . . . . . . . . . . . . . . . . . . . Performance characteristics . . . . . . . . . . . . . Environment . . . . . . . . . . . . . . . . . . . . . . . . Mechanical construction . . . . . . . . . . . . . . . 13 Appendix . . . . . . . . . . . . . . . . . . . . . . . . 119 109 109 110 111 111 112 113 113 116 117 117 118 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 4 Endress+Hauser Liquisys M CCM223/253 Document information 1 Document information 1.1 Warnings Structure of information LDANGER Causes (/consequences) Consequences of non-compliance (if applicable) ‣ Corrective action LWARNING Causes (/consequences) Consequences of non-compliance (if applicable) ‣ Corrective action LCAUTION Causes (/consequences) Consequences of non-compliance (if applicable) ‣ Corrective action NOTICE Cause/situation Consequences of non-compliance (if applicable) ‣ Action/note 1.2 Meaning This symbol alerts you to a dangerous situation. Failure to avoid the dangerous situation will result in a fatal or serious injury. This symbol alerts you to a dangerous situation. Failure to avoid the dangerous situation can result in a fatal or serious injury. This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or more serious injuries. This symbol alerts you to situations which may result in damage to property. Symbols used Additional information, tips Permitted or recommended Forbidden or not recommended 1.3 Symbol Symbols on the device Meaning Reference to device documentation Endress+Hauser 5 Document information Liquisys M CCM223/253 1.4 Electrical symbols Symbol Meaning A0027423 A0027424 A0027425 A0027426 Direct current A terminal at which DC is present or through which DC flows. Alternating current A terminal to which alternating voltage (sine-wave) is applied or through which alternating current flows. Direct current or alternating current A terminal at which direct voltage or alternating voltage is present or through which direct current or alternating current flows. Ground connection A terminal which, from the user's point of view, is already grounded via a grounding system. Protective ground connection A terminal which must be connected to ground prior to establishing any other connections. A0027427 Class II equipment Reinforced or double insulation A0019929 Alarm relay A0027420 Input A0027428 Output A0027429 DC voltage source A0027430 Temperature sensor A0027431 6 Endress+Hauser Liquisys M CCM223/253 Basic safety instructions 2 Basic safety instructions 2.1 Requirements for personnel • Installation, commissioning, operation and maintenance of the measuring system may be carried out only by specially trained technical personnel. • The technical personnel must be authorized by the plant operator to carry out the specified activities. • The electrical connection may be performed only by an electrical technician. • The technical personnel must have read and understood these Operating Instructions and must follow the instructions contained therein. • Measuring point faults may be repaired only by authorized and specially trained personnel. Repairs not described in the Operating Instructions provided may only be carried out directly by the manufacturer or by the service organization. 2.2 Designated use Liquisys M CCM223/253 is a transmitter for determining the amount of free chlorine, chlorine dioxide or total chlorine dissolved in water. The transmitter is particularly suited for use in the following areas: • Drinking water • Water treatment • Cooling water • Gas scrubbers • Reverse osmosis • Food processing • Swimming pool and bathing pool water Use of the device for any purpose other than that described, poses a threat to the safety of people and of the entire measuring system and is therefore not permitted. The manufacturer is not liable for damage caused by improper or non-designated use. 2.3 Occupational safety As the user, you are responsible for complying with the following safety conditions: • Installation guidelines • Local standards and regulations Electromagnetic compatibility • The product has been tested for electromagnetic compatibility in accordance with the applicable European standards for industrial applications. • The electromagnetic compatibility indicated applies only to a product that has been connected in accordance with these Operating Instructions. Endress+Hauser 7 Basic safety instructions Liquisys M CCM223/253 2.4 Operational safety 1. Before commissioning the entire measuring point, verify that all connections are correct. Ensure that electrical cables and hose connections are undamaged. 2. Do not operate damaged products, and safeguard them to ensure that they are not operated inadvertently. Label the damaged product as defective. 3. If faults cannot be rectified: Take the products out of operation and safeguard them to ensure that they are not operated inadvertently. 2.5 Product safety 2.5.1 State of the art The product is designed to meet state-of-the-art safety requirements, has been tested, and left the factory in a condition in which it is safe to operate. The relevant regulations and European standards have been observed. 2.5.2 IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions. The device is equipped with security mechanisms to protect it against any inadvertent changes to the device settings. IT security measures in line with operators' security standards and designed to provide additional protection for the device and device data transfer must be implemented by the operators themselves. 8 Endress+Hauser Liquisys M CCM223/253 Incoming acceptance and product identification 3 Incoming acceptance and product identification 3.1 Incoming acceptance 1. Verify that the packaging is undamaged.  Notify your supplier of any damage to the packaging. Keep the damaged packaging until the matter has been settled. 2. Verify that the contents are undamaged.  Notify your supplier of any damage to the delivery contents. Keep the damaged products until the matter has been settled. 3. Check the delivery for completeness.  Check it against the delivery papers and your order. 4. Pack the product for storage and transportation in such a way that it is protected against impact and moisture.  The original packaging offers the best protection. The permitted ambient conditions must be observed (see "Technical data"). If you have any questions, please contact your supplier or your local sales center. 3.2 Scope of delivery The delivery of the field device comprises: • 1 transmitter • 1 plug-in screw terminal, 3-pin • 1 cable gland Pg 7 • 1 cable gland Pg 16 reduced • 2 cable glands Pg 13.5 • 1 set of Operating Instructions • For versions with HART communication: 1 set of Operating Instructions: Field communication with HART • For versions with PROFIBUS interface: 1 set of Operating Instructions: Field communication with PROFIBUS PA/DP The delivery of the panel-mounted device comprises: • 1 transmitter • 1 set of plug-in screw terminals • 2 tensioning screws • Also for EP version: 1 BNC connector (solder-free) • 1 set of Operating Instructions • For versions with HART communication: 1 set of Operating Instructions: Field communication with HART • For versions with PROFIBUS interface: 1 set of Operating Instructions: Field communication with PROFIBUS PA/DP Endress+Hauser 9 Incoming acceptance and product identification 3.3 Product identification 3.3.1 Nameplate Liquisys M CCM223/253 The nameplate provides you with the following information on your device: • Manufacturer identification • Order code • Extended order code • Serial number • Ambient and process conditions • Input and output values • Safety information and warnings Compare the data on the nameplate with your order. 3.3.2 Product identification The order code and serial number of your product can be found in the following locations: • On the nameplate • In the delivery papers Obtaining information on the product 1. Go to the product page for your product on the Internet. 2. In the navigation area on the right-hand side, select "Check your device features" under "Device support".  An additional window opens. 3. Enter the order code from the nameplate into the search field.  You will receive information on each feature (selected option) of the order code. 3.4 Certificates and approvals 3.4.1  mark The product meets the requirements of the harmonized European standards. As such, it complies with the legal specifications of the EC directives. The manufacturer confirms successful testing of the product by affixing to it the  mark. 3.4.2 CSA General Purpose The following device versions meet the requirements of CSA and ANSI/UL for Canada and the US: • CCM253-**2/3/7*** • CCM223-**2/3/7*** 10 Endress+Hauser Liquisys M CCM223/253 Installation 4 Installation 4.1 Installation at a glance Proceed as follows to completely install the measuring point: • Install the transmitter (see the "Installation instructions" section). • If the sensor is not yet installed in the measuring point, install it (see Technical Information of the sensor). • Connect the sensor to the transmitter as illustrated in the "Electrical connection" section. • Connect the transmitter as illustrated in the "Electrical connection" section. • Commission the transmitter as explained in the "Commissioning" section. Endress+Hauser 11 Installation Liquisys M CCM223/253 4.1.1 Measuring system Version 1: free chlorine and chlorine dioxide A complete measuring system comprises: • Transmitter Liquisys M CCM223 or CCM253 • A membrane covered sensor CCS140/141 for Cl2 or CCS240/241 for ClO2 an open sensor 963 for Cl2 • Flow assembly CCA250 (not required for sensor 963) Optionally: • pH or ORP electrode • Proximity switch INS for flow monitoring (not with sensor 963) • Extension cable CMK for chlorine measurement • Extension cable CYK71 for pH/ORP measurement • An extension cable MK for proximity switch INS • Junction box VBC 8 9 4 5 6 7 3 2 1 A0024088 1 1 2 3 4 5 6 7 8 9 Measuring system for the measurement of free chlorine or chlorine dioxide in flow operation (example) Flow assembly CCA250 Medium inflow Proximity switch INS Mounting location for pH/ORP sensors Chlorine sensor Medium outlet Sampling tap Measuring cable Transmitter CCM253 Version 2: total chlorine A complete measuring system comprises: • Transmitter Liquisys M CCM223 or CCM253 • Total chlorine sensor CCS120 • Flow assembly CCA250 or immersion assembly CYA611 • Measuring cable CPK9 with internal PML 12 Endress+Hauser Liquisys M CCM223/253 Installation Optionally: • pH or ORP electrode • Proximity switch INS for flow monitoring (only with flow assembly) • Extension cable CPK9 with internal PML for chlorine measurement • Extension cable CYK71 for pH/ORP measurement • An extension cable MK for proximity switch INS • Junction box VBC • Weather protection cover CYY101 for field housing 1 2 4 3 6 5 A0024089 2 1 2 3 4 5 6 Endress+Hauser Measuring system for the measurement of total chlorine in immersion operation (example) Junction box Transmitter CCM253 Measuring cable Immersion assembly CYA611 Chlorine sensor CCS120 Assembly adapter G1 13 Installation Liquisys M CCM223/253 4.2 Installation conditions 4.2.1 Field device Pg 13.5 Pg 7 Pg 16 247 (9.72) Ø 6 (0.24) 70 (2.76) 157 (6.18) M5 11 (0.43) 115 (4.53) 70 (2.76) 154 (6.06) 170 (6.69) A0024637 3 Field device, dimensions in mm (inch) There is a hole in the perforation for the cable entry (connection of supply voltage). It serves as a pressure balance during air shipment. Make sure no moisture penetrates the inside of the housing before the cable installation. The housing is completely airtight after cable installation. 14 Endress+Hauser Liquisys M CCM223/253 Installation 1 4 3 2 A0024640 4 1 2 3 4 View into the field housing Removable electronics box Terminals Partition plate Fuse 4.2.2 Panel-mounted device 96 (3.78) 6 (0.24) 149.5 (5.89) 139 (5.47) 92 (3.62) 90 (3.54) A0024641 5 Endress+Hauser Panel-mounted device, dimensions in mm (inch) 15 Installation Liquisys M CCM223/253 4.3 Installation instructions 4.3.1 Field device There are several ways of securing the field housing: • Wall mounting with fixing screws • Post mounting to cylindrical pipes • Post mounting to a square securing mast NOTICE Effect of climatic conditions (rain, snow, direct sunlight etc.) Impaired operation to complete transmitter failure ‣ When installing outside, always use the weather protection cover (accessory). Transmitter wall mounting 2 Ø 6 (0.24) 1 154 (6.06) A0024638 6 1 2 Field device wall mounting Fixing bore holes Plastic caps Proceed as follows to mount the transmitter on the wall: • Create the bore holes as shown in →  6. • Drive two fixing screws through the fixing bore holes (1) from the front. • Mount the transmitter on the wall as shown. • Cover the bores with plastic caps (2). Transmitter post mounting You require a post mounting kit to secure the field device to horizontal and vertical posts or pipes (max. Ø 60 mm (2.36")). This can be acquired as an accessory (see the "Accessories" section). 16 Endress+Hauser Liquisys M CCM223/253 Installation 1 1 2 Ø max. 60 (2.36) 3 1 3 A0024635 7 1 2 3 Field device on horizontal or vertical pipes Securing screws Fixing screws Securing plate Proceed as follows to mount the transmitter on a post: 1. Guide the two securing screws (1) of the mounting kit through the openings on the securing plate (3). 2. Screw the securing plate onto the transmitter using the four fixing screws (2). 3. Secure the bracket with the field device on the post or pipe using the clip. You can also secure the field device to the Flexdip CYH112 bracket in conjunction with the weather protection cover. These can be acquired as accessories, see the "Accessories" section. A0027433 8 Endress+Hauser Field device on Flexdip CYH112 bracket with weather protection cover 17 Installation Liquisys M CCM223/253 4.3.2 Panel-mounted device The panel-mounted device is secured with the tensioning screws supplied →  9 The necessary installation depth is approx. 165 mm (6.50"). +0.5 (3.62 +0.02 ) 92+0.5 (3.62+0.02) 92 1 max. 45 (1.77) 139 (5.47) ~ 25 (0.98) 3 96 (3.78) 92 (3.62) 3 33 (1.30) 90 (3.54) 57 (2.24) 2 3 6 (0.24) ~ 165 (6.50)* A0024639 9 1 2 3 * Dimensions in mm (inch) Mounting plate Seal Tensioning screws Necessary installation depth 4.4 Post-installation check • After installation, check the transmitter for damage. • Check whether the transmitter is protected against moisture and direct sunlight (e.g. by the weather protection cover). 18 Endress+Hauser Liquisys M CCM223/253 Electrical connection 5 Electrical connection LWARNING Device is live Incorrect connection may result in injury or death. ‣ The electrical connection may be performed only by an electrical technician. ‣ The electrical technician must have read and understood these Operating Instructions and must follow the instructions contained therein. Prior to commencing connection work, ensure that no voltage is present on any cable. ‣ 5.1 Wiring LWARNING Risk of electric shock! ‣ At the supply point, the power supply must be isolated from dangerous live cables by double or reinforced insulation in the case of devices with a 24 V power supply. NOTICE The device does not have a power switch ‣ The customer must provide a protected circuit breaker in the vicinity of the device. ‣ The circuit breaker must be a switch or power switch, and you must label it as the circuit breaker for the device. The electrical connection of the transmitter depends on the sensor: • If you are using the membrane-covered sensor CCS140 / 141 / 240 / 241 or the open sensor 963, follow the instructions and illustrations in the "Electrical connection, version 1" section. • If you are using the total chlorine sensor CCS120, follow the instructions and illustrations in the "Electrical connection, version 2" section. 5.2 Electrical connection, version 1 The wiring diagram shows the connections of a device equipped with all the options. The connection of the sensors to the various measuring cables is explained in more detail in the "Measuring cables and sensor connection" section. Endress+Hauser 19 Electrical connection Liquisys M CCM223/253 pH/ Redox A pH Ref. Red. PA/ PM S B GN 11 NTC BN 12 K 90 K RD A 41 A 91 Cl2 42 ClO2 43 J BU A 47 48 RD 92 K K C 49 31 Cl2 ClO2 D 32 33 57 58 mA L 59 51 52 mA M E * F G BK 10–50 V 53 81 82 54 55 56 93 23 H 85 I N 24 94 BN BU 34 O mA ~ = L1L+ 15 V N L– P 86 A0001903  10 Electrical connection of the transmitter (version 1) A pH/ORP input (optional) I Auxiliary voltage output B Sensor CCS140/141/240/241 J Alarm (current-free contact position) C Sensor 963 (alternative) K Relay 1 (current-free contact position) D Signal output 1, chlorine / chlorine dioxide L Relay 2 (current-free contact position) E Signal output 2, temperature, pH or ORP M Relay 3 (current-free contact position) F Binary input 1 (hold/cleaning) N Relay 4 (current-free contact position) G Proximity switch INS O Current input 4 to 20 mA H Binary input 2 P Power connection * Auxiliary voltage of terminal 85/86 can be used The device is approved for protection class II and is generally operated without a protective ground connection. Circuits "E" and "I" are not galvanically isolated from each other. 20 Endress+Hauser Liquisys M CCM223/253 Electrical connection 5.3 Electrical connection, version 2 The wiring diagram shows the connections of a device equipped with all the options. The connection of the sensors to the various measuring cables is explained in more detail in the "Measuring cables and sensor connection" section. pH/ Redox A pH Ref. Red. PA/ PM S B YE 11 WH BK 12 CCS 120 90 Cl2 41 42 ClO2 85 GN C 43 47 48 15 V 86 D 32 33 57 58 mA Cl2 ClO2 F G BK 10–50 V mA 34 53 81 82 54 55 56 93 23 H BN BU 24 94 85 C L 59 51 52 E * K 49 BN 31 J M N O mA 15 V ~ = L1L+ N L– 86 P A0001904  11 Endress+Hauser Electrical connection of the transmitter (version 2) A pH/ORP input (optional) * Auxiliary voltage of terminal 85/86 can be used B Sensor CCS120 J Alarm (current-free contact position) C Auxiliary voltage output K Relay 1 (current-free contact position) D Signal output 1, total chlorine L Relay 2 (current-free contact position) E Signal output 2, temperature, pH or ORP M Relay 3 (current-free contact position) F Binary input 1 (hold/cleaning) N Relay 4 (current-free contact position) 21 Electrical connection Liquisys M CCM223/253 G Proximity switch INS O Current input 4 to 20 mA H Binary input 2 P Power connection The device is approved for protection class II and is generally operated without a protective ground connection. Circuits "E" and "C" are not galvanically isolated from each other. 5.4 Device connection Field device connection Proceed as follows to connect the field device: 1. Open the housing cover to access the terminal block in the connection compartment. 2. Break through the perforation for a cable gland, mount a Pg gland and guide the cable through this Pg gland. 3. Connect the cable in accordance with the terminal assignment. 4. Tighten the Pg gland again. NOTICE Non-observance could cause incorrect measurement. ‣ Make absolutely sure to protect the cable ends and terminals from moisture. ‣ Terminals marked NC may not be connected. ‣ Unmarked terminals may not be connected. REL 4 pH / Redox SENSOR REL 2 REL 1 Contacts: max. 2A AC: 250V/500VA DC: 30V/60W 54 55 56 51 52 53 57 58 59 47 48 49 41 42 43 Mains Hilfsenergie REF 90 12 PA/PM BN BN REL 3 NC NC 31 32 33 34 NC 85 86 93 94 81 82 23 24 NC + - + + - + - + - + 4..20mA Digital 1 Digital 2 (INS) 11 +15V 10mA 91/A Temp. pH/Redox (opt.) 12 (963:92/K) 90/K Cl 2 ClO 2 91 11 92 S (BU) GN (RD) L1 N (AC) + - (DC) CCM 253 131194-4D A0002276  12 Field device connection compartment sticker Please label the sensor terminal block with the sticker provided. Panel-mounted device connection To connect the panel-mounted device, connect the cables in accordance with the terminal assignment to the terminals on the rear of the device. 22 Endress+Hauser Liquisys M CCM223/253 Electrical connection Sensor BNC: pH/Redox + REF 47 31 + COM 48 32 - REL1 59 33 + 57 34 - COM 58 REL2 Cl2 ClO2 Temp. pH Redox (opt.) (REF) 92 K 963 RD 12 BN GN NC 11 53 85 + 91 A 51 86 - COM 52 93 + REL3 REL4 56 94 - 54 81 + 82 - 24 NC + 23 NC 4..20mA Digital 2 (INS) 963 BU CCS.. 90 K S 42 43 Digital 1 COM 55 - +15V 10mA BN PA/PM Contacts: max. 2A, AC:250V/500VA, DC:30V/60W 49 131192-4C 41 AC DC L1 + N - Mains 131084-4C A0002277  13 Panel-mounted device connection sticker NOTICE Non-observance could cause incorrect measurement. ‣ Make absolutely sure to protect the cable ends and terminals from moisture. ‣ Terminals marked NC may not be connected. ‣ Unmarked terminals may not be connected. Please label the sensor terminal block with the sticker provided. Endress+Hauser 23 Electrical connection Liquisys M CCM223/253 5.5 Measuring cables and sensor connection Sensor type Cable Extension Chlorine/chlorine dioxide sensors CCS140 / 141 / 240 / 241 3 m (9.8 ft) CMK, permanently connected VBC box + CMK Chlorine sensor 963 - Temperature sensor for chlorine sensor 963 CPK1 Total chlorine sensor CCS120 CPK9-N*A1B VBC box + CYK71 pH or ORP sensor without temperature sensor CPK1 for sensors with GSA plug-in head CPK9 for sensors with ESA plug-in head VBC box + CYK71 VBC box + MK Connecting the chlorine sensors CCS140 / 141 / 240 /241 The sensors are equipped with a 3 m (9.8 ft) fixed cable. Connect the sensors to the transmitter according to the following diagram: Sensor with 3 m fixed cable Transmitter Assignment Core Outer shield Terminal S Anode [A] red 91 Cathode [K] 90 NTC temperature sensor green 11 NTC temperature sensor brown 12 Connecting the total chlorine sensor CCS120 Connect the sensor with the measuring cable CPK9-N*A1B (with internal PML) according to the following connection diagram: Cable with TOP68 connection Transmitter Pin Assignment Core Terminal 1 TC signal Coax, inside (white) 90 2 AGND Coax, outside (black) 12 4 +UB (15 V) green 85 5 NTC1 yellow* 11 NTC1 white* 11 6 NTC2/AGND brown 86 S Shielding S S 3 * The white and yellow wires are interconnected in the TOP68 connector. 24 Endress+Hauser Liquisys M CCM223/253 Electrical connection 5 4 4 5 6 3 2 1 3 6 1 2 A0026048  14 TOP68 connection; pin arrangement of connector and coupling (shown from contact side) Connecting the chlorine sensor 963 The chlorine sensor 963 is supplied without a temperature sensor ex factory. Connect the chlorine sensor to the transmitter as follows: • Without temperature measurement: Connect the 10 kΩ equivalent resistor supplied to terminals 11 and 12. The measured value display will then constantly show 25 °C (77 °F). • With temperature measurement: Mount an NTC temperature sensor 10 kΩ / 25 °C (77 °F) (120 mm installation version TSP 3692) in the chlorine sensor 963. Use the CPK1 connecting able to connect the temperature sensor to terminals 11 and 12. • Chlorine sensor: Connect the red cable to terminal 92 (cathode) and the blue cable to terminal 91 (anode). Connection of pH or ORP sensors Connect the pH or ORP sensor always symmetrically to prevent a mutual interference of several sensors mounted in the CCA250 assembly. Symmetrical connection requires a potential matching pin. The pin is integrated as standard in the CCA250 flow assembly and is connected by a PML to the PA/PM terminal. CPK1 PM pH / Redox Coax Ref. pH or Redox BN PM PM CPK9 pH + Pt 100 / Pt 1000 Coax BK Ref. inner pH GN Temp. WH Temp. YE Temp. BN PM A0002330-EN  15 Endress+Hauser Connection of the pH or ORP sensor to the field instrument with the cables CPK1 or CPK9 25 Electrical connection Liquisys M CCM223/253 If you are using glass electrodes with the panel-mounted device, you have to terminate the measuring cable with a BNC connector. A solder-free BNC connector is supplied with the device. To do this, proceed as follows: 1. Cut off end ferrules 2 and 3 of the coaxial cable. 2 3 1 4 A0005744  16 1 2 3 4 2. Push the cable gland 5 and the washer 6 onto the coaxial cable. 3. Remove the insulation (13 mm (0.51")) and screw the clamping ring 7 onto the insulation. Coax cable Inner shield BK (ref) Inner coax (pH / mV) Strand BN (PA) Parts 5 to 7 are supplied with the BNC connector for cable diameters 3.2 mm and 5 mm. 4. Fold the braided shield 8 of the shield over the clamping ring and cut off the excess material. 5. There is a semiconductor layer 14 (conductive membrane) between the inner insulation and the braided shield 8. Strip this semiconductor layer as far as the braided shield. Cable CPK1: device connection 5 6 5 6 7 13 (0.51) 16 (0.63) 14 8 A0005745  17 6. Terminating the pH connecting cable for mounting the BNC elbow plug. Dimensions in mm (inch) Remove the inner insulation (4 mm (0.16")), fit end ferrule 13 on the stripped inner conductor and secure the end ferrule with a crimping pliers. 13 4 (0.16) A0005746  18 7. Push the BNC connector housing 9 over the cable. The inner conductor must be located on the clamping surface 10 of the connector. 8. Tighten the cable gland 5. 9. Insert the clamp element 11 and screw in the connector cover 12. This creates a safe connection between the inner conductor and the connector pin. Terminating the pH connecting cable for mounting the BNC elbow plug. Dimensions in mm (inch) 9 5 10 11 12 A0005747  19 26 Mounting the pH connecting cable in the BNC elbow plug Endress+Hauser Liquisys M CCM223/253 Electrical connection Sensor Maximum cable length Chlorine/chlorine dioxide sensors CCS140/141/240/ 241 Max. 30 m (98.4 ft) with cable CMK Chlorine sensor 963 Max. 30 m (98.4 ft) with cable MK Total chlorine sensor CCS120 Max. 15 m (49.2 ft) with cable CYK71 pH/ORP measurement Max. 50 m (164 ft) with cable CYK71 Use the junction box VBC and the appropriate extension cable to extend the measuring cable. 5 x Pg 7 52 (2.05) B A B 2 x Pg 7 2 x Pg 11 113 (4.45) 125 (4.92) 54 (2.13) A0005740  20 A B Junction box VBC with grounding point View in arrow direction 2 fixing bore holes Ø 4.5 mm (0.18") 1 3 2 4 2 1 3 BN GN 8 5 7 7 6 5 4 6 A0002332 A0002331  21 1 2 3 4 5 6 7 8 Structure of cable CMK Outer shield Inner shield, anode Semi-conductor layer Inner insulation Inner conductor, measuring signal Temperature sensor connection 2nd insulation Outer insulation  22 1 2 3 4 5 6 7 Structure of cable CYK71 Outer shield Inner shield, reference signal Inner insulation Inner conductor, measuring signal Semi-conductor layer 2nd insulation Outer insulation NOTICE Incorrect measurement due to short-circuit ‣ Make sure to remove the black semiconductor layer as far as the inner shield when connecting cable CMK and CYK71. Endress+Hauser 27 Electrical connection Liquisys M CCM223/253 5.6 Three-point step controller for Cl2 / ClO2 / total chlorine Connect the continuously variable motor valves as follows: 28 1. Connect the NO contact of the motor valve to relay 3. 2. Connect the NC contact of the motor valve to relay 4. Endress+Hauser Liquisys M CCM223/253 Electrical connection 5.7 Alarm contact A B 41 41 42 42 43 43 A0006415  23 A B Recommended fail-safe switching for the alarm contact Normal operating status Alarm condition Normal operating status Alarm condition Device in operation and no error message present (alarm LED off): • Relay energized • Contact 42/43 closed Error message present (alarm LED red) or device defective or de-energized (alarm LED off): • Relay de-energized • Contact 41/42 closed 5.8 Post-connection check Carry out the following checks once you have made the electrical connection: Device state and specifications Notes Are the devices and cables free from damage on the outside? Visual inspection Electrical connection Notes Are the mounted cables strain relieved? Are the connected cables provided with strain relief? Is the cable run correct, without loops and cross-overs? Are the power cable and signal cables connected correctly and in accordance with the wiring diagram? Are all the screw terminals tightened? Are all the cable entries fitted, tightened and leak-proof? Endress+Hauser 29 Operation options Liquisys M CCM223/253 6 Operation options 6.1 Quick operation guide You have the following ways of operating the transmitter: • On site via the key field • Via the HART interface (optional, with corresponding order version) with: – HART handheld terminal – PC with HART modem and the Fieldcare software package • Via PROFIBUS PA/DP (optional, with corresponding order version) by PC with a corresponding interface and the Fieldcare software package or via a programmable logic controller (PLC). For operation via HART or PROFIBUS PA/DP, please read the relevant sections in the additional Operating Instructions: • PROFIBUS PA/DP, field communication for Liquisys M CXM223/253, BA00209C/07/EN • HART, field communication for Liquisys M CXM223/253, BA00208C/07/EN The following section only explains operation via the keys. 6.2 Display and operating elements 6.2.1 Display LED displays Indicates the current operating mode, "Auto" (green LED) or "Manual" (yellow LED) A0027220 Indicates the activated relay in the "Manual" mode (red LED) The status of relays 3 and 4 is indicated on the LC display. A0027222 A0027221 A0027218 30 Indicates the working status of relay 1 and 2 LED green: measured value within the permitted limit, relay inactive LED red: measured value outside the permitted limit, relay active Alarm display, e.g. in event of continuous limit value overshoot, temperature sensor failure or system error (see error list) Endress+Hauser Liquisys M CCM223/253 Operation options LC display 1 2 13 11 5 4 042 14 12 3 mg/l R242 Setpoint 10 6 7 8 9 A0001924-EN Endress+Hauser  24 Transmitter LC display 1 Indicator for measuring mode (normal operation) 2 Indicator for calibration mode 3 Indicator for setup mode (configuration) 4 Indicator for "Hold" mode (current outputs remain at last current state) 5 Indicator for receipt of a message on devices with communication 6 Indicator of working status of relays 3/4: 7 Function code inactive, active 8 In measuring mode: measured variable - in setup mode: configured variable 9 In measuring mode: secondary measured value - in setup/calibr. mode: e.g. set value 10 Indicator for autom. Temperature compensation 11 Indicator for man. Temperature compensation 12 "Error": error display 13 Temperature offset 14 Sensor symbol (see the "Calibration" section) 31 Operation options Liquisys M CCM223/253 6.2.2 Operating elements The display shows the current measured value and the temperature simultaneously, which means you have an overview of the most important process data at once. Help text in the configuration menu helps users configure the device parameters. 1 2 7 3 4 6 5 A0024631-EN  25 1 2 3 4 5 6 7 Operating elements LC display for displaying the measured values and configuration data Key to switch relays in manual mode and to display the active contact LED for alarm function Changeover switch for automatic/manual mode LEDs for limit contactor relay (switch status) Main operating keys for calibration and device configuration Field for user-defined information 6.2.3 Key functions CAL key A0027235 When you press the CAL key, the device first prompts you for the calibration access code: • Code 22 for calibration • Code 0 or any other code for reading the last calibration data Use the CAL key to accept the calibration data or to switch from field to field within the calibration menu. ENTER key A0027236 When you press the ENTER key, the device first prompts you for the setup mode access code: • Code 22 for setup and configuration • Code 0 or any other code for reading all the configuration data. The ENTER key has several functions: • Calls up the Setup menu from the measuring mode • Saves (confirms) data entered in the setup mode • Moves on within function groups 32 Endress+Hauser Liquisys M CCM223/253 Operation options PLUS key and MINUS key A0027240 In the Setup mode, the PLUS and MINUS keys have the following functions: • Selection of function groups. Press the MINUS key to select the function groups in the order given in the "System configuration" section. • Configuration of parameters and numerical values • Operation of the relays in manual mode In the measuring mode, the following sequence of functions is accessed by repeatedly pressing the PLUS key: • Temperature displayed in °F • Temperature is hidden • pH measured value or ORP (only for EP version) • pH sensor signal in mV (only for EP version) • Sensor current of chlorine/chlorine dioxide sensor in nA • Zero current of sensor CCS120 • Current input signal in % • Current input signal in mA • Return to basic settings In the measuring mode, the following sequence of information is displayed by repeatedly pressing the MINUS key: • The current errors are displayed consecutively (max. 10). • Once all the errors have been displayed, the standard measurement display appears. In the function group F, an alarm can be defined separately for each error code. A0027241 A0027234 REL key In the manual mode, you can use the REL key to switch between the relay and the manual start of cleaning. In automatic mode, you can use the REL key to read out the switchon points (for limit contactor) or set points (for PID controller) assigned to the relay in question. Press the PLUS key to jump to the settings of the next relay. Use the REL key to get back to the display mode (automatic return after 30 s). AUTO key Use the AUTO key to switch between automatic mode and manual mode. Escape function If you press the PLUS and MINUS key simultaneously, you return to the main menu, or are taken to the end of calibration if calibrating. If you press the PLUS and MINUS key again, you return to the measuring mode. A0027237 Endress+Hauser 33 Operation options Liquisys M CCM223/253 Locking the keyboard Press the PLUS and ENTER key simultaneously for at least 3 s to lock the keyboard against any unauthorized data entry. All the settings can continue to be read. The code prompt displays the code 9999. A0027238 Unlocking the keyboard Press the CAL and MINUS key simultaneously for at least 3 s to unlock the keyboard. The code prompt displays the code 0. A0027239 34 Endress+Hauser Liquisys M CCM223/253 Operation options 6.3 Local operation 6.3.1 Automatic/manual mode The transmitter normally operates in automatic mode. Here, the relays are triggered by the transmitter. In the manual mode, you can trigger the relays manually using the REL key or start the cleaning function. How to change the operating mode: 1. The transmitter is in automatic mode. The top LED (green) next to the AUTO key is lit. 2. Press the AUTOMATIC key. 3. To enable the manual mode, enter the code 22 via the PLUS and MINUS keys and press ENTER to confirm. The lower LED (manual mode) is lit. 4. Select the relay or the function. You can use the REL key to switch between the relays. The relay selected and the switch status (ON/OFF) is displayed on the second line of the display. In the manual mode, the measured value is displayed continuously (e.g. for measured value monitoring for dosing functions). 5. Switch the relay. The relay is switched on with PLUS and switched off with MINUS. The relay remains in this switched state until it is switched again. 6. Press the AUTOMATIC key to return to the measuring mode, i.e. to the automatic mode. All the relays are triggered again by the transmitter. A0027242 A0027243 A0027240 A0027241 A0027240 A0027234 • The operating mode remains in effect even after a power failure. The relays assume the quiescent state, however. • The manual mode has priority over all other automatic functions. • Hardware locking is not possible in the manual mode. • The manual settings are kept until they are actively reset. • Error code E102 is signaled during manual operation. Endress+Hauser 35 Operation options Liquisys M CCM223/253 6.3.2 Operating concept Operating modes Measuring mode: standard mode of operation, displaying current measured values Setup mode access to all configuration settings Calibration mode: execution of calibration routine Code The function groups are selected with the PLUS or MINUS key. A0027244-EN  26 Description of the possible operating modes If no key is pressed in the setup mode for approx. 15 min, the device automatically returns to the measuring mode. Any active hold (hold during setup) is canceled. Access codes All device access codes are fixed and cannot be altered. When the device requests the access code, it distinguishes between different codes. • CAL key + code 22: access to Calibration and Offset menu • ENTER key + code 22: access to the menus for the parameters which make configuration and user-specific settings possible • PLUS + ENTER keys simultaneously (min. 3 s): lock the keyboard • CAL + MINUS keys simultaneously (min. 3 s): unlock the keyboard • CAL or ENTER key + any code: access to read mode, i.e. all the settings can be read but not modified. The device continues measuring in the read mode. It does not shift to the "Hold" status. The current output and the controllers remain active. 36 Endress+Hauser Liquisys M CCM223/253 Operation options Menu structure The configuration and calibration functions are arranged in function groups. • In the setup mode, select a function group with the PLUS and MINUS keys. • In the function group itself, switch from function to function with the ENTER key. • Within the function, select the desired option with the PLUS and MINUS keys or edit the settings with these keys. Then confirm with the ENTER key and continue. • Press the PLUS and MINUS keys simultaneously (Escape function) to exit programming (return to the main menu). • Press the PLUS and MINUS keys simultaneously again to switch to the measuring mode. If a modified setting is not confirmed by pressing ENTER, the old setting is retained. An overview of the menu structure is provided in the Appendix to these Operating Instructions. 1 - 2 3 E E E E E A0027245  27 1 2 3 Menu structure Functions (selection of parameters, entry of numbers) Function groups, scroll backwards and forwards with the PLUS and MINUS keys Switch from function to function with the ENTER key Hold function: "freeze" the outputs In both the setup mode and during calibration, the current output can be "frozen" (factory setting), i.e. it constantly retains its current status. "HOLD" appears on the display. If the controller actuating variable (steady control 4 to 20 mA) is output via current output 2, it is set to 0/4 mA during a hold. • Hold settings can be found in the "Service" function group. • During a hold, all contacts assume a quiescent state. • An active hold has priority over all other automatic functions. • With every hold, the I-component of the controller is set to "0". • Any alarm delay is reset to "0". • This function can also be activated externally via the hold input (see Wiring diagram; binary input 1). • A manual hold (field S3) remains active even after a power failure. Endress+Hauser 37 Commissioning Liquisys M CCM223/253 7 Commissioning 7.1 Function check LWARNING Incorrect connection, incorrect supply voltage Safety risks for staff and device malfunctions ‣ Check that all connections have been established correctly in accordance with the wiring diagram. ‣ Ensure that the supply voltage matches the voltage indicated on the nameplate. 7.2 Switching on Familiarize yourself with the operation of the transmitter before it is first switched on. In particular please read the "Basic safety instructions" and "Operation options" sections. After power-up, the device performs a self-test and then goes to the measuring mode. Now calibrate the sensor in accordance with the instructions in the "Calibration" section. During initial commissioning, the sensor must be calibrated so that the measuring system can return precise measurement data. Then perform the first configuration in accordance with the instructions in the "Quick setup" section. The values set by the user are kept even in the event of a power failure. The following function groups are available in the transmitter (the groups that are only available in the Plus Package are marked accordingly in the functional description): Setup mode • SETUP 1 (A) • SETUP 2 (B) • CURRENT INPUT (Z) • CURRENT OUTPUT (O) • ALARM (F) • CHECK (P) • RELAY (R) • SERVICE (S) • E+H SERVICE (E) • INTERFACE (I) Calibration and offset mode CALIBRATION (C) A detailed explanation of the function groups available in the transmitter can be found in the "Device configuration" section. 2 s F3 Err.delay Function display: The displayed code indicates the function position in the function group. Additional information A0025560-EN  28 38 Information for the user on the display Endress+Hauser Liquisys M CCM223/253 Commissioning C131 C132 C133 C121 C C1 C111 To make it easier for you to select and find function groups and functions, a code for the corresponding field is displayed for each function →  28 The structure of this code is illustrated in →  29. The function groups are indicated as letters in the first column (see the names of the function groups). The functions of the individual groups are displayed incrementally by row and by column. A0027502  29 Function code Factory settings The first time the device is switched on, the factory setting is set for all the functions. The table below provides an overview of the most important settings. All other factory settings can be found in the description of the individual function groups in the "System configuration" section (the factory setting is highlighted in bold). Function Factory setting Type of measurement Concentration of free chlorine/total chlorine in mg/l Temperature measurement in °C pH value (EP version) Sensor setting CCS140 for free chlorine Alarm contact Steady contact Alarm delay Setting in minutes Error current for alarm 22 mA Check functions* Off. Can be switched on if required Limit value 1 and 2 for chlorine/chlorine dioxide 0.5 mg/l Limit value 1 and 2 for pH* pH 7.2 Limit value 1 and 2 for ORP* 750 mV Limit value 1 and 2 for temperature 50 °C Current outputs 1 and 2 4 to 20 mA Current output 1: measured value for 4 mA signal current 0.00 mg/l Current output 1: measured value for 20 mA signal current 2.00 mg/l Current output 2: temperature value for 4 mA signal current* 0 °C Current output 2: temperature value for 20 mA signal current* 50 °C * with appropriate version Endress+Hauser 39 Commissioning Liquisys M CCM223/253 7.3 Quick Setup After power-up, you must make some settings to configure the most important functions of the transmitter which are required for correct measurement. The following section gives an example of this. User entry 1. Press the ENTER key 2. Enter the code 22 to open access to the menus. Press the ENTER key. 3. Press the MINUS key until you get to the "Service" function group. 4. Press ENTER to be able to make your settings. Range of adjustment (factory settings in bold) Display S SERVICE A0008408-EN 5. Select your language in S1, e.g. "ENG" for English. Press ENTER to confirm your entry. ENG = English GER = German FRA = French ITA = Italian NEL = Dutch ESP = Spanish ENG S1 Language A0008409-EN 6. Press the PLUS and MINUS key simultaneously to exit the "Service" function group. 7. Press the MINUS key until you get to the "Setup 1" function group. 8. Press ENTER to be able to make your settings for "Setup 1". A SETUP 1 A0007824-EN 9. In A1, select the desired sensor type. Press ENTER to confirm your entry. 120 = CCS120 140 = CCS140 141 = CCS141 240 = CCS240 241 = CCS241 963 140 A1 Sensor A0001954-EN 10. In A2, select the desired engineering unit. Press ENTER to confirm your entry. mg/l ppm ppb mg/l A2 Unit A0024894-EN 11. If you have connected the INS proximity switch, you Off can switch on flow monitoring of the sample INS stream through the CCA250 assembly in A3. Press ENTER to confirm your entry. Off A3 Cont.stop A0001956-EN 12. If flow briefly falls below the threshold value, you can suppress controller switch-off by entering a delay time in A4. Press ENTER to confirm your entry. 0s 0 to 2000 s s 0 A4 Off Delay A0001957-EN 40 Endress+Hauser Liquisys M CCM223/253 Commissioning User entry Range of adjustment (factory settings in bold) 13. In A5, enter the delay time for controller switchon. In the case of chlorine/chlorine dioxide control, a delay until the reception of a representative measured value is recommended after a long period without flow. Press ENTER to confirm your entry. 0s 0 to 2000 s In A6, select the binary input. Press ENTER to confirm your entry. Hold = external hold Clean = cleaning trigger 14. Display s 0 A5 On Delay A0001958-EN Hold A6 Digital 1 A0001959-EN 15. 16. Endress+Hauser In A7, enter the measured value damping. Measured value damping causes the measured value to be averaged over the specified number of individual measured values (if A7 = 1, no damping takes place). Press ENTER to confirm your entry. The display returns to the initial display of the "Setup 1" function group. 1 1 to 60 1 A7 Damping A0001960-EN Press PLUS and MINUS simultaneously to switch to the measurement mode. 41 Commissioning Liquisys M CCM223/253 7.4 Device configuration 7.4.1 Setup 1 (chlorine/chlorine dioxide) Coding Field Range of adjustment (factory settings in bold) Display Info A Configuration of basic functions SETUP 1 function group A SETUP 1 A0007824-EN A1 Select the connected sensor type 120 = CCS120 140 = CCS140 240 = CCS240 241 = CCS241 963 Select the display unit mg/l ppm ppb 140 A1 Sensor If the device is reset in field S9, the configured sensor type is not modified. A0001954-EN A2 mg/l A2 Unit A0001955-EN A3 A4 Select flow Off monitoring of the INS sample flow through the CCA250 assembly (with controller switchoff) Enter the delay for controller switch-off by the sample flow 0s 0 to 2000 s Enter the delay for controller switch-on by the sample flow 0s 0 to 2000 s Off A3 Cont.stop May only be switched on when the INS proximity switch is connected. A0001956-EN s 0 A4 Off Delay Brief flow shortfalls can be suppressed by this delay and do not result in controller switch-off. A0001957-EN A5 s 0 A5 On Delay A0001958-EN A6 Select binary input 1 Hold = external hold Clean = cleaning trigger In the case of chlorine/ chlorine dioxide control, a delay until the reception of a representative measured value is recommended after a long period without flow. Hold A6 Digital 1 A0001959-EN A7 Enter the value for measured value damping 1 1 to 60 1 A7 Damping A0001960-EN 42 Endress+Hauser Liquisys M CCM223/253 Commissioning Flow monitoring in the sample stream If the flow falls below 30 l/h or if sample flow through the CCA250 assembly fails completely, this causes an alarm to be signaled when an INS proximity switch is connected. This alarm becomes active when the switch-off delay time elapses (A4 field). The alarm is canceled immediately as soon as the necessary rate of flow is restored. The device automatically stops the dosing of chemicals and the Chemoclean cleaning function for the duration of the alarm. All the relays assigned to the PID controller or to a cleaning function go to the quiescent state. The NO contact closes in the case of the three-point step controller. Dosing and cleaning actions are only resumed once the switch-on delay time has elapsed (A5 field). 1 A 0 1 B A4 A5 0 1 A4 A5 C 0 1 D 0 E F G A0002018  30 A B C D E F G 0 1 A4 A5 Endress+Hauser Alarm signaling and dosing switch-off by the sample stream Flow in sample stream Relay contacts of PID controller NO contact on three-point step controller Alarm relay Flow < 30 l/h or flow failure Flow alarm Flow restored Off On Field A4 (controller switch-off delay) Field A5 (controller switch-on delay) 43 Commissioning Liquisys M CCM223/253 7.4.2 Setup 2 (temperature or pH/ORP) Use this function group to change the settings for temperature measurement and pH/ORP measurement. You already made all the settings for this function group during initial commissioning. However, you can change the values chosen at any time. Coding Field Range of adjustment (factory settings in bold) Display Info B Initial display screen in the SETUP 2 function group SETUP 2 function group B SETUP 2 A0007830-EN B1 Select operating mode Off pH ORPmV Off B1 Oper.Mode A0001963-EN B2 Select pH compensation Off Manu Auto Off B2 pH comp. Field only available for EP version. ORPmV = ORP (oxidationreduction potential) in mV. When the operating mode is changed, all user settings are automatically reset to the basic settings. If the device is reset in field S9, the configured operating mode is not modified. Field only available for ES and EP versions. (operation with CCS140/141) A0001964-EN B3 Enter the value for manual pH compensation Last compensation value pH 4.00 to 9.00 pH 7.20 B3 Manu.Comp The field is only displayed if » manual« (Manu) was selected in the B2 field. The measured pH value is displayed as the secondary parameter. A0001965-EN B4 Enter the process temperature Current measured value 0 to 50 °C ¡C 0.0 B4 RealTemp. A0001966-EN B5 Enter the temperature differential (offset) Current offset -5.0 to 5.0 °C ¡C 0.0 B5 Temp.Offs You can edit the displayed value. The value can be changed by a maximum of ±5 °C. As the measurements are very accurate, the value generally does not need to be adjusted. The offset is the difference between the actual value entered and the measured temperature. A0007835-EN Types of chlorine A distinction is made between free chlorine and combined chlorine. Free chlorine 44 Endress+Hauser Liquisys M CCM223/253 Commissioning Free chlorine is understood as the sum of elementary chlorine (Cl2), hypochlorous acid (HOCl) and hypochlorite ions (OCl–). These forms of chlorine are able to kill bacteria, inactivate viruses and oxidize organic substances within a short period of time. Combined chlorine Combined chlorine refers to the forms of chlorine in water and consists of chemical compounds made up of chlorine and ammonia (NH3) or ammonium (NH4 +) entstehen. Combined chlorine still has a disinfectant property, but far less than that of free chlorine. Total chlorine Total chlorine is the sum of free chlorine and combined chlorine. Measuring free chlorine with the CCS140 and CCS141 sensors Molecular chlorine (Cl2) is present at pH values < 4. Consequently, hypochlorous acid (HOCl) and hypochlorite (OCl– remain as components of free chlorine within the range of pH 4 to 11. As hypochlorous acid splits up (dissociates) with an increasing pH value to form hypochlorite ions (OCl–) and hydrogen ions (H+), the amounts of the individual components of free effective chlorine change with the pH value. For example, if the amount of hypochlorous acid is 97% at pH 6, it drops to approx. 3% at pH 9. 100 A 0 % 80 20 60 40 OCl- HOCl C 40 60 B 20 80 % 100 0 4 5 6 7 8 pH 9 10 11 A0002017  31 A B C Basic representation of pH compensation Measured value with pH compensation Measured value without pH compensation pH compensation The CCS140 or CCS141 chlorine sensors selectively measure the amount of hypochlorous acid in amperometric measurement.. This works as a powerful disinfectant in a watery solution. In contrast to this, hypochlorite is an extremely weak disinfectant. Therefore, when used as a disinfectant at higher pH values, the effectiveness of chlorine is limited. As hypochlorite ions cannot permeate the sensor membrane, the sensors do not record this value. Measuring total chlorine with the CCS120 sensor If, in addition to free available chlorine, ammonium is also present in the medium preferably water - chloramines (ClnNHm) form quickly. This compound is formed in various Endress+Hauser 45 Commissioning Liquisys M CCM223/253 degrees of dimerization. It is known as "combined chlorine". Combined chlorine has a lower disinfecting effect but it forms larger depots compared to free chlorine. This means: • Significantly slower elimination of existing germs. • Disinfectant effect over considerably longer periods. • Disinfectant effect over considerably longer transport distances. The CCS120 amperometric sensor measures the total chlorine content, i.e. free chlorine as well as chloramine components. This type of measurement is only slightly pH dependent. pH compensation of the chlorine sensor signal during free chlorine measurement (only for ES and EP versions, for CCS140/141 sensors) To calibrate and verify the chlorine measuring system, a colorimetric reference measurement must be carried out using the DPD method. Free chlorine reacts with diethyl-p-phenylendiamine to form a red dye. The intensity of the red color increases proportionally to the chlorine content. With the DPD method, the water under measurement is constantly buffered to a pH value of approx. 6.3. Therefore, the pH value of the water under measurement is not included in the DPD measurement here. Due to the buffer function in the DPD method, all components of free effective chlorine are recorded and thus the total free chlorine is measured. If you select pH compensation in fields B2 or B3, the sum of hypochlorous acid and hypochlorite corresponding to the DPD measurement is calculated from the hypochlorous acid measured by the sensor and the pH value in the region of pH 4 to 9. For this calculation, the curve is stored in the transmitter. When free chlorine is measured with pH compensation switched on, always perform calibration in pH-compensated mode. When you use pH compensation, the measured chlorine value that is displayed and applied to the device output corresponds to the DPD measured value even if the pH values fluctuate. If you do not use pH compensation, the measured chlorine value corresponds to the DPD measurement only if the pH value remains unchanged compared with the calibration. Without pH compensation, the chlorine measuring system must be recalibrated when the pH value changes. pH compensation can be performed both automatically using the connected pH electrode (EP version) and manually (ES version) by entering the pH value in the B3 field. Chlorine dioxide and total chlorine measurement is largely or entirely independent of the pH value and therefore no pH compensation is required. Accuracy of pH compensation when measuring free chlorine The accuracy of the pH-compensated measured chlorine value is derived from the sum of several individual deviations (chlorine, pH, temperature, DPD measurement etc.). High levels of hypochlorous acid (HOCl) during chlorine calibration have a positive effect on accuracy, whereas low levels of hypochlorous acid have a negative effect. The inaccuracy of the pH-compensated measured chlorine value increases the greater the pH difference between measuring mode and chlorine calibration or the more inaccurate the underlying individual measured values are. Calibration of free chlorine taking the pH value into consideration The reference measurement (DPD method, photometer) determines the total free chlorine by buffering to pH 6.2. In contrast to this, amperometric measurement determines only the HOCl component. During operation, pH compensation is effective up to a pH value of 9. However, there is hardly any HOCl left at this pH value, and the measured current is very low. At this point, pH compensation has the effect of increasing the measured HOCl value to the actual value of the free chlorine. 46 Endress+Hauser Liquisys M CCM223/253 Commissioning Calibration of the complete measuring system makes sense only up to a pH value of the medium of 8 or 8.2. Sensor pH value HOCl content Uncompensated value Compensated value CCS141 8.2 15 % 12 nA 80 nA CCS140 8 20 % 4 nA 20 nA Above these pH values, the total error of the measuring system is unacceptably high. 7.4.3 Current input For the "Current input" function group, you require a relay card with a current input which is not available in the basic device version. With this function group, you can monitor process parameters and use them for feedforward control. For this purpose, you must connect the current output of an external measured variable (e.g. flowmeter) to the 4 to 20mA input of the transmitter. The following assignment applies: Flow in main stream Current signal in mA Current input signal in % Flowmeter start of measuring range 4 0 Flowmeter end of measuring range 20 100 Flow monitoring in the main stream This arrangement is particularly practical if the sample flow through the CCA250 assembly is completely independent of the flow in the main stream. This permits signaling of an alarm condition in the main stream (flow too low or has completely stopped) and triggers dosing switch-off even if the medium flow is maintained due to the method of installation. This monitoring method corresponds to monitoring the flow rate in the sample stream (see SETUP 1). 1 A 0 1 B Z2 Z3 0 1 Z2 Z3 C 0 1 D 0 E F G A0002019  32 Endress+Hauser Alarm signaling and dosing switch-off by the main stream A Flow in main stream F Flow alarm B G Flow restoration Relay contacts of PID controller 47 Commissioning Liquisys M CCM223/253 C NO contact on three-point step controller Z2 Delay for controller switch-off, see field Z2 D Alarm relay Z3 Delay for controller switch-on, see field Z3 E Flow below switch-off limit Z 4 or flow failure 0 Off 1 On Feedforward control to PID controller You can optimize control on control systems with very short response times by measuring the medium flow rate in addition to the oxygen content. Then apply this flow rate value (4 to 20 mA) as feedforward control to the PID controller. 1 2 4 3 F 6 ENDRESS+HAUSER LIQUISYS S 5 Cl2 pH 4 ... 20 mA A0025120  33 Sample arrangement for feedforward control of the flow in the main stream to the PID controller 1 Medium tapping point 5 Flow assembly CCA250 2 Static mixer 6 Liquisys CCM253 3 Injection points 4 Flowmeter Feedforward control is a multiplying function as illustrated in the figure below (example with factory setting): 48 Endress+Hauser Liquisys M CCM223/253 Commissioning Y 1.5 1 0.5 0 20 40 Z7 60 80 100 X A0008942  34 Y X Endress+Hauser Multiplying feedforward control Gain Kinfl Current input signal in [%] 49 Commissioning Liquisys M CCM223/253 Functions marked in italics are not supported by the basic device version. Coding Field Range of adjustment (factory settings in bold) Display Info Z Current input settings CURRENT INPUT function group Z CUR.INPUT A0024903-EN Z1 Select flow monitoring of main stream (with controller switchoff) Off On Off Z1 Cont.stop Flow monitoring may only be switched on if the flowmeter is connected in the main stream. If Z1 = off, fields Z2 to Z5 are not available. A0024904-EN Z2 Enter the delay for controller switchoff through current input 0s 0 to 2000 s s 0 Z2 Off Delay Brief flow shortfalls can be suppressed by this delay and do not result in controller switchoff. A0024905-EN Z3 Enter the delay for controller switchon through current input 0s 0 to 2000 s s 0 Z3 On Delay In the case of a controller, a delay until the reception of a representative measured value is recommended after a long period without flow. A0024934-EN Z4 Enter the switch-off 50 % limit value for the 0 to 100 % current input % 50 Z4 A.Thresh 0 to 100% corresponds to 4 to 20 mA at the current input. Observe measured value assignment to the current output of the flowmeter. A0024935-EN Z5 Enter the switch-off Low direction for the High current input Low Z5 Stop Dir The controller is switched off if the value entered in Z4 is undershot or overshot. A0024939-EN Z6 Select feedforward control to PID controller Off Lin = linear Basic Off Z6 PID influ A0024940-EN Z7 Enter value for 50 % feedforward control 0 to 100 % at which gain = 1 applies % 50 Z7 Kinflu=1 If Z6 = off, the field Z7 is not available. Z6 = basic: disturbance variable only affects the basic load (alternatively dosing in proportion to quantity, if usual PID controller not possible, e.g. defective sensor). When the value is set, the controller actuating variable is the same size when feedforward control is switched on as when feedforward control is switched off. A0024941-EN 50 Endress+Hauser Liquisys M CCM223/253 Commissioning 7.4.4 Current outputs Use the "Current output" function group to configure the individual outputs. You can enter either a linear characteristic (O3 (1)) or a user-defined current output characteristic in conjunction with the Plus Package (O3 (3)). Exception: if you have chosen a "continuous controller" for current output 2, you cannot enter a user-defined current output characteristic for this current output. In addition, you can also simulate a current output value (O3 (2)) to check the current outputs. Cl [mg/l] 2 Δ Signal 1 0 4 8 12 16 Δ[mA] 20 [mA] A0002021  35 User-defined current output characteristic (example) The current output characteristic must increase or decrease very monotonically. The distance per mA between two table value pairs must be greater than: Sensor/measurement parameter Minimum distance per mA CCS120 0.005 mg/l CCS140/240 0.01 mg/l CCS141/241 and 963 0.003 mg/l pH pH 0.03 ORP 5 mV Temperature 0.25 °C The values for the sample characteristic →  35 are entered in the following table. The distance per mA is calculated from Δ signal / Δ mA. Current output 1 Endress+Hauser Current output 2 Value pair Cl[mg/l] Current [mA] Distance per mA 1 0 4 2 0.5 14 0.05 3 2 20 0.25 .....[] Current [mA] Distance per mA 51 Commissioning Liquisys M CCM223/253 First enter the desired current output configuration into the following blank table with a pencil. Calculate the resulting signal distance per mA to observe the necessary minimum slope. Then enter the values in the device. Current output 1 Value pair .....[] Current [mA] Current output 2 Distance per mA .....[] Current [mA] Distance per mA 1 2 3 4 5 6 7 8 9 10 Functions marked in italics are not supported by the basic device version. Coding Field Range of adjustment (factory settings in bold) Display Info O CURRENT OUTPUT function group O Configuration of the current output (does not apply for PROFIBUS). OUTPUT A0025026-EN O1 Select current output Out 1 Out 2 Out1 A characteristic can be selected for every output. O1 Sel.Out A0025027-EN O2 Select measured °C variable for 2nd Contr current output ¡C O2 Parameter A0025028-EN O3 (1) Enter the characteristic type Lin = linear (1) Sim = simulation (2) Tab = table (3) lin O3 Sel.Type A0025029-EN 52 pH or ORPmV only with EP version and depending on option selected in B1. R247 or R257 =curr (current output 2) can only be selected if O2=Contr (controller output) is selected. The characteristic can have a positive or negative slope for the measured value output. In the case of actuating variable output (O2 = Contr), an increasing current corresponds to an increasing actuating variable. Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field Range of adjustment (factory settings in bold) O311 4 to 20mA 0 to 20 mA Select current range Display Info 4-20 O311 Sel.Range A0025030-EN O312 O313 0/4 mA value: Enter the associated measured value 20 mA value: Enter the associated measured value 0 ppb 0 to 20000 ppb 0.00 ppm 0 to 20 ppm 0.00 mg/l 0 to 20 (5) mg/l pH 4.00 pH 4 to 9 0 mV 0 to 1500 mV 0 °C 0 to 50 °C 2000 ppb 0 to 20000 ppb 2.00 ppm 0 to 20 ppm 2.00 (0.50) mg/l 0 to 20 (5) mg/l pH 9.00 pH 4 to 9 1000 mV 0 to 1500 mV 50 °C 0 to 50 °C mg/l 0.00 O312 0/4 mA A0001944-EN mg/l 2.00 O313 20 mA A0001946-EN Here you can enter the measured value at which the min. current value (0/4 mA) is applied at the transmitter output (not for controller). For the minimum distance between the 0/4 mA and 20 mA value, see field O313 This field is not displayed if O2 = Contr. Here you can enter the measured value at which the max. current value (20 mA) is applied at the transmitter output. The minimum distance between the 0/4 mA and 20 mA value must be as follows: • • • • • • 140/240: 0.2 mg/l 141/241/963: 0.05 mg/l 120: 0.1 mg/l pH: pH 0.5 ORP: 100 mV Temperature: 5 °C This field is not displayed if O2 = Contr. O3 (2) Simulate current output Lin = linear (1) Sim = simulation (2) Tab = table (3) sim O3 Sel.Type Simulation is not ended until O3(1) or O3(3) is selected. For further characteristics, see O3 (1), O3 (3). A0025039-EN O321 Enter simulation value Current value 0.00 to 22.00 mA mA 10.20 O321 Simulat. Entering a current value results in this value being directly output at the current output. A0025040-EN O3 (3) Enter current output table Lin = linear (1) Sim = simulation (2) Tab = table (3) table O3 Sel.Type A0025041-EN Endress+Hauser Only for ES and EP versions. Values can also be subsequently added or modified. The values entered are automatically sorted by increasing current value. For further characteristics, see O3 (1), O3 (2). 53 Commissioning Liquisys M CCM223/253 Coding Field Range of adjustment (factory settings in bold) O331 Read Edit Select table option Display Info read O331 Sel.Table A0025042-EN O332 Enter number of 1 table value pairs 1 to 10 1 O332 Enter the number of pairs of x and y values (measured value and current value) here. No.Elem. A0025043-EN O333 Select table value pair 1 1 to no. elem. Assign 1 O333 Sel.Elem. The system runs through the O333 to O335 function chain as often as indicated in O332. "Assign" appears as the last step. The display goes to O336 after confirmation. A0025044-EN O334 O335 Enter x value Enter y value 0 ppb 0 to 20000 ppb 0.00 ppm 0 to 20 ppm 0.00 mg/l 0 to 20 (5) mg/l pH 4.00 pH 4 to 9 0 mV 0 to 1500 mV 0 °C 0 to 50 °C 0.00 mA 0.00 to 20.00 mA mg/l 0.00 O334 x value = measured value specified by user. Meas.val. A0025046-EN mA 0.00 O335 y value = user-defined current value pertaining to O334. Return to O333 until all values are entered. mA value A0025048-EN O336 Message as to whether table status is OK Yes No yes O336 Status ok Back to O3. If status = no, correct the table (all settings made up until now remain intact) or go back to the measuring mode (table is deleted). A0025049-EN 54 Endress+Hauser Liquisys M CCM223/253 Commissioning 7.4.5 Alarm You can use the "Alarm" function group to define various alarms and configure output contacts. Each individual error can be defined to be effective or not (at the contact or as an error current). Functions marked in italics are not supported by the basic device version. Coding Field Range of adjustment (factory settings in bold) Display Info F Alarm function settings. ALARM function group F ALARM A0025141-EN F1 Select contact type Latch = latching contact Momen = momentary contact Latch F1 The option selected only applies for the fault-signaling contact, not for the error current. Cont.Type A0025142-EN F2 Select the time unit for the alarm delay min s s F2 Time Unit A0025143-EN F3 Enter alarm delay 0 min (s) 0 to 2000 s (min) s 0 F3 Depending on the option selected in F2, the alarm delay can be entered in s or min. Err.Delay A0025144-EN F4 Select error current 22 mA 2.4 mA 22mA "0-20 mA" was selected in  IfO311, "2.4 mA" may not be F4 used. Err.Curr A0025145-EN F5 Select the error number 1 1 to 255 1 F5 Sel.error A0025146-EN F6 Set alarm Yes contact to be No effective for the selected error yes F6 Rel.Assg Here you can select all the errors which should trigger an alarm. The errors are selected by the error numbers. Please refer to the table in the "System error messages" section for the meaning of the individual error numbers. The factory settings remain in effect for all errors that are not edited. If “no” is selected, all the other alarm settings are deactivated (e.g. alarm delay). The settings themselves are maintained. This setting only applies to the error currently selected in F5. A0025147-EN Endress+Hauser 55 Commissioning Liquisys M CCM223/253 Coding Field F7 Range of adjustment (factory settings in bold) Set error No current to be Yes effective for the selected error Display Info no F7 Curr.Assg The option selected in F4 is effective or not effective in the event of an error. This setting only applies to the error currently selected in F5. A0025148-EN F8 Automatic cleaning function start No Yes no F8 This field is not available for certain errors, see the "Troubleshooting and fault elimination" section. CleanTrig A0025149-EN F9 Select return to Next = next menu or next error number error ←R next F9 If ←R is selected, you return to F. If Next is selected, you go to F5. Select A0025150-EN 7.4.6 Check The CHECK function group is only available for devices with the Plus Package (ES and EP versions). In the CHECK function group, you can select different monitoring functions for the measurement. By default all monitoring functions are switched off. The Sensor Check System is adapted to the current application conditions by adding and setting the suitable functions. Alarm threshold monitoring When you perform chlorine or chlorine dioxide measurements without chemical dosage control, sensor errors lead to a measured value error, but have no impact on the process medium (examples: monitoring measurements in water works). Sensor errors generally cause implausibly high or low readings. This is detected and signaled by user-definable alarm thresholds. Controller monitoring When you perform chlorine or chlorine dioxide measurements with simultaneous chemical dosage control, sensor errors not only result in incorrect measured values but also directly impact the state of the process medium. Particularly in the case of regulated water disinfection, due to the closed control loop there is the risk that chemical dosing will not switch on if the measured value is constantly too high. This poses a considerable danger to process stability, and could even pose a serious health hazard for humans. On the other hand, if the measured value is constantly too low this results in higher operating costs and a risk of corrosion due to the continuous dosing of chemicals. These cases are detected and signaled using user-definable monitoring times for maximum permitted limit value overshoot and undershoot. Sensor activity monitoring The effect of the process medium on the sensor can also result in incorrect measured values. For example, severe deposit buildup on the sensor membrane can cause the 56 Endress+Hauser Liquisys M CCM223/253 Commissioning measuring signal to be very sluggish or not even change at all (constant signal). This passive behavior is detected and signaled by constantly monitoring the signal activity. Overview of SCS monitoring functions Mode of operation Alarm threshold monitoring (P111 to P114) (P121 to P124) Possible setting • User-definable lower Off alarm threshold (AS) • User-definable upper Only lower alarm threshold (AS) alarm threshold Only upper alarm threshold Alarm event Use - Applications with or without chemical dosage control Lower alarm threshold reached or undershot Upper alarm threshold reached or exceeded Lower and Lower alarm threshold upper alarm reached or undershot or threshold upper alarm threshold reached or exceeded Endress+Hauser Controller monitoring (CC: controller check, P115 to P118 P125 to P128) • Switch-on duration monitoring • Switch-off duration monitoring Off - On Set maximum duration for permanent switch-on or switch-off exceeded Sensor activity monitoring (AC: alternation check, P115 to P118 P125 to P128) Signal change monitoring Off - On Change within 1 hour less than • ±0.01 mg/l (CCS140/240, sensor 963) • ±0.005 mg/l (CCS141/241) • pH ±0.01 • ±1 mV Applications with chemical dosage control Applications with or without chemical dosage control 57 Commissioning Liquisys M CCM223/253 You can use the "Check" function group to monitor the measured value for permissible upper and lower limits and trigger an alarm. Functions marked in italics are not supported by the basic device version. Coding Field Range of Display adjustment (factory settings in bold) Info P Settings for sensor and process monitoring CHECK function group P CHECK A0009045-EN P1(1) Cl2 ClO2 P1 Cl2 if A1 = "120", "140", "141", "963" ClO2 if A1 = "240", "241" Parameter A0001988-EN P111 P112 Select alarm threshold monitoring Enter alarm delay Off Low High LoHi = low and high Lo! Hi! LoHi! 0 min (s) 0 to 2000 min (s) Off P111 A.Thresh A0001989-EN min 0 P112 Err.Delay A0001990-EN P113 Enter lower alarm threshold 0 ppb 0 to 20000 ppb 0.00 ppm 0 to 20 ppm 0.00 mg/l 0 to 20 (5) mg/l Alarm possible with or without controller switch-off. xxxx = without controller switch-off xxxx! = with controller switchoff Depending on the option selected in F2, the alarm delay can be entered in s or min. This delay must first elapse before undershooting/ overshooting in accordance with fields P113/P114 results in an alarm. Not applicable when P111 = off mg/l 0.00 P113 LowAlarm A0001991-EN P114 Enter upper alarm threshold 20000 ppb 0 to 20000 ppb 20.00 ppm 0 to 20 ppm 20.00 (5.00) mg/l 0 to 20 (5) mg/l Not applicable when P111 = off mg/l 20.00 P114 HighAlarm A0001992-EN P115 58 Select process monitoring Off AC CC AC+CC AC! CC! AC+CC! mg/l Off P115 ProcMonit A0001993-EN AC = sensor activity monitoring CC = controller monitoring Alarm possible without or with simultaneous controller switchoff. xxxx = without controller switch-off xxxx! = with controller switchoff Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field Range of Display adjustment (factory settings in bold) Info P116 Enter maximum permissible duration for alarm threshold undershoot 60 min 0 to 2000 min Only if P115 = CC or AC+CC Enter maximum permissible duration for alarm threshold overshoot 120 min 0 to 2000 min Enter limit value 500 ppb 0 to 20000 ppb 0.5 ppm 0 to 20 ppm 0.5 (0.1) mg/l 0 to 20 (5) mg/l P117 P118 min 60 P116 Tmax Low A0002006-EN Only if P115 = CC or AC+CC min 120 P117 Tmax High A0002007-EN mg/l 0.5 P118 Setpoint A0002008-EN P1(2) pH ORPmV pH P1 Parameter Limit value for monitoring according to fields P116 and P117. performing  When external control from a process control system with an external set point, make sure that the setting matches that in field P118. Only for EP version pH or ORPmV is displayed depending on the mode of operation selected in field B1. A0001997-EN P121 P122 Select alarm threshold monitoring Enter alarm delay Off Low High LoHi = low and high Lo! Hi! LoHi! 0 min (s) 0 to 2000 min (s) Off P121 A.Thresh A0001998-EN min 0 P122 Err.Delay A0001999-EN P123 Enter lower alarm threshold pH 4.00 pH 4 to 8.9 0 mV 0 to 1490 mV Alarm possible with or without controller switch-off. xxxx = without controller switch-off xxxx! = with controller switchoff Depending on the option selected in F2, the alarm delay can be entered in s or min. This delay must first elapse before undershooting/ overshooting in accordance with fields P123/P124 results in an alarm. Not applicable when P121 = off pH 4.00 P123 LowAlarm A0002000-EN P124 Enter upper alarm threshold pH 9.00 pH 4.1 to 9 1500 mV 10 to 1500 mV Not applicable when P121 = off pH 9.00 P124 HighAlarm A0002001-EN Endress+Hauser 59 Commissioning Liquisys M CCM223/253 Coding Field Range of Display adjustment (factory settings in bold) Info P125 Off AC CC AC+CC AC! CC! AC+CC! AC = sensor activity monitoring CC = controller monitoring Alarm possible without or with simultaneous controller switchoff. xxxx = without controller switch-off xxxx! = with controller switchoff Options CC, AC+CC, CC! and AC +CC! can only be selected if pH is selected in field P1(2). P126 P127 P128 Select process monitoring Enter maximum permissible duration for alarm threshold undershoot 60 min 0 to 2000 min Enter maximum permissible duration for alarm threshold overshoot 120 min 0 to 2000 min Enter limit value pH 7.20 pH 4 to 9 Off P125 ProcMonit A0002002-EN Only if P125 = CC or AC+CC min 60 P126 Tmax Low A0002003-EN Only if P125 = CC or AC+CC min 120 P127 Tmax High A0002004-EN pH 7.20 P128 Setpoint A0002005-EN 7.4.7 Limit value for monitoring according to fields P126 and P127. performing  When external control from a process control system with an external set point, make sure that the setting matches that in field P128. Relay configuration For the "RELAY" function group, you require a relay card which is not available in the basic device version. The following relay contacts can be selected and configured as desired (max. four contacts, depending on options installed): • Limit contactor for chlorine/chlorine dioxide measured value: R2 (1) • Limit contactor for pH/ORP measured value: R2 (2) • Limit contactor for temperature: R2 (3) • PID controller for chlorine/chlorine dioxide: R2 (4) • PID controller for pH: R2 (5) • Timer for cleaning function: R2 (6) • Chemoclean function: R2 (7) • Three-point step controller for chlorine/chlorine dioxide: R2 (8) Only one function can be assigned to each relay. If a relay function is already switched on (R211 to R281), it is switched off automatically when you select another function and press ENTER to confirm (R2(1) to R2(8)). Pressing the REL key allows you to display the corresponding setpoint of every relay function. 60 Endress+Hauser Liquisys M CCM223/253 Commissioning Limit contactors for chlorine/chlorine dioxide/total chlorine measured value and temperature or pH or ORP measured value The transmitter has different ways of assigning a relay contact. Switch-on and switch-off points and pickup and dropout delays can be assigned to the limit contactor. In addition, you can configure an alarm threshold to output an error message and to start a cleaning function in conjunction with this. These functions can be used both for the primary value and for temperature measurement. Please refer to the switch states in →  36 for a clear illustration of the relay contact states. • When the measured values increase (maximum function), the relay contact is closed as of t2 after the switch-on point (t1) has been exceeded and the pickup delay has elapsed (t2-t1). The alarm contact switches if the alarm threshold (t3) is reached and the alarm delay (t4-t3) has also elapsed (errors E067 to E070). • When the measured values decrease, the alarm contact is reset when the value falls below the alarm threshold (t5) again, as is the relay contact (t7) after the dropout delay (t7-t6). • If the pickup and dropout delays are set to 0 s, the switch-on and switch-off points are also switch points of the contacts. The same settings can also be made for a minimum function in the same way as for the maximum function. 5 6 1 4 A 2 3 7 t1 t2 t3 t4 t5 t6 t7 t 7 B 3 2 4 6 1 5 t1 t2 t3 t4 t5 t6 t7 t A0025215  36 A B 1 2 3 4 5 6 7 Endress+Hauser Illustration of the alarm and limit value functions Switch-on point > switch-off point: Max. function Switch-on point < switch-off point: Min. function Alarm threshold Switch-on point Switch-off value Contact ON Alarm ON Alarm OFF Contact OFF 61 Commissioning Liquisys M CCM223/253 P(ID) controller You can define various controller functions for the transmitter. On the basis of the PID controller, P, PI, PD and PID controllers can be implemented. For an optimum control system, use the controller that best suits your application. • P controller Used for simple linear control purposes with small system deviations. Where major changes are to be controlled, overshooting may occur. In addition, a lasting control deviation must be expected. • PI controller Is used for control systems where overshooting is to be avoided and no lasting control deviation should occur. • PD controller Is used for processes that require quick changes and where peaks must be corrected. • PID controller Is used for processes where a P, PI or PD controller does not control sufficiently. Configuration options of the P(ID) controller The following configuration options are available for a PID controller: • Change control gain Kp (P influence) • Set integral action time Tn (I influence) • Set derivative action time Tv (D influence) Basic load dosing (basic) You can set a constant dosage amount (field R2411) with basic load dosing (field R241). PID control plus basic load dosing If you have selected this function (PID + Basic) in field R241, the PID-controlled dosage amount does not drop below the basic load value entered in field R2411. A 100 % B 100 % C A0025221  37 A B C Control characteristic of PID controller with basic load dosing PID plus basic load Basic load PID Commissioning If you do not yet have any experience for setting the control parameters, set the values that yield the greatest possible stability in the control circuit. Proceed as follows to optimize the control circuit further: • Increase the control gain Kp until the controlled variable just starts to overshoot. • Reduce Kp slightly again and then reduce the integral action time Tn so that the shortest possible correction time without overshooting is achieved. • To reduce the response time of the controller, also set the derivative action time Tv. Control and fine optimization of the set parameters with a recorder 62 Endress+Hauser Liquisys M CCM223/253 Commissioning A A 2 1 B B A A 4 3 B B A 5 B A0025218  38 A B 1 2 3 4 5 Optimization of settings Tn and Kp Actual value Time Tn too small Tn too large Kp too large Kp too small Optimum setting Actuating signal outputs via contacts (R247 to R2410 and R257 to R2510) Each control contact outputs a cyclical signal whose intensity corresponds to the controller's actuating value. A distinction is made according to the type of signal cycle: • Pulse length modulation The bigger the calculated manipulated variable is, the longer the contact affected remains picked up. The period T can be adjusted between 0.5 and 99 s (field R248 or R258). Outputs with pulse length modulation are used to activate solenoid valves. • Pulse frequency modulation The bigger the calculated manipulated variable is, the higher the switching frequency of the contact affected. The maximum switching frequency 1/T can be set between 60 and 180 min-1 (field R249 or R259). The on-time ton is constant. It depends on the set maximum frequency and is approx. 0.5 s for 60 min-1 and approx. 170 ms for 180 min-1. 170 ms. Outputs with pulse frequency modulation are used to activate directly controlled solenoid dosing pumps. Endress+Hauser 63 Commissioning Liquisys M CCM223/253 A t1 A t2 t1 1 1 0 0 t [s] T T1 t [s] T2 A0025219  39 Signal of a pulse-length modulated controller contact (left) and of a pulse frequency-modulated controller contact (right) Contact: 1 = on, 0 = off T Period Time (s): t1 = ton t2 = toff T1 T2 Impulse period length ( 1/T1 and 1/T2) Constant controller The controller can also control the second analog current output (if provided). You can configure the constant controller in the fields R247 or R257 and O2. Control characteristic for direct and inverse control action You can choose between two control characteristics in the R246 and R256 field: • Direct control action = maximum function • Inverse control action = minimum function Y 100 % A XW – XW Y 100 % B – XW XW A0025222  40 A B XW Y Control characteristic of a proportional controller with direct and inverse control action Direct = maximum function Inverse = minimum function Control deviation Current output signal = controller actuating variable Timer for cleaning function This function includes a simple cleaning option. You can set the time interval after which cleaning should start. Therefore you can only select a constant interval sequence. Other cleaning functions are available for selection in conjunction with the Chemoclean function (device version with four contacts required, see the "Chemoclean function" section). The timer and Chemoclean do not work independently of one another. While one of the two functions is active, the other cannot be started. 64 Endress+Hauser Liquisys M CCM223/253 Commissioning 1 A 0 t 1 B 0 t0 t1 t2 t3 t4 t A0025223  41 Connection between cleaning time, pause time and hold dwell period A Wiper and/or spray cleaning system B Hold function 0 Inactive 1 active t0 Normal operation t1 cleaning start t2-t1Cleaning time t3-t2Clean hold dwell period (0 to 999 s) t4-t3Pause time between two cleaning intervals (1 to 7200 min) Chemoclean function Just like the timer function, Chemoclean can also be used to start a cleaning cycle. However, Chemoclean also gives you the added option of defining various cleaning and rinsing intervals and of dosing cleaning agent. Therefore, it is possible to clean irregularly with different repeat cycles and to separately set the cleaning times with post rinse times. Please note the following: • To use the Chemoclean function the transmitter has to be equipped with a designated relay board (see product structure or chapter "accessories"). • The timer and Chemoclean are mutually dependent. While one of the two functions is active, the other cannot be started. • For the Chemoclean function, the relays 3 (water) and 4 (cleaner) are used. • If the cleaning is prematurely aborted, a post rinse time always follows. • If the setting is "Economy", cleaning only takes place with water. Endress+Hauser 65 Commissioning Liquisys M CCM223/253 1 A 0 1 B 0 1 C 0 t0 t1 t2 t3 t4 t5 A0025216  42 Sequence of a cleaning cycle A Hold function B Water valve is triggered C Cleaning valve is triggered 0 Contact off 1 Contact on t0 Normal operation t1 cleaning start t2-t1Pre-rinse time t3-t2Cleaning time t4-t3Post rinse time t5-t4Hold dwell period 66 Endress+Hauser Liquisys M CCM223/253 Commissioning Three-point step controller With this type of controller, you can control motorized valves for metering chlorine gas. • If the controller activates relay 3, the motorized valve closes. • If the controller activates relay 4, the motorized valve opens. measuring signal C overdosed X underdosed B XW A R4 mark-tospace ratio B R3 mark-tospace ratio C relay output A0025217-EN  43 A B C W X Function of the three-point step controller Measured value is in set point window Measured value is smaller than the set point Measured value is larger than the set point Set point Measured value • Measured value is in set point window (A) Relays 3 and 4 are not activated. The motorized valve does not change. • Measured value is smaller than the set point (B) Not enough chlorine gas is metered. Relay 4 is activated (pulse control). The motorized valve is opened further and the dosage metered is increased. • Measured value is larger than the set point (C) Too much chlorine gas is metered. Relay 3 is activated (pulse control). The motorized valve is closed further and the dosage metered is reduced. Endress+Hauser 67 Commissioning Liquisys M CCM223/253 Functions marked in italics are not supported by the basic device version. Coding Field Range of adjustment (factory settings in bold) Display Info R Relay contact settings RELAY R RELAIS A0009058-EN R1 Select the contact to be configured Rel1 Rel2 Rel3 Rel4 Rel1 R1 Sel.Relay A0009059-EN R2 (1) R211 Configure limit contactor for Cl2/ClO2 Switch function of R2 (1) off or on LC PV= limit contactor Cl2/ClO2 (1) LC °C = limit contactor pH (2) LC °C = limit contactor T (3) PID controller Cl2/ClO2 (4) PID controller pH (5) Timer (6) Clean= Chemoclean (7) Three-point step controller Off On LC PV R2 Sel.Type A0009060-EN Rel3 (water) and Rel4 (cleaner) are only available with the relevant version of the transmitter. If Chemoclean is used as the cleaning method, Rel4 is not available. PV = process value If Rel4 is selected in the R1 field, Clean = Chemoclean cannot be selected. By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. All the settings are retained. off R211 Function A0009067-EN R212 Enter the switch-on point of the contact 20000 ppb 0 to 20000 ppb 20 ppm 0 to 20 ppm 20 (5) mg/l 0 to 20 (5) mg/l Enter the switch-off point of the contact 20000 ppb 0 to 20000 ppb 20 ppm 0 to 20 ppm 20 (5) mg/l 0 to 20 (5) mg/l mg/l 20 R212 On Value Never set the switch-on point and the switch-off point to the same value! (Only the operating mode selected in A1 is displayed.) A0002033-EN R213 mg/l 20 R213 Off Value A0002034-EN 68 Entering a switch-off point selects either a Max contact (switch-off point < switch-on point) or a Min contact (switchoff point > switch-on point), thereby implementing a hysteresis that is constantly required (see "Illustration of the alarm and limit functions" figure). Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field Range of adjustment (factory settings in bold) R214 0s 0 to 2000 s Enter pickup delay Display Info 0 s R214 On Delay A0009070-EN R215 Enter dropout delay 0s 0 to 2000 s 0 s R215 Off Delay A0009071-EN R216 Enter alarm threshold (as absolute value) 20000 ppb 0 to 20000 ppb 20 ppm 0 to 20 ppm 20 (5) mg/l 0 to 20 (5) mg/l mg/l 20 R216 A.Thresh A0002038-EN R217 Display status for limit contactor MAX MIN If the alarm threshold is undershot/overshot, this triggers an alarm with the error message (E067 to E070) and an error current at the transmitter (note alarm delay in field F3). If defined as a Min contact, the alarm threshold must be < switch-off point. Display only MAX R217 LC State A0009073-EN R2 (2) Configure limit contactor for pH or ORP mV LC pH= limit contactor pH LVORP = limit contactor ORP mV LC pH R2 Function A0002025-EN R221 Switch function of R2 (2) off or on Off On off R221 Only for EP version. Measurement is configured for pH or ORP depending on the mode of operation selected in field B1. By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. Any settings made for the limit contactor are not deleted if the function is switched off. Function A0009074-EN R222 Enter the switch- pH 9 on point of the pH 4 to 9 contact 1500 mV 0 to 1500 mV pH 9.00 R222 On Value Never set the switch-on point and the switch-off point to the same value! A0002041-EN Endress+Hauser 69 Commissioning Liquisys M CCM223/253 Coding Field R223 Range of adjustment (factory settings in bold) Enter the switch- pH 9 off point of the pH 4 to 9 contact 1500 mV 0 to 1500 mV Display Info pH 9.00 R223 Off Value A0002042-EN R224 Enter pickup delay 0s 0 to 2000 s Entering a switch-off point selects either a Max contact (switch-off point < switch-on point) or a Min contact (switchoff point > switch-on point), thereby implementing a hysteresis that is constantly required (see "Illustration of the alarm and limit functions" figure). 0 R224 s On Delay A0009077-EN R225 Enter dropout delay 0s 0 to 2000 s 0 R225 s Off Delay A0009078-EN R226 Enter alarm threshold (as absolute value) pH 9 pH 0 to 9 1500 mV 0 to 1500 mV pH 9.00 R226 A.Thresh A0005998-EN R227 Display status for limit contactor MAX MIN Configure limit contactor for temperature LC °C = limit contactor T If the alarm threshold is undershot/overshot, this triggers an alarm with the error message (E067 to E070) and an error current at the transmitter (note alarm delay in field F3). If defined as a Min contact, the alarm threshold must be < switch-off point. Display only MAX R227 LC State A0009080-EN R2 (3) LC ¡C R2 Sel.Type By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. A0009061-EN R231 Switch function of R2 (3) off or on Off On off R231 Any settings made for the limit contactor are not deleted if the function is switched off. Function A0009081-EN R232 Enter switch-on temperature 50 °C 0 to 50 °C °C 50.0 R232 On Value Never set the switch-on point and the switch-off point to the same value! A0006003-EN 70 Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field Range of adjustment (factory settings in bold) R233 50 °C 0 to 50 °C Enter switch-off temperature Display Info ¡C 50.0 R233 Off Value A0002049-EN R234 Enter pickup delay 0s 0 to 2000 s Entering a switch-off point selects either a Max contact (switch-off point < switch-on point) or a Min contact (switchoff point > switch-on point), thereby implementing a hysteresis that is constantly required (see "Illustration of the alarm and limit functions" figure). s 0 R234 On Delay A0002050-EN R235 Enter dropout delay 0s 0 to 2000 s s 0 R235 Off Delay A0002051-EN R236 Enter alarm threshold (as absolute value) 50 °C 0 to 50 °C ¡C 50.0 R236 A.Thresh A0002052-EN R237 Display status for limit contactor MAX MIN Configure P(ID) controller for Cl2/ClO2 PIDPV If the alarm threshold is undershot/overshot, this triggers an alarm with the error message (E067 to E070) and an error current at the transmitter (note alarm delay in field F3). If defined as a Min contact, the alarm threshold must be < switch-off point. Display only MAX R237 LC State A0002053-EN R2 (4) PIDPV R2 Function A0002027-EN R241 Switch function of R2 (4) off or on Off On Basic PID+B Enter set point 500 ppb 0 to 20000 ppb 0.5 ppm 0 to 20 ppm 0.5 (0.1) mg/l 0 to 20 (5) mg/l Off R241 Function PV = process value of main measuring parameter By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. On = PID controller Basic = basic load dosing PID+B = PID controller + basic load dosing A0002054-EN R242 mg/l 0.50 R242 Setpoint The set point is the value to be maintained by the control system. Using this control process, this value is restored when an upwards or downwards deviation occurs. A0002057-EN Endress+Hauser 71 Commissioning Liquisys M CCM223/253 Coding Field Range of adjustment (factory settings in bold) R243 1.00 0.01 to 20.00 Enter control gain KP Display Info 1.00 R243 See the "P(ID) controller" section. Kp A0002058-EN R244 Enter integral action time Tn (0.0 = no Icomponent) 0.0 min 0.0 to 999.9 min min 0.0 R244 Time Tn A0002059-EN R245 Enter derivative action time Tv (0.0 = no Dcomponent) 0.0 min 0.0 to 999.9 min min 0.0 R245 Time Tv See the "P(ID) controller" section. With every hold, the Icomponent is set to zero. Although the hold can be deactivated in field S2, this does not apply for Chemoclean and timer! See the "P(ID) controller" section. A0002060-EN R246 Select controller characteristic Inv = inverse (initial setting for sodium hypochlorite Dir = direct inv R246 Direction See the "P(ID) controller" section. This setting is required depending on the desired dosing direction (dosing above or below the set point). A0002061-EN R247 Select pulse length or pulse frequency Len = pulse length Freq = pulse frequency Curr = current output 2 len R247 Oper.Mode A0002062-EN R248 Enter pulse interval 10.0 s 0.5 to 999.9 s s 10.0 R248 PulsePer. Pulse length e.g. for solenoid valve, pulse frequency e.g. for solenoid dosing pump, see the "Actuating signal outputs" section. Curr = current output 2 can only be selected if O2 = Contr. This field only appears if pulse length is selected in R247. If pulse frequency is selected, R248 is skipped and entries continue with R249. A0002063-EN R249 Enter maximum pulse frequency of the adjuster min-1 120 60 to 180 min-1 1/min 120 R249 Max.PFreq This field only appears if pulse frequency is selected in R247. If pulse length is selected, R249 is skipped and entries continue with R2410. A0002064-EN R2410 Enter minimum switch-on time tON 0.3 s 0.1 to 5.0 s s 0.3 R2410 Min.PTime This field only appears if pulse length is selected in R247. A0002055-EN 72 Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field Range of adjustment (factory settings in bold) R2411 0% 0 to 40 % Enter basic load Display Info % 0 R2411 BasicLoad A0002056-EN R2 (5) Configure P(ID) PIDpH controller for pH PIDpH R2 Function When you select the basic load, you enter the desired dosing quantity. 100% basic load would correspond to: • Constantly on if R247 = len • Fmax if R247 = freq (field R249) • 20 mA if R247 = curr By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. A0002028-EN R251 Switch function of R2 (5) off or on Off On Basic PID+B Off R251 Function On = PID controller Basic = basic load dosing PID+B = PID controller + basic load dosing A0002084-EN R252 Enter set point pH 7.20 pH 4 to 9 pH 7.20 R252 Setpoint The set point is the value to be maintained by the control system. Using this control process, this value is restored when an upwards or downwards deviation occurs. A0002087-EN R253 Enter control gain KP 1.00 0.01 to 100.00 See the "P(ID) controller" section 1.00 R253 Kp A0002088-EN R254 Enter integral action time Tn (0.0 = no Icomponent) 0.0 min 0.0 to 999.9 min min 0.0 R254 Time Tn A0002089-EN R255 Enter derivative action time Tv (0.0 = no Dcomponent) 0.0 min 0.0 to 999.9 min See the "P(ID) controller" section With every hold, the Icomponent is set to zero. Although the hold can be deactivated in field S2, this does not apply for Chemoclean and timer! See the "P(ID) controller" section min 0.0 R255 Time Tv A0002090-EN R256 Select controller characteristic Inv = inverse Dir = direct (Initial setting for acid) dir R256 Direction See the "P(ID) controller" section This setting is required depending on the desired dosing direction (dosing above or below the set point). A0002091-EN Endress+Hauser 73 Commissioning Liquisys M CCM223/253 Coding Field Range of adjustment (factory settings in bold) R257 Len = pulse length Freq = pulse frequency Curr = current output 2 Select pulse length or pulse frequency Display Info len R257 Oper.Mode Pulse length e.g. for solenoid valve Pulse frequency e.g. for solenoid dosing pump Curr = current output 2 can only be selected if O2 = Contr. A0002092-EN R258 Enter pulse interval 10.0 s 0.5 to 999.9 s Enter maximum pulse frequency of the adjuster 120 min-1 60 to 180 min-1 Enter minimum switch-on time tON 0.3 s 0.1 to 5.0 s Enter basic load 0% 0 to 40 % s 10.0 R258 PulsePer. This field only appears if pulse length is selected in R257. If pulse frequency is selected, R258 is skipped and entries continue with R259. A0002093-EN R259 1/min 120 R259 Max.PFreq This field only appears if pulse length is selected in R257. If pulse length is selected, R259 is skipped and entries continue with R2510. A0002094-EN R2510 s 0.3 R2510 Min.PTime This field only appears if pulse length is selected in R257. A0002085-EN R2511 % 0 R2511 BasicLoad A0002086-EN R2 (6) Configure cleaning function (timer) Timer (6) Timer R2 Sel.Type A0009063-EN R261 Switch function of R2 (6) off or on Off On This field only appears for the EP version. When you select the basic load, you enter the desired dosing quantity. 100% basic load would correspond to: • Constantly on if R257 = len • Fmax if R257 = freq (field R259) • 20mA if R257 = curr Only one cleaning agent (generally water) is used for the cleaning. By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. Off R261 Function A0002095-EN R262 Enter rinsing/ cleaning time 30 s 0 to 999 s s 30 R262 RinseTime Settings for hold and relay are active for this time. A0002096-EN 74 Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field R263 Range of adjustment (factory settings in bold) Enter pause time 360 min 1 to 7200 min Display Info min 360 R263 PauseTime The pause time is the time between two cleaning cycles (see the "Timer for cleaning function" section). A0002097-EN R264 Enter minimum pause time 120 min 1 to 3600 min min 120 R264 Min.Pause The minimum pause time prevents constant cleaning if a cleaning trigger is pending. A0002098-EN R2 (7) R271 Configure Clean= cleaning with Chemoclean (7) Chemoclean (for version with four contacts, Chemoclean option and contacts 3 and 4 assigned) Switch function of R2 (7) off or on Off On Select type of start pulse Int = internal (timecontrolled) Ext = external (digital input 2) I+ext = internal + external I+stp = internal, suppressed by external Clean R2 Sel.Type A0009064-EN See the "Chemoclean function" section. By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. Off R271 Function A0002099-EN R272 R273 Enter pre-rinse time 20 s 0 to 999 s int R272 CleanTrig No real time clock is available. External suppression is required for irregular time intervals (e.g. weekends). A0002100-EN s 20 R273 PreRinse Rinsing is performed with water. A0002101-EN R274 Enter cleaning time 10 s 0 to 999 s s 10 R274 CleanTime Cleaning is performed with cleaning agent and water. A0002102-EN R275 Enter post rinse time 20 s 0 to 999 s s 20 R275 PostRinse Rinsing is performed with water. A0002103-EN Endress+Hauser 75 Commissioning Liquisys M CCM223/253 Coding Field Range of adjustment (factory settings in bold) R276 0 0 to 5 Enter number of repeat cycles Display Info R273 to R275 is repeated. 0 R276 Rep. Rate A0002104-EN R277 Enter pause time 360 min 1 to 7200 min min 360 R277 PauseTime The pause time is the time between two cleaning cycles (see the "Chemoclean function" section). A0002105-EN R278 Enter minimum pause time 120 min 1 to R277 min 120 R278 Min.Pause The minimum pause time prevents constant cleaning if an external cleaning start is pending. A0002106-EN R279 Enter number of 0 cleaning cycles 0 to 9 without cleaning agent (economy function) 0 R279 EconomyCl After cleaning with cleaner, up to 9 cleaning sessions can be carried out with water only until the next cleaning session with cleaner takes place. A0002107-EN R2 (8) Configure threepoint step controller for Cl2/ClO2 3 PSt (8) 3PSt R2 Function Only with relays 3 and 4.. By confirming with ENTER, another relay function already switched on is switched off and its settings are reset to the factory settings. A0002031-EN R281 Switch function of R2 (8) off or on Off On Off R281 Function A0002108-EN R282 Enter set point 500 ppb 0 to 20000 ppb 0.5 ppm 0 to 20 ppm 0.5 (0.1) mg/l 0 to 20 (5) mg/l mg/l 0.50 R282 Setpoint The set point is the value to be maintained by the control system. Using this control process, this value is restored when an upwards or downwards deviation occurs. A0002109-EN R283 Enter control gain KP 1.00 0.10 to 100.00 See the "P(ID) controller" section 1.00 R283 Kp A0002110-EN R284 Enter integral action time Tn 0.0 min 0.0 to 999.9 min See the "P(ID) controller" section min 0.0 R284 Time Tn A0002111-EN 76 Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field Range of adjustment (factory settings in bold) R285 0.3 s 0.1 to 5.0 s Enter minimum switch-on time tON Display Info s 0.3 R285 Min.PTime A0002112-EN R286 Enter motor run time 60 s 10 to 999 s Enter neutral zone 10 % 0 to 40 % s 60 R286 MotorTime Motor run time from "fully closed" state to "fully open" state. A0002113-EN R287 % 10 R287 NeutrZone A0002114-EN 7.4.8 Service Coding Field Range of adjustment (factory settings in bold) Display Info S Service function settings. SERVICE function group S SERVICE A0008408-EN S1 Select language ENG = English GER = German FRA = French ITA = Italian NL = Dutch ESP = Spanish ENG S1 The option selected only applies for the faultsignaling contact, not for the error current. Language A0008409-EN S2 S3 Configure a hold S+C = hold during configuration and calibration Cal = hold during calibration Setup = hold during configuration None = no hold Manual hold Off On S+C S = setup C = calibration S2 Auto HOLD A0008413-EN off S3 The setting is retained even in the event of a power failure. Man. HOLD A0008414-EN Endress+Hauser 77 Commissioning Liquisys M CCM223/253 Coding Field S4 Range of adjustment (factory settings in bold) Display Info Enter hold dwell 10 s period 0 to 999 s 10 s S4 Cont.Time A0008415-EN S5 Enter SW upgrade release code (Plus Package) 0000 0000 to 9999 0000 S5 PlusCode A0008416-EN S6 Enter SW upgrade release code for Chemoclean 0000 0000 to 9999 0000 S6 CleanCode A0008417-EN S7 Order number is displayed The code can be found on the nameplate. If an incorrect code is entered, you are taken back to the measurement menu. The number is edited with the PLUS or MINUS key and confirmed with the ENTER key. "1" is displayed if the code is active. The code can be found on the nameplate. If an incorrect code is entered, you are taken back to the measurement menu. The number is edited with the PLUS or MINUS key and confirmed with the ENTER key. "1" is displayed if the code is active. If the device is upgraded, the order code is changed automatically. order S7 EK0005 A0006005 S8 Serial number is displayed SerNo S8 12345678 A0008420-EN S9 Reset the device to the basic settings No Sens = sensor data Facty = factory settings no S9 S.Default Sens = last calibration is deleted and is reset to factory setting. Facty = all data (apart from A1 and S1) are deleted and reset to the factory setting! A0008421-EN S10 Perform device test No Displ = display test no S10 Test A0008410-EN 78 Endress+Hauser Liquisys M CCM223/253 Commissioning 7.4.9 E+H Service Coding Field Range of adjustment (factory settings in bold) Display Info E Information on the device version E+H SERVICE function group E E+H SERV A0007857-EN E1 Select module Contr = controller (central module) (1) Trans = transmitter (2) Main = power unit (3) Rel = relay module (4) Sens = sensor (5) Contr E1 Select A0007858-EN E111 E121 E131 E141 E151 Software version is displayed E112 E122 E132 E142 E152 Hardware version is displayed xx.xx E111 SW-Vers. If E1 = contr: device software If E1 = trans, main, rel: module firmware If E1 = sens: sensor software A0007859-EN Info display xx.xx E112 HW-Vers. A0007861-EN E113 E123 E133 E143 E153 Serial number is displayed Info display SerNo E113 12345678 A0007860-EN E114 E124 E134 E144 E154 Module ID is displayed Info display LSG E114 Modul-ID A0007862-EN Endress+Hauser 79 Commissioning Liquisys M CCM223/253 7.4.10 Interfaces Coding Field Range of adjustment (factory settings in bold) Display Info I INTERFACE function group I Communication settings (only for HART or PROFIBUS device version). INTERFACE A0007863-EN I1 Enter bus address Address HART: 0 to 15 or PROFIBUS: 0 to 126 126 I1 Address A0007864-EN I2 The tag name is displayed Each address may only be assigned once in a network. If a device address ≠ 0 is selected for a HART device, the current output is automatically set to 4 mA and the device prepares for multi-drop operation. Tag I2 @@@@@@@@ A0007865-EN 7.4.11 Communication For devices with a communication interface, please also refer to the separate Operating Instructions BA00208C/07/EN (HART®) or BA00209C/07/DE (PROFIBUS®). 80 Endress+Hauser Liquisys M CCM223/253 Commissioning 7.5 Calibration Use the CAL key to access the calibration function group. Use this function group to calibrate the transmitter. When calibrating the "Free chlorine" measurement mode, make sure to pay attention to the pH value and the temperature of the medium. The limit values are provided in the following table: Sensor pHmin pHmax Tmin Tmax CCS140 4 8 10 °C (50 °F) 45 °C (113 °F) CCS141 4 8.2 2 °C (36 °F) 45 °C (113 °F) CCS240 - - 2 °C (36 °F) 45 °C (113 °F) CCS241 - - 2 °C (36 °F) 45 °C (113 °F) CCS120 5.5 9.5 5 °C (41 °F) 45 °C (113 °F) Please note the following: • You require a photometer, e.g. PF-3 (see "Accessories") to calibrate chlorine and chlorine dioxide. A photometer with a higher accuracy rating and lower detection limit is required for calibration in the trace range (<0.1 mg/l). • If the calibration is aborted by simultaneously pressing the PLUS and MINUS keys (return to C15, C29 or C35), or if the calibration is incorrect, the original calibration data are used again. A calibration error is indicated by “ERR” and the sensor symbol flashes on the display. Repeat calibration! • For each calibration, the device automatically switches to hold (factory setting). • On completion of the calibration, the device returns to the measurement mode. The "hold" symbol appears on the display during the hold dwell period (field S4). Coding Field Range of adjustment (factory settings in bold) C(1) Cl2 ClO2 CALIBRATION function group: Calibration Cl2/ ClO2 Display Info Cl2 C CALIBRAT Cl2 if A1 = 120/140/141/963 ClO2 if A1 = 240/241 A0006351-EN C11 Enter DPD calibration value Value of last calibration mg/l 0.50 C11 DPD value Minimum values for the calibration: • For CCS120/140/240 and sensor 963: 0.05 mg/l • For CCS141/241: 0.01 mg/l A0002420-EN C12 Zero point calibration? No Yes no C12 Zero cal A0002421-EN Endress+Hauser Only if A1 = 963 Zero point calibration: 1. Pass unchlorinated water through the assembly. 2. Wait for 10 minutes. 3. Accept by selecting YES and pressing ENTER 81 Commissioning Liquisys M CCM223/253 Coding Field Range of adjustment (factory settings in bold) C13 100 % Minimum 25% (3%) Maximum 500% Slope is displayed Display Info % 100 C13 Slope A0002422-EN C14 Calibration status is displayed o. k. E xxx Minimum permitted slope: • For CCS140/141 with pH compensation and for CCS240/241: 25% • For CCS120/140/141 without pH compensation and for sensor 963: 3% o.k. C14 Status A0002423-EN C15 Store calibration result Yes No New yes C15 Store If C14 = E xxx, then only No or New. If New, then return to C. If Yes/No, then return to "Measurement". A0002424-EN C(2) pH CALIBRATION function group: pH calibration pH C CALIBRAT A0002418-EN C21 Calibration status is displayed 25 °C 0 to 50 °C ¡C 25.0 C21 MTC-Temp This field is only for recording the calibration temperature. An entry must not be made. A0002425-EN C22 Enter pH value of the first buffer solution Buffer value of the last calibration pH 3.50 to 9.50 pH 7.00 C22 Buffer 1 Press the ENTER key to display the current measured value. Press the ENTER key again as soon as the measured value has adjusted to the buffer value. A0002427-EN C23 Calibration is performed pH 7.00 C23 Buffer 1 Stability check: The value is accepted if the stability level is ≤pH ±0.05 for more than 10 seconds. A0002428-EN C24 Enter pH value of the second buffer solution Buffer value of the last calibration pH 3.50 to 9.50 pH 4.00 C24 Buffer 2 Buffer 2 must have a different value to buffer 1. A plausibility check is performed. Press the ENTER key and proceed as in field C22. A0002429-EN C25 Calibration is performed pH 4.00 C25 Buffer 2 Stability check: The value is accepted if the stability level is ≤pH ±0.05 for more than 10 seconds. A0002430-EN 82 Endress+Hauser Liquisys M CCM223/253 Commissioning Coding Field Range of adjustment (factory settings in bold) C26 59.16 mV/pH 38.00 to 65.00 mV/pH Slope is displayed Display Info mV/pH 59.16 C26 Slope A0002431-EN C27 Zero point is displayed pH 7.00 pH 5.00 to 9.00 pH 7.00 C27 Zero A0002432-EN C28 Calibration status is displayed o. k. E xxx o.k. C28 Status A0002452-EN C29 Store calibration result? Yes No New yes C29 Store If C28 = E xxx, then only No or New. If New, then return to C. If Yes/No, then return to "Measurement". A0002434-EN C(3) ORPmV CALIBRATION function group: ORP mV calibration ORPmV C CALIBRAT A0002419-EN C31 Enter the value of the ORP buffer Buffer value of the last calibration 0 to 1500 mV mV 225 C31 mV Buffer Press the ENTER key to display the current measured value. Press the ENTER key again as soon as the measured value has adjusted to the buffer value. A0002435-EN C32 Calibration is performed mV 225 C32 CAL mV Stability check: The value is accepted if the stability level is ≤pH ± 1 mV for more than 10 seconds. A0002436-EN C33 Zero point is displayed -100 to +100 mV mV 0 C33 Zero A0002437-EN C34 Calibration status is displayed o. k. E xxx o.k. C34 Status A0002438-EN Endress+Hauser 83 Commissioning Liquisys M CCM223/253 Coding Field Range of adjustment (factory settings in bold) C35 Yes No New Store calibration result? Display Info yes C35 Store If C34 = E xxx, then only No or New. If New, then return to C. If Yes/No, then return to "Measurement". A0002439-EN C(4) Zero point CALIBRATION function group: Zero point CCS120 Zero C CALIBRAT Zero point calibration for CCS120 A0006376-EN C12 Zero point calibration? No Yes no C12 Zero cal A0002421-EN C14 Calibration status is displayed o. k. E xxx Only if A1 = 120 Zero point calibration: 1. Pass unchlorinated water through the assembly. 2. Wait for 10 minutes. 3. Accept by selecting YES and pressing ENTER o.k. C14 Status A0002423-EN C15 Store calibration result? Yes No New yes C15 Store If C14 = E xxx, then only No or New. If New, then return to C. If Yes/No, then return to "Measurement". A0002424-EN 84 Endress+Hauser Liquisys M CCM223/253 Diagnostics and troubleshooting 8 Diagnostics and troubleshooting 8.1 Trouble shooting instructions The transmitter continuously monitors its functions itself. If an error occurs which the device recognizes, this is indicated on the display. The error number is shown below the display of the main measured value. If more than one error occurs, you can call these up with the MINUS key. Refer to the "System error messages" table for the possible error numbers and remedial measures. Should a malfunction occur without any transmitter error message, please refer to the "Process-specific errors" or the "Device-specific errors" tables to localize and rectify the error. These tables provide you with additional information on any spare parts required. 8.2 System error messages You can display and select the error messages with the MINUS key. Error No. E001 E002 E003 E004 E007 E010 E032 E033 Endress+Hauser Display Tests/remedial action Alarm contact Error current Autom. cleaning start PROFIBU S Status Facty Facty Facty PV 1) User User User Temp • Switch off device and switch it on again. • Load software compatible with Device not calibrated, hardware calibration data invalid, no user data or • Load measurementparameter specific user data invalid device software. (EEPROM error), • If the error persists, device software not send in the device for suitable for hardware repair to your local (controller) sales center or replace the device. Yes No X 0C X 0C X 0C X 0C Download error Invalid configuration. Repeat download. Yes X 0C X 0C Load software compatible with hardware Load measurementparameter specific device software. Yes X 0C X 0C X 0C X 0C No 80 EEPROM memory error Device software version not compatible with module hardware version Transmitter malfunction, device software not compatible with transmitter version Yes Yes Temperature sensor defective, not connected or shortcircuited (measurement continues with 25 °C) Check temperature sensor Yes and connections; check the measuring device and measuring cable with a temperature simulator if necessary. Upper or lower pH slope range exceeded No Repeat calibration and replace buffer solution; if necessary, replace sensor pH value zero point too and check the device and low or too high No No No No No No 0C No No X 80 X 80 X 80 85 Diagnostics and troubleshooting Error No. E034 E035 E038 E041 E042 E043 E044 E045 E055 E056 E057 E058 E059 86 Liquisys M CCM223/253 Display ORP offset range exceeded or below range Tests/remedial action measuring cable with a simulator. Alarm contact Error current Autom. cleaning start PROFIBU S Status Facty Facty Facty PV 1) User User User Temp X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 No 44 No Sensor 963 zero point signal outside permitted range • Service the sensor (in accordance with sensor manual). • Check connections. • Check activated carbon filter. No Cl sensor signal outside permitted range during slope calibration • Service the sensor (in accordance with sensor manual). • Check connections. • Check DPD measuring device. • Do not use organic chlorination agent. No Calculation of calibration parameters aborted Repeat calibration and replace buffer solution; replace sensor if necessary, check device and measuring cable. No Distance between buffer value and zero point (pH7) too small (single-point calibration) For slope calibration, use a buffer solution which has at least a distance of ΔpH = 2 to the electrode zero point. No Distance between buffer 1 and buffer 2 calibration values too small (two-point calibration) Use buffer solutions which differ by at least Δ pH = 2. No Stability requirement not met during calibration Repeat calibration and replace buffer solution; if necessary, replace sensor and check the device and measuring cable with a simulator. No Check measurement and connections; if necessary, check device and measuring cable with a simulator. Yes Calibration aborted Lower Cl/ClO2 measuring range exceeded Lower pH/mV measuring range exceeded No No No No No No No No No No 80 Yes No No 44 80 Upper Cl/ClO2 measuring range exceeded Yes Upper pH/mV measuring range exceeded Yes Below temperature measuring range Yes No No 44 80 No No 44 80 No No 80 44 Endress+Hauser Liquisys M CCM223/253 Diagnostics and troubleshooting Error No. E061 E063 E064 E065 E066 E067 E068 E069 E070 E080 E081 E085 E100 E101 E102 E106 E116 E152 Endress+Hauser Display Tests/remedial action Temperature measuring range exceeded Below current output range 1 Alarm contact Error current Autom. cleaning start PROFIBU S Status Facty Facty Facty PV 1) User User User Temp Yes No No 80 44 Check measured value and current assignment Yes Yes Below current output range 2 Yes Current output range 2 exceeded Yes Check configuration Yes Set point exceeded limit contactor 4 Yes Current output 1 range Increase range in "Current too small outputs" menu. Yes Current output 2 range too small Yes No No 80 No No 80 No No 80 No No 80 80 No No 80 80 No No 80 80 If the current range "0 to 20 mA" was selected in field O311, the error current may not be set to "2.4 mA". Current simulation active Yes No No No No Switch off service function No or switch device off and then on again. No No No Wait for download to finish. No Repeat download. Yes • Check and service the sensor and connection, and replace if necessary. X 80 X 80 X 80 X 80 No 80 80 Yes Manual mode active Measuring signal of Cl/ClO2 parameter delayed or frozen 80 80 Yes Download error No 80 Set point exceeded limit contactor 3 Download active No 80 Yes Service function active 80 80 Set point exceeded limit contactor 2 Incorrect setting for error current No 80 Current output range 1 exceeded Set point exceeded limit contactor 1 No No No No No X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 80 X 0C X 0C No 44 44 87 Diagnostics and troubleshooting Error No. E153 E154 E155 E156 E157 E158 E159 E160 E161 E162 E163 88 Liquisys M CCM223/253 Display Tests/remedial action Alarm contact Error current Autom. cleaning start PROFIBU S Status Facty Facty Facty PV 1) User User User Temp No 44 Measuring signal of pH/mV parameter delayed or frozen • Check whether medium No has really changed or not. No Cl/ClO2 below lower alarm threshold for period exceeding alarm delay • Perform manual comparison measurement if necessary. • Service the sensor (in accordance with sensor manual). • Recalibrate the measuring system. • Check the flow. • Check the chemical supply. • Check dosing devices. No Cl/ClO2 above upper alarm threshold for period exceeding alarm delay Actual Cl/ClO2 value undershoots alarm threshold for longer than the set permissible maximum period Yes Yes X No No X X Yes No No X X Yes pH/mV below lower alarm threshold for period exceeding alarm delay Yes pH/mV above upper alarm threshold for period exceeding alarm delay Yes Actual pH/mV value undershoots alarm threshold (CC setpoint) for longer than the set permissible maximum period Yes Actual pH/mV value exceeds alarm threshold (CC setpoint) for longer than the set permissible maximum period Yes Uncompensated chlorine value too imprecise since pH value > 9 No X Actual Cl/ClO2 value exceeds alarm threshold for longer than the set permissible maximum period Dosage stop 44 No No X X No No X X No No X X No No X X No No X X Check settings in the CURRENT INPUT and CHECK function groups. Yes Check pH value and adjust Yes according to system requirements. If pH values > 9, the disinfection effect is questionable since the chlorine now exists as the less effective OCl-. No No X X No No X X Endress+Hauser Liquisys M CCM223/253 Diagnostics and troubleshooting Error No. E170 E171 E172 E173 Display Tests/remedial action Alarm contact Error current Autom. cleaning start PROFIBU S Status Facty Facty Facty PV 1) User User User Temp No No X Flow through assembly too low or zero Restore flow. Check medium pipe. Yes Flow in main stream too low or zero Restore flow. Yes X No No X X Switch-off limit for Check process variables at Yes current input exceeded sending measuring device. Change range assignment Current input < 4 mA if necessary. Yes No No X X No No X X E174 Current input > 20 mA Yes No No X X 1) 8.3 PV = process variable, primary value Process-specific errors Use the following table to localize and rectify any errors occurring. Error Possible cause Tests/remedial action Tools, spare parts Replace fuse Fine-wire fuse, M 250 V / 3.15 A No power supply Establish power supply Check with voltmeter Automatic controller switch-off due to alarm Determine cause according to error code Exxx and eliminate. Current output simulation End the simulation Chlorine measurement: Slope too low Sensor was in chlorinefree water or in air. Short conditioning over (not in!) Chlorine bleach / chlorine chlorine bleach, wait for parent solution conditioning time in water before calibration. No match with DPD control measurement Measurement takes place Measure chlorine value pHwithout pH compensation, compensated while DPD measurement is always buffered to pH 6.3. Select CCM223/253 with ES option (manual compensation) or EP (automatic compensation). DPD measured value much too high Organic chlorination agent Use free (gaseous) chlorine or used (may also be used chlorine from inorganic chlorine only at times or for shock compounds. chlorination). In this case, no correlation between actual free chlorine, DPD measurement and amperometric measurement. DPD value too high by a factor of up to 5. If organic chlorination agent was used previously, the entire system must be evacuated and carefully cleaned! Chlorine value too high Membrane defective Replace membrane cap. Replacement cartridges CCY 14-WP Polarization not complete Wait for polarization time to finish Be patient Foreign oxidizing agent Analyze medium Detailed knowledge of the process No device function Device fuse defective Display flashes Endress+Hauser 89 Diagnostics and troubleshooting Error Chlorine value too low Chlorine value wrong/cannot be calibrated; zero current too large pH/mV measurement: Measuring chain zero-point cannot be adjusted No or slow change of readings Measuring chain slope not adjustable/ slope too low Measuring chain slope not adjustable/ No slope Liquisys M CCM223/253 Possible cause Tests/remedial action Tools, spare parts Shunt in chlorine sensor Replace sensor Replacement sensor Measuring chamber not closed Refill and screw closed carefully Electrolyte Air cushion outside in front of membrane Remove air bubble, possibly select better installation position Air cushion inside membrane Refill and screw closed so that it Electrolyte is bubble-free Wrong polarization voltage Measure polarization voltage, replace MKC1 module if necessary. Wrong sensor type selected Check sensor selection Contaminated reference system Test with new sensor pH/mV sensor Membrane clogged Clean or grind membranes (not with TEFLON® membranes) HCl 3%, needle file (only file in one direction); new sensor Measuring line open Short-circuit pH input and connect to PM -> reading pH 7 Asymmetric sensor voltage too high Clean junction or test with another sensor HCl 3%, needle file (only file in one direction); new sensor Potential matching of Liquisys -> medium incorrect Always connect CCM223/253 symmetrically with PM. Wiring diagrams Sensor fouled Clean sensor Cleaning agent Sensor old Replace sensor New sensor Sensor defective (reference lead) Replace sensor New sensor Connection not at high impedance (moisture, dirt) Check cable, plug connector and pH simulator, insulation junction boxes tester Device input defective pH measurement directly at device pH simulator Sensor old Replace sensor pH sensor Hair-line crack in the glass Replace sensor membrane pH sensor Connection not at high impedance Constant, incorrect Sensor does not immerse measured value properly or protection cap not removed Check cable, plug connector and pH simulator, insulation junction boxes tester Check installation position, remove protection cap Air pockets in assembly Check assembly and installation position Grounding short at or in device Perform test measurement in insulated vessel, perform with buffer solution if required. Hair-line crack in the glass Replace sensor membrane 90 DVM (+) at S or 90, DVM (-) at 91 CCS140/141: -20 mV CCS240/241: +120 mV Plastic vessel, buffer solutions pH sensor Endress+Hauser Liquisys M CCM223/253 Diagnostics and troubleshooting Error Incorrect temperature value Incorrect pH measured value in the process Fluctuations in measured value Tests/remedial action Tools, spare parts Device in impermissible operating condition (does not respond when key pressed) Disconnect line voltage for approx. 10 seconds Possibly EMC problem: if problem persists, check grounding and wire routing. Incorrect sensor connection Check connections using wiring Wiring diagram in diagram. Three-wire connection "Electrical connection" always required section Sensor or measuring cable defective Check sensor and cable Flow too high Reduce flow or measure in a bypass. Potential in medium Possibly ground with or/at PM pin (connect PA/PM with PE). Problem mainly occurs in plastic lines. Sensor fouling or buildup on sensor Clean sensor For heavily contaminated media: use spray cleaning Ohmmeter Interference on measuring Connect cable shield as per cable wiring diagram See the "Electrical connection" section Interference on signal output cable Check cable routing, possibly route cable separately Route signal output and measuring input lines separately Interference potential in medium Eliminate source of interference or ground medium as close as possible to sensor. No potential matching on symmetrical input Connect PM pin in assembly to device terminal PA/PM. Controller or timer No relay module available cannot be activated Install LSR1-2 or LSR1-4 module Controller/limit contact does not work Controller switched off Activate controller See fields R2xx Controller in operating mode "Manual off" Select "Auto" or "Manual on" mode Keyboard, REL key Pickup delay setting too long Switch off or shorten pickup delay time See fields R2xx "Hold" function active “Auto hold” for calibration, “Hold” input activated; “Hold” active via keyboard See fields S2 to S4 Controller in operating mode "Manual on" Select "Auto" or "Manual off" mode Keyboard, REL and AUTO keys Dropout delay setting too long Shorten dropout delay time See fields R2xx Control loop interruption Check measured value, current output value, actuators, chemical supply Cable disconnected or short-circuited Disconnect cable and measure directly at device Output defective See the "Device-specific errors" section Fixed current output signal Current simulation active Switch off simulation. See field O3 Impermissible operating state of processor system Disconnect line voltage for approx. 10 seconds Possibly EMC problem: if problem persists, check grounding and wire routing. Incorrect current output signal Incorrect current assignment Check current assignment: 0– 20 mA or 4–20 mA? Field O311 Controller/limit contact works continuously No current output signal Endress+Hauser Possible cause mA meter 0–20 mA 91 Diagnostics and troubleshooting Error Current output table is not accepted Liquisys M CCM223/253 Possible cause Tests/remedial action Tools, spare parts Total load in the current loop too high (> 500 Ω) Disconnect output and measure directly at device mA meter for 0–20 mA DC EMC (interference coupling) Disconnect both output cables and measure directly at device Use shielded cables, ground shields at both ends, where necessary route cable in another cable duct Value interval too small Select practical intervals No output signal Device does not have a for temperature or second current output pH/mV Check version using nameplate, if necessary replace the LSCHx1 module LSCH-x2 module, see the "Spare parts" section Device with PROFIBUS-PA PA device has no current output! Chemoclean function not available No relay module (LSR1-x) installed or only LSR1-2 available Install LSR1-4 module. Chemoclean is enabled using the release code supplied by the manufacturer in the Chemoclean retrofit kit. Plus Package functions not available Plus Package not enabled • For Plus Package retrofit: (enable by entering a code code is supplied by E+H → which depends on the enter this code. serial number and which is • After replacing a defective supplied by E+H when a LSCH/LSCP module: first Plus Package is ordered) enter device serial number manually (see nameplate), then enter the existing code number. No HART communication No HART central module Verify using nameplate: HART = Upgrade to LSCH-H1 / -H2 -xxx5xx and -xxx6xx No or incorrect DD (device description) For further information, see BA00208C/07/EN, "HART field communication with Liquisys CxM223/253” HART interface missing LSR1-4 module, see the "Spare parts" section For a detailed description, see the "Replacement of central module" section. Load too small (must be > 230 Ω) HART receiver (e.g. FXA 191) not connected via load but via power supply Incorrect device address (addr. = 0 for single operation, addr. > 0 for multidrop operation) Line capacitance too high Interference on line No PROFIBUS communication Several devices set to same Assign addresses correctly address No communication possible if several devices set to the same address No PA/DP central module Verify using the nameplate: PA = -xxx3xx /DP = xxx4xx Upgrade to LSCP module, see the "Spare parts" section Incorrect device software version (without PROFIBUS) For further information, see BA00209C/07/EN "PROFIBUS PA/DP - Field communication for Liquisys CxM223/253". Information about PROFIBUS configuration is provided in Technical Information TI00260F, while detailed information about instrumentation and accessories is provided in Operating Instructions BA00198F With Commuwin (CW) II: CW II version and device software version incompatible No or incorrect DD/DLL 92 Endress+Hauser Liquisys M CCM223/253 Diagnostics and troubleshooting Error Possible cause Tests/remedial action Tools, spare parts Incorrect baud rate setting for segment coupler in DPV-1 server Bus user (master) has wrong address or address assigned twice Bus user (slave) has wrong address Bus line not terminated Line problems (too long, cross-section too small, not shielded, shield not grounded, wires not twisted) Bus voltage too low (Bus voltage typ. 24 V DC for non-Ex) 8.4 The voltage at the device's PA/DP connector must be at least 9 V Device-specific errors The following table helps you during the diagnosis and points to any spare parts required. Depending on the degree of difficulty and the measuring equipment present, diagnosis is carried out by: • Trained operator personnel • The user's trained electrical technicians • Company responsible for system installation/operation • Endress+Hauser Service Information on the exact spare part designations and on how to install these parts can be found in the "Spare parts" section. Endress+Hauser Error Possible cause Tests/remedial action Execution, tools, spare parts Device cannot be operated, display value 9999 Operation locked Press CAL and MINUS keys simultaneously. See the "Key functions" section Display dark, no light-emitting diode active No line voltage Check whether line voltage is present Electrical technician / e.g. multimeter Supply voltage wrong/too low Compare actual line voltage and nameplate data User (data for energy supply company or multimeter) Connection faulty • Terminal not tightened • Insulation jammed • Wrong terminals used Electrical technician Device fuse defective Compare line voltage and the nameplate data and replace fuse Electrical technician/suitable fuse; see exploded drawing in the the "Spare parts" section Power unit defective Replace power unit, note version Onsite diagnosis by Endress +Hauser Service, test module necessary Central module defective Replace central module, note version Onsite diagnosis by Endress +Hauser Service, test module necessary Field device: ribbon cable loose or defective Check ribbon cable, replace if necessary See the "Spare parts" section 93 Diagnostics and troubleshooting Error Liquisys M CCM223/253 Possible cause Tests/remedial action Execution, tools, spare parts Display dark, light- Central module defective emitting diode (module: LSCH/LSCP) active Replace central module, note version Onsite diagnosis by Endress +Hauser Service, test module necessary Values appear on display but: • Display does not change and / or • Device cannot be operated Device or module in device not correctly mounted Panel-mounted device: reinstall Perform with the aid of the insert. installation drawings in the Field device: remount display the "Spare parts" section module Impermissible operating system condition Disconnect line voltage for approx. 10 seconds Possibly Possible EMC problem: if this persists, check the installation or have checked by Endress+Hauser Service Device gets hot Voltage wrong/too high Compare line voltage and nameplate data User, electrical technician Power unit defective Replace power unit Diagnosis only by Endress +Hauser Service Cl/ClO2 measured value and/or temperature measured value incorrect Transmitter module defective (module: MKIC), please first carry out tests and take measures as per the "Process-specific errors" section Measuring input test: • Chlorine input open = display 0.00 mg/l • 10 kΩ resistance at terminals 11 + 12 = display 25 °C If test negative: replace module (note version) Perform with the aid of the exploded drawings in the "Spare parts" section. Current output, incorrect current value Incorrect adjustment Check with integrated current simulation, connect mA meter directly to current output. If simulation value incorrect: adjustment in factory or new LSCH module required. If simulation value correct: check current loop for load and shunts. Load too large Shunt / short to ground in current loop Incorrect mode of operation Check whether 0–20 mA or 4– 20 mA is selected. No current output signal Current output stage defective (only for LSCH module; LSCP has no current output) Check with integrated current simulation, connect mA meter directly to current output If test negative: Replace central module (note version) Additional relays not working Field device: ribbon cable loose or defective Check ribbon cable seating, replace cable if required. See the "Spare parts" section Only 2 additional relays can be triggered LSR1-2 relay module with 2 relays is installed Upgrade to LSR1-4 with 4 relays. User or Endress+Hauser Service Additional functions (Plus Package) missing No or incorrect release code used If retrofitting: check whether the correct serial number was quoted when ordering the Plus Package. Handled by Endress+Hauser Sales Incorrect device serial number saved in LSCH/ LSCP module Check whether serial number on the nameplate matches SNR in LSCH/ LSCP (field S 8). The serial number of the device is definitive for the Plus Package. Replacement modules LSCH or LSCP have the device serial number 0000 when they leave the factory. The Plus Package or Chemoclean are not enabled on leaving the factory. In the case of LSCH/LSCP with SNR 0000, a device serial number can be entered once in fields E115 to E117. Then enter the release codes for the Plus Package and/or Chemoclean if necessary. For a detailed description, see the "Replacement of central module" section. Additional functions (Plus Package and/or Chemoclean) missing after LSCH/LSCP module replacement 94 Endress+Hauser Liquisys M CCM223/253 Maintenance Error Possible cause Tests/remedial action Execution, tools, spare parts No HART or PROFIBUS PA/DP interface function Incorrect central module HART: LSCH-H1 or H2 module, PROFIBUS-PA: LSCP-PA module, PROFIBUS-DP: LSCP-DP module, see field E112. Replace central module; User or Endress+Hauser Service. Wrong software SW version, see field E111. Bus problem Remove some devices and repeat the test. 9 Contact Endress+Hauser Service. Maintenance LWARNING Process pressure and temperature, contamination, electrical voltage Risk of serious or fatal injury ‣ If the sensor has to be removed during maintenance work, avoid hazards posed by pressure, temperature and contamination. ‣ Make sure the device is de-energized before you open it. ‣ Power can be supplied to switching contacts from separate circuits. De-energize these circuits before working on the terminals. Take all the necessary precautions in time to ensure the operational safety and reliability of the entire measuring point. The maintenance of the measuring point comprises: • Calibration • Cleaning the controller, assembly and sensor • Checking the cables and connections When performing any work on the device, bear in mind any potential impact this may have on the process control system or on the process itself. NOTICE Electrostatic discharge (ESD) Risk of damaging the electronic components ‣ Take personal protective measures to avoid ESD, such as discharging beforehand at PE or permanent grounding with a wrist strap. ‣ For your own safety, only use genuine spare parts. With genuine parts, the function, accuracy and reliability are also ensured after maintenance work. 9.1 Maintenance of the entire measuring point 9.1.1 Cleaning the transmitter Clean the front of the housing using commercially available cleaning agents only. The front of the housing is resistant to the following in accordance with DIN 42 115: • Ethanol (for a short time) • Diluted acids (max. 2% HCl) • Diluted alkaline solutions (max. 3% NaOH) • Soap-based household cleaning agents When performing any work on the device, bear in mind any potential impact this may have on the process control system or on the process itself. Endress+Hauser 95 Maintenance Liquisys M CCM223/253 NOTICE Prohibited cleaning agents Damage to the housing surface or housing seal ‣ Never use concentrated mineral acids or alkaline solutions for cleaning. ‣ Never use organic cleaners such as benzyl alcohol, methanol, methylene chloride, xylene or concentrated glycerol cleaner. ‣ Never use high-pressure steam for cleaning purposes. 9.1.2 Cleaning the pH/mV sensors (EP version) LCAUTION Cleaning not switched off during calibration or maintenance activities Risk of injury due to medium or cleaning agent ‣ If a cleaning system is connected, switch if off before removing a sensor from the medium. ‣ If you wish to check the cleaning function and have therefore not switched off the cleaning system, please wear protective clothing, goggles and gloves or take other appropriate measures. LCAUTION Risk of injury from cleaning agents ‣ When using the following cleaning agents, make sure to protect your hands, eyes and clothing. Please clean contamination on the glass electrodes as follows: • Oily and greasy films: Clean with hot water or temperature-controller detergent (grease remover, e.g. alcohol, acetone, possibly dishwashing detergent). • Lime and metal hydroxide buildup: Dissolve buildup with diluted hydrochloric acid (3 %) and then rinse thoroughly with plenty of clear water. • Sulfidic buildup (from flue gas desulfurization or sewage treatment plants): Use a mixture of hydrochloric acid (3 %) and thiocarbamide (commercially available) and then rinse thoroughly with plenty of clear water. • Buildup containing proteins (e.g. food industry): Use a mixture of hydrochloric acid (0.5 %) and pepsin (commercially available) and then rinse thoroughly with plenty of clear water. • Fibers, suspended substances: Pressurized water, surface-active agents if necessary • Light biological buildup: Pressurized water ORP electrodes: Carefully clean the metal pins or surfaces mechanically. After mechanical cleaning, the ORP sensor can require several hours conditioning time. For this reason, check the calibration after one day. ISFET sensors • Never use acetone to clean ISFET sensors as this could damage the material. • After being cleaned with compressed air, ISFET sensors require approx. 5 to 8 minutes until the closed-control loop is re-established and the measured value has adjusted to the real value. Clogged membranes can be cleaned mechanically under certain circumstances (does not apply to ISFET sensors, Teflon membranes and open ring junction electrodes): • Use a small warding file. • Only file in one direction. 96 Endress+Hauser Liquisys M CCM223/253 Maintenance Air bubbles in the electrode: • Air bubbles can indicate incorrect mounting. For this reason check the orientation. • The range 15° to 165° to the horizontal is allowed (ISFET sensors are the exception). • Not permitted: horizontal installation or installation with the plug-in head pointing downwards. > 15° > 15° A0027183  44 Permitted angle of installation for glass electrodes Check for reference system reduction The inner reference lead of the reference system (Ag/AgCl) of a combination electrode or a separate reference electrode is usually brownish and matt. A silver-colored reference system is reduced and therefore defective. This is caused by a current flowing through the reference element. Possible causes for the current flow: • Incorrect measuring device operating mode selected (PML pin connected, but operating mode asymmetrical ("without PML"). See also the function description for "Selecting the connection type". • Shunt in measuring cable (e.g. due to moisture) between reference line and grounded shield or PM line. • Measuring device defective (shunt in reference input or entire input amplifier downstream of PE). 9.1.3 Maintenance of chlorine sensors Please refer to the Operating Instructions for your sensor for sensor maintenance and troubleshooting: CCS120 BA00388C/07/EN CCS140/141 BA00058C/07/EN CCS240/241 BA00114C/07/EN 963 BA00039C/07/EN The Operating Instructions contain detailed information including: • Sensor design and function • Mounting and installation • Electrical connection • Commissioning and calibration • Calculation examples and tables for verification of measured values • Maintenance, regeneration, cleaning • Troubleshooting table • Accessories and spare parts • Technical data and ordering information 9.1.4 Assembly Refer to the assembly operating manual for information on servicing and troubleshooting the assembly. The assembly operating manual describes the procedure for mounting and disassembling the assembly, replacing the sensors and seals, and contains information on the material resistance properties, as well as on spare parts and accessories. Endress+Hauser 97 Maintenance Liquisys M CCM223/253 9.1.5 Maintenance of pH connecting cables and junction boxes (EP version) Check the cables and connections for moisture. Moisture is indicated by a sensor slope that is too small. If nothing more can be displayed or if the display is fixed at pH 7, please check the following components: • Sensor head • Sensor plug • Junction box, if fitted • Extension cable NOTICE Incorrect measurements caused by moisture in the measuring cable ‣ If there is moisture in the measuring cable, the cable must be replaced! A shunt in the cable of > 20 MΩ cannot be measured with normal multimeters but is damaging for the pH measurement. Connect a pH simulator instead of the sensor. The value that is displayed on the transmitter must match the value set at the simulator. The value can differ at the second decimal place at the very maximum. If you do not have a pH simulator, you can test the cable with a commercially available megohmmeter. Please note the following when performing the test: • Make sure to disconnect the pH measuring cable from the sensor and device! • If you are using a junction box, you should check the infeed and outfeed measuring cable separately. • Check the cable with 1000 V DC (at least with 500 V DC) testing voltage. • If the cable is intact, the insulation resistance is > 100 GΩ. • If the cable is defective (moist), there is flashover. The cable must be replaced. You can clean (desalinate) the sensor head and junction box with de-ionized water and dry them with a hot air dryer. 9.2 Test and simulation 9.2.1 Chlorine sensors Chlorine sensors work according to the amperometric principle and supply very small direct currents as the measuring signal. A chlorine sensor can be simulated by a DC source. Due to the small currents, however, the simulation is highly sensitive. Use shielded cables and ground the simulator. Typical slope values are provided in the table below: 98 Sensor Typical slope value CCS120 Approx. 115 nA per mg Cl/l CCS140 Approx. 25 nA per mg Cl/l CCS141 Approx. 80 nA per mg Cl/l CCS240 Approx. 100 nA per mg ClO2/l CCS241 Approx. 350 nA per mg ClO2/l 963 Approx. 20 μA per mg Cl/l Endress+Hauser Liquisys M CCM223/253 Maintenance 9.2.2 Temperature measurement The transmitter uses the NTC sensor of the chlorine sensor to measure the temperature. Due to the relatively high sensor resistance, a two-wire connection is sufficient. Simulation can be performed with a normal decade resistor. The table below contains some simulation values: Temperature NTC simulation value 0 °C (32 °F) 29.490 kΩ 10 ° C (50 °F) 18.787 kΩ 20 °C (68 °F) 12.268 kΩ 25 °C (77 °F) 10.000 kΩ 30 °C (86 °F) 8.197 kΩ 40 °C (104 °F) 5.594 kΩ 9.2.3 pH/ORP measurement Simulation is performed with a pH/mV simulator or an mV voltage source. In the case of the CCM223/253, the pH or mV must always be measured symmetrically. For this reason, each simulation requires potential matching with the simulator. Connect the reference signal of the simulator (normal shield of the pH coaxial measuring line) to the PA/PM terminal of the transmitter. Zero point rapid test • In the case of the panel-mounted device, connect the BNC inner conductor to the BNC receptacle and the PM terminal. • In the case of the field device, connect the pH terminal, the Ref terminal and the PM terminal. • For pH the reading must be approx. 7, and for ORP approx. 0 mV. Test with DC supply point pH value Simulation 2 295 mV 4 177 mV 7 0 mV 9 -118 mV 12 -295 mV 9.2.4 Flow monitoring Flow is monitored by an inductive proximity switch (INS) in the CCA250 assembly. This switch is powered by 15 V from the auxiliary voltage output of the transmitter. Function of the INS Flow INS INS output Yes damped low impedance No not damped high-impedance Test or emergency mode Endress+Hauser 99 Maintenance Liquisys M CCM223/253 If you connect terminal 93 to terminal 85 and terminal 94 to terminal 86, this simulates an active proximity switch and thus a correct flow. Do not run the measuring system continuously in this state. Reestablish flow monitoring as soon as possible! 100 Endress+Hauser Liquisys M CCM223/253 Repair 10 Repair 10.1 Spare parts Please order spare parts from your local Sales Office. For this purpose, use the order numbers listed in the "Spare part kits" section. For safety, you should always provide the following additional data when ordering spare parts: • Device order code • Serial number • Software version, if possible You can take the order code and serial number from the nameplate. The software version is provided in the device software provided that the device processor system is still working. For more detailed information on spare parts kits, please refer to the "Spare Part Finding Tool" on the Internet: www.endress.com/spareparts_consumables 10.2 Disassembling the panel-mounted device Please note the effects on the process if the device is taken out of service! See the exploded drawing for the item numbers. 1. Disconnect the terminal block (item 150 to 180) from the rear of the device to deenergize the device. 2. Press in the latches of the end frame (item 340) and remove the frame from the rear. 3. Release the special screw (item 400) by turning it counter-clockwise. 4. Remove the entire electronics block from the housing. The modules are only mechanically connected and can be easily separated: 5. Simply remove the processor/display module towards the front. 6. Pull out the brackets of the rear plate (item 320) slightly. 7. Now you can remove the side modules. 8. Remove the Cl transmitter (item 110/120) as follows: 9. Using a fine wire cutter, nip off the heads of the synthetic distance holders. 10. Then remove the module from above. Assembly is the reverse of the disassembly sequence. Tighten the special screw fingertight without using a tool. Endress+Hauser 101 Repair Liquisys M CCM223/253 150 -170 340 400 210 200 110/120 10/20 50 - 100 C 130 320 310 180 30 - 45 10 15 A 230 V B 115 V 100 V A0001912  45 102 Exploded drawing of panel-mounted device Endress+Hauser Liquisys M CCM223/253 Repair The exploded drawing contains the components and spare parts of the panel-mounted device. You can take the spare parts and the corresponding order number from the following section using the item numbers. Item Kit description Name Function/contents Order no. 10 Power unit (main module) LSGA 100/115/230 V AC 51500317 15 Jumper 20 Power unit (main module) LSGD 24 V AC + DC 51500318 30 Relay module LSR1-2 2 relays 51500320 35 Relay module LSR2-2i 2 relays + 4-20 mA current input 51504304 35 Kit for Cxm2x3 relay module PROFIBUS DP LSR2-DP Relay module + 2 relays Curr. input + DP terminals Hardware version 2.10 and higher 71134732 40 Relay module LSR1-4 4 relays 51500321 45 Relay module LSR2-4i 4 relays + 4-20 mA current input 51504305 50 Central module LSCH-S1 1 current output 51502467 50 Kit for CCM2x3 central module PROFIBUS DP LSCP PROFIBUS DP central module Relay module + 2 relays Curr. input + DP terminals Hardware version 2.10 and higher 71134731 60 Central module LSCH-S2 2 current outputs 51502468 70 Central module LSCH-H1 1 current output + HART 51502497 80 Central module LSCH-H2 2 current outputs + HART 51502496 90 Central module LSCP-PA PROFIBUS PA/no current output 51502495 100 Central module LSCP-DP PROFIBUS DP/no current output 51502498 110 Cl transmitter MKC1 Input Cl and temperature 51502466 120 Cl/pH transmitter MKC1 Input Cl, pH/mV, temperature 51502465 Housing module Housing with front membrane, sensory tappets, seal, special screw, tensioning dogs, connection plates and nameplates 51501075 150 Complete terminal strip set Standard + HART Terminal strip set, inputs/outputs, power supply, alarm relay 51502463 160 Complete terminal strip set PROFIBUS-PA Terminal strip set, inputs/outputs, power supply, alarm relay 51502464 170 Complete terminal strip set PROFIBUS-DP Terminal strip set, inputs/outputs, power supply, alarm relay 51502490 180 Terminal strip Terminal strip for relay modules 51501078 200 pH input socket Socket with screen plate 51501070 210 BNC connector BNC easy solder-free, angled 50074961 Rear plate, side panel, end frame, special screw 51501076 End frame PROFIBUS-DP Rear frame for PROFIBUS DP, with Dsubmin plug connector 51502513 A Fuse Part of power unit, item 10 B Choice of line voltage Position of jumper on power unit, item 10 depending on line voltage C End frame latches Part of the end frame 130, 400 310, 320, Housing mechanical 340, 400 parts 340 Endress+Hauser Part of power unit, item 10 103 Repair Liquisys M CCM223/253 10.3 Disassembling the field device Please note the effects on the process if the device is taken out of service! See the exploded drawing for the item numbers. You require the following tools to disassemble the field device: • Standard set of screwdrivers • Torx screwdriver, size TX 20 Proceed as follows to disassemble the field device: 1. Open and remove the cover of the connection compartment (item 420). 2. Disconnect the supply terminal (item 270)) to de-energize the device. 3. Open the display cover (item 410) and release the ribbon cables (item 250) on the central module side (item 50 to 100) . 4. To remove the central module (item 50) release the screw in the display cover (item 450 b). 5. Proceed as follows to remove the electronics box (item 230) : 6. Turn the screws in the housing base (item 450 a) by two revolutions to release them. 7. Then push the entire box backwards and remove it from above while making sure that the module locks do not open. 8. Release the ribbon cables (item 250) . 9. Bend the module locks out and remove the modules. 10. To remove the docking module (item 240) remove the screws in the housing base (item 450 c) and remove the entire assembly from above. 11. To remove the CI transmitter (item 110/120) on devices with a pH/mV input, bend the shielding plate up. 12. Disconnect the connected strand (pH input, strand comes from the BNC connection jack) and nip off the heads of the synthetic distance sleeves using a fine wire cutter. 13. Then remove the module from above. To assemble, carefully push the modules into the guide rails of the electronics box and let them engage in the side box noses. It is not possible to mount the modules incorrectly. Modules inserted in the electronics box incorrectly are not operable since the ribbon cables cannot be connected. Make sure the cover seals are intact to guarantee IP 65 ingress protection. 104 Endress+Hauser Liquisys M CCM223/253 Repair A B 10 15 C 410 370 230 V D 115 V 50 - 100 100 V 450b 460b 230 450a 250 400 460a 430 420 110/120 280 30 - 45 10/20 240 450c 480 270 A0001915  46 Field device exploded drawing Endress+Hauser 105 Repair Liquisys M CCM223/253 The exploded drawing contains the components and spare parts of the field device. You can take the spare parts and the corresponding order number from the following section using the item numbers. Item Kit description Function/contents Order no. 51500317 10 Power unit (main module) LSGA 100/115/230 V AC 15 Jumper Part of power unit, item 10 20 Power unit (main module) LSGD 24 V AC + DC 51500318 30 Relay module LSR1-2 2 relays 51500320 35 Relay module LSR2-2i 2 relays + 4-20 mA current input 51504304 35 Kit for Cxm2x3 relay module PROFIBUS DP LSR2-DP Relay module + 2 relays Curr. input + DP terminals Hardware version 2.10 and higher 71134732 40 Relay module LSR1-4 4 relays 51500321 45 Relay module LSR2-4i 4 relays + 4-20 mA current input 51504305 50 Central module LSCH-S1 1 current output 51502467 50 Kit for CCM2x3 central module PROFIBUS DP LSCP PROFIBUS DP central module Relay module + 2 relays Curr. input + DP terminals Hardware version 2.10 and higher 71134731 60 Central module LSCH-S2 2 current outputs 51502468 70 Central module LSCH-H1 1 current output + HART 51502497 80 Central module LSCH-H2 2 current outputs + HART 51502496 90 Central module LSCP-PA PROFIBUS PA/no current output 51502495 100 Central module LSCP-DP PROFIBUS DP/no current output 51502498 110 Cl transmitter MKC1 Input Cl and temperature 51502466 120 Cl/pH transmitter MKC1 Input Cl, pH/mV, temperature 51502465 Inner housing fittings Docking module, empty electronics box, small parts 51501073 250 Ribbon cable lines 2 ribbon cable lines 51501074 270 Terminal strip Terminal strip for connection to power supply 51501079 280 pH terminal pH terminal with shielding plate 51501071 370, 410, Housing cover 420, 430, 460 Display cover, connection compartment cover, front membrane, hinges, cover screws, small parts 51501068 400, 480 Base, threaded joints 51501072 Rear plate, side panel, end frame, special screw 51501076 230, 240 Housing base 310, 320, Housing mechanical parts 340, 400 106 Name A Electronics box with relay module LSR1-x (bottom) and power unit LSGA/ LSGD (top) B Fuse also accessible if electronics box installed C Fuse Part of power unit, item 10 D Choice of line voltage Position of jumper on power unit, item 10 depending on line voltage Endress+Hauser Liquisys M CCM223/253 Repair 10.4 Replacing the central module Generally, when a central module has been replaced, all data which can be changed are set to the factory setting. If possible, note the customized settings of the device, such as: • Calibration data • Current assignment, main parameter and temperature • Relay function selections • Limit value/controller settings • Cleaning settings • Monitoring functions • Interface parameters Proceed as described below if a central module is replaced: 1. Disassemble the device as explained in the "Dismantling the panel-mounted instrument" or "Dismantling the field instrument" section. 2. Use the part number on the central module to check whether the new module has the same part number as the previous module. 3. Reassemble the device with the new module. 4. Put the device back into operation and check the basic functions (e.g. measured value and temperature display, operation via keyboard). 5. Read the serial number (“ser-no.”) off the nameplate of the device (e.g. 6A345605G00) and enter this number in fields E115 (1st digit = year, one-digit (6 in the example)), E116 (2nd digit: month, one-digit (A in the example)), E117 (digits 3-6 cons. number, four-digit (3456 in the example)).  In the field E118, the complete number is displayed again so you can check it is correct. You can only enter the serial number for new modules with the serial number 0000. This can only be done once! For this reason, make sure the number entered is correct before you press ENTER to confirm! If an incorrect code is entered, the additional functions are not enabled. An incorrect serial number can only be corrected at the factory! 1. Press ENTER to confirm the serial number or cancel the entry to enter the number again. 2. If available, enter the release codes for the Plus Package and/or Chemoclean in the "Service" menu. 3. Check the Plus Package release (e.g. by opening the function group CHECK / Code P) or the Chemoclean function. 4. Make the customized device settings again. 10.5 Return The product must be returned if repairs or a factory calibration are required, or if the wrong product was ordered or delivered. As an ISO-certified company and also due to legal regulations, Endress+Hauser is obliged to follow certain procedures when handling any returned products that have been in contact with medium. To ensure swift, safe and professional device returns, please read the return procedures and conditions at www.endress.com/support/return-material. Endress+Hauser 107 Repair Liquisys M CCM223/253 10.6 Disposal The device contains electronic components and must therefore be disposed of in accordance with regulations on the disposal of electronic waste. Observe the local regulations. 108 Endress+Hauser Liquisys M CCM223/253 Accessories 11 Accessories 11.1 Sensors CCS120 • Amperometric sensor for total chlorine • Measuring range 0.1 to 10 mg/l • Product Configurator on the product page: www.endress.com/ccs120 Technical Information TI00388C CCS140 • Membrane-covered amperometric sensor for free chlorine • Measuring range 0.05 to 20 mg/l • Product Configurator on the product page: www.endress.com/ccs140 Technical Information TI00058C CCS141 • Membrane-covered amperometric trace sensor for free chlorine • Measuring range 0.01 to 5 mg/l • Product Configurator on the product page: www.endress.com/ccs141 Technical Information TI00058C CCS240 • Membrane-covered amperometric sensor for chlorine dioxide • Measuring range 0.05 to 20 mg/l • Product Configurator on the product page: www.endress.com/ccs240 Technical Information TI00114C CCS241 • Membrane-covered amperometric trace sensor for chlorine dioxide • Measuring range 0.01 to 5 mg/l • Product Configurator on the product page: www.endress.com/ccs241 Technical Information TI00114C 11.2 Connection accessories Measuring cable CYK71 • Unterminated cable for connecting analog sensors and for extending sensor cables • Sold by the meter, order numbers: – Non-Ex version, black: 50085333 – Ex-version, blue: 50085673 CPK1 For pH/ORP electrodes with GSA plug-in head Ordering information is available from your sales office or at www.endress.com. CPK9 • Terminated measuring cable for connecting analog sensors with TOP68 plug-in head • Selection in accordance with product structure For more information and to order, please contact your sales office. Endress+Hauser 109 Accessories Liquisys M CCM223/253 MK extension cable • Twin-core signal cable with additional shielding and PVC insulation • Particularly for the transmission of output signals of transmitters or input signals of controllers and for temperature measurement. • Order number: 50000662 VBC junction box • For cable extension (for chlorine measuring systems) • Dimensions (B x D x H): 125 x 80 x 54 mm (4.92 x 3.15 x 2.13 ") • 10 terminal strips • Cable entries: 7 x Pg 7, 2 x Pg 11 • Material: aluminum • Degree of protection: IP 65 (i NEMA 4x) • Order No. 50005181 VBM • Junction box for cable extension • 10 terminal strips • Cable entries: 2 x Pg 13.5 or 2 x NPT ½" • Material: aluminum • Degree of protection: IP 65 • Order numbers – Cable entries Pg 13.5 : 50003987 – Cable entries NPT ½": 51500177 11.3 Installation accessories CYY101 • Weather protection cover for field devices • Absolutely essential for field installation • Material: stainless steel 1.4301 (AISI 304) • Order No. CYY101-A 270 (10.6) 320 (12.6) 300 (11.8) A0024627  47 Dimensions in mm (inch) Flexdip CYH112 • Modular holder system for sensors and assemblies in open basins, channels and tanks • For Flexdip CYA112 water and wastewater assemblies • Can be affixed anywhere: on the ground, on the capstone, on the wall or directly onto railings. • Stainless steel version • Product Configurator on the product page: www.endress.com/cyh112 Technical Information TI00430C 110 Endress+Hauser Liquisys M CCM223/253 Accessories 30 (1.18) Ø max. 60 (2.36) M6 60 (2.36) 90 (3.54) 70 (2.76) Ø 8 (0.31) 90 (3.54) 70 (2.76) Ø 8 (0.31) Post mounting kit • For securing the field housing to horizontal and vertical posts and pipes • Material: stainless steel 1.4301 (AISI 304) • Order No. 50086842 Ø 6 (0.24) 70 (2.76) 90 (3.54) A0024660  48 Dimensions in mm (inch) 11.4 Software and hardware add-ons The add-ons can only be ordered by quoting the serial number of the device in question. • Plus Package Order No. 51502242 • Chemoclean function (requires four-relay card) Order No. 51502871 • Two-relay card Order No. 51500320 • Four-relay card Order No. 51500321 • Two-relay card with current input Order No. 51504304 • Four-relay card with current input Order No. 51504305 • pH package for EK version Order No. 51502460 • pH package for ES version Order No. 51503526 11.5 Metering system Compact measuring station CCE10/CCE11 • Fully assembled and wired panel for one or three transmitters, with CCA250-A1 flow assembly • Product Configurator on the product page: www.endress.com/cce10 or www.endress.com/cce11 Technical Information TI00440C Endress+Hauser 111 Accessories Liquisys M CCM223/253 11.6 Calibration accessories Photometer PF-3 • Compact hand-held photometer for determining free available chlorine • Color-coded reagent bottles with clear dosing instructions • Order No.: 71257946 112 Endress+Hauser Liquisys M CCM223/253 Technical data 12 Technical data 12.1 Input Measured variables Total chlorine Free available chlorine Chlorine dioxide Temperature pH value or ORP (optional) Cl2/ClO2 signal input CCS120/140/141/240/241: Sensor 963: 0 to 5000 nA -100 to 500 µA Temperature measurement Temperature sensor for CCS120/140/141/240/241: Display range: NTC, 10 kΩ at 25 °C (77 °F) pH and ORP measurement pH measuring range: ORP measuring range: Zero point adjustment: Slope adjustment pH 3.5 to 9.5 0 to 1500 mV ±100 mV 38 to 65 mV/pH Binary inputs Voltage Current consumption 10 to 50 V Max. 10 mA Current input 4 to 20 mA, galvanically isolated 0 to 50 °C (32 to 122 °F) Load: 260 Ω for 20 mA (voltage drop 5.2 V) 12.2 Output signal Output HART Signal encoding Frequency Shift Keying (FSK) + 0.5 mA via current output signal Data transmission rate 1200 baud Galvanic isolation Yes PROFIBUS PA Endress+Hauser Signal encoding Manchester Bus Powered (MBP) Data transmission rate 31.25 kBit/s, voltage mode Galvanic isolation Yes (IO modules) 113 Technical data Liquisys M CCM223/253 PROFIBUS DP Signal encoding RS485 Data transmission rate 9.6 kBd, 19.2 kBd, 93.75 kBd, 187.5 kBd, 500 kBd, 1.5 MBd Galvanic isolation Yes (IO modules) Signal on alarm 2.4 or 22 mA in the event of an error Load Max. 500 Ω Transmission range Cl2/ClO2 CCS120 CCS140/240 CCS141/241 and 963 Temperature pH ORP 0 to 10 mg/l 0 to 20 mg/l 0 to 5 mg/l 0 to 50 °C (32 to 120 °F) 4 to 9 0 to 1500 mV Signal resolution Max. 700 digits/mA Separation voltage Max. 350 VRMS / 500 V DC Auxiliary voltage output Output voltage Output current 15 V ± 0.6 V Max. 10 mA Contact outputs Switching current with ohmic load (cos φ = 1) Switching current with inductive load (cos φ = 0.4) Switching voltage Switching power with ohmic load (cos φ = 1) Switching power with inductive load (cos φ = 0.4) Max. 2 A Max. 2 A Limit contactors Pickup/dropout delay 0 to 2000 s Controller Function (configurable) 114 Max. 250 V AC, 30 V DC Max. 500 VA AC, 60 W DC Max. 500 VA AC, 60 W DC Pulse length/pulse frequency controller, continuous controller Three-point step controller for Cl2/ClO2 Controller behavior P, PI, PD, PID, basic load dosing Control gain Kp 0.01 to 20.00 Integral action time Tn 0.0 to 999.9 min Derivative action time Tv 0.0 to 999.9 min Period length for pulse length controller 0.5 to 999.9 s Frequency for pulse frequency controller 60 to 180 min-1 Basic load 0 to 40 % of max. actuating variable Motor run time for three-point step controller 10 to 999 s Neutral zone for three-point step controller 0 to 40 % Endress+Hauser Liquisys M CCM223/253 Alarm Technical data Function (switchable) Alarm threshold adjustment range Alarm delay Monitoring time for lower limit violation Monitoring time for upper limit violation Protocol-specific data Latching/momentary contact Cl2/ClO2/pH/ORP/temperature: entire range 0 to 2000 s 0 to 2000 min 0 to 2000 min HART Manufacturer ID 11h Device type 0094h Transmitter-specific revision 0001h HART version 5.0 Device description files (DD) www.endress.com/hart HART load (communication resistor) 250 Ω Device variables None (only dynamic variables PV and SV) Supported features - PROFIBUS PA Manufacturer ID 11h Device type 1518h Device revision 0001h Profile version 2.0 GSD files www.endress.com/profibus GSD version Output values Primary value, temperature Input variables PCS display value Supported features Device lock: The device can be locked using the hardware or software. PROFIBUS DP Manufacturer ID 11h Device type 151Eh Profile version 2.0 GSD files www.endress.com/profibus GSD version Endress+Hauser Output values Primary value, temperature Input variables PCS display value Supported features Device lock: The device can be locked using the hardware or software. 115 Technical data Liquisys M CCM223/253 12.3 Supply voltage Power supply via fieldbus Power supply Depending on order version: • 100/115/230 V AC +10/-15 %, 48 to 62 Hz • 24 V AC/DC +20/-15 % HART Supply voltage Not applicable, active current outputs Reverse polarity protection Not applicable, active current outputs PROFIBUS PA Supply voltage 9 V to 32 V, max. 35 V Sensitivity to reverse polarity No FISCO/FNICO compliant according to IEC 60079-27 No PROFIBUS DP Supply voltage 9 V to 32 V, max. 35 V Sensitivity to reverse polarity Not applicable FISCO/FNICO compliant according to IEC 60079-27 No Power consumption Max. 7.5 VA Mains fuse Fine-wire fuse, semi-delay 250 V/3.15 A Circuit breaker NOTICE The device does not have a power switch ‣ The customer must provide a protected circuit breaker in the vicinity of the device. ‣ The circuit breaker must be a switch or power switch, and you must label it as the circuit breaker for the device. ‣ At the supply point, the power supply for the 24 V versions must be isolated from dangerous live cables by double or reinforced insulation. Cable specification Cable length (CCS140/141/240/241) Cable length (chlorine sensor 963) Cable length (CCS120) Cable length (pH/ORP) Overvoltage protection According to EN 61000-4-5 116 Max. 30 m (98 ft) with CMK cable Max. 30 m (98 ft) with CMK cable Max. 15 m (49 ft) with CPK9 cable Max. 50 m (160 ft) with cable CYK71 Endress+Hauser Liquisys M CCM223/253 Technical data 12.4 Performance characteristics Reference operating conditions Reference temperature: 25 ˚C (77 ˚F) Measured value resolution CCS120/140/240 and 963 CCS141/241 pH value ORP Temperature 0.01 mg/l 0.001 mg/l 0.01 pH 1 mV 0.1 °C Maximum measured error Display(pH, T = const.) CCS140/141/240/241 CCS120 and 963 Temperature Signal output CCS140/141/240/241/ CCS120/963 pH ORP Temperature Max. 0.5 % of measured value ± 4 digits Max. 1 % of measured value ±4 digits 0.03 pH 3 mV ±0.3 K Max. 0.75 % of measuring range Max. 1.25 % of current output range Max. 1.25 % of current output range Max. 1.25 % of measuring range Measured errors in accordance with DIN IEC 746 Part 1, at rated operating conditions Repeatability Max. 0.2 % of measuring range 12.5 Environment Ambient temperature range -10 to +55 °C (+10 to +130 °F) Storage temperature –25 to +65 °C (-10 to +150 °F) Electromagnetic compatibility Interference emission and interference immunity as per EN 61326-1:2006, EN 61326-2-3:2006 Degree of protection Field device Panel-mounted device Electrical safety As per EN/IEC 61010-1:2010, overvoltage category II for installations up to 2000 m (6500 ft) above MSL CSA Device versions with CSA General Purpose approval are certified for indoor use. Endress+Hauser IP 65 / integrity according to NEMA 4X IP 54 (front), IP 30 (housing) 117 Technical data Liquisys M CCM223/253 Relative humidity 10 to 95%, not condensing Degree of contamination The product is suitable for pollution degree 2. 12.6 Mechanical construction Field device L x B x D: 96 x 96 x 145 mm (3.78" x 3.78" x 5.71") Installation depth: approx. 165 mm (6.50 ") L x B x D: 247 x 170 x 115 mm (9.72" x 6.69" x 4.53") Weight Panel-mounted device Field device Max. 0.7 kg (1.54 lbs.) Max. 2.3 kg (5.07 lbs.) Materials Panel-mounted device housing Field housing Front membrane Polycarbonate ABS PC FR Polyester, UV-resistant Terminals Cable cross-section Max. 2.5 mm2 (14 AWG) Dimensions 118 Panel-mounted device Endress+Hauser Liquisys M CCM223/253 Appendix 13 Endress+Hauser Appendix 119 Appendix Liquisys M CCM223/253 Zero calibration (only if A1 = 120) CALIBRATION zero (CCS120) Calibration status is displayed no; yes o.k. CALIBRAT Cl2 / ClO2 C14 Zero calibration (only if A1 = 120 or 963) Enter DPD value no; yes Value of last cal. C C11 Operating matrix versions EK and ES yes; no; new Exxx C15 Store calibration result C15 Slope is displayed 100% min. 25% (3%) max. 500% C12 Calibration status is displayed o.k. Store calibration Exxx yes; no; new C13 C14 C15 Edit: Code 22 Read: any code MEAS. VALUE DISPLAY with TEMPERATURE READING in °C Meas. value display Meas. value display Meas. value display Meas. value display Meas. value display Temperature reading in °F no temp. display Sensor current in nA Current input in mA Current input in % 1st error displayed Other errors are displayed (up to max. 10 errors) (if present) Only display switchover! Edit: Code 22 Read: any code Select sensor 140; 141; 240; 241; 963; 120 SETUP 1 A mg/l; ppm; ppb Off; INS B2 Cont. switch-off by current input Off; Input B3 0s Z 0 ... 2000 s Sw.-off direction for current input 0 ... 100% read O Output1; Output2 °C; mg/l; ppm; ppb; Contr O1 Select contact type F F1 lin = linear min; s F2 Select table pairs 1 1 ... no. Table pair asign 1 ... 10 O332 O333 O321 Select current range Enter 0/4 mA value Enter 20 mA value 4–20 mA; 0–20 mA 0.00; 0 ... 20 (5) mg/l 0 °C; 0 ... 50 °C 2.0 (0.5); 0 ... 20 (5) mg/l 50 °C; 0 ... 50 °C O3(1) O311 Define error current Alarm delay 0 min (s) 0 ... 2000 min (s) (dep. on F2) Select unit of alarm delay Latch = latching c. Momen = momentary c. ALARM O2 1 O331 O3(2) CURRENT OUTPUT Z6 Enter simulation val. current value 0 ... 22.0 mA sim = Simulation Select meas. unit for 2nd current output Off; lin = linear Z5 Enter no. of table pairs edit O3(3) Feedforward control to PID cont. Low; High Z4 Select table options Select current output A6 B5 Z3 Tab = Table Clean trig. A5 Enter temperature difference (offset) current offset –5.0 ... + 5.0 °C 50% 0 ... 2000 s Z2 Select digital input 1 ext.Hold 0 ... 2000 s 0s Sw.-off limit value for current input Delay for cont. sw.-on current input Delay for contr. swi.-on sam. stream A4 B4 0s Z1 0 ... 2000 s A3 Enter correct process temperature current meas. value 0 ... 50 °C Delay for cont. switch-off curr. input Delay for controller switch-off sam. stream 0s A2 Manual pH compensation last comp. value pH 4.00 ... 9.00 Off; Manu B CURRENT INPUT Controller switch-off by sample stream A1 PH compensation SETUP 2 Select display unit Select error number 22 mA; 2.4 mA F3 O312 1 F4 1 ... 255 O313 Enable alarm contact yes; no F5 F6 A0002633-EN 120 Endress+Hauser Liquisys M CCM223/253 Appendix Enter meas. value damping 1 (no damping) 1 ... 60 A7 Feedforward control gain = 1 at 50% 0 ... 100% Z7 Enter x value (meas. val.) Enter y value (current) Table status o.k. 0.00; 0 ... 20 (5) mg/l 0 °C; 0 ... 50 °C 4.00 mA 0 ... 20.00 mA yes; no O334 O335 Enable error current for error just entered Automatic start of cleaning function no; yes no; yes F7 F8 O336 Select “next error” or return to menu next = next error <---R F9 A0002634-EN Endress+Hauser 121 Appendix Liquisys M CCM223/253 CHECK Chlorine / ClO2 P P1(1) P111 Switch function R2(8) on or off int = internal ext = external Off; On R2(7) Timer Off; On; Basic; PID+B R2(4) RELAY Rel1; Rel2; Rel3; Rel4 Switch function R2(3) on or off Off; On; Basic; PID+B S+C = for param. + cal. Setup = for param. S Hardware version SW Version HW Version E1(4) Main (= mainboard) E141 Trans (= transmitter) Hardware version SW Version HW Version E131 E+H SERVICE Contr (= controller) E Hardware version SW Version HW Version E121 SW Version HW Version E111 E112 0s Select switch-off point of contact 20 (5) mg/l 0 ... 20 (5) mg/l R234 Set pick-up delay 0s 0 ... 2000 s R213 10 s Serial number is displayed 0 ... 2000 s R233 Enter Hold dwell time S3 R244 Set pick-up delay 0 ... 50 °C R212 Off; On 0.0 min 0.0 ... 999.9 min R243 R232 Select switch-on point of contact 20 (5) mg/l 0 ... 20 (5) mg/l R264 R214 Enter SW upgrade release code (Plus pack.) 0 0 ... 999 s S4 0 ... 9999 S5 Module identification is displayed E143 E144 Module identification is displayed Serial number is displayed E133 E134 Module identification is displayed Serial number is displayed E123 E124 Module identification is displayed Serial number is displayed E113 E114 Tag description HART: 0 ... 15 or PROFIBUS: 1 ... 126 I Hardware version 0.01 ... 100.00 50 °C 0 ... 50 °C E122 Instrument software E1(1) Enter address INTERFACE 50 °C R273 Enter integral action time Tn (0.0 = no I comp.) Enter switch-off temperature Enter switch-on temperature E132 Module software E1(2) 1.00 R242 E142 Module software E1(3) Enter control gain Kp 0.5 (0.1) mg/l 0 ... 20 (5) mg/l S2 Module software 0 ... 999 s R263 Enter setpoint Manual Hold CAL = with Cal. no = no Hold S1 Rel (= relay) 360 min 1 ... 7200 min R262 R211 Configure Hold Select language ENG; GER; FRA; ITA; NEL; ESP SERVICE Off; On R2(1) 20 s Define minimum pause time 120 min 1 ... 3600 min Define pause time 0 ... 999 s R231 Switch contact R2(1) on or off LC PV = limit contactor Cl2 / ClO2 R1 R Define rinse time R241 R2(3) Select contact to be configured i+ext = internal + external i+stp = int. w. suppression by ext. R261 Switch function R2(4) on or off R284 Enter pre-rinse time R272 30 s Off; On R2(6) 0.0 min 0.0 ... 999.9 min R283 R271 Switch function R2(6) on or off LC °C = Limit contactor T 0.01 ... 100.00 1.00 P115 Enter integral action time Tn (0.0 = no I comp.) Select start pulse Switch function R2(7) on or off Clean = Chemoclean (only with Rel3 and Rel4) Enter control gain Kp R282 R281 Select process monitoring Off; AC; CC; AC CC AC!; CC!; ACCC! P114 Enter setpoint 0.5 (0.1) mg/l 0 ... 20 (5) mg/l Off; On R2(8) PID controller Cl2 / ClO2 P113 P112 3-point step controller Cl2 / ClO2 (only with Rel3 and Rel4) Set upper alarm threshold 20.00 (5.00) mg/l 0.1 ... 20 (5) mg/l Set lower alarm threshold 0.00 mg/l 0 ... 19.9 (4.9) mg/l Alarm delay 0 min (s) 0 ... 2000 min (s) (dep. on F2) Select alarm threshold monitoring Off; Low; High LoHi; Lo!; Hi!; LoHi! @@@@@@@@ I1 I2 A0002635-EN 122 Endress+Hauser Liquisys M CCM223/253 Set max. perm. period of lower limit exceeding 60 min 0 ... 2000 min Appendix Set max. perm. period of upper limit exceeding 120 min 0 ... 2000 min P117 P116 Enter min. switch-on time tON 0.3 s 0.1 ... 5.0 s Motor run time 60 s 10 s 10% 20 s 0 ... 999 s R274 3-p. step contr.: assigns 2 contacts, only permitted for contacts 3+4 0 ... 40% R286 Enter post-rinse time 0 ... 999 s P118 Neutral zone 10 ... 999 s R285 Enter cleaning time Set limit value 0.5 (0.1) mg/l 0 ... 20 (5) mg/l R287 Define period between two cleaning cycles (pause time) 360 min 1 ... 7200 min Define repeat times 0 0 ... 5 R275 R276 Define min. pause time 120 min 1 ... R277 min Number of cleaning cycles without cleaning agent 0 0 ... 9 R278 R277 R279 Chemoclean: assigns 2 contacts, only permitted for contacts 3+4 Enter deriv. action time Tv (0.0 = no D comp.) Select control characteristic 0.0 min 0.0 ... 999.9 min inv; dir R245 Set drop-out delay 0s 50 °C R235 0 ... 2000 s R215 Enter SW upgrade release code Chemocl. 0 R247 Enter pulse period 10.0 s 0.5 ... 999.9 s R249 R248 Enter min switch-on time tON 0.3 s 0.1 ... 5.0 s R2410 Enter basic load 0% 0 ... 40% R2411 Display LC status R236 R216 Order number is displayed R237 Display LC status MAX; MIN R217 R216 Serial number is displayed Reset instrument 0 ... 9999 Start instrument test no; sens; factory S6 Enter max. pulse frequency 120 1/min 60 ... 180 1/min MAX; MIN 0 ... 50 °C Set alarm threshold (as abs. value) 20 (5) mg/l 0 ... 20 (5) mg/l Set dropout delay 0s R246 Set alarm threshold (as abs. value) 0 ... 2000 s Select len = pulse length freq = pulse frequency curr = current output 2 S7 S8 no; display S9 S10 A0002636-EN Endress+Hauser 123 Appendix Liquisys M CCM223/253 Zero calibration (only if A1 = 120) CALIBRATION zero (CCS120) Calibration status is displayed no; yes o.k. Enter value of ORP buffer Buffer value of last cal. 0 ... 1500 mV CALIBRATION ORP mV (dep. on B1) C14 Enter calibration temperature CALIBRATION pH (dep. on B1) 25.0 °C –10 ... +60 °C Enter pH value of first buffer solution Buffer value of last cal. pH 3.50 ... 9.50 Adopt if stable pH ±0.05 (> 10 s) C23 C12 C35 Calibrating Calibration status is displayed C25 C26 Store calibration result yes; no; new Exxx o.k. Slope is displayed 59.16 mV/pH 38.00 ... 65.00 mV/pH Adopt if stable pH ±0.05 (> 10 s) C24 Slope is displayed 100% min. 25% (3%) max. 500% no; yes C11 C34 Enter pH value of second buffer solution Buffer value of last cal. pH 3.50 ... 9.50 Calibrating Enter calibration results yes; no; new Exxx o.k. C33 C22 Value of last cal. C –100 ... +100 mV Zero calibration (only if A1 = 963) Enter DPD calibration value Calibration status is displayed C32 C21 CALIBRATION Cl2 / ClO2 C15 Zero point is displayed Calibrating Adopt if stable ±1 mV (> 10 s) C31 Operating matrix version EP yes; no; new Exxx C15 Store calibration result C13 C14 C15 Edit: Code 22 Read: any code MEAS. VALUE DISPLAY with TEMPERATURE DISPLAY in °C Meas. value display Meas. value display Meas. value display Meas. value display Meas. value display Temperature display in °F No temp. display pH; ORP (dep. on B1) pH signal in mV Sensor current in nA 1st error is displayed Other errors are displayed (up to max. 10 errors) Delay for contr. sw.-off by sample stream Delay for contr. sw.-on by sample stream Select digital input 1 (if present) Edit: Code 22 Read: any code Display unit Select sensor 140; 141; 240; 241; 963; 120 SETUP 1 A SETUP 2 Controller switch-off by sample stream mg/l; ppm; ppb Off; INS Select operating mode pH compensation Off; pH; ORP mV Off; Manu; Auto B 0s A2 A1 B1 0 ... 2000 s A3 Enter correct process temperature current meas. value 0 ... 50 °C Manual pH compensation last comp. value pH 4.00 ... 9.00 B2* ext.Hold 0 ... 2000 s 0s A6 Enter temperature difference (offset) current offset –5.0 ... + 5.0 °C B4 B3 Clean Trig. A5 A4 B5 * field B2 not available for CCS240/241 Controller switch-off by current input Off; Input CURRENT INPUT 0s Z1 Z Delay for controller sw.-off current input Delay for controller sw.-on current input 0 s 0 ... 2000 s 50% 0 ... 2000 s Z2 Switch-off direction for current input Switch-off limit for current input Low; High 0 ... 100% Z3 read O3(3) sim = simulation O3(2) Select current output Select meas. parameter for 2nd current output Output1; Output2 °C; pH; ORPmV; Contr O O1 O2 edit 1 O331 1 ... 10 Z6 Select table pairs 1 1 ... No. of table pairs asign O332 O333 Enter simulation value current value 0 ... 22.0 mA O321 Select current range lin = linear O3(1) Z5 Enter number of table pairs 4–20 mA; 0–20 mA CURRENT OUTPUT Off; lin = linear Z4 Select table options Tab = Table Feedforward control to PID controller O311 Enter 0/4-mA value 0.00 mg/l; 0 ... 20 (5) mg/l 0.00 ppm; 0 … 20 ppm 0 ppb; 0 … 20000 ppb pH 4.00; pH 4 ... 9 0 mV; 0 ... 1500 mV 0 °C; 0 ... 50 °C O312 Enter 20-mA value 2.0 (0.5); 0 ... 20 (5) mg/l 2.0 ppm; 0 … 20 ppm 2000 ppb; 0 … 20000 ppb pH 9.00; pH 4 ... 9 1000 mV; 0 ... 1500 mV 50 °C; 0 ... 50 °C O313 A0002637-EN 124 Endress+Hauser Liquisys M CCM223/253 Appendix Calibration status is displayed Zero point is displayed pH 7.00 pH 5.00 ... 9.00 o.k. C27 Store calibration results yes; no; new Exxx C28 Meas. value display Meas. value display Current input in mA Current input in % C29 Only LCD switchover! Enter meas. value damping 1 (no damping) 1 ... 60 A7 Feedforward control gain = 1 at 50% 0 ... 100% Z7 Enter x value (meas. val.) 0.,00; 0 ... 20 (5) mg/l pH 4.00; pH 4 ... 9 0 mV; 0 ... 1500 mV 0 °C; 0 ... 50 °C Enter y value (current) Table status o.k. 4.00 mA 0 ... 20.00 mA yes; no O334 O335 O336 A0002638-EN Endress+Hauser 125 Appendix Liquisys M CCM223/253 Select contact type ALARM F min; s F1 F2 Select alarm threshold monitoring Off; Low; High; Lo Hi Low!; High!; LoHi! ORP mV (dep. on B1) P1(2) CHECK Select alarm threshold monitoring Off; Low; High Lo Hi; Low!; High!; LoHi! Chlorine / ClO2 P 3-point step controller Cl2 / ClO2 (only with Rel3 and Rel4) Alarm delay 0 min (s) 0 ... 2000 min (s) (depending on F2) Alarm delay 0 min (s) 0 ... 2000 min (s) (depending on F2) Switch function R2(8) on or off Off; On Off; On; Basic; PID+B Off; On; Basic; PID+B R2(4) Switch function R2(3) on or off Off; On R R1 R2(1) pH 4.1 ... 9 P124 Switch function R2(2) on or off Off; On Off; On R211 Select process monitoring Off; AC; CC; AC CC AC!; CC!; ACCC! P115 Enter control gain Kp Enter integral action time Tn (0.0 = no I comp.) 0.01 ... 100.00 1.00 0.0 min 0.0 ... 999.9 min R283 R284 Select start pulse Enter pre-rinse time i+ext = internal + external i+stp = int. w. suppression of ext. 20 s 0 ... 999 s R273 R272 Define rinse time 0 ... 999 s 360 min 1 ... 7200 min R263 pH 4 ... 9 0.0 min 0.0 ... 999.9 min R253 Enter setpoint R254 Enter integral action time Tn (0.0 = no I comp.) Enter control gain Kp 1.00 0.0 min 0.0 ... 999.9 min 0.01 ... 100.00 R242 Set switch-on temperature Enter integral action time Tn (0.0 = no I comp.) 0.01 ... 100.00 1.00 R252 0.5 (0.1) mg/l; 0 ... 20 (5) mg/l 0.5 ppm; 0 … 20 ppm 500 ppb; 0 … 20000 ppb R264 Enter control gain Kp Enter setpoint pH 7.20 Define min. pause time 120 min 1 ... 3600 min Define pause time R262 R243 R244 Set switch-off temperature 0 ... 50 °C R232 Select contact switch-on point 1500 mV 0 ... 1500 mV R222 Select contact switch-on point pH 9 pH 4 ... 9 R221 Switch function R2(1) on or off P125 P114 R282 R221 R2(2) RELAY pH 9.00 Enter setpoint R231 Switch function R2(2) on or off P125 Select process monitoring Off; AC; CC; AC CC AC!; CC!; ACCC! Set upper alarm threshold 20.00 mg/l; 0 ... 20 mg/l 20.00 ppm; 0 … 20 ppm 20000 ppb; 0 … 20000 ppb 0.5 (0.1) mg/l; 0 ... 20 (5) mg/l 0.5 ppm; 0 … 20 ppm 500 ppb; 0 … 20000 ppb 50 °C Off; On R2(2) LC PV = Limit contactor Cl2 / ClO2 Off; AC; AC! P124 P113 R241 R2(3) Rel1; Rel2; Rel3; Rel4 1500 mV 10 ... 1500 mV Set upper alarm threshold 0.00 mg/l; 0 ... 20 mg/l 0.00 ppm; 0 … 20 ppm 0 ppb; 0 … 20000 ppb R251 Switch function R2(4) on or off Select contact to be configured Set lower alarm threshold R261 R2(5) LC pH = Limit contactor pH (dep. on B1) Select process monitoring P123 30 s Switch function R2(5) on or off LCORP = Limit contactor ORP (dep. on B1) pH 4 ... 8.9 F6 Set upper alarm threshold R271 R2(6) LC °C = Limit contactor T pH 4.00 int = internal ext = external Off; On PID controller Cl2 / ClO2 Set lower alarm threshold Switch function R2(7) on or off Off; On yes; no F5 P123 R281 Switch function R2(6) on or off PID controller pH 0 ... 1490 mV P112 R2(7) Timer 0 mV P122 R2(8) Clean = Chemoclean (only with Rel3 and Rel4) Set lower alarm threshold Enable alarm contact 1 ... 255 1 F4 P122 P111 P1(1) 22 mA; 2.4 mA Alarm delay 0 min (s) 0 ... 2000 min (s) (depending on F2) P121 P1(2) Select error number F3 P121 Select alarm threshold monitoring Off; Low; High; Lo Hi Low!; High!; LoHi! pH (dep. on B1) Define error current Alarm delay 0 min (s) 0 ... 2000 min (s) (depending on F2) Select unit for alarm delay Latch = latching c. Momen = momentary c. R222 50 °C Set pick-up delay 0 ... 50 °C 0s R234 Set pick-up delay Select contact switch-off point 1500 mV 0 ... 1500 mV 0s 0 ... 2000 s R223 R224 Set pick-up delay Select contact switch-off point pH 9 pH 4 ... 9 0s 0 ... 2000 s R223 R224 Select contact switch-off point Select contact switch-on point 0 ... 2000 s R233 20 (0.5) mg/l; 0 ... 20 (5) mg/l 20 ppm; 0 … 20 ppm 20000 ppb; 0 … 20000 ppb 20 (0.5) mg/l; 0 ... 20 (5) mg/l 20 ppm; 0 … 20 ppm 20000 ppb; 0 … 20000 ppb R212 R213 Set pick-up delay 0s 0 ... 2000 s R214 A0002639-EN 126 Endress+Hauser Liquisys M CCM223/253 Appendix Enable error current for error just selected Automatic start of clean function no; yes no; yes Select “next error” or return to menu next = next error <---R F7 F8 Set max. perm. period for lower alarm threshold Set max. perm. period for upper alarm threshold 60 min 0 ... 2000 min 0 ... 2000 min 120 min 60 min 0 ... 2000 min Set max. perm. period for lower limit exceeding 0 ... 2000 min 120 min 0.3 s 0.1 ... 5.0 s Motor run time 10 ... 999 s 60 s R285 Enter cleaning time 10 s 0 ... 999 s pH 7.20 pH 4 ... 9 P128 Set limit value 0.5 (0.1) mg/l; 0 ... 20 (5) mg/l 0.5 ppm; 0 … 20 ppm 500 ppb; 0 … 20000 ppb P117 P116 Enter min. switch-on time tON Set limit value P127 P126 Set max. perm. period for lower limit exceeding F9 P118 10% 0 ... 40% R286 Enter post-rinse time 0 ... 999 s 20 s R274 3-p. step controller: assigns 2 contacts, only permitted for contacts 3+4 Neutral zone R287 Define period between two cleaning cycles (pause time) 360 min 1 ... 7200 min Define repeat cycles 0 0 ... 5 R275 R276 R277 Define minimum pause time 120 min 1 ... R277 min Number of cleaning cycles without cleaning agent 0 0 ... 9 R278 R279 Chemoclean: assigns 2 contacts, only permitted for contacts 3 (+4) Enter deriv. action time Tv (0.0 = no D comp.) Select control characteristic 0.0 min 0.0 ... 999.9 min dir; inv R255 R256 Enter deriv. action time Tv (0.0 = no D comp.) Select control characteristic 0.0 min 0.0 ... 999.9 min inv; dir R245 Set drop-out delay 0s 0 ... 2000 s Set drop-out delay 50 °C 0 ... 2000 s 0 ... 2000 s R225 MAX; MIN R226 0 ... 2000 s R215 20 (5) mg/l; 0 ... 20 (5) mg/l 20 ppm; 0 … 20 ppm 20000 ppb; 0 … 20000 ppb R216 Enter pulse period 10.0 s 0.5 ... 999.9 s R248 R259 Enter max. pulse frequency 120 1/min 60 ... 180 1/min R249 0.1 ... 5.0 s 0% R2510 Enter min. switch-on time tON 0.3 s 0.1 ... 5.0 s R2410 0 ... 40% R2511 Enter basic load 0% 0 ... 40% R2411 R227 Display of LC status MAX; MIN R226 Set alarm threshold Set drop-out delay R258 0.3 s Enter basic load R237 1500 mV 0 ... 1500 mV pH 0 ... 9 0.5 ... 999.9 s Enter min. switch-on time tON MAX; MIN Display of LC status pH 9.00 10.0 s Enter max. pulse frequency 120 1/min 60 ... 180 1/min Display of LC status Set alarm threshold Set alarm threshold Set drop-out delay 0s 0 ... 50 °C R247 R236 R225 0s Select len = pulse length freq = pulse frequency curr = current output 2 Set alarm threshold Enter pulse period R257 R246 R235 0s Select len = pulse length freq = pulse frequency curr = current output 2 R227 Display of LC status MAX; MIN R217 A0002640-EN Endress+Hauser 127 Appendix Liquisys M CCM223/253 Configure Hold Select language S+C = for param. + cal. Setup = for param. ENG; GER; FRA; ITA; NEL; ESP SERVICE S S1 Rel (= relay) Module software Hardware version SW Version HW Version Main (= mainboard) E141 Hardware version SW Version HW Version E131 E1(3) Trans (= transmitter) Hardware version SW Version HW Version E121 E1(2) Contr (= controller) E E1(1) Enter address I HW Version E112 0 ... 999 s 0 S4 0 ... 9999 S5 E144 Module identification is displayed Serial number is displayed E133 E134 Module identification is displayed Serial number is displayed E123 E124 Module identification is displayed Serial number is displayed E113 E114 Tag description HART: 0 ... 15 or PROFIBUS: 1 ... 126 INTERFACE Hardware version SW Version Enter SW upgrade release code (Plus pack.) Module identification is displayed E143 E122 Instrument software E111 Serial number is displayed E132 Module software 10 s S3 E142 Module software Enter Hold dwell time Off; On S2 E1(4) E+H SERVICE Manual Hold CAL = for Cal. no = no Hold I1 @@@@@@@@ I2 A0002641-EN 128 Endress+Hauser Liquisys M CCM223/253 Control SW upgrade release code Chemocl. 0 Appendix Order number is displayed Serial number is displayed Reset instrument 0 ... 9999 Start instrument test no; sens; factory S6 S7 S8 no; display S9 S10 A0002642-EN Endress+Hauser 129 Index Liquisys M CCM223/253 Index A Access codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Alarm contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Automatic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 C Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Central module replacement . . . . . . . . . . . . . . . . . . 107 Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Cleaning Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Connecting cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Current outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 D Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Device configuration . . . . . . . . . . . . . . . . . . . . . . . . . 42 Device-specific errors . . . . . . . . . . . . . . . . . . . . . . . . . 93 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Disassembling Field device . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Panel-mounted device . . . . . . . . . . . . . . . . . . . . 101 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 E E+H Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . 19 Version 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Version 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 F Feedforward control . . . . . . . . . . . . . . . . . . . . . . . . . 48 H Hold function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 I Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . 14 Installation instructions . . . . . . . . . . . . . . . . . . . . . . . 16 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 J Junction boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 130 K Key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 L Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 M Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Maintenance of the entire measuring point . . . . . . . . 95 Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Mechanical construction . . . . . . . . . . . . . . . . . . . . . 118 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 N Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 O Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 P P(ID) controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Performance characteristics . . . . . . . . . . . . . . . . . . . 117 Post mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . 29 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . 18 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Process-specific errors . . . . . . . . . . . . . . . . . . . . . . . . 89 Product identification . . . . . . . . . . . . . . . . . . . . . . . . . 9 Q Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 R Relay configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Replacing the central module . . . . . . . . . . . . . . . . . . 107 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 S Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 SCS monitoring functions . . . . . . . . . . . . . . . . . . . . . . 57 Sensor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Setup 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Setup 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Switching on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 System error messages . . . . . . . . . . . . . . . . . . . . . . . 85 Endress+Hauser Liquisys M CCM223/253 Index T Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Test Chlorine sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Flow monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . 99 pH/ORP measurement . . . . . . . . . . . . . . . . . . . . . 99 Temperature measurement . . . . . . . . . . . . . . . . . 99 Test and simulation . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Three-point step controller . . . . . . . . . . . . . . . . . 28, 67 Trouble shooting instructions . . . . . . . . . . . . . . . . . . 85 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 U Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 W Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Endress+Hauser 131 *71300499* 71300499 www.addresses.endress.com