Det-Tronics SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
SAFETY MANUAL
X2200 UV, X9800 IR, X5200 UVIR
SIL 2 Certified Flame Detectors
SAFETY-CERTIFIED Flame DETECTORs
This manual addresses the specific requirements and
recommendations applicable to the proper installation,
operation, and maintenance of all Safety‑Certified
(SIL‑Certified) X2200 UV, X9800 IR, and X5200
UVIR Flame Detectors. The safety function of the
X2200/X9800/X5200 is to detect a variety of fires
and to provide present alarm status to its relay and
analog outputs. For complete information regarding
performance, installation, operation, maintenance and
specifications, refer to appropriate instruction manual:
X2200 UV Flame Detector
95-8549
X9800 IR Flame Detector
95-8554
X5200 UVIR Flame Detector
95-8546
QUALITY POLICY STATEMENT
All quality assurance control measures necessary for
safety management as specified in IEC 61508 Part 1
have been implemented. The quality management
system of Det-Tronics is based on the requirements
of EN ISO 9001 and ANSI/ASQC Q9001 through the
application of the United Technologies Company
Achieving Competitive Excellence (ACE) program. In
addition, the Quality Management System complies
with the European ATEX Directive requirements per EN
13980, the International Electrotechnical Commission
requirements per OD005/V2, and the supervised
testing requirements per ISO 17025.
WARNING
The X2200, X9800 and X5200 are intended for
use in hazardous environments that may include
explosive levels of flammable gases and vapors.
These products must be properly installed,
operated and maintained. Improper installation
or use could result in an explosion or fire resulting
in death or serious injury.
SAFETY MESSAGES
• Do not remove the detector cover in explosive
environments when device power is on and
circuits are live.
Procedures and instructions in this section may
require special precautions to ensure the safety of
personnel performing the operations. Information that
raises potential safety issues is indicated by the word
“Warning”. Always read and understand these safety
messages.
1.1
1.1
© Detector Electronics Corporation 2011
• Detector must be properly installed, and wiring
compartment cover must be fully engaged
to meet hazardous area explosion-proof/
non‑incendive requirements.
1
95-8672
Rev: 8/11 95-8672
DESIGN
NOTE
The X2200/X9800/X5200 analog signal and relay
outputs are not safety-rated during detector
warm-up or signal output loop testing (including
proof testing). Alternative means should be used
at the job site to ensure facility safety during
these activities.
The X2200/X9800/X5200 flame detector is classified
as a Type B smart device according to IEC61508.
The standard model provides an isolated 4-wire,
0-20 mA output, together with on-board Alarm and
Fault relay contacts. These outputs serve to indicate
normal operating condition of the detector, fault, or the
presence of a flame alarm. The X2200/X9800/X5200
contains extensive self-diagnostics and is programmed
to send the current output to a specified state (0 mA, 1
mA, or 2 mA) upon internal detection of a failure or fault
condition.
DIAGNOSTIC RESPONSE TIME
The X2200/X9800/X5200 will perform all critical
diagnostic functions within 58 minutes, worst case
diagnostic detection time. The user must not configure
the automatic oi test interval and failure annunciation
count combination to be greater than 58 minutes
(default setting is one minute intervals, with failure
annunciation after three failed oi tests).
HART communication is available as an option. The
HART option allows the operator to monitor the status
of the detector, determine factory settings, adjust
field settings, and initiate field tests. For specific
information regarding HART communication, refer to
the appropriate HART Addendum:
X2200 UV Flame Detector
95-8638
X9800 IR Flame Detector
95-8637
X5200 UVIR Flame Detector
Optical Integrity Test
The oi test is designed to generate a fault when the
unit’s detection range has been reduced by 50% or
more. This factor should be carefully considered
during detector placement with regard to the required
safety function.
95-8636
NOTE
All configuration changes to the X2200/X9800/
X5200 must be verified by the user via a proof
test, power cycle and re-check of settings, or
other appropriate method.
CERTIFICATION
The X2200/X9800/X5200 Safety-Certified version is
certified to IEC61508:2010 for single input use in low
demand SIL 2 Safety Instrumented Systems.
The X2200/X9800/X5200 is designed for operation with
a supply voltage from 18-30 volts DC. Proper operation
outside this range cannot be assumed.
SAFETY-CERTIFIED PRODUCT IDENTIFICATION
Safety Certification of all X2200/X9800/X5200 models
meeting SIL 2 safety standards is clearly identified on
the product label.
Safety-Certification of the X2200/X9800/X5200 includes:
• Analog Output
• Relay Output
• HART Output as non-interfering.
INSTALLATION
Safety-Certification of the X2200/X9800/X5200 does
not include:
note
For complete information regarding performance,
installation,
operation,
maintenance
and
specifications, refer to the appropriate instruction
manual:
X2200 UV Flame Detector
95-8549
X9800 IR Flame Detector
95-8554
X5200 UVIR Flame Detector
95-8546
• Pulse Output
• EQP LON Output version
• RS-485 Modbus signal.
VALID INPUT RANGE
Fault annunciation is provided on the 0-20 mA signal
output loop by signaling to a 1 mA, 2 mA, or 3 mA current
output level. The receiving device must be programmed
to indicate a fault condition when current levels reach
over-current (> 21 mA) or undercurrent (< 2.25 mA).
1.1
Tools Required:
• 14 mm hexagonal wrench
2
95-8672
No special installation requirements exist above and
beyond the standard installation practices documented
in the instruction manual. Environmental specification
limits are also as published in the general specifications
section in the instruction manual.
Commissioning Personnel
The Safety Certified X2200/X9800/X5200 flame
detector can be commissioned by any qualified person
with knowledge of flame detection instruments and the
configuration device being used. Refer to the Start‑Up
section provided in the instruction manual.
The operating power distribution system must be
designed and installed so the terminal voltage does
not drop below 18 Vdc when measured at any specific
location. The maximum current limit must be less than
2 amperes. The external system providing power to the
X2200/X9800/X5200 must have overvoltage protection
that ensures supply voltage does not exceed 33 Vdc.
Relay Configuration Requirements
The end user must provide transient and current limiting
on the output contacts of the relays. The maximum
relay contact output must be limited to 2 amperes at 30
Vdc. The load must be a resistive load. The user must
protect against transients by using standard protection
methods such as proper grounding of shielded wire
and separation of relay load wires from other lines
carrying rapidly switched high current (e.g. large motor
power supply lines).
Common Misuse Scenarios
Refer to the General Application Information section
of the appropriate instruction manual for detailed
information on common misuse scenarios. Application
environments to avoid include the following:
UV Detectors
IR Detectors
If the 0-20 mA analog output is not being monitored for
fault conditions, the status of the Fault relay must be
monitored and appropriate action taken.
Intense UV sources including
electric arc welding, high voltage
corona, x-rays and gamma
radiation should not be present in
the detection area.
The fault relay is configured for normally energized
operation. The alarm relay must be configured for
normally de-energized operation (i.e. the alarm relay
must energize during alarm conditions).
Intense IR sources should not be
present in detection area.
Configuration
Digital communication with the X2200/X9800/X5200 is
necessary to monitor internal status and to modify the
factory settings. For specific information regarding HART
communication, refer to the appropriate HART Addendum:
X2200 UV Flame Detector
95-8638
X9800 IR Flame Detector
95-8637
X5200 UVIR Flame Detector
95-8636
NOTE
The above common misuse scenarios will cause
the X2200/X9800/X5200 relay or 4-20 mA outputs
to annunciate a high background and/or false
alarm depending on the intensity of the radiation
and the relay configuration.
UV & IR Detectors Glass and Plexiglas windows
attenuate radiation and should not
be located between the detector
and detection area.
NOTE
Prior to device configuration (setting alarm
thresholds, latch/non-latch function, etc.) all alarm
outputs must be bypassed. The device is not safety
certified during configuration change activities.
The detector must have a direct
line-of-sight to any potential flame
source in the detection area; care
must be taken to keep physical
obstructions out of the line of view
of the detector.
NOTE
All configuration changes to the X2200/X9800/
X5200 must be verified by the user via a proof
test, power cycle and re-check of settings, or
other appropriate method. The LED flash rate
during power-up should be checked to verify
proper setting.
note
The black plastic shipping cap must be removed
prior to placing the detector into service.
Configuration Protection
When using the 0-20 mA output with HART as a safety
output, it is required that Write Protect be set to “on”
to ensure that the HART is non-interfering. If HART
write protect is temporarily disabled, the user must take
specific action to re-enable Write Protect to ensure that
HART communication remains non-interfering.
START-UP AND COMMISSIONING
All safety functions of the X2200/X9800/X5200 are
active within 30 seconds of power-up without any user
action required.
1.1
3
95-8672
Table 1—Frequency of Proof Tests
Proof Test Name
Commissioning
Frequency
Visual Field Inspection Proof Test
Yes
As needed, depending on level and
type of contaminants present
Detector Response Mag oi Proof Test
Yes
Yearly
Detector Response Mag oi Proof Test
OPERATION, MAINTENANCE, INSPECTION AND
PROOF TESTING
Warning
Any external alarm equipment, systems or
signaling devices that could be automatically
initiated by performing this test must be disabled
or bypassed before performing this test!
Tools Required:
• Magnetic oi test tool (p/n 102740-002)
• Window cleaner (p/n 001680-001 or isopropanol)
• Lens tissue and cotton swabs
• 4 mm flat blade screwdriver
Tools Required:
• Magnetic oi test tool (part number 102740-002)
After normal installation and start-up have been
completed as recommended within the instruction
manual, Proof Tests must be performed for every SafetyCertified X2200/X9800/X5200 detector installed.
All flame detectors must be performance tested using
the Mag oi Procedure as described in the Magnetic
oi / Manual oi section of the instruction manual and
inspected to ensure that they are capable of providing
expected performance and protection. Note that
the Mag oi Procedure and Manual oi Tests are not
interference free. During these tests the unit is not
performing normal flame detection functions. Model
X2200/X9800/X5200 provides an onboard status LED,
which indicates Green color when internal operational
parameters are normal.
Personnel performing Proof Test procedures shall be
competent to perform the task. All Proof Test results
must be recorded and analyzed. Any corrective actions
taken must be documented in the event that an error is
found in the safety functionality. The Proof Tests must
be performed at a frequency as shown in Table 1.
warning
Failure to perform the specified testing and
inspection may lower or void the SIL rating for the
product or system.
To indicate a successful proof test, the LED changes to
a Red color, the Alarm and Auxiliary relays change state
to indicate an alarm condition, and the current output
indicates 20 mA. These results should be verified on
the control device.
Visual Field Inspection Proof test
Visual inspection of all Safety-Certified X2200/X9800/
X5200 flame detectors shall be conducted as needed
to confirm that there are no obstructions in the optical
field of view. Corrective action will include removal of
such impediments should they exist.
To indicate an unsuccessful proof test, the LED changes
to Yellow, the Fault relay becomes de-energized, and
the current output indicates 2 mA. The fault indication
can be reset by momentarily applying the magnet or
manual oi switch.
Completion of Visual Field Inspection Proof test will be
recorded and documented in the SIS logbook.
1.1
4
95-8672
Fault/Failure Action Plan
CERTIFICATION AND FAILURE RATE DATA
In the event of a non-alarm condition result with the Mag
oi test, the standard Maintenance and Troubleshooting
procedures listed in the instruction manual must be
followed. In the event that the condition cannot be
resolved, the standard Device Repair and Return
procedures listed in the instruction manual must be
followed.
All Safety-Certified X2200/X9800/X5200 models are
certified compliant to:
IEC61508: 2010
Type B Device
Systematic Capability: SIL 2 certified
HFT: 0
Any and all failures to successfully complete the alarm
test must be recorded and documented in the SIS
logbook.
Low Demand Mode
PFDavg should be calculated for any safety
instrumented function using the X2200/X9800/X5200.
(Refer to FMEDA report for necessary information,
including DU rate).
WARNING
Any external alarm equipment, systems or
signaling devices that were disabled must be
re-activated at the conclusion of proof testing
activities.
Safety Accuracy:
Not applicable.
Safety Response Time: See appendix A of the
corresponding instruction
manual for response time
details.
Product Repair
The X2200/X9800/X5200 is not field-repairable and any
internal device repairs must be conducted at the factory.
No firmware changes are permitted or authorized. All
failures indicated by internal diagnostics or Proof Tests
that cannot be resolved through the troubleshooting
and maintenance procedures described in the manual
must be reported to the manufacturer.
OPERATING, ENVIRONMENTAL and
PERFORMANCE SPECIFICATIONS
Product Life X2200:
25-53 years, based on
manufacturer data.
Product Life X9800:
21-43 years, based on
manufacturer data.
Product Life X5200:
10-78 years, based on
manufacturer data.
All failure rate data for SIL verification is in the FMEDA
report, which is available upon request.
The operating temperature range for the Safety
Certified X2200/X9800/X5200 is –40C to +75C. The
Safety-Certified X2200/X9800/X5200 product versions
fully comply with, and must be operated in accordance
with the functional and performance specifications
provided in the corresponding instruction manual. A 24
hour mean time to repair should be assumed for safety
availability calculations.
SPARE PARTS
Refer to the spare parts section of the instruction
manual. Safety certification is based on a sufficient
number of spares to achieve a 24 hour mean time to
repair.
1.1
5
95-8672
Product Certifications
TERMS AND DEFINITIONS
EQP
Eagle Quantum Premier System
EQPSL/SLC
FM, CSA, ATEX, CE, IECEx, and exida.
Refer to the Instruction Manual for details.
Eagle Quantum Premier Safety Loop /
Signaling Line Circuit
FMEDA
FMEDA Report available.
Failure Mode Effects and Diagnostics
Analysis
HART
Highway Addressable Remote
Transducer
For complete information regarding performance,
installation, operation, maintenance and specifications
of the X2200/X9800/X5200, refer to the appropriate
instruction manual:
HFT
Hardware Fault Tolerance
LFL
Lower Flammable Limit
PFD
X2200 UV Flame Detector
95-8549
Probability of Failure on Demand
(Probability of Dangerous Failure)
X9800 IR Flame Detector
95-8554
PFDavg
Average Probability of Failure on
Demand
X5200 UVIR Flame Detector
95-8546
SFF
Safe Failure Fraction
SIF
Safety Instrumented Function
SIL
Safety Integrity Level
SIS
Safety Instrumented System
X2200
Ultraviolet Flame Detector
X9800
Infrared Flame Detector
X5200
Ultraviolet and Infrared Flame
Detector
FM
M
F
M
F
®®
®
APPROVED
APPROVED
APPROVED
IEC 61508 Failure Rates in FIT1
Failure Category
lsd
lsu2
ldd
ldu
SFF3
X2200 Analog Output
0
75
704
61
92.7%
X2200 Analog Output w HART
0
67
877
73
92.8%
X2200 Relay
208
78
501
72
91.6%
X9800 Analog Output
0
93
628
68
91.4%
X9800 Analog Output w HART
0
84
800
80
91.7%
X9800 Relay
220
95
412
79
90.2%
X5200 Analog Output
0
98
834
74
92.6%
X5200 Analog Output w HART
0
90
1007
86
92.7%
X5200 Relay
248
102
591
85
91.7%
1 FIT = 1 Failure / 109 Hours
2 It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to
IEC 61508, ed2, 2010.
3 Safe Failure Fraction needs to be calculated on (sub)system level.
ED
ER
BY UL
AN
Detector Electronics Corporation
D
BS
T
IS
I
S
REGI
NO
.
M
TER
ED FIR
A 23
TE
RM
ISO 9001
REGIS
Det-Tronics and the DET-TRONICS logo are registered trademarks or
trademarks of Detector Electronics Corporation in the United States, other
countries, or both. Other company, product, or service names may be
trademarks or service marks of others.
RE
G
Specifications subject to change without notice.
RED FI
05 • NO. 25
82
6
©Copyright Detector Electronics Corporation 2011. All rights reserved.
95-8672
6901 West 110th Street • Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491 • Fax (952) 829-8750
http://www.det-tronics.com • E-mail: det-tronics@det-tronics.com