General Monitors / MSA IR5500 Infrared Open Path Detector Instruction Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
MODEL IR5500
Infrared Open Path Detector for
Hydrocarbon Gas Applications
The information and technical data disclosed in
this document may be used and disseminated
only for the purposes and to the extent specifically
authorized in writing by General Monitors.
Instruction Manual
08-16
General Monitors reserves the right to change
published specifications and designs without prior
notice.
MANIR5500
Part No.
Revision
MANIR5500
M/08-16
Model IR5500
This page intentionally left blank
i
Model IR5500
TABLE OF CONTENTS
MODEL IR5500 .................................................................................................................................. I
INFRARED OPEN PATH DETECTOR FOR HYDROCARBON GAS APPLICATIONS ............... I
QUICK START GUIDE .................................................................................................................V
System Mounting .................................................................................................................................... v
Conduit Sealing ......................................................................................................................................vi
Terminal Connections ............................................................................................................................ vii
1.0 INTRODUCTION..................................................................................................................... 1
1.1
Protection for Life ...................................................................................................................... 1
1.2
Features and Benefits ............................................................................................................... 2
1.3
Applications ............................................................................................................................... 2
1.4
System Integrity Verification ...................................................................................................... 3
2.0 PRODUCT DESCRIPTION ..................................................................................................... 4
2.1
General Description ................................................................................................................... 4
2.1.1 Infrared Detection Principles ........................................................................................ 4
2.1.2 IR5500 Detection Method ............................................................................................. 4
2.1.3 Measurement Scale...................................................................................................... 5
2.1.4 Typical System Gas Cloud Measurements .................................................................. 6
2.1.5 Control Electronics ....................................................................................................... 6
3.0 INSTALLATION ...................................................................................................................... 8
3.1
Receipt of Equipment ................................................................................................................ 8
3.2
Location Considerations ............................................................................................................ 8
3.3
System Mounting ....................................................................................................................... 9
3.4
Installation................................................................................................................................ 10
3.5
Conduit Sealing ....................................................................................................................... 11
3.6
Terminal Connections.............................................................................................................. 11
3.6.1 Terminal Block Operation ........................................................................................... 14
3.6.2 Terminal Functions ..................................................................................................... 15
3.7
Applying Power and Alignment................................................................................................ 16
3.7.1 Start-Up Checklist....................................................................................................... 16
3.7.2 Startup ........................................................................................................................ 16
3.7.3 Alignment and Adjustment.......................................................................................... 17
3.7.4 Response Test ........................................................................................................... 18
3.7.5 Visible Light Filter ....................................................................................................... 18
3.8
Operational Cautions ............................................................................................................... 19
3.8.1 Rapid and Massive Liquid Propane Releases............................................................ 19
3.8.2 Solutions to Guard against These Situations ............................................................. 19
4.0 OPERATION ......................................................................................................................... 21
4.1
Using the IR5500 Menus ......................................................................................................... 21
4.2
Menu Options .......................................................................................................................... 23
4.3
Test “---” ................................................................................................................................... 23
ii
Model IR5500
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
Setup “SE” ............................................................................................................................... 23
Flash Input “in” ......................................................................................................................... 33
Alignment/Adjustment “Pct” or “AJ” ......................................................................................... 35
Log – Fault Log and Zero ........................................................................................................ 37
Finish “Fi” ................................................................................................................................. 39
Maintenance ............................................................................................................................ 39
Display and Fault Codes ......................................................................................................... 39
LEL and ppm Negative Drift Faults ......................................................................................... 39
5.0 TROUBLESHOOTING.......................................................................................................... 41
5.1
Fault Codes ............................................................................................................................. 41
5.1.1 F0 Excess Negative Drift ............................................................................................ 42
5.1.2 F1 Close to Low IR ..................................................................................................... 42
5.1.3 F3 Beam Block ........................................................................................................... 43
5.1.4 F4 IR Flash Timing ..................................................................................................... 43
5.1.5 F5 Setup Menu ........................................................................................................... 43
5.1.6 F6 Low Voltage Input at the Receiver ........................................................................ 43
5.1.7 F7 Code Checksum .................................................................................................... 43
5.1.8 F8 Fault during Zeroing .............................................................................................. 43
5.1.9 F9 Gas Left ................................................................................................................. 43
5.1.10 F10 Reset Short ......................................................................................................... 43
5.1.11 F11 Receiver Overheating.......................................................................................... 44
5.1.12 F12 IR Flash Intensity Variation ................................................................................. 44
5.1.13 F13 Non-Volatile Memory (NVM) Checksum ............................................................. 44
5.1.14 F14 Analog Output for LEL-m .................................................................................... 44
5.1.15 F15 Receiver Heater .................................................................................................. 44
5.1.16 F16 High IR ................................................................................................................ 45
5.1.17 F18 Dirty Lens ............................................................................................................ 45
5.1.18 F19 Magnet ................................................................................................................ 45
5.1.19 F20 Low Alignment Signal .......................................................................................... 45
5.1.20 F21 Zeroing ................................................................................................................ 45
5.1.21 F22 RAM Checksum .................................................................................................. 45
5.1.22 F23 Hardware Revision .............................................................................................. 45
5.1.23 F24 Receiver Temperature Sensor ............................................................................ 46
5.1.24 F25 Analog Output for ppm-m .................................................................................... 46
5.1.25 tF6 Low Voltage Input at the Source .......................................................................... 46
5.1.26 tF7 Source Heater ...................................................................................................... 46
5.1.27 tF8 Source Overheating ............................................................................................. 46
5.2
Other Troubleshooting Tips ..................................................................................................... 46
5.2.1 Source does not flash ................................................................................................. 46
5.2.2 Receiver does not display startup sequence when power is applied ......................... 47
5.2.3 Receiver displays ]-[ during alignment ....................................................................... 47
5.2.4 Receiver displays F1 or F3 after alignment ................................................................ 47
5.2.5 Receiver does not respond to the magnet ................................................................. 47
5.2.6 Receiver signal level number went to 0 with no “A” on the display ............................ 47
5.2.7 Receiver displays information other than described .................................................. 47
5.2.8 Source or Receiver will not move ............................................................................... 47
6.0 CUSTOMER SUPPORT ....................................................................................................... 48
iii
Model IR5500
7.0 APPENDIX ............................................................................................................................ 49
7.1
Warranty .................................................................................................................................. 49
7.2
Specifications........................................................................................................................... 50
7.2.1 System Specifications ................................................................................................ 50
7.2.2 Electrical Specification................................................................................................ 51
7.2.3 Mechanical Specification ............................................................................................ 51
7.2.4 Environmental Specification ....................................................................................... 52
7.2.5 Approvals .................................................................................................................... 52
7.2.6 Cable Requirements ................................................................................................... 52
7.3
Spare Parts and Accessories .................................................................................................. 53
7.3.1 Spare Parts ................................................................................................................. 53
7.3.2 Accessories ................................................................................................................ 53
7.4
Engineering Documentation .................................................................................................... 54
8.0 APPENDIX A ........................................................................................................................ 55
8.1
Split-Range Analog Output Option .......................................................................................... 55
8.2
Alignment Using Legacy AJ Value .......................................................................................... 56
Table of Figures
Figure 1:
Figure 2:
Figure 3:
Figure 4:
Figure 5:
IR5500 Open Path Gas Detector .................................................................................. 1
Indoor Gas Cloud .......................................................................................................... 5
Outdoor Gas Cloud ....................................................................................................... 5
Outline and Dimensional Drawing with Mounting Options ............................................ 9
Installation onto Mounting Arm ................................................................................... 10
Table of Tables
Table 1:
Table 2:
Table 3:
Table 4:
Table 5:
Table 6:
Readings of Methane Gas Clouds 0-5000 ppm•m Range .............................................. 6
Readings of Methane Gas Clouds 0-5 LEL•m Range..................................................... 6
Receiver Wiring Terminal Locations ............................................................................. 14
Locations....................................................................................................................... 48
Distances from Power Supply to Source and Receiver ................................................ 52
Distances from Receiver to Analog Output Load .......................................................... 53
iv
Model IR5500
Quick Start Guide
Quick Start Guide
System Mounting
The Model IR5500 units are shipped with either mounting assembly shown below. After
the mounting location has been established, mount the support arm/base. Attach a pan-tilt
assembly to each unit. Apply lithium grease on each taper joint before attaching a unit to
a support arm/base. Add the supplied bolt and washers; do not tighten until unit is fully
adjusted. If the bolt has been tightened and further adjustment is necessary, loosen the
bolt two turns and use a screwdriver between the pan-tilt assembly and arm to release the
taper.
Arm Assembly with Fine Adjustments
Basic Arm Assembly
Base Assembly with Fine Adjustments
v
Model IR5500
Quick Start Guide
Conduit Sealing
Each conduit run from a hazardous to a non-hazardous location should be sealed so that
gas or flames cannot pass from one electrical installation to another through the conduit
system. A conduit seal must also be installed within 18 inches of the Source and Receiver
enclosure if installed in a Division 1 location. A conduit seal may not be required if installed
in a Division 2 location.
General Monitors requires the use of a drain loop or conduit seal in the conduit to prevent
moisture from entering the unit housing. For installation in a Division 2 location using
Division 2 wiring methods, a drain loop or conduit seal may not be required. Consult
Article 501 of the NEC for details.
WARNING:
The conduit entries should be sealed per the NEC 501.15 or Canadian
Electrical Code Handbook (Part 1, Section 18-154) for Division 1
installations.
WARNING:
Unused cable entry holes must be sealed with an approved explosion-proof
stopping plug.
CAUTION: Acetic acid will damage metal components, hardware, and other
components. If damage results from the use of a sealant that outgases
acetic acid such as a room temperature vulcanizing sealant (RTV), the twoyear warranty will be void.
CAUTION: Consult the manufacturer for dimensional information on the flameproof
joints for repair.
vi
Model IR5500
Quick Start Guide
Terminal Connections
To make the wiring connections to the Model IR5500, loosen the retaining screw on the
cover of each unit using the supplied hex wrench and unscrew the rear cover. All output
connections are made inside the housing (see figures on following page for terminal block
locations). Recommended stripping length is 4/10” (10 mm) for push terminals, ½” (11
mm) for screw terminals.
NOTE: Contact with printed circuit board (PCB) components should be avoided to
prevent damage by static electricity.
vii
Model IR5500
Quick Start Guide
16
COM
15
RST
14
COM
13
0-20mA P
12
COM
11
0-20mA L
10
COM
+24V
9
8
MOD1-
Modbus1-
Modbus2-
MOD2-
17
7
MOD1+
Modbus1+
Modbus2+
MOD2+
18
Normally
Deenergized
Normally
Energized
Normally
Energized
Normally
Deenergized
6
A2
Alarm NO
Alarm NC
Fault NO
Fault NO
FLT1
19
5
AC
Alarm C
Alarm C
Fault C
Fault C
FLTC
20
4
A1
Alarm NC
Alarm NO
Fault NC
Fault NC
FLT2
21
3
W2 L
Warn
LEL•m NO
Warn
LEL•m NC
Warn
ppm•m NC
Warn
ppm•m NO
W2 P
2
WC L
Warn
LEL•m C
Warn
LEL•m C
Warn
ppm•m C
Warn
ppm•m C
WC P
1
W1 L
Warn
LEL•m NC
Warn
LEL•m NO
Warn
ppm•m NO
Warn
ppm•m NC
W1 P
Receiver Wiring Terminal Locations
viii
22
23
24
Model IR5500
Quick Start Guide
Terminal Block Operation
To connect wiring to the terminal block, insert a screwdriver into the orange tab and
press down, opening the terminal (see figure below). Insert the wire into the terminal
and release the orange tab, clamping the wire in the terminal. Check the clamp by
GENTLY tugging the wire to ensure it is locked in. Make sure that the terminal clamps
on to the wire, not the insulation.
Terminal Block Operation Diagram
The push terminal block is designed to accept 24 AWG to 16 AWG (0.2 mm2 to 1.5 mm2)
stranded or solid-wire. The optional screw terminal block accepts 26 AWG to 14 AWG
(0.14 mm2 to 2.5 mm2 ) wire.
Primary DC voltage power must be provided by the customer. Since the Model IR5500
Infrared Open Path System is designed to continuously monitor for leaks of combustible
gas, a power switch is not included to prevent accidental system shutdown. Power must
remain disconnected until all other wiring connections are made.
ix
Model IR5500
Quick Start Guide
Startup
Before applying power to the system for the first time, all wiring connections should be
checked and the housing cover securely fastened.
Display Sequence on Power Up
Display
Duration (s)
000
1
8.8.8. (Test all segments)
2
blank
3
Software revision letter
2
SU (Start Up)
120
0 (Gas Concentration)
Continuous
The IR5500 contains a heater circuit to remove condensation from the windows. The unit
should be allowed to stabilize for approximately two hours before continuing with the
setup mode.
The resolution of the display is the either 0.1 LEL•m or 100 ppm•m. Since HART,
Modbus, and 4-20 mA outputs have more resolution, the least significant digit of the
displayed value might not agree with that of other outputs due to rounding error.
x
Model IR5500
Quick Start Guide
Alignment/Adjustment
Ensure that there is no significant amount of background gas when the unit is setting the
zero value, as this will alter the Model IR5500’s performance. If there is gas present, try
setting-up the IR5500 on a breezy day, as this dissipates the gas.
Alignment Outline
Verify that the beam path is clear of all obstruction and that unit optics are clean.
Adjust units for maximum signal.
Adjust the Source first, then the Receiver.
Adjust pan first, then tilt.
Make sure that mounting screws are fully tightened.
Make sure that the Receiver displays 0C to complete alignment.
1. It is recommended that two people are involved in alignment. One person should be at
the Source and one person should be at the Receiver. An alignment scope is helpful
but not necessary.
2. At the Receiver, check the four M6 screws that hold the unit to the pan-tilt assembly.
Ensure that a small amount of anti-seize lubricant (p/n 2421) has been applied to the
xi
Model IR5500
Quick Start Guide
first few threads of each M6 screw. A packet of lubricant is included with the pan/tilt
assembly. Without lubricant, alignment will be more difficult, and bolts may seize.
Verify that the back two screws have been hand-tightened but that the front two have
not. Hand-tighten the 24 mm nut for the pan-tilt assembly. On the assembly, verify
that the front and back fine adjust screws are flush with the assembly surface, to allow
full movement of tilt. If necessary, use a 2.5 mm hex wrench to adjust the screws.
Align the notch and pin of the sights with the Source center.
3. At the Source, adjust the Source pan (side-to-side) for maximum signal level. Slowly
tighten the 24 mm nut at the bottom of the pan-tilt assembly while holding the left side
of the Source. Verify that the signal level is reduced by 10% or less.
4. At the Source, check the four M6 screws that hold the unit to the pan-tilt assembly.
Verify that the back two screws have been hand-tightened but that the front two have
not. On the pan-tilt assembly, verify that the front and back fine adjust screws are
flush with the assembly surface. Use the housing sights to aim the unit at the center of
the Source. Verify that the Receiver display is 0. If the Receiver does not have
adequate signal from the Source, it may be in fault, depending on fault delay settings.
Put the magnet on the upper right edge of the display over the GM logo. The display
will change from 0 to rst, ---, SE, in, and Pct or AJ. To align the system using AJ, refer
to the Appendix. To align the system using Pct, remove the magnet when Pct
appears. Apply the magnet when Pth appears. Select the units for the path length,
enter the path length (LEn), and whether or not there is an attenuator on the Source
(nAt/At, for 5-30m range systems only), whether or not there is a visible light filter on
the Source (nLF/LF), and Fi to finish the Pth menu. The path length entered (LEn)
should be accurate to within ±5% of the actual distance. The Receiver will display a
number that is a percent of expected signal level. Aim for 100 percent or higher. The
minimum acceptable percent is 80. Below 50, the alignment fault F20 will be set.
5. At the Source, lightly tighten the front fine adjust screw until it bottoms out against the
internal tilt lever. Slowly make a small turn to tighten the screw and lower the front of
the Source. Wait a few seconds for the signal level number at the Receiver to settle.
Continue making small turns, waiting after each turn for the signal level number to
settle. Once the signal level number begins to decline, back out the front fine adjust
screw until it is flush with the assembly surface. Lightly tighten the back fine adjust
screw until it bottoms out, and then slowly make a small turn to further tighten it. Wait
a few seconds for the signal level number to settle. Continue until the signal level
reaches its maximum and begins to decline. Back out the back fine adjust screw.
6. Secure all four M6 mounting screws, tightening them gradually and alternately in a
crisscross pattern to minimize change in alignment. Verify that signal level is reduced
by 10% or less (increase of any amount is acceptable). To complete alignment, all
four M6 mounting screws and the 24 mm nut of the pan/tilt assembly must be
fully tightened and secure.
7. With the Source secure, repeat steps 3 through 6 for the Receiver. The Pct should be
at least 80 percent. Aim for 100 percent or higher.
8. Once adjusts are done and the signal level has been maximized, put the magnet on
the upper right edge of the display to exit alignment mode. The unit will display a
flashing AC and begin zeroing the gas reading. Once zeroing is complete, the unit will
display 0C, followed by the gas concentration. To complete alignment, 0C must be
displayed. With all screws secured on both units, once 0C is displayed, system
alignment is complete.
xii
Model IR5500
Quick Start Guide
Response Test
After initial alignment, a test of the IR5500 should be carried out using the test gas films
for methane or propane (part numbers 329083 or 329084, respectively). Follow the
instructions listed on the films.
xiii
Model IR5500
1.0 Introduction
1.1
Protection for Life
General Monitors’ mission is to benefit society by providing solutions through
industry leading safety products, services, and systems that save lives and protect
capital resources from the dangers of hazardous flames, gases, and vapors.
This manual provides instruction for installing and operating General Monitors’
Model IR5500 for combustible gas detection. It should be read in full and the
information contained herein understood before attempting to place the system in
service.
The safety products you have purchased should be handled carefully and installed,
calibrated, and maintained in accordance with the respective product instruction
manual. Remember these products are for your safety.
Special Warnings
The Model IR5500 Infrared Open Path System contains components which can be
damaged by static electricity. Special care must be taken when wiring the system
to ensure that only the connection points are touched.
WARNING: Toxic, combustible, and flammable gases and vapors are dangerous.
Extreme caution should be used when these hazards are present.
Do not open when an explosive atmosphere is present.
Potential electrostatic charging hazard. Use only a damp cloth for
cleaning.
CAUTION: Read and understand this instruction manual before operating or
servicing the equipment.
Seal all conduits within 18 inches of enclosure.
Use wire suitable for 16°C above ambient for the Receiver and 32°C
above ambient for the Source.
Figure 1: IR5500 Open Path Gas Detector
1
Model IR5500
1.2
Features and Benefits
The advantageous features and benefits of the Model IR5500 Infrared Open Path
System include:
Performance certified: only open path detector to meet multiple agency
performance requirements on both the LEL•meter and ppm•meter scales.
Single detection beam: eliminates drift and false alarms.
Parts-per-million accuracy: sensitive to low-level leaks.
Unitized design - digital readout, 4 relays and two 4 to 20 mA outputs:
wide variety of outputs.
Type 4X, IP66/IP67 weatherproof rating: highly durable unit.
Fail-to-safe operation: alerts user to fault in operation.
Automatic gain control: compensates for dirty optics, rain, and fog.
Power supply input reversal protection: protection against miswiring
damage.
Dirty Window delay and Beam Block delay: reduces maintenance and
false alarms.
1.3
Applications
This is a partial list of applications suitable for the Model IR5500 Infrared Open
Path System:
Compressor stations
Drilling and production platforms
Fence line monitoring
Fuel loading facilities
Gas turbines
LNG/LPG processing and storage facilities
Petrochemical plants
Tank farms
Wastewater treatment
2
Model IR5500
1.4
System Integrity Verification
Commissioning Safety Systems
Before power up, verify wiring, terminal connections and stability of mounting for all
integral safety equipment including, but not limited to:
Power supplies
Control modules
Field detection devices
Signaling or output devices
Accessories connected to field and signaling devices
After the initial application of power and any factory specified warm-up period to the
safety system, verify that all signal outputs to and from devices and modules, are
within the manufacturers’ specifications. Initial alignment, alignment checking, and
testing should be performed according to the manufacturers’ recommendations and
instructions.
Proper system operation should be verified by performing a full, functional test of
all component devices of the safety system, ensuring that the proper levels of
alarming occur. Fault detection should be verified.
Periodic Testing of Field Devices
Periodic testing or alignment should be performed per the manufacturers’
recommendations and instructions. Testing and alignment procedures should
include, but not be limited to:
Verify zero reading
Verify gas reading by applying a Test Gas Film
Verify integrity of all optical surfaces and devices
When testing produces results outside of the manufacturers’ specifications, repair,
or replacement of the suspect device(s) should be performed as necessary. Test
intervals should be independently established through a documented procedure,
including a verification log maintained by plant personnel or third party testing
services.
Periodic System Verification
The following system verifications should be performed at least annually:
Wiring, terminal connections and stability of mounting
Proper system operation verified by performing a full, functional test
of all component devices of the safety system, ensuring that the
proper levels of alarming occur
Fault circuit operation
3
Model IR5500
2.0 Product Description
2.1
General Description
The Model IR5500 Infrared Open Path System is a hydrocarbon gas detector
(Figure 1). The system consists of a Source and a Receiver. Both units are
calibrated at the factory and need no further alignment. The operation of the Model
IR5500 can be checked by placing a Test Gas Film in front of the Receiver. The
system requires only a periodic cleaning of the windows to assure dependable
performance, and is recommended prior to zero check, test gas, and optical
integrity testing. The Model IR5500 Infrared Open Path System continuously
monitors hydrocarbon gases. The gas detection range of a Receiver calibrated for
methane is 0 to 5,000 ppm•m and 0 to 5 LEL•m while that for propane it is 0 to
2,000 ppm•m and 0 to 1 LEL•m. The Receiver provides two 4 to 20 mA analog
signals, one proportional to ppm•m and the other to LEL•m. Alarm and Fault
relays, split range (A/O-ppm), Modbus, and HART outputs are optional.
The Model IR5500 Infrared Open Path System is easily aligned using the digital
display and adjustable mounting arms, therefore does not require any bulky setup
equipment such as digital volt meters and handheld alignment aids. For setups that
require the distance from the Source to the Receiver to be greater than 100
meters, General Monitors offers an optical alignment scope that makes the initial
alignment easier.
Prior revisions of the product were marked as the Ultima OPIR-5 Detector.
2.1.1 Infrared Detection Principles
Most gases absorb infrared radiation. Hydrocarbon gases absorb infrared radiation
at specific wavelengths but with different degrees of absorption. Absorption of the
radiation follows the Beer-Lambert Law, which states that the transmittance (T) of
radiation through an absorbing medium decreases exponentially by the product of
the absorption coefficient (A), the concentration (C), and the path length (L):
T = T0 exp(-ACL)
Here T0 is the transmittance of light containing no absorbing medium.
2.1.2 IR5500 Detection Method
The Model IR5500 uses a single beam, dual wavelength method of infrared
absorption detection. The gas absorbs one wavelength but not the other, which is
the reference wavelength. By comparing the signals from these two wavelengths,
the detector measures gas concentration. The reference wavelength is chosen to
compensate for interferences that can otherwise occur from atmospheric variation,
such as humidity, rain, dust, snow, fog, steam, and temperature. This method of
detection comes under what is commonly known as the non-dispersive infrared
(NDIR) absorption principle.
4
Model IR5500
NOTE: Extremely dense fog, steam or interruption of the beam by an object or
person may cause a system fault
2.1.3 Measurement Scale
With the Model IR5500 Open Path System, as there is no fixed path length, the
reading is reported in concentration•meter. The Model IR5500 reports
concentrations in the ppm•m range (highly sensitive to low levels of hydrocarbons)
and the LEL•m range (large hazardous levels of hydrocarbons). The Model IR5500
display is auto-ranging. In general, an open path monitor can give similar
responses to large, low concentration gas clouds and small, high concentration gas
clouds as shown below. The Alarm setpoint should be equal to or less than the
reading for a gas concentration of 60% LEL at the target gas cloud length.
Typical gas cloud configuration:
No Wind
Figure 2: Indoor Gas Cloud
Figure 3: Outdoor Gas Cloud
5
Model IR5500
2.1.4 Typical System Gas Cloud Measurements
Example readings of methane gas clouds by the standard Model IR5500 are:
Size of Gas Cloud
IR5500 Display
(ppm•m)
50 ppm x 2 meters
100
25 ppm x 4 meters
100
10 ppm x 10 meters
100
100 ppm x 5 meters
500
50 ppm x 10 meters
500
500 ppm x 5 meters
2500
100 ppm x 25 meters
2500
5% LEL x 1 meter
2500
1% LEL x 5 meters
2500
.5% LEL x 10 meters
2500
Table 1: Readings of Methane Gas Clouds 0-5000 ppm•m Range
Size of Gas Cloud
IR5500 Display
(LEL•m)
20% LEL x 1 meter
0.2
10% LEL x 2 meters
0.2
100% LEL x 2½ meters
2.5
50% LEL x 5 meters
2.5
100% LEL x 1 meter
1.0
50% LEL x 2 meters
1.0
25% LEL x 4 meters
1.0
10% LEL x 10 meters
1.0
Table 2: Readings of Methane Gas Clouds 0-5 LEL•m Range
2.1.5 Control Electronics
Both the Model IR5500 Source and Receiver units operate from a 24 VDC input. This
unregulated 24 VDC is fed to on-board power supplies that produce all necessary voltages
for the Model IR5500 Source and Receiver.
6
Model IR5500
In normal operation, the microprocessor program constantly monitors the two infrared
wavelengths and performs mathematical operations on this information in conjunction with
values obtained during the factory calibration process.
The microprocessor derives output information and feeds it to the digital to analog converter
to produce two 4 to 20 milliampere (mA) signals that are proportional to the 0 to 5,000 ppm•m
and 0 to 5 LEL•m for the methane sensing unit and 0 to 2,000 ppm•m and 0 to 1 LEL•m for
the propane unit. The 4-20 mA signal is converted to gas concentration in % of full scale
using the formula [(Analog Output – 4)/16] * (100% full scale), where Analog Output is the 420 mA signal.
The microprocessor program also monitors aspects of system operation such as supply
voltage and optical path integrity.
7
Model IR5500
3.0
Installation
3.1 Receipt of Equipment
Original shipping containers should be kept for future shipping or storage needs.
Shipping container contents should be carefully removed and checked against the packing
list. If any damage has occurred or there is any discrepancy in the order, please notify
General Monitors as soon as possible. All correspondence with General Monitors must
specify the equipment part number and the serial number.
Each unit is tested by the factory; however, a complete system checkout is suggested upon
initial installation to ensure system integrity.
3.2
Location Considerations
There are no standard rules for placement, since the optimum location varies with each
application.
Some factors to consider when selecting locations are as follows:
The system should be accessible for occasional response checks.
The Receiver should be mounted so that the display is visible to aid in alignment.
Do not mount near strong magnetic fields as degradation of performance may result.
The line of sight between the Source and Receiver should be free from obstructions
such as:
o
a parked truck or moveable machinery
o
frequent human or animal crossings
Although the Source and Receiver are designed to resist radio frequency
interferences, they should not be mounted close to radio sources or similar
equipment.
Mount the Receiver unit so that direct sunlight does not enter the front window.
Locate the units away from concentrated sources of heat.
Mount away from sources of excessive vibration and away from high voltage/high
current power lines.
If the path length is less than 20 meters (65 feet), a Source with an attenuator is
required.
8
Model IR5500
3.3
System Mounting
The Model IR5500 units are shipped with either mounting assembly shown in Figure 4. After
the mounting location has been established, mount the support arm/base. Attach a pan-tilt
assembly to each unit. Apply lithium grease on each taper joint before attaching a unit to a
support arm/base. Add the supplied bolt and washers; do not tighten until unit is fully
adjusted. If the bolt has been tightened and further adjustment is necessary, loosen the bolt
two turns and use a screwdriver between the pan-tilt assembly and arm to release the taper.
Arm Assembly with Fine Adjustments
Basic Arm Assembly
Base Assembly with Fine Adjustments
Figure 4: Outline and Dimensional Drawing with Mounting Options
9
Model IR5500
3.4
1.
Installation
If necessary, remove the pan-tilt assembly from the arm. To do so, unscrew the 24 mm
nut from the bottom of the pan-tilt. Remove the lock washer and flat washer. Put the
washers and the nut in a secure place.
2. Put the source or the receiver unit on a work surface with the 4 mounting holes facing
up. Align the 4 mounting holes of the pan-tilt assembly with those on the unit. Verify
that the gap in the mounting surface of the pan-tilt assembly is across the unit rather
than from front to back. Apply a small amount of anti-seize lubricant (p/n 2421) to the
first few threads of each M6 screw. A packet of lubricant is included with the pan/tilt
assembly. Without lubricant, alignment will be more difficult, and bolts may seize.
Install the 4 screws without tightening the front two. Hand-tighten the back two screws.
3. Mount the unit and pan-tilt assembly on the arm. Install the washer, the lock washer,
and the 24mm nut to the bottom of the pan-tilt assembly, without tightening the nut.
4. Verify that the front and back fine adjust screws for tilt are flush with the assembly
surface, to allow full movement of tilt. If necessary, use a 2.5 mm hex wrench to adjust
the screws.
Figure 5: Installation onto Mounting Arm
10
Model IR5500
3.5
Conduit Sealing
Each conduit run from a hazardous to a non-hazardous location should be sealed so that gas
or flames cannot pass from one electrical installation to another through the conduit system.
A conduit seal must also be installed within 18 inches of the Source and Receiver enclosure if
installed in a Division 1 location. A conduit seal may not be required if installed in a Division 2
location.
General Monitors requires the use of a drain loop or conduit seal in the conduit to prevent
moisture from entering the unit housing. For installation in a Division 2 location using Division
2 wiring methods, a drain loop or conduit seal may not be required. Consult Article 501 of the
NEC for details.
WARNING:
The conduit entries should be sealed per the NEC 501.15 or Canadian
Electrical Code Handbook (Part 1, Section 18-154) for Division 1 installations.
WARNING:
Unused cable entry holes must be sealed with an approved explosion-proof
stopping plug.
CAUTION: Acetic acid will damage metal components, hardware, and other components.
If damage results from the use of a sealant that outgases acetic acid such as a
room temperature vulcanizing sealant (RTV), the two-year warranty will be
void.
CAUTION: Consult the manufacturer for dimensional information on the flameproof joints
for repair.
3.6
Terminal Connections
To make the wiring connections to the Model IR5500, loosen the retaining screw on the cover
of each unit using the supplied hex wrench and unscrew the rear cover. All output
connections are made inside the housing (see figures on following page for terminal block
locations). Stripping length is 4/10” (10 mm) for push terminals, ½” (11 mm) for screw
terminals.
NOTE: Contact with printed circuit board (PCB) components should be avoided to prevent
damage by static electricity.
11
Model IR5500
Figure 6: Source Wiring
12
Model IR5500
Figure 7: Receiver Wiring
13
Model IR5500
15
16
COM
14
RST
COM
13
COM
12
0-20mA P
11
0-20mA L
10
COM
+24V
9
8
MOD1-
Modbus1-
Modbus2-
MOD2-
17
7
MOD1+
Modbus1+
Modbus2+
MOD2+
18
Normally
Deenergized
Normally
Energized
Normally
Energized
Normally
Deenergized
6
A2
Alarm NO
Alarm NC
Fault NO
Fault NO
FLT1
19
5
AC
Alarm C
Alarm C
Fault C
Fault C
FLTC
20
4
A1
Alarm NC
Alarm NO
Fault NC
Fault NC
FLT2
21
3
W2 L
Warn
LEL•m NO
Warn
LEL•m NC
Warn
ppm•m NC
Warn
ppm•m NO
W2 P
2
WC L
Warn
LEL•m C
Warn
LEL•m C
Warn
ppm•m C
Warn
ppm•m C
WC P
1
W1 L
Warn
LEL•m NC
Warn
LEL•m NO
Warn
ppm•m NO
Warn
ppm•m NC
W1 P
Table 3: Receiver Wiring Terminal Locations
3.6.1 Terminal Block Operation
To connect wiring to the terminal block, insert a screwdriver into the orange tab
and press down, opening the terminal (see Figure ). Insert the wire into the
terminal and release the orange tab, clamping the wire in the terminal. Check
the clamp by GENTLY tugging the wire to ensure it is locked in. Make sure that
the terminal clamps on to the wire, not the insulation.
14
22
23
24
Model IR5500
Figure 8: Terminal Block Operation Diagram
The push terminal block is designed to accept 24 AWG to 16 AWG (0.2 mm2 to 1.5
mm2) stranded or solid-wire. The optional screw terminal block accepts 26 AWG to
14 AWG (0.14 mm2 to 2.5 mm2 ) wire.
Primary DC voltage power must be provided by the customer. Since the Model
IR5500 Infrared Open Path System is designed to continuously monitor for leaks of
combustible gas, a power switch is not included to prevent accidental system
shutdown. Power must remain disconnected until all other wiring connections are
made.
3.6.2 Terminal Functions
Reset
The Model IR5500 provides external Reset Switch terminations to allow remote
resetting of the alarms. Connect each end of a normally open SPST momentary
switch to RST and COM (refer to Table 3). To reset a latched relay, simply press
and release the switch.
Relays
Inductive loads (bells, buzzers, and relays) on dry relay contacts must be clamped
as shown in Figure 6. Unclamped inductive loads can generate voltage spikes in
excess of 1,000 volts. Spikes of this magnitude may cause false alarms and contact
damage.
NOTE: All relay states shown with power applied.
15
Model IR5500
Figure 6: Relay Contact Protection for AC/DC Loads
3.7
Applying Power and Alignment
3.7.1 Start-Up Checklist
Prior to starting the system, perform the following steps:
Inhibit any external devices, such as a trip amplifier, a PLC, or a DCS
system.
Verify that optional settings are correct.
Verify that the unit is properly mounted. Ensure the conduit/cable gland
entries are pointed downward.
Verify that the signal wiring is correct.
Verify that the power supply is connected properly. The Model IR5500 is
powered by +24 VDC.
Make sure the cover is securely installed or the area has been
declassified.
3.7.2 Startup
Before applying power to the system for the first time, all wiring connections should
be checked and the housing cover securely fastened.
Display Sequence on Power Up
Display
Duration
000
1 second
8.8.8. (Test all segments)
2 seconds
blank
3 seconds
Software revision letter
2 seconds
SU (Start Up)
2 minutes
0 (Gas Concentration)
Ongoing
16
Model IR5500
The IR5500 contains a heater circuit to remove condensation from the windows.
The unit should be allowed to stabilize for approximately two hours before
continuing with the setup mode.
The resolution of the display is the either 0.1 LEL·m or 100 ppm·m. Since HART,
Modbus, and 4-20 mA outputs have more resolution, the least significant digit of
the displayed value might not agree with that of other outputs.
3.7.3 Alignment and Adjustment
Ensure that there is no significant amount of background gas when the unit is
setting the zero value, as this will alter the Model IR5500’s performance. If there is
gas present, try setting-up the IR5500 on a breezy day, as this dissipates the gas.
Alignment Outline
Verify that the beam path is clear of all obstruction and that unit optics are
clean.
Adjust units for maximum signal.
Adjust the Source first, then the Receiver.
Adjust pan first, then tilt.
Make sure that mounting screws are fully tightened.
Make sure that the Receiver displays 0C to complete alignment.
1. It is recommended that two people are involved in alignment. One person
should be at the Source and one person should be at the Receiver. An
alignment scope is helpful but not necessary.
2. At the Receiver, check the four M6 screws that hold the unit to the pan-tilt
assembly. Ensure that a small amount of anti-seize lubricant (p/n 2421) has
been applied to the first few threads of each M6 screw. A packet of the lubricant
is included with the pan/tilt assembly. Without lubricant, alignment will be more
difficult, and bolts may seize. Verify that the back two screws have been handtightened but that the front two have not. Hand-tighten the 24 mm nut for the
pan-tilt assembly. On the assembly, verify that the front and back fine adjust
screws are flush with the assembly surface, to allow full movement of tilt. If
necessary, use a 2.5 mm hex wrench to adjust the screws. Align the notch and
pin of the sights with the Source center.
3. At the Source, adjust the Source pan (side-to-side) for maximum signal level.
Slowly tighten the 24 mm nut at the bottom of the pan-tilt assembly while
holding the left side of the Source. Verify that the signal level is reduced by 10
% or less.
4. At the Source, check the four M6 screws that hold the unit to the pan-tilt
assembly. Verify that the back two screws have been hand-tightened but that
the front two have not. On the pan-tilt assembly, verify that the front and back
fine adjust screws are flush with the assembly surface. Use the housing sights
to aim the unit at the center of the Source. Verify that the Receiver display is 0.
If the Receiver does not have adequate signal from the Source, it may be in
17
Model IR5500
fault, depending on fault delay settings. Put the magnet on the upper right edge
of the display over the GM logo. The display will change from 0 to rst, ---, SE,
in, and Pct or AJ. To align the system using AJ, refer to the Appendix. To align
the system using Pct, remove the magnet when Pct appears. Apply the magnet
when Pth appears. Select the units for the path length, enter the path length
(LEn), and whether or not there is an attenuator on the Source (nAt/At, for 530m range systems only), whether or not there is a visible light filter on the
Source (nLF/LF), and Fi to finish the Pth menu. The path length entered (LEn)
should be accurate to within ± 5% of the actual distance. The Receiver will
display a number that is a percent of expected signal level. Aim for 100 percent
or higher. The minimum acceptable percent is 80. Below 50, the alignment
fault F20 will be set.
5. At the Source, lightly tighten the front fine adjust screw until it bottoms out
against the internal tilt lever. Slowly make a small turn to tighten the screw and
lower the front of the Source. Wait a few seconds for the signal level number at
the Receiver to settle. Continue making small turns, waiting after each turn for
the signal level number to settle. Once the signal level number begins to
decline, back out the front fine adjust screw until it is flush with the assembly
surface. Lightly tighten the back fine adjust screw until it bottoms out, and then
slowly make a small turn to further tighten it. Wait a few seconds for the signal
level number to settle. Continue until the signal level reaches its maximum and
begins to decline. Back out the back fine adjust screw.
6. Secure all four M6 mounting screws, tightening them gradually and alternately in
a crisscross pattern to minimize change in alignment. Verify that signal level is
reduced by 10% or less (increase of any amount is acceptable). To complete
alignment, all four M6 mounting screws and the 24 mm nut of the pan/tilt
assembly must be fully tightened and secure.
7. With the Source secure, repeat steps 3 through 6 for the Receiver. The Pct
should be at least 80 percent. Aim for 100 percent or higher.
8. Once adjusts are done and the signal level has been maximized, put the
magnet on the upper right edge of the display to exit alignment mode. The unit
will display a flashing AC and begin zeroing the gas reading. Once zeroing is
complete, the unit will display 0C, followed by the gas concentration. To
complete alignment, 0C must be displayed. With all screws secured on both
units, once 0C is displayed, system alignment is complete.
3.7.4 Response Test
After initial alignment, a test of the IR5500 should be carried out using the Test Gas
Films for methane or propane (part numbers 329083-1 or 329084-1, respectively).
Follow the instructions on the films.
3.7.5 Visible Light Filter
One of the ModeI IR5500’s configurations is equipped with a visible light filter
(Figure 7). Such configuration can prove useful in installations where an intermittent
light beam is considered disruptive to surrounding operations. A visible light filter
blocks light in the visible portion of the electromagnetic spectrum, allowing the
instrument to detect and measure hydrocarbon gas concentrations without the
attendant effects of flashing light.
18
Model IR5500
IR5500 detectors with a visible light filter should be installed as described in the
installation section. Without the flashing light as a guide for alignment, users may
need to use the Long Range Alignment Kit (part number 329082-1) to establish
orientation and positioning of the receiver and source. The kit is recommended for
separations of 50 meters or more.
Visible light filters should not be removed from the IR5500. The filters are attached
at the factory with a protective seal that prevents ingress of water or dust into the
Source. If removed by accident, the Source should be returned to the factory for
repair.
Figure 7: IR5500 Source with Visible Light Filter
3.8 Operational Cautions
WARNING: During operation, the line of sight between the Source and the Receiver
should be free from blockage caused by frequent human or animal
crossings. The IR5500 will not respond to gas leaks upon complete IR
beam blockage. Interruptions of the IR beam will delay the
response time of this unit, and thus lead to a potentially unsafe
situation.
The Heavy Hydrocarbon version of the Model IR5500 Open Path System performs
accurately and reliably for propane gas detection applications in extreme industrial
environments. However, under certain conditions, the Heavy Hydrocarbon IR5500
could give a beam block indication rather than a gas reading or alarm.
3.8.1 Rapid and Massive Liquid Propane Releases
A sudden release of a large amount of liquid propane can form very cold gas clouds
due to cooling resulting from gas expansion and liquid propane evaporation. This is
an intrinsic problem for all open path optical detection technologies. Installing the
Model IR5500 at a distance of at least 10 meters from potential liquid propane
leakage will reduce this problem.
3.8.2 Solutions to Guard against These Situations
Use complementary point detectors such as Models IR400, S4000CH, or
S4100CH at potential sources of leaks of high concentration liquid propane
19
Model IR5500
Use the beam block signal as an alarm. To reduce the number of false
alarms due to an actual physical beam block, there are user selectable time
delays. A signal will then be given if a beam block exceeds the specified
time delay.
The ppm•m range of the IR5500 should be used as a warning that there is a gas
leak. This may allow action to take place before a leak reaches a hazardous level,
while the LEL•m range should be used for a gas leak alarm.
NOTE: The IR5500 will detect hydrocarbons other than methane and propane.
Consult the manufacturer for details regarding sensitivity to other
hydrocarbons.
20
Model IR5500
4.0
Operation
The Model IR5500 Open Path Gas Detector front panel includes an LED digital
display, Alarm and Warning LEDs, and displays a set of menu options that provide
the user with the most flexible detector system possible. In addition to the IR5500
menu options for operations and configuration tasks, there is an extensive set of
Modbus and HART commands for the same tasks that can be sent from remote
Modbus and HART devices in control room areas.
The IR5500 menu options are described in detail in this section.
Modbus commands are described in a separate Modbus programming
manual available for download from the General Monitors website.
HART commands are described in the HART Field Device Specification
available for download from the General Monitors website.
4.1
Using the IR5500 Menus
The IR5500 menus allow the user to complete many operational tasks.
Start the alignment of the Source and Receiver or initiate a gas check via
Test Gas Mode.
Configure the % LEL required to generate a Warning or Alarm, as well as
the warning and alarm relay settings for Energized/De-energized and
Latching/Non-Latching.
Configure Modbus or HART communication settings.
Select mirror image option for display (FLP).
Select delays for beam block fault.
21
Model IR5500
LEL or PPM
##
RM
HM
M
rSt
HM
T
---
HM
RM
SE
HM
in
HM
Pct
HM
Log
HM
Fi
T
T
r
###
bb
Main Menu
rSt
Reset relays
--Gas check
SE
Setup
in
Flash Input data
Pct
% Signal for Alignment
Log Fault Log
Fi
Finish
T
diS
M
T
Ao1
T
Setup Menu
bb
Beam block > delay times
diS
Display > Pct / AJ, Std / Flip
Ao1 4-20 mA LEL-m > HART, fault levels,
enable / disable
Ao2 4-20 mA ppm-m > on / off
rLY Relays > on / off
AL1 Warn ppm-m > energized, latching, setpoint
AL2 Warn LEL-m > energized, latching, setpoint
AL3 Alarm LEL-m > energized, latching, setpoint
CH1 Channel 1 Modbus > baud, format, address
CH2 Channel 2 HART > on / off
Ao2
T
rLY
T
AL1
T
AL2
T
IR5500 MENU LEGEND
AL3
XXX
STATIC MENU OPTION
XXX
FLASHING MENU
OPTION
T
CH1
T
HM
HOLD MAGNET
CH2
RM
REMOVE MAGNET
M
T
T
T
Fi
M
Figure 8: IR5500 Main Menu Tree
22
APPLY MAGNET
TIMEOUT
Model IR5500
4.2
Menu Options
The Model IR5500 allows the user to reset, test, and align the system as well as
configure Receiver outputs. To access the menu, place the magnet supplied with
the Model IR5500 over the General Monitors logo on the label of the Receiver for
approximately five seconds. The display will cycle between the options. Remove
the magnet to select an option. These options are:
“rSt” – Reset relays
“---” – Gas check
“SE” – Setup
“in” – Flash Input data
“Pct” – % signal for alignment
“Log” – Fault log and zero offset
“Fi” - Finish, return to normal operation
4.3
Test “---”
Apply the magnet when the flashing bars are showing and the unit enters Test
Mode. While the unit is in this mode the optical faults and relays will be inhibited, the
analog output will drop from 4 mA to 1.5 mA and the display will flash.
This mode allows the user to check the IR5500 response to a Test Gas Film without
activating the relays and analog outputs. After verifying the response, remove the
Test Gas Film. The unit will return to normal operation. If the Test Gas Film is not
removed after 5 minutes, the unit will revert to a fault condition. If left in this mode
for 5 minutes without a Test Gas Film, the unit will return to normal operation
automatically.
To abort Test Mode before the gas has been applied, reapply the magnet and the
unit will return to normal operation.
4.4
Setup “SE”
Apply the magnet when “SE” is showing and the unit enters Setup.
This mode allows the user to change various unit attributes. Following is the order in
which the options are displayed (to change, apply magnet when the desired option
is showing):
Fi - Exits the current option and goes on to next.
bb - Beam Block and IR Flash Intensity fault delay settings
23
Model IR5500
AOd – Analog Output delay
0, 1, 2…10, 15, 20, 25… 60 - Seconds before the F1 fault code becomes
active. Ao1 level changes to bbF, and the Receiver displays fault code F1.
oFd – Output Fault delay
0 to 60 - Minutes before the F3 fault is active. The Ao1 level changes from
bbF to dEt, and the displayed fault code changes from F1 to F3.
ind – IR Input Fault delay
0 to 60 - Minutes before the F12 fault is active. The Ao1 level changes to
inF, and the Receiver displays fault code F12.
diS – Display options
Pct / AJ – Display alignment signal strength displayed as percent expected
(Pct) or as a logarithm of signal strength during adjustment (AJ).
Std / FLP – Display standard or flipped as a mirror image, for reading via
mirror when the display is close to a pipe, tank, wall, or other surface.
24
Model IR5500
Default values are in red
Beam Block Menu
LEL or PPM
##
RM
HM
M
rSt
HM
---
HM
HM
SE
HM
in
Pct
HM
HM
Log
Fi
RM
T
T
T
r
T
###
M
T
T
AOd
bb
T
M
5
T
M
Pct
AJ
T
M
5
M
M
T
M
10
Fi
M
M
T
M
diS
ind
oFd
M
M
T
T
Std
FLP
T
Fi
T
Ao1
bb: Beam Block Menu
AOd: Analog Output delay (4 mA to bbF mA).
AOd values 0, 1, 2,...8, 9, 10, 15, 20, 25,...60 seconds
T
Ao2
oFd: Output delay (bbF mA to dEt mA).
oFd values 0, 1, 2,...8, 9, 10, 15, 20, 25,...60 minutes
T
rLY
ind: Flash input fault delay (4 to inF mA).
ind values 0, 1, 2,...8, 9, 10, 15, 20, 25,...60 minutes
T
Alarm menus
T
diS: Signal Display Menu
Pct: Display alignment signal level as % of expected
AJ: Display alignment signal level as AJ (legacy)
CH1
FLP: Flip (reverse) display
T
CH2
T
T
Fi
M
Figure 9: IR5500 Beam Block Menu Tree
25
Model IR5500
Ao1 – Apply magnet when this code is showing to alter the options for Analog
Output #1 for LEL-m.
For HART 1.25 mA and Dual Modbus Receivers, the fault levels for Ao1 are
adjustable.
Each fault code is in one of four fault output levels
bbF
Beam block fault
F1 Close to Low IR
dEt
ELc
inF
Detection fault
Electronics fault
IR Input fault
F0 Excessive Drift
F5 Setup Menu
F4 Flash Erratic
F3 Beam Block / Low IR
F6 Receiver Low Supply
Voltage
F12 Optical Signal
Variation
F10 Relay Reset Short
F16 High IR
F7 Code Checksum
F8 Fault While Zeroing
F9 Gas Left
F13 Memory
F18 Dirty Lens
F20 Alignment
F21 Zeroing
F22 RAM
F11 Receiver Overheating
F14 AO1 LEL-m Circuit
F15 Receiver Heater
F19 Magnet Switch
F23 Hardware Revision
F24 Temperature Sensor
F25 AO2 ppm-m Circuit
tF6 Source Low Supply
Voltage
tF7 Source Heater
tF8 Source Overheating
26
Model IR5500
EdF (Enable / disable non-critical faults)
0: Enable all faults
1: Disable Close to Low IR (F1)
2: Disable Dirty Optics (F18)
3: Disable Close to Low IR (F1) and Dirty Optics (F18)
4: Disable Heater fault (F15)
5: Disable Closer to Low IR (F1) and Heater fault (F15)
6: Disable Dirty Optics (F18) and Heater fault (F15)
7: Disable Close to Low IR (F1), Dirty Optics (F18), and Heater (F15)
SPL – Split-Range - on or off
Refer to “Split-Range Analog Output Option” in the appendix.
Std / FLP – Display standard or flipped as a mirror image, for reading via mirror
when the display is close to a pipe, tank, wall, or other surface.
Ao2 - Analog #2 for ppm-m on or off (Not available if Split-Range is on)
27
IF ANALOG OUT 1
SPLIT IS OFF
Model IR5500
Figure 10: IR5500 Analog Output Menu Tree
rLy – Relay
Password required to turn relays off: u19, ^61
AL1 - Alarm Relay #1 (0-5,000 / 0-2,000 ppm•m)
En or dE - Energized or De-energized.
LA or nL - Latching or Non-Latching.
2000 to 4500 - Alarm level, increments by 100 or
28
Model IR5500
800 to 1800 - Alarm level, increments by 100.
(Value increments each time magnet is applied)
(The ppm-m values are displayed in hundreds. For example, 2000 ppm-m
is displayed as 20.)
AL2 - Warn Relay #2 (0-5 / 0-1 LEL•m)
En or dE - Energized or De-energized.
LA or nL - Latching or Non-Latching.
0.5 (0.1) to AL3 - Alarm level, increments by 0.1.
(Value increments each time magnet is applied)
AL3 - Alarm Relay #3 (0-5 / 0-1 LEL•m)
En or dE - Energized or De-energized.
LA or nL - Latching or Non-Latching. If this relay is set to “nL” (nonLatching), the IR5500 must be connected to an auxiliary system which is
able to provide the same function as a latching relay i.e. the alarm can only
be reset manually.
AL2 to 4.5 (1.8) - Alarm level, increments by 0.1.
(Value increments each time magnet is applied)
29
Model IR5500
Default values are in red
Alarm Menu
LEL or PPM
##
RM
HM
M
rSt
HM
T
---
HM
RM
SE
HM
HM
in
HM
Pct
Log
HM
Fi
T
T
r
###
bb
T
relay set
password 1
Other menus
T
M
M
M
M
on
oFF
rLY
Alarm Menus
En: Energized
dE: De-energized
La: Latching
nL: Non-latching
relay set
password 2
T
T
T
M
u##
T
^##
Fi
M
T
M
M
En
dE
AL1
T
La
nL
M
relay setpoint (methane default*)
La
nL
M
relay setpoint (methane default*)
M
En
dE
AL3
Fi
L1.5
M
M
T
La
nL
T
T
T
Only if rLY is on
M
M
M
En
dE
AL2
Fi
P45
M
T
T
T
T
Only if rLY is on
M
T
relay setpoint (methane default*)
M
T
T
T
T
L3.0
Fi
T
Only if rLY is on
Other
menus
T
T
*Propane defaults are
P18
L0.3
L0.6
Fi
M
Figure 11: IR5500 Alarm Menu Tree
30
M
M
Model IR5500
CH1 – Channel 1 Modbus
br – baud rate – 2.4, 4.8, 9.6, 19.2, or 38.4 kbps
For – Format – 8n1, 8E1, 8o1, or 8n2 – bits, parity (none, Even, odd),
stop bits
Add – Address
CH2 – Channel 2 HART
HART
on or off
31
Model IR5500
Default values are in red
Channel Menu
LEL or PPM
##
RM
HM
M
rSt
HM
T
--RM
HM
HM
SE
HM
in
Pct
HM
HM
Log
Fi
T
T
r
###
bb
T
Other menus
M
T
T
M
br
CH1
Channel Menus
CH1: Channel 1 Modbus
br: baud rate
For: Format
Add: Address
T
T
T
For
T
M
T
M
Add
T
M
9.6
8n1
1
M
M
M
CH2: Channel 2 HART
T
T
M
CH2
Hrt
T
M
Fi
M
M
on
oFF
T
Fi
M
Figure 12: IR5500 Channel Menu Tree
32
T
Fi
M
Model IR5500
4.5
Flash Input “in”
The flash input data is used to diagnose issues such as poor alignment, path interference, and aging
Source lamp.
The rSd is the relative standard deviation of reference flash input intensity. The rEF is the average
reference flash intensity. An rSd > 60 for ind time sets fault F12. An rSd ≤ 60 resets fault F12. The
rSd and rEF values are updated every 30 seconds
33
Model IR5500
Flash Input Menu
LEL or PPM
##
RM
HM
M
rSt
HM
---
HM
SE
HM
in
HM
Pct
HM
Log
HM
Fi
RM
rSd
T
###
T
rEF
T
T
###
in: Flash Signal Input Menu
The flash input data is used to diagnose poor
alignment, path interference, aging Source
lamp, etc.
rSd: relative standard deviation of reference
flash input intensity.
### after rSd = 100% x ref stdev / ref average
ref stdev and ref average: standard deviation
and average of reference flash intensity.
rSd > 60 for ind time sets fault F12
rSd ≤ 60 resets fault F12
M
rEF: Reference flash
### after rEF: average reference flash intensity
rSd and rEF are updated every 30 seconds
IR5500 MENU LEGEND
XXX
STATIC MENU OPTION
XXX
FLASHING MENU
OPTION
HM
HOLD MAGNET
RM
REMOVE MAGNET
M
APPLY MAGNET
T
Figure 13: IR5500 Flash Input Menu Tree
34
TIMEOUT
Model IR5500
4.6
Alignment/Adjustment “Pct” or “AJ”
Pth (Path length) – Active only when the display (diS) option in the SE menu is set
for IR input signal is percent of expected (Pct).
AJ is the legacy value for signal strength. Refer to the Appendix for aligning a
system using AJ.
Yd, ntr, ft – Path length units in yards, meters, or feet, where “ntr” is used for meters
instead of “mtr” due to display constraints.
nAt / At – no attenuator / attenuator (5-30 meter range Receivers only).
nLF / LF – no light filter / light filter on the Source.
### or A## -- Alignment signal strength as percent expected (###) or as a logarithm
of signal strength during adjustment (A##).
AC (flashing) – Alignment and zeroing in progress.
0C – Alignment and zeroing is complete.
35
Model IR5500
Default values are in red
Alignment Menu
LEL or PPM
##
RM
HM
M
rSt
HM
HM
---
HM
SE
HM
in
Pct
AJ
HM
HM
Log
Fi
Pct
only
M
M
Pth
M
Yd
ntr
Ft
T
T
Len
M
M
T
RM
T
M
nAT
AT
T
nLF
LF
T
5-30 m range
only
Fi
M
20
###
(A##)
M
AC
Pth: Path Length Menu
Settings to calculate the expected signal level in percent.
Yd, ntr, Ft: units (“ntr” for meters in 7-segment display)
T
0C
T
M
LEn: Path length. The default is the minimum length.
nAt: no Attenuator (5-30 meter range only)
nLF: no visible Light Filter
Alignment and Zeroing
### = Pct = 100% x actual signal level / expected signal level
### flashes for Pct < 80. Pct < 50 sets alignment fault (F20).
A## is the legacy AJ number.
AC: Alignment and zeroing in progress
0C: Alignment and zeroing complete
Figure 14: IR5500 Alignment Menu Tree
36
Model IR5500
4.7
Log – Fault Log and Zero
Zro – The Zero offset. If there is no offset, Zro is 100. Background gas during
zeroing creates Zro > 100. Dirty optics or partial obscuration can make Zro < 100.
## -- Event index, 1 to 10, 1 is most recent.
ddd -- runtime in days. ddd before FLt shows the current runtime.
Fxx -- Fault code for the highest priority fault.
hi FF and lo FF -- High and low bytes of the fault code, to indicate if there is more
than one fault.
hi DD and lo DD -- High and low bytes of the diagnostics code, to provide more
detail on the cause of the fault.
37
Model IR5500
LEL or PPM
##
RM
HM
M
rSt
HM
---
HM
SE
HM
in
HM
Pct
HM
RM
T
Log
HM
T
T
M
r
###
Zro
T
M
##
M
T
Log: Fault Log Menu
Zro: Zero offset
M
ddd
T
## after Zro: Zero offset value. Ideal is 100.
M
FLt
ddd before FLt: Current runtime in days.
T
FLt: Fault
M
##
## after FLt: Event number, 1 to 10, 1 is most recent.
T
ddd before Fxx: Runtime in days at the time of fault.
M
ddd
Fxx: Fault code for the highest priority fault.
T
M
hi FF and lo FF: hi and lo bytes of fault code, to indicate
if there is more than one fault.
Fxx
T
hi DD and lo DD: hi and lo bytes of diagnostic code, to
provide more detail.
hi
.FF
M
lo
FF.
M
hi
.DD
M
lo
DD.
M
T
T
T
T
Figure 15: IR5500 Fault Log Menu Tree
38
Fi
Model IR5500
4.8
Finish “Fi”
Apply the magnet when “Fi” is showing and the unit will exit the Options Mode, save
any changes that were made, and return to normal operation. This is the only way
changes made in Setup Mode are saved.
4.9
Maintenance
After the Model IR5500 has been initially aligned, the unit requires little
maintenance. Although calibration is not required, response should be tested from
time to time using the Test Gas Films designed for the IR5500.
If the Model IR5500 is operated under dusty or dirty conditions, the windows should
be cleaned periodically. This is accomplished by gently wiping them with a soft,
clean cloth, which has had a commercial window cleaning solution applied. Water
and ethanol are suitable solvents. The cleaning should be done in Test Gas Mode to
prevent false alarms.
The estimated mean time between failures (MTBF) for the Source lamp is 4 years.
Should the Source lamp need replacement, use the Lamp Replacement Kit listed in
the Spare Parts section.
The Model IR5500 Gas Detector should be stored in a clean, dry area, and within
the temperature and humidity ranges noted for environmental specifications in
Section 8.2. Insert the red dust caps into any vacant cable entry holes while the unit
is stored.
NOTE: The IR5500 will detect vapors from alcohol and other cleaning solvents.
4.10 Display and Fault Codes
The display codes during normal operation are:
SU
Start-Up - This is displayed immediately after power is applied and lasts for
approximately two minutes.
SF
Re-Start from an optical Fault - This is displayed when an optical Fault
condition has been corrected.
0-50
Steady Numeric Indications - This is displayed when a concentration of gas
is detected in the operational mode.
0-50
Flashing Numeric Indications - This is displayed when a concentration of
test gas is at the detector in the test gas mode.
Other codes that can appear on the display are Fault codes, which are listed in the
following section.
4.11 LEL and ppm Negative Drift Faults
The ppm negative drift fault occurs when the IR5500 is zeroed with a small
background gas and strong air currents dissipate the remaining gas. Under such
circumstances, the ppm range current may decrease to 0 mA, prompting the
detector to produce a fault.
39
Model IR5500
It is unsafe to use the IR5500 when there is negative drift in the LEL range. A LEL
negative drift causes both currents to go to zero and the fault relay to de-energize.
The LEL negative drift may occur when the system is first installed and not yet
aligned.
Negative drift on the ppm range is not a dangerous condition as with a LEL negative
drift. The ppm negative drift does not put the IR5500 into a total fault. Nonetheless,
it returns the ppm current to zero.
40
Model IR5500
5.0 Troubleshooting
If equipment or qualified personnel required to troubleshoot are not available, it is
recommended that the defective unit be returned to General Monitors for repair.
CAUTION: General Monitors’ warranty will be voided if damage results from repair
attempts other than routine replacement of recommended spare parts.
Repairs performed by persons other than General Monitors’ authorized
personnel may void the warranty. Please read the warranty statement
carefully. A defective IR5500 Infrared Open Path System should be
returned to the factory for repair even if the warranty has expired. A
complete written description of the problem should be included with all
returned equipment.
CAUTION: Component level repair must be undertaken either by General
Monitors’ personnel, or by competent authorized service engineers.
SMT PCB repair shall only be performed at a General Monitors facility.
Failure to comply with this requirement will invalidate the warranty.
Be sure to inhibit or disconnect the external alarm wiring before making any check,
which might send the unit into alarm.
5.1 Fault Codes
The Model IR5500 Infrared Open Path System will indicate a fault code number on
the three-digit display as an aid to troubleshooting. The following list identifies the
fault codes, gives a description of the fault, and indicates the corrective action that
should be taken.
Fault
Code
Fault Name
F0
F1
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
Excess Negative Drift
Close to Low IR
Low IR
IR Flash Timing
Setup Menu
Low Voltage Input at Receiver
Code Checksum
Fault during Zeroing
Gas Left
Reset Short
Receiver Overheating
IR Flash Intensity Variation
NVM Checksum
Analog Output for LEL‐m
41
Fault
Code
F15
F16
F18
F19
F20
F21
F22
F23
F24
F25
tF6
tF7
tF8
Fault Name
Receiver Heater
High IR
Dirty Lens
Magnet
Low Alignment Signal
Zeroing
RAM Checksum
Hardware Revision
Receiver Temperature Sensor
Analog Output for ppm‐m
Low Voltage Input at Source
Source Heater
Source Overheating
Model IR5500
All faults have a 10-second delay before activating, unless otherwise noted.
During a fault, the ability of the system to detect gas depends on which fault is
active. Fault groups are to highlight that gas detection is generally disabled during
detection and flash input faults (dEt and inF) and enabled during electrical faults
(ELc). Exceptions are noted. If both types of faults are active, the fault which
prevents gas detection has priority.
Fault
Code
Fault
Group
Can
detect
gas
Fault
Code
Fault
Group
Can
detect
gas
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
dEt
bbF
dEt
dEt
inF
ELc
ELc
dEt
dEt
dEt
ELc
ELc
inF
dEt
Yes
Yes*
No
No
No
Yes
Yes
No
No
No
Yes
Yes
No
No
F14
F15
F16
F18
F19
F20
F21
F22
F23
F24
F25
tF6
tF7
tF8
ELc
ELc
inF
dEt
ELc
dEt
dEt
dEt
ELc
ELc
ELc
ELc
ELc
ELc
No
Yes
No
Yes
Yes
No
No
No
Yes
Yes
No
Yes
Yes
Yes
*The system can detect gas during F1 provided that there is sufficient flash input
signal. The system cannot detect gas if no flash input is received.
5.1.1 F0 Excess Negative Drift
This fault indicates LEL-m < -10% of full scale LEL-m.
ACTION – Clean the optics. Remove any partial blockage in the beam path.
Verify that the distance between the Source and Receiver is greater than the
range minimum. Align the system.
5.1.2 F1 Close to Low IR
This fault indicates that either (1) IR input intensity is within 10% of the Low IR
fault threshold, or (2) IR input intensity is below the Low IR fault threshold and
the output fault delay time (oFd) has not yet elapsed. .
ACTION – Unit windows should be cleaned and the optical path checked for
blockage. If the window is clean and the path is clear, realigning the Source
and Receiver when no background gas is present should correct this fault.
42
Model IR5500
5.1.3 F3 Beam Block
This fault indicates that IR input is below the Low IR fault threshold.
ACTION – The system should be aligned and the optical path should be
checked for blockage or windows cleaned.
5.1.4 F4 IR Flash Timing
Flashes from the Source are erratic.
ACTION – Verify that IR is only from one Source. .
5.1.5 F5 Setup Menu
This fault indicates that the user has not exited the setup menu after 6 minutes
of inactivity.
ACTION – Apply the magnet to exit the setup menu.
5.1.6 F6 Low Voltage Input at the Receiver
ACTION – Ensure the supply voltage at the Receiver is within specification..
5.1.7 F7 Code Checksum
This fault indicates a fault in device program memory.
ACTION – Cycle power. If the fault persists, contact the factory.
5.1.8 F8 Fault during Zeroing
This fault indicates that a fault occurred during zeroing.
ACTION – Repeat zeroing with no faults present.
5.1.9
F9 Gas Left
This fault indicates the unit timed out while in Gas Check Mode.
ACTION – Remove the Test Gas Film and apply the magnet to clear the fault.
5.1.10 F10 Reset Short
This fault indicates that the reset external connection is shorted to ground for
more than 30 seconds.
ACTION – Remove the reset short wire from ground.
43
Model IR5500
5.1.11 F11 Receiver Overheating
This fault indicates that the Receiver unit is over temperature. The IR5500
continues to detect gas but its accuracy is degraded and the long term reliability
is compromised.
ACTION – Ensure that the ambient temperature for the Receiver is within
specification.
5.1.12 F12 IR Flash Intensity Variation
This fault indicates that the flashing signal to the Receiver is unstable.
F12 is most often caused by inadequate alignment. Other causes are partial
obscuration, interference from another Source, interference in the beam path,
and mounting movement or vibration.
ACTIONS
-
Re-align Source and Receiver for maximum signal level.
Remove partial obstructions or move the system so that the beam path
is clear.
Clean optics.
Prevent flash input from another Source by either swapping Source and
Receiver or changing system orientation.
Verify that the Source voltage supply exceeds minimum requirements.
Ensure that mounting for the Source and Receiver is stable.
Review the flash input fault delay time (ind) – see Section 4.4.
5.1.13 F13 Non-Volatile Memory (NVM) Checksum
This fault indicates a fault in device data memory.
ACTION – Cycle power. If the fault persists, contact the factory.
5.1.14 F14 Analog Output for LEL-m
This fault indicates that the Analog Output circuit has malfunctioned.
ACTION – Verify that AO LEL-m output wiring is correct and that the load is
within specification.
5.1.15 F15 Receiver Heater
This fault indicates that the heater in the Receiver has malfunctioned.
ACTION – Verify that the heater is properly connected and cycle power. If the
fault persists, contact the factory.
44
Model IR5500
5.1.16 F16 High IR
IR Flash Input is saturating the Receiver. Receiver displays ‘Aor’.
ACTION – Move the Source and Receiver apart, or for 5-30 meter systems
only, re-install the attenuation plate.
5.1.17 F18 Dirty Lens
Gas output is between -7 % full scale LEL-m and -10 % full-scale LEL-m.
ACTION – Clean the optics, remove any partial obscuration of the beam path,
and re-align the system.
5.1.18 F19 Magnet
The Receiver senses a magnet in place for more than 6 minutes.
ACTION – Remove the magnet from the Receiver. If a magnet is not in place,
remove the Receiver cover and verify that the magnetic switch SW1 on the right
side of the LED Display board was not damaged during wiring.
5.1.19 F20 Low Alignment Signal
The alignment signal was below 50 % of the expected value or AJ was below
20.
ACTION – For Pct, verify that the path (Pth) values in the user menu are
correct. Carefully follow instructions for system alignment for maximum signal
level. Verify that the beam path is clear without any obstruction. Verify that the
beam path length is within the specified range for the system.
5.1.20 F21 Zeroing
The zero offset was excessive, or the IR input during zeroing was unstable.
ACTION – Verify that the optics are clean are mounting is secure for both
Source and Receiver. Align units when there is no ambient gas or beam path
interference, including rain, snow, sand, et cetera.
5.1.21 F22 RAM Checksum
This fault indicates a fault in device data memory.
ACTION – Cycle power. If the fault persists, contact the factory.
5.1.22 F23 Hardware Revision
The hardware revision signal is out of tolerance.
ACTION – Cycle power. If the fault persists, contact the factory.
45
Model IR5500
5.1.23 F24 Receiver Temperature Sensor
The temperature sensor signal is out of range.
ACTION – Ensure that the ambient temperature is within specification. Cycle
power. If the fault persists, contact the factory.
5.1.24 F25 Analog Output for ppm-m
The Analog Output circuit for ppm-m has malfunctioned.
ACTION – Verify that AO output wiring is correct and that the load is within
specification.
5.1.25 tF6 Low Voltage Input at the Source
ACTION – Ensure the supply voltage at the Source is within specification
5.1.26 tF7 Source Heater
The heater in the Source has malfunctioned.
ACTION – Verify that the heater is properly connected and cycle power. If
the fault persists, contact the factory.
5.1.27 tF8 Source Overheating
This fault indicates that the Source is over temperature. The IR5500 continues
to detect gas but its accuracy is degraded and the long term reliability is
compromised.
ACTION – Ensure that the ambient temperature for the Source is within
specification.
5.2 Other Troubleshooting Tips
5.2.1 Source does not flash
-
Verify whether or not the Source is fitted with a visible light filter. A
Source with a visible light filter does not display a flashing light.
Verify that the wiring is correct and that there are no stray wire strands
that could create an intermittent short.
Verify that the voltage at the Source wiring terminal is stable and meets
minimum requirements.
If all above conditions are met and the Source does not flash, replace
the lamp. Detailed instructions are in the lamp replacement kit listed in
the Spare Parts section.
46
Model IR5500
5.2.2 Receiver does not display startup sequence when power is
applied
-
Verify that the power supply is on and that it is set to 24 volts +/- 1 volt.
Verify that the wiring is correct.
Use a voltmeter to check the voltage at the wiring terminal, or remove
the unit and check it using a different supply.
5.2.3 Receiver displays ]-[ during alignment
-
Verify that the Source is aimed at the Receiver and that the Receiver is
aimed at the source.
Verify that the beam path from the Source to the Receiver is free of
obstruction.
On the Receiver and on the Source, with power removed from the
Source, verify that the window on each unit is clean and that an
attenuator is not in place.
5.2.4 Receiver displays F1 or F3 after alignment
-
Verify that the Source is aimed at the Receiver and that the Receiver is
aimed at the source.
Verify that the beam path from the Source to the Receiver is free of
obstruction.
On the Receiver and on the Source, with power removed from the
Source, verify that the window on each unit is clean and that an
attenuator is not in place.
5.2.5 Receiver does not respond to the magnet
-
Try a slightly different location for the magnet.
5.2.6 Receiver signal level number went to 0 with no “A” on the
display
-
Apply the magnet to resume alignment (The alignment mode times out
after 30 minutes)
Stack a second magnet onto the first.
5.2.7 Receiver displays information other than described
-
Refer to the IR5500 Receiver User Menu to apply the magnet and
resume alignment.
5.2.8 Source or Receiver will not move
-
-
Verify that fine adjust screw tops are flush with the assembly surface.
Verify that the two front mounting screws have not been tightened
down.
Verify that the nut at the bottom of the pan-tilt assembly has not been
tightened down.
Insert a large screw driver or rod between the bottom of the unit and the
mounting assembly. Press on it to loosen the mounting.
47
Model IR5500
6.0 Customer Support
Area
Phone / Email
UNITED STATES
26776 Simpatica Circle
Lake Forest, CA 92630
Phone: +1-949-581-4464. 800-446-4872
Email: info.gm@MSAsafety.com
UNITED KINGDOM
Heather Close
Lyme Green Business Park
Macclesfield, Cheshire,
United Kingdom, SK11 0LR
Phone: +44-1625-619-583
IRELAND
Ballybrit Business Park
Galway
Republic of Ireland, H91 H6P2
Phone: +353-91-751175
SINGAPORE
No. 2 Kallang Pudding Rd.
#09-16 Mactech Building
Singapore 349307
Phone: +65-6-748-3488
MIDDLE EAST
PO Box 54910
Dubai Airport Free Zone
United Arab Emirates
Phone: +971-4294 3640
Table 4: Locations
Additional locations can be found on our web site, www.MSAsafety.com
48
Model IR5500
7.0 Appendix
7.1
Warranty
General Monitors warrants the Model IR5500 to be free from defects in workmanship or
material under normal use and service within two years from the date of shipment.
General Monitors will repair or replace without charge any such equipment found to be
defective during the warranty period. Full determination of the nature of, and responsibility for,
defective or damaged equipment will be made by General Monitors’ personnel.
Defective or damaged equipment must be shipped to the General Monitors plant or
representative from which the original shipment was made. In all cases, this warranty is limited
to the cost of the equipment supplied by General Monitors. The customer will assume all
liability for the misuse of this equipment by its employees, or other personnel.
All warranties are contingent upon proper use in the application for which the product was
intended and do not cover products which have been modified or repaired without General
Monitors’ approval or which have been subjected to neglect, accident, improper installation or
application, or on which the original identification marks have been removed or altered.
Except for the express warranty stated above, General Monitors disclaims all warranties with
regard to the products sold, including all implied warranties of merchantability and fitness, and
the express warranties stated herein are in lieu of all obligations or liabilities on the part of
General Monitors for damages including, but not limited to, consequential damages arising out
of, or in connection with, the performance of the product.
49
Model IR5500
7.2
Specifications
7.2.1 System Specifications
Sensor Type:
Infrared
Gas Detected:
Methane or Propane
Dual Measuring Range: Methane Light Hydrocarbon Unit:
0 to 5,000 ppm•m and 0 to 5 LEL•m
Propane Heavy Hydrocarbon Unit:
0 to 2,000 ppm•m and 0 to 1 LEL•m
Response Time:
T90 ≤ 3 seconds
Accuracy:
≤ ± 5% of full scale concentration at 25°C
Repeatability:
≤ ± 5%
Linearity:
≤ ± 5% of full scale for each scale
Or ± 10% of applied gas concentration, whichever is greater
Drift:
Short term: ≤ ± 5% of the measuring range
or ≤ ± 10% of the measured value, whichever is greater.
Long term: ≤ ± 10% of the measuring range or ≤ ± 20% of the
measured value, whichever is greater
Hazardous Locations
Classification:
Path Lengths:
CSA/FM: Class I, Division 1, 2 Groups B, C, D; Class II,
Division 1, 2 Groups E, F, G; Class III
T4 (Tamb=-55°C to +65°C) for FM
T3C (Tamb=-60°C to +75°C) for CSA
ATEX/IECEx: II 2 G D, Ex d IIB+H2 T4 Gb, Ex tb IIIC T135C Db,
IP66/67 (Tamb=-55°C to +65°C) IEC 60079-29-4
FM10ATEX0031X, IECEx FMG 10.0011X
5 - 30 m*, 20 - 100 m, 80 - 150 m
* 5 m achieved with attenuator
Modes:
Misalignment:
Set-up, test mode, alignment
Meet all performance specifications with at least ±0.5° of
misalignment
Solar Blind:
Complies with FM 6325 performance requirements
Fog Immunity:
FM 6325 performance requirement: at least 90% blockage with
≤ ±10% mid-scale gas accuracy
Hazardous Location
and Electrical Safety
Temperature Range:
-60°C to +75°C
Certified Performance
Temperature Range:
-55°C to +65°C
Warranty:
Two years
Product Compatibility: IR4000M, MC600, TA502A, HazardWatch, DC110
50
Model IR5500
7.2.2 Electrical Specification
Input Voltage:
Input Current:
Supply Power:
Start-up Time:
Warm-up Time
Relay Ratings:
Relay Quantity:
Relay Contact
Type:
Analog Signal:
Function
Fault
Test Gas
Setup mode
Beam Block
Startup
Zero reading
0-5 LEL·m
Split Range
Over-range
RS-485 Output:
Baud Rate:
HART
(Optional):
RFI/EMI
Protection:
20 to 36 VDC, 24 VDC nominal
Source: 0.64 A maximum at 20 VDC input voltage
Receiver: 0.50 A maximum at 20 VDC input voltage; less 0.04 A with
relays disabled
Source: Rated 12 watts maximum at 24 VDC input
Receiver: Rated 10 watts maximum at 24 VDC input
2 minutes
2 hours minimum
8 A @ 250 VAC, 8 A @ 30 VDC resistive max.
4 internal; Fault, Alarm, ppm·m Warn, LEL·m Warn
Single Pole Change Over (SPDT)
0 to 22 mA (700 ohms max. load)
HART Not Installed
0 mA
1.5 mA
1.5 mA
2.0 mA
0 mA
4.04 mA
4-20 mA
4-12 mA for 0-5000
ppm·m (methane) or 02000 ppm·m (propane)
12-20 mA for 0-5 LEL·m
(methane) or 0-1 LEL·m
(propane)
21.7 mA
HART Low Range
1.25 mA
1.5 mA
1.5 mA
2.0 mA
1.25 mA
4.04 mA
4-20 mA
4-12 mA for 0-5000
ppm·m (methane) or 02000 ppm·m (propane)
12-20 mA for 0-5 LEL·m
(methane) or 0-1 LEL·m
(propane)
21.7 mA
HART High Range
3.5 mA
3.5 mA
3.5 mA
3.5 mA
3.5 mA
4.04 mA
4-20 mA
4-12 mA for 0-5000
ppm·m (methane) or 02000 ppm·m (propane)
12-20 mA for 0-5 LEL·m
(methane) or 0-1 LEL·m
(propane)
21.7 mA
Modbus RTU with Block and Single Data transfer modes
2400, 4800, 9600, 19200, or 38400 BPS
Fully HART Compliant. User selectable between HART and Modbus.
HART current source Rx = 120 kilo ohms, Cx = 8 nF.
EN 61000-6-4, EN 50270
7.2.3 Mechanical Specification
Length:
Diameter:
Weight:
Material:
12.4 inches (315 mm)
4.5 inches (113 mm) for SS enclosure
5.3 inches (135 mm) for Nosecone
Source: 12.20 lb (5.53 kg)
Receiver: 12.34 lb (5.60 kg)
Pan-Tilt Arm Assembly 329073-1: 7.62 lb (3.46 kg)
316 stainless steel for electronics enclosure
51
Model IR5500
7.2.4 Environmental Specification
Operating Range:
Storage Range:
Enclosure Protection Rating:
-55°C to +65°C @ 10% to 95% RH non-condensing,
86-108 kPa non-compensated
-65°C to +75°C @ 10% to 95% RH non-condensing,
86-108 kPa non-compensated
Type 4X, IP66/67
7.2.5 Approvals
Meets the performance requirements of FM 6325, EN 60079-29-4 and IEC 60079-29-4.
CSA, FM, ATEX, IECEx, INMETRO, BV approved; HART Registered; IEC 61508 approved
to SIL 3, 2 or 1.
CSA & FM Approval:
Explosion-proof for Class I, Division 1, Groups B, C, and D, Dust-ignition proof for Class
II/III, Division 1 Groups E, F and G, Non-Incendive for Class I/II/III, Division 2, Groups B, C,
D, E, F, G.
ATEX & IECEx Approval:
Flameproof ‘d’ with Equipment Protection Level ‘Gb’ for Gas Group IIB + H2, Category 2G.
Dust Ignition Protection by Enclosure with level of protection ‘tb’ and Equipment Protection
Level ‘Db’ for Dust Group IIIC, Category 2D.
7.2.6 Cable Requirements
It is the responsibility of the facilities engineer to comply with all regulatory, legal, and safety
issues concerning appropriate wiring for the facility.
The sample calculations are for reference only. Customers must derive the distance from
supply to device based on cable specifications, expected maximum ambient temperature
and cable temperature rise, estimated connection losses, allowances for error in distance
measurement, and other variables particular to the customer installation.
Sample Calculations for Power Cable
V_supply = 24 VDC, V_device = 20 VDC, I_Receiver_max = 0.50 A, cable resistance per
meter = 9.00 ohms per meter at maximum ambient temperature for 2.5 mm2 cable.
Maximum distance from supply to Receiver = (1/2) x (V_supply – V_device) / (I_device_max
x cable resistance per meter)
Maximum distance = (1/2) x (24 – 20) / (0.50 x 9.00 / 1000) = 444 meters
Sample maximum distances from supply to device
Terminal Type
Max Wire Size
Typical
Resistance
Source
Receiver
Push
16 AWG
5.00 ohms /
1000 ft
625 feet
800 feet
Screw
14 AWG
3.00 ohms /
1000 ft
1040 feet
1330 feet
Push
1.5 mm2
16.0 ohms /
1000 m
195 meters
250 meters
Screw
2.5 mm2
9.00 ohms /
1000 m
347 meters
444 meters
Table 5: Distances from Power Supply to Source and Receiver
52
Model IR5500
Sample Calculations for Analog Output Cable
Maximum load is 700 ohms. If an external device has an input impedance of 600 ohms, the
cable resistance must not exceed 100 ohms, where maximum load = device load + cable
resistance. For 16 AWG cable with resistance of 5 ohms / 1000 feet, the maximum distance
from IR5500 and AO device is ((100 / 5 ) / 2) x 1000 feet = 10,000 feet.
AWG
#20
#18
#16
Ohms/1000 ft
11
7
5
Feet
4,550
7,140
10,000
Meters
1,390
2,180
3,050
Table 6: Distances from Receiver to Analog Output Load
7.3
Spare Parts and Accessories
To order spare parts or accessories, please contact your nearest General Monitors
Representative or General Monitors directly and give the following information:
Configuration Number
Description
Quantity
7.3.1 Spare Parts
329071-1
329073-1
329123-1
329083-1
329084-1
329113-1
329118-1
954-021
Pan-Tilt Base Assembly
Pan-Tilt Arm Assembly
Basic Mounting Arm Assembly (No longer available)
Methane Test Gas Film Kit
Propane Test Gas Film Kit
Attenuator
Lamp Replacement Kit
5 mm T-handle hex key. Used for instrument-mounting screws
and cover-locking screw.
Recommended Spare Parts for one (1) year:
30060-1
31037-1
Single Magnet Assembly
Double Magnet Assembly
7.3.2 Accessories
329071-1
329073-1
329123-1
329082-1
329120
Pan-Tilt Base Assembly
Pan-Tilt Arm Assembly
Basic Mounting Arm Assembly (No longer available)
Long Range Alignment Kit (includes scope)
Instruction Sheet Arm Mounting
53
Model IR5500
7.4
Engineering Documentation
Figure 16: Outline Drawing
54
Model IR5500
8.0 Appendix A
8.1
Split-Range Analog Output Option
NOTE: This section is intended to be read and understood by a systems integration
engineer. It is not necessary to understand this in order to safely use the Model
IR5500 gas detector. The split-range analog output option is turned off by default
and should be left off unless you are certain the control room PLC is properly
configured.
If the split-range mode is turned on and the PLC is not set to calculate the analog
output this way, the system will fail-to-safe because the analog is interpreted as
representing a higher concentration than is present. This may cause the PLC to
falsely indicate alarms.
The IR5500 can be set through the SE menu to operate in split-range analog output mode.
This mode gives the advantages of very high sensitivity of the ppm·m range and the full
range detection of the LEL·m scale. The analog output range from 4 to 20 mA is split so that
values from 4 to 12 mA represent 0 – 5,000 ppm·m and values from 12 to 20 mA represent 0
– 5.0 LEL·m.
For the heavy hydrocarbon version of the Model IR5500 detector the ranges are 4 to 12 mA
represent 0 – 2,000 ppm·m and values from 12 to 20 mA represent 0 – 1 LEL·m.
This mode is intended for use with a PLC which will convert the analog current back to both
ppm·m and LEL·m readings.
The conversion equations for the PLC are:
ppm·m % F.S. = (Analog Output – 4.00) / 0.08
LEL·m % F.S. = (Analog Output – 12.0) / 0.08
where Analog Output is the current measured by the PLC in units of mA.
To display the value in ppm·m or LEL·m the following conversion should be used:
Methane detectors
ppm·m = ppm·m % F.S. * 50
LEL·m = LEL·m % F.S. / 20
Propane detectors
ppm·m = ppm·m % F.S. * 20
LEL·m = LEL·m % F.S. / 100
55
Model IR5500
8.2
Alignment Using Legacy AJ Value
To change the alignment signal strength indication from Pct to AJ, apply the magnet over the
GM logo on the Receiver cover until rSt appears. When SE appears, remove the magnet.
Apply the magnet when diS appears. When Pct appears, apply the magnet until AJ appears.
Remove the magnet. Apply the magnet when Fi appears. The display will cycle through more
menu choices. When Fi appears again, apply the magnet to exit the setup menu. For a
diagram of the menu choices, refer to the User Menu in the Operation section.
During alignment, verify that the AJ level is comparable to typical values listed below. For
80150-meter configuration, add 50 meters to the range.
Range
20 m
30 m
40 m
50 m
60 m
70 m
80 m
90 m
100 m
AJ value
72 to 67
65 to 60
59 to 54
53 to 48
49 to 43
45 to 38
43 to 35
39 to 32
35 to 30
Typical AJ Signal Level Values
56
Model IR5500
ADDENDUM
This product may contain hazardous and/or toxic substances.
EU Member states shall dispose according to WEEE regulations. For further WEEE disposal
information please visit: www.MSAsafety.com
All other countries or states: please dispose of in accordance with existing federal, state and local
environmental control regulations.
57
Model IR5500
Technical Index
30878-2, xii, 18
NEC 500-3d or Canadian Electrical Code Handbook, vi, 11
329083, xii, 18, 40
Operating Range, 39
329084, xii, 18, 40
Output Options, 23
4-20 mA signal, 7
path length is less than 20 meters, 8
Accuracy, 37
Performance Temperature, 37
AJ, xii, 17, 18, 23, 26, 34, 56
Product Compatibility, 37
Analog Signal, 38
Relay Ratings, 38
Approvals, 39
resolution, x, 17
AWG, ix, 15, 40
Response Time, 37
Baud Rate, 38
RFI/EMI Protection, 38
conduit seal, vi, 11
RS-485 Output, 38
Display Sequence on Power Up, x, 16
Safety temperature range, 37
Drift, 27, 37
Spare Parts and Accessories, 40
Fog Immunity, 37
Split-Range analog output option, 42
HART (Optional), 38
Start-up Time, 38
heater, x, 17
Storage Range, 39
Input Voltage, 38
stripping length, vii
IP66/IP67, 2
Supply Power, 38
IR5500 Menus, 21
Test Gas Film, xii, 3, 4, 23, 30, 40
Linearity, 37
time out, xii, 17
Lithium grease, v
Type 4X, 2, 39
Misalignment, 37
Water or ethanol, 27
Modes, 37
58