Det-Tronics Instructions UV Flame Detector X2200
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
UV Flame Detector
X2200
15.1
Rev: 1/16
95-8549
Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 14
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . 15
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3
oi Plate Removal and Replacement . . . . . . . . 15
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Periodic Checkout Procedure . . . . . . . . . . . . . . 15
Integral Wiring Compartment . . . . . . . . . . . . . . . 3
Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SIGNAL PROCESSING OPTIONS . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
GENERAL APPLICATION INFORMATION . . . . . . . . 4
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Response Characteristics . . . . . . . . . . . . . . . . . . 4
False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 4
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 18
Factors Inhibiting Detector Response . . . . . . . . . 4
Replacement Parts List . . . . . . . . . . . . . . . . . . . 18
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 5
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . 18
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 18
Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 6
X2200 Model Matrix . . . . . . . . . . . . . . . . . . . . . 19
Protection Against Moisture Damage . . . . . . . . . 7
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . 7
Setting Device Network Addresses
(EQ and EQP Models Only) . . . . . . . . . . . . 13
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 20
APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 24
STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 14
Fire Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . 14
APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 25
APPENDIX D – IECEx APPROVAL . . . . . . . . . . . . . 27
APPENDIX E – EN54 APPROVALS . . . . . . . . . . . . 28
APPENDIX F – ADDITIONAL APPROVALS . . . . . . 29
INSTRUCTIONS
UV Flame Detector
X2200
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X2200 includes the Automatic oi ® (Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
DESCRIPTION
The X2200 UV Flame Detector meets the most stringent
requirements worldwide with advanced detection
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
detector is equipped with both automatic and manual
oi test capability. The detector has Division and Zone
explosion-proof ratings and is suitable for use in indoor
and outdoor applications.
The X2200 housing is available in copper-free aluminum
or stainless steel, with NEMA/Type 4X and IP66/IP67
rating.
OUTPUTS
Relays
The standard detector is furnished with fire, fault, and
auxiliary relays. All three relays are rated 5 amperes at
30 Vdc.
The standard output configuration includes fire, fault, and
auxiliary relays. Output options include:
––
0 to 20 mA output (in addition to the three relays)
––
Pulse output for compatibility with existing Detector
Electronics Corporation (Det-Tronics) controller
based systems (with fire and fault relays)
––
Eagle Quantum
(EQP) compatible model
(no analog or relay outputs)
––
HART communication
15.1
The Fire Alarm relay has redundant terminals and normally
open / normally closed contacts, normally de-energized
operation, and latching or non-latching operation.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
Premier ®
©Detector Electronics Corporation 2016
1
Rev: 1/16
95-8549
The Auxiliary relay has normally open / normally
closed contacts, and is configurable for energized or
de-energized operation, and latching or non-latching
operation.
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions. Table 2 indicates the condition of the
LED for each status.
0 to 20 mA Output
A 0 to 20 mA output is available as an option (in addition
to the three relays). This option provides a 0 to 20 mA dc
current output for transmitting detector status information
to other devices. The circuit can be wired in either an
isolated or non-isolated configuration and can drive
a maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table 1
indicates the detector status conditions represented by
the various current levels. The output is calibrated at the
factory, with no need for field calibration. A model with
relays and 0-20 mA with HART is also available. Refer to
Addendum number 95-8638 for complete details.
Table 2—Detector Status Indicator
Power Fault
1 mA
General Fault
2 mA
oi Fault
4 mA
Normal Operation
16 mA
Pre-Alarm
20 mA
Fire Alarm
Fire (Alarm)
Green, flashing off for 0.5 sec.
every 5 sec.
Yellow
Red, flashing on for 1 sec. and
off for 1 sec.
Steady Red
On Power-Up, The LED Flashes in Sequence as Follows,
Indicating Sensitivity and Signal Processing Status
Low UV Sensitivity
Medium UV Sensitivity
High UV Sensitivity
Very High UV Sensitivity
One Red Flash
Two Red Flashes
Three Red Flashes
Four Red Flashes
Stand. UV Signal Process.
Arc Rej. UV Signal Process.
One Yellow Flash
Two Yellow Flashes
ATTENTION
The X2200 contains a source tube that is filled
with a gas mixture containing Krypton 85 (Kr85),
a radioactive material. Radioactive materials are
subject to regulation under U.S. and international
law.
oi (OPTICAL INTEGRITY)
Automatic oi
The X2200 includes the Automatic oi feature — a
calibrated performance test that is automatically
performed once per minute to verify complete detector
operation capabilities. No testing with an external test
lamp is required. The detector automatically performs
the same test that a maintenance person with a test
lamp would perform — once every minute, 60 times per
hour. However, a successful Automatic oi test does not
produce an alarm condition.
LON/SLC Output
The EQP model is designed for use exclusively with
the Det-Tronics Eagle Quantum Premier system. The
detector communicates with the system controller over
a digital communication network or LON/SLC (Local
Operating Network / Signaling Line Circuit). The LON/
SLC is a fault tolerant, two wire digital communication
network arranged in a loop configuration. Analog and
relay outputs are not available on this model.
15.1
Green
Pre-Alarm/Background UV
Table 1—Detector Status Conditions Indicated by Current Level
Detector Status
Power On/Normal Auto oi
(no fault or fire alarm)
Fault
An alarm condition will normally over-ride a fault condition,
unless the nature of the fault condition impairs the ability
of the detector to generate or maintain an alarm output,
i.e., loss of operating power.
0 mA
LED Indicator
Power On/Normal Man oi
NOTE
The output of the 0 to 20 mA current loop is not
monitored by the fault detection circuitry of the
X2200. Therefore, an open circuit on the loop will
not cause the fault relay to change state or the
detector status LED to indicate a fault. The status
of the LED always follows the status of the relays.
Current Level (±0.3 mA)
Detector Status
The detector signals a fault condition when less than half
of the detection range remains. This is indicated by the
Fault output and is evident by the yellow color of the LED
on the face of the detector. See the "Troubleshooting"
section for further information.
2
95-8549
Magnetic oi / Manual oi
DATA LOGGING
The detector also incorporates both Magnetic oi
(Mag oi) and Manual oi (Man oi) features that
provide the same calibrated test as the Automatic
oi, and in addition actuates the Alarm output to verify
operation for preventive maintenance requirements.
These features can be performed at any time and
eliminate the need for testing with a non-calibrated
external test lamp.
Data logging capability is also provided. Status conditions
such as normal, power down, general and oi faults, prealarm, fire alarm, time, and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active,
and again when the status changes. Data is accessible
using the Inspector Connector accessory, RS-485, or the
EQP Controller.
CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
INTEGRAL WIRING COMPARTMENT
All external wiring to the device is connected within
the integral junction box. The detector is furnished with
four conduit entries, with either 3/4 inch NPT or M25
threads.
The Mag oi test is performed by placing a magnet
at the location marked "MAG OI" on the outside
of the detector (see Figure 2). The Man oi test is
accomplished by connecting the oi lead (terminal
22) to power supply minus via an external switch. The
magnet or switch must be held in place for a minimum
of 6 seconds to complete the test. Either of these test
methods activates the calibrated UV emitter. If the
resulting signal meets the test criteria, indicating that
greater than half of the detection range remains, the fire
alarm output of the detector is activated. This condition
remains until the magnet is removed or the switch is
released, regardless of whether the detector has been
configured for latching or non-latching operation.
SIGNAL PROCESSING OPTIONS
The UV detector output (measured in counts per second)
is compared to the fire threshold (the "sensitivity" setting).
If the radiant energy level from the fire exceeds the
selected alarm threshold level, the fire alarm output is
activated. In every application, it is crucial to ensure that
the radiant ultraviolet energy level from the expected fire
at the required distance from the detector will exceed the
selected sensitivity level.
The UV detector in the X2200 can be programmed for:
––
––
If less than half of the detection range remains, no alarm
is produced and a fault is generated. The fault indication
can be reset by momentarily applying the Mag oi or Man
oi switch. In this case, the detector's optics should be
cleaned and the oi tests should be repeated. See the
"Cleaning Procedure" section of this manual for details.
Arc Rejection
The Arc Rejection mode enables the detector to
prevent nuisance fire alarms caused by UV from shortduration electrical arcs or electrostatic discharge,
while maintaining the ability to reliably detect the UV
radiation given off by a flame. Typical applications that
benefit from arc rejection logic include electrostatic
coating processes and uncontrolled environments where
transient UV sources can be present, such as many
typical outdoor applications. Most false alarm sources
have short transient UV signatures, while fire creates
a long UV signature over many seconds. Most fires
are detected in a few seconds (see response times in
Appendix A).
NOTE
Refer to Appendix A for FM verification of
the o i function.
COMMUNICATION
The X2200 is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 supports MODBUS protocol, with
the detector configured as a slave device.
Standard Signal Processing
For HART communication, connect a HART communicator
across a 250 ohm resistor in the 0-20 mA loop.
Standard signal processing is recommended for highspeed suppression systems only. To allow for high-speed
operation, the standard processing mode does not
incorporate the arc rejection programming. This mode
should only be used in a controlled, indoor environment.
NOTE
The EQP model uses LON/SLC communication.
RS-485 and HART communication are not
available on the EQP model.
15.1
Arc Rejection
Standard Signal Processing
3
95-8549
GENERAL APPLICATION
INFORMATION
FACTORS INHIBITING DETECTOR RESPONSE
RESPONSE CHARACTERISTICS
Glass and Plexiglas windows significantly attenuate UV
radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Det-Tronics for recommendations regarding window
materials that will not attenuate UV radiation.
Windows
Response is dependent on the detector's sensitivity
setting, arc rejection, and time delay settings. Other
factors include distance, type of fuel, temperature of the
fuel, and time required for the fire to come to equilibrium.
As with all fire tests, results must be interpreted according
to an individual application.
Obstructions
Radiation must be able to reach the detector in order
for it to respond. Care must be taken to keep physical
obstructions out of the line of view of the detector.
In addition, UV absorbing gases or vapors must not
be allowed to accumulate between the detector and
the protected hazard. See Table 3 for a list of these
substances.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics.
Welding
Electric arc welding is a source of intense ultraviolet
radiation. UV radiation from arc welding readily scatters
and can deflect across significant distances, even when
direct obstructions exist. Any open door or window can
allow nuisance UV radiation from arc welding to enter an
enclosed area.
Smoke
It is recommended that the system be bypassed during
welding operations in situations where the possibility of a
false alarm cannot be tolerated. Gas welding mandates
system bypass, since the gas torch is an actual fire.
Smoke will absorb UV radiation. If accumulations
of dense smoke can be expected to precede the
presence of a flame, then detectors that are used
in enclosed areas should be mounted on the wall
approximately 3 feet (0.9 m) from the ceiling where
the accumulation of smoke is reduced.
Artificial Lighting
Detector Viewing Windows
It is important to keep the detector viewing windows as
free of contaminants as possible in order to maintain
maximum sensitivity. Commonly encountered substances
that can significantly attenuate UV radiation include, but
are certainly not limited to, the following:
The X2200 should not be located within 3 feet (0.9 m)
of artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
EMI/RFI Interference
The X2200 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE Marked. It will
not respond to a 5 watt walkie-talkie at distances greater
than 1 foot (0.3 m).
––
Silicones
––
Oils and greases
––
Dust and dirt buildup
––
Paint overspray
FALSE ALARM SOURCES
The UV sensor is solar blind to the ultraviolet component
of solar radiation. However, it may respond to sources of
UV besides fire, such as arc flash, electric arc welding,
grinding metal, lightning, high voltage corona, x-rays,
and gamma radiation.
15.1
4
95-8549
IMPORTANT SAFETY NOTES
Table 3—UV Absorbing Gases and Vapors
The following is a partial list of compounds that exhibit
significant UV absorption characteristics. These are
also usually hazardous vapors. While generally of little
consequence in small amounts, these gases can restrict
UV detection if they are in the atmosphere in heavy
concentrations. It should also be determined whether or
not large amounts of these gases may be released as a
result of a fire-causing occurrence.
WARNING
Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage.
Acetaldehyde
Methyl Methacrylate
Acetone Alpha-Methylstyrene
Acrylonitrile Naphthalene
Ethyl Acrylate
Nitroethane
Methyl Acrylate
Nitrobenzene
Ethanol Nitromethane
Ammonia 1-Nitropropane
Aniline 2-Nitropropane
Benzene 2-Pentanone
1,3 Butadiene
Phenol
2—Butanone Pyridine
Butylamine
Hydrogen Sulfide
Chlorobenzene Styrene
1-Chloro-1-Nitropropane Tetrachloroethylene
Chloroprene Toluene
Cumene Trichloroethylene
Cyclopentadiene
Vinyl Toluene
O-Dichlorobenzene Xylene
P-Dichlorobenzene
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be done
by a properly trained person.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing detection system tests or maintenance.
If UV-absorbing gases may be a factor in a given
application, precautionary measures should be taken.
Detectors can be placed closer to the potential hazard
area, and/or the sensitivity of the detection system can be
increased. Contact the factory for further details.
CAUTION
The UV flame detectors are to be installed in places
where the risk of mechanical damage is low.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
Substances such as methane, propane, butane, hexane,
camphor, and octane are not UV absorbing.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.
ATTENTION
The source tube is a flame-sealed gas tube
containing Neon, Hydrogen, and a trace amount
of Krypton 85 (Kr85), a radioactive material. The
total volume of gas within the tube is 0.6 ml per
tube, making the gas mixture inside the tube
nonflammable. If the gas envelope is broken, it
will not produce a flammable mixture, and the gas
immediately disperses into the air and is unlikely
to present any type of hazard. Krypton gas and its
radioactive isotope are inert and are not absorbed
by the body. No special handling measure or
personal protection equipment is needed for the
UV detectors.
15.1
5
95-8549
INSTALLATION
NOTE
The recommended lubricant for threads and
O-rings is a silicone-free grease (p/n 005003001) available from Det-Tronics. Under no
circumstances should a lubricant containing
silicone be used.
DETECTOR POSITIONING
Identify all high risk fire ignition sources.
•
Be sure that enough detectors are used to adequately
cover the hazardous area.
•
Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
•
Verify that all detectors in the system are properly
located and positioned so that any fire hazards are
within both the Field of View (FOV) and detection
range of the detector. The Q1201C Laser Aimer
is recommended for establishing the detector's
FOV. Refer to Appendix A for specific information
regarding detector range and FOV.
•
The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain (see
Figure 1). The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.
•
Dense fog, rain as well as certain gases and vapors
(see Table 3) can absorb UV radiation and reduce
the sensitivity of the detector.
•
If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
•
For ATEX/IECEx installations, the X2200 Flame
Detector housing must be electrically connected to
earth ground.
DETECTOR ORIENTATION
Detectors should be positioned to provide the best
unobstructed view of the area to be protected.
The following factors should also be taken into
consideration:
•
•
Refer to Figure 2 and ensure that the oi plate will be
oriented as shown when the X2200 is mounted and
sighted. This will ensure proper operation of the oi
system and will also minimize the accumulation of
moisture and contaminants between the oi plate and
the viewing windows.
IMPORTANT
If removed, the o i plate must be securely
tightened to ensure proper operation of the o i
system (40 oz./inches [28.2 N . cm] recommended).
oi PLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
UV VIEWING WINDOW
oi MAGNET
B2171
DETECTOR
STATUS INDICATOR
The detector must be mounted on a rigid surface in
a low vibration area.
Figure 2—Front View of the X2200
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
INCORRECT
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
D1974
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon
15.1
6
95-8549
PROTECTION AGAINST MOISTURE DAMAGE
NOTE
R e f e r t o “ Po w e r C o n s u m p t i o n” i n t h e
“Specifications” section of this manual.
It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
operation and is the responsibility of the installer.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures 7
through 12, and Figure 15. Consult the factory if not using
shielded cable.
If conduit is used, we recommend installing drains,
according to local codes, at water collection points
to automatically drain accumulated moisture. It is
also recommended to install at least one breather,
according to local codes, at upper locations to provide
ventilation and allow water vapor to escape.
In applications where the wiring cable is installed in
conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate disconnect
capability must be provided.
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
WARNING
All entries must contain appropriately rated plugs
or fittings. It is required that each plug or fitting be
wrench-tightened to an appropriate installation
torque and meet the minimum thread engagement
requirements per the applicable local standards,
codes, and practices in order to retain the defined
ratings. PTFE sealant or equivalent should be used
on NPT threads.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are
highly recommended to prevent water ingress in
outdoor applications. Units with M25 threads must use
an IP66/IP67 washer to prevent water ingress.
IMPORTANT
Devices certified for hazardous locations shall be
installed in accordance with EN/IEC 60079-14 and
NEC 505.
WIRING PROCEDURE
Wire Size and Type
CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.
The system should be wired according to local
codes. The wire size selected should be based
on the number of detectors connected, the supply
voltage and the cable length. Typically 16 AWG or
2.5 mm2 shielded cable is recommended. Wires
should be stripped 3/8 inch (9 mm). A minimum input
voltage of 18 Vdc must be present at the X2200.
4X ø0.42
(1.1)
3.0
(7.6)
4.0
(10.2)
13.1
(33.3)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
3.0
(7.6)
4.0
(10.2)
10.6
(27.0)
F2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
15.1
7
95-8549
Detector Installation
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 or M10 bolts with a length
of at least 1 inch (25 mm). The surface must also have
sufficient capacity to hold the detector and mounting
arm weights (See "Specifications" section). Refer to the
Q9033 Mounting Arm manual (95-8686) for additional
installation information. See Figure 3 for dimensions.
3. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
EOL Resistors (Not Used with EQP Model)
Relay and 0-20 mA Output Models
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
by EOL resistors, observe the following guidelines when
installing the resistors.
Follow the instructions below to install the X2200.
1. Make field connections following local ordinances
and guidelines in this manual. Refer to Figures 4
through 12.
1. Required EOL resistor power rating must be 5 watts
minimum.
2. Check all field wiring to be sure that the proper
connections have been made.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies to
ATEX/IECEx installations only.
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3. Bend the leads and install the EOL resistor as shown
in Figure 6.
4. Maintain a 3/8 inch (10 mm) minimum gap between
the resistor body and the terminal block or any other
neighboring parts.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused conduit
entries shall be closed with suitable blanking
elements.
Figure 4—X2200 Terminal Block
9
mA +
19
mA –
29
SPARE
8
mA + REF
18
mA – REF
28
SPARE
7
COM FIRE
17
COM FIRE
27
COM AUX
6
NO FIRE
16
NO FIRE
26
NO AUX
5
NC FIRE
15
NC FIRE
25
NC AUX
4
COM FAULT
14
COM FAULT
24
RS485 A
3
NO FAULT
13
NO FAULT
23
RS485 B
2
+Vin
12
+Vin
22
MAN Oi
1
–Vin
11
–Vin
21
–Vin
3/8 INCH (10 MM) GAP MINIMUM
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
E2061
Figure 5—Wiring Terminal Identification
15.1
Figure 6—EOL Resistor Installation
8
95-8549
X2200 DETECTOR
FIRE ALARM PANEL
SHIELD
ALARM
+
24 VDC
–
9
mA +
19
mA –
SPARE
29
8
mA + REF
18
mA – REF
SPARE
28
7
COM FIRE2
COM AUX
27
6
NO FIRE2
NO AUX
26
NC AUX
25
COM FIRE
17
NO FIRE
16
5
NC FIRE2
4
COM FAULT1
3
NO FAULT1
2
+Vin
12
1
–Vin
11
EOL
DEVICE4
NC FIRE
15
COM FAULT
14
RS485 A
24
NO FAULT
13
RS485 B
23
+Vin
MAN Oi
22
–Vin
–Vin
21
oi TEST 3
WIRING NOTES:
C2151
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 7—Ex d Wiring Option
SHIELD
X2200 DETECTOR
FIRE ALARM PANEL
9
ALARM
EOL
DEVICE 4
ALARM
+
24 VDC
–
mA +
8
mA + REF
7
COM FIRE2
19
mA –
18
mA – REF
SPARE
29
SPARE
28
COM FIRE
17
COM AUX
27
6
NO FIRE2
NO FIRE
16
NO AUX
26
5
NC FIRE2
NC FIRE
15
NC AUX
25
4
COM FAULT1
COM FAULT
14
3
NO FAULT1
13
2
+Vin
12
1
–Vin
11
RS485 A
24
RS485 B
23
+Vin
MAN Oi
22
–Vin
–Vin
21
NO FAULT
oi TEST 3
WIRING NOTES:
C2152
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 8—Ex e Wiring Option
15.1
9
95-8549
X2200 DETECTOR
X2200 DETECTOR
PLC
PLC
600 Ω MAX
AT 24 VDC
600 Ω MAX
AT 24 VDC
9
9
mA +
19 mA –
29
+
8
mA + REF
18
28
+
–
7
17
27
–
mA
+
24 VDC
6
16
26
5
15
25
24 VDC
24
14
4
–
mA
+
–
26
5
15
25
4
14
24
23
3
2
+Vin
12
MAN Oi
22
1
–Vin
11
–Vin
1
–Vin
11
–Vin
21
13
D2154
21
Oi TEST1
Figure 10—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sinking)
24 VDC
+
–
PLC
19 mA –
29
+
9
8
18
28
–
7
17
27
6
16
26
5
15
25
mA +
4
14
24
3
13
23
2
+Vin
12
MAN Oi
22
1
–Vin
11
–Vin
21
600 Ω MAX
AT 24 VDC
24 VDC
X2200 DETECTOR
19 mA –
29
+
9
8
18
28
–
7
17
27
6
16
26
5
15
25
4
14
24
3
13
mA
+
–
D2155
mA +
23
2
+Vin
12
MAN Oi
1
–Vin
11
–Vin
22
21
D2156
Oi TEST1
Oi TEST1
Figure 12—X2200 Detector Wired for Isolated 0 to 20 mA
Current Output (Sinking)
Figure 11—X2200 Detector Wired for Isolated 0 to 20 mA
Current Output (Sourcing)
NOTES: 1.
15.1
16
23
X2200 DETECTOR
–
27
6
MAN Oi 22
24 VDC
+
–
+
28
17
12
Figure 9—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sourcing)
24 VDC
18 mA – REF
7
13
Oi TEST1
mA
8
+Vin
D2153
600 Ω MAX
AT 24 VDC
29
2
3
PLC
19 mA –
mA +
INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE
INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.
10
95-8549
5. Check all field wiring to be sure that the proper
connections have been made.
EQP Model
1. Connect external wires to the appropriate terminals
inside the device junction box, shown in Figure 13.
See Figure 14 for terminal identification.
6. Replace the device cover and apply input power.
7. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
2. Connect the shield of the power cable to earth
ground at the power source.
3. Connect shields for the LON cable as indicated. See
Figure 15.
NOTE
Refer to the Eagle Quantum Premier system
manual (95-8533) for information regarding power
requirements, network communication cable
requirements, and configuration.
NOTE
DO NOT ground any shields at the detector housing.
4. With input power disconnnected, set the device
network address. (See “Setting Device Network
Addresses” section of this manual for switch
setting procedure.)
Figure 13—X2200 Terminal Block (EQP Model)
6
SHIELD
16
SHIELD
5
COM 1 A
15
COM 2 A
4
COM 1 B
14
COM 2 B
3
PWR SHIELD
13
PWR SHIELD
2
+Vin
12
+Vin
1
–Vin
11
–Vin
C2089
Figure 14—Wiring Terminal Identification for X2200 EQP Model
15.1
11
95-8549
15.1
C 45
12
9 3+
RELAY 5
RELAY 6
RELAY 7
C 42
NO 43
NC 44
31 NO
32 NC
NC 41
29 NC
RELAY 3
30 C
C 39
NO 40
28 NO
NC 38
26 NC
RELAY 2
27 C
C 36
NO 37
25 NO
NC 35
23 NC
RELAY 1
24 C
NO 34
22 NO
P5
C 33
DIGITAL INPUTS
21 C
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
P3
1
2
CH 3
P4
8– 20
8+ 19
CH 7
12 4–
11 4+
7– 18
7+ 17
A
4
P4
B
5
3
COM1
SHIELD
6
COM2
1
4
P2
2
24 VDC –
24 VDC +
5
3
SHIELD
6
P1
EQP3700DCIO
CH 2
10 3–
6– 16
6+ 15
5– 14
5+ 13
P3
A 56
B 55
CH 6
8 2–
7 2+
6 1–
5 1+
P2
59 TxD
58 RxD
57 GND GND 54
P8
NC 47
FAULT NO 46
CH 5
DB-9
CONNECTION
TO COM PORT
OF PC
TXD 3
RXD 2
GND 5
50
A
53
P9
49
B
52
P6
48
COM1
SHIELD
51
COM2
1
3
P7
2
24 VDC –
24 VDC +
4
P1
CONTROLLER
CH 1
CH 4
CH 8
RELAY 4
RELAY 8
95-8549
–
–
24 VDC
BATTERY
+
H
N
AC LINE
24 VDC
SUPPLY
+
+
+
–
–
POWER
–
–
+ DISTRIBUTION +
+
–
+ –
+ –
2
B
N
H
AC LINE
COM2
15
14
16
A
B
5
4
6
COM1
SHIELD
Figure 15—A Typical EQP System
4
3
1
2
C
A
10
3
P3
B
11
1
BUS BAR
SHIELD
12
COM1
12 24 VDC + 2
8
5
COM2
11 24 VDC – 1
7
24 VDC –
24 VDC +
3
6
SHIELD
EQPX2200
13
SHIELD
4
9
EQP2100PSM
COM2
15
14
16
A
B
SHIELD
5
4
6
COM1
2
15
14
16
COM2
A
B
SHIELD
5
4
6
COM1
12 24 VDC + 2
3
11 24 VDC – 1
SHIELD
EQPX2200
13
12 24 VDC +
3
11 24 VDC – 1
SHIELD
EQPX2200
13
3
B
A
14
15
5
4
6
COM1
SHIELD
16
COM2
12 24 VDC + 2
11 24 VDC – 1
SHIELD
EQPX2200
13
A2209
ADDRESS SWITCHES
SENSOR MODULE
REMOVED FROM HOUSING
A2191
Figure 16—Location of Address Switches
The address number is binary encoded with each switch
having a specific binary value with switch 1 being the
LSB (Least Significant Bit), see Figure 17. The device’s
LON address is equal to the added value of all closed
rocker switches. All “Open” switches are ignored.
SETTING DEVICE NETWORK ADDRESSES
(EQ and EQP Models Only)
Overview of Network Addresses
Each device on the LON must be assigned a unique
address. Addresses 1 to 4 are reserved for the controller.
Valid addresses for field devices are from 5 to 250.
Example: for node No. 5, close rocker switches 1 and
3 (binary values 1 + 4); for node No. 25, close rocker
switches 1, 4, and 5 (binary values 1 + 8 + 16).
IMPORTANT
If the address is set to zero or an address above
250, the switch setting will be ignored.
NOTE
The field device sets the LON address only when
power is applied to the device. Therefore, it is
important to set the switches before applying
power. If an address is ever changed, system
power must be cycled before the new address will
take effect.
Duplicated addresses are not automatically detected.
Modules given the same address will use the number
given and report to the controller using that address. The
status word will show the latest update, which could be
from any of the reporting modules using that address.
Setting Field Device Addresses
After setting address switches, record the address
number and device type.
Selection of the node address is done by setting rocker
switches on an 8 switch “DIP Switch Assembly” within the
detector’s housing. Refer to Figure 16 for switch location.
WARNING
The network address switches are located within
the detector housing. Disassembly of the detector
head that contains powered electrical circuits is
required to gain access to the network address
switches. For hazardous areas, the area must
be de-classified before attempting disassembly
of the device. Always observe precautions for
handling electrostatic sensitive devices.
ON
BINARY
VALUE
1
2
3
4
5
1
2
4
8
16 32 64 128
6
7
8
NODE ADDRESS EQUALS THE ADDED VALUE
OF ALL CLOSED ROCKER SWITCHES
OPEN = OFF
CLOSED = ON
A2190
Figure 17—Address Switches for X2200
15.1
13
95-8549
STARTUP PROCEDURE
3. Check input power to the unit.
4. If the fire system has a logging function, check
the fire panel log for output status information.
See Table 4 for information regarding 0 to 20 mA
output.
When installation of the equipment is complete, perform
the “Fire Alarm Test” below.
FIRE ALARM TEST
1. Disable any extinguishing
connected to the system.
equipment
that
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
is
2. Apply input power to the system.
3. Initiate an oi test. (See “Magnetic oi / Manual oi”
under Optical Integrity in the "Description" section of
this manual.)
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
high levels of background UV radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears, extreme
background UV radiation is present. Re-adjust the
view of the detector away from the UV source or
relocate the detector.
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Q1201C
Laser Aimer is recommended for this purpose.)
If none of these actions corrects the problem, return the
detector to the factory for repair.
6. Enable extinguishing equipment when the test is
complete.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
TROUBLESHOOTING
MAINTENANCE
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
1. Disable any extinguishing
connected to the unit.
equipment
that
IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
is
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
WARNING
To avoid a potential electrostatic discharge (ESD),
the painted surface of the detector should only be
cleaned with a damp cloth.
Table 4—Current Level Output Troubleshooting Guide
Current Level
(±0.3 mA)
Status
Action
0 mA
Power Fault
1 mA
General Fault
Check system wiring.
Cycle power.1
2 mA
oi Fault
Clean windows.2
4 mA
Normal Operation
16 mA
Hi Background UV
Fault
20 mA
Fire Alarm
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
NOTE
Refer to the X2200 Safety manual (95-8672) for
specific requirements and recommendations
applicable to the proper installation, operation,
and maintenance of all SIL-Certified X2200 Flame
Detectors.
Remove UV source
or aim detector away
from UV source.
1If fault continues, return device to factory for repair.
2See “Maintenance” section for cleaning procedure.
15.1
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X2200 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.
14
95-8549
CLEANING PROCEDURE
LOOSEN TWO CAPTIVE SCREWS
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
To clean the windows and oi plate, use the window
cleaner (p/n 001680-001) with a soft cloth, cotton swab,
or tissue and refer to the following procedure:
GRASP VISOR AND
REMOVE oi PLATE
1. Disable any extinguishing equipment that is
connected to the unit.
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.
B2211
Figure 18—oi Plate Removal
2. Clean the viewing window and reflective surfaces
of the oi plate using a clean cloth, cotton swab,
or tissue with the window cleaning solution. Use
Isopropyl alcohol for contaminations that the DetTronics window cleaning solution can not remove.
If a fault condition is still indicated after cleaning,
remove and clean the oi plate using the oi Plate
Removal and Replacement procedure.
Recalibration of the oi system requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the system using
the Mag oi or Man oi feature should performed regularly
to ensure that the system is operating properly. Refer to
Table 1 in the X2200 Safety manual, number 95-8672, for
frequency of proof tests. To test the system, perform the
“Fire Alarm Test” as described in the “Startup Procedure”
section of this manual.
IMPORTANT
When used in extreme environments, the reflective
surface of the detector oi plate may eventually
deteriorate, resulting in reoccurring oi faults and
the need for oi plate replacement.
oi PLATE REMOVAL AND REPLACEMENT
CLOCK BATTERY
1. Disable any extinguishing equipment that is
connected to the unit.
The real time clock has a backup battery that will
operate the clock with no external power. Return the
device to the factory for battery replacement if needed.
2. Loosen the two captive screws, then grasp the oi
plate by the visor and remove it from the detector.
See Figure 18.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
3. Install the new (or cleaned) oi plate.
4. Recalibrate the detector's oi system. Refer to the
Inspector Monitor manual, number 95-8581, for
instructions regarding oi plate replacement and oi
system recalibration.
CAUTION
Do not replace the oi reflector plate without also
recalibrating the oi system.
15.1
15
95-8549
FEATURES
SPECIFICATIONS
•
Responds to a fire in the presence of modulated
blackbody radiation (i.e., heaters, ovens, turbines)
without false alarm
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
•
High speed capability
•
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms)
•
Automatic, manual or magnetic oi testing
•
Easily replaceable oi plate
•
Fire, fault and auxiliary relays standard
•
0 to 20 mA isolated output (optional)
•
Eagle Quantum Premier LON/SLC output (optional)
•
HART communication (optional)
•
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
•
Operates under adverse weather conditions
•
Mounting arm allows easy sighting
•
Integral wiring compartment for ease of installation
•
Explosion-proof/flame-proof
detector
housing.
Meets FM, CSA, ATEX, and IECEx certification
requirements.
•
Class A wiring per NFPA-72
•
Meets NFPA-33 response requirement for under
0.5 second (available when model selected)
•
3 year warranty
•
Advanced signal processing (ARC)
•
RFI and EMC Directive compliant
POWER CONSUMPTION—
2.5 watts at 24 Vdc nominal;
4.5 watts at 24 Vdc in alarm.
2.8 watts at 30 Vdc nominal;
5.1 watts at 30 Vdc in alarm.
Total power:
7.6 watts at 30 Vdc with EOL resistor installed.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8638.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open / normally
closed contacts, normally energized or de-energized
operation, and latching or non-latching operation.
Associated Manuals
List of X2200 related manuals:
TITLE
Pulse
EQP
SIL 2 (Safety)
HART Addendum
FORM NUMBER
95-8552
95-8533
95-8672
95-8638
Q9033 Mounting Arm
and Collar Attachment
95-8686
Inspector Monitor Software for
X-Series Flame Detectors
95-8581
CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
15.1
16
95-8549
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
VIEWING ANGLE
15°
30°
0°
100
15°
30°
90
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
80
45°
45°
70
60
DETECTION
DISTANCE
(PERCENT)
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
50
40
30
20
SHIPPING WEIGHT (Approximate)—
Aluminum:
7 pounds (3.2 kilograms)
Stainless Steel:
14.6 pounds (6.7 kilograms)
Mounting Arm (AL): 6 pounds (2.75 kilograms)
Mounting Arm (SS): 14 pounds (6.4 kilograms)
10
C1288
Figure 19—Detector Cone of Vision
WARRANTY PERIOD—
3 years
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 18.
CERTIFICATION—
®
RESPONSE TIME—
Less than 6 seconds. (See Appendix A for details.)
VdS
SOURCE TUBE—
Contains radioactive isotope Krypton 85 (Kr85)
Calculated Activity: 14,800 Becquerels (0.4μCi).
For complete approval details, refer to the appropriate
Appendix:
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - EN54
Appendix F - Additional Approvals
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMENSIONS—
See Figure 20.
4.7
(11.9)
B2223
10.2
(25.9)
4.8
(12.2)
Figure 20—Dimensions in Inches (cm)
15.1
17
95-8549
REPLACEMENT PARTS
NOTE
Radioactive material is subject to regulation.
All products containing a source tube meet
the definition of an “excepted package” for
radioactive material under the US Department of
Transportation (DOT), the International Air Transport
Association (IATA), the International Civil Aviation
Organization (ICAO), the International Maritime
Dangerous Goods Code (IMDG), and any other
specific hazardous material regulations from the
country of source of return (TDG, RID, ADR, etc.).
These units are classified as “UN2911, Radioactive
Material, Excepted Package – Article.”
The detector is not designed to be repaired in the field. If
a problem should develop, refer to the "Troubleshooting"
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the
factory for repair.
REPLACEMENT PARTS LIST
Part Number
Description
009208-002
oi Replacement kit for X52/X22/X98 (5 Reflector Plates)
with Inspector Connector and Monitor
Replacement oi Reflector Plate for X52/X22/X98
(requires Inspector Connector to calibrate)
007307-002
ORDERING INFORMATION
DEVICE REPAIR AND RETURN
When ordering, please specify:
X2200 UV Flame Detector
Refer to the X2200 Model Matrix for details.
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure. When items are being returned, please note:
Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel detectors
ACCESSORIES
NOTE
Shipping personnel must be hazmat trained to
pack, mark, and label the return package. Please
consult your country-specific regulations.
Part Number
Description
000511-029
103881-001
Converter RS485 to RS232
Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
Flame Inspector Monitor CD
Model 475 HART Communicator
Magnet
Magnet and Adapter for Extension Pole
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
Q1120A1001 Paint Shield mounting ring (AL)
Q1201 Laser
Laser Battery, 3V Lithium (laser)
Q1201C1001 X-Series Laser Holder (AL/Plastic)
Q2000A1001 X-Series Weather Shield (AL)
Q9033B Stainless Steel Mounting Arm Assembly is for
aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum
detectors only
Q9033 Collar Attachment
Stop Plug, 3/4” NPT, AL
Stop Plug, 3/4” NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4”NPT, AL
Stop Plug, 20 Pack, 3/4”NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
Window cleaner (6 pack)
O-ring - Rear Cover (Viton) - black or brown
1 oz grease for detectors (silicone-free)
O-ring - Rear Cover (Fluorosilicone) - blue
1 oz PTFE silicone-free lubricant
007819-001
007819-002
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
009207-001
103922-001
102740-002
008082-001
007739-001
007240-001
007818-001
007818-002
009177-001
006097-001
102871-001
007255-001
007338-001
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.
Return all equipment transportation prepaid to the factory
in Minneapolis.
007290-001
007290-002
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
15.1
011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
001680-001
107427-040
005003-001
104346-154
012549-001
18
95-8549
X2200 MODEL MATRIX
MODEL
X2200
X2200M
DESCRIPTION
UV Flame Detector
UV Flame Detector with Molybdenum Tube
TYPE
MATERIAL
A
Aluminum
S
Stainless Steel (316)
TYPE
THREAD TYPE
4M
4 Port, Metric M25
4N
4 Port, 3/4" NPT
TYPE
OUTPUTS
11
Relay
13
Relay and 0-20 mA
14
Eagle Quantum Premier (EQP)
15
Relay and Pulse
16
Addressable Module Only (Third Party Type)*
23
HART, Relay and 0-20 mA
24
Eagle Quantum
TYPE
APPROVALS**
T
SIL/FM/CSA/ATEX/IECEx
W
FM/CSA/ATEX/IECEx
S
SIL
B
INMETRO (Brazil)
R
VNIIPO/VNIIFTRI (Russia)
TYPE
CLASSIFICATION
1
Division/Zone Ex d e
2
Division/Zone Ex d
*The Addressable Module Only (Type 16) is not FM approved.
**Type Approvals can use one or more letters to designate
the approvals of the product.
15.1
19
95-8549
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS, AND OPTIONS DESCRIBE THE FM APPROVAL:
•
Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615.
•
Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T5) Hazardous (Classified) Locations per FM 3615.
•
Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611.
•
Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
•
Enclosure rating NEMA/Type 4X per NEMA 250.
•
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
•
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
CL I, ZONE 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
CL I, ZONE 1, AEx db IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
The following accessories are FM approved for use with the X2200 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector
was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.
15.1
20
95-8549
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)*
Mode
n-Heptane
Methane
1 x 1 foot
32 inch plume
85 (25.9)
100 (30.5)
3
2
Low Arc
Low Arc
*Add 2 seconds for EQP model.
High Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)*
Mode
n-Heptane
n-Heptane
n-Heptane
Methane
Methane
Methane
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
32 inch plume
60 (18.3)
60 (18.3)
60 (18.3)
70 (21.3)
70 (21.3)
70 (21.3)
2
2
7
2
2
2
Standard
Hi Arc
Very Hi Arc
Standard
Hi Arc
Very Hi Arc
*Add 2 seconds for EQP model.
Medium Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)*
Mode
n-Heptane
n-Heptane
Methane
Methane
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
35 (10.6)
50 (15.2)
55 (16.8)
55 (16.8)
2
3
2
2
Standard
Hi Arc
Standard
Hi Arc
*Add 2 seconds for EQP model.
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
Very High Sensitivity (Standard Mode)
Distance
feet (m)
False Alarm Source
Sunlight, direct, modulated, reflected
6 kw heater, modulated & unmodulated
250 w vapor lamp, modulated & unmodulated
300 w incandescent lamp, modulated & unmodulated
1500 w electric radiant heater, modulated & unmodulated
2-34 w fluorescent lamps, modulated & unmodulated
—
10 (3)
3 (0.9)
3 (0.9)
10 (3)
3 (0.9)
Fire Source
Distance
feet (m)
Typical
Response Time
(seconds)*
6-inch propane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
10 (3)
75 (22.9)
75 (22.9)
75 (22.9)
75 (22.9)
75 (22.9)
<30
1
1
1
1
1
*Add 2 seconds for EQP model.
FALSE ALARM IMMUNITY
Very High Sensitivity (Standard Mode)
False Alarm Source
Sunlight, direct, modulated, reflected
Vibration
6 kw heater
250 w vapor lamp
300 w incandescent lamp
1500 w electric radiant heater
2-34 w fluorescent lamps
15.1
Distance
feet (m)
—
N/A
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
21
Modulated Response
Unmodulated Response
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
95-8549
FM Approval and Performance Report – Continued
FIELD OF VIEW
Very High Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)*
Vertical
(degrees)
Typical
Response
(seconds)*
Mode
n-Heptane
1 x 1 foot
42.5
(13)
+45
–45
2
2
+45
–30
2
2
Low Arc
Methane
32 inch plume
50
(15.2)
+45
–45
2
2
+45
–30
2
2
Low Arc
*Add 2 seconds for EQP model.
High Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)*
Vertical
(degrees)
Typical
Response
(seconds)*
Mode
n-Heptane
1 x 1 foot
30
(9.1)
+45
–45
1
1
+45
–30
1
1
Standard
n-Heptane
1 x 1 foot
30
(9.1)
+45
–45
1
1
+45
–30
1
1
Hi Arc
n-Heptane
1 x 1 foot
30
(9.1)
+45
–45
2
2
+45
–30
2
2
Very Hi Arc
Methane
32 inch plume
40
(12.2)
+45
–45
1
1
+45
–30
1
1
Standard
Methane
32 inch plume
40
(12.2)
+45
–45
1
1
+45
–30
1
1
Hi Arc
Methane
32 inch plume
35
(10.7)
+45
–45
1
1
+45
–30
1
1
Very Hi Arc
*Add 2 seconds for EQP model.
Medium Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)*
Vertical
(degrees)
Typical
Response
(seconds)*
Mode
n-Heptane
1 x 1 foot
17.5
(5.3)
+45
–45
1
1
+45
–30
1
1
Standard
n-Heptane
1 x 1 foot
25
(7.6)
+45
–45
1
1
+45
–30
1
1
Hi Arc
Methane
32 inch plume
30
(9.1)
+45
–45
2
2
+45
–30
2
2
Standard
Methane
32 inch plume
30
(9.1)
+45
–45
1
1
+45
–30
1
1
Hi Arc
*Add 2 seconds for EQP model.
15.1
22
95-8549
FM Approval and Performance Report – Continued
MODEL X2200M
The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with
unusual chemistry such as black powder. Consult factory for usage recommendations.
X2200M RESPONSE CHARACTERISTICS
High Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)
Mode
Black Powder
40 grams
10 (3)
0.1
Standard
X2200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS
High Sensitivity (Standard Mode)
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Typical
Response Time
(seconds)
Sunlight, direct, reflected, modulated & unmodulated
—
2-inch dia n-Heptane
10 (3)
<15
70 w sodium vapor lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
250 w vapor lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
300 w incandescent lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
500 w halogen lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
1500 w electric radiant heater, modulated & unmodulated
10 (3)
1 x 1 foot n-Heptane
40 (12)
0.1
2-34 w fluorescent lamps, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
X2200M FALSE ALARM IMMUNITY
High Sensitivity (Standard Mode)
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No Alarm
No Alarm
70 w sodium vapor lamp
3 (0.9)
No Alarm
No Alarm
250 w vapor lamp
3 (0.9)
No Alarm
No Alarm
False Alarm Source
300 w incandescent lamp
3 (0.9)
No Alarm
No Alarm
500 w halogen lamp
3 (0.9)
No Alarm
No Alarm
1500 w electric radiant heater
3 (0.9)
No Alarm
No Alarm
2-34 w fluorescent lamps
3 (0.9)
No Alarm
No Alarm
X2200M FIELD OF VIEW
High Sensitivity (Standard Mode)
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)
Vertical
(degrees)
Typical
Response
(seconds)
Black Powder
40 grams
5
(1.5)
+45
–45
0.1
0.1
+45
–30
0.1
0.1
15.1
23
95-8549
APPENDIX B
CSA APPROVAL
DIVISION CLASSIFICATION:
Ultraviolet Flame Detector/Controller X2200 series, rated 18-30 Vdc, 2.5 Watts to 7.6 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);
Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3);
Class III; Enclosure NEMA/Type 4X;
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91
–
General requirements - Canadian Electrical Code, Part II
CAN/CSA-C22.2 No. 25-1966
–
Enclosures for use in Class II Groups E,F & G Hazardous Locations
CAN/CSA-C22.2 No. 30-M1986
–
Explosion-Proof Enclosures for Use in Class I Hazardous Locations
CAN/CSA-C22.2 No. 94-M91
–
Special Purpose Enclosures
CAN/CSA-C22.2 No. 142-M1987
–
Process Control Equipment
CAN/CSA-C22.2 No. 213-M1987
–
Nonincendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex db eb IIC T6...T5
T6 (Tamb = -50°C to +60°C)
T5 (Tamb = -50°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -50°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
Ex db IIC T6...T5
T6 (Tamb = -55°C to +60°C)
T5 (Tamb = -55°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -55°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0: 2007
–
Electrical apparatus for explosive atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1: 2011
–
Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7: 2012
–
Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
CAN/CSA-C22.2 No. 60079-31: 2012
–
Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure "t"
The following accessories are CSA approved for use with the X2200 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
15.1
24
95-8549
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 02 ATEX 132195X
Increased Safety Model
FM
APPROVED
Flameproof Model
II 2 G
II 2 G
FM
0539
II 2 D
II 2 D
Ex db eb IIC T6...T5
Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67 IP66/IP67
0539
®
®
APPROVED
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-31: 2009
EN 60529:1991+A1:2000+A2:2013
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG, 2.5-0.2 mm2.
The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e." They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical
damage.
•
See the "Maintenance" section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual for
more information on conducting repairs.
15.1
25
95-8549
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.
NOTE
For ATEX installations, the X2200 Flame Detector housing must be electrically connected to earth ground.
The following accessories are ATEX approved for use with the X2200 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
15.1
26
95-8549
APPENDIX D
IECEx APPROVAL
CERTIFICATE OF CONFORMITY
IECEx ULD 06.0018X
Ex db eb IIC T6...T5 Ex db IIC T6...T5
Ex tb IIIC T80°C Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
or
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
Compliance with:
IEC 60079-0: 2011, Ed. 6
IEC 60079-1: 2014, Ed. 7
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
IEC 60529: 2013, Ed. 2.2
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e." They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical
damage.
•
See the "Maintenance" section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual for
more information on conducting repairs.
The following accessories are IECEx approved for use with the X2200 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
15.1
27
95-8549
APPENDIX E
EN54 APPROVALS
Certification Bodies
Conventional Output
Certificate/Approval
Basis of Approval
Number
VdS –
Construction Product Regulation
0786 – CPR – 20777
EN 54-10 + A1
—
—
G 203083
VdS 2344
VdS 2504
EN 54-10 + A1
G212020
VdS 2344
VdS 2504
EN 54-10
EN 54-17
S 212002*
VdS 2344
EN 54-13
S 212002*
VdS 2344
EN 54-13
—
—
0832 – CPD – 1383
EN 54-10 + A1
EN 54-17
973e/04
EN 54-10 + A1
973a/04
EN 54-10 + A1
EN 54-17
VdS
BRE –
Construction Product Directive
LPCB
LON Output
Certificate/Approval
Basis of Approval
Number
* Approved for use in conjunction with the EN54-13 compliant EQP System.
INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM
The installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view
angle in this direction is <90°.
The UV-flame detector corresponds to class 1.
The following accessories are EN54-10 and EN54-17 approved for use with the X2200 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
15.1
28
95-8549
APPENDIX F
ADDITIONAL APPROVALS
SIL 2
BRAZIL
IEC 61508
Certified SIL 2 Capable.
Applies to specific models – refer to the SIL 2 Certified
X2200 Safety Manual (95-8672) for details.
UL-BRHZ-0061X
Ex d e IIC T6-T5 Gb IP66/IP67
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C)
– OR –
RUSSIA & KAZAKHSTAN
Ex d IIC T6-T5 Gb IP66/IP67
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
VNIIFTRI
CERTIFICATE OF CONFORMITY TO TP TC 012/2011
TC RU C-US. ГБ06.B.00158
FRANCE
2ExdeIICT6/T5 IP66
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
– OR –
1ExdIICT6/T5IP66
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
AFNOR Identification No: LUV 002 A0.
For specific information regarding the X2200 Flame
Detector's conformity to NF EN54-10, reference
Addendum number 95-8699.
RUSSIA
VNIIPO
CERTIFICATE OF CONFORMITY TO TECHNICAL
REGULATIONS, GOST R 53325-2012
C-US.ПБ01.B.02841
15.1
29
95-8549
95-8549
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2016 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.