Det-Tronics Instructions UV Flame Detector with Pulse Output X2200
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
UV Flame Detector with Pulse Output
X2200
8.1
Rev: 12/15
95-8552
Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 16
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . 17
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3
oi Plate Removal and Replacement . . . . . . . . 17
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Periodic Checkout Procedure . . . . . . . . . . . . . . 18
Integral Wiring Compartment . . . . . . . . . . . . . . . 3
Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . 18
SIGNAL PROCESSING OPTIONS . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
GENERAL APPLICATION INFORMATION . . . . . . . . 4
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Response Characteristics . . . . . . . . . . . . . . . . . . 4
False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 4
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 20
Factors Inhibiting Detector Response . . . . . . . . . 4
Replacement Parts List . . . . . . . . . . . . . . . . . . . 20
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 5
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . 20
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 20
Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 6
X2200 Model Matrix . . . . . . . . . . . . . . . . . . . . . 21
Protection Against Moisture Damage . . . . . . . . . 7
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . 7
Setting Device Network Addresses
(EQ and EQP Models Only) . . . . . . . . . . . . 15
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 22
APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 26
STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 15
Fire Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . 15
APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 27
APPENDIX D – IECEx APPROVAL . . . . . . . . . . . . . 29
INSTRUCTIONS
UV Flame Detector
with Pulse Output
X2200
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X2200 includes the Automatic oi ® (Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
The detector has Division and Zone explosion-proof
ratings and is suitable for use in indoor and outdoor
applications. The X2200 housing is available in copperfree aluminum or stainless steel, with NEMA/Type 4X and
IP66IP67 rating.
DESCRIPTION
The X2200 UV Flame Detector meets the most stringent
requirements worldwide with advanced detection
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
detector is equipped with both automatic and manual oi
test capability.
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
The X2200 with pulse/relay output is designed for use
in controller based systems. In addition to use in new
systems, it can serve as a direct field replacement
for Detector Electronics Corporation’s (Det-Tronics)
controller based flame detectors that generate a pulse
output (not compatible with R7484 and R7409B/C).
OUTPUTS
Relays
The detector is furnished with fire and fault relays. The
relays are rated 5 amperes at 30 Vdc.
The Fire Alarm relay has redundant terminals and normally
open / normally closed contacts, normally de-energized
operation, and latching or non-latching operation.
When used as a field replacement, all operating features
of the current controller are retained in addition to gaining
the advanced features of the X2200 Flame Detector. In
typical applications, the four wire X2200 can utilize all
existing system wiring.
8.1
©Detector Electronics Corporation 2016
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
1
Rev: 12/15
95-8552
Latching relays can be reset by removing input power
(0.1 second minimum).
oi (OPTICAL INTEGRITY)
An alarm condition will normally over-ride a fault condition,
unless the nature of the fault condition impairs the ability
of the detector to generate or maintain an alarm output,
i.e., loss of operating power.
The X2200 includes the Automatic oi feature — a
calibrated performance test that is automatically
performed once per minute to verify complete detector
operation capabilities. No testing with an external test
lamp is required. The detector automatically performs
the same test that a maintenance person with a test
lamp would perform — once every minute, 60 times per
hour. However, a successful Automatic oi test does not
produce an alarm condition.
Automatic oi
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions. Table 1 indicates the condition of the
LED for each status.
The detector signals a fault condition when less than half
of the detection range remains. This is indicated by the
Fault output and is evident by the yellow color of the LED
on the face of the detector. See the “Troubleshooting”
section for further information.
Table 1—Detector Status Indicator
Detector Status
LED Indicator
Power On/Normal Auto oi
(no fault or fire alarm)
Green
Power On/Normal Man oi
Green, flashing off for 0.5 sec.
every 5 sec.
Fault
Pre-Alarm/Background UV
Fire (Alarm)
Magnetic oi / Manual oi
CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
Yellow
Red, flashing on for 1 sec. and
off for 1 sec.
Steady Red
The detector incorporates both Magnetic oi (Mag oi)
and Manual oi (Man oi) test capabilities. These tests
provide pulses (80 to 100 CPS) to the controller (R7404
or R7494) when the detector is not in fault. If the test
is successful, the controller indicates a fire and the
appropriate zone output is active.
On Power-Up, The LED Flashes in Sequence as Follows,
Indicating Sensitivity and Signal Processing Status
Low UV Sensitivity
Medium UV Sensitivity
High UV Sensitivity
Very High UV Sensitivity
One Red Flash
Two Red Flashes
Three Red Flashes
Four Red Flashes
Stand. UV Signal Process.
Arc Rej. UV Signal Process.
One Yellow Flash
Two Yellow Flashes
NOTE
If the detector is in a fault condition, a successful
Mag o i or Man o i test cannot be performed.
The Mag oi test is performed by placing a magnet by
the location marked “MAG OI” on the outside of the
detector (see Figure 2). This action causes the detector
to immediately send pulses to the controller. Controller
response is as follows:
ATTENTION
The X2200 contains a source tube that is filled
with a gas mixture containing Krypton 85 (Kr85),
a radioactive material. Radioactive materials are
subject to regulation under U.S. and international
law.
8.1
2
•
The Zone LED blinks.
•
The digital display indicates which Zone is in alarm.
•
The status indicator shows “6” (fire).
95-8552
IMPORTANT
Mag o i can be performed with the controller’s
(R7404/R7494) keylock switch in either the
NORMAL or TEST position. In NORMAL, the
controller goes into alarm and activates its outputs.
If no controller alarm output is desired, place
the keylock switch in the TEST position before
touching the magnet to the outside of the detector.
Man o i operates only with the keylock switch in
the TEST position.
INTEGRAL WIRING COMPARTMENT
All external wiring to the device is connected within the
integral junction box. The detector is furnished with four
conduit entries, with either 3/4 inch NPT or M25 threads.
SIGNAL PROCESSING OPTIONS
The UV detector output (measured in counts per second)
is compared to the fire threshold (the “sensitivity”
setting). If the radiant energy level from the fire exceeds
the selected alarm threshold level, the fire alarm output is
activated. In every application, it is crucial to ensure that
the radiant ultraviolet energy level from the expected fire
at the required distance from the detector will exceed the
selected sensitivity level.
During the entire test, the detector gives no indication
of alarm.
To reset the controller status and alarms, place the
keylock switch in RESET. Return the keylock switch to
NORMAL when testing is complete.
The UV detector in the X2200 can be programmed for:
The Man oi test is nearly identical to the Mag oi test,
except for the manner in which the test is initiated:
––
Arc Rejection
––
Standard Signal Processing.
•
Place the keylock switch on the controller (R7404/
R7494) in the TEST position.
Arc Rejection
•
Press the SELECT button to select the appropriate
detector for test.
•
Press the TEST/ACCEPT button to initiate the test.
The Arc Rejection mode enables the detector to
prevent nuisance fire alarms caused by UV from shortduration electrical arcs or electrostatic discharge,
while maintaining the ability to reliably detect the UV
radiation given off by a flame. Typical applications that
benefit from arc rejection logic include electrostatic
coating processes and uncontrolled environments where
transient UV sources can be present, such as many
typical outdoor applications. Most false alarm sources
have short transient UV signatures, while fire creates
a long UV signature over many seconds. Most fires
are detected in a few seconds (see response times in
Appendix A).
Controller and detector responses are identical to the
Mag oi test described above.
To reset the controller status and alarms, place the
keylock switch in RESET. Return the keylock switch to
NORMAL when testing is complete.
NOTE
Refer to Appendix A for FM verification of the
o i function.
Standard Signal Processing
Standard signal processing is recommended for highspeed suppression systems only. To allow for high-speed
operation, the standard processing mode does not
incorporate the arc rejection programming. This mode
should only be used in a controlled, indoor environment.
COMMUNICATION
The X2200 is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 supports Modbus protocol, with the
detector configured as a slave device.
DATA LOGGING
Data logging capability is also provided. Status conditions
such as normal, power down, general and oi faults, prealarm, fire alarm, time, and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active,
and again when the status changes. Data is accessible
using the Inspector Connector accessory or RS-485.
8.1
3
95-8552
GENERAL APPLICATION
INFORMATION
FACTORS INHIBITING DETECTOR RESPONSE
RESPONSE CHARACTERISTICS
Glass and Plexiglas windows significantly attenuate UV
radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Det-Tronics for recommendations regarding window
materials that will not attenuate UV radiation.
Windows
Response is dependent on the detector’s sensitivity
setting, arc rejection, and time delay settings. Other
factors include distance, type of fuel, temperature of the
fuel, and time required for the fire to come to equilibrium.
As with all fire tests, results must be interpreted according
to an individual application.
Obstructions
Radiation must be able to reach the detector in order
for it to respond. Care must be taken to keep physical
obstructions out of the line of view of the detector.
In addition, UV absorbing gases or vapors must not
be allowed to accumulate between the detector and
the protected hazard. See Table 2 for a list of these
substances.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics.
Welding
Electric arc welding is a source of intense ultraviolet
radiation. UV radiation from arc welding readily scatters
and can deflect across significant distances, even when
direct obstructions exist. Any open door or window can
allow nuisance UV radiation from arc welding to enter an
enclosed area.
Smoke
It is recommended that the system be bypassed during
welding operations in situations where the possibility of a
false alarm cannot be tolerated. Gas welding mandates
system bypass, since the gas torch is an actual fire.
Smoke will absorb UV radiation. If accumulations
of dense smoke can be expected to precede the
presence of a flame, then detectors that are used
in enclosed areas should be mounted on the wall
approximately 3 feet, 0.9 m from the ceiling where the
accumulation of smoke is reduced.
Artificial Lighting
Detector Viewing Windows
The X2200 should not be located within 3 feet, 0.9 m
of artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
It is important to keep the detector viewing windows as
free of contaminants as possible in order to maintain
maximum sensitivity. Commonly encountered substances
that can significantly attenuate UV radiation include, but
are certainly not limited to, the following:
EMI/RFI Interference
The X2200 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE Marked. It will
not respond to a 5 watt walkie-talkie at distances greater
than 1 foot, 0.3 m.
––
Silicones
––
Oils and greases
––
Dust and dirt buildup
––
Paint overspray
FALSE ALARM SOURCES
The UV sensor is solar blind to the ultraviolet component
of solar radiation. However, it may respond to sources of
UV besides fire, such as arc flash, electric arc welding,
grinding metal, lightning, high voltage corona, x-rays,
and gamma radiation.
8.1
4
95-8552
IMPORTANT SAFETY NOTES
Table 2—UV Absorbing Gases and Vapors
The following is a partial list of compounds that exhibit
significant UV absorption characteristics. These are
also usually hazardous vapors. While generally of little
consequence in small amounts, these gases can restrict
UV detection if they are in the atmosphere in heavy
concentrations. It should also be determined whether or
not large amounts of these gases may be released as a
result of a fire-causing occurrence.
WARNING
Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage. This type of damage
could be undetected and could result in failure to
see a fire and/or false alarm.
Acetaldehyde
Methyl Methacrylate
Acetone Alpha-Methylstyrene
Acrylonitrile Naphthalene
Ethyl Acrylate
Nitroethane
Methyl Acrylate
Nitrobenzene
Ethanol Nitromethane
Ammonia 1-Nitropropane
Aniline 2-Nitropropane
Benzene 2-Pentanone
1,3 Butadiene
Phenol
2—Butanone Pyridine
Butylamine
Hydrogen Sulfide
Chlorobenzene Styrene
1-Chloro-1-Nitropropane Tetrachloroethylene
Chloroprene Toluene
Cumene Trichloroethylene
Cyclopentadiene
Vinyl Toluene
O-Dichlorobenzene Xylene
P-Dichlorobenzene
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be done
by a properly trained person.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing system tests or maintenance.
If UV-absorbing gases may be a factor in a given
application, precautionary measures should be taken.
Detectors can be placed closer to the potential hazard
area, and/or the sensitivity of the detection system can be
increased. Contact the factory for further details.
CAUTION
The UV flame detectors are to be installed in places
where the risk of mechanical damages is low.
Substances such as methane, propane, butane, hexane,
camphor, and octane are not UV absorbing.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.
ATTENTION
The source tube is a flame-sealed gas tube
containing Neon, Hydrogen, and a trace amount
of Krypton 85 (Kr85), a radioactive material. The
total volume of gas within the tube is 0.6 ml per
tube, making the gas mixture inside the tube
nonflammable. If the gas envelope is broken, it
will not produce a flammable mixture, and the gas
immediately disperses into the air and is unlikely
to present any type of hazard. Krypton gas and its
radioactive isotope are inert and are not absorbed
by the body. No special handling measure or
personal protection equipment is needed for the
UV detectors.
8.1
5
95-8552
INSTALLATION
NOTE
The recommended lubricant for threads and
O-rings is a silicone free grease (p/n 005003001) available from Det-Tronics. Under no
circumstances should a lubricant containing
silicone be used.
DETECTOR POSITIONING
Identify all high risk fire ignition sources.
•
Be sure that enough detectors are used to adequately
cover the hazardous area.
•
Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
•
Verify that all detectors in the system are properly
located and positioned so that any fire hazards are
within both the Field of View (FOV) and detection
range of the detector. The Q1201C Laser Aimer
is recommended for establishing the detector’s
FOV. Refer to Appendix A for specific information
regarding detector range and FOV.
•
The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain (see
Figure 1). The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.
•
Dense fog, rain as well as certain gases and vapors
(see Table 2) can absorb UV radiation and reduce
the sensitivity of the detector.
•
If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
•
For ATEX/IECEx installations, the X2200 Flame
Detector housing must be electrically connected to
earth ground.
DETECTOR ORIENTATION
Detectors should be positioned to provide the best
unobstructed view of the area to be protected.
The following factors should also be taken into
consideration:
•
•
Refer to Figure 2 and ensure that the oi plate will be
oriented as shown when the X2200 is mounted and
sighted. This will ensure proper operation of the oi
system and will also minimize the accumulation of
moisture and contaminants between the oi plate and
the viewing windows.
IMPORTANT
If removed, the o i plate must be securely
tightened to ensure proper operation of the o i
system (40 oz./inches [28.2 N . cm] recommended).
oi PLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
UV VIEWING WINDOW
oi MAGNET
B2171
DETECTOR
STATUS INDICATOR
The detector must be mounted on a rigid surface in
a low vibration area.
Figure 2—Front View of the X2200
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
INCORRECT
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
D1974
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon
8.1
6
95-8552
PROTECTION AGAINST MOISTURE DAMAGE
IMPORTANT
A minimum input voltage of 18 Vdc must be
present at the X2200.
It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
operation and is the responsibility of the installer.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures
6 through 10. Consult the factory if not using shielded
cable.
If conduit is used, we recommend installing drains,
according to local codes, at water collection points
to automatically drain accumulated moisture. It is
also recommended to install at least one breather,
according to local codes, at upper locations to provide
ventilation and allow water vapor to escape.
The “B” (pulse output) and “D” (oi driver) leads from
each detector should be shielded from the “B” and
“D” leads of all other detectors in order to prevent
false alarms resulting from crosstalk between zones.
It is recommended that the “A” and “C” leads also be
shielded to provide maximum immunity to EMI/RFI.
(See Figures 6 to 10.)
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
In applications where the wiring cable is installed in
conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate
disconnect capability must be provided.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are
highly recommended to prevent water ingress in
outdoor applications. Units with M25 threads must use
an IP66/IP67 washer to prevent water ingress.
WARNING
All entries must contain appropriately rated plugs
or fittings. It is required that each plug or fitting be
wrench-tightened to an appropriate installation
torque and meet the minimum thread engagement
requirements per the applicable local standards,
codes, and practices in order to retain the defined
ratings. PTFE sealant or equivalent should be
used.
IMPORTANT
Devices certified for hazardous locations shall be
installed in accordance with EN/IECEx 60079-14
and NEC 505
WIRING PROCEDURE
Wire Size and Type
The system should be wired according to local codes.
The wire size selected should be based on the number
of detectors connected, the supply voltage, and the
cable length. Typically 16 AWG or 2.5 mm2 shielded
cable is recommended. Wires should be stripped
3/8 inch (9 mm). In some cases where the X2200 is
replacing existing pulse output detectors, the wiring
and power supplies may not be adequate. Consult the
factory for assistance.
4X ø0.42
(1.1)
3.0
(7.6)
4.0
(10.2)
13.1
(33.4)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
3.0
(7.6)
4.0
(10.2)
10.6
(27.0)
E2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
8.1
7
95-8552
Detector Wiring
CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.
IMPORTANT
If installing an X2200 in place of an existing
detector, be sure to move the “A” Lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source. Do not apply 290 Vdc to
the X2200.
Detector Installation
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 or M10 bolts with a length of at
least 1 inch, 25 mm. The surface must also have sufficient
capacity to hold the detector and mounting arm weights
(See “Specifications” section). Refer to the Q9033
Mounting Arm manual, number 95-8686, for additional
mounting information. See Figure 3 for dimensions.
1. Make field connections following local ordinances
and guidelines in this manual.
Figure 4 shows the wiring terminal strip located
inside the detector’s integral junction box.
Figure 5 shows the wiring terminal identification
for the X2200 detector with pulse output.
Leave the shield open at the detector end and
permanently isolate it from accidental contact
with the case and/or other conductors. At the
controller/fire panel end, connect the shield
and power minus (–) to chassis (earth) ground
either directly or through a 0.47 µF 400 Volt nonpolarized capacitor (not supplied). (Refer to
Figures 6 through 10.)
Figures 11 and 12 provide examples of typical
installations with an X2200 wired to a fire alarm
panel.
Figure 13 shows an EOL resistor installed within the
integral wiring compartment of the detector (refer to
the “EOL Resistors” section for details).
2. Check all field wiring to be sure that the proper
connections have been made.
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
Figure 4—X2200 Terminal Block
9
19
8
18
PULSE OUT
29
SPARE
28
SPARE
7
COM FIRE
17
COM FIRE
27
6
N.O. FIRE
16
N.O. FIRE
26
5
N.C. FIRE
15
N.C. FIRE
25
4
COM FAULT
14
COM FAULT
24
RS-485 A
3
N.O. FAULT
13
N.O. FAULT
23
RS-485 B
2
+ Vin
12
+ Vin
22
MAN Oi
1
– Vin
11
– Vin
21
– Vin
3. Make the final sighting adjustments and use a 14
mm hex wrench to ensure that the mounting arm
assembly is tight.
D2070
Figure 5—X2200 Pulse Wiring Terminal Identification
8.1
8
95-8552
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X2200
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
DETECTOR 5
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-9
J1-17
DETECTOR 6
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-10
J1-18
DETECTOR 7
X2200
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
–
2
+
–
3
J2
R7404 CONTROLLER
} 10 TO 38 VDC
ZONE OUTPUT 1
33
ZONE OUTPUT 2
34
(A) +290 VDC
ZONE OUTPUT 3
35
4
B - INPUT 1
ZONE OUTPUT 4
36
5
B - INPUT 2
ZONE OUTPUT 5
37
6
B - INPUT 3
ZONE OUTPUT 6
38
7
B - INPUT 4
ZONE OUTPUT 7
39
8
B - INPUT 5
ZONE OUTPUT 8
40
9
B - INPUT 6
FIRE LOGIC “A”
41
10
B - INPUT 7
FIRE LOGIC “B”
42
11
B - INPUT 8
ALARM OUTPUT
43
12
D1-1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D1-2 oi DRIVER
OUTPUTS INHIBITED
45
14
D1-3 oi DRIVER
FAULT OUTPUT
46
15
D1-4 oi DRIVER
EXTERNAL ACCEPT
47
16
D1-5 oi DRIVER
STATUS & DET. OUTPUT S1
48
17
D1-6 oi DRIVER
STATUS & DET. OUTPUT S2
49
18
D1-7 oi DRIVER
STATUS & DET. OUTPUT S3
50
19
D1-8 oi DRIVER
STATUS & DET. OUTPUT S4
51
20
D2-1 oi DRIVER
STATUS & DET. OUTPUT S5
52
21
D2-2 oi DRIVER
STATUS & DET. OUTPUT S6
53
22
D2-3 oi DRIVER
STATUS & DET. OUTPUT S7
54
23
D2-4 oi DRIVER
STATUS & DET. OUTPUT S8
55
24
D2-5 oi DRIVER
DATA BUS 0
56
25
D2-6 oi DRIVER
DATA BUS 1
57
26
D2-7 oi DRIVER
DATA BUS 2
58
27
D2-8 oi DRIVER
DATA BUS 3
59
28
DMA OUT AVAILABLE
DATA BUS 4
60
29
DMA OUT
DATA BUS 5
61
30
DMA IN
DATA BUS 6
62
31
DATA STROBE
DATA BUS 7
63
32
DMA IN AVAILABLE
CHASSIS (EARTH) GND
64
A2157
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X2200
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
62
63
0.47 μF / 400 VDC
NON-POLARIZED
64
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 6—A Typical System, X2200 Detectors Wired to R7404 Controller
8.1
9
95-8552
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X2200
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+290 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
STATUS & DET. OUTPUT S3
50
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
DATA BUS 5
61
DATA BUS 6
62
DATA BUS 7
63
17
18
#2
#1
#19
#22
#2
#1
#19
#22
21
22
23
24
25
J1-9
J1-17
26
27
28
#2
#1
#19
#22
#2
#1
#19
#22
29
30
J1-10
J1-18
DETECTOR 7
X2200
1
20
DETECTOR 6
X2200
J1
+
19
DETECTOR 5
X2200
24
VDC
31
32
J2
R7404 STAR LOGIC CONTROLLER
D7 oi DRIVER
D8 oi DRIVER
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED
EARTH GROUND
64
A2158
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X2200
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
62
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
63
0.47 μF / 400 VDC
NON-POLARIZED
64
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 7—A Typical System, X2200 Detectors Wired to R7404 Star Logic Controller
8.1
10
95-8552
X2200
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
#2
#1
#19
#22
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+24 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
17
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
STATUS & DET. OUTPUT S3
50
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
DATA BUS 5
61
DATA BUS 6
62
DATA BUS 7
63
18
#2
#1
#19
#22
21
22
23
24
25
J1-9
J1-17
26
27
28
#2
#1
#19
#22
#2
#1
#19
#22
29
30
J1-10
J1-18
DETECTOR 7
X2200
1
20
DETECTOR 6
X2200
J1
+
19
DETECTOR 5
X2200
24
VDC
31
32
J2
R7494 CONTROLLER
D7 oi DRIVER
D8 oi DRIVER
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED
EARTH GROUND
64
A2159
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X2200
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
62
63
0.47 μF / 400 VDC
NON-POLARIZED
64
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 8—A Typical System, X2200 Detectors Wired to R7494 Controller
8.1
11
95-8552
R7495 CONTROLLER
(NOT FM APPROVED)
X2200
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X2200
#2
#1
#19
#22
#2
#1
#19
#22
33
34
J2-45
J2-37
DETECTOR 3
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-46
J2-38
DETECTOR 4
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
DETECTOR 6
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-50
J2-42
DETECTOR 8
47
B5
48
B6
49
B7
50
B8
A2160
TO J1-2
TERMINAL IDENTIFICATION FOR X2200
WITH PULSE OUTPUT.
TERMINAL NO.
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
FUNCTION
3
4
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
0.47 μF / 400 VDC
NON-POLARIZED
5
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 9—A Typical System, X2200 Detectors Wired to R7495 Controller
8.1
12
95-8552
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO
TERMINAL J2-34 (290 VDC).
R7405 CONTROLLER
(NOT FM APPROVED)
X2200
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X2200
#2
#1
#19
#22
#2
#1
#19
#22
33
J2-45
J2-37
DETECTOR 3
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-46
J2-38
DETECTOR 4
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
34
+290 VDC
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
DETECTOR 6
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X2200
#2
#1
#19
#22
#2
#1
#19
#22
J2-50
J2-42
DETECTOR 8
47
B5
48
B6
49
B7
50
B8
A2161
TO J1-2
TERMINAL IDENTIFICATION FOR X2200
WITH PULSE OUTPUT.
TERMINAL NO.
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
FUNCTION
3
4
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
0.47 μF / 400 VDC
NON-POLARIZED
5
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 10—A Typical System, X2200 Detectors Wired to R7405 Controller
8.1
13
95-8552
X2200 DETECTOR
FIRE ALARM PANEL
9
19
8
7
6
5
ALARM
4
3
+
24 VDC
2
–
1
PULSE OUT
18
COM FIRE2
SPARE
29
SPARE
28
17
N.O. FIRE2
27
16
N.C. FIRE2
26
END OF
LINE DEVICE 4
15
COM FAULT1
N.O. FAULT1
+ Vin
14
RS-485 A
24
13
RS-485 B
23
MAN Oi
22
12
– Vin
25
– Vin
11
21
oi TEST 3
WIRING NOTES:
B2162
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
Figure 11—Ex d Wiring Option
X2200 DETECTOR
FIRE ALARM PANEL
9
19
8
EOL
DEVICE 4
ALARM
7
ALARM
6
5
4
3
+
24 VDC
2
–
1
PULSE OUT
18
COM FIRE2
N.O. FIRE2
N.C. FIRE2
COM FAULT1
N.O. FAULT1
+ Vin
– Vin
SPARE
29
SPARE
28
17
27
16
26
15
25
14
RS-485 A
24
13
RS-485 B
23
MAN Oi
22
12
11
– Vin
21
oi TEST 3
B2163
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
4 EOL RESISTOR SUPPLIED BY PANEL.
Figure 12—Ex e Wiring Option
8.1
14
95-8552
STARTUP PROCEDURE
EOL RESISTORS
To ensure that the insulating material of the wiring terminal
block will not be affected by the heat generated by EOL
resistors, observe the following guidelines when installing
the resistors.
When installation of the equipment is complete, apply
power and allow 20 to 30 minutes for the detector’s
heated optics to reach equilibrium. Then perform one or
more of the following tests:
1. Required EOL resistor power rating must be 5 watts
minimum.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies to
ATEX/IECEx installations only.
•
Man oi Test — Tests detector output and wiring,
without generating a fire alarm.
•
Count Test Mode — Measures actual detector output
to controller (cps), without generating a fire alarm.
•
Fire Alarm Test — For complete system test including
detector relays. Generates fire alarm output.
MANUAL oi TEST (Output to Controller)
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches, 40 mm.
1. Place the keylock switch in the TEST position.
3. Bend the leads and install the EOL resistor as shown
in Figure 13.
2. Press the SELECT button to display the desired
zone on the ZONE indicator on the front panel of the
controller.
4. Maintain a 3/8 inch, 10 mm minimum gap between
the resistor body and the terminal block or any other
neighboring parts.
3. Press and hold the TEST button. The ZONE OUTPUT
LED for the tested zone flashes and the SYSTEM
STATUS display indicates a “6” (fire condition) if the
test is successful.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused
apertures shall be closed with suitable blanking
elements.
4. Release the TEST button. The ZONE OUTPUT LED
for the tested zone should remain on steadily.
5. Return to step 2 to test the next detector.
If the system responds differently than indicated above,
proceed with the count test for the problem zone to verify
detector and wiring operation.
3/8 INCH (10 MM) GAP MINIMUM
COUNT TEST MODE (Output to Controller)
When in the Count Test mode, the frequency of the
digital pulses from the detector is displayed on the ZONE
and DETECTOR indicators on the controller faceplate.
The Count Test mode may be used to check the signal
(cps) from a test fire or false alarm source. This can be
useful during system set-up for sensitivity and time delay
settings. This test is performed in the following manner:
19 18 17 16 15 14 13 12 11
1. Place the keylock switch in the TEST position.
2. Simultaneously press and release the SELECT and
TEST buttons. The Status display will change from
a “1” to an “8” indicating that the controller is in the
Count Test mode of operation.
B2126
BULKHEAD
Figure 13—EOL Resistor Installation
8.1
15
95-8552
TROUBLESHOOTING
3. Press the SELECT button until the desired zone is
displayed on the ZONE indicator on the controller
front panel.
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
4. Press and hold the TEST button. The DETECTOR/
ZONE display indicates the counts per second (cps)
received from the detector. If the counts per second
exceeds 99, the FIRE LOGIC LEDs are illuminated to
indicate that the number shown on the display must
be multiplied by 10. The normal reading for an oi
test is 80 to 110 cps. For a live fire test, 270 - 330
cps will be generated.
1. Disable any extinguishing
connected to the unit.
equipment
that
is
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
A zero reading may indicate a dirty window, oi problem,
faulty detector, or defective wiring.
3. Check input power to the unit.
4. Check system and detector logs.
Release the Test button, and the ZONE and DETECTOR
display should drop to a reading of zero to one counts
per second.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
3. Initiate a live fire test or a Mag oi test. (See “Magnetic
oi / Manual oi” under “Optical Integrity” in the
"Description" section of this manual.)
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
high levels of background UV radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears, extreme
background UV radiation is present. Re-adjust the
view of the detector away from the UV source or
relocate the detector.
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
If none of these actions corrects the problem, return the
detector to the factory for repair.
FIRE ALARM TEST (Pulse Output to Fire Alarm Panel)
1. Disable any extinguishing
connected to the system.
equipment
that
is
2. Apply input power to the system.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Q1201C
Laser Aimer is recommended for this purpose.)
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
6. Enable extinguishing equipment when the test is
complete.
8.1
16
95-8552
MAINTENANCE
LOOSEN TWO CAPTIVE SCREWS
IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
GRASP VISOR AND
REMOVE oi PLATE
WARNING
To avoid potential electrostatic discharge (ESD),
the painted surface of the detector should only be
cleaned with a damp cloth.
B2211
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
Figure 14—oi Plate Removal
IMPORTANT
When used in extreme environments, the reflective
surface of the detector o i plate may eventually
deteriorate, resulting in reoccurring o i faults and
the need for o i plate replacement.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X2200 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.
CLEANING PROCEDURE
oi PLATE REMOVAL AND REPLACEMENT
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
1. Disable any extinguishing
connected to the unit.
To clean the windows and oi plate, use the window
cleaner (p/n 001680-001) with a soft cloth, cotton swab,
or tissue and refer to the following procedure:
1. Disable any extinguishing
connected to the unit.
equipment
that
that
is
2. Loosen the two captive screws, then grasp the oi
plate by the visor and remove it from the detector.
See Figure 14.
is
3. Install the new (or cleaned) oi plate.
4. Recalibrate the detector’s oi system. Refer to the
Inspector Monitor Manual (95-8581) for instructions
regarding oi plate replacement and oi system
recalibration.
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.
CAUTION
Do not replace the o i reflector plate without also
recalibrating the o i system.
2. Clean the viewing window and reflective surfaces
of the o i plate using a clean cloth, cotton swab,
or tissue with the window cleaning solution. Use
Isopropyl alcohol for contaminations that the DetTronics window cleaning solution cannot remove.
If a fault condition is still indicated after cleaning,
remove and clean the o i plate using the o i Plate
Removal and Replacement procedure.
8.1
equipment
Recalibration of the oi system requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.
17
95-8552
SPECIFICATIONS
PERIODIC CHECKOUT PROCEDURE
A checkout of the system using the Mag oi or Man oi
feature should be performed on a regularly scheduled
basis to ensure that the system is operating properly. To
test the system, perform the “Manual oi Test,” “Count Test
Mode” or “Fire Alarm Test” as described in the “Startup
Procedure” section of this manual.
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
CLOCK BATTERY
The real time clock has a backup battery that will operate
the clock with no external power. Return the device to the
factory for battery replacement if needed.
POWER CONSUMPTION—
2.5 watts at 24 Vdc nominal;
4.5 watts at 24 Vdc in alarm.
2.8 watts at 30 Vdc nominal;
5.1 watts at 30 Vdc in alarm.
Total power: 7.6 watts at 30 Vdc with EOL resistor installed.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
FEATURES
•
Responds to a fire in the presence of modulated
blackbody radiation (i.e., heaters, ovens, turbines)
without false alarm
•
High speed capability
•
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms)
•
Pulse output for compatibility with controller based
systems
•
Automatic, manual or magnetic oi testing
•
Easily replaceable oi plate
•
Fire and fault relays
•
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
•
Operates under adverse weather conditions
•
Mounting arm allows easy sighting
•
Integral wiring compartment for ease of installation
•
Explosion-proof/flame-proof
detector
housing.
Meets FM, CSA, ATEX, and IECEx certification
requirements.
•
Class A wiring per NFPA-72 (relay connections).
(Pulse output is equivalent to class A when detectors
are installed in a redundant configuration)
•
3 year warranty
•
Advanced signal processing (ARC)
•
RFI and EMC Directive Compliant
8.1
For CSA compliance, the power source must
utilize a SELV (Safety Extra Low Voltage) or Class
2 style power supply.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or nonlatching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
18
95-8552
DIMENSIONS—
See Figure 16.
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 15.
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
VIEWING ANGLE
15°
30°
0°
100
15°
90
30°
80
45°
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
45°
70
60
DETECTION
DISTANCE
(PERCENT)
50
SHIPPING WEIGHT (Approximate)—
Aluminum:
7 pounds (3.2 kilograms).
Stainless Steel:
14.6 pounds (6.7 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).
40
30
20
10
WARRANTY PERIOD—
3 years
A1288
Figure 15—Detector Cone of Vision
CERTIFICATION—
FM
®
APPROVED
RESPONSE TIME—
Typical response times are under 6 seconds.
See Appendix A for actual response times.
For complete approval details, refer to the appropriate
Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
SOURCE TUBE—
Contains radioactive isotope Krypton 85 (Kr85)
Calculated Activity: 14,800 Becquerels (0.4μCi).
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW),
4.7
(11.9)
B2223
10.2
(25.9)
4.8
(12.2)
Figure 16—Dimensions in Inches (cm)
8.1
19
95-8552
REPLACEMENT PARTS
NOTE
Radioactive material is subject to regulation.
All products containing a source tube meet
the definition of an “excepted package” for
radioactive material under the US Department of
Transportation (DOT), the International Air Transport
Association (IATA), the International Civil Aviation
Organization (ICAO), the International Maritime
Dangerous Goods Code (IMDG), and any other
specific hazardous material regulations from the
country of source of return (TDG, RID, ADR, etc.).
These units are classified as “UN2911, Radioactive
Material, Excepted Package – Article.”
The detector is not designed to be repaired in the field. If
a problem should develop, refer to the "Troubleshooting"
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the
factory for repair.
REPLACEMENT PARTS LIST
Part Number
Description
009208-002
oi Replacement kit for X52/X22/X98 (5 Reflector Plates)
with Inspector Connector and Monitor
Replacement oi Reflector Plate for X52/X22/X98
(requires Inspector Connector to calibrate)
007307-002
ORDERING INFORMATION
When ordering, please specify:
X2200 UV Flame Detector with Pulse Output
Refer to the X2200 Model Matrix for details.
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure. When items are being returned, please note:
Q9033 mount is required:
Q9033A for aluminum detectors only.
Q9033B for aluminum and stainless steel detectors.
ACCESSORIES
NOTE
Shipping personnel must be hazmat trained to
pack, mark, and label the return package. Please
consult your country-specific regulations.
Description
000511-029
103881-001
Converter RS485 to RS232
Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
Flame Inspector Monitor CD
Model 475 HART Communicator
Magnet
Magnet and Adapter for Extension Pole
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
Q1120A1001 Paint Shield mounting ring (AL)
Q1201 Laser
Laser Battery, 3V Lithium (laser)
Q1201C1001 X-Series Laser Holder (AL/Plastic)
Q2000A1001 X-Series Weather Shield (AL)
Q9033B Stainless Steel Mounting Arm Assembly is for
aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum
detectors only
Q9033 Collar Attachment
Stop Plug, 3/4” NPT, AL
Stop Plug, 3/4” NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4”NPT, AL
Stop Plug, 20 Pack, 3/4”NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
Window cleaner (6 pack)
O-ring - Rear Cover (Viton) - black or brown
1 oz grease for detectors (silicone-free)
O-ring Rear Cover (Fluorosilicone) - blue
1 oz PTFE silicone-free lubricant
007819-001
007819-002
009207-001
103922-001
102740-002
008082-001
007739-001
007240-001
007818-001
007818-002
009177-001
006097-001
102871-001
007255-001
007338-001
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.
007290-001
Return all equipment transportation prepaid to the factory
in Minneapolis.
007290-002
011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
001680-001
107427-040
005003-001
104346-154
012540-001
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
8.1
Part Number
20
95-8552
X2200 MODEL MATRIX
MODEL
X2200
X2200M
DESCRIPTION
UV Flame Detector
UV Flame Detector with Molybdenum Tube
TYPE
MATERIAL
A
Aluminum
S
Stainless Steel (316)
TYPE
THREAD TYPE
4M
4 Port, Metric M25
4N
4 Port, 3/4" NPT
TYPE
15
OUTPUTS
Relay and Pulse
TYPE
W
APPROVALS
FM/CSA/ATEX/IECEx
TYPE
8.1
21
CLASSIFICATION
1
Division/Zone Ex d e
2
Division/Zone Ex d
95-8552
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS, AND OPTIONS DESCRIBE THE FM APPROVAL:
•
Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615.
•
Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T5) Hazardous (Classified) Locations per FM 3615.
•
Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611.
•
Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
•
Enclosure rating NEMA Type 4X per NEMA 250.
•
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
•
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
CL I, ZONE 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
CL I, ZONE 1, AEx db IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
The following accessories are FM approved for use with the X2200 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector
was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
The oi test procedure, as described in the “Magnetic oi / Manual oi” section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.
8.1
22
95-8552
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)
Mode
n-Heptane
Methane
1 x 1 foot
32 inch plume
85 (25.9)
100 (30.5)
3
2
Low Arc
Low Arc
High Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)
Mode
n-Heptane
n-Heptane
n-Heptane
Methane
Methane
Methane
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
32 inch plume
60 (18.3)
60 (18.3)
60 (18.3)
70 (21.3)
70 (21.3)
70 (21.3)
2
2
7
2
2
2
Standard
Hi Arc
Very Hi Arc
Standard
Hi Arc
Very Hi Arc
Medium Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)
Mode
n-Heptane
n-Heptane
Methane
Methane
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
35 (10.6)
50 (15.2)
55 (16.8)
55 (16.8)
2
3
2
2
Standard
Hi Arc
Standard
Hi Arc
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
Very High Sensitivity (Standard Mode)
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Typical
Response Time
(seconds)
Sunlight, direct, modulated, reflected
6 kw heater, modulated & unmodulated
250 w vapor lamp, modulated & unmodulated
300 w incandescent lamp, modulated & unmodulated
1500 w electric radiant heater, modulated & unmodulated
2-34 w fluorescent lamps, modulated & unmodulated
—
10 (3)
3 (0.9)
3 (0.9)
10 (3)
3 (0.9)
6-inch propane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
10 (3)
75 (22.9)
75 (22.9)
75 (22.9)
75 (22.9)
75 (22.9)
<30
1
1
1
1
1
FALSE ALARM IMMUNITY
Very High Sensitivity (Standard Mode)
False Alarm Source
Sunlight, direct, modulated, reflected
Vibration
6 kw heater
250 w vapor lamp
300 w incandescent lamp
1500 w electric radiant heater
2-34 w fluorescent lamps
8.1
Distance feet (m)
Modulated Response
Unmodulated Response
—
N/A
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
No Alarm
23
95-8552
FM Approval and Performance Report – Continued
FIELD OF VIEW
Very High Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)
Vertical
(degrees)
Typical
Response
(seconds)
Mode
n-Heptane
1 x 1 foot
42.5
(13)
+45
–45
2
2
+45
–30
2
2
Low Arc
Methane
32 inch plume
50
(15.2)
+45
–45
2
2
+45
–30
2
2
Low Arc
High Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)
Vertical
(degrees)
Typical
Response
(seconds)
Mode
n-Heptane
1 x 1 foot
30
(9.1)
+45
–45
1
1
+45
–30
1
1
Standard
n-Heptane
1 x 1 foot
30
(9.1)
+45
–45
1
1
+45
–30
1
1
Hi Arc
n-Heptane
1 x 1 foot
30
(9.1)
+45
–45
2
2
+45
–30
2
2
Very Hi Arc
Methane
32 inch plume
40
(12.2)
+45
–45
1
1
+45
–30
1
1
Standard
Methane
32 inch plume
40
(12.2)
+45
–45
1
1
+45
–30
1
1
Hi Arc
Methane
32 inch plume
35
(10.7)
+45
–45
1
1
+45
–30
1
1
Very Hi Arc
Medium Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)
Vertical
(degrees)
Typical
Response
(seconds)
Mode
n-Heptane
1 x 1 foot
17.5
(5.3)
+45
–45
1
1
+45
–30
1
1
Standard
n-Heptane
1 x 1 foot
25
(7.6)
+45
–45
1
1
+45
–30
1
1
Hi Arc
Methane
32 inch plume
30
(9.1)
+45
–45
2
2
+45
–30
2
2
Standard
Methane
32 inch plume
30
(9.1)
+45
–45
1
1
+45
–30
1
1
Hi Arc
8.1
24
95-8552
FM Approval and Performance Report – Continued
MODEL X2200M
The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with
unusual chemistry such as black powder. Consult factory for usage recommendations.
X2200M RESPONSE CHARACTERISTICS
High Sensitivity
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)
Mode
Black Powder
40 grams
10 (3)
0.1
Standard
X2200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS
High Sensitivity (Standard Mode)
Distance
feet (m)
Typical
Response Time
(seconds)
2-inch dia n-Heptane
10 (3)
<15
1 x 1 foot n-Heptane
40 (12)
0.1
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
1500 w electric radiant heater, modulated & unmodulated
10 (3)
1 x 1 foot n-Heptane
40 (12)
0.1
2-34 w fluorescent lamps, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
Distance
feet (m)
Fire Source
Sunlight, direct, reflected, modulated & unmodulated
—
70 w sodium vapor lamp, modulated & unmodulated
3 (0.9)
250 w vapor lamp, modulated & unmodulated
300 w incandescent lamp, modulated & unmodulated
500 w halogen lamp, modulated & unmodulated
False Alarm Source
X2200M FALSE ALARM IMMUNITY
High Sensitivity (Standard Mode)
Distance feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
False Alarm Source
—
No Alarm
No Alarm
70 w sodium vapor lamp
3 (0.9)
No Alarm
No Alarm
250 w vapor lamp
3 (0.9)
No Alarm
No Alarm
300 w incandescent lamp
3 (0.9)
No Alarm
No Alarm
500 w halogen lamp
3 (0.9)
No Alarm
No Alarm
1500 w electric radiant heater
3 (0.9)
No Alarm
No Alarm
2-34 w fluorescent lamps
3 (0.9)
No Alarm
No Alarm
X2200M FIELD OF VIEW
High Sensitivity (Standard Mode)
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical
Response Time
(seconds)
Vertical
(degrees)
Typical
Response
(seconds)
Black Powder
40 grams
5
(1.5)
+45
–45
0.1
0.1
+45
–30
0.1
0.1
8.1
25
95-8552
APPENDIX B
CSA APPROVAL
DIVISION CLASSIFICATION:
Ultraviolet Flame Detector/Controller X2200 series, rated 18-30 Vdc, 2.5 Watts to 7.6 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);
Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3);
Class III; Enclosure NEMA/Type 4X;
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91
–
General requirements - Canadian Electrical Code, Part II
CAN/CSA-C22.2 No. 25-1966
–
Enclosures for use in Class II Groups E,F, & G Hazardous Locations
CAN/CSA-C22.2 No. 30-M1986
–
Explosion-Proof Enclosures for Use in Class I Hazardous Locations
CAN/CSA-C22.2 No. 94-M91
–
Special Purpose Enclosures
CAN/CSA-C22.2 No. 142-M1987
–
Process Control Equipment
CAN/CSA-C22.2 No. 213-M1987
–
Nonincendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex db eb IIC T6...T5
T6 (Tamb = -50°C to +60°C)
T5 (Tamb = -50°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -50°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
Ex db IIC T6...T5
T6 (Tamb = -55°C to +60°C)
T5 (Tamb = -55°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -55°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0: 2007
–
Electrical apparatus for explosive atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1: 2011
–
Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7: 2012
–
Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
CAN/CSA-C22.2 No. 60079-31: 2012
–
Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure "t"
The following accessories are CSA approved for use with the X2200 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
8.1
26
95-8552
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 02 ATEX 132195X
Increased Safety Model
FM
APPROVED
Flameproof Model
II 2 G
II 2 G
FM
0539
II 2 D
II 2 D
Ex db eb IIC T6...T5
Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
0539
®
®
APPROVED
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-31: 2009
EN 60529:1991+A1:2000+A2:2013
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e." They
shall be IP66/IP67 rated, suitable for the conditions of use, and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
•
•
•
•
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical
damage.
See the "Maintenance" section of this manual for guidance on minimizing risk from electrostatic discharge.
Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual
for more information on conducting repairs.
8.1
27
95-8552
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.
NOTE
For ATEX installations, the X2200 Flame Detector housing must be electrically connected to earth ground.
The following accessories are ATEX approved for use with the X2200 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
8.1
28
95-8552
APPENDIX D
IECEx APPROVAL
CERTIFICATE OF CONFORMITY
IECEx ULD 06.0018X
Ex db eb IIC T6...T5 Ex db IIC T6...T5
Ex tb IIIC T80°C Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
or
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
Compliance with:
IEC 60079-0: 2011, Ed. 6
IEC 60079-1: 2014, Ed. 7
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
IEC 60529: 2013, Ed. 2.2
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X2200UV shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Ultraviolet (UV) flame detector type X2200 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
•
•
•
•
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical
damage.
See the "Maintenance" section of this manual for guidance on minimizing risk from electrostatic discharge.
Flameproof joints are not intended to be repaired. See the "Device Repair and Return" section of this manual
for more information on conducting repairs.
The following accessories are IECEx approved for use with the X2200 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
8.1
29
95-8552
95-8552
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2016 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.