Det-Tronics Instructions UV Flame Detector X2200
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions UV Flame Detector X2200 15.1 Rev: 1/16 95-8549 Table of Contents DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 14 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2 Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . 15 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3 oi Plate Removal and Replacement . . . . . . . . 15 Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Periodic Checkout Procedure . . . . . . . . . . . . . . 15 Integral Wiring Compartment . . . . . . . . . . . . . . . 3 Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . 15 SIGNAL PROCESSING OPTIONS . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 GENERAL APPLICATION INFORMATION . . . . . . . . 4 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Response Characteristics . . . . . . . . . . . . . . . . . . 4 False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 4 REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 18 Factors Inhibiting Detector Response . . . . . . . . . 4 Replacement Parts List . . . . . . . . . . . . . . . . . . . 18 IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 5 DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . 18 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 18 Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 6 X2200 Model Matrix . . . . . . . . . . . . . . . . . . . . . 19 Protection Against Moisture Damage . . . . . . . . . 7 Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . 7 Setting Device Network Addresses (EQ and EQP Models Only) . . . . . . . . . . . . 13 APPENDIX A – FM APPROVAL AND PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 20 APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 24 STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 14 Fire Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . 14 APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 25 APPENDIX D – IECEx APPROVAL . . . . . . . . . . . . . 27 APPENDIX E – EN54 APPROVALS . . . . . . . . . . . . 28 APPENDIX F – ADDITIONAL APPROVALS . . . . . . 29 INSTRUCTIONS UV Flame Detector X2200 IMPORTANT Be sure to read and understand the entire instruction manual before installing or operating the flame detection system. Any deviation from the recommendations in this manual may impair system performance and compromise safety. ATTENTION The X2200 includes the Automatic oi ® (Optical Integrity) feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. Testing with an external test lamp is not approved or required. A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. DESCRIPTION The X2200 UV Flame Detector meets the most stringent requirements worldwide with advanced detection capabilities and immunity to extraneous sources, combined with a superior mechanical design. The detector is equipped with both automatic and manual oi test capability. The detector has Division and Zone explosion-proof ratings and is suitable for use in indoor and outdoor applications. The X2200 housing is available in copper-free aluminum or stainless steel, with NEMA/Type 4X and IP66/IP67 rating. OUTPUTS Relays The standard detector is furnished with fire, fault, and auxiliary relays. All three relays are rated 5 amperes at 30 Vdc. The standard output configuration includes fire, fault, and auxiliary relays. Output options include: –– 0 to 20 mA output (in addition to the three relays) –– Pulse output for compatibility with existing Detector Electronics Corporation (Det-Tronics) controller based systems (with fire and fault relays) –– Eagle Quantum (EQP) compatible model (no analog or relay outputs) –– HART communication 15.1 The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. Premier ® ©Detector Electronics Corporation 2016 1 Rev: 1/16 95-8549 The Auxiliary relay has normally open / normally closed contacts, and is configurable for energized or de-energized operation, and latching or non-latching operation. LED A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Table 2 indicates the condition of the LED for each status. 0 to 20 mA Output A 0 to 20 mA output is available as an option (in addition to the three relays). This option provides a 0 to 20 mA dc current output for transmitting detector status information to other devices. The circuit can be wired in either an isolated or non-isolated configuration and can drive a maximum loop resistance of 500 ohms from 18 to 19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table  1 indicates the detector status conditions represented by the various current levels. The output is calibrated at the factory, with no need for field calibration. A model with relays and 0-20 mA with HART is also available. Refer to Addendum number 95-8638 for complete details. Table 2—Detector Status Indicator Power Fault 1 mA General Fault 2 mA oi Fault 4 mA Normal Operation 16 mA Pre-Alarm 20 mA Fire Alarm Fire (Alarm) Green, flashing off for 0.5 sec. every 5 sec. Yellow Red, flashing on for 1 sec. and off for 1 sec. Steady Red On Power-Up, The LED Flashes in Sequence as Follows, Indicating Sensitivity and Signal Processing Status Low UV Sensitivity Medium UV Sensitivity High UV Sensitivity Very High UV Sensitivity One Red Flash Two Red Flashes Three Red Flashes Four Red Flashes Stand. UV Signal Process. Arc Rej. UV Signal Process. One Yellow Flash Two Yellow Flashes ATTENTION The X2200 contains a source tube that is filled with a gas mixture containing Krypton 85 (Kr85), a radioactive material. Radioactive materials are subject to regulation under U.S. and international law. oi (OPTICAL INTEGRITY) Automatic oi The X2200 includes the Automatic oi feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. No testing with an external test lamp is required. The detector automatically performs the same test that a maintenance person with a test lamp would perform — once every minute, 60 times per hour. However, a successful Automatic oi test does not produce an alarm condition. LON/SLC Output The EQP model is designed for use exclusively with the Det-Tronics Eagle Quantum Premier system. The detector communicates with the system controller over a digital communication network or LON/SLC (Local Operating Network / Signaling Line Circuit). The LON/ SLC is a fault tolerant, two wire digital communication network arranged in a loop configuration. Analog and relay outputs are not available on this model. 15.1 Green Pre-Alarm/Background UV Table 1—Detector Status Conditions Indicated by Current Level Detector Status Power On/Normal Auto oi (no fault or fire alarm) Fault An alarm condition will normally over-ride a fault condition, unless the nature of the fault condition impairs the ability of the detector to generate or maintain an alarm output, i.e., loss of operating power. 0 mA LED Indicator Power On/Normal Man oi NOTE The output of the 0 to 20 mA current loop is not monitored by the fault detection circuitry of the X2200. Therefore, an open circuit on the loop will not cause the fault relay to change state or the detector status LED to indicate a fault. The status of the LED always follows the status of the relays. Current Level (±0.3 mA) Detector Status The detector signals a fault condition when less than half of the detection range remains. This is indicated by the Fault output and is evident by the yellow color of the LED on the face of the detector. See the "Troubleshooting" section for further information. 2 95-8549 Magnetic oi / Manual oi DATA LOGGING The detector also incorporates both Magnetic oi (Mag oi) and Manual oi (Man oi) features that provide the same calibrated test as the Automatic oi, and in addition actuates the Alarm output to verify operation for preventive maintenance requirements. These features can be performed at any time and eliminate the need for testing with a non-calibrated external test lamp. Data logging capability is also provided. Status conditions such as normal, power down, general and oi faults, prealarm, fire alarm, time, and temperature are recorded. Each event is time and date stamped, along with the temperature and input voltage. Event data is stored in non-volatile memory when the event becomes active, and again when the status changes. Data is accessible using the Inspector Connector accessory, RS-485, or the EQP Controller. CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test. INTEGRAL WIRING COMPARTMENT All external wiring to the device is connected within the integral junction box. The detector is furnished with four conduit entries, with either 3/4 inch NPT or M25 threads. The Mag oi test is performed by placing a magnet at the location marked "MAG OI" on the outside of the detector (see Figure 2). The Man oi test is accomplished by connecting the oi lead (terminal 22) to power supply minus via an external switch. The magnet or switch must be held in place for a minimum of 6 seconds to complete the test. Either of these test methods activates the calibrated UV emitter. If the resulting signal meets the test criteria, indicating that greater than half of the detection range remains, the fire alarm output of the detector is activated. This condition remains until the magnet is removed or the switch is released, regardless of whether the detector has been configured for latching or non-latching operation. SIGNAL PROCESSING OPTIONS The UV detector output (measured in counts per second) is compared to the fire threshold (the "sensitivity" setting). If the radiant energy level from the fire exceeds the selected alarm threshold level, the fire alarm output is activated. In every application, it is crucial to ensure that the radiant ultraviolet energy level from the expected fire at the required distance from the detector will exceed the selected sensitivity level. The UV detector in the X2200 can be programmed for: –– –– If less than half of the detection range remains, no alarm is produced and a fault is generated. The fault indication can be reset by momentarily applying the Mag oi or Man oi switch. In this case, the detector's optics should be cleaned and the oi tests should be repeated. See the "Cleaning Procedure" section of this manual for details. Arc Rejection The Arc Rejection mode enables the detector to prevent nuisance fire alarms caused by UV from shortduration electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect the UV radiation given off by a flame. Typical applications that benefit from arc rejection logic include electrostatic coating processes and uncontrolled environments where transient UV sources can be present, such as many typical outdoor applications. Most false alarm sources have short transient UV signatures, while fire creates a long UV signature over many seconds. Most fires are detected in a few seconds (see response times in Appendix A). NOTE Refer to Appendix A for FM verification of the o i function. COMMUNICATION The X2200 is furnished with an RS-485 interface for communicating status and other information with external devices. The RS-485 supports MODBUS protocol, with the detector configured as a slave device. Standard Signal Processing For HART communication, connect a HART communicator across a 250 ohm resistor in the 0-20 mA loop. Standard signal processing is recommended for highspeed suppression systems only. To allow for high-speed operation, the standard processing mode does not incorporate the arc rejection programming. This mode should only be used in a controlled, indoor environment. NOTE The EQP model uses LON/SLC communication. RS-485 and HART communication are not available on the EQP model. 15.1 Arc Rejection Standard Signal Processing 3 95-8549 GENERAL APPLICATION INFORMATION FACTORS INHIBITING DETECTOR RESPONSE RESPONSE CHARACTERISTICS Glass and Plexiglas windows significantly attenuate UV radiation and must not be located between the detector and a potential flame source. If the window cannot be eliminated or the detector location changed, contact Det-Tronics for recommendations regarding window materials that will not attenuate UV radiation. Windows Response is dependent on the detector's sensitivity setting, arc rejection, and time delay settings. Other factors include distance, type of fuel, temperature of the fuel, and time required for the fire to come to equilibrium. As with all fire tests, results must be interpreted according to an individual application. Obstructions Radiation must be able to reach the detector in order for it to respond. Care must be taken to keep physical obstructions out of the line of view of the detector. In addition, UV absorbing gases or vapors must not be allowed to accumulate between the detector and the protected hazard. See Table  3 for a list of these substances. See Appendix A for third-party approved fire test results. Additional fire test results are available from Det-Tronics. Welding Electric arc welding is a source of intense ultraviolet radiation. UV radiation from arc welding readily scatters and can deflect across significant distances, even when direct obstructions exist. Any open door or window can allow nuisance UV radiation from arc welding to enter an enclosed area. Smoke It is recommended that the system be bypassed during welding operations in situations where the possibility of a false alarm cannot be tolerated. Gas welding mandates system bypass, since the gas torch is an actual fire. Smoke will absorb UV radiation. If accumulations of dense smoke can be expected to precede the presence of a flame, then detectors that are used in enclosed areas should be mounted on the wall approximately 3 feet (0.9 m) from the ceiling where the accumulation of smoke is reduced. Artificial Lighting Detector Viewing Windows It is important to keep the detector viewing windows as free of contaminants as possible in order to maintain maximum sensitivity. Commonly encountered substances that can significantly attenuate UV radiation include, but are certainly not limited to, the following: The X2200 should not be located within 3 feet (0.9 m) of artificial lights. Excess heating of the detector could occur due to heat radiating from the lights. EMI/RFI Interference The X2200 is resistant to interference by EMI and RFI, and is EMC Directive compliant and CE Marked. It will not respond to a 5 watt walkie-talkie at distances greater than 1 foot (0.3 m). –– Silicones –– Oils and greases –– Dust and dirt buildup –– Paint overspray FALSE ALARM SOURCES The UV sensor is solar blind to the ultraviolet component of solar radiation. However, it may respond to sources of UV besides fire, such as arc flash, electric arc welding, grinding metal, lightning, high voltage corona, x-rays, and gamma radiation. 15.1 4 95-8549 IMPORTANT SAFETY NOTES Table 3—UV Absorbing Gases and Vapors The following is a partial list of compounds that exhibit significant UV absorption characteristics. These are also usually hazardous vapors. While generally of little consequence in small amounts, these gases can restrict UV detection if they are in the atmosphere in heavy concentrations. It should also be determined whether or not large amounts of these gases may be released as a result of a fire-causing occurrence. WARNING Do not open the detector assembly in a hazardous area when power is applied. The detector contains limited serviceable components and should never be opened. Doing so could disturb critical optical alignment and calibration parameters, possibly causing serious damage. Acetaldehyde Methyl Methacrylate Acetone Alpha-Methylstyrene Acrylonitrile Naphthalene Ethyl Acrylate Nitroethane Methyl Acrylate Nitrobenzene Ethanol Nitromethane Ammonia 1-Nitropropane Aniline 2-Nitropropane Benzene 2-Pentanone 1,3 Butadiene Phenol 2—Butanone Pyridine Butylamine Hydrogen Sulfide Chlorobenzene Styrene 1-Chloro-1-Nitropropane Tetrachloroethylene Chloroprene Toluene Cumene Trichloroethylene Cyclopentadiene Vinyl Toluene O-Dichlorobenzene Xylene P-Dichlorobenzene CAUTION The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local ordinances. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person. CAUTION To prevent unwanted actuation or alarm, extinguishing devices must be disabled prior to performing detection system tests or maintenance. If UV-absorbing gases may be a factor in a given application, precautionary measures should be taken. Detectors can be placed closer to the potential hazard area, and/or the sensitivity of the detection system can be increased. Contact the factory for further details. CAUTION The UV flame detectors are to be installed in places where the risk of mechanical damage is low. ATTENTION Remove the protective cap from the front of the detector before activating the system. Substances such as methane, propane, butane, hexane, camphor, and octane are not UV absorbing. ATTENTION Observe precautions for handling electrostatic sensitive devices. ATTENTION The source tube is a flame-sealed gas tube containing Neon, Hydrogen, and a trace amount of Krypton 85 (Kr85), a radioactive material. The total volume of gas within the tube is 0.6 ml per tube, making the gas mixture inside the tube nonflammable. If the gas envelope is broken, it will not produce a flammable mixture, and the gas immediately disperses into the air and is unlikely to present any type of hazard. Krypton gas and its radioactive isotope are inert and are not absorbed by the body. No special handling measure or personal protection equipment is needed for the UV detectors. 15.1 5 95-8549 INSTALLATION NOTE The recommended lubricant for threads and O-rings is a silicone-free grease (p/n 005003001) available from Det-Tronics. Under no circumstances should a lubricant containing silicone be used. DETECTOR POSITIONING Identify all high risk fire ignition sources. • Be sure that enough detectors are used to adequately cover the hazardous area. • Be sure that the unit is easily accessible for cleaning and other periodic servicing. • Verify that all detectors in the system are properly located and positioned so that any fire hazards are within both the Field of View (FOV) and detection range of the detector. The Q1201C Laser Aimer is recommended for establishing the detector's FOV. Refer to Appendix A for specific information regarding detector range and FOV. • The detector should be aimed downward at least 10 to 20 degrees to allow lens openings to drain (see Figure  1). The detector should be positioned so that its FOV does not cover areas outside the hazardous area. This will minimize the possibility of false alarms caused by activities outside the area requiring protection. • Dense fog, rain as well as certain gases and vapors (see Table  3) can absorb UV radiation and reduce the sensitivity of the detector. • If possible, fire tests can be conducted to verify correct detector positioning and coverage. • For ATEX/IECEx installations, the X2200 Flame Detector housing must be electrically connected to earth ground. DETECTOR ORIENTATION Detectors should be positioned to provide the best unobstructed view of the area to be protected. The following factors should also be taken into consideration: • • Refer to Figure  2 and ensure that the oi plate will be oriented as shown when the X2200 is mounted and sighted. This will ensure proper operation of the oi system and will also minimize the accumulation of moisture and contaminants between the oi plate and the viewing windows. IMPORTANT If removed, the o i plate must be securely tightened to ensure proper operation of the o i system (40 oz./inches [28.2 N . cm] recommended). oi PLATE PLACE MAGNET HERE TO INITIATE MAGNETIC oi UV VIEWING WINDOW oi MAGNET B2171 DETECTOR STATUS INDICATOR The detector must be mounted on a rigid surface in a low vibration area. Figure 2—Front View of the X2200 CENTER AXIS OF DETECTOR FIELD OF VIEW INCORRECT CENTER AXIS OF DETECTOR FIELD OF VIEW CORRECT D1974 NOTE: DETECTOR MUST ALWAYS BE AIMED DOWNWARD AT LEAST 10 TO 20 DEGREES. Figure 1—Detector Orientation Relative to Horizon 15.1 6 95-8549 PROTECTION AGAINST MOISTURE DAMAGE NOTE R e f e r t o “ Po w e r C o n s u m p t i o n” i n t h e “Specifications” section of this manual. It is important to take proper precautions during installation to ensure that moisture will not come in contact with the electrical connections or components of the system. The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer. The use of shielded cable is required to protect against interference caused by EMI and RFI. When using cables with shields, terminate the shields as shown in Figures 7 through 12, and Figure 15. Consult the factory if not using shielded cable. If conduit is used, we recommend installing drains, according to local codes, at water collection points to automatically drain accumulated moisture. It is also recommended to install at least one breather, according to local codes, at upper locations to provide ventilation and allow water vapor to escape. In applications where the wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical equipment. If disconnection of power is required, separate disconnect capability must be provided. Conduit raceways should be inclined so that water will flow to low points for drainage and will not collect inside enclosures or on conduit seals. If this is not possible, install conduit drains above the seals to prevent the collection of water or install a drain loop below the detector with a conduit drain at the lowest point of the loop. WARNING All entries must contain appropriately rated plugs or fittings. It is required that each plug or fitting be wrench-tightened to an appropriate installation torque and meet the minimum thread engagement requirements per the applicable local standards, codes, and practices in order to retain the defined ratings. PTFE sealant or equivalent should be used on NPT threads. Conduit seals are not required for compliance with explosion-proof installation requirements, but are highly recommended to prevent water ingress in outdoor applications. Units with M25 threads must use an IP66/IP67 washer to prevent water ingress. IMPORTANT Devices certified for hazardous locations shall be installed in accordance with EN/IEC 60079-14 and NEC 505. WIRING PROCEDURE Wire Size and Type CAUTION Installation of the detector and wiring should be performed only by qualified personnel. The system should be wired according to local codes. The wire size selected should be based on the number of detectors connected, the supply voltage and the cable length. Typically 16 AWG or 2.5 mm2 shielded cable is recommended. Wires should be stripped 3/8 inch (9 mm). A minimum input voltage of 18 Vdc must be present at the X2200. 4X ø0.42 (1.1) 3.0 (7.6) 4.0 (10.2) 13.1 (33.3) NOTE: THIS ILLUSTRATION SHOWS THE DETECTOR MOUNTED AT THE 10° MINIMUM. THESE DIMENSIONS WILL CHANGE BASED ON THE DETECTOR’S MOUNTING ANGLE. 3.0 (7.6) 4.0 (10.2) 10.6 (27.0) F2069 Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm) (See Figure 1 for Correct Detector Orientation.) 15.1 7 95-8549 Detector Installation IMPORTANT Do not test any wiring connected to the detector with a meg-ohmmeter. Disconnect wiring at the detector before checking system wiring for continuity. Install the mounting arm assembly on a rigid surface. The ideal installation surface should be free of vibration and suitable to receive 3/8 or M10 bolts with a length of at least 1 inch (25 mm). The surface must also have sufficient capacity to hold the detector and mounting arm weights (See "Specifications" section). Refer to the Q9033 Mounting Arm manual (95-8686) for additional installation information. See Figure 3 for dimensions. 3. Make the final sighting adjustments and use a 14 mm hex wrench to ensure that the mounting arm assembly is tight. EOL Resistors (Not Used with EQP Model) Relay and 0-20 mA Output Models To ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors, observe the following guidelines when installing the resistors. Follow the instructions below to install the X2200. 1. Make field connections following local ordinances and guidelines in this manual. Refer to Figures 4 through 12. 1. Required EOL resistor power rating must be 5 watts minimum. 2. Check all field wiring to be sure that the proper connections have been made. NOTE EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. This applies to ATEX/IECEx installations only. 2. Resistor leads should be cut to a length of approximately 1 1/2 inches (40 mm). 3. Bend the leads and install the EOL resistor as shown in Figure 6. 4. Maintain a 3/8 inch (10 mm) minimum gap between the resistor body and the terminal block or any other neighboring parts. NOTE The EOL resistor can only be used within the flameproof terminal compartment. Unused conduit entries shall be closed with suitable blanking elements. Figure 4—X2200 Terminal Block 9 mA + 19 mA – 29 SPARE 8 mA + REF 18 mA – REF 28 SPARE 7 COM FIRE 17 COM FIRE 27 COM AUX 6 NO FIRE 16 NO FIRE 26 NO AUX 5 NC FIRE 15 NC FIRE 25 NC AUX 4 COM FAULT 14 COM FAULT 24 RS485 A 3 NO FAULT 13 NO FAULT 23 RS485 B 2 +Vin 12 +Vin 22 MAN Oi 1 –Vin 11 –Vin 21 –Vin 3/8 INCH (10 MM) GAP MINIMUM 19 18 17 16 15 14 13 12 11 B2126 BULKHEAD E2061 Figure 5—Wiring Terminal Identification 15.1 Figure 6—EOL Resistor Installation 8 95-8549 X2200 DETECTOR FIRE ALARM PANEL SHIELD ALARM + 24 VDC – 9 mA + 19 mA – SPARE 29 8 mA + REF 18 mA – REF SPARE 28 7 COM FIRE2 COM AUX 27 6 NO FIRE2 NO AUX 26 NC AUX 25 COM FIRE 17 NO FIRE 16 5 NC FIRE2 4 COM FAULT1 3 NO FAULT1 2 +Vin 12 1 –Vin 11 EOL DEVICE4 NC FIRE 15 COM FAULT 14 RS485 A 24 NO FAULT 13 RS485 B 23 +Vin MAN Oi 22 –Vin –Vin 21 oi TEST 3 WIRING NOTES: C2151 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION FOR INSTALLATION DETAILS. 5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE REQUIRED TO FILL ALL CONDUIT ENTRIES. 6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING. Figure 7—Ex d Wiring Option SHIELD X2200 DETECTOR FIRE ALARM PANEL 9 ALARM EOL DEVICE 4 ALARM + 24 VDC – mA + 8 mA + REF 7 COM FIRE2 19 mA – 18 mA – REF SPARE 29 SPARE 28 COM FIRE 17 COM AUX 27 6 NO FIRE2 NO FIRE 16 NO AUX 26 5 NC FIRE2 NC FIRE 15 NC AUX 25 4 COM FAULT1 COM FAULT 14 3 NO FAULT1 13 2 +Vin 12 1 –Vin 11 RS485 A 24 RS485 B 23 +Vin MAN Oi 22 –Vin –Vin 21 NO FAULT oi TEST 3 WIRING NOTES: C2152 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION FOR INSTALLATION DETAILS. 5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE REQUIRED TO FILL ALL CONDUIT ENTRIES. 6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING. Figure 8—Ex e Wiring Option 15.1 9 95-8549 X2200 DETECTOR X2200 DETECTOR PLC PLC 600 Ω MAX AT 24 VDC 600 Ω MAX AT 24 VDC 9 9 mA + 19 mA – 29 + 8 mA + REF 18 28 + – 7 17 27 – mA + 24 VDC 6 16 26 5 15 25 24 VDC 24 14 4 – mA + – 26 5 15 25 4 14 24 23 3 2 +Vin 12 MAN Oi 22 1 –Vin 11 –Vin 1 –Vin 11 –Vin 21 13 D2154 21 Oi TEST1 Figure 10—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current Output (Sinking) 24 VDC + – PLC 19 mA – 29 + 9 8 18 28 – 7 17 27 6 16 26 5 15 25 mA + 4 14 24 3 13 23 2 +Vin 12 MAN Oi 22 1 –Vin 11 –Vin 21 600 Ω MAX AT 24 VDC 24 VDC X2200 DETECTOR 19 mA – 29 + 9 8 18 28 – 7 17 27 6 16 26 5 15 25 4 14 24 3 13 mA + – D2155 mA + 23 2 +Vin 12 MAN Oi 1 –Vin 11 –Vin 22 21 D2156 Oi TEST1 Oi TEST1 Figure 12—X2200 Detector Wired for Isolated 0 to 20 mA Current Output (Sinking) Figure 11—X2200 Detector Wired for Isolated 0 to 20 mA Current Output (Sourcing) NOTES: 1. 15.1 16 23 X2200 DETECTOR – 27 6 MAN Oi 22 24 VDC + – + 28 17 12 Figure 9—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current Output (Sourcing) 24 VDC 18 mA – REF 7 13 Oi TEST1 mA 8 +Vin D2153 600 Ω MAX AT 24 VDC 29 2 3 PLC 19 mA – mA + INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 10 95-8549 5. Check all field wiring to be sure that the proper connections have been made. EQP Model 1. Connect external wires to the appropriate terminals inside the device junction box, shown in Figure 13. See Figure 14 for terminal identification. 6. Replace the device cover and apply input power. 7. Make the final sighting adjustments and use a 14 mm hex wrench to ensure that the mounting arm assembly is tight. 2. Connect the shield of the power cable to earth ground at the power source. 3. Connect shields for the LON cable as indicated. See Figure 15. NOTE Refer to the Eagle Quantum Premier system manual (95-8533) for information regarding power requirements, network communication cable requirements, and configuration. NOTE DO NOT ground any shields at the detector housing. 4. With input power disconnnected, set the device network address. (See “Setting Device Network Addresses” section of this manual for switch setting procedure.) Figure 13—X2200 Terminal Block (EQP Model) 6 SHIELD 16 SHIELD 5 COM 1 A 15 COM 2 A 4 COM 1 B 14 COM 2 B 3 PWR SHIELD 13 PWR SHIELD 2 +Vin 12 +Vin 1 –Vin 11 –Vin C2089 Figure 14—Wiring Terminal Identification for X2200 EQP Model 15.1 11 95-8549 15.1 C 45 12 9 3+ RELAY 5 RELAY 6 RELAY 7 C 42 NO 43 NC 44 31 NO 32 NC NC 41 29 NC RELAY 3 30 C C 39 NO 40 28 NO NC 38 26 NC RELAY 2 27 C C 36 NO 37 25 NO NC 35 23 NC RELAY 1 24 C NO 34 22 NO P5 C 33 DIGITAL INPUTS 21 C C COMMON C B IN–/OUT+ B A + SUPPLY A C COMMON C B IN–/OUT+ B A + SUPPLY A C COMMON C B IN–/OUT+ B A + SUPPLY A C COMMON C B IN–/OUT+ B A + SUPPLY A P3 1 2 CH 3 P4 8– 20 8+ 19 CH 7 12 4– 11 4+ 7– 18 7+ 17 A 4 P4 B 5 3 COM1 SHIELD 6 COM2 1 4 P2 2 24 VDC – 24 VDC + 5 3 SHIELD 6 P1 EQP3700DCIO CH 2 10 3– 6– 16 6+ 15 5– 14 5+ 13 P3 A 56 B 55 CH 6 8 2– 7 2+ 6 1– 5 1+ P2 59 TxD 58 RxD 57 GND GND 54 P8 NC 47 FAULT NO 46 CH 5 DB-9 CONNECTION TO COM PORT OF PC TXD 3 RXD 2 GND 5 50 A 53 P9 49 B 52 P6 48 COM1 SHIELD 51 COM2 1 3 P7 2 24 VDC – 24 VDC + 4 P1 CONTROLLER CH 1 CH 4 CH 8 RELAY 4 RELAY 8 95-8549 – – 24 VDC BATTERY + H N AC LINE 24 VDC SUPPLY + + + – – POWER – – + DISTRIBUTION + + – + – + – 2 B N H AC LINE COM2 15 14 16 A B 5 4 6 COM1 SHIELD Figure 15—A Typical EQP System 4 3 1 2 C A 10 3 P3 B 11 1 BUS BAR SHIELD 12 COM1 12 24 VDC + 2 8 5 COM2 11 24 VDC – 1 7 24 VDC – 24 VDC + 3 6 SHIELD EQPX2200 13 SHIELD 4 9 EQP2100PSM COM2 15 14 16 A B SHIELD 5 4 6 COM1 2 15 14 16 COM2 A B SHIELD 5 4 6 COM1 12 24 VDC + 2 3 11 24 VDC – 1 SHIELD EQPX2200 13 12 24 VDC + 3 11 24 VDC – 1 SHIELD EQPX2200 13 3 B A 14 15 5 4 6 COM1 SHIELD 16 COM2 12 24 VDC + 2 11 24 VDC – 1 SHIELD EQPX2200 13 A2209 ADDRESS SWITCHES SENSOR MODULE REMOVED FROM HOUSING A2191 Figure 16—Location of Address Switches The address number is binary encoded with each switch having a specific binary value with switch 1 being the LSB (Least Significant Bit), see Figure 17. The device’s LON address is equal to the added value of all closed rocker switches. All “Open” switches are ignored. SETTING DEVICE NETWORK ADDRESSES (EQ and EQP Models Only) Overview of Network Addresses Each device on the LON must be assigned a unique address. Addresses 1 to 4 are reserved for the controller. Valid addresses for field devices are from 5 to 250. Example: for node No. 5, close rocker switches 1 and 3 (binary values 1 + 4); for node No. 25, close rocker switches 1, 4, and 5 (binary values 1 + 8 + 16). IMPORTANT If the address is set to zero or an address above 250, the switch setting will be ignored. NOTE The field device sets the LON address only when power is applied to the device. Therefore, it is important to set the switches before applying power. If an address is ever changed, system power must be cycled before the new address will take effect. Duplicated addresses are not automatically detected. Modules given the same address will use the number given and report to the controller using that address. The status word will show the latest update, which could be from any of the reporting modules using that address. Setting Field Device Addresses After setting address switches, record the address number and device type. Selection of the node address is done by setting rocker switches on an 8 switch “DIP Switch Assembly” within the detector’s housing. Refer to Figure 16 for switch location. WARNING The network address switches are located within the detector housing. Disassembly of the detector head that contains powered electrical circuits is required to gain access to the network address switches. For hazardous areas, the area must be de-classified before attempting disassembly of the device. Always observe precautions for handling electrostatic sensitive devices. ON BINARY VALUE 1 2 3 4 5 1 2 4 8 16 32 64 128 6 7 8 NODE ADDRESS EQUALS THE ADDED VALUE OF ALL CLOSED ROCKER SWITCHES OPEN = OFF CLOSED = ON A2190 Figure 17—Address Switches for X2200 15.1 13 95-8549 STARTUP PROCEDURE 3. Check input power to the unit. 4. If the fire system has a logging function, check the fire panel log for output status information. See Table 4 for information regarding 0 to 20 mA output. When installation of the equipment is complete, perform the “Fire Alarm Test” below. FIRE ALARM TEST 1. Disable any extinguishing connected to the system. equipment that 5. Turn off the input power to the detector and check all wiring for continuity. Important: Disconnect wiring at the detector before checking system wiring for continuity. is 2. Apply input power to the system. 3. Initiate an oi test. (See “Magnetic oi / Manual oi” under Optical Integrity in the "Description" section of this manual.) 6. If all wiring checks out and cleaning of the oi plate/ window did not correct the fault condition, check for high levels of background UV radiation by covering the detector with the factory supplied cover or aluminum foil. If the fault condition clears, extreme background UV radiation is present. Re-adjust the view of the detector away from the UV source or relocate the detector. 4. Repeat this test for all detectors in the system. If a unit fails the test, refer to the “Troubleshooting” section. 5. Verify that all detectors in the system are properly aimed at the area to be protected. (The Q1201C Laser Aimer is recommended for this purpose.) If none of these actions corrects the problem, return the detector to the factory for repair. 6. Enable extinguishing equipment when the test is complete. NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. TROUBLESHOOTING MAINTENANCE WARNING The sensor module (“front” half of the detector) contains no user serviceable components and should never be tampered with. 1. Disable any extinguishing connected to the unit. equipment that IMPORTANT Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t recommended, since the product is not intended to be serviced and provides proper ingress protection to eliminate potential deterioration of the flamepaths. is 2. Inspect the viewing windows for contamination and clean as necessary. (Refer to the “Maintenance” section for complete information regarding cleaning of the detector viewing windows.) WARNING To avoid a potential electrostatic discharge (ESD), the painted surface of the detector should only be cleaned with a damp cloth. Table 4—Current Level Output Troubleshooting Guide Current Level (±0.3 mA) Status Action 0 mA Power Fault 1 mA General Fault Check system wiring. Cycle power.1 2 mA oi Fault Clean windows.2 4 mA Normal Operation 16 mA Hi Background UV Fault 20 mA Fire Alarm WARNING The sensor module (“front” half of the detector) contains no user serviceable components and should never be tampered with. NOTE Refer to the X2200 Safety manual (95-8672) for specific requirements and recommendations applicable to the proper installation, operation, and maintenance of all SIL-Certified X2200 Flame Detectors. Remove UV source or aim detector away from UV source. 1If fault continues, return device to factory for repair. 2See “Maintenance” section for cleaning procedure. 15.1 To maintain maximum sensitivity and false alarm resistance, the viewing windows of the X2200 must be kept relatively clean. Refer to the following procedure for cleaning instructions. 14 95-8549 CLEANING PROCEDURE LOOSEN TWO CAPTIVE SCREWS CAUTION Disable any extinguishing equipment that is connected to the unit to prevent unwanted actuation. To clean the windows and oi plate, use the window cleaner (p/n 001680-001) with a soft cloth, cotton swab, or tissue and refer to the following procedure: GRASP VISOR AND REMOVE oi PLATE 1. Disable any extinguishing equipment that is connected to the unit. NOTE Remove input power when cleaning the detector windows. The rubbing motion on the surface of the windows during cleaning can create static electricity that could result in unwanted output activation. B2211 Figure 18—oi Plate Removal 2. Clean the viewing window and reflective surfaces of the oi plate using a clean cloth, cotton swab, or tissue with the window cleaning solution. Use Isopropyl alcohol for contaminations that the DetTronics window cleaning solution can not remove. If a fault condition is still indicated after cleaning, remove and clean the oi plate using the oi Plate Removal and Replacement procedure. Recalibration of the oi system requires the use of the Inspector Connector Cable and Inspector Monitor Software. These two items are included in the oi replacement kit, or they can be purchased separately. See Ordering Information for details. PERIODIC CHECKOUT PROCEDURE In compliance with SIL 2, a checkout of the system using the Mag oi or Man oi feature should performed regularly to ensure that the system is operating properly. Refer to Table 1 in the X2200 Safety manual, number 95-8672, for frequency of proof tests. To test the system, perform the “Fire Alarm Test” as described in the “Startup Procedure” section of this manual. IMPORTANT When used in extreme environments, the reflective surface of the detector oi plate may eventually deteriorate, resulting in reoccurring oi faults and the need for oi plate replacement. oi PLATE REMOVAL AND REPLACEMENT CLOCK BATTERY 1. Disable any extinguishing equipment that is connected to the unit. The real time clock has a backup battery that will operate the clock with no external power. Return the device to the factory for battery replacement if needed. 2. Loosen the two captive screws, then grasp the oi plate by the visor and remove it from the detector. See Figure 18. NOTE If the backup battery is depleted, there is no effect on the operation of the flame detector, but the time stamping of the data log may be affected. 3. Install the new (or cleaned) oi plate. 4. Recalibrate the detector's oi system. Refer to the Inspector Monitor manual, number 95-8581, for instructions regarding oi plate replacement and oi system recalibration. CAUTION Do not replace the oi reflector plate without also recalibrating the oi system. 15.1 15 95-8549 FEATURES SPECIFICATIONS • Responds to a fire in the presence of modulated blackbody radiation (i.e., heaters, ovens, turbines) without false alarm OPERATING VOLTAGE— 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). Maximum ripple is 2 volts peak-to-peak. • High speed capability • Built-in data logging / event monitoring, up to 1500 events (up to 1000 general, 500 alarms) • Automatic, manual or magnetic oi testing • Easily replaceable oi plate • Fire, fault and auxiliary relays standard • 0 to 20 mA isolated output (optional) • Eagle Quantum Premier LON/SLC output (optional) • HART communication (optional) • A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions • Operates under adverse weather conditions • Mounting arm allows easy sighting • Integral wiring compartment for ease of installation • Explosion-proof/flame-proof detector housing. Meets FM, CSA, ATEX, and IECEx certification requirements. • Class A wiring per NFPA-72 • Meets NFPA-33 response requirement for under 0.5 second (available when model selected) • 3 year warranty • Advanced signal processing (ARC) • RFI and EMC Directive compliant POWER CONSUMPTION— 2.5 watts at 24 Vdc nominal; 4.5 watts at 24 Vdc in alarm. 2.8 watts at 30 Vdc nominal; 5.1 watts at 30 Vdc in alarm. Total power: 7.6 watts at 30 Vdc with EOL resistor installed. EOL resistor must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. For HART model, refer to Addendum number 95-8638. POWER UP TIME— Fault indication clears after 0.5 second; device is ready to indicate an alarm condition after 30 seconds. OUTPUT RELAYS— Fire Alarm relay, Form C, 5 amperes at 30 Vdc: The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. Fault relay, Form A, 5 amperes at 30 Vdc: The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. Auxiliary relay, Form C, 5 amperes at 30 Vdc: The auxiliary relay has normally open / normally closed contacts, normally energized or de-energized operation, and latching or non-latching operation. Associated Manuals List of X2200 related manuals: TITLE Pulse EQP SIL 2 (Safety) HART Addendum FORM NUMBER 95-8552 95-8533 95-8672 95-8638 Q9033 Mounting Arm and Collar Attachment 95-8686 Inspector Monitor Software for X-Series Flame Detectors 95-8581 CURRENT OUTPUT (Optional)— 0 to 20 milliampere (±0.3 mA) dc current, with a maximum loop resistance of 500 ohms from 18 to 19.9 Vdc and 600 ohms from 20 to 30 Vdc. LON OUTPUT— Digital communication, transformer isolated (78.5 kbps). TEMPERATURE RANGE— Operating: –40°F to +167°F (–40°C to +75°C). Storage: –67°F to +185°F (–55°C to +85°C). Hazardous location ratings from –55°C to +75°C available on flameproof model. HUMIDITY RANGE— 0 to 95% relative humidity, can withstand 100% condensing humidity for short periods of time. 15.1 16 95-8549 WIRING— Field wiring screw terminals are UL/CSA rated for up to 14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire. Screw terminal required torque range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m). 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES. VIEWING ANGLE 15° 30° 0° 100 15° 30° 90 Important: 18 Vdc minimum must be available at the detector. For ambient temperatures below –10°C (14°F) and above +60°C (140°F) use field wiring suitable for both minimum and maximum ambient temperature. 80 45° 45° 70 60 DETECTION DISTANCE (PERCENT) THREAD SIZE— Conduit connection: Four entries, 3/4 inch NPT or M25. Conduit seal not required. 50 40 30 20 SHIPPING WEIGHT (Approximate)— Aluminum: 7 pounds (3.2 kilograms) Stainless Steel: 14.6 pounds (6.7 kilograms) Mounting Arm (AL): 6 pounds (2.75 kilograms) Mounting Arm (SS): 14 pounds (6.4 kilograms) 10 C1288 Figure 19—Detector Cone of Vision WARRANTY PERIOD— 3 years CONE OF VISION— The detector has a 90° cone of vision (horizontal) with the highest sensitivity lying along the central axis. See Figure 18. CERTIFICATION— ® RESPONSE TIME— Less than 6 seconds. (See Appendix A for details.) VdS SOURCE TUBE— Contains radioactive isotope Krypton 85 (Kr85) Calculated Activity: 14,800 Becquerels (0.4μCi). For complete approval details, refer to the appropriate Appendix: ENCLOSURE MATERIAL— Copper-free aluminum (painted) or Stainless Steel (316/ CF8M Cast). Appendix A - FM Appendix B - CSA Appendix C - ATEX Appendix D - IECEx Appendix E - EN54 Appendix F - Additional Approvals VIBRATION— Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW). DIMENSIONS— See Figure 20. 4.7 (11.9) B2223 10.2 (25.9) 4.8 (12.2) Figure 20—Dimensions in Inches (cm) 15.1 17 95-8549 REPLACEMENT PARTS NOTE Radioactive material is subject to regulation. All products containing a source tube meet the definition of an “excepted package” for radioactive material under the US Department of Transportation (DOT), the International Air Transport Association (IATA), the International Civil Aviation Organization (ICAO), the International Maritime Dangerous Goods Code (IMDG), and any other specific hazardous material regulations from the country of source of return (TDG, RID, ADR, etc.). These units are classified as “UN2911, Radioactive Material, Excepted Package – Article.” The detector is not designed to be repaired in the field. If a problem should develop, refer to the "Troubleshooting" section. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair. REPLACEMENT PARTS LIST Part Number Description 009208-002 oi Replacement kit for X52/X22/X98 (5 Reflector Plates) with Inspector Connector and Monitor Replacement oi Reflector Plate for X52/X22/X98 (requires Inspector Connector to calibrate) 007307-002 ORDERING INFORMATION DEVICE REPAIR AND RETURN When ordering, please specify: X2200 UV Flame Detector Refer to the X2200 Model Matrix for details. Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure. When items are being returned, please note: Q9033 Mounting Arm is required: –– Q9033A for aluminum detectors only –– Q9033B for aluminum and stainless steel detectors ACCESSORIES NOTE Shipping personnel must be hazmat trained to pack, mark, and label the return package. Please consult your country-specific regulations. Part Number Description 000511-029 103881-001 Converter RS485 to RS232 Converter RS485 to USB W6300B1002 Serial Inspector Connector (Inspector Monitor software included) W6300B1003 USB Inspector Connector (Inspector Monitor software included) Flame Inspector Monitor CD Model 475 HART Communicator Magnet Magnet and Adapter for Extension Pole Magnet and Extension Pole Q1116A1001, Air Shield (AL) Q1118A1001 Aluminum Air Shield/Flange Mount (AL) Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS) Q1120A1001 Paint Shield mounting ring (AL) Q1201 Laser Laser Battery, 3V Lithium (laser) Q1201C1001 X-Series Laser Holder (AL/Plastic) Q2000A1001 X-Series Weather Shield (AL) Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment Stop Plug, 3/4” NPT, AL Stop Plug, 3/4” NPT, SS Stop Plug, M25, AL, IP66 Stop Plug, M25, SS, IP66 Stop Plug, 20 Pack, 3/4”NPT, AL Stop Plug, 20 Pack, 3/4”NPT, SS Stop Plug, 20 Pack, M25, AL, IP66 Stop Plug, 20 Pack, M25, SS, IP66 14 mm Hex Wrench (Steel) Screwdriver Window cleaner (6 pack) O-ring - Rear Cover (Viton) - black or brown 1 oz grease for detectors (silicone-free) O-ring - Rear Cover (Fluorosilicone) - blue 1 oz PTFE silicone-free lubricant 007819-001 007819-002 Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge. 009207-001 103922-001 102740-002 008082-001 007739-001 007240-001 007818-001 007818-002 009177-001 006097-001 102871-001 007255-001 007338-001 NOTE Det-Tronics reserves the right to apply a service charge for repairing returned product damaged as a result of improper packaging. Return all equipment transportation prepaid to the factory in Minneapolis. 007290-001 007290-002 NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. 15.1 011385-001 101197-001 101197-004 101197-005 101197-003 010816-001 010817-001 010818-001 010819-001 103363-001 103406-001 001680-001 107427-040 005003-001 104346-154 012549-001 18 95-8549 X2200 MODEL MATRIX MODEL X2200 X2200M DESCRIPTION UV Flame Detector UV Flame Detector with Molybdenum Tube TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 0-20 mA 14 Eagle Quantum Premier (EQP) 15 Relay and Pulse 16 Addressable Module Only (Third Party Type)* 23 HART, Relay and 0-20 mA 24 Eagle Quantum TYPE APPROVALS** T SIL/FM/CSA/ATEX/IECEx W FM/CSA/ATEX/IECEx S SIL B INMETRO (Brazil) R VNIIPO/VNIIFTRI (Russia) TYPE CLASSIFICATION 1 Division/Zone Ex d e 2 Division/Zone Ex d *The Addressable Module Only (Type 16) is not FM approved. **Type Approvals can use one or more letters to designate the approvals of the product. 15.1 19 95-8549 APPENDIX A FM APPROVAL AND PERFORMANCE REPORT THE FOLLOWING ITEMS, FUNCTIONS, AND OPTIONS DESCRIBE THE FM APPROVAL: • Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615. • Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T5) Hazardous (Classified) Locations per FM 3615. • Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611. • Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611. • Enclosure rating NEMA/Type 4X per NEMA 250. • Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C). • Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000). Flameproof per ANSI/ISA 60079-0, -1, -7, -31 CL I, ZONE 1, AEx db eb IIC T6...T5 T6 (Tamb –40°C to +60°C) T5 (Tamb –40°C to +75°C) ZONE 21, AEx tb IIIC T80°C Tamb –40°C to +75°C IP66/IP67 CL I, ZONE 1, AEx db IIC T6...T5 T6 (Tamb –40°C to +60°C) T5 (Tamb –40°C to +75°C) ZONE 21, AEx tb IIIC T80°C Tamb –40°C to +75°C IP66/IP67 The following accessories are FM approved for use with the X2200 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 011385-001 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment The following performance criteria were verified: AUTOMATIC OPTICAL INTEGRITY TEST: The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector was verified to detect a fire. MANUAL OPTICAL INTEGRITY TEST: The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated. The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual, is the approved external optical test method for this detector to verify end-to-end detector function. This test replaces the function and need of a traditional external test lamp. 15.1 20 95-8549 FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS Very High Sensitivity Fuel Size Distance feet (m) Typical Response Time (seconds)* Mode n-Heptane Methane 1 x 1 foot 32 inch plume 85 (25.9) 100 (30.5) 3 2 Low Arc Low Arc *Add 2 seconds for EQP model. High Sensitivity Fuel Size Distance feet (m) Typical Response Time (seconds)* Mode n-Heptane n-Heptane n-Heptane Methane Methane Methane 1 x 1 foot 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume 32 inch plume 60 (18.3) 60 (18.3) 60 (18.3) 70 (21.3) 70 (21.3) 70 (21.3) 2 2 7 2 2 2 Standard Hi Arc Very Hi Arc Standard Hi Arc Very Hi Arc *Add 2 seconds for EQP model. Medium Sensitivity Fuel Size Distance feet (m) Typical Response Time (seconds)* Mode n-Heptane n-Heptane Methane Methane 1 x 1 foot 1 x 1 foot 1 x 1 foot 32 inch plume 35 (10.6) 50 (15.2) 55 (16.8) 55 (16.8) 2 3 2 2 Standard Hi Arc Standard Hi Arc *Add 2 seconds for EQP model. RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES Very High Sensitivity (Standard Mode) Distance feet (m) False Alarm Source Sunlight, direct, modulated, reflected 6 kw heater, modulated & unmodulated 250 w vapor lamp, modulated & unmodulated 300 w incandescent lamp, modulated & unmodulated 1500 w electric radiant heater, modulated & unmodulated 2-34 w fluorescent lamps, modulated & unmodulated — 10 (3) 3 (0.9) 3 (0.9) 10 (3) 3 (0.9) Fire Source Distance feet (m) Typical Response Time (seconds)* 6-inch propane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 10 (3) 75 (22.9) 75 (22.9) 75 (22.9) 75 (22.9) 75 (22.9) <30 1 1 1 1 1 *Add 2 seconds for EQP model. FALSE ALARM IMMUNITY Very High Sensitivity (Standard Mode) False Alarm Source Sunlight, direct, modulated, reflected Vibration 6 kw heater 250 w vapor lamp 300 w incandescent lamp 1500 w electric radiant heater 2-34 w fluorescent lamps 15.1 Distance feet (m) — N/A 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 21 Modulated Response Unmodulated Response No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm No Alarm 95-8549 FM Approval and Performance Report – Continued FIELD OF VIEW Very High Sensitivity Fuel Size Distance feet (m) Horizontal (degrees) Typical Response Time (seconds)* Vertical (degrees) Typical Response (seconds)* Mode n-Heptane 1 x 1 foot 42.5 (13) +45 –45 2 2 +45 –30 2 2 Low Arc Methane 32 inch plume 50 (15.2) +45 –45 2 2 +45 –30 2 2 Low Arc *Add 2 seconds for EQP model. High Sensitivity Fuel Size Distance feet (m) Horizontal (degrees) Typical Response Time (seconds)* Vertical (degrees) Typical Response (seconds)* Mode n-Heptane 1 x 1 foot 30 (9.1) +45 –45 1 1 +45 –30 1 1 Standard n-Heptane 1 x 1 foot 30 (9.1) +45 –45 1 1 +45 –30 1 1 Hi Arc n-Heptane 1 x 1 foot 30 (9.1) +45 –45 2 2 +45 –30 2 2 Very Hi Arc Methane 32 inch plume 40 (12.2) +45 –45 1 1 +45 –30 1 1 Standard Methane 32 inch plume 40 (12.2) +45 –45 1 1 +45 –30 1 1 Hi Arc Methane 32 inch plume 35 (10.7) +45 –45 1 1 +45 –30 1 1 Very Hi Arc *Add 2 seconds for EQP model. Medium Sensitivity Fuel Size Distance feet (m) Horizontal (degrees) Typical Response Time (seconds)* Vertical (degrees) Typical Response (seconds)* Mode n-Heptane 1 x 1 foot 17.5 (5.3) +45 –45 1 1 +45 –30 1 1 Standard n-Heptane 1 x 1 foot 25 (7.6) +45 –45 1 1 +45 –30 1 1 Hi Arc Methane 32 inch plume 30 (9.1) +45 –45 2 2 +45 –30 2 2 Standard Methane 32 inch plume 30 (9.1) +45 –45 1 1 +45 –30 1 1 Hi Arc *Add 2 seconds for EQP model. 15.1 22 95-8549 FM Approval and Performance Report – Continued MODEL X2200M The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with unusual chemistry such as black powder. Consult factory for usage recommendations. X2200M RESPONSE CHARACTERISTICS High Sensitivity Fuel Size Distance feet (m) Typical Response Time (seconds) Mode Black Powder 40 grams 10 (3) 0.1 Standard X2200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS High Sensitivity (Standard Mode) False Alarm Source Distance feet (m) Fire Source Distance feet (m) Typical Response Time (seconds) Sunlight, direct, reflected, modulated & unmodulated — 2-inch dia n-Heptane 10 (3) <15 70 w sodium vapor lamp, modulated & unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 0.1 250 w vapor lamp, modulated & unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 0.1 300 w incandescent lamp, modulated & unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 0.1 500 w halogen lamp, modulated & unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 0.1 1500 w electric radiant heater, modulated & unmodulated 10 (3) 1 x 1 foot n-Heptane 40 (12) 0.1 2-34 w fluorescent lamps, modulated & unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 0.1 X2200M FALSE ALARM IMMUNITY High Sensitivity (Standard Mode) Distance feet (m) Modulated Response Unmodulated Response Sunlight, direct, reflected — No Alarm No Alarm 70 w sodium vapor lamp 3 (0.9) No Alarm No Alarm 250 w vapor lamp 3 (0.9) No Alarm No Alarm False Alarm Source 300 w incandescent lamp 3 (0.9) No Alarm No Alarm 500 w halogen lamp 3 (0.9) No Alarm No Alarm 1500 w electric radiant heater 3 (0.9) No Alarm No Alarm 2-34 w fluorescent lamps 3 (0.9) No Alarm No Alarm X2200M FIELD OF VIEW High Sensitivity (Standard Mode) Fuel Size Distance feet (m) Horizontal (degrees) Typical Response Time (seconds) Vertical (degrees) Typical Response (seconds) Black Powder 40 grams 5 (1.5) +45 –45 0.1 0.1 +45 –30 0.1 0.1 15.1 23 95-8549 APPENDIX B CSA APPROVAL DIVISION CLASSIFICATION: Ultraviolet Flame Detector/Controller X2200 series, rated 18-30 Vdc, 2.5 Watts to 7.6 Watts. Relay contacts rated 5 Amps @ 30 Vdc. CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5); Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3); Class III; Enclosure NEMA/Type 4X; APPLICABLE REQUIREMENTS CAN/CSA-C22.2 No. 0-M91 – General requirements - Canadian Electrical Code, Part II CAN/CSA-C22.2 No. 25-1966 – Enclosures for use in Class II Groups E,F & G Hazardous Locations CAN/CSA-C22.2 No. 30-M1986 – Explosion-Proof Enclosures for Use in Class I Hazardous Locations CAN/CSA-C22.2 No. 94-M91 – Special Purpose Enclosures CAN/CSA-C22.2 No. 142-M1987 – Process Control Equipment CAN/CSA-C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations ZONE CLASSIFICATION: CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Ex db eb IIC T6...T5 T6 (Tamb = -50°C to +60°C) T5 (Tamb = -50°C to +75°C) Ex tb IIIC T95°C (Tamb = -50°C to +75°C) Seal required adjacent to enclosure IP66/IP67 Ex db IIC T6...T5 T6 (Tamb = -55°C to +60°C) T5 (Tamb = -55°C to +75°C) Ex tb IIIC T95°C (Tamb = -55°C to +75°C) Seal required adjacent to enclosure IP66/IP67 APPLICABLE REQUIREMENTS CAN/CSA-C22.2 No. 60079-0: 2007 – Electrical apparatus for explosive atmospheres. Part 0: General requirements CAN/CSA-C22.2 No. 60079-1: 2011 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d" CAN/CSA-C22.2 No. 60079-7: 2012 – Explosive atmospheres. Part 7: Equipment protection by increased safety "e" CAN/CSA-C22.2 No. 60079-31: 2012 – Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure "t" The following accessories are CSA approved for use with the X2200 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 011385-001 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 15.1 24 95-8549 APPENDIX C ATEX APPROVAL EC-TYPE EXAMINATION CERTIFICATE DEMKO 02 ATEX 132195X Increased Safety Model FM APPROVED Flameproof Model II 2 G II 2 G FM 0539 II 2 D II 2 D Ex db eb IIC T6...T5 Ex db IIC T6...T5 Ex tb IIIC T80°C Ex tb IIIC T80°C T6 (Tamb = –50°C to +60°C) T6 (Tamb = –55°C to +60°C) T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C) IP66/IP67 IP66/IP67 0539 ® ® APPROVED Compliance with: EN 60079-0: 2012+A11:2013 EN 60079-1: 2014 EN 60079-7: 2007 EN 60079-31: 2009 EN 60529:1991+A1:2000+A2:2013 INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from 14-24 AWG, 2.5-0.2 mm2. The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion protection increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e." They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: • The EOL resistor can only be used within the flameproof terminal compartment. • EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. • The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical damage. • See the "Maintenance" section of this manual for guidance on minimizing the risk from electrostatic discharge. • Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual for more information on conducting repairs. 15.1 25 95-8549 NOTE Operational performance verified from –40°C to +75°C. NOTE An optional third party addressable module can only be used within the Ex d flameproof model unless the addressable module is component certified as Ex e for use within the Ex d e increased safety model. NOTE Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable blanking elements. NOTE For ATEX installations, the X2200 Flame Detector housing must be electrically connected to earth ground. The following accessories are ATEX approved for use with the X2200 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 15.1 26 95-8549 APPENDIX D IECEx APPROVAL CERTIFICATE OF CONFORMITY IECEx ULD 06.0018X Ex db eb IIC T6...T5 Ex db IIC T6...T5 Ex tb IIIC T80°C Ex tb IIIC T80°C T6 (Tamb = –50°C to +60°C) or T6 (Tamb = –55°C to +60°C) T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C) IP66/IP67. IP66/IP67. Compliance with: IEC 60079-0: 2011, Ed. 6 IEC 60079-1: 2014, Ed. 7 IEC 60079-7: 2006, Ed. 4 IEC 60079-31: 2008, Ed. 1 IEC 60529: 2013, Ed. 2.2 INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from 14-24 AWG or 2.5-0.2 mm2. The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion protection increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e." They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: • The EOL resistor can only be used within the flameproof terminal compartment. • EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. • The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical damage. • See the "Maintenance" section of this manual for guidance on minimizing the risk from electrostatic discharge. • Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual for more information on conducting repairs. The following accessories are IECEx approved for use with the X2200 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 15.1 27 95-8549 APPENDIX E EN54 APPROVALS Certification Bodies Conventional Output Certificate/Approval Basis of Approval Number VdS – Construction Product Regulation 0786 – CPR – 20777 EN 54-10 + A1 — — G 203083 VdS 2344 VdS 2504 EN 54-10 + A1 G212020 VdS 2344 VdS 2504 EN 54-10 EN 54-17 S 212002* VdS 2344 EN 54-13 S 212002* VdS 2344 EN 54-13 — — 0832 – CPD – 1383 EN 54-10 + A1 EN 54-17 973e/04 EN 54-10 + A1 973a/04 EN 54-10 + A1 EN 54-17 VdS BRE – Construction Product Directive LPCB LON Output Certificate/Approval Basis of Approval Number * Approved for use in conjunction with the EN54-13 compliant EQP System. INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM The installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view angle in this direction is <90°. The UV-flame detector corresponds to class 1. The following accessories are EN54-10 and EN54-17 approved for use with the X2200 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 011385-001 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 15.1 28 95-8549 APPENDIX F ADDITIONAL APPROVALS SIL 2 BRAZIL IEC 61508 Certified SIL 2 Capable. Applies to specific models – refer to the SIL 2 Certified X2200 Safety Manual (95-8672) for details. UL-BRHZ-0061X Ex d e IIC T6-T5 Gb IP66/IP67 T6 (Tamb = –50°C to +60°C) T5 (Tamb = –50°C to +75°C) – OR – RUSSIA & KAZAKHSTAN Ex d IIC T6-T5 Gb IP66/IP67 T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) VNIIFTRI CERTIFICATE OF CONFORMITY TO TP TC 012/2011 TC RU C-US. ГБ06.B.00158 FRANCE 2ExdeIICT6/T5 IP66 T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) – OR – 1ExdIICT6/T5IP66 T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) AFNOR Identification No: LUV 002 A0. For specific information regarding the X2200 Flame Detector's conformity to NF EN54-10, reference Addendum number 95-8699. RUSSIA VNIIPO CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS, GOST R 53325-2012 C-US.ПБ01.B.02841 15.1 29 95-8549 95-8549 FlexSonic ® Acoustic Leak Detector X3301 Multispectrum IR Flame Detector ­Corporate Office 6901 West 110th Street Minneapolis, MN 55438 USA www.det-tronics.com PointWatch Eclipse ® IR Combustible Gas Detector Phone: 952.946.6491 Toll-free: 800.765.3473 Fax: 952.829.8750 det-tronics@det-tronics.com FlexVu ® Universal Display with GT3000 Toxic Gas Detector Eagle Quantum Premier ® Safety System All trademarks are the property of their respective owners. © 2016 Detector Electronics Corporation. All rights reserved. Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.