Servomex 2700 Best Practices Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
For full installations details refer to the Servomex 2700 Quickstart and Installation Manuals.
Best Practice Guide,
Servomex 2700
Mounting:
General Guidelines:
Servomex 2700 Control Units and air supplies (utilities units) should, ideally, be mounted
within easy reach of one another to aid routine calibration. They should also be mounted
as close as possible to the Sensor Head to minimise the analyser’s response time to
calibration gases, to help maintain the stability of the air supply units and to minimise the
effects of pressure drops. Follow the guidelines for maximum separation of the Sensor
Head and Control Unit described in the Servomex 2700 Installation Manual.
Servomex 2700 Sensor Head Mounting:
Ambient Temperature:
Ensure that the operating ambient
temperature is in the range of -20°C to
+70°C and that the Sensor Head is
protected from radiant heat sources or
from direct sunlight (in ambient
temperatures over 30°C). This can be
achieved by installing a Heat Shield
between the Sensor Head and the
source; a thin metal sheet is usually
adequate.
Heat Shield
Radiating
Heat
Source
Sensor
Head
Orientation:
The Sensor Head may be mounted in any orientation, except with the terminals box
directly above the sensor enclosure or with the mounting flange facing directly upwards.
Servomex 2700 Best Practice Guide, 02700006B
This document is to be used in conjunction with, not in place of,
Servomex 2700 Quickstart and Installation Manuals
Page 1 of 7
For full installations details refer to the Servomex 2700 Quickstart and Installation Manuals.
Servomex 2700 Control Unit Mounting:
Ambient Temperature:
Ensure that the operating ambient temperature is in the range of -10°C to +55°C and that
the Control Unit is protected from radiant heat sources or from direct sunlight (in ambient
temperatures over 30°C). This can be achieved by installing a Heat Shield between the
Control Unit and the source; a thin metal sheet is usually adequate.
Servomex 2700 Utilities Panel Mounting:
Ambient Temperature:
Ensure that the operating ambient temperature is in the range of -10°C to +50°C and that
the Utilities Panel is protected from radiant heat sources or from direct sunlight (in
ambient temperatures over 30°C). This can be achieved by installing a Heat Shield
between the Utilities Panel and the source; a thin metal sheet is usually adequate.
All pressure regulators, flow meters and gauges exhibit variations of output with changes
in ambient temperature (their temperature coefficient). Although Servomex has chosen
products that have good rejection to ambient temperature variations, utility units should
be installed in locations with relatively stable ambient conditions. Ideally temperature
swings from one extreme to another should be avoided.
Instrument air and other gases supplied to the utilities panel must have dew points of at
least 5 to 10°C less than the minimum anticipated ambient temperature.
Air Supplies and Calibration Gases:
General Guidelines:
All instrument air supplies used should be clean, dry and free from oil and dirt. For
optimum performance, only one analyser should be used in conjunction with an air
supply or utilities unit. The minimum air supply pressure to a Servomex utilities panel
should be 15psig (1barg) and the air consumption (depending on aspirator, calibration
and blow back options), at this pressure should be between 0.75 to 1.5l/min.
All pressure regulators, flow meters and gauges exhibit variations of output with changes
in ambient temperature (their temperature coefficient). Care should be taken to choose
products with either a good rejection to changes in ambient temperature or to install air
supply units in stable ambient conditions.
Servomex recommends that the Servomex 2700 is initially checked/validated with check
gases every week and then calibrated as required. This period can be extended as a result
of operating experience. For optimum performance, it is also recommended that the
analyser calibration is carried out at both the low and high calibration points.
Servomex 2700 Best Practice Guide, 02700006B
This document is to be used in conjunction with, not in place of,
Servomex 2700 Quickstart and Installation Manuals
Page 2 of 7
For full installations details refer to the Servomex 2700 Quickstart and Installation Manuals.
NOTE: Experience has shown that for best calibration results the calibration sequence
should be Air, followed be 0.3% O2 balance N2, followed by 1000ppm CO
balance Air.
Recommended Calibration Gases
Gas Composition
Oxygen Sensor
Zero Air
HIGH
3000ppm(v) O2 balance N2
LOW
1000ppm(v) CO balance Air
N/A
Combustibles Sensor
LOW
N/A
HIGH
Aspirator Air Supply:
The aspirator air supply is used to extract the sample from the flue. Under typical flue
pressure conditions, air consumption is usually 1.5l/min at 3 to 5psig (0.2 to 0.3barg), to
give a sample flow of 300ml/min. The factory tested aspirator pressure is marked within
the terminal’s box of the Sensor Head. In applications where the process pressure is
close to that of ambient pressure (within ±0.5psig) set the aspirator pressure to the
pressure shown on the label. For other process pressures, please consult Servomex for
installation details.
Care should be taken to fit regulators and gauges that give suitable resolution over
expected pressure ranges. As the inlet pressure to the aspirator is directly proportional to
sample flow rate, stable aspirator pressure regulation is of the utmost importance for a
stable measurement. Two-stage regulation is recommended. A additional primary
regulator maybe required to reduce the supply pressure to more manageable pressure
levels. Servomex recommends that the stability of the pressure regulation should be
better than ±5% of the aspirator set-point i.e. 4 ± 0.2 psig, for combustibles only and dual
sensor versions of the Servomex 2700 and better than ±10% for oxygen only versions.
Auxiliary Air Supply:
The combustibles only and dual sensor versions of the Servomex 2700 require auxiliary
air to supplement the level of oxygen present in the combustibles sensor. As the auxiliary
air mixes with the sample gas, any fluctuations will affect the measurement of the
analyser; therefore the auxiliary air supply should be regulated to give nominally
100ml/min, stable to ±1ml/min.
Blow-Back:
Blow-back must not be used instead of a suitably specified filtered sample probe. If you
have any concerns over the included sample probe, consult Servomex prior to
installation. Blow-back pressure must not exceed 15psig (1barg).
Servomex 2700 Best Practice Guide, 02700006B
This document is to be used in conjunction with, not in place of,
Servomex 2700 Quickstart and Installation Manuals
Page 3 of 7
For full installations details refer to the Servomex 2700 Quickstart and Installation Manuals.
Calibration Gases:
Calibration gas flow rate should be set via a suitable flow meter to 600±25ml/min,
maximum inlet pressure 15psig (1barg).
Auto Calibration:
Time must be given to allow for calibration pipe work to be flushed and for the sensors to
stabilise. Field experience shows that 4 to 5 minutes are usually adequate, depending on
the separation between gas cylinders and the Probe Head.
Analyser Purge Options:
Sensor Head:
Corrosive Purge: This purge is to help prevent corrosion within the Sensor Head and is
supplied through the terminal’s box and left to freely vent through the
breather port. It does not provide protection for use in hazardous
areas. A flow rate of between 50 to 100ml/min of instrument air is
required, at an inlet pressure of 50 to 100mmH2O.
Hazardous Area Purge: Refer to local standards.
Control Unit:
Corrosive Purge: This purge is to help prevent corrosion within the Control Unit. It does
not provide protection for use in hazardous areas. A flow rate of
between 100 to 200ml/min of instrument air is required, at 50 to
100mmH2O.
Hazardous Area Purge: Refer to local standards.
Air Supplies and Calibration Gases
Specification
Aspirator
Oxygen Only
Typically 3 to 5 psig (0.2 to 0.3barg) stable to ±10%
of set point.
CO only and dual Typically 3 to 5 psig (0.2 to 0.3barg) stable to ±5% of
measurements
set point.
Auxiliary air (CO only and dual Nominally 100ml/min stable to ± 1ml/min.
measurements)
Blow Back
No greater than 15psig (1barg)
Calibration Gases
600 ± 25ml/min
Purge Gases
Sensor Head
50 to 100ml/min, at 50 to 100mmH2O
Control Unit
100 to 200ml/min, at 50 to 100mmH2O
Servomex 2700 Best Practice Guide, 02700006B
This document is to be used in conjunction with, not in place of,
Servomex 2700 Quickstart and Installation Manuals
Page 4 of 7
For full installations details refer to the Servomex 2700 Quickstart and Installation Manuals.
Cabling:
The electrical terminations in the Servomex 2700 are suitable for 20AWG (0.5mm2) to
14AWG (2.5mm2) solid and 16AWG (1.5mm2) stranded conductors. Both the Control
Unit and Sensor Head have independent AC power supplies.
Analyser
Interconnecting Cable Requirements
Interconnecting Cable
Maximum
Cable Length
Oxygen Only Minimum of three twisted pairs with an overall 300m
screen. Maximum loop resistance of heater
interconnections is 4W.
Combustibles Minimum of six twisted pairs with individual and 100m
Only
overall screens. Maximum loop resistance of heater
interconnections is 4W.
Oxygen and
Minimum of nine twisted pairs with individual and 100m
Combustibles overall screens. Maximum loop resistance of heater
interconnections is 4W.
Note: To utilise the optional sensor head temperature facility at the control unit, add
one extra twisted pair to the above cable specification.
Recommended Cables and Suppliers (Always check manufactures specification for full
compatibility before use).
Analyser
Oxygen Only
Combustibles Only
Oxygen and Combustibles
Cable Supplier
Alpha……………………………………
Belden…………………………………..
Alpha……………………………………
Belden…………………………………..
Alpha……………………………………
Belden…………………………………..
Part Number
5610B2004
1056A
5620B2008
1077A
5620B2012
1078A
The maximum loop resistance limit of 4W is required for the sensor heater lines (two per
sensor); the sensor outputs, temperature signals and bridge supply wires need not be
limited by this, but they are limited to a cross sectional area of 0.5mm2 for electrical
termination. Depending on installation environment, it may prove cost effective to use
interconnecting cables with more twisted pairs, but with a smaller cross sectional area per
core and to run the cell heater wires in parallel to produce the maximum 4W loop
resistance.
Ensure that good EMC practices are observed when making connections. In order to
avoid ground loops, it is essential that cable screens associated with the signal cable(s)
connecting the Sensor Head, do not terminate directly to ground, they should be
terminated to TB5/13, TB3/9 and the stud terminal – S, see figure 10 Installation Manual.
The Control Unit must be connected to a local EMC earth and with the signal cable(s)
Servomex 2700 Best Practice Guide, 02700006B
This document is to be used in conjunction with, not in place of,
Servomex 2700 Quickstart and Installation Manuals
Page 5 of 7
For full installations details refer to the Servomex 2700 Quickstart and Installation Manuals.
screens terminated to the control unit enclosure. The recommended method is to
terminate the screen at the cable gland, if this is impractical, the screens maybe
terminated to the M4 threaded studs adjacent to the cable entries.
Any conduit or screen associated with the power supply, should be grounded at the cable
gland or conduit entry to the Sensor Head or Control Unit enclosure in accordance with
local wiring regulations.
Installation and Commissioning:
After installation, the Sensor Head should not be left on the flue without being powered
for an extended period, as condensation may form within the sample pipe work. The
Sensor Head should be removed from the process and protected against external
contamination, or left with 600ml/min of instrument air running through the calibration
port, until the analyser can be fully commissioned and placed online.
Initial Start-up and Analyser Warm-up:
Typical Analyser Warm-up:
On powering the 2700 Control Unit and Sensor Head, the Sensor Head and sensors are
heated. These temperatures are interlocked with the aspirator solenoid valve, to
determine when to start extracting a sample; thus protecting the analyser from
condensation forming within the sample pipe work.
The Sensor Head and the combustibles sensor heating starts at switch on; with the oxygen
sensor waiting until its ambient temperature has been raised to 65°C, before it in turn
switches on.
Using the Diagnostics menu, see Servomex 2700 Quickstart Manual, section 3.2, you can
monitor the warm-up of the Sensor Head and sensors. You should see the Sensor Head
and combustibles sensor temperatures rise slowly from switch on, stabilising in 15 to 60
minutes, depending on the ambient temperature. The oxygen sensor will rise slowly at
first, until its temperature is over 65°C, then more quickly as it is heated, until it stabilises
in 5 to 15 minutes.
Servomex 2700 Best Practice Guide, 02700006B
This document is to be used in conjunction with, not in place of,
Servomex 2700 Quickstart and Installation Manuals
Page 6 of 7
For full installations details refer to the Servomex 2700 Quickstart and Installation Manuals.
When the unit is fully up to temperature, the following diagnostics values are typical:
Probe Head………………
Oxygen Sensor…………..
Oxygen Sensor…………..
COe Sensor……………...
COe Sensor……………...
245±10°C
0mV (on air); 80mV (on 0.3%O2)
700±10°C
-60 to 60mV (on air); plus either 40 to 110mV (on
1000ppmCO) for 0-2000ppm range COe sensors or 15 to
40mV (on 1000ppmCO) for 0-6000ppm range COe sensors
300±5°C
At this point the Sensor Head solenoid valve will activate, and the analyser will start to
extract a sample from the process. It is recommended that the analyser is not calibrated
at this point, but left for three hours to fully reach thermal equilibrium. If the analyser is
now calibrated good results will be achieved but, due to the large thermal mass of the
analyser, some measurement drift may be experienced over the next 24 hours. It is
recommended that for best results the analyser is calibrated once more after 24 hours.
Routine Maintenance, Calibration and Servicing:
The Servomex 2700 is designed to be a low maintenance product, with the minimum of
support required after commissioning. The Sensor Head contains an internal 5mm
sintered stainless steel filter, which prevents contamination of the Sensor Head. On
processes with higher dust levels, greater than 0.2g/m3, Servomex supply a range of
standard and special filtered sample probes, that prevent the transmission of dust from the
process into the Sensor Head. If you have any concerns over the included sample probe,
consult Servomex prior to installation.
General Guidelines:
The analyser should initially have its calibration, catch pots and air filters checked once
per week; this can then be adjusted depending on site experience, but should be at least
monthly.
Analyser flow rates, air supplies, probes and filters (internal and external), should be
checked once per year, as well as the whole analyser and cabling for general signs of
wear. In some applications, these times may need to be shorter, depending on
experience.
Servomex 2700 Best Practice Guide, 02700006B
This document is to be used in conjunction with, not in place of,
Servomex 2700 Quickstart and Installation Manuals
Page 7 of 7