DET-TRONICS Eagle Quantum Premier Instruction Manual in English
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
Eagle Quantum Premier ®
Fire and Gas Alarm Control System and Automatic
Releasing for Pre-Action and Deluge Systems
18.2
Rev: 12/16
95-8533
Table of Contents
Section 1 - Safety
ALERT MESSAGES....................................................... 1-1
Section 2 - Introduction
SYSTEM DESCRIPTION............................................... 2-1
Communications Loop.................................................... 2-1
LON Communication Heartbeat...................................... 2-2
Theory of Operation........................................................ 2-3
Controller Logs................................................................ 2-4
Controller User Logic...................................................... 2-4
Communication Network Fault Operation....................... 2-5
Multiple Wiring Faults...................................................... 2-5
SIL2 Capable System...................................................... 2-5
MAJOR COMPONENT DESCRIPTIONS......................2-6
System Controller............................................................ 2-6
Controller Redundancy................................................ 2-6
Ethernet Interface Board.............................................. 2-7
Serial Interface Board.................................................. 2-7
EQP RS-485 Surge Protector....................................... 2-7
ControlNet Board or EtherNet DLR Board.................... 2-7
Controller-to-Controller Communication....................... 2-8
EQP Marine Application System.................................. 2-8
Local Operating Network (LON)..................................... 2-8
Network Extenders....................................................... 2-8
Section 3 - Installation
SAFETY SYSTEM DESIGN REQUIREMENTS.............. 3-1
Identifying the Area of Protection.................................... 3-1
Identifying Wiring, Network (LON),
and System Power Requirements................................... 3-1
General Wiring Requirements...................................... 3-1
Power Wiring................................................................ 3-1
System Wiring (ATEX and IECEx)................................. 3-1
Determining Power Requirements............................... 3-3
EQ211xPS, EQ213xPS and EQ217xPS
Power Supplies............................................................ 3-5
Backup Battery............................................................. 3-5
Battery Charger............................................................ 3-5
EQP21x0PS(–X) Power Supplies.................................. 3-5
EQP2410PS(–P) Converter........................................... 3-6
Determining Power Requirements............................... 3-6
Shield Grounding......................................................... 3-7
Junction Box Grounding.............................................. 3-7
Response Time vs. System Size.................................. 3-7
Moisture Damage Protection........................................ 3-7
Electrostatic Discharge................................................ 3-7
GROUND FAULT MONITOR (GFM) INSTALLATION.......3-8
Mounting......................................................................... 3-8
Wiring ............................................................................. 3-8
EQ21xxPS Series Power Supplies and
EQ2100PSM Power Supply Monitor............................. 2-9
NETWORK & NETWORK EXTENDER INSTALLATION....3-8
EQP21xxPS(–X) Power Supplies and
EQP2410PS(–P) Converter........................................... 2-9
Wiring ............................................................................. 3-8
EQ2220GFM Ground Fault Monitor.............................. 2-9
Enclosure Requirements............................................... 3-10
Field Devices................................................................... 2-9
Flame Detectors........................................................... 2-9
EQ2200 UVHT + C7050 Detector................................ 2-9
Model HD Heat Detector.............................................. 2-9
U5015 Explosion-Proof Smoke Detector.................... 2-10
X7050 xWatch Explosion-Proof Camera.................... 2-10
EQ3730EDIO Enhanced Discrete I/O Module........... 2-10
EQ3700 8 Channel DCIO Module.............................. 2-11
EQ3720 8 Channel Relay Module.............................. 2-11
EQ3710AIM Analog Input Module............................. 2-12
EQ3770 Explosion-Proof I/O (EIO) Module................ 2-12
EQ3760ASM Addressable Smoke and Heat Module.... 2-13
EQ3750ASH Addressable Smoke and Heat Module.... 2-13
EQ22xxARM Agent Release Module......................... 2-14
EQ22xxSAM Signal Audible Module.......................... 2-15
EQ22xxIDC Series Initiating Device Circuit................ 2-15
UD10 DCU Emulator.................................................. 2-16
EQ22xxDCU and EQ22xxDCUEX
Digital Communication Units...................................... 2-16
PIRECL PointWatch Eclipse....................................... 2-17
LS2000 Line-of-Sight.................................................. 2-17
EQ3900 Enclosure Solutions...................................... 2-17
EQ3900RPS Explosion-Proof Power Supply.............. 2-17
Mounting......................................................................... 3-8
EQ3XXX CONTROLLER INSTALLATION.................. 3-10
Mounting....................................................................... 3-11
Serial Interface Board................................................... 3-11
Ethernet Interface Board............................................... 3-11
Wiring ........................................................................... 3-11
Power Wiring.............................................................. 3-11
Electrical Connections............................................... 3-11
Controller to Controller Communication........................ 3-16
Configuration................................................................. 3-20
Software Defined Addresses...................................... 3-20
EQ3XXX REDUNDANT CONTROLLER
INSTALLATION...........................................................3-22
Enclosure Requirements............................................... 3-22
Mounting....................................................................... 3-22
Wiring ........................................................................... 3-22
LON Wiring.................................................................... 3-22
High Speed Serial Link (HSSL)..................................... 3-23
Configuration................................................................. 3-23
S³ Configuration.......................................................... 3-23
Controller Addresses.................................................. 3-23
RS-485/RS-232........................................................... 3-23
ControlNet.................................................................. 3-23
EtherNet DLR............................................................. 3-23
Table of Contents – Continued
Ethernet...................................................................... 3-23
Section 4 - Operation
EQ21XXPS SERIES POWER SUPPLY AND
POWER SUPPLY MONITOR INSTALLATION............3-23
SYSTEM CONTROLLER............................................... 4-1
Pushbuttons.................................................................... 4-1
Mounting....................................................................... 3-24
Controller Status Indicators............................................. 4-2
Wiring ........................................................................... 3-24
Text Display..................................................................... 4-2
Startup........................................................................... 3-24
Controller Menu Options................................................. 4-2
Measuring Battery Voltage and Charging Current........... 3-25
Controller Audible Alarm................................................. 4-6
EQP2XX0PS(–X) POWER SUPPLIES AND
REDUNDANCY MODULE INSTALLATION................3-26
ControlNet Status Indicators (Optional).......................... 4-7
Mounting....................................................................... 3-26
EtherNet DLR Status Indicators...................................... 4-7
Wiring ........................................................................... 3-26
Sequence of Events During a Configuration
Data Download................................................................ 4-8
Startup........................................................................... 3-29
Controller Redundancy................................................... 4-9
EDIO MODULE INSTALLATION.................................3-29
ENHANCED DISCRETE I/O MODULE....................... 4-11
Configuration................................................................. 3-33
Power-Up Sequence..................................................... 4-11
8 CHANNEL DCIO INSTALLATION........................3-35
8 CHANNEL DCIO MODULE..................................... 4-12
Mounting....................................................................... 3-35
Power-Up Sequence..................................................... 4-12
Wiring ........................................................................... 3-36
8 CHANNEL RELAY MODULE................................... 4-13
Configuration................................................................. 3-38
Power-Up Sequence..................................................... 4-13
8 CHANNEL RELAY MODULE INSTALLATION........3-38
ANALOG INPUT MODULE......................................... 4-14
Wiring ........................................................................... 3-38
EQ21XXPSM POWER SUPPLY MONITOR................. 4-15
Mounting....................................................................... 3-38
Configuration................................................................. 3-39
ANALOG INPUT MODULE INSTALLATION..............3-39
Mounting....................................................................... 3-39
Wiring ........................................................................... 3-39
Configuration................................................................. 3-41
GAS DETECTOR LOCATION AND INSTALLATION..3-42
Environments and Substances that Affect
Gas Detector Performance........................................... 3-42
EQ22xxDCU Digital Communication Unit used with
Det‑Tronics H2S/O2 Sensors or other Two-Wire
4‑20 mA Devices........................................................... 3-43
Power-Up Sequence..................................................... 4-14
EQ2220GFM GROUND FAULT MONITOR................ 4-15
EQ22XXDCU AND EQ22XXDCUEX DIGITAL
COMMUNICATION UNITS......................................... 4-16
EQ24XXNE NETWORK EXTENDER.......................... 4-16
SYSTEM STARTUP..................................................... 4-17
Pre-Operation Checks................................................... 4-17
General Start-up Procedures........................................ 4-18
Startup Procedure for Controller................................... 4-19
Startup Procedure for EDIO Module............................. 4-20
Startup Procedure for DCIO Module............................. 4-21
Assembly and Wiring Procedure................................ 3-43
Relay Module Startup.................................................... 4-21
Sensor Separation for DCU with H2S and O2
Sensors......................................................................... 3-45
Analog Input Module Startup........................................ 4-21
EQ22xxDCU Digital Communication Unit used with
PointWatch/DuctWatch.................................................. 3-45
Assembly and Wiring Procedure................................ 3-45
Sensor Separation for DCU with PointWatch................ 3-45
EQ22xxDCUEX Digital Communication Unit (used with
Det-Tronics Combustible Gas Sensors)........................ 3-46
Mounting.................................................................... 3-46
Wiring......................................................................... 3-46
Sensor Separation with DCUEX.................................... 3-47
TYPICAL APPLICATIONS...........................................3-48
SYSTEM CONFIGURATION.......................................3-50
Setting Device Network addresses............................... 3-50
Overview of Network Addresses................................ 3-50
Setting Field Device Addresses................................. 3-50
Rocker Switch Table...................................................... 3-51
Table of Contents – Continued
Section 5 - Maintenance
Section 6 - Specifications
ROUTINE MAINTENANCE........................................... 5-1
EQ3XXX Controller............................................................. 6-1
Batteries.......................................................................... 5-1
EQ3LTM LON Termination Module..................................... 6-3
Manual Check of Output Devices................................... 5-1
EQ3730EDIO Enhanced Discrete I/O Module .................. 6-3
O-Ring Maintenance....................................................... 5-1
EQ3700 DCIO Module........................................................ 6-5
GAS SENSOR MAINTENANCE.................................... 5-1
CALIBRATION AND ADJUSTMENTS..........................5-2
Calibration Algorithm A For Manual Calibration
of Universal DCU............................................................. 5-2
EQ3720 Relay Module........................................................ 6-7
EQ3710AIM Analog Input Module...................................... 6-7
HART Interface Module...................................................... 6-8
EQ21xxPS Power Supplies................................................. 6-8
Normal Calibration....................................................... 5-2
EQP2xx0PS(–x) Power Supplies........................................ 6-9
Sensor Replacement.................................................... 5-3
Redundancy Module Quint-Diode/40................................. 6-9
Calibration Algorithm C For Combustible Gas DCUs
and Automatic Calibration of Universal DCUs................ 5-3
EQ21xxPSM Power Supply Monitor................................. 6-10
Routine Calibration....................................................... 5-3
EQ22xxDCU Series Digital Communication Unit............. 6-12
Initial Installation and Sensor Replacement —
Combustible Gas......................................................... 5-4
EQ24xxNE Network Extender........................................... 6-15
Sensor Replacement — Toxic Gas.............................. 5-5
Combustible Gas Sensor................................................. 6-16
Calibration Algorithm D For Universal DCUs
with O2 Sensor................................................................ 5-5
Normal Calibration....................................................... 5-5
EQ2220GFM Ground Fault Monitor.................................. 6-11
EQ3760ASM Smoke & Heat Module................................ 6-16
Electrochemical Sensors.................................................. 6-16
EQ21xxPS Power Supply................................................. 6-16
Sensor Replacement.................................................... 5-5
Calibration Algorithm G For DCUs with PointWatch
or DuctWatch................................................................... 5-6
Section 7 - Ordering Information
Routine Calibration....................................................... 5-6
DEVICE MODEL MATRICES.........................................7-1
Sensor Replacement.................................................... 5-6
DEVICE CALIBRATION LOGS AND RECORDS.......... 5-7
Appendix
TROUBLESHOOTING.................................................. 5-7
APPENDIX A — FM CERTIFICATION (FIRE AND GAS
PERF., HAZLOC)............................................................A-1
REPLACEMENT PARTS................................................ 5-7
DEVICE REPAIR AND RETURN................................... 5-7
ORDERING INFORMATION.........................................5-9
Power Supplies..........................................................5-9
LON Devices..............................................................5-9
Redundancy...............................................................5-9
Controller Communication Cables............................5-9
APPENDIX B — CSA CERTIFICATION (GAS PERF.,
HAZLOC).......................................................................B-1
APPENDIX C — ATEX/CE AND IECEX CERTIFICATION..... C-1
APPENDIX D — DNV CERTIFICATION (GAS PERF.,
HAZLOC) MARINE........................................................D-1
Equipment Safety Symbols
Symbol
Description
Direct current
Alternating current
Both direct and alternating current
Three-phase alternating current
Earth (ground) current
Protective conductor terminal
Frame or chassis terminal
On (power)
Off (power)
Equipment protected throughout
by double insulation or reinforced
insulation
Caution, possibility of electric shock
Caution, hot surface
Caution*
In position of bi-stable push control
Out position of bi-stable push control
Ionizing radiation
* Manufacturer to state that documentation must be
consulted in all cases where this symbol is marked.
Instructions
Eagle Quantum Premier ®
Fire and Gas Alarm Control System and Automatic
Releasing for Pre-Action and Deluge Systems
Section 1
Safety
ALERT MESSAGES
The following Alert Messages, DANGER,
WARNING, CAUTION, and IMPORTANT are
used throughout this manual and on the system
to alert the reader and operator to dangerous
conditions and/or important operational or
maintenance information.
DANGER
Identifies immediate hazards that WILL
result in severe personal injury or death.
WARNING
Identifies hazards or unsafe practices
that COULD result in severe personal
injury or death.
CAUTION
Identifies hazards or unsafe practices
that COULD result in minor personal
injury or damage to equipment or
property.
IMPORTANT
A brief statement of fact, experience, or
importance that is given as an aid or
explanation.
WARNING
The hazardous area must be
de-classified prior to removing a
junction box cover or opening a detector
assembly with power applied.
©Detector Electronics Corporation 2017
CAUTION
1. Be sure to read and understand the entire
instruction manual before installing or
operating the Eagle Quantum Premier ®
system. Only qualified personnel should
install, maintain or operate the system.
2. The wiring procedures in this manual are
intended to ensure proper functioning of the
devices under normal conditions. However,
because of the many variations in wiring
codes and regulations, total compliance
with these ordinances cannot be
guaranteed. Be certain that all wiring and
equipment installation meets or exceeds
the latest revisions of the appropriate
NFPA Standards, National Electrical
Code (NEC), and all local ordinances. If
in doubt, consult the Authority Having
Jurisdiction (AHJ) before wiring the system.
All wiring shall be installed in accordance with
the manufacturer’s recommendations.
3. Some Eagle Quantum Premier devices
contain semiconductor devices that are
susceptible to damage by electrostatic
discharge. An electrostatic charge can
build up on the skin and discharge when
an object is touched. Always observe the
normal precautions for handling electrostatic
sensitive devices, i.e., use of a wrist strap (if
available) and proper grounding.
4. To prevent unwanted actuation, alarms and
extinguishing devices must be secured
prior to performing system tests.
18.212/16
Rev:
Section 2
Introduction
SYSTEM DESCRIPTION
The EQP system is a combined fire and gas
safety system that is globally approved for
hazardous locations. It is a distributed releasing
system and is certified for annunciation and
releasing.
The system consists of a Controller and a
number of addressable microprocessor based
field devices. The Controller coordinates
system device configuration, monitoring,
annunciation, and control, while the field
devices communicate their status and alarm
conditions to the Controller.
The EQP controller can be arranged in a
redundant configuration, thereby increasing
the availability of the system. The controllers
work in “Master” and “Hot Standby” mode.
Various combinations of field devices can be
configured as part of the system. The actual
selection depends on the requirements of the
application and the regulations that cover the
type of protection required. See Figure 2-1 for
a block diagram of the Eagle Quantum Premier
system.
All field devices are tied into a communication
loop that starts and ends at the Controller.
Each device connected to the communication
loop is assigned a unique identity by setting
its address switches. All other device operation
parameters are configured through Det-Tronics
“Safety System Software.” These selections
define the type of device and how it is to
operate. This system configuration data is then
downloaded into the Controller.
A programmed Controller is configured to
automatically download the configuration
data into the individual devices when they first
communicate with the Controller.
In addition to Det-Tronics advanced flame
and gas detectors, Eagle Quantum Premier
offers the capability of incorporating third party
fire and gas protection equipment into the
system. These can be either input or output
devices. Typical input devices include manual
fire alarm "call boxes," heat detectors, and
analog combustible or toxic gas measurement
instruments. Typical output equipment includes
18.2
solenoids, strobes, and horns. All equipment is
monitored for wiring fault conditions.
For complete system integration, the Controller
has the capability to communicate with other
systems such as PLCs and DCSs. Different
communication protocols are supported,
allowing the Controller to communicate with
other systems either directly or through
communication gateways.
NOTE
For specific information relating to the
SIL 2 rated EQP system, refer to manual
number 95-8599.
COMMUNICATIONS LOOP
Eagle Quantum Premier utilizes a Det-Tronics
Signaling Line Circuit (SLC), a version of
Echelon’s Local Operation Network (LON)
customized specifically for Eagle Quantum
Premier. This network provides several key
advantages:
•
•
•
•
ANSI/NFPA Class X performance of SLC
Peer-to-peer communications
Short message formats
Expandability
The Controller utilizes several mechanisms
to continuously check the LON loop for fault
conditions, thereby providing the highest level
of reliable communication.
Every device on the LON loop has the ability
to communicate with the Controller at any
time. This design allows immediate alarm
messages to be sent from the field devices to
the Controller.
All messages are kept short in order to
maximize network performance. This minimizes
network bottlenecks.
The Eagle Quantum Premier system is easily
modified to accommodate design changes
or plant expansions. This can involve adding
LON sections, repositioning LON sections, or
removing LON sections from the loop. There
are LON communication implementation
details that affect and limit how the LON loop
is changed.
2-1
95-8533
GAS DETECTION
CONFIGURABLE INPUTS AND OUTPUTS
FIRE DETECTION
COMBUSTIBLE, TOXIC, OR
OTHER 4-20 MA INPUT
CONTACT
CLOSURE
DEVICES
DIGITAL
COMMUNICATION
UNITS
X3301
DETECTOR
X3302
DETECTOR
UVHT/C7050
DETECTOR
UV
DETECTOR
UVIR
DETECTOR
IR
DETECTOR
DRY CONTACT INPUTS
INITIATING
DEVICE
CIRCUIT
CONFIGURABLE
OUTPUT POINTS
8 CHANNEL DCIO MODULE
NOTE: CHANNELS CAN BE CONFIGURED
AS EITHER INPUTS OR OUTPUTS.
UD10-DCU
PIRECL
GAS
DETECTOR
LS2000
GAS
DETECTOR
UNSUPERVISED INPUTS AND OUTPUTS
ASM/ASH
MODULE
AC
POWER
INPUT
BATTERY
CHARGER
–
+ –
8 4-20 MA INPUTS
RELAY
MODULE
8 UNSUPERVISED
RELAY OUTPUT POINTS
FIRE
SUPPRESSION
(SOLENOID)
8 RELAY
OUTPUT POINTS
8 DRY CONTACT INPUTS
APOLLO
DEVICES
NETWORK
EXTENDER
ANALOG
INPUT
MODULE
EIO
MODULES
POWER
SUPPLY
MONITOR
SYSTEM
POWER
HORNS
&
BEACONS
TROUBLE RELAY
(NC CONTACT)
EQP CONTROLLER
CONTROLNET or ETHERNET or SERIAL
ETHERNET DLR
INTERFACE
(OPTIONAL
BOARD
INTERFACE)
ONBOARD
SERIAL
INTERFACE
8 CHANNEL EDIO MODULE
+
RS-232
CHANNELS CAN BE CONFIGURED AS INPUTS,
OUTPUTS, SMOKE/HEAT DETECTORS,
CLASS A INPUTS, OR CLASS A OUTPUTS.
RS-485
HSSL
ETHERNET
or RS-232
HARDWIRED I/O
ETHERNET
or RS-232
SIGNALING LINE CIRCUIT (SLC)
CONFIGURATION
PC
RS-485
MODBUS
INTERFACE
ETHERNET OR SERIAL INTERFACE BOARD
P2114
Figure 2-1—Block Diagram of Eagle Quantum Premier System
Only devices that have been approved for use
with Eagle Quantum Premier can be connected
up to the LON. All approved devices have
been tested and certified to operate properly
on the LON.
LON COMMUNICATION HEARTBEAT
The Controller continuously broadcasts a
heartbeat signal over the LON loop. This
heartbeat is used for verifying the integrity
of the LON loop and for keeping the field
devices from going into a fault isolation mode.
Once every second, the heartbeat contains
the current time and date, which are used
by the field devices to log status events and
calibrations.
18.2
2-2
The Controller continuously tests LON
continuity by sending out a heartbeat on one
LON port and then listening for it on the other
LON port. The Controller also broadcasts
the heartbeat signal in the opposite direction
around the loop. This ensures that all field
devices, the LON Network Extenders (NE), and
communication wiring are correctly passing
the digital information around the loop.
The field devices use the heartbeat as
a mechanism to ensure that there is a
communication path back to the Controller. If
the field device does not receive a heartbeat
for a period of time, the device will go into a
LON fault isolation. In this situation, the device
opens one side of the LON and listens for a
heartbeat on the other side. If the device
doesn’t receive a heartbeat, it listens on the
other side of the LON and opens the opposite
LON connection.
95-8533
Table 2-1—Controller Based Faults
Controller Faults
Shown on Text
Display
Controller Fault
Device Offline
Extra LON Device
Invalid Config
Lon Fault
LON Ground Fault
Power Fail 1
Power Fail 2
Trouble
LED
LON Fault
LED
x
x
x
x
x
x
x
x
x
Table 2-2—Field Device Based Faults
Field Device Faults
Shown on Text Display
Trouble
LED
Trouble
x
290 Volt Fault
X
X
x
AC Failed
X
X
x
Battery Fault
X
X
x
Beam Block
X
X
x
Calibration Fault
X
X
x
Channel Open
X
X
x
Channel Short
X
X
x
Dirty Optics
X
X
X
X
Trouble
Relay
Relay
RTC Fault
x
x
Ground Fault Negative
Redundancy Fault*
x
x
Ground Fault Positive
X
X
IR Auto Oi Fault
X
X
IR Fault
X
X
IR Manual Oi Fault
X
X
Low Aux Power Fault
X
X
Missing IR Sensor Fault
X
X
Missing UV Sensor Fault
X
X
Power Supply Fault
X
X
Sensor Fault
X
X
Supply Voltage Fault
X
X
Tx Lamp Fault
X
X
UV Auto Oi Fault
X
X
UV Fault
X
X
UV Manual Oi Fault
X
X
*Only for controller pair configured for redundancy.
THEORY OF OPERATION
During normal operation, the Controller
continuously checks the system for fault
conditions and executes user defined
programmed logic that coordinates the control
of the field devices. At the same time, the field
devices are continuously monitoring for device
based fault and alarm conditions.
When a fault condition occurs, the Controller
displays the fault condition on the Vacuum
Fluorescent Text Display, activates the
appropriate fault LED(s), activates the Trouble
signal using the Controller’s internal enunciator,
and de-energizes the Controller’s Trouble relay.
18.2
Controller based fault conditions include the
Controller status and LON communications
such as the heartbeat being sent around
the loop and the field device loss of
communications. Controller based fault
conditions are listed in Table 2-1.
Field device based fault conditions are
transmitted to the Controller, where they are
then annunciated. Refer to Table 2-2 for a
listing of field device faults. Each field device
transmits its status to the Controller on a
regular basis.
When an alarm condition occurs, the Controller
displays the alarm condition on the text display,
activates the appropriate Alarm LED(s), and
activates the alarm signal using the Controller’s
internal annunciator.
2-3
95-8533
Table 2-3—Eagle Quantum Premier Status Update Rates
Controller Type
# of
Devices
Input –
No Exception
Input –
With Exception
Input –
With Exception
U-Series
DCU
PIRECL
(UV & UVIR)
DCIO, EDIO, AIM
Relay Module
ASM/ASH Module
X-Series
LS2000
EQ3001
EQ3150
EQ3016
1 to 100
1 Second
1 Second
1 Second
101 to 200
2 Seconds
2 Seconds
1 Second
201 to 246
2 Seconds
3 Seconds
1 Second
1 to 50
1 Second
1 Second
1 Second
51 to 100
2 Seconds
2 Seconds
1 Second
101 to 150
2 Seconds
3 Seconds
1 Second
1 to 16
1 Second
1 Second
1 Second
Each field device must communicate alarm
and fault conditions to the Controller. The
timing for transmitting alarms and faults to the
Controller is displayed in Table 2-3.
NOTE
All fault and alarm conditions are latched
on the Controller. To reset the Controller,
conditions indicated on the text display
must currently be in the OFF state.
Pushing the reset button then initiates a
Controller reset. Active alarms will remain
through a Controller reset.
Typical programmed functions include flame/
gas voting, timing delays, timing executions,
latching conditions, alarm and trouble
notification, suppression control, condition
control, and process shutdown notification.
The Controller executes program logic
by starting with the first logic page of the
first program and then progressing onto
subsequent pages of the same program. In
turn, subsequent programs are then executed.
CONTROLLER LOGS
The controller has an internal alarm and
event log. The logs can be accessed via the
S³ software configuration ports (Configuration
Port or Port 3) using a RS-232 serial cable
and a Windows™ computer. The controller
can save up to 4,095 alarms and events in the
controller memory.
CONTROLLER USER LOGIC
The Controller continuously executes the
user logic programs that are programmed
using S³ software. The user logic programs
are set up in the same fashion as IEC 611313 programmable logic programmed into
Programmable Logic Controllers (PLCs).
Block diagram logic gates are tied together
with inputs, outputs, and other logic gates to
18.2
perform a specific task. A number of tasks can
be tied together to perform a system function.
2-4
Every one hundred milliseconds, the
Controller will start executing the user logic
that is programmed into the Controller. Within
this logic execution cycle, the Controller
will execute as many of the logic pages as
possible. If all programmed logic is executed
in a cycle, the Controller will start executing
program logic with the next cycle. Otherwise,
subsequence logic execution cycles are used
to finish executing the remaining logic gates.
Only when all the logic gates have been
executed will the Controller start over. The
Controller will start executing the first logic
page of the first program at the beginning of
the next logic cycle.
95-8533
NODE 4
NODE 5
NODE 3
NODE 6
NODE 2
NODE 7
EQP
CONTROLLER
DET-TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
NODE 1
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Enter
Next
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Previous
Reset
NODE 8
Power
D1851
Acknowledge Silence
Figure 2-2—Normal Communication over the LON
NODE 4
NODE 5
WIRING FAULT
NODE 3
NODE 2
NODE 6
PATH A
PATH B
DET-TRONICS
MULTIPLE WIRING FAULTS
®
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Enter
Next
Previous
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
NODE 8
Power
D1852
Acknowledge Silence
Figure 2-3—Communication over the LON with a Single
Wiring Fault
NODE 4
NODE 5
WIRING FAULTS
NODE 3
NODE 2
NODE 6
PATH A
PATH B
NODE 7
EQP
CONTROLLER
DET-TRONICS
NODE 1
®
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Enter
Next
Previous
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
For a single wiring fault, the field devices with
the fault will isolate the fault by opening LON
fault isolation relays. After the field devices
isolate the wiring fault, communications will
be resumed between the Controller and field
devices. Refer to Figure 2-3.
NODE 7
EQP
CONTROLLER
NODE 1
The LON fault isolation routine is disabled and
the LON fault isolation relays are closed when
the LON fault timeout period has elapsed.
The LON fault isolation routine will be enabled
when the device again receives a heartbeat.
Power
Acknowledge Silence
NODE 8
D1853
Figure 2-4—Communication over LON with Multiple Wiring
Faults
In the event of multiple wiring faults on the LON,
the devices between the faults will continue to
function, but the faults will prevent them from
communicating with the Controller. See Figure
2-4. In this example, nodes 1 to 4 communicate
using one Controller port (path A) and nodes
7 and 8 use the other Controller port (path
B). Nodes 5 and 6 are unable to report to the
Controller because they are isolated by the
two wiring faults. If a device is prevented from
communicating with the Controller, the text
display on the Controller will show the message
“Device Offline.”
IMPORTANT
COMMUNICATION NETWORK
FAULT OPERATION
During normal operation, the Controller is
continuously broadcasting a heartbeat around
the communication loop as shown in Figure
2-2. The Controller broadcasts the heartbeat
in both directions. At the same time, the field
devices are transmitting status information to
the Controller over the communication loop.
Every field device except the network extender
has two LON fault isolation relays. Each relay
is tied to a communication port on the device.
When a field device fails to receive the heartbeat
from the Controller, the device initiates a LON
fault isolation routine. The isolation routine
disconnects one of the communication ports
via one of the LON fault isolation relays.
The device listens for a heartbeat on the
communication port that is connected. If
a heartbeat is not found, the routine then
disconnects the other communication port and
listens for a heartbeat on the connected side.
The process is repeated until either a heartbeat
is located or a LON fault timeout period of two
hours is reached.
18.2
Since it is impossible to predict where
a network fault might occur or exactly
what effect it will have on actual system
operation, it is important to diagnose
and repair any fault as soon as possible
after it is detected to ensure continuous,
uninterrupted system operation.
SIL2 CAPABLE SYSTEM
The EQP SIL2 capable system uses the
following components:
• EQ3XXX - EQP Controller
• EQ3730 - Enhanced discrete input/output
module
• EQ3710 - Analog input module
• EQ3760ASM - Addressable Smoke & Heat
Module
• X3301 - Multispectrum IR Flame Detector
• PIRECL - Infrared gas detector
Refer to safety system manual (95-8599) for
safety related data.
2-5
95-8533
MAJOR COMPONENT
DESCRIPTIONS
LON
ETHERNET OR
RS-232
SERIAL LINK
The system has three main component groups
– the System Controller, LON (Local Operating
Network), and Intelligent Field Devices.
ETHERNET
OR MODBUS
RS-485
DCS/PLC/HMI
CONTROLLER A
LON ADDRESS 1
S3
CONFIGURATION
SOFTWARE
HIGH SPEED
RS-232
SERIAL LINK
SYSTEM CONTROLLER
The Controller (see Figure 2-5) performs
all communication, command, and control
functions for the system. The Controller
supports both “Static” and “Programmable”
logic. Other features include:
• Redundant controller capability
• User pushbutton controls (reset,
acknowledge, etc.)
• “Real time” system clock
• Internal alarm sounder
• Vacuum fluorescent text based display that
shows current system status
• 8 programmable unsupervised inputs
• 8 programmable unsupervised relay
outputs
• RS-485 Modbus RTU communication
interface that supports coils, discrete
inputs, and holding registers
• Optional ControlNet communication board
supports redundant communication
channels.
• Optional EtherNet DLR communication
board supports EtherNet Device Level Ring
communications.
• Ethernet Interface Board supports
configuration, Modbus TCP/IP, controller
redundancy, and RS-485 Modbus.
• Serial Interface Board supports
configuration, RS-232 Modbus, controller
redundancy, and RS-485 Modbus.
ONE PROJECT FILE
LOADED TO
CONTROLLER A
CONTROLLER B
LON ADDRESS 2
B2275
Figure 2-6— Block Diagram of EQP System
with Redundant Controllers
Controller Redundancy
The EQP controllers can be configured
as a redundant pair. See Figure 2-6. The
redundancy scheme is a hot standby system
that offers the following primary features:
• Automatic configuration of the standby
controller
• Bumpless transfer
• Forced and automatic switchover
• No downtime on controller replacement
• Automatic synchronization between
controllers
• Increased system availability
During normal operation one controller acts as
the “Master” while the other acts as the “Hot
Standby.”
Terminology used for redundancy:
Master controller
This is the normal mode
for non-redundant and
master controllers. User
logic is executed, outputs
are being controlled and
all serial and/or Ethernet
ports are active.
Standby controller
This controller is receiving
all inputs but does not
have any control over the
outputs and user logic is
not executed. The standby
controller
receives
update information from
the master controller
to ensure a bumpless
transfer should a controller
switchover occur.
Figure 2-5–System Controller
18.2
2-6
95-8533
Table 2-4—Ports on Ethernet Interface Board
Port Name
Comm
Function
RS-485
Modbus (Master/
Slave) Ground
Fault Monitored,
Isolated
Ethernet Port 3
Ethernet
Modbus TCP/IP
(Master/Slave)
S³ Configuration
Ethernet Port 4
Ethernet
ModbusTCP/IP
(Master/Slave)
RS-232
Redundant
Controller to
Controller Only
Serial Port 2
HSSL Redundancy
Port
Primary controller The controller assigned
address 1.
Secondary controller The controller assigned
address 2.
Bumpless transfer During
a
controller
switchover no change in
output will occur due to
the switchover.
Ethernet Interface Board
The Ethernet Interface Board supports two
additional serial ports and two Ethernet ports.
See Table 2-4. Ethernet supports 10/100 Mbs
communication. Figure 2-7 shows the Ethernet
TCP/IP Server/Client and Modbus RTU Master/
Slave relationship. For a redundant controller
configuration, the board is required in both
controllers.
Serial Interface Board
Table 2-5—Ports on Serial Interface Board
Port Name
Comm
Function
Serial Port 2
RS-485
Modbus (Master/
Slave) Ground Fault
Monitored, Isolated
Serial Port 3
RS-232
Modbus (Master/
Slave) S³
Configuration
Serial Port 4
RS-232
Modbus (Master/
Slave)
HSSL
Redundancy Port
RS-232
Redundant Controller
to Controller Only
EQ2230 RSP
The EQ2230 RSP Surge Protector is a device
that protects the EQP RS-485 Ports (Ports 1
and 2) from surge transients on the RS-485
cable.
ControlNet Board or EtherNet DLR Board
(Optional)
An optional ControlNet Board or EtherNet
Device Level Ring (DLR) Board can be
installed to allow ControlNet or EtherNet
DLR communication to a compatible PLC.
Both interfaces operate in a non-interfering
manner. The functionality of the ControlNet
and EtherNet DLR boards is not covered by
any approval. Both options offer two ports. See
Tables 2-6 and Table 2-7. The interfaces must
be configured through S3 prior to use. Consult
the factory for details. For redundant controller
configurations, identical option boards are
required in both controllers.
The Serial Interface Board supports up to four
additional serial ports. See Table 2-5. For a
redundant controller configuration, the board
is required in both controllers.
Table 2-7—Ports on EtherNet DLR Interface Board
Port Name
Comm
Function
Port 1
EtherNet
DLR
EtherNet DLR
Communication
Port 2
EtherNet
DLR
EtherNet DLR
Communication
Table 2-6—Ports on ControlNet Interface Board
Port Name
Comm
Function
Port A
ControlNet
ControlNet
Communication
Port B
ControlNet
ControlNet
Communication
18.2
Controller-to-Controller Communication
(SLC485)
The EQP controllers can be configured to
communicate with up to 12 controllers via
RS-485 communication. The controller-tocontroller scheme provides the ability to meet
NFPA 72 SLC requirements with the following
primary features:
2-7
95-8533
EQP Controller
EQP Controller
Modbus Slave
Modbus Slave
TCP/IP Server
TCP/IP Server
10/100M Ethernet LAN
TCP/IP Client
Modbus Master
Figure 2-8—Eagle Quantum Premier Network Extender
HMI/DCS
Figure 2-7—Ethernet TCP/IP Server/Client Relationship &
Modbus RTU Master/Slave Relationship
NOTE
All LON devices support ANSI/NFPA
72 Class X communication with the
Controller.
• Modular trouble and alarm configuration
• Multiple zone application with controller-tocontroller communication
• Multiple media options
Network Extenders
Transmitted signals can travel a maximum
distance of 2,000 meters through LON
communication wire. At the end of this
distance, a network extender (see Figure
2-8) must be installed to rebroadcast the
communications into the next wire segment.
For every network extender added, the length
of the communications loop extends up to
2,000 meters. Due to propagation delays
around the loop, the maximum loop length is
limited to 10,000 meters.
IMPORTANT
When using RS-485 communications P8
(Port 1) and P10 (Port 2) wiring must be
less than 20 feet and placed into conduit.
Or, fiber optic converters (see table 3-9
for performance verified units) shall be
used. Or,, the EQ2230 RSP can be used
to protect against electrical surge and
transient EMI. The fiber optic converter
and RSP must be placed inside the
cabinet with the controller.
NOTES
A network extender is required for
communication loops greater than 60
nodes.
EQP Marine Application System
For information regarding EQP Marine
Application Systems, refer to Appendix D.
LOCAL OPERATING NETWORK (LON)
The LON is a fault tolerant, two wire, digital
communication network. The circuit is arranged
in a loop starting and ending at the Controller.
The circuit supports up to 246 intelligent field
devices spread over a distance of up to 10,000
meters (32,500 feet).
18.2
2-8
Communication wire segment lengths
are dependant upon physical and
electrical characteristics of the cable.
Refer to the installation section for LON
cable wire information.
No more than six network extenders may
be used on the communication loop.
When a network extender is installed in
the communication loop, up to 40 field
devices can be installed per network
segment. The network segment is the
wiring segment between two network
extenders or bet ween a net work
extender and a controller.
95-8533
Table 2-8—Flame Detector Instruction Manuals
Detector
Manual Number
X3301 95-8704
X3301A
95-8527 & 95-8534
X3302 95-8576
X5200 95-8546
X2200 95-8549
X9800 95-8554
UVHT 95-8570
Figure 2-9—Ground Fault Monitor
EQ21xxPS Series Power Supplies and
EQ2100PSM Power Supply Monitor
The Power Supply, Power Supply Monitor, and
backup batteries are used to provide power
to the system. The power supply monitor
communicates trouble conditions to the
Controller. Monitored status conditions include:
power supply failure, loss of AC power, loss
of battery power, power ground fault, AC and
DC voltage (hi/low level), and backup battery
current charge levels.
The Power Supply provides main and backup
power to the EQP System. The device includes
many features such as voltage regulation, high
efficiency, and high power factor.
An equalize switch is located on the front
panel of the charger for manual activation,
or a multi-mode electronic timer can be used
for automatic activation. Steady state output
voltage remains within +/– 1/2% of the setting
from no load to full load for AC input voltages
within +/– 10% of the nominal input voltage.
EQP21xxPS(–X) Power Supplies and
EQP2410PS(–P) Converter
The Power Supplies and Converter provide
main and backup power to the EQP System
in ordinary and marine applications. Refer
to Section 3 of this manual for complete
information.
EQ2220GFM Ground Fault Monitor
The EQ2220GFM Ground Fault Monitor (see
Figure 2-9) provides ground fault monitoring
in a system that includes a floating 24 Vdc
power source. The device detects ground fault
conditions on +/– power and all secondary
I/O circuits. A positive or negative ground
fault condition is indicated immediately by
local LEDs, and by a relay contact after a 10
second time delay. The ground fault monitor is
intended to be mounted in the same enclosure
as the controller.
18.2
FIELD DEVICES
Flame Detectors
For flame detector installation, operation,
maintenance, specifications and ordering
information, refer to Table 2-8.
For information regarding USCG Approval of
the X3301 Flame Detector, refer to Appendix D.
NOTE
Existing Eagle Quantum field devices
such as EQ22xxUV and EQ22xxUVIR
are supported by the Eagle Quantum
Premier system (not FM Approved).
EQ2200UVHT + C7050 Detector
The EQ2200UVHT + C7050 UV Flame Detector
is used with the EQP system to provide UV
flame protection in continuous duty, high
temperature applications such as turbine
enclosures, generator rooms, etc. where the
ambient temperature can continuously exceed
+ 75 deg C (+ 167 def F). The EQ2200 UVHT
is an electronic module assembly that is used
in conjunction with a high temperature rated
C7050B detector.
Model HD Heat Detector
The Model HD Heat Detector senses the
surrounding air temperature and actuates an
electrical contact output at a pre-determined
temperature. It can be used to sense excessive
heat or fire and warn personnel, or it can be
used as a signaling device to sense fire and
send a signal to an alarm panel for actuation of
a fire suppression system.
2-9
95-8533
U5015 Explosion Proof Smoke Detector
IMPORTANT
The Det-Tronics SmokeWatchTM U5015
Explosion-Proof Smoke Detector has Division
and Zone explosion-proof ratings and is suitable
for industrial and commercial applications. It is
designed to operate effectively with smoldering
and rapidly growing fires. Outputs include a
localized LED, 0-20mA, and relays.
X7050 xWatch® Explosion-Proof Camera
The xWatch high resolution color camera
operates in an explosion–proof enclosure and
can be used to view an area in alarm or to
record activity in an area. It can be used as
a stand-alone unit or attached to any of the
X-series flame detectors. Users have an option
to include a digital video recorder (DVR) as
part of the solution to capture a digital video of
hazard events.
EQ3730EDIO Enhanced Discrete Input/
Output Module
For Class A wiring, two input/output
ch a n n e l s a re c o m b i n e d , t h e re by
supporting up to four input/output
circuits.
NOTE
An input must be active for at least 750
milliseconds in order to be recognized.
The EDIO module can be mounted directly to
a panel, or it can be DIN rail mounted. System
status can be determined using the troubleshooting procedures, Eagle Quantum Safety
System Software (S³) and the status indicators
on the module.
Refer to the Enhanced Discrete Input/Output
Module Specification Data sheet (form number
90-1189) for additional information.
The 8 Channel EDIO Module (see Figure 2-10)
expands the Input and Output capability of the
Eagle Quantum Premier System.
The unit is designed to provide continuous
and automated fire/gas protection, while
ensuring system operation through continuous
supervision of System Inputs/Outputs.
The EDIO module provides eight channels of
configurable input or output points that can be
programmed for supervised or unsupervised
operation. Each input point can accept fire
detection devices such as heat, smoke, or
unitized flame detectors. Each output point
can be configured for signaling or releasing
output operation. Each channel on the module
is provided with individual indicators for active
and fault conditions.
18.2
2-10
Figure 2-10—Enhanced Discrete
Input/Output Module
95-8533
EQ3700 8 Channel DCIO Module
EQ3720 8 Channel Relay Module
The 8 Channel Discrete Input/Output (DCIO)
Module (see Figure 2-11) consists of eight
individually configured channels. Each channel
is configured as either an input or output with
the appropriate wiring supervision. Wiring
supervision includes none, open circuits, and
"open and short" circuits. In addition to defining
the type of supervision, an input channel is also
configured to generate the appropriate static
logic alarm message to the controller.
The 8 Channel Relay Module (see Figure 2-12)
consists of eight individually configured output
channels.
NOTE
NFPA 72 requires wire supervision
s e l e c t i o n fo r fi re d e te c t i o n a n d
n o t i fi c a t i o n d ev i c e s ( I D C , N AC ,
supervisory and releasing devices).
Heat, smoke, or unitized flame detectors can
be wired into channels defined as inputs.
Horns and strobes/beacons can be wired into
channels defined as outputs.
NOTE
NOTE
The relay module supports equipment
that operates on:
24 Vdc (not to exceed 1 amperes)
The relay module has two LEDs for the device
and two LEDs for each channel. On the device
level, one green LED indicates power, while
the other amber LED indicates a LON CPU
fault. For each channel, one red LED indicates
channel activation and the other amber LED
indicates that the module operating voltage is
low or that the module has not been configured
(all eight channel LEDs blink).
Refer to the Relay Module Specification Data
sheet (form number 90-1181) for additional
information.
Th e D C I O o u t p u t s o n ly s u p p o r t
equipment that operates on 24 vdc (not
to exceed 2 amperes per channel).
The DCIO has two device status LEDs, as well
as two LEDs for each channel. On the device
level, one green LED indicates power, while
the other amber LED indicates a LON CPU
fault. For each channel, one red LED indicates
channel activation and the other amber
LED indicates a fault condition when wiring
supervision is defined for the channel.
Figure 2-12—Eight Channel Relay Module
Refer to the DCIO Specification Data sheet
(form number 90-1149) for additional
information.
Figure 2-11—DCIO Module
18.2
2-11
95-8533
EQ3710AIM Analog Input Module
EQ3770 Explosion-Proof I/O (EIO) Module
The 8 Channel Analog Input Module (see
Figure 2-13) provides a means of connecting
devices with a calibrated 4–20 mA output
signal to the Eagle Quantum Premier System.
This module includes on EDIO/AIM/RM/DCIO
module in an explosion-proof enclosure (see
Figure 2-14). Options include: Window, NTP/
Metric ports, and a Ground Fault Monitor (GFM)
The Analog Input Module (AIM) provides 8
configurable channels that can be set for either
combustible gas mode or universal mode. The
combustible gas mode provides a number
of automatically programmed settings, and
alarm thresholds that are limited to approval
body requirements. The universal mode is
used for generic devices where control over
all configuration parameters is required. All
devices must provided their own calibration
facilities.
Refer to the EQ3770EIO Instruction Manual
(form number 95-8761) for additional
information.
For fire detector 4–20 mA inputs, the Analog
Input Module (AIM) is certified for use as an
NFPA 72 Class B Approved input.
Refer to the Analog Input Module Specification
Data sheet (form number 90-1183) for
additional information.
Figure 2-14—EIO Module
Figure 2-13—Eight Channel Analog Input Module
18.2
2-12
95-8533
EQ3760ASM Addressable Smoke & Heat
Module
The EQ3760ASM Addressable Smoke &
Heat Module (see Figure 2-15) is an interface
device designed to provide continuous and
automated fire protection for the EQP system.
The EQ3760ASM is located directly on the
LON of the EQP system, with a loop of up
to 100 addressable devices tied into the
EQ3760ASM. This allows all of the flame, gas,
and addressable smoke and heat detectors
to run on one system, enabling the EQP
controller to annunciate a fire alarm from either
its own LON based I/O, or from the connected
addressable smoke and heat detection loops.
The EQP controller can support up to 10
EQ3760ASM modules.
The EQ3760ASM can support a variety of
Apollo Discovery and XP95 devices, including
smoke, heat, manual call, sounders, beacons
and I/O modules. The addressable devices are
configured individually via the S³ software.
To ensure reliable system operation, the
EQ3760ASM continuously monitors its input
and output circuits for opens and short circuit
conditions.
During normal operation, the EQ3760ASM
continuously checks the loop for fault
conditions and executes user defined
programmed logic that coordinates the control
of the field devices. The EQ3760ASM reports
any device based fault and alarm conditions to
the EQP controller.
The EQP Controller continuously monitors the
status of the EQ3760ASM, as well as the status
of each device connected to the EQ3760ASM.
The EQ3760ASM's alarm and fault status
conditions are logged in the EQP controller.
System status can be determined using
S³ software or the status indicators on the
EQ3760ASM, where LEDs annunciate power
on, faults, or an active device on the loop.
Refer to the EQ3760ASM instruction manual
(form number 95-8755) for additional
information.
18.2
Figure 2-15—EQ3760ASM
EQ3750ASH Addressable Smoke & Heat
Module
The Addressable Smoke and Heat (ASH)
Module (see Figure 2-16) is an interface
device designed to provide continuous and
automated fire protection for the EQP system.
The ASH module is located directly on the
LON of the EQP system, with a loop of up to
64 addressable devices tied into the ASH
module. This allows all of the flame, gas, and
addressable smoke and heat detectors to run
on one system, enabling the EQP controller to
annunciate a fire alarm from either its own LON
based I/O, or from the connected addressable
smoke and heat detection loops. The EQP
controller can support up to 10 ASH modules.
The ASH module can support a variety of
Apollo Discovery and XP95 devices, including
smoke, heat, manual call, sounders, beacons
and I/O modules. The addressable devices are
configured individually via the S³ software.
To ensure reliable system operation, the ASH
module continuously monitors its input and
output circuits for opens and short circuit
conditions.
During normal operation, the ASH module
continuously checks the loop for fault
conditions and executes user defined
programmed logic that coordinates the control
of the field devices. The ASH module reports
any device based fault and alarm conditions to
the EQP controller.
2-13
95-8533
The EQP Controller continuously monitors the
status of the ASH module, as well as the status
of each device connected to the ASH module.
ASH module alarm and fault status conditions
are logged in the EQP controller.
The device can monitor and control two output
devices (24 Vdc rated) that are programmed
and energized together. The release circuits
are compatible with a variety of solenoid or
initiator based suppression systems.
System status can be determined using S³
software or the status indicators on the ASH
module, where LEDs annunciate power on,
faults, or an active device on the loop.
The release circuit is supervised for open circuit
conditions. If a trouble condition occurs (open
circuit or solenoid supply voltage less than 19
volts), it will be indicated at the Controller. Each
output is rated at 2 amperes and auxiliary input
terminals are provided for additional 24 Vdc
output power where needed.
Refer to the ASH module instruction manual
(form number 95-8654) for additional
information.
Refer to the EQ25xxARM Specification Data
sheet (form number 90-1128) for additional
information.
Figure 2-16—EQ3750ASH
Figure 2-17—Agent Release Module
EQ25xxARM Agent Release Module
NOTE
The EQ25xxARM Series Agent Release Module
(ARM) (see Figure 2-17) provides agent
release or deluge pre-action capability. The
device is controlled by programmable logic in
the Controller. Time delay, abort and manual
release sequences allow the device output to
be programmed for use in unique applications.
Special Condition of Use: For use in
systems installed in compliance with
NFPA 72:2010 or earlier.
The device is field programmed to operate in
one of the following modes:
Timed–
Output is activated for a field
selectable duration from 1 to
65,000 seconds.
Continuous–
Output latches until reset.
Non-latching– Output follows the input.
NOTE
Special Condition of Use: For use in
systems installed in compliance with
NFPA 72:2010 or earlier.
18.2
2-14
95-8533
EQ25xxSAM Signal Audible Module
The EQ25xxSAM Series Signal Audible
Module (SAM) (see Figure 2-18) provides two
indicating circuits for controlling UL Listed
24 Vdc polarized audible/visual indicating
appliances.
The device is located on the LON and is
controlled by programmable logic in the
Controller.
Each output circuit is independently
programmable to allow notification of separate
events. Each output can be individually
activated for any one of the following predefined outputs:
1. Continuous
2. 60 beats per minute
3. 120 beats per minute
4. Temporal pattern.
Device outputs operate in the reverse polarity
manner when activated. Each output is rated
at 2 amperes. Auxiliary power input terminals
are provided for additional 24 Vdc signaling
power where required. The output circuits
are supervised for open and short circuit
conditions. If a wiring fault occurs, a trouble
condition will be indicated at the Controller.
Refer to the EQ25xxSAM Specification Data
sheet (form number 90-1129) for additional
information
NOTE
Special Condition of Use: For use in
systems installed in compliance with
NFPA 72:2010 or earlier.
EQ22xxIDC Series Initiating Device
Circuit (IDC)
There are three IDC models available (see
Figure 2-19):
The EQ22xxIDC allows discrete inputs from
smoke/heat detectors, manual call stations or
other contact devices.
The IDC accepts two dry contact inputs for use
with devices such as relays, pushbuttons, key
switches, etc. The IDC supports ANSI/NFPA 72
Class B supervised input circuits
Each circuit requires its own end of line
(EOL) resistor for monitoring circuit continuity.
Nominal resistance of the resistor is 10 k ohms.
The EQ22xxIDCGF Initiating Device Circuit
Ground Fault Monitor (IDCGF) responds to
the presence of a ground fault within the
power circuitry of the system. It provides an
unsupervised dry contact input and ground
fault monitoring circuitry for indicating a power
supply trouble condition. It is intended for use
with a third party power supply.
The EQ22xxIDCSC Initiating Device Circuit
Short Circuit (IDCSC) is similar to the IDC, but
supports supervision per EN 54 for European
installations.
Refer to the EQ22xxIDC Specification Data
sheet (form number 90-1121) for additional
information.
NOTE
Input types (e.g. fire alarm, trouble, and
gas alarms) are configurable through
Det-Tronics Safety System Software (S³).
NOTE
Special Condition of Use: For use in
systems installed in compliance with
NFPA 72:2010 or earlier.
Figure 2-18—Signal Audible Module
18.2
2-15
95-8533
EQ22xxDCU and EQ22xxDCUEX
Digital Communication Units
The EQ22xxDCU Digital Communication
Unit (DCU) is an analog signal input device
that accepts a 4–20 mA signal. The device
is typically connected to gas detectors,
where the analog signal represents the gas
concentration.
Calibration of the DCU involves a non-intrusive
procedure that can be performed by one
person at the device without declassifying the
area.
Figure 2-19—Initiating Device Circuit
UD10 DCU Emulator
The FlexVu® Model UD10 DCU Emulator
(UD10-DCU) is designed for applications that
require a gas detector with digital readout of
detected gas levels. Its LON interface board
makes the UD10-DCU compatible with Eagle
Quantum Premier systems by digitizing the
4-20 mA analog signal from the attached
sensor/transmitter and transmitting the value
as a process variable over the LON to the EQP
controller.
The UD10-DCU is designed for use with most
currently available Det‑Tronics gas detectors.
The UD10-DCU with CGS with conditioning
board is designed for use with combustible
gas, see manual 95-8656 for more information.
For a list of compatible gas detectors, as
well as information regarding installation,
operation, maintenance, specifications and
ordering information, refer to form number
95-8656.
The device supports two alarm setpoints that
are defined as part of the device’s configuration
setup. When detecting combustible gases,
the alarm setpoints represent low and high
gas alarm levels. When detecting oxygen, the
alarms represent the range for the acceptable
oxygen level. If oxygen drops below the alarm
range, a low alarm is generated by the device.
PointWatch/DuctWatch IR gas detector as well
as electrochemical sensors (hydrogen sulfide,
carbon monoxide, chlorine, sulfur dioxide, and
nitrogen dioxide) are examples of devices that
can be connected to the DCU.
NOTE
A catalytic sensor can be connected
to a DCU through a transmitter, which
converts the millivolt signal to a 4–20
milliampere signal.
The EQ22xxDCUEX is a specialized version
of the DCU that contains a transmitter for
connection to a Det-Tronics Model CGS
catalytic combustible gas sensor.
Refer to the EQ22xxDCU Specification Data
sheet (form number 90-1118) for additional
information.
18.2
2-16
95-8533
PIRECL PointWatch Eclipse
The Pointwatch Eclipse® Model PIRECL
is a diffusion-based, point-type infrared
gas detector that provides continuous
monitoring of combustible hydrocarbon gas
concentrations in the range of 0–100% LFL.
The LON supervision meets Signaling Line
Circuit (Class X) requirements per NFPA72:
2010 for the Model PIRECL.
For
PIRECL
installation,
operation,
maintenance, specifications and ordering
information, refer to form number 95-8526.
NOTE
The low alarm range for the EQP
PIRECL is 5–40% LFL (the standard
PIRECL is 5–60% LFL).
For information regarding USCG Approval of
the PIRECL Detector, refer to Appendix D.
LS2000 Line-of-Sight
The FlexSight™ Line-of-Sight Infrared
Hydrocarbon Gas Detector Model LS2000 is a
gas detection system that provides continuous
monitoring of combustible hydrocarbon gas
concentrations in the range of 0–5 LFL-meters,
over a distance of 5–120 meters.
EQ3900 Series Fire and Gas Alarm
Control Panel and Pre-Action System
Solutions
As part of providing the total solution to
commercial and industrial customers globally,
Det-Tronics offers several performance
approved
hazardous
area
(EQ3900N
and EQ3900E) and non-hazardous area
(EQ3900G) enclosure solutions. These are
custom solutions that can include 1 or more
of the following components: EQP controller,
EDIO, AIM, RM, DCIO, PSM, and GFM. Refer
to Instruction Manuals (95-8559 and 95-8641)
for additional information.
EQ3900RPS Explosion-Proof Power
Supply
The EQ3900RPS is an industrial power supply
that accepts two independent AC inputs and
produces 24 Vdc with up to 18 amps output
current. It can be configured with various
numbers of 24 Vdc power outputs, ground
fault test operator, status indicators, fuse
monitoring and window. It is intended for use
in Class 1 Division 1 locations.
The LON supervision meets Signaling Line
Circuit (Class X) requirements per NFPA72:
2010 for the Model LS2000.
For
LS2000
installation,
operation,
maintenance, specifications, and ordering
information, refer to form number 95-8714.
18.2
2-17
95-8533
Section 3
Installation
CAUTION
Any deviation from the manufacturer’s
recommended wiring practices can
compromise system operation and
effectiveness. ALWAYS consult the factory
if different wire types or methods are
being considered.
NOTE
For specific information regarding
systems meeting EN54 standards, refer
to the EQ5400 Series operation manual
95-8642.
NOTE
SAFETY SYSTEM DESIGN
REQUIREMENTS
All field wiring must be marked per NFPA
70 Article 760.
Many factors need to be considered when
determining proper EQP System design. The
following paragraphs will discuss these factors
and other issues useful in designing, installing
and configuring the Eagle Quantum Premier
System.
IDENTIFYING THE AREA OF PROTECTION
In order for the system to provide optimum
coverage and protection, it is critical to properly
define the required “Area of Protection” (total
area being monitored by the system). The area
of protection should include all hazard sources
requiring monitoring, as well as suitable
locations for mounting detection, extinguishing,
notification, and manual devices. In order to
accurately define the area of protection and
provide maximum protection, all potential
“Real” and “False” hazard sources must be
identified. The number and location of Real
Hazards determines the extent of the area of
protection, and impacts all subsequent design
decisions.
WARNING
When drilling through surfaces in the
process of mounting equipment, verify
that the location is free of electrical
wiring and electrical components.
Power Wiring
IMPORTANT
To ensure proper operation of field
devices, the voltage input to the device
(measured at the device) must be within
the range indicated for that device in the
“Specifications” section of this manual
(18 Vdc minimum).
System Wiring (ATEX and IECEx)
For the interconnection of the modules within
the EQP system, use fixed installed wiring.
(For correct wiring size and type for a specific
device, refer to the appropriate section in this
manual.)
For ambient temperatures below –10°C and
above +60°C, use field wiring suitable for both
minimum and maximum ambient temperatures.
IDENTIFYING WIRING, NETWORK (LON),
AND SYSTEM POWER REQUIREMENTS
The EQP Ex n modules may only be installed,
connected, or removed when the area is known
to be non-hazardous. The screw terminals are
to be tightened with a minimum torque of 0.5
Nm. Equipotential bonding connection facilities
on the outside of electrical equipment shall
provide effective connection of a conductor
with a cross-sectional area of at least 4 mm2.
General Wiring Requirements
WARNING
DO NOT open any junction box or device
enclosure when power is applied without
first de-classifying the hazardous area.
18.2
NOTE
Specific installation requirements may
differ depending on local installation
practices and compliance with third
party certifications. For local installation
practices, consult the local authority
having jurisdiction. For compliance with
third party certifications, consult the
appropriate appendix in this manual for
additional installation requirements.
3-1
95-8533
The Eagle Quantum Premier system utilizes a
power supply that provides an isolated 24 Vdc
battery backed-up power to the fire protection
devices as described in NFPA 72. More than
one power supply may be used in a system to
provide power to different sets of equipment as
part of the system.
The power supply wiring may consist of one or
more daisy-chained wire segments providing
power to the devices. For each of the daisychained wire segments, the installer must
calculate the voltage drops that occur across
the devices in order to determine the gauge of
the wire that will be installed.
A power supply wiring diagram should contain
information describing wire distances and
current draws associated with all devices
connected to the wire segment. A typical
power supply wiring recommendation is that
the voltage drop from the power source to the
end device should not exceed 10%. Using 24
Vdc as a reference, the maximum voltage drop
should not exceed 2.4 Vdc. A wire gauge must
be selected to ensure that the end device has
at least 21.6 Vdc or higher.
24 vdc Power
Supply
50 ft
0.6385 Ohms
150 ft
1.9155 Ohms
Total Current
695 mA
In order to calculate the power supply voltage
for the end device, calculate the voltage drops
that occur due to each wire segment between
the devices. This involves determining the
total current draw and the two conductor wire
resistance per each wire segment.
Example: Can 18 AWG wire be used to power
three devices from the 24 Vdc power supply?
Refer to the figure below for wiring and device
current draw information along with voltage
drop calculations.
Answer: If the Authority Having Jurisdiction
(AHJ) requires a voltage loss of 10% or less,
only 16 AWG wire could be used, since the end
device would require 21.4 Vdc. If there is no
local requirement, then 18 AWG wire could be
used to provide power to the devices.
18 AWG Single Wire Resistance: R = 0.6385 Ohms per 100 ft
2 Conductor Resistance: CR = 2 • R
Device 1
65 mA
Current Draw
Total Current
630 mA
=
Device 2
+
Device 3
Device 2
65 mA
Current Draw
150 ft
1.9155 Ohms
Device 1 Voltage = Supply Voltage – (Voltage Drop)
= 24 – (I • CR)
= 24 – (0.695 • 0.6385)
= 23.55 vdc
Device 2 Voltage = Device 1 Voltage – (Voltage Drop)
= 23.55 – (I • CR)
= 23.55 – (0.630 • 1.9155)
= 22.35 vdc
Total Current
565 mA
=
Device 3
Device 3
565 mA
Current Draw
18.2
3-2
Device 3 Voltage = Device 2 Voltage – (Voltage Drop)
= 22.35 – (I • CR)
= 22.35 – (0.565 • 1.9155)
= 21.27 vdc
95-8533
Determining Power Requirements
Tables 3-1 and 3-2 are provided for calculating
the total current requirements for those parts of
the system requiring battery backup.
Table 3–1—Standby Current Requirements at 24 Vdc
Device Type
Number of
Devices
Standby
Current
Total Current for Device Type
EQP Controller
X
0.360
=
EQ3LTM Module
X
0.001
=
EDIO Module
X
0.075
=
DCIO Module
X
0.075
=
Power Supply. Monitor
X
0.060
=
IDC/IDCGF/IDCSC
X
0.055
=
X3301/X3301A - without heater
X
0.160
=
X3301/X3301A - with heater
X
0.565
=
X3302 - without heater
X
0.160
=
X3302 - with heater
X
0.565
=
X2200
X
0.135
=
X9800 - without heater
X
0.085
=
X9800 - with heater
X
0.420
=
X5200 - without heater
X
0.155
=
X5200 - with heater
X
0.490
=
Relay Module
X
0.120
=
Analog Input Module
X
0.160
=
EQ2220GFM
X
0.018
=
PIRECL
X
0.270
=
LS2000 Transmitter without heater
X
0.149
=
LS2000 Transmitter with heater
X
0.336
=
LS2000 Receiver without heater
X
0.116
=
LS2000 Receiver with heater
X
0.258
=
Network Extender
X
0.090
=
ASM/ASH Module
X
0.560
=
EQ21xxPS Power Supply
X
0.350
=
UD10DCU - with heater off
X
0.054
=
UD10DCU - with heater on
X
0.167
=
UD10DCU CGS - w/ heater off
X
0.221
=
UD10DCU CGS - w/ heater on
X
0.333
=
Other
X
Total Standby Current for System (in amperes)
=
=
Notes: Standby current is the average current draw for the device in normal mode.
This table is for battery calculations only.
For OPECL standby current requirements, reference versions 16.1 and earlier of this manual.
18.2
3-3
95-8533
Table 3-2—Alarm Current Requirements at 24 Vdc
Device Type
Number of
Devices
Alarm Current
Total Current for Device Type
EQP Controller
X
0.430
=
EQ3LTM Module
X
0.001
=
EDIO 8 Inputs
X
0.130
=
EDIO 8 Outputs
X
0.075
=
DCIO 8 Inputs
X
0.130
=
DCIO 8 Outputs
X
0.075
=
Relay Module
X
0.120
=
Power Supply Monitor
X
0.060
=
IDC/IDCGF/IDCSC
X
0.090
=
X3301/X3301A - w/o heater
X
0.160
=
X3301/X3301A - with heater
X
0.565
=
X3302 - without heater
X
0.160
=
X3302 - with heater
X
0.565
=
X2200
X
0.135
=
X9800 - without heater
X
0.085
=
X9800 - with heater
X
0.420
=
X5200 - without heater
X
0.155
=
X5200 - with heater
X
0.490
=
Analog Input Module
X
0.300
=
EQ2220GFM
X
0.018
=
PIRECL
X
0.275
=
LS2000 Transmitter without heater
X
0.149
=
LS2000 Transmitter with heater
X
0.336
=
LS2000 Receiver without heater
X
0.182
=
LS2000 Receiver with heater
X
0.326
=
Network Extender
X
0.090
=
EQ3760ASM Module
X
0.560
=
EQ21xxPS Power Supply
X
0.350
=
UD10DCU - with heater off
X
0.054
=
UD10DCU - with heater on
X
0.167
=
UD10DCU CGS - with heater off
X
0.221
=
UD10DCU CGS - with heater on
X
0.333
=
Other
X
=
Total Solenoid Load
+
Total Signaling Load
Total Alarm Current for System (in amperes)
+
=
Notes: This table is for battery calculations only.
For OPECL alarm current requirements, reference versions 16.1 and earlier of this manual.
18.2
3-4
95-8533
Table 3-3A—EQ21xxPS Power Supply Specifications
Characteristic
Power Supply
EQ2110PS/EQ2111PS
EQ2130PS/EQ2131PS
EQ2175PS/EQ2176PS
Input Voltage
120 vac
120/208/240 vac
120/208/240 vac
Input Current
4 Amps
11/6/6 Amps
24/15/12 Amps
Input Frequency
60 Hz – EQ2110PS
60 Hz – EQ2130PS
60 Hz – EQ2175PS
Input Frequency
50 Hz – EQ2176PS
50 Hz – EQ2111PS
50 Hz – EQ2131PS
Supply Rating
10 Amps
30 Amps
75 Amps
Maximum Alarm Current
10 Amps
30 Amps
75 Amps
Maximum Standby Current
3.33 Amps
10 Amps
25 Amps
Recharge Current
6.67 Amps
20 Amps
50 Amps
Minimum Battery Capacity
40 AmpHours
120 AmpHours
300 AmpHours
Maximum Battery Capacity
100 AmpHours
300 AmpHours
750 AmpHours
1 Amp
3 Amps
7.5 Amps
Maximum Deluge Standby Current*
*Only applies to 90 hour back-up applications.
EQ211xPS, EQ213xPS and EQ217xPS
Power Supplies
WARNING
Refer to Table 3-3A for Power Supply ratings.
Backup Battery
Refer to Table 3-4 or 3-5 to calculate the
minimum size of the backup battery (in amp
hours). Select a sealed lead-acid battery with
an adequate amp hour rating.
NOTE
Connect two batteries in series for 24
volts. Batteries must be protected from
physical damage. The battery installation
shall be adequately ventilated.
Battery Charger
Use the following formula to calculate the
minimum battery charger size:
Minimum
=
Charge Rate
Alarm
Current
+
Total Amp Hours
48
EQP21X0PS(–X) Power Supplies
The EQP2120PS(–B) Power Supply is used in
pairs where the primary source of input supply
is connected to one and the secondary source is
connected to the other. Each power supply may
be backed up by another power supply of the
same model or by a DC-DC converter (see Figures
3-23A, B and C for available configurations). A
maximum of eight power supplies operated in
parallel can be connected to each input supply.
Both the primary and secondary sets must be
individually capable of operating the system
without the other supply. The secondary source
is required to be continuously powered.
The use of these supplies is based upon
acceptance of the local AHJ of the secure supply
system that provides the secondary supply. These
supplies must be used in a redundant configuration,
where one bank of supplies is fed from the primary
source and the other bank from the secondary
source. Both primary and secondary supplies
shall be continuously available and both rated for a
minimum 100% of load.
CAUTION
Care should be taken when considering
the final voltage at the device during AC
power loss. With loss of AC power, the
device voltage will drop over time as the
batteries lose their charge. If extended
periods of AC power loss are to be
expected, either consider a heavier wire
gauge or specify batteries with higher
amp-hour ratings.
18.2
To av o i d b a tte ry d a m ag e a d j u s t
float voltage to battery manufacturer
recommendations only. Serious injury
may result from battery explosion if
improperly adjusted.
Refer to Table 3-3B for power supply ratings.
3-5
95-8533
Table 3-4—Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge
Standby Current
Alarm Current
X
X
Standby Time*
24 Hours
5 Minute Alarm Time*
0.083 Hours
=
=
Sum of Standby and Alarm Amp Hours
=
Multiply by 1.2 (20% Safety Factor)
X
Standby Amp Hours
Alarm Amp Hours
T0014B
Total Battery Amp Hour Requirement
* FM MINIMUM REQUIREMENT FOR EXTINGUISHING SYSTEMS
IS 24 HOURS STANDBY TIME AND 5 MINUTES ALARM TIME.
Table 3-5—Backup Battery Requirements for Deluge and Pre-Action Applications
Standby Current
Alarm Current
X
X
Standby Time*
90 Hours
10 Minute Alarm Time*
0.166 Hours
=
=
Sum of Standby and Alarm Amp Hours
=
Multiply by 1.2 (20% S afety Factor)
X
Standby Amp Hours
Alarm Amp Hours
T0040B
Total Battery Amp Hour Requirement
* FM MINIMUM REQUIREMENT
FOR DELUGE SYSTEMS IS
90 HOURS ST ANDBY TIME AND 15 MINUTES ALARM TIME.
IMPORTANT
The EQP21X0PS(–X) Power Supplies
provide EQP System devices with power
from input supply 120 to 220 V ac. Use
of this power supply does not provide
the source of the secondary supply such
as secondary source batteries, their
supervision or charging, or UPS. Per
NFPA 72-2013 requirements, such power
supply related requirements must be
separately provided for and be accepted
by the local Authority Having Jurisdiction
(AHJ).
EQP2410PS(–P) Converter
The EQP2410PS(–P) Converter converts the
DC input voltage to an adjustable, controlled
and galvanically separated 24 Vdc output
voltage. The converter is always connected to
the secondary source.
Determining Power Requirements
Use of the EQP2120PS(–B) Power Supply
provides the primary and secondary supplies.
The EQP2410PS(–P) Converter provides the
18.2
secondary supply only. It is used in conjunction
with the EQP2120PS(–B) Power Supply, which
serve as the primary supply (see Figures
3-23A, B and C for available configurations).
The customer is responsible for providing
adequate secondary power supply source
needs. The ac input current requirements for
EQP2XX0PS(–X) in relation to EQP system
dc current load (power supply output) are
calculated using the following formula:
Input Current = [Output Current x Output
Voltage÷ Input Voltage ÷ Efficiency] + 0.43 A
Example:
[20 Adc x 28 Vdc ÷ 120 Vac ÷ 0.91] + 0.43 =
5.56 Aac
For
Standby
Current
(amperes
ac)
requirements, use Total Standby Current
(amperes dc) for the system’s applicable field
devices from Table 3-1.
For Alarm Current (amperes ac) requirements,
use Total Alarm current (amperes dc) for the
system’s applicable field devices from Table
3-2.
3-6
95-8533
Table 3-3B – EQP2XX0PS Power Supply and Converter Specifications
Characteristic
EQP2120PS(-B)
Power Supply
EQP2410PS(-P)
Converter
Input Frequency
60/50
N/A
Input Voltage
120/220 Vac
24 Vdc
Input Current, Max.
6.6 / 3.6 Iac
15.7 Idc
Output Voltage Range
24.5 … 28.0 Vdc
24.5 … 28.0 Vdc
Supply Rating
20
10
Maximum Alarm Current
20
10
Maximum Standby Current
20
10
Efficiency
91% for 120 Vac
93% for 220 Vac
88%
The System Controller requires a specific length
of time to process each bit of information that is
transferred along the communication loop. As
the number of nodes increases, so does the
amount of data being processed as well as the
time required for processing by the Controller.
NOTE
The suffix (-P) or (-B) defines the method
for mounting the panel mount models:
(-P) = mounting plate
(-B) = mounting brackets.
Shield Grounding
Two shield ground terminals are provided
inside the junction box of each device, and
also at the System Controller. Connect shield
ends to the terminals provided (not to each
other) inside the junction box.
Moisture Damage Protection
CAUTION
Moisture can adversely affect the performance
of electronic devices. It is important to take
proper precautions during system installation
to ensure that moisture will not come in contact
with electrical connections or components.
Insulate the shields to prevent shorting
to the device housing or to any other
conductor. Refer to Appendix E for EMC
Directive requirements.
Junction Box Grounding
All junction boxes must
connected to earth ground.
be
electrically
Response Time vs. System Size
When designing a system, it is important to
realize that by increasing the number of nodes
(devices) on the communication loop, the
amount of time required for a status change
message from a detection device to reach the
System Controller also increases.
18.2
If the fastest possible communication response
time is an important criteria for a large system,
it is recommended that the number of nodes on
an individual loop be kept as small as possible.
Consider using multiple controllers with fewer
nodes per loop.
3-7
In applications where the network wiring is
installed in conduit, the use of watertight
conduit seals, drains, breathers, or equivalent
is recommended to prevent damage caused
by condensation within the conduit.
Electrostatic Discharge
An electrostatic charge can build up on the
skin and discharge when an object is touched.
ALWAYS use caution when handling devices,
taking care not to touch the terminals or
electronic components.
95-8533
24 VDC
INPUT VOLTAGE
CAUTION
ALWAYS discharge static charges
from hands before handling electronic
devices or touching device terminals.
Many devices contain semiconductors
that are susceptible to damage by
electrostatic discharge.
+
+
–
EARTH
GROUND
5
1
2
3
4
+
–
+
–
NOTE
RELAY
For more information on proper handling,
refer to Det-Tronics Service Memo form
75-1005.
SPARE
GROUND FAULT MONITOR
(GFM) INSTALLATION
6
7
8
9
10
COMMON
NO
NC
N/C
EARTH
GROUND
NOTE: RELAY CONTACTS ARE SHOWN IN THE REST STATE,
NO POWER APPLIED. RELAY IS ENERGIZED WITH
POWER APPLIED AND NO GROUND FAULT
(TERMINALS 6 & 7 CLOSE, TERMINALS 6 & 8 OPEN).
Mounting
The GFM is a DIN rail mountable device
designed to be mounted in the same enclosure
as the EQP controller.
Figure 3-1—Terminal Configuration for Ground Fault Monitor
NOTE
Wiring
Cable meeting the specifications listed in
Table 3-6 is suitable for distances up to
2000 meters.
1. Connect power wiring from the EQP
controller power terminals 1 and 2 to the
GFM terminals 1 and 2.
2. Connect power wiring from the GFM
terminals 3 and 4 to the EQP controller
power terminals 3 and 4.
–
Any of the cable types listed in Table 3-7 can
be used for wiring the LON for the distances
indicated.
NOTE
3. Connect earth ground to terminal 5 or 10.
If no network extenders are used, the
distances listed are for the entire loop.
If network extenders are used, the
distances listed are for the wiring length
between network extenders or between
a network extender and the System
Controller.
4. Connect the relay contacts as required.
Refer to Figure 3-1 for terminal block
identification.
NETWORK AND NETWORK
EXTENDER INSTALLATION
IMPORTANT
Mounting
Det-Tronics recommends the use of
shielded cable (required by ATEX)
to prevent external electromagnetic
interference from affecting field devices.
The device should be securely mounted to a
vibration free surface. (See the “Specifications”
section in this manual for device dimensions.)
Wiring
WARNING
All devices on the LON are wired in a loop that
starts and ends at the System Controller. To
ensure proper operation, the LON should be
wired using high speed communication grade
cable.
18.2
Be sure that the selected cable meets
all job specifications and is rated for the
installation per local and national codes
and practices. The use of other cable
3-8
95-8533
types can degrade system operation.
If necessary, consult factory for further
suggested cable types.
NOTE
Cables designed to ISA SP50 Type A or IEC
61158-2 Type A are suitable for use in LON/
SLC wiring. For armored version, contact cable
manufacturer.
LON Cable
Maximum Length**
(Manufacturer and Part No.)*
Feet
Meters
Belden 3073F (Tray Rated)
6,500
2,000
Det-Tronics NPLFP
6,500
2,000
Technor BFOU
4,900
1,500
1 Shielded Pair, 16 AWG,
Type TC, p/n FB02016-001
6,500
2,000
1 Shielded Pair, 18 AWG,
Type TC, p/n FB02018-001
6,500
2,000
Rockbestos Gardex Fieldbus
1. Remove the cover from the Network
Extender enclosure.
2. Connect 24 Vdc power lead wires and
communication network cable to the
terminal block. (See Figure 3-2 for terminal
location and Figure 3-3 for terminal
identification).
Table 3-7—LON Maximum Cable Lengths
Note: *Use the same type of cable in each wiring
segment between network extenders.
See Table 3-8 to determine maximum wiring
length.
COM 1 - Communication network connections:
Connect to COM 2 terminals of the
next device on the loop, A to A and B
to B.
**Maximum wire lengths represent the linear
wire distance of LON communications wiring
between network extenders.
Be sure that selected cable meets all job
specifications, indoor, outdoor and direct
burial.
If necessary, consult factory for further
suggested cable types.
24 Vdc - Connect the "+" terminal to the
positive side of the 24 Vdc power
source. (Both "+" terminals are
connected internally.)
COM 2 - Communication network connections:
Connect to COM 1 terminals of the
previous device on the loop, A to A
and B to B.
Connect the "–" terminal to the
negative side of the 24 Vdc power
source. (Both "–" terminals are
connected internally.)
Table 3-6—Typical Specification for 16 AWG (1.5 mm2) LON Wiring Cable per Echelon
DC Resistance, each conductor
Minimum
Typical
Maximum
Units
14
14.7
15.5
ohm/km
Condition
20 C per ASTM D 4566
DC Resistance Unbalanced
5%
Mutual Capacitance
55.9
nF/km
108
ohm
20 kHz
1.3
dB/km
20 C per ASTM D 4566
64 kHz
1.9
78 kHz
2.2
nsec/m
78 kHz
Characteristic Impedance
Attenuation
Propagation Delay
92
100
156 kHz
3
256 kHz
4.8
512 kHz
8.1
772 kHz
11.3
1000 kHz
13.7
5.6
20 C per ASTM D 4566
per ASTM D 4566
64 kHz to 1 MHz, per ASTM D 4566
Length:
feet/2000 meters maximum (basic loop or between Network Extenders).
Length:
6,500 6,500
feet/2000
meters maximum (basic loop or between Network Extenders).
Type:
Single twisted pair.
Type:
Single
twisted
W ire Gauge: 16 AWG,pair.
stranded (19 x 29), tinned copper with overall shield.
Wire
AWG,
stranded (19
29),for
tinned
with overall shield.
CablesGauge:
meeting16
these
specifications
arexgood
up tocopper
2000 meters.
Cables meeting these specifications are good for up to 2000 meters.
18.2
3-9
T0049B
95-8533
Table 3-8—Maximum Wiring Length from Nominal 24 Vdc
Power Source to Network Extender
(Maximum wire lengths are based upon the cable’s physical
and electrical characteristics.)
Wire Size
Maximum Wiring Distance
Feet Meters
18 AWG (1.0 mm2)* 2200
16 AWG (1.5 mm2)* 3500
14 AWG (2.5 mm2)* 5600
650
750
1700
*Approximate Metric Equivalent.
1
SHIELD
2
A
3
B
4
SHIELD
5
+
6
–
7
–
8
+
9
SHIELD
10
A
11
B
12
SHIELD
COM 1
24 VDC
3. Connect shields to the designated "shield"
terminals. The two shield terminals are
connected internally to ensure shield
continuity.
CAUTION
Do not ground either shield at the
network extender enclosure. Insulate the
shields to prevent shorting to the device
housing or to any other conductor.
COM 2
A1947
Figure 3-3—Network Extender Wiring Terminal Identification
4. Check ALL wiring to ensure that proper
connections have been made.
5. Inspect the junction box O-ring to be sure
that it is in good condition.
6. Lubricate the O-ring and the threads of the
junction box cover with a thin coat of grease
to ease installation and ensure a watertight
enclosure.
NOTE
The recommended lubricant is a silicone
free grease, available from Det-Tronics.
7. Place the cover on the enclosure. Tighten
only until snug. Do not over tighten.
TERMINAL NO. 1
1
12
EQ3XXX CONTROLLER
INSTALLATION
The following paragraphs describe how to
properly install and configure the EQ3XXX
Controller.
ENCLOSURE REQUIREMENTS
The Controller must be properly installed in a
suitable enclosure that is rated for the location.
The enclosure must provide space to install
and wire the Controller and must also provide
for ground wire termination. The enclosure
must contain either a keyed lock or a special
tool to gain access into the enclosure. The
enclosure should be rated for the temperature
range of the location plus the temperature rise
of all equipment installed inside the enclosure.
The enclosure must be rated for electrical
equipment that is going to be installed.
A2021
Figure 3-2—Network Extender Wiring Terminal Location
18.2
3-10
95-8533
NOTE
NOTE
The Controller and enclosure must be
connected to earth ground.
A minimum clearance of 4 inches
between the Controller and nearby
equipment is required to provide room
for wiring and ventilation.
For ordinary locations when entry is required to
operate the equipment, the cabinet should be
a dead-front construction and 16-gauge coldrolled steel. The door lock system shall accept
different keys for entry. An Authorized Persons
key and a Person-in-charge key will allow entry
into the cabinet. The cabinet should contain a
window to view the Controller’s text display and
LED indicators.
NOTE
Fo r a ny s e l e c te d e n c l o s u re , t h e
enclosure must conform to all applicable
regulations and requirements.
NOTE
The Trouble signal must be located in an
area where it is likely to be heard.
Classified locations require the appropriate
hazardous rated enclosure. It is recommended
that operators/switches be installed in the
enclosure. This avoids the need to declassify
the area in order to operate the Controller.
Regulations require that key switches be
installed for certain operations. An appropriate
window should be part of the enclosure in order
to allow an operator to view the text display and
LED indicators.
NOTE
If an enclosure does not have a keyed
entry, a special tool is required to gain
entry into an enclosure.
SERIAL INTERFACE BOARD
A Serial Interface Board is available for the
EQP Controller. See Figures 3-8A and 3-9 for
details on the electrical connections.
ETHERNET INTERFACE BOARD
An Ethernet Interface Board is available for the
EQP Controller. See Figures 3-8B and 3-9 for
details on the electrical connections.
WIRING
Power Wiring
CAUTION
Input voltage at the Controller must be 18
Vdc minimum to ensure proper operation.
It is important to consider both the wire gauge
and the distance from the Controller to the
power supply. As the distance between the
Controller and the power supply increases,
so must the diameter of the power wiring in
order to maintain a minimum of 18 Vdc at the
Controller.
IMPORTANT
Det-Tronics offers several approved (FM/CSA/
ATEX/CE) hazardous area enclosures that have
Eagle Quantum Premier equipment installed in
the enclosure. Contact Det-Tronics for further
information.
MOUNTING
The Controller is designed for direct panel
mounting or DIN rail (optional) mounting. See
“Specifications” section of this manual for
mounting dimensions.
NOTE
Clips for DIN rail mounting are available,
but must be specified at the time of
ordering.
18.2
To ensure proper operation of devices,
t h e v o l tag e i n p u t to t h e d ev i c e
(measured at the device) must be within
the range indicated for that device in the
"Specifications" section of this manual.
Electrical Connections
Figure 3-8 shows the location of wiring
connectors on the Controller module. Figure
3-9 identifies individual terminals.
Connector P1, Terminals 1 to 4 —
24 Vdc Input Power
Connect the power supply to terminals 1 and
2 of the Controller. Terminals 3 and 4 must also
be connected to power.
3-11
95-8533
P4
P2
COMMON 21
INPUT, + 5
+
N. O. 22
COMMON, – 6
N. C. 23
–
Figure 3-4—Unsupervised Input Wiring
When controller and power supplies are
installed in separate NRTL cabinets, two
power cables from two distribution circuits are
required, so that if one is lost, the controller
will continue to operate and signal a trouble
condition. The power circuit must be protected
against physical damage.
Shields on power cables must be connected to
chassis ground (earth).
Connector P2, Terminals 5 to12 —
Unsupervised Digital Input Channels 1 to 4
Connector P3, Terminals 13 to 20 —
Unsupervised Digital Input Channels 5 to 8
See Figure 3-4 for example. Only channel 1 is
shown in Figure 3-4. The information is typical
for channels 2-8.
Connector P4, Terminals 21 to 32 —
Unsupervised Relay Output Channels 1 to 4
Connector P5, Terminals 33 to 44 —
Unsupervised Relay Output Channels 5 to 8
See Figure 3-5 for example. Only channel 1 is
shown in Figure 3-5. The information is typical
for channels 2-8.
opening the N.C. contact (terminals 45-47).
The relay coil is de-energized in the trouble
condition.
Connector P7, Terminals 48 to 53 —
LON Signaling Line Circuit Terminals
The LON loop is wired so that the controller’s
LON COM 1 is connected to the field device’s
COM 2 connection. The field device’s COM 1 is
wired to the next device’s COM 2 connection.
This continues through the last field device
on the loop. The last field device’s COM 1
is then wired back to the Controller’s COM 2
connection. LON A and B polarities must be
maintained throughout the loop (i.e., always
wire A to A and B to B between the devices).
Port Pinout (6-position connection terminal
block)
48 — COM 1 shield connection
49 — "B" side of signaling circuit for COM 1
50 — "A" side of signaling circuit for COM 1
51 — COM 2 shield connection
52 — "B" side of signaling circuit for COM 2
53 — "A" side of signaling circuit for COM 2
NOTE
Refer to Figures 3-12A and 3-12B for
location of termination jumpers.
NOTE
C h a n n e l s o ft wa re c o n fi g u ra t i o n s
include all panel indicator functions to
automatically mimic the controller front
panel indicators.
Jumper P24 – RS-485 Termination Jumper
1-2 Unterminated
2-3 Terminated 121 ohms (factory setting)
Transceiver input impedance: 68 kohm
Connector P6, Terminals 45, 46 & 47 —
Trouble Relay
The Trouble relay is not configurable. In the
normal condition, the relay coil is energized,
closing the N.O. contact (terminals 45-46) and
18.2
Figure 3-5—Unsupervised Relay Output
3-12
Jumper P25 – LON COM 1 Termination
1-2 COM 1 Terminated (factory setting)
2-3 COM 1 Unterminated (Redundancy)
95-8533
1
4
5
3-13
20 21
Previous
Reset
Supr
32 33
Acknowledge Silence
Silence
44 45
47
P1: TERMINALS 1 TO 4
24 VDC INPUT POWER
P2: TERMINALS 5 TO 12
DIGITAL INPUTS 1 TO 4
P3: TERMINALS 13 TO 20
DIGITAL INPUTS 5 TO 8
P4: TERMINALS 21 TO 32
RELAYS 1 TO 4
P5: TERMINALS 33 TO 44
RELAYS 5 TO 8
P6: TERMINALS 45 TO 47
FAULT RELAY (NC CONTACT)
P7: TERMINALS 48 TO 53
LON CONNECTIONS
P8: TERMINALS 54 TO 56 - PORT 1
RS-485 MODBUS RTU MASTER/SLAVE
P9: TERMINALS 57 TO 59
RS-232 S3 CONFIGURATION PORT
SERIAL INTERFACE BOARD
P10: TERMINALS 60 TO 62 - PORT 2
RS-485 MODBUS RTU MASTER/SLAVE
Figure 3-6A—Location of Wiring Terminals on EQP Controller with Serial Interface Board
12 13
Next
Ack
Power
60
Configuration data downloaded into the
controller configures the serial interface
transmission baud rate, parity check for the
serial port, and Modbus device address.
Enter
Low Gas
Inhibit
Out Inhibit
63 62
Connector P8, Terminals 54, 55 & 56 , Port 1—
RS-485 Modbus RTU Master/Slave
Cancel
Lon Fault
High Gas
Time & Date
Trouble
Cntrl Flt
Fire Alarm
Eagle Quantum Premier
EAGLE QUANTUM PREMIER
Safety System Controller
®
66 65
DET-TRONICS
68
P11: TERMINALS 63 TO 65 – PORT 3
RS-232 MODBUS RTU MASTER/SLAVE
OR S3 CONFIGURATION
1-2 COM 2 Terminated (factory setting)
2-3 COM 2 Unterminated (Redundancy)
G2105
CONTROLNET
BNC CONNECTOR A
OR
ETHERNET DLR RJ45
CONNECTOR PORT 1
CONTROLNET
BNC CONNECTOR B
OR
ETHERNET DLR RJ45
CONNECTOR PORT 2
P13: HIGH SPEED SERIAL LINK (HSSL)
RS-232 (REDUNDANCY ONLY)
59
56 57
54
53
18.2
48
P12: TERMINALS 66 TO 68 – PORT 4
RS-232 MODBUS RTU MASTER/SLAVE
Jumper P26 – LON COM 2 Termination
Software selectable baud rates are 2400,
4800, 9600,19200, 38400, 57600, and 115200.
Software selectable parity is None, Odd, and
Even. The controller uses 8 data bits with 1
stop bit.
Port Pinout (3-position terminal block)
54 — GND
55 — B
56 — A
95-8533
3-14
A2632
CONTROLNET
BNC CONNECTOR A
OR
ETHERNET DLR RJ45
CONNECTOR PORT 1
CONTROLNET
BNC CONNECTOR B
OR
ETHERNET DLR RJ45
CONNECTOR PORT 2
1
4
5
Enter
Previous
20 21
Next
Reset
Trouble
Inhibit
Ack
Out Inhibit
Silence
Supr
Power
32 33
Acknowledge Silence
Lon Fault
Cntrl Flt
®
62
60
44 45
47
P1: TERMINALS 1 TO 4
24 VDC INPUT POWER
P2: TERMINALS 5 TO 12
DIGITAL INPUTS 1 TO 4
P3: TERMINALS 13 TO 20
DIGITAL INPUTS 5 TO 8
P4: TERMINALS 21 TO 32
RELAYS 1 TO 4
P5: TERMINALS 33 TO 44
RELAYS 5 TO 8
P6: TERMINALS 45 TO 47
FAULT RELAY (NC CONTACT)
P7: TERMINALS 48 TO 53
LON CONNECTIONS
P8: TERMINALS 54 TO 56 - PORT 1
RS-485 MODBUS RTU MASTER/SLAVE
P9: TERMINALS 57 TO 59
RS-232 S3 CONFIGURATION PORT
ETHERNET INTERFACE BOARD
P10: TERMINALS 60 TO 62 - PORT 2
RS-485 MODBUS RTU MASTER/SLAVE
Port 3, ETHERNET, MODBUS TCP/IP MASTER/SLAVE
or S3 CONFIGURATION
Figure 3-6B—Location of Wiring Terminals on EQP Controller with Ethernet Interface Board
12 13
Cancel
High Gas
Time & Date
Low Gas
Fire Alarm
Eagle Quantum Premier
EAGLE QUANTUM PREMIER
Safety System Controller
DET-TRONICS
P13: HIGH SPEED SERIAL LINK (HSSL)
RS-232 (REDUNDANCY ONLY)
59
56 57
54
53
18.2
48
Port 4, ETHERNET, MODBUS TCP/IP MASTER/SLAVE
Connector P9, Terminals 57, 58 & 59 —
S³ Configuration Port
115200 (factory default is 115200). Software
selectable parity is None, Odd, and Even.
Configuration data downloaded into the
controller configures the serial interface
transmission baud rate and parity check for the
serial port. Software selectable baud rates are
2400, 4800, 9600,19200, 38400, 57600, and
Port Pinout (3-position terminal block)
57 — GND
58 — RXD
59 — TXD
95-8533
P1
24 VDC INPUT POWER
P2
DIGITAL INPUTS 1 TO 4
P3
DIGITAL INPUTS 5 TO 8
P4
RELAYS 1 TO 4
P5
RELAYS 5 TO 8
P6
TROUBLE RELAY
48
SHIELD
49
1B
+
1
–
2
+
3
50
1A
–
4
51
SHIELD
1+
5
52
2B
1–
6
2+
7
2–
8
3+
9
3–
10
4+
11
COM 1
RESET*
COM 2
ACKNOWLEDGE*
SILENCE*
INHIBIT ENABLE**
53
2A
54
GND
55
B
56
A
57
GND
58
RxD
59
TxD
4–
12
5+
13
5–
14
6+
15
6–
16
7+
17
7–
18
8+
19
8–
20
1 C
21
1 NO
22
1 NC
23
66
TxD
2 C
24
67
RxD
2 NO
25
68
GND
2 NC
26
3 C
27
3 NO
28
3 NC
29
4 C
30
4 NO
31
4 NC
32
5 C
33
5 NO
34
5 NC
35
6 C
36
6 NO
37
6 NC
38
7 C
39
7 NO
40
7 NC
41
8 C
42
8 NO
43
8 NC
44
C
45
NO
46
NC
47
P7
LON
P8
RS-485
PORT 1
P9
RS-232
CONFIG
PORT
ENTER*
CANCEL*
NEXT*
PREVIOUS*
FIRE ALARM*
SUPERVISORY*
SERIAL INTERFACE BOARD
60
A
61
B
62
GND
63
TxD
64
RxD
65
GND
INHIBIT*
P11
RS-232
PORT 3
P12
RS-232
PORT 4
P13
RS-232 - HSSL
(Custom Connector,
for Redundancy Only)
LOW GAS ALARM*
HIGH GAS ALARM*
P10
RS-485
PORT 2
ETHERNET INTERFACE BOARD
60
A
61
B
62
GND
P10
RS-485
PORT 2
RJ45
ETHERNET
PORT 3
RJ45
ETHERNET
PORT 4
OUTPUT INHIBIT*
LON FAULT*
BEEPER*
P13
RS-232 - HSSL
(Custom Connector,
for Redundancy Only)
* DIGITAL INPUTS AND RELAY OUTPUTS CAN BE
H2104
CONFIGURED AS THE STATIC FUNCTION NAME (AS
SHOWN) OR CAN BE USER DEFINED.
** INHIBIT ENABLE FOR SIL CONTROLLERS ONLY.
Figure 3-7—EQP Controller Terminal Identification
18.2
3-15
95-8533
Connector P10, Terminals 60, 61 & 62, Port 2–
RS-485 Modbus RTU Master/Slave
CONTROLLER TO CONTROLLER
COMMUNICATION
Configuration data downloaded into the
controller configures the serial interface
transmission baud rate, parity check for the
serial port, and Modbus device address.
Software selectable baud rates are 9600,19200,
38400, 57600, 115200 and 230400. Software
selectable parity is None, Odd, and Even. The
controller uses 8 data bits with 1 stop bit.
Controller to Controller Communication
(SLC485) with Signaling Line Circuit
Classification Class B or X, per NFPA 72
Port Pinout (3-position terminal block)
60 — A
61 — B
62 — GND
To meet the signaling line circuit (Class B or
Class X) requirements, the following must be
configured for correct operation:
• All controllers must have the same type
Interface Board (Ethernet or Serial)
installed.
Serial Interface Board Jumpers
Jumper P25 – RS-485 Termination
Jumper, Port 2
1-2 Terminated 121 ohms (factory setting)
2-3 Unterminated
Transceiver input impedance: 68 kohm
Jumper P3 – RS-485 Ground Fault
Monitor, Port 2
1-2 Enabled
2-3 Disabled (factory setting)
Ethernet Interface Board Jumpers
Jumper P6 – RS-485 Termination Jumper,
Port 2
1-2 Terminated 121 ohms (factory setting)
2-3 Unterminated
Transceiver input impedance: 68 kohm
Jumper P5 – RS-485 Ground Fault
Monitor, Port 2
1-2 Enabled
2-3 Disabled (factory setting)
Use Port 2 to pass safety critical information
between controllers. Ensure that Ground Fault
Monitoring is enabled. User logic can pass all
alarm, trouble, and supervisory information
between the controllers. Watchdog timers
must be implemented in user logic to verify
the integrity of the SLC. Consult the local
authority having jurisdiction for annunciation
requirements.
18.2
To connect up to twelve controllers together
and be able to transfer safety information
between the controllers, the communication
link must be classified as a signaling line circuit
per NFPA 72. With the Serial Interface Board,
Port 2 (plug 10) is a RS-485 serial connection
that is ground fault monitored.
3-16
CAUTION
When using the Ethernet Interface Board,
controllers communicating over P10, Port
2 - RS-485 are required to be located
within the same room or be wired in
conduit within 20 feet (6 meters) for
signalling line transient protection.
• The Termination jumper P28 must be
set to Terminate (position 1-2) on all
controllers.
• The Ground Fault Monitor jumper P29
must be set to Enabled (position 1-2) on all
controllers.
• For Class X, Connect terminals A (# 56) and
B (# 55) between the controllers. Connect
terminal A (# 60) and B (# 61) between
controllers using a different cable route.
Connect GND (# 54) to GND (# 62) on each
controller.
• For Class B, connect terminals A (terminal
number 60) and B (terminal number 61)
between the controllers. The GND (terminal
number 62) must not be connected.
See Figure 3-13A and 3-13B for wiring details.
Note 1: 56.7 kbps minimum and 115.2 kbps
maximum baud rate required for
proper communication.
Note 2: Consult the factory for configuration
set-up.
Note 3: Maximum SLC485 length over
copper not to exceed 1000 meters.
95-8533
68
67
66
65
64
63
62
61
P12
P11
P10
PORT 4
PORT 3
PORT 2
60
3
3
P3
P25
1
1
RS-232 Transmit LED (Amber)
RS-232 Receive LED (Green)
P3: RS-485 Ground Fault
MonitorJumper
RS-485 Transmit LED (Amber)
RS-232 Transmit LED
(Amber)
RS-485 Receive LED (Green)
P25: RS-485 Termination Jumper
RS-232 Receive LED (Green)
DET-TRONICS
A
B
Channel
Indicators
®
RS-485 Transmit LED (Amber)
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Time & Date
Cancel
Enter
Next
Previous
3
RS-485 Termination Jumper
Fire Alarm
Trouble
Inhibit
Power
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
P
O
R
T
1
1
P24
RS-485 Receive LED (Green)
1
P26
LON COM 2
Termination Jumper
3
Acknowledge Silence
1
P25
3
LON COM 1
Termination Jumper
Figure 3-10A—Location of Termination Jumpers, Communication Indicator LEDs, and Communication Ports
for Controller with Serial Interface Board
Manufacturer
Model
Number
Description
Moxa
(www.moxa.com)
TCF-142-S
RS-485 to Singlemode Fiber Optical
Converter
Phoenix Contact
PSI-MOSRS-485W2/
FO
RS-485 to Multimode Fiber Optical
Converter
Table 3-9—Approved Supported Media Converters
for Fiber Optic Link
72 to allow safety information to be transferred
between controllers.
The fiber optic link incorporates media
converters to convert from copper to fiber
optic cable. The converter must be located in
the same cabinet as the controller and cannot
use ground fault monitoring. The approved
supported converters are shown in Table
3-9. The link budget for the listed fiber optic
converters is 10dB.
Controller to Controller with Fiber Optic
Link, Signal Line Circuit Classification
Class B or X per NFPA 72.
WARNING
The fiber converters must be mounted
inside the same enclosure as the
controllers to conform to NFPA 72.
Up to twelve EQP controllers (single or
redundant pair) can be inter-connected via
a fiber optic link. This communication link is
classified as a signaling line circuit per NFPA
18.2
3-17
95-8533
62
61
60
RJ45
RJ45
P10
PORT 4
PORT 3
PORT 2
1
P6
3
1
P5
3
RS-232 Transmit LED (Amber)
RS-232 Receive LED (Green)
Ethernet Transmit LED (Amber)
Ethernet Receive LED (Green)
Ethernet Port Ready LED (Blue)
RS-232 Transmit LED
(Amber)
P6: RS-485 Termination Jumper
RS-485 Transmit LED (Amber)
RS-485 Receive LED (Green)
P5: RS-485 Ground Fault
Monitor Jumper
RS-232 Receive LED (Green)
DET-TRONICS
A
Channel
Indicators
B
®
RS-485 Transmit LED (Amber)
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Enter
Next
Previous
3
RS-485 Termination Jumper
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
P
O
R
T
1
1
P24
Power
RS-485 Receive LED (Green)
1
P26
LON COM 2
Termination Jumper
3
Acknowledge Silence
1
P25
3
LON COM 1
Termination Jumper
Figure 3-10B—Location of Termination Jumpers, Communication Indicator LEDs, and Communication Ports
for Controller with Ethernet Interface Board
The media converter can be connected to either
of the EQP controller RS-485 communication
ports (Port 1 or Port 2). Figure 3-14 illustrates
a typical Class B wiring connection (single
mode) between two EQP controllers in a
redundant configuration using Port 1. Note: If
Port 2 is preferred, the Serial Interface Board
must be purchased.
The maximum distance of a particular optic
link given the optical budget is calculated as:
Figure 3-13 shows a typical Class X wiring
connection (single mode).
Example:
Figure 3-14 shows a typical Class X wiring
connection for Phoenix (multi mode).
For more information regarding selection and
installation of fiber optic media, please contact
Det-Tronics customer service.
18.2
3-18
Fiber Length = [Optical budget] – [Link Loss]
[Fiber Loss / km]
where link loss includes number of end
connectors, splices and safety margin.
10 db link budget
Cable Attenuation: 0.4 db / km
2 connectors: (1 each end) with
0.5 db ea.
Safety margin: 3.0 db max
Max. Distance = 10 – (2 x 0.5) – 3.0 = 15 km
0.4
95-8533
TO
ADDITIONAL
CONTROLLER(S)
68
67
66
65
64
63
62
61
GND
60
B
68
67
66
64
65
A
GND
60
B
A
P12
P11
P10
P12
P11
P10
PORT 3
PORT 2
PORT 4
PORT 3
PORT 2
3
3
3
P25
1
DET-TRONICS
Time & Date
Cancel
Enter
Next
Previous
P25: RS-485 Termination Jumper,
Position 1 & 2
DET-TRONICS
®
56
55
54
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
1
P3: RS-485 Ground Fault
Monitor Jumper, Position 1 & 2
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
P25
1
P25: RS-485 Termination Jumper,
Position 1 & 2
Fire Alarm
3
P3
1
P3: RS-485 Ground Fault
Monitor Jumper, Position 1 & 2
B
61
62
PORT 4
P3
A
63
A
B
Eagle Quantum Premier
Power
Fire Alarm
Time & Date
Acknowledge Silence
®
56
55
54
EAGLE QUANTUM PREMIER
Safety System Controller
Cancel
Enter
Next
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Previous
Reset
Power
Acknowledge Silence
E2276
Figure 3-11A—Controller to Controller Communication with Class A Signaling Line Circuit Classification per NFPA 72,
for Controllers with Serial Interface Board
TO
ADDITIONAL
CONTROLLER(S)
62
61
GND
60
B
A
GND
P10
RJ45
RJ45
P10
PORT 2
PORT 4
PORT 3
PORT 2
3
1
P5
3
1
DET-TRONICS
Fire Alarm
Cancel
Enter
Next
Previous
56
55
54
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
DET-TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
Time & Date
3
1
P5
3
P5: RS-485 Ground Fault
Monitor Jumper, Position 1 & 2
P5: RS-485 Ground Fault
Monitor Jumper, Position 1 & 2
Eagle Quantum Premier
P6
P6: RS-485 Termination Jumper,
Position 1 & 2
P6: RS-485 Termination Jumper,
Position 1 & 2
B
A
RJ45
PORT 3
P6
60
B
RJ45
PORT 4
1
A
61
62
A
B
Eagle Quantum Premier
Power
Fire Alarm
Time & Date
Acknowledge Silence
®
56
55
54
EAGLE QUANTUM PREMIER
Safety System Controller
Cancel
Enter
Next
Previous
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
Power
Acknowledge Silence
A2633
Figure 3-11B—Controller to Controller Communication with Class A Signaling Line Circuit Classification per NFPA 72,
for Controllers with Ethernet Interface Board
18.2
3-19
95-8533
Connector P11, Terminals 63, 64 & 65, Port 3–
(Serial Interface Board only)
RS-232 Modbus RTU Master/Slave or S³
Configuration Port (Non-Isolated)
Configuration data downloaded into the
controller configures the serial interface
transmission baud rate, parity check and
Modbus device address for the serial port.
Software selectable baud rates are 9600,19200,
38400, 57600, 115200, and 230400. Software
selectable parity is None, Odd, and Even. The
controller uses 8 data bits with 1 stop bit.
Port Pinout (3-position terminal block)
63 — TXD
64 — RXD
65 — GND
RJ45, Port 3
(Ethernet Interface Board only)
Ethernet Modbus TCP Client/Server
or S³ Configuration Port (Non-Isolated)
Configuration data downloaded into the
controller configures the Ethernet interface
IP address, subnet mask, gateway, and local
port number. This port may be used as a
Modbus TCP Client or a Modbus TCP Server.
This port may also be used as an alternate S³
configuration port. EQP controllers come from
the factory with the following default values for
Port 3:
Port 3
IP Address
192.168.127.251
Port 3
Subnet Mask
255.255.255.000
Port Pinout (3-position terminal block)
66 — TXD
67 — RXD
68 — GND
RJ45, Port 4
(Ethernet Interface Board only)
Ethernet Modbus TCP Client/Server
Configuration data downloaded into the
controller configures the Ethernet interface
IP address, subnet mask, gateway, and local
port number. This port may be used as a
Modbus TCP Client or a Modbus TCP Server.
EQP controllers come from the factory with the
following default values for Port 4:
Port 4
IP Address
192.168.127.252
Port 4
Subnet Mask
255.255.255.000
NOTE
Maximum Modbus update time per port
is 250 mSec.
Connector P13 —
RS-232 High Speed Serial Port
This port is dedicated to inter-controller
connection required for redundancy, and is
not available for any other use. This port is
automatically configured.
CONFIGURATION
Software Defined Addresses
NOTE
Maximum Modbus update time per port
is 250 mSec.
Connector P12, Terminals 66, 67 & 68, Port 4–
(Serial Interface Board only)
RS-232 Modbus RTU Master/Slave
(Non-Isolated)
Configuration data downloaded into the
controller configures the serial interface
transmission baud rate, parity check and
Modbus device address for the serial port.
Software selectable baud rates are 9600,19200,
38400, 57600, 115200, and 230400. Software
selectable parity is None, Odd, and Even. The
controller uses 8 data bits with 1 stop bit.
18.2
3-20
Det-Tronics Safety System Software (S³)
is programmed with the addresses that
are assigned to the controller when the
configuration file is downloaded into the
controller. Addresses define and configure
the Controller’s LON address, Modbus slave
address, ControlNet option board address,
and EtherNet DLR option board address. Each
device on the LON must be assigned a unique
tag number. This tag number must include
zone designation, which will be shown on the
Controller's display when the device is in alarm.
95-8533
EQP CONTROLLER No. 3
EQP CONTROLLER No. 1
SINGLE MODE
PORT 1
RS-485
A
56
B
55
GND
54
FIBER OPTIC CABLE
Rx
56
Tx
Rx
Tx
T+
T+
T–
T–
R+D+
R–D–
PORT 1
RS-485
B
54
GND
PORT 1
RS-485
R+D+
Moxa
TCF-142-S
Moxa
TCF-142-S
R–D–
Tx
EQP CONTROLLER No. 2
A
55
Tx
Rx
Rx
GND
GND
EQP CONTROLLER No. 4
A
56
56
B
55
55
B
GND
54
54
GND
A
PORT 1
RS-485
B2328
Figure 3-12—Controller to Controller NFPA 72 Approved Fiber Optic Link, Class B
SINGLE MODE
FIBER OPTIC CABLE
Rx
EQP CONTROLLER No. 1
Rx
Tx
T+
T–
T–
R+D+
R–D–
PORT 2
RS-485
Tx
T+
Moxa
TCF-142-S
Moxa
TCF-142-S
R+D+
EQP CONTROLLER No. 2
R–D–
A
60
Tx
Tx
60
B
61
Rx
Rx
61
B
GND
62
GND
GND
62
GND
56
A
A
PORT 2
RS-485
SINGLE MODE
FIBER OPTIC CABLE
Rx
PORT 1
RS-485
A
56
B
55
GND
54
Tx
Rx
Tx
T+
T+
T–
T–
R+D+
R–D–
Moxa
TCF-142-S
Moxa
TCF-142-S
B
54
GND
PORT 1
RS-485
R+D+
R–D–
Tx
55
B2371
Tx
Rx
Rx
GND
GND
Figure 3-13—Single Mode Controller to Controller NFPA 72 Approved Fiber Optic Link, Class X
18.2
3-21
95-8533
EQP CONTROLLER No. 1
A
60
B
61
GND
62
PORT 2
RS-485
TROUBLE INPUT
TO EQP SYSTEM
TROUBLE INPUT
TO EQP SYSTEM
MULTI MODE
FIBER OPTIC CABLE
ATD
ARD
BTD
BRD
60
BTD
BRD
ATD
D(P)
D(N)
EQP CONTROLLER No. 2
EQP CONTROLLER No. 3
ARD
A
PORT 2
RS-485
61
B
62
GND
D(P)
Phoenix
Phoenix
PSI-MOSRS485W2/FO
PSI-MOSRS485W2/FO
GND
D(N)
GND
EQP CONTROLLER No. 4
A
60
60
A
B
61
61
B
GND
62
62
GND
PORT 2
RS-485
PORT 2
RS-485
B2372
Figure 3-14—Multi-Mode Controller to Controller NFPA 72 Approved Fiber Optic Link, Class X
EQ3XXX REDUNDANT
CONTROLLER
INSTALLATION
LON WIRING
The redundant controllers must be purchased
with the following options for correct installation:
• Either Ethernet or Serial Interface Board
• High-speed serial cable
• LON termination modules (2).
The LON must be connected to both redundant
controllers to ensure correct operation. Two
LON Termination Modules are required for the
installation as shown in Figure 3-15.
EQP
CONTROLLER
LON
TERMINATION
MODULE
A 53
3
A
6
B 52
2
B
5
ENCLOSURE REQUIREMENTS
S 51
1
S
4
The redundant controllers must be located
next to each other in the same enclosure (4 ft
interconnecting cable).
A 50
COM 2
COM 1
COM 2 TO
FIELD
DEVICES
B 49
S 48
MOUNTING
The controllers are designed for direct
panel mounting or DIN rail mounting. See
“Specifications” section of this manual for
mounting dimensions.
EQP
CONTROLLER
A 53
COM 2
WIRING
B 52
S 51
The redundant controllers are wired the same
as a simplex controller except for the LON
wiring and the dedicated high-speed serial
link, which are defined below. Refer to EQ3XXX
Controller Installation for general installation
details.
COM 1
LON
TERMINATION
MODULE
A 50
3
A
6
B 49
2
B
5
S 48
1
S
4
COM 1 TO
FIELD
DEVICES
C2274
NOTE:
LON TERMINATION JUMPERS P25 AND P26 (SEE FIGURE 3-12)
MUST BE IN POSITION 2 AND 3 FOR REDUNDANT CONFIGURATION
(ON BOTH CONTROLLERS).
Figure 3-15— LON Connection for Redundant EQP
Controllers
18.2
3-22
95-8533
HIGH SPEED SERIAL LINK (HSSL)
The redundant controllers are connected
together by a dedicated high-speed serial link.
This link is a pre-fabricated cable that has a
custom connector for ease of use. Redundant
controllers are automatically addressed with
the HSSL cable. One end of the cable is
labeled Primary. The primary controller takes
address 1, while the secondary controller is
address 2. The significance this has for the
user is that the primary is the default master
when both controllers are powered-up at the
same time.
CONFIGURATION
S³ Configuration
The S³ configuration software is used to
configure the redundant controllers. A check
box on the controller configuration screen must
be enabled and downloaded to the controllers.
IMPORTANT
If the controllers have not been
configured for redundancy via the S ³
configuration software, redundancy will
not function.
Controller Addresses
The LON addresses are pre-determined and
cannot be adjusted. Address 1 and 2 have
been reserved for a redundant controller
configuration.
RS-485/RS-232 (Port 1 through Port 4)
RS-485/RS-232 ports 1 through 4 on each
controller share the serial settings including
baud rate and address. Controllers in standby
mode don’t respond to or issue Modbus
RTU messages. This allows for transparent
switching on a multi-drop network. If RS-232
is used, a relay switching mechanism can be
used.
controller has the correct output information.
Information coming from the PLC should be
written to both Premier Controllers.
EtherNet DLR
The EtherNet DLR interface on each controller
will have a different address. This allows both
to reside on the same network at the same time.
The primary controller uses the configured
address while the standby assumes an
address 1 higher than the primary controller.
Application logic in the attached PLC must
be used to determine which controller has the
correct output information. Information coming
from the PLC should be written to both Premier
Controllers.
Ethernet
The Ethernet interface ports on each controller
will all have unique IP addresses. This allows
both controllers to reside on the same Ethernet
network at the same time. The primary and
secondary controller IP addresses for ports
3 and 4 are part of the configuration data.
During the configuration download, the primary
controller assigns the primary IP address to
itself and passes the secondary IP address
on to the secondary controller. Controllers
in standby mode do not respond to Modbus
TCP/IP messages. Ethernet applications need
to redirect to the alternate IP address when
controller switchovers occur.
EQ21XXPS SERIES
POWER SUPPLY AND
POWER SUPPLY MONITOR
INSTALLATION
WARNING
ALWAYS follow all safety notes and
instructions when installing power supply
or batteries!
ControlNet
WARNING
The ControlNet interface on each controller
will have a different address. This allows both
controllers to reside on the same ControlNet
network at the same time. The primary
controller uses the configured address while
the standby assumes an address 1 higher than
the primary controller. Application logic in the
attached PLC must be used to determine which
18.2
Make sure a.c. power is OFF at main a.c.
breaker before beginning power supply
installation!
IMPORTANT
Power supplies require unrestricted air
flow for proper cooling.
3-23
95-8533
MOUNTING
Mount the power supply monitor in a Nationally
Recognized Test Laboratory (NRTL) labeled
enclosure. Refer to the “Specifications” section
for mounting dimensions.
WIRING
CAUTION
The power supply should be properly
connected to an earth ground! A ground
wire MUST be connected to the power
supply units’s case ground!
4. Connect external wiring to the appropriate
points on Power Supply. Refer to Figure 3-18
for terminal block locations and Figures
3-19 and 3-20 for terminal identification.
Connect the 24 Vdc power wires and the
LON network cable to the appropriate points
on J1. (Redundant “+,” “–,” and shield
terminals are connected internally.) Do not
ground any shield at the monitor / power
distribution cabinet. Insulate the shields to
prevent shorting to the device housing or to
any other conductor.
5. Connect a two wire cable between the AC
input of the power supply and terminals 1
and 4 on J3, the AC input terminal block
on the power supply monitor. See Figure
3-20.
NOTE
The Power Supply Monitor uses two
of the four DIP switches to select an
appropriate fault level for the installation.
See Figure 3-18. The unit will fault when
the batteries source a current level
higher than the threshold for 20 seconds.
The fault will clear when the current
drops to half the level for 20 seconds. The
current level selection is based on the
minimum current draw of the attached
equipment. The selected value must be
less than the actual minimum current
draw for the system.
6. Connect the “B” terminal on the power
supply monitor to the negative (–) side of
the backup battery. Connect a correctly
sized circuit breaker in the battery circuit
as shown in Figure 3-21. The circuit breaker
must be rated between 130% and 250% of
the total load.
7. Connect the “C” terminal on the power
supply monitor to the negative (–) side of
the power supply.
1. Verify that the input source is the same
voltage and frequency as that marked on
the nameplate of the power supply.
2. Verify that transformer taps are set for the
correct a.c. input. (Input tap setting is located
inside the power supply enclosure.)
3. Verify that the supply power wire size and
fusing are adequate for the current indicated
on the power supply nameplate.
NOTE
8. Wire the power distribution circuit breakers
to the output of the power supply. Circuit
breaker ratings must be between 130% and
250% of the full load rating.
9. Set the device network address for the
power supply monitor.
NOTE
For additional information, refer to the
power supply manufacturer’s instruction
manual provided with the support
documentation received with the Eagle
Quantum Premier system.
STARTUP
Consult the power supply manufacturer’s
instruction manual provided with the
support documentation received with the
Eagle Quantum System.
Turn on the power supply and allow the voltage
to stabilize at 27 volts before closing the circuit
to the battery.
NOTE
Required Overload Current is usually
equal to 15% of the nominal rating.
18.2
3-24
95-8533
J1: POWER AND LON WIRING
LON ADDRESS SWITCHES
J3: AC INPUT
TERMINAL NO. 1
1
TERMINAL J2-1 TO
TERMINAL B
1
TERMINAL J2-2 TO
TERMINAL C
J2
SWITCH NO. 1
+ –
4
3
2
1
+
1
YELLOW LED
RED LED
TERMINAL NO. 1
GREEN LED
C1949
0.0005 OHM SHUNT
J2: BATTERY TEST POINTS
TERMINAL NO. 1
TERMINAL "C"
POWER SUPPLY MONITOR
PC BOARD ASSEMBLY
TERMINAL "B"
NOTE: J2 TERMINALS 3 AND 4 ARE CONNECTED TO J1 TERMINALS 7 AND 8 INTERNALLY
ON THE PC BOARD. J1 TERMINALS 7 AND 8 ARE ALSO CONNECTED TO THE
BATTERY CIRCUIT BREAKER VIA POWER DIST CKT.
ALARM CURRENT LEVEL SWITCH SETTINGS
ALARM LEVEL
1
2
3
4
200 mA
O
O
–
–
400 mA
X
O
–
–
800 mA
O
X
–
–
2 AMP
X
X
–
–
X = CLOSED
O = OPEN
Figure 3-16—Power Supply Monitor Terminal and Switch Location
MEASURING BATTERY VOLTAGE AND
CHARGING CURRENT
1
SHIELD
2
A
3
B
4
SHIELD
5
+
6
–
7
–
8
+
9
SHIELD
1
AC INPUT 120 / 240 VAC
10
A
2
NOT USED
11
B
3
NOT USED
12
SHIELD
4
AC INPUT 120 / 240 VAC
COM 1
Measure the battery voltage at terminals 3 and
4 of terminal block J2. See Figure 3-16 and
3-20.
To measure the battery charging current,
connect a digital voltmeter to terminals 1 and
2 of terminal block J2. The voltmeter will read
1 millivolt (0.001 volt) for each 2 amperes of
current.
24 VDC
Current in Amperes = Meter reading in millivolts
x2
Example: A reading of 50 millivolts indicates a
charging current of 100 amperes.
COM 2
A1947
A1950
Figure 3-17—J1: Power and LON Wiring Terminal
18.2
Figure 3-18—J3: AC Input Terminal
3-25
95-8533
POWER SUPPLY MONITOR
See Note 10
1
AC MONITOR
4
C
B
AC POWER
H
See Notes 1 & 3
N
–
–
+
+
12
11
10
9
8
7
6
5
4
3
2
1
TERMINAL J1
See Note 4
24 VDC
OUTPUT
G
+ POWER DIST CKT #1 –
+ POWER DIST CKT #2 –
+ POWER DIST CKT #3 –
AC BREAKER
DC BREAKER
See Note 3
EQ21XXPS POWER SUPPLY
(See Note 9)
NRTL DISTRIBUTION CABINET
See Note 2
See Note 6
+
–
+
–
12 VDC
E1951
+ POWER DIST CKT #4 –
BATTERY
CIRCUIT
BREAKER
12 VDC
BACKUP BATTERIES
NOTES
1. AC INPUT SELECTABLE (THROUGH THE OIS) FOR 120 / 208 / 240 VAC.
2. BATTERY SIZE CALCULATED BASED ON SYSTEM LOAD.
3. CIRCUIT BREAKER SHALL PROTECT AGAINST EXCESSIVE CURRENT LOAD.
4. REMOVAL OF TERMINAL PLUG WITH POWER APPLIED TO TERMINALS
B AND C WILL DAMAGE POWER SUPPLY MONITOR.
5. NRTL DISTRIBUTION CABINET IS KEY LOCKED ENCLOSURE.
6. DASH LINES DENOTE PROTECTION AGAINST PHYSICAL DAMAGE.
7. ANY PRIMARY AND SECONDARY POWER SUPPLY UNITS MAY BE INSTALLED
EXTERNALLY TO THE NRTL DISTRIBUTION CABINET, PROVIDED THEY ARE
PROTECTED AGAINST PHYSICAL DAMAGE. ALL DEDICATED BRANCH
CIRCUITS AND CONNECTIONS BETWEEN PRIMARY AND SECONDARY
POWER SUPPLY UNITS AND THE NTRL DISTRIBUTION CABINET SHALL ALSO
BE PROTECTED AGAINST PHYSICAL DAMAGE.
8. SUPERVISION (SINGLE OPENS & GROUNDS) OF THE INTERCONNECTIONS
BETWEEN POWER SUPPLY (24 VDC OUTPUT) TO NRTL DISTRIBUTION
CABINET AND BACKUP BATTERIES TO NRTL DISTRIBUTION CABINET IS
PERFORMED BY EQ2100PSM POWER SUPPLY MONITOR.
9. THE CIRCUIT DISCONNECTING MEANS (AC & DC BREAKERS) SHALL BE
ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL.
10. AC WIRING CABLE MUST BE ≤20 FEET IN CONDUIT.
Figure 3-19— Wiring Connections for a Power Supply Monitor, EQ21XXPS Series Power Supply and Backup Batteries
EQP2XX0PS(–X) POWER
SUPPLIES AND
REDUNDANCY MODULE
INSTALLATION
MOUNTING
Mount the power supply and Redundancy
Module in a Nationally Recognized Test
Laboratory (NRTL) labeled enclosure. Refer
to the “Specifications” section for mounting
dimensions. Refer to power supply and module
manufacturer's instruction manual provided
with support documentation received with the
EQP system for additional installation details
and instructions.
WARNING
ALWAYS follow all safety notes and
instructions when installing power supply
or module!
WIRING
WARNING
Make sure a.c. power is OFF at main a.c.
breaker before beginning power supply
installation!
CAUTION
The power supply should be properly
connected to an earth ground! A ground
wire MUST be connected to the power
supply units’s ground terminal!
IMPORTANT
Power supplies require unrestricted air
flow for proper cooling.
18.2
3-26
95-8533
1. Connect
external
wiring
to
the
appropriate points on Power Supplies.
Refer to
locations
NOTE
Contacts are closed during normal
operation. The circuit shall be wired to
an input on the EQP system (EDIO or
IDC). In Logic, the selected input must
be inverted and used to activate an
alarm trigger gate, which initiates a fault
message on the Controller and activates
the fault relay output.
Figure 3-23A for terminal
for
EQP21X0PS(-X).
Refer to Figure 3-23B for terminal
locations for EQP2410PS(-P) Converter.
Refer to Figure 3-23C for terminal locations
for EQP2120PS(-X) with EQP2410PS(-P)
Converter.
No supervision is necessary, since the
EDIO or IDC module must be installed in
the same cabinet with EQP21X0PS and
EQP2410PS.
2. Connect the 24 Vdc output to the
Redundancy Module. (Redundant “+” and
“–” power supply terminals are connected
internally.)
For USCG Approved System monitoring
details, refer to Appendix D.
3. To ensure compliance with NFPA 72,
primary and secondary power supplies
shall be monitored for the presence of
voltage at the point of connection to the
system. Connect the power supply unit for
preferred preventive function monitoring.
Refer to Figure 3-22 for an example of
power supply relays wired in series for
power monitoring.
1
CURRENT SENSE
+
2
CURRENT SENSE
–
3
BATTERY –
4
BATTERY +
Figure 3-20—J2: Battery Test Points
NRTL DISTRIBUTION CABINET
CB
PRIMARY POWER
See Notes 1 & 2
L
N
–
24 VDC
OUTPUT
G
–
+
+
EQP2120PS(-x) POWER SUPPLY
CB
SECONDARYPOWER
See Notes 1 & 2
L
N
G
–
–
24 VDC
OUTPUT
–
+
+
1
2
IN
OUT
+
EQP2120PS (-x) POWER SUPPLY
REDUNDANCY
MODULE
+
POWER DIST CKT #1
–
+
POWER DIST CKT #2
–
+
POWER DIST CKT #3
–
+
POWER DIST CKT #4
–
D2445
NOTES:
1. AC INPUT IS AUTO-SELECTABLE FOR 120–220 VAC, 60/50 Hz (CUSTOMER SUPPLIED).
2. PRIMARY SOURCE OF INPUT SUPPLY IS CONNECTED TO ONE POWER SUPPLY AND SECONDARY SOURCE IS
CONNECTED TO THE OTHER.
3. A MAXIMUM OF 8 REDUNDANT PAIRS CAN BE CONNECTED TO INPUT AC POWER.
4. THE SECONDARY SOURCE IS CONTINUOUSLY POWERED.
Figure 3-21A—Wiring Connections for a 20amp DC (Maximum) Power Supply with Primary and Secondary AC Sources
18.2
3-27
95-8533
NRTL DISTRIBUTION CABINET
CB
PRMARY POWER
–
L
See Notes 1 & 2
24 VDC
OUTPUT
N
–
+
G
+
EQP2120PS(-x) POWER SUPPLY
–
–
CB
SECONDARY POWER
24 VDC
OUTPUT
+
See Notes 2 & 4
–
–
1
+
+
OUT
IN
2
+
EQP2410PS(–P) CONVERTER
REDUNDANCY
MODULE
+
POWER DIST CKT #1
–
+
POWER DIST CKT #2
–
+
POWER DIST CKT #3
–
+
POWER DIST CKT #4
–
E2543
NOTES:
1. AC INPUT IS AUTO-SELECTABLE FOR 120–220 VAC, 60/50 Hz. BOTH AC AND DC INPUTS ARE CUSTOMER SUPPLIED.
2. PRIMARY SOURCE OF INPUT SUPPLY IS CONNECTED TO AC POWER SUPPLY AND SECONDARY SOURCE IS CONNECTED
TO DC CONVERTER.
3. A MAXIMUM OF 8 REDUNDANT PAIRS CAN BE CONNECTED TO INPUT AC/DC POWER.
4. THE SECONDARY SOURCE IS CONTINUOUSLY POWERED.
Figure 3-21B—Wiring Connections for a 10amp (Maximum) Power Supply with an AC Primary and DC Secondary Source
NRTL DISTRIBUTION CABINET
CB
PRIMARY POWER
–
L
See Notes 1 & 2
24 VDC
OUTPUT
N
–
1
+
G
OUT
IN
+
EQP2120PS(–X) POWER SUPPLY
REDUNDANCY
MODULE
–
–
CB
SECONDARY POWER
24 VDC
OUTPUT
+
See Notes 2 & 4
–
–
1
+
+
2
+
OUT
IN
+
EQP2410PS(–P) CONVERTER
REDUNDANCY
MODULE
–
24 VDC
OUTPUT
+
–
+ POWER DIST CKT #1
–
+ POWER DIST CKT #2
–
+ POWER DIST CKT #3
–
+ POWER DIST CKT #4
–
–
+
+
EQP2410PS(–P) CONVERTER
A2566
NOTES:
1. AC INPUT IS AUTO-SELECTABLE FOR 120–220 VAC, 60/50 Hz. BOTH AC AND DC INPUTS ARE CUSTOMER SUPPLIED.
2. PRIMARY SOURCE OF INPUT SUPPLY IS CONNECTED TO AC POWER SUPPLY AND SECONDARY SOURCE IS CONNECTED
TO DC CONVERTER.
3. A MAXIMUM OF 4 REDUNDANT PAIRS CAN BE CONNECTED TO INPUT AC/DC POWER.
4. THE SECONDARY SOURCE IS CONTINUOUSLY POWERED.
Figure 3-21C—Wiring Connections for a 20amp (Maximum) Power Supply with an AC Primary and DC Secondary Source
To EDIO or IDC
PS 1
L
PS
PHOENIX
–
QUINT-PS
–
N
L
PS
PHOENIX
–
QUINT-PS
–
N
+
13
14
DC
OK
+
L
PS n
PHOENIX
–
QUINT-PS
–
N
+
13
14
DC
OK
+
L
PHOENIX
QUINT-PS
N
14
DC
OK
+
–
+
+
13
–
13
14
DC
OK
+
D2438
Figure 3-22—Power Supply and Converter Relays Wired in Series for Trouble Monitoring (up to 16 Power Supplies/Converters)
18.2
3-28
95-8533
ENHANCED DISCRETE
INPUT/OUTPUT (EDIO)
MODULE INSTALLATION
NOTE
For additional information, refer to the
power supply manufacturer’s documents
provided with the support documentation
received with the Eagle Quantum
Premier system.
STARTUP
Turn on the power supply and allow the voltage
to stabilize. Verify the output voltage and adjust
as needed. Refer to "EQP2XX0PS(–X) Power
Supplies" in the Specifications section of this
manual.
IMPORTANT
The output voltage is adjustable. An even
current distribution must be ensured by
precisely setting all power supply units
that are operated in parallel to the same
output voltage ±10 mV.
All electrical connections are made to the field
wiring connectors furnished with the module.
Refer to Figure 3-23 for identification of module
wiring terminals.
Connector P1, Terminals 1 to 6
24 Vdc Power Input
Connect the module power supply to terminals
1 and 2. If additional terminals are required for
powering other devices, these devices should
be connected to terminals 4 and 5. Shields
are to be connected to terminals 3 and 6 —
chassis (earth) ground terminals. Total output
current should be limited to 10 amperes.
Connector P2, Terminals 1 to 6
LON/SLC Signaling Circuit Terminals
IMPORTANT
To e n s u r e sy m m e t r i c a l c u r r e n t
distribution it is recommended that all
cable connections from all power supply
units/diode redundancy modules to the
power distribution bus are the same
length and have the same cross section.
Be sure to observe polarity when wiring the
LON/SLC.
1 — "A" side of signaling circuit for COM 1
2 — "B" side of signaling circuit for COM 1
4 — "A" side of signaling circuit for COM 2
5 — "B" side of signaling circuit for COM 2
3, 6 — shield connection
EQ3730EDIO
COMMON C 24
CHANNEL 8
IN–/OUT+ B 23
LON FROM
PREVIOUS DEVICE
LON TO
NEXT DEVICE
SHLD
6 COM 2 SHLD
B
5 COM 2 B
A
4 COM 2 A
SHLD
+ SUPPLY A 22
2 COM 1 B
A
1 COM 1 A
CHANNEL 7
IN–/OUT+ B 20
3 COM 1 SHLD
B
CLASS A
CHANNEL 7
COMMON C 21
+ SUPPLY A 19
COMMON C 18
COM
CHANNEL 6
IN–/OUT+ B 17
+ SUPPLY A 16
CLASS A
CHANNEL 5
COMMON C 15
CHANNEL 5
IN–/OUT+ B 14
+ SUPPLY A 13
TO
EARTH
GROUND
COMMON C 12
CHANNEL 4
IN–/OUT+ B 11
+ SUPPLY A 10
CLASS A
CHANNEL 3
COMMON C 9
CHANNEL 3
IN–/OUT+ B 8
24 VDC
INPUT VOLTAGE
24 VDC
INPUT VOLTAGE
SHLD*
–
5 –
+
4 +
SHLD*
+ SUPPLY A 7
6 SHLD
COMMON C 6
–
2 –
+
1 +
CHANNEL 2
IN–/OUT+ B 5
3 SHLD
+ SUPPLY A 4
CLASS A
CHANNEL 1
COMMON C 3
POWER
CHANNEL 1
IN–/OUT+ B 2
+ SUPPLY A 1
* SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES.
A2287
Figure 3-23—EDIO Module Wiring Terminals
18.2
3-29
95-8533
Connector P3, Terminals 1 to 12
Terminals A,B & C
Channels 1 to 4 Input / Output Terminals
Refer to individual wiring configurations for
terminal descriptions. Only channel 1 is shown
in each diagram. The information is typical for
channels 2-8.
Connect external system wiring to the
appropriate terminals on the terminal block.
For Class B wiring, see Figure 3-27. For Class A
wiring, see Figure 3-28. Note that two channels
are used for one circuit when using Class A
wiring. Both wiring configurations provide
indication of open and short circuit fault.
COMMON C 3
Connector P4, Terminals 13 to 24
Terminals A, B & C
Channels 5 to 8 Input / Output Terminals
EOL
RESISTOR
10 K Ω
Refer to individual wiring configurations for
terminal descriptions. Only channel 1 is shown
in each diagram. The information is typical for
channels 2-8.
IN– / OUT+ B 2
+ SUPPLY A 1
C2091
Figure 3-25—Supervised Input Configuration – Class B
Unsupervised Input
COMMON C 6
Connect external system wiring to the
appropriate terminals on the terminal block.
See Figure 3-24.
IN– / OUT+ B 5
+ SUPPLY A 4
The input to the EDIO consists of one or more
normally open or normally closed switches. An
EOL resistor is not required.
COMMON C 3
EOL
RESISTOR
10 K Ω
Make no connection to “+ Supply” terminal.
IN– / OUT+ B 2
Supervised Input (IDC) Open Circuit
Supervision
+ SUPPLY A 1
B2291
Figure 3-26—Supervised Input Configuration – Class A
Connect external system wiring to the
appropriate terminals on the terminal block.
For Class B wiring, see Figure 3-25. For
Class A wiring, see Figure 3-26. Note that two
channels are used for one circuit when using
Class A wiring.
COMMON C 3
INLINE
RESISTOR
3.3 K Ω
EOL
RESISTOR
10 K Ω
IN– / OUT+ B 2
+ SUPPLY A 1
The input to the EDIO module consists of one
or more normally open switches, with a 10 K
ohm, 1/4 watt EOL resistor in parallel across
the last switch.
C2092
Figure 3-27—Supervised Input Configuration
for Opens and Shorts – Class B
COMMON C 6
Make no connection to “+ Supply” terminal.
Supervised Input Open and
Short Circuit Supervision
INLINE
RESISTOR
3.3 K Ω
IN– / OUT+ B 5
+ SUPPLY A 4
COMMON C 3
COMMON C 3
EOL
RESISTOR
10 K Ω
IN– / OUT+ B 2
IN– / OUT+ B 2
+ SUPPLY A 1
+ SUPPLY A 1
B2292
C2090
Figure 3-24—Unsupervised Input Configuration
18.2
3-30
Figure 3-28—Supervised Input Configuration
for Opens and Shorts – Class A
95-8533
The input to the EDIO module consists of
normally open switches, with a 10 K ohm, 1/4
watt EOL resistor in parallel across the return
channel, and a 3.3 K ohm, 1/4 watt resistor in
series with each switch.
IMPORTANT
No more than 15 devices can be
connected per channel.
Unsupervised Output
NOTE
Connect external system wiring to the
appropriate terminals on the terminal block.
See Figure 3-31.
If using more than one switch, the first
active condition (switch closed) must be
latched. Any subsequent closed switch
will indicate a short circuit fault condition.
No connection should be made to “+ Supply”
terminal.
Make no connection to “+ Supply” terminal.
Input — Deluge and Pre-Action
The initiating device circuit(s) for use with the
deluge and pre-action system configuration
must use Class A wiring or be wired within 20
feet and in conduit from the EDIO.
COMMON C 3
Two-Wire Smoke Detectors
The EDIO supports 2-wire devices from KiddeFenwal and Apollo. Figure 3-29 shows the
wiring for Apollo detectors connected to EDIO
Channel 1 through terminals 1 and 2.
IN– / OUT+ B 2
+ SUPPLY A 1
A2321
Figure 3-30 shows the typical wiring for KiddeFenwal detectors connected to the EDIO
through Channel 1 using terminals 1 and 2.
NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
TO BE INSTALLED ON THE FIELD DEVICE.
CIRCUIT PROTECTION IS PROVIDED
WITHIN THE EDIO MODULE.
The EDIO supports either brand of detection
products, however, mixing brands is not
supported on either a single channel or module.
Figure 3-31—Unsupervised Output Configuration
EDIO_IN +
End of
Line Device
EDIO_IN 2
2
1
6
3
1
4
6
5
2
3
1
4
6
5
3
4
5
B2283
Figure 3-29—Apollo 2-Wire Devices
+ SUPPLY A
1
1
2
1
2
1
3
7
18.2
IN–/OUT+ B
2
COMMON C
3
3
6
7
6
2
EOL
RESISTOR
5KΩ
7
3
6
A2284
UNUSED
Figure 3-30—Kidde-Fenwal 2-Wire Devices
3-31
95-8533
module. This type of output does not require
the use of EOL resistors or diodes to supervise
the circuit.
Supervised Output—
Notification Supervised for Open & Short
Circuits
Connect external system wiring to the
appropriate terminals on the terminal block.
For Class B wiring, refer to Figure 3-32.
For Class A wiring, refer to Figure 3-33. Note
that two channels are used for one output
circuit.
The output of the EDIO module supervises
the notification circuit by reversing the polarity
of the monitoring circuit. Polarity must be
observed when connecting the notification
device. It is essential to utilize a notification
device approved for fire alarm notification.
These devices are polarized and would not
require the use of an external diode for the
supervision of the circuit. Wire one or more
notification devices to the output, with a 10 K
ohm, 1/4 watt EOL resistor in parallel across
the last device.
The output can be configured for latching,
continuous, supervisory, trouble or timed
response.
To ensure adequate operating voltage for the
output device, the maximum wiring length from
the power source to the output device must
not exceed the values shown in Table 3-10 for
automatic release applications. (For solenoids,
COMMON C 3
EOL
RESISTOR
10 K Ω
IN– / OUT+ B 2
+ SUPPLY A 1
Figure 3-32—Supervised Output Configuration
(Notification)— Class B
No connection should be made to “+ Supply”
terminal.
COMMON C 6
Each output channel is individually activated
for response pattern:
––supervisory
––continuous output
––60 beats per minute
––20 beats per minute
––temporal
––timed
––trouble.
IN– / OUT+ B 5
+ SUPPLY A 4
COMMON C 3
EOL
RESISTOR
10 K Ω
IN– / OUT+ B 2
Supervised Output—
Agent Release (Solenoid Circuit)
+ SUPPLY A 1
A2285
Connect external system wiring to the
appropriate terminals on the terminal block.
For Class B wiring, refer to Figure 3-34.
Figure 3-33—Supervised Output Configuration
(Notification)— Class A
COMMON C 3
For Class A wiring, refer to Figure 3-35. Note
that two channels are used for one output
circuit. Trouble indication is provided for any
open wire and the output can still be activated
with a single open wire.
No connection should be made to “+ Supply”
terminal.
The output of the EDIO module supervises the
releasing circuit via the coil of the releasing
solenoid. It is essential to utilize a releasing
device approved for use with this output
18.2
3-32
IN– / OUT+ B 2
+ SUPPLY A 1
A2322
NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
TO BE INSTALLED ON THE FIELD DEVICE.
CIRCUIT PROTECTION IS PROVIDED
WITHIN THE EDIO MODULE.
Figure 3-34—Supervised Output Configuration
(Agent Release)
95-8533
this wire length includes both the wiring from
the power supply to the EDIO module and the
wiring from the module to the solenoid.)
Figure 3-35—Supervised Output Configuration (Agent
Release)— Class A Wiring
COMMON C 6
Supervised Output for Deluge
and Pre-action
IN– / OUT+ B 5
The maximum wiring length must not exceed
the values shown in Table 3-10 for deluge
and pre-action applications. Per FM Approval
requirements, the secondary power must
provide capacity for a 90 hour minimum
standby operation followed by a minimum of
10 minutes of releasing and alarm operation.
+ SUPPLY A 4
COMMON C 3
IN– / OUT+ B 2
The initiating device circuit(s) for use
with the deluge and pre-action system
configuration must use Class A wiring or
be wired in conduit within 20 feet from the
EDIO.
NOTE
In EQP systems with EQP2120PS(–B)
Power Supplies, the secondary power
is customer supplied and must be
accepted by the Authority Having
Jurisdiction (AHJ).
CONFIGURATION
B2286
NOTE: SHUNT/FLYBACK DIODES DO
NOT NEED TO BE INSTALLED
ON THE FIELD DEVICE.
CIRCUIT PROTECTION IS
PROVIDED WITHIN THE
EDIO MODULE.
8 CHANNEL DISCRETE
INPUT/OUTPUT (DCIO)
MODULE INSTALLATION
The following paragraphs describe how to
properly install and configure the 8 Channel
DCIO Module.
MOUNTING
Setting EDIO Network Address
One unique network address must be assigned
to each EDIO module. The address is set by the
8 switch DIP assembly on the EDIO module.
When using the switches located on the EDIO
module, the address is binary coded and is
the sum of all switches placed in the “closed”
position.
Each discrete point of an EDIO module has
a tag number and a descriptor for unique
identification. A tag number must include
zone designation, which will be shown on the
controller's display when the point is in alarm.
The DCIO must be properly installed in a
suitable enclosure that is rated for the location.
The enclosure must provide space to install and
wire the DCIO module and must also provide
for ground wire termination. Access into the
enclosure is gained by using a special tool to
open the enclosure. The enclosure should be
rated for the temperature range of the location
plus the temperature rise of all equipment
installed inside the enclosure. The enclosure
must be rated for electrical equipment that is
going to be installed.
The DCIO can be panel or DIN rail mounted.
Det-Tronics S³ Safety System Software is used
for device configuration. The following shows
the minimum software/firmware releases:
Controller Firmware
18.2
+ SUPPLY A 1
NOTE
It is recommended to maintain a
minimum of four inches clearance
b e t we e n t h e m o d u l e a n d o t h e r
equipment to provide adequate room for
wiring and ventilation.
S³
Revision
Version
Version
B
4.28
3.1.0.0
3-33
95-8533
Table 3-10—Typical Maximum Wire Length for FM Approved Solenoids for Deluge and Pre-Action Applications
Isol Table 3-10
Manufacturer
PN
Isol (mAdc) @ 20.4 Vdc
Parker (Viking)
11591 NC
365
Parker (Viking)
11592 NC
365
Parker (Viking)
71395SN2ENJ1NOH111C2
340
Parker (Viking)
73218BN4UNLVNOC111C2
320
Parker (Viking)
73212BN4TNLVNOC322C2
600
Parker (Viking)
73212BN4TN00N0C111C2
330
ASCO RedHat
R8210A107
525
ASCO RedHat
8210A107
555
ASCO RedHat
8210G207
365
ASCO RedHat
Cat#
11601
325
Viking PN
HV2740607 N.C.
Viking PN
HV274608 N.C.
ASCO RedHat
Cat #
310
11602
Kidde-Fenwal
897494
Cat #
202-749-260563
Kidde-Fenwal
895630
Cat #
1500
81-895630-000
Kidde-Fenwal
890181
Det-Tronics PN
1500
00219-209
Ansul
570537
Macron
130
200
304.209.001
*Note: Alternate secondary power source when accept by Local AHJ, may increase permissible wire voltage drops. Actual
secondary voltage must be determined. Voltage and current at solenoid must be known and used in the equation.
Supply
VLa
Voltage Drop
EDIO
VLb
Solenoid
Voltage Drop
The following is based on EQ21xxPS (Primary Source) and Battery (Secondary Source)
Total wire voltage drop = 1.2 Vdc (MAX) = VLa + VLb*
VLa = IEDIO x RLa
IEDIO = Total current of EDIO and all active outputs
VLb = Isol x RLb
Isol see Table 3-10
RLa & RLb = wire resistance = Ω per foot x 2 (x2 = B+ & B- wires)
Figure 3-36—Field Wiring Distance Requirements for Solenoids
WIRING
All electrical connections are made to the field
wiring connectors furnished with the module.
See Figure 3-37 for terminal identification.
Power Connector, Terminals 1 to 6
24 Vdc Power Input
Power connections to the DCIO depend upon
the total current consumption of all the channels
in the device. Each output-configured channel
can consume up to 2 amperes. Total output
current should be limited to 10 amperes.
18.2
3-34
Connect the power supply to terminals 1 and
2 or to terminals 4 and 5. Power wire shielding
should be connected to terminals 3 and 6.
1— +
2— –
3 — Shield*
4— +
5— –
6 — Shield*
*Shields on power wires are optional unless
required by local codes.
95-8533
EQ3700DCIO
COMMON C 24
CHANNEL 8
IN–/OUT+ B 23
LON FROM
PREVIOUS DEVICE
LON TO
NEXT DEVICE
SHLD
6 COM 2 SHLD
B
5 COM 2 B
A
4 COM 2 A
SHLD
COMMON C 21
3 COM 1 SHLD
B
2 COM 1 B
A
1 COM 1 A
+ SUPPLY A 22
CHANNEL 7
IN–/OUT+ B 20
+ SUPPLY A 19
COMMON C 18
COM
CHANNEL 6
IN–/OUT+ B 17
+ SUPPLY A 16
COMMON C 15
CHANNEL 5
IN–/OUT+ B 14
+ SUPPLY A 13
TO
EARTH
GROUND
COMMON C 12
CHANNEL 4
IN–/OUT+ B 11
+ SUPPLY A 10
COMMON C 9
CHANNEL 3
IN–/OUT+ B 8
24 VDC
INPUT VOLTAGE
24 VDC
INPUT VOLTAGE
SHLD*
6 SHLD
–
5 –
+
4 +
SHLD*
+ SUPPLY A 7
COMMON C 6
–
2 –
+
1 +
CHANNEL 2
IN–/OUT+ B 5
3 SHLD
+ SUPPLY A 4
COMMON C 3
POWER
CHANNEL 1
IN–/OUT+ B 2
+ SUPPLY A 1
* SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES.
B2097
Figure 3-37—DCIO Module Wiring Terminal Configuration
Connect the module power supply to terminals
1 and 2. If additional terminals are required for
powering other devices, these devices should
be connected to terminals 4 and 5. Shields are
to be connected to terminals 3 and 6.
Unsupervised Input
Connect external system wiring to
appropriate terminals. See Figure 3-38.
COM Connector, Terminals 1 to 6
LON Terminals
Be sure to observe polarity when wiring the
LON.
1 — "A" side of signaling circuit for COM 1
2 — "B" side of signaling circuit for COM 1
4 — "A" side of signaling circuit for COM 2
5 — "B" side of signaling circuit for COM 2
3 & 6 — shield connections.
COMMON C
3
IN– / OUT+ B
2
+ SUPPLY A
1
the
B2090
Figure 3-38—Unsupervised Input Configuration
Channel Connectors, Terminals 1 to 24
Terminals A, B & C
Channels 1 to 8 Input / Output Terminals
Refer to individual wiring configurations for
terminal descriptions. Only channel 1 is shown
in each diagram. The information is typical for
channels 2-8.
18.2
Input to the DCIO consists of one or more
normally open or normally closed switches.
NOTE
An EOL resistor is not required.
3-35
95-8533
The input to the DCIO module consists of a
normally open switch, with a 10 K ohm, 1/4
watt EOL resistor in parallel across the switch,
and a 3.3 K ohm, 1/4 watt resistor in series with
the switch.
NOTE
No connection should be made to the “+
Supply” terminal.
Supervised Input (IDC) Open Circuit
Supervision Class B
NOTE
Connect external system wiring to the
appropriate terminals on the DCIO terminal
block. See Figure 3-39.
No connection should be made to the “+
Supply” terminal. For correct operation,
only one input switch can be used per
channel.
Supervised Output Notification (Horns
and Strobes) Supervised Outputs for
Open & Short Circuits Class B
COMMON C 3
EOL
RESISTOR
10 K Ω
Connect external wiring to the appropriate
terminals on the DCIO terminal block. See
Figure 3-41.
IN– / OUT+ B 2
+ SUPPLY A 1
B2091
COMMON C 3
Figure 3-39—Supervised Input Configuration
The input to the DCIO module consists of one
or more normally open switches, with a 10K
ohm, 1/4 watt EOL resistor in parallel across
the last switch.
NOTE
EOL
RESISTOR
10 K Ω
IN– / OUT+ B 2
+ SUPPLY A 1
Figure 3-41—Supervised Output Configuration (Notification)
No connection should be made to the “+
Supply” terminal.
NOTE
Supervised Input (IDCSC) Open
and Short Circuit Supervision
(Three state – open, switch closure, and
short) Class B
Polarity MUST be observed when
connecting the notification device.
Connect external wiring to the appropriate
terminals on the DCIO terminal block. See
Figure 3-40. Indication of short circuit fault is
provided.
It is critical to use a notification device
approved for fire alarm notification. These
devices are polarized and do not require the
use of an external diode for the supervision
of the circuit. Wire one or more notification
devices to the output, with a 10 K ohm, 1/4 watt
EOL resistor in parallel across the last device.
NOTE
COMMON C 3
INLINE
RESISTOR
3.3 K Ω
No connection should be made to the “+
Supply” terminal.
EOL
RESISTOR
10 K Ω
IN– / OUT+ B 2
+ SUPPLY A 1
B2092
Figure 3-40—Supervised Input Configuration
(Opens and Shorts)
18.2
3-36
95-8533
Each output channel is individually activated
for response pattern:
– continuous output
– 60 beats per minute
– 120 beats per minute
– temporal
– supervisory
– timed
– trouble.
Supervised Output for Automatic Release
Supervised Output for Open Circuits
Connect external wiring to the appropriate
terminals on the DCIO terminal block. See
Figure 3-42.
NOTE
For solenoids, this wire length includes
both the wiring from the power supply to
the DCIO module and the wiring from the
module to the solenoid.
Supervised Output for Deluge and
Pre-action
Connect external wiring to the appropriate
terminals on the DCIO terminal block. See
Figure 3-42.
The output of the DCIO module supervises the
releasing circuit via the coil of the releasing
solenoid. It is essential to use a releasing
device approved for use with this output
module.
COMMON C 3
NOTE
This type of output does not require
the use of EOL resistors or diodes to
supervise the circuit.
IN– / OUT+ B 2
+ SUPPLY A 1
A2323
NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
TO BE INSTALLED ON THE FIELD DEVICE.
CIRCUIT PROTECTION IS PROVIDED
WITHIN THE DCIO.
NOTE
For new or retrofit installations, any
manufacturer’s non-water based agent
release valves can be wired into the
outputs of the DCIO modules as long
as the devices utilize 24 Vdc and do not
exceed 2 amperes current draw.
Figure 3-42—Supervised Output Configuration
(Automatic Release)
Wire one or more releasing devices to the
module output.
NOTE
NOTE
Make no connection to the “+ Supply”
terminal.
For FM system approval listing, preaction and deluge applications require
that only FM approved deluge valves
can be wired into the EDIO or DCIO
modules. Table 3-10 lists the supported
solenoid groups. Remember that the
valves must utilize 24 Vdc and must not
exceed 2 amperes current draw.
The output of the DCIO module supervises the
releasing circuit via the coil of the releasing
solenoid. It is essential to use a releasing device
approved for use with this output module.
NOTE
This type of output does not require
the use of EOL resistors or diodes to
supervise the circuit.
The output can be configured for latching,
continuous or timed response.
To ensure proper operating voltage, the maximum
wiring length from the power source to the DCIO
module must not exceed the values shown in
Table 3-10 for automatic release applications.
18.2
The output can be configured for latching,
continuous or timed response.
The maximum wiring length must not exceed
the values shown in Table 3-10 for deluge
and pre-action applications. Per FM Approval
requirements, the secondary power must
provide capacity for a 90 hour minimum
standby operation followed by a minimum of
10 minutes of releasing and alarm operation.
3-37
95-8533
For initiating device circuit(s) for use
with the deluge and pre-action system
configuration, an Enhanced Discrete Input/
Output Module (EDIO) must be used.
NOTE
In EQP systems with EQP2120PS(–B)
Power Supplies, the secondary power
is customer supplied and must be
accepted by the Authority Having
Jurisdiction (AHJ).
8 CHANNEL RELAY MODULE
INSTALLATION
The following paragraphs describe how to
properly install and configure the 8 Channel
Relay Module.
MOUNTING
Unsupervised Output Ancillary
Applications (Unrelated to Fire Detection/
Protection)
Connect external wiring to the appropriate
terminals on the DCIO terminal block. See
Figure 3-43.
COMMON C 3
The Relay Module must be properly installed
in a suitable enclosure that is rated for the
location. The enclosure must provide space
to install and wire the relay module and must
also provide for ground wire termination.
Access into the enclosure is gained by using
a special tool to open the enclosure. The
enclosure should be rated for the temperature
range of the location plus the temperature rise
of all equipment installed inside the enclosure.
The enclosure must be rated for electrical
equipment that is going to be installed. The
device can be panel or DIN rail mounted.
NOTE
It is recommended to maintain a
minimum of four inches clearance
b e t we e n t h e m o d u l e a n d o t h e r
equipment to provide adequate room for
wiring and ventilation.
IN– / OUT+ B 2
+ SUPPLY A 1
A2323
NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
TO BE INSTALLED ON THE FIELD DEVICE.
CIRCUIT PROTECTION IS PROVIDED
WITHIN THE DCIO.
Figure 3-43—Unsupervised Output Configuration
WIRING
NOTE
All electrical connections are made to the field
wiring connectors furnished with the module.
See Figure 3-45 for terminal identification.
No connection should be made to the “+
Supply” terminal.
CONFIGURATION
Power Connector, Terminals 1 to 6
24 Vdc Power Input
Setting DCIO Network Address
One unique network address must be assigned
to each DCIO module. The address is set
by the 8 switch DIP assembly on the DCIO
module. The address is binary coded and is
the sum of all switches placed in the “closed”
position.
Each discrete point of a DCIO module has
a tag number and a descriptor for unique
identification. A tag number must include
zone designation, which will be shown on the
controller's display when the point is in alarm.
Det-Tronics S³ Safety System Software is used
for device configuration. The following shows
the minimum software/firmware releases:
Controller Firmware
18.2
1— +
2— –
3 — Shield*
4— +
5— –
6 — Shield*
*Shields on power wires are optional unless
required by local codes.
Connect the module power supply to terminals
1 and 2. If additional terminals are required for
powering other devices, these devices should
be connected to terminals 4 and 5. Shields are
to be connected to terminals 3 and 6.
S³
Revision
Version
Version
A
1.03
2.0.2.0
3-38
95-8533
COM Connector, Terminals 1 to 6
LON Terminals
Each discrete point of a relay module has
a tag number and a descriptor for unique
identification.
Be sure to observe polarity when wiring the
LON.
1 — "A" side of signaling circuit for COM 1
2 — "B" side of signaling circuit for COM 1
4 — "A" side of signaling circuit for COM 2
5 — "B" side of signaling circuit for COM 2
3 & 6 — shield connections.
Det-Tronics S³ Safety System Software is used
for device configuration. The following shows
the minimum software/firmware releases:
Controller Firmware
Channel Connectors, Terminals 1 to 24
Unsupervised Output Ancillary Applications
(Unrelated to Fire Detection/Protection)
Connect external wiring to the appropriate
terminals on the relay module terminal block.
See Figure 3-44.
S³
Revision
Version
Version
A
2.01
2.0.8.0
ANALOG INPUT
INSTALLATION
MODULE
MOUNTING
CONFIGURATION
The Analog Input Module must be properly
installed in a suitable enclosure that is rated
for the location. The enclosure must provide
space to install and wire the device and must
also provide for ground wire termination.
Access into the enclosure must be gained by
using a special tool to open the enclosure.
Setting Relay Module Network Address
One unique network address must be assigned
to each relay module. The address is set by
the 8 switch DIP assembly on the relay module.
The address is binary coded and is the sum
of all switches placed in the “closed” position.
EQ3720RM
NC C 24
CHANNEL 8
NO B 23
LON FROM
PREVIOUS DEVICE
LON TO
NEXT DEVICE
SHLD
6
COM 2 SHLD
B
COMMON A 22
5
COM 2 B
A
4
COM 2 A
NC C 21
SHLD
3
COM 1 SHLD
NO B 20
B
2
COM 1 B
A
1
COM 1 A
CHANNEL 7
COMMON A 19
NC C 18
COM
CHANNEL 6
NO B 17
COMMON A 16
NC C 15
CHANNEL 5
NO B 14
COMMON A 13
TO
EARTH
GROUND
NC C 12
CHANNEL 4
NO B 11
COMMON A 10
NC C 9
CHANNEL 3
NO B 8
24 VDC
INPUT VOLTAGE
24 VDC
INPUT VOLTAGE
SHLD*
COMMON A 7
6
SHLD
–
5
–
NC C 6
+
4
+
NO B 5
3
SHLD
–
2
–
+
1
+
SHLD*
CHANNEL 2
COMMON A 4
NC C 3
POWER
CHANNEL 1
NO B 2
COMMON A 1
* SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES.
C2206
NOTE: RELAY CONTACTS SHOWN IN REST (DE-ENERGIZED) STATE.
Figure 3-44— Relay Module Wiring Terminal Configuration
18.2
3-39
95-8533
The enclosure should be rated for the
temperature range of the location plus the
temperature rise of all equipment installed
inside the enclosure. The enclosure must be
rated for electrical equipment that is going to
be installed.
NOTE
It is recommended to maintain a
minimum of four inches clearance
b e t we e n t h e m o d u l e a n d o t h e r
equipment to provide adequate room for
wiring and ventilation.
Power Connector — Terminals 1 to 6
24 Vdc Power Input
1— +
2— –
3 — Shield*
4— +
5— –
6 — Shield*
*Shields on power wires are optional unless
required by local codes.
WIRING
All electrical connections are made to the field
wiring connectors furnished with the module.
(Connectors accept up to 12 AWG wire.) Refer
to Figure 3-45 for identification of module
wiring terminals.
Connect the module power supply to terminals
1 and 2. If additional terminals are required for
powering other devices, these devices should
be connected to terminals 4 and 5. Shields are
to be connected to terminals 3 and 6.
EQ3710AIM
COMMON C 24
CHANNEL 8
4-20 MA IN B 23
LON FROM
PREVIOUS DEVICE
LON TO
NEXT DEVICE
SHLD
6
COM 2 SHLD
B
5
COM 2 B
A
4
COM 2 A
SHLD
3
COM 1 SHLD
B
2
COM 1 B
A
1
COM 1 A
COM
+ SUPPLY A 22
COMMON C 21
CHANNEL 7
4-20 MA IN B 20
+ SUPPLY A 19
COMMON C 18
CHANNEL 6
4-20 MA IN B 17
+ SUPPLY A 16
COMMON C 15
CHANNEL 5
4-20 MA IN B 14
+ SUPPLY A 13
TO
EARTH
GROUND
COMMON C 12
CHANNEL 4
4-20 MA IN B 11
+ SUPPLY A 10
COMMON C 9
CHANNEL 3
4-20 MA IN B 8
24 VDC
INPUT VOLTAGE
24 VDC
INPUT VOLTAGE
SHLD*
+ SUPPLY A 7
6
SHLD
–
5
–
COMMON C 6
+
4
+
4-20 MA IN B 5
3
SHLD
–
2
–
+
1
+
SHLD*
CHANNEL 2
+ SUPPLY A 4
COMMON C 3
POWER
CHANNEL 1
4-20 MA IN B 2
+ SUPPLY A 1
* SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES.
A2224
Figure 3-45—Analog Input Module Wiring Terminal Configuration
18.2
3-40
95-8533
COM Connector — Terminals 1 to 6
LON Terminals
CONFIGURATION
Be sure to observe polarity when wiring the
LON.
1 — "A" side of signaling circuit for COM 1
2 — "B" side of signaling circuit for COM 1
4 — "A" side of signaling circuit for COM 2
5 — "B" side of signaling circuit for COM 2
3 & 6 — shield connections (shields required).
Channel Connectors — Terminals 1 to 24
4-20 mA Input Devices
Connect external wiring to the appropriate
terminals on the analog input module terminal
block. See Figure 3-46 for an example of a
2-wire input. See Figure 3-47 for a 2-wire input
with HART interface module. See Figure 3-48
for a 3-wire input, where the transmitter must
source a 4-20 mA signal. See Figure 3-49 for a
3-wire input with HART interface module.
Setting Analog Input Module
Network Address
One unique network address must be assigned
to each analog input module. The address is
set by the 8 switch DIP assembly on the analog
input module.
When using the switches located on the analog
input module, the address is binary coded and
is the sum of all switches placed in the “closed”
position.
Each point of an analog input module has
a tag number and a descriptor for unique
identification. A tag number must include
zone designation, which will be shown on the
controller's display when the point is in alarm.
CHANNEL 1
Only channel 1 is shown in each diagram. The
information is typical for channels 2-8.
Analog Input Module Channels used
as NFPA 72 Approved 4-20 mA Flame
Detector Input
Configure the High Alarm setpoint at 19 mA via
the S³ configuration screen, and use the High
Alarm to trigger the Fire Alarm in S³ logic. The
AIM sends an exception message for the High
Alarm so there is no delay in transmitting the
Fire Alarm.
Fault indications and other status information
must be decoded in logic from the analog
process variable. A five second delay should
be used to avoid indicating an incorrect status
condition while the analog value is changing
between two values. See Table 3-11.
TRANSMITTER
COMMON C
3
4-20 MA IN B
2
SIG
+ SUPPLY A
1
+
A2235
Figure 3-46—Two-Wire Transmitter — Non-Isolated 4 to 20 mA
Current Output (Sourcing)
HIM
CHANNEL 1
COMMON C
3
6 COMMON
4-20 MA IN B
2
5 4-20 MA IN 2
3
+ SUPPLY A
1
4 + SUPPLY
TRANSMITTER
SIG
+
1
A2238
Figure 3-47—Two-Wire Transmitter with HART Interface
Module — Non-Isolated 4 to 20 mA Current Output (Sourcing)
TRANSMITTER
CHANNEL 1
COMMON C
3
–
4-20 MA IN B
2
SIG
+ SUPPLY A
1
+
A2236
Table 3-11—
Analog Values (in mA) for Fault and Status Indications when
the AIM is Used as a 4-20 mA Flame Detector Input
Status
X3301/2
X5200
X9800
X2200
Fault
0-3.5
0-3.5
0-3.5
0-3.5
IR Pre-Alarm
Figure 3-48—Three-Wire Transmitter — Non-Isolated 4 to 20
mA Current Output (Sourcing)
CHANNEL 1
7.0-9.0
UV Alarm
11.0-12.99
IR Alarm
13.0-14.99
Pre-Alarm
15.0-16.99 15.0-16.99 15.0-16.99
HIM
TRANSMITTER
COMMON C
3
6 COMMON
4-20 MA IN B
2
5 4-20 MA IN 2
+ SUPPLY A
1
4 + SUPPLY
3
1
–
SIG
+
A2239
Figure 3-49—Three-Wire Transmitter with HART Interface
Module — Non-Isolated 4 to 20 mA Current Output (Sourcing)
18.2
3-41
95-8533
Det-Tronics S³ Safety System Software is used
for device configuration. The following tables
show the minimum software/firmware releases:
For Gas Applications
Controller Firmware*
S³
AIM
Rev.
Version
Rev.
Version
Version
B
3.06
B
1.02
2.9.1.1
*for part number 007606-002
AIM
S³
NOTE
The use of the Sensor Separation Kit will
be required in some installations.
Rev.
Version
Rev.
Version
Version
C
5.52
D
1.07
4.0.0.0
ENVIRONMENTS AND SUBSTANCES
THAT AFFECT GAS DETECTOR
PERFORMANCE
*for part number 008983-001
GAS DETECTOR LOCATION
AND INSTALLATION
Gas detection devices must be properly
located to provide maximum protection.
Determining the proper number of devices and
placement varies depending on the specific
requirements of the area of protection.
The following should be considered when
locating a gas detection device:
1. Gas type. If it is lighter than air (acetylene,
hydrogen, methane, etc.), place the
sensor above the potential source. Place
the sensor close to the floor for gases that
are heavier than air (benzene, butane,
butylene, propane, hexane, pentane, etc.)
or for vapors resulting from flammable liquid
spills.
NOTE
Air currents can cause a gas that is
heavier than air to rise. Also, if the gas is
hotter than ambient air, it could also rise.
2. How rapidly will the gas diffuse into the air?
Select a location for the sensor as close as
possible to the anticipated source of a gas
leak.
18.2
4. Devices should be pointed down to prevent
the buildup of moisture or contaminants on
the filter.
5. Devices must be accessible for testing and
calibration.
For Flame Applications
Controller Firmware*
3. Ventilation characteristics. Air movement
will cause gas to accumulate more heavily
in one area than another. The devices
should be placed in areas where the
most concentrated accumulation of gas is
anticipated.
3-42
Catalytic sensors should be located where
they are safe from potential sources of
contamination that can cause a decrease in
the sensitivity of the device including:
A. Substances that can clog the pores of the
flame arrestor and reduce the gas diffusion
rate to the sensor including:
Dirt and oil, corrosive substances such as
Cl2 (Chlorine) or HCl, paint overspray, or
residue from cleaning solutions that can
clog the flame arrestor.
NOTE
A dust cover should be installed to
protect the flame arrester whenever
these conditions exist.
B. Substances that cover or tie up the active
sites on the catalytic surface of the active
sensing element such as volatile metal
organics, gases, or vapors of hydrides,
and volatile compounds containing
phosphorous, boron, silicone, etc.
Examples:
RTV silicone sealants
Silicone oils and greases
Tetraethyl lead
Phosphine
Diborane
Silane
Trimethyl chlorsilane
Hydrogen fluoride
Boron trifluoride
95-8533
Phosphate esters
replaced.
C. Materials that remove the catalytic metals
from the active element of the sensor. Some
substances react with the catalytic metal
forming a volatile compound that can erode
the metal from the surface of the sensor’s
active element.
Halogens and compounds containing
halogen are materials of this nature and
others include:
Examples:
Chlorine
Bromine
Iodine
Hydrogen Chloride, Bromide or Iodide
Organic halides:
Trichloroethylene
Dichlorobenzene
Vinyl chloride
Freons
Halon 1301
(Bromotrifluoromethane).
NOTE
Brief exposure to these materials can
temporarily increase sensor sensitivity
due to the surface of the active element
being etched. Prolonged exposure
continues this process until the sensitivity
of the sensor is degraded, resulting in
shortened sensor life.
D.
Exposure to high concentrations of
combustible gases for extended periods
of time can stress the sensing element and
seriously affect its performance.
The degree of damage to the sensor is
determined by a combination of contaminant
type, contaminant concentration in the
atmosphere, and the length of time the
sensor is exposed.
NOTE
A combination of accessories such
as rain shields and dust covers is not
recommended and can result in slow
response to a gas leak.
EQ22XXDCU DIGITAL COMMUNICATION
UNIT USED WITH DET-TRONICS
H2S/O2 SENSORS OR OTHER
TWO-WIRE 4-20 MA DEVICES
Determine the best mounting locations for
the detectors. Whenever practical, detectors
should be placed where they are easily
accessible for calibration.
WARNING
Do not apply power to the system with
the cover removed unless the area has
been verified to be free of combustible
gases or vapors.
The DCU utilizes the following:
1. A terminal wiring board mounted at the
bottom of the junction box.
2. A communication module mounted above
the terminal wiring board using the standoffs
provided. See Figure 3-50.
Assembly and Wiring Procedure
Attach the sensor to the DCU enclosure. Do not
over-tighten. If a sensor separation kit is being
used, attach the sensor to the separation kit
junction box and wire the device as described
in the “Sensor Separation” section.
CAUTION
NOTE
If a sensor has been exposed to
a contaminant or a high level of
combustible gas, it should be calibrated
at the time of exposure. An additional
calibration a few days later should
be performed to determine whether
a significant shift in sensitivity has
occurred. If necessary, sensor should be
18.2
The sensor threads can be coated
with an appropriate grease to ease
installation. Also lubricate the cover
threads. (See “Ordering Information” for
part number of recommended lubricant.)
Connect the external wiring to the appropriate
terminals on the DCU terminal wiring board.
Refer to Figure 3-51 for terminal identification.
3-43
95-8533
POINTWATCH CALIBRATE
1
4 TO 20 MA IN
2
–
3
+
4
A
5
B
6
COMMUNICATION
MODULE
SENSOR POWER
COM 2
STANDOFFS (4)
TERMINAL
WIRING BOARD
7
14
–
8
13
–
A
9
12
+
B
10
11
+
COM SHIELD
24 VDC
A1571
COM 1
Figure 3-50—Printed Circuit Boards in Universal DCU
A1726
See Figure 3-52 for an example of a Det-Tronics
electrochemical sensor connected to a DCU.
Attach the communication module to the
standoffs as shown in Figure 3-48. Connect the
ribbon cable from the terminal wiring board to
the communication module.
Set the address for the device. Refer to
“Setting Device Network Addresses” for
complete information regarding the switch
setting procedure.
Check the wiring to ensure proper connections,
then pour the conduit seals and allow them to
dry (if conduit is being used).
Figure 3-51—Wiring Configuration for DCU
DCU
H2S/TOXIC/O2
POINTWATCH CALIBRATE
1
4 TO 20 MA IN
2
BLACK
–
3
RED
+
4
GREEN
A
5
B
6
SENSOR POWER
COM 2
7
14
–
8
13
–
A
9
12
+
B
10
11
+
COM SHIELD
NOTE
24 VDC
Before placing the cover back on the
enclosure following completion of
assembly and wiring, inspect the
enclosure O-ring to be sure that it is in
good condition and properly installed.
Lubricate the O-ring and the threads
of the cover with a thin coat of an
appropriate grease to ease installation.
Refer to the “Ordering Information”
section for the part number of the
recommended grease (available from
Detector Electronics). If the installation
uses catalytic type combustible gas
sensors, it is imperative that lubricants
containing silicone not be used, since
they will cause irreversible damage to the
sensor. Place the cover on the enclosure.
Tighten only until snug. Do not over
tighten.
18.2
COM 1
Figure 3-52—Electrochemical Sensor Connected to DCU
Table 3-12
Maximum Separation Distances —
Electrochemical Sensor to DCU
Wire Size
Maximum Wiring Distance
(AWG)
Feet
Meters
18
16
5700
9000
1750
2800
T0020A
3-44
95-8533
Sensor Separation for DCU with H2S
and O2 Sensors
Since the transmitter for the electrochemical
sensor is already mounted within the sensor
housing, simply mount the entire sensor
assembly to the sensor separation kit junction
box and wire it to terminals 2 and 4 inside the
DCU, the same as a regular (without sensor
separation) installation. Connect the shield to
the ground terminal in the DCU junction box.
Refer to Table 3-12 for separation distance
limitations for H2S and O2 sensors
EQ22XXDCU DIGITAL COMMUNICATION UNIT USED WITH POINTWATCH/
DUCTWATCH
Determine the best mounting location for the
detector. Whenever practical, detectors should
be placed where they are easily accessible for
calibration.
WARNING
Do not apply power to the system with
the cover removed unless the area has
been verified to be free of combustible
gases and vapors.
The DCU utilizes the following:
1. A terminal wiring board mounted at the
bottom of the junction box.
DCU
POINTWATCH
POINTWATCH CALIBRATE
1
YELLOW
4 TO 20 MA IN
2
WHITE
–
3
BLACK
+
4
RED
A
5
GREEN
B
6
SENSOR POWER
2. A communication module mounted above
the terminal wiring board using the standoffs
provided. See Figure 3-50.
Assembly and Wiring Procedure
Attach the PointWatch/DuctWatch to the DCU
enclosure. Do not over-tighten. If a sensor
separation kit is being used, attach the sensor
to the separation kit junction box and wire the
device as described in the “Sensor Separation”
section.
Refer to the PointWatch instruction manual
(form number 95-8440) or the DuctWatch
instruction manual (form number 95-8573)
for complete installation and application
information.
Refer to Figure 3-53 when wiring a PointWatch
IR gas detector and a DCU. The wiring code
for PointWatch is:
Red =
Black =
White =
Yellow =
Green =
+ (24 Vdc)
– (common)
4 to 20 mA signal
Calibration input
Chassis ground
Set the address for the device. Refer to
“Setting Device Network Addresses” for
complete information regarding the switch
setting procedure.
Sensor Separation for DCU
with PointWatch
Shielded four wire cable is recommended for
connecting the detector junction box to the
DCU. Cable with a foil shield is recommended.
The shield of the cable should be open at the
detector junction box and connected to earth
ground at the DCU junction box.
NOTE
COM 2
7
14
–
8
13
–
A
9
12
+
B
10
11
+
To ensure proper operation, it is
essential to maintain a minimum of 18
Vdc (including ripple) at the PointWatch
detector.
COM SHIELD
24 VDC
COM 1
Figure 3-53—PointWatch/DuctWatch Connected to DCU
18.2
3-45
95-8533
EQ22XXDCUEX DIGITAL COMMUNICATION UNIT (USED WITH DET-TRONICS
COMBUSTIBLE GAS SENSORS)
DCU TRANSMITTER BOARD1
(MIDDLE BOARD)
DCU TERMINAL BOARD
POINTWATCH CALIBRATE
1
4 TO 20 MA IN
2
–
3
+
4
A
5
B
6
Mounting
Determine the best mounting location for the
device. Whenever practical, the device should
be placed where it can easily be reached for
calibration.
2
2
SENSOR POWER
IMPORTANT
SIG
–
2
+
COM 2
Always orient the junction box with the
sensor pointing down.
7
14
–
8
13
–
A
9
12
+
B
10
11
+
COM SHIELD
WARNING
24 VDC
Do not apply power to the system with
the cover removed unless the area has
been verified to be free of combustible
gases or vapors.
COM 1
B1877
NOTES: 1 Catalytic Combustible Gas Sensor
Plugs into Connector Pins on the
Middle Board inside the Junction Box.
Wiring
2 Connections Wired at the Factory.
1. Remove the cover from the DCUEX.
Figure 3-54—DCU Transmitter Board Connected
to Terminal Wiring Board
CAUTION
ALWAYS discharge static from tools and
hands by touching the device body
before touching the communication
module or transmitter board.
NOTE
2. Loosen the screws on the communication
module and remove it from the transmitter
board standoffs.
3. Disconnect the ribbon cable from the
communication module.
4. Remove the standoffs and detach the
transmitter board from the terminal wiring
board. Do not disconnect any wiring.
5. Connect all external wiring to the terminal
wiring board. (See Figure 3-54.)
NOTE
Make sure the ribbon cable is connected
to the terminal wiring board.
6. Attach the sensor to the device enclosure.
DO NOT overtighten.
If a sensor separation kit is being used,
attach the sensor to the separation kit
junction box. (See Sensor Separation
with DCUEX below.)
7. Plug the sensor into P2 on the transmitter
board.
8. Mount the transmitter board to the
terminal wiring board and attach with the
standoffs.
NOTE
Be sure to note the correct orientation of
the transmitter board. If the transmitter
board is rotated 180° from proper
orientation, the device will not operate
correctly — a LON communication fault
will result. See Figure 3-57.
9. Plug the ribbon cable into the
communication module and re-attach it to
the transmitter board.
10. Set the device network address. (See
“Setting Device Network Addresses” in
this section.)
18.2
3-46
95-8533
11. Inspect the junction box O-ring to be sure
that it is in good condition. Lubricate the
O-ring and the threads of the junction
box cover with a thin coat of silicone-free
grease (available from Det-Tronics).
12. Replace the device cover.
Sensor Separation with DCUEX
6. Inspect the O-ring on the DCU and
separation junction box to be sure that
they are in good condition. Lubricate the
O-ring and the threads of the junction box
cover with a thin coat of silicone-free grease
(available from Det-Tronics).
7. Replace the cover on the DCU and
separation junction box.
COMMUNICATION MODULE
If the installation requires mounting the sensor
in a different location than the DCUEX, observe
the following guidelines.
SWITCHES ON SAME SIDE
(RIGHT)
There are two methods that can be used to
separate the sensor from the DCUEX:
TRANSMITTER BOARD
Preferred Method
1. Disassemble the DCUEX and remove
the transmitter board. (Refer to “Wiring”
for disassembly procedure.) Do not reassemble at this time.
TERMINAL WIRING BOARD
CORRECT ORIENTATION OF TRANSMITTER BOARD
2. Mount the transmitter board inside the
sensor separation junction box (remove the
existing board).
COMMUNICATION MODULE
G
N
O
R
W
NOTE
This assembly can be separated from
the DCUEX by up to 1000 feet using
three conductor 18 AWG shielded cable.
(Regardless of separation distance,
operating voltage at the transmitter must
be at least 18 Vdc for proper device
operation.) (See Figure 3-56.)
SWITCHES ON OPPOSITE SIDES
(WRONG)
TRANSMITTER BOARD
TERMINAL WIRING BOARD
3. Mount the sensor to the separation junction
box. DO NOT overtighten. Plug the sensor
into P2 on the transmitter board.
INCORRECT ORIENTATION OF TRANSMITTER BOARD
4. Use a three conductor 18 AWG shielded
cable to connect P1 on the transmitter
board to terminals 2, 3 and 4 on the DCU
terminal board (See Figure 3-56). Connect
the shield to the ground terminal in the
DCUEX junction box.
COMMUNICATION MODULE
5. Connect all external wiring to the terminal
wiring board inside the DCU (if not already
completed). Re-assemble the DCUEX as
described in the “Wiring” section. When
completed, it should look similar to the DCU
as shown in Figure 3-50.
TRANSMITTER BOARD
STANDOFFS (4)
TERMINAL WIRING BOARD
B1570
Figure 3-55—Printed Circuit Boards in Combustible Gas DCU
18.2
3-47
95-8533
Alternate Method
If the transmitter board must be mounted
separate from the sensor (high temperature
applications, etc.), separate the sensor only,
leaving the transmitter PC board inside the
DCUEX enclosure. When using this installation
option, see Table 3-13 for maximum wiring
distances.
Mount the sensor directly to the separation kit
junction box. Use three conductor shielded
cable for the connection between the terminal
block in the separation kit junction box and P2
on the DCUEX transmitter board.
A plug with screw terminals is provided for
connecting the cable to P2 on the transmitter
board. Observe the wiring color code. Connect
the shield to the ground terminal in the DCUEX
junction box.
TYPICAL APPLICATIONS
Figure 3-57 is a simplified drawing of a
typical EQP system. This system includes an
EQP Controller, DCIO and various LON field
devices.
Table 3-13—Maximum Separation Distances —
Combustible Gas Sensor to DCU (Alternate Method)
+
–
Maximum Separation
Distance
N
GR
Wire Size
Feet
Meters
18 AWG (1.0 mm2)*
40
12
16 AWG (1.5 mm2)*
60
18
14 AWG (2.5 mm2)*
100
30
12 AWG (4.0 mm2)*
150
45
+
–
N
GR
ELECTROCHEMICAL SENSOR
*Approximate Metric Equivalent.
CHASSIS
SPARE
CAL
4-20
4-20
RET
RET
+24
+24
GND
CAL
DCU TERMINAL BOARD
POINTWATCH
1
POINTWATCH CALIBRATE
2
4 TO 20 MA IN
3
–
4
+
P1
SENSOR POWER
SIG
–
+
TRANSMITTER BOARD
4 TO 20
A
5
B
6
COM 2
–
+
7
14
–
8
13
–
A
9
12
+
B
10
11
+
COM SHIELD
P2
NOTE: ALWAYS ORIENT
JUNCTION BOX WITH
CATALYTIC SENSOR
POINTING DOWN.
24 VDC
COM 1
SENSOR
C1878
CATALYTIC SENSOR
Figure 3-56—Sensor Separation Kits
18.2
3-48
95-8533
18.2
RXD 2
GND 5
DB-9
CONNECTION
TO COM PORT
OF PC
TXD 3
53
P6
50
49
48
P8
NC 47
FAULT NO 46
3-49
C 36
RELAY 1
C 39
RELAY 2
C 42
30 C
RELAY 3
32 NC
NC 44
NO 43
RELAY 7
31 NO
NC 41
NO 40
29 NC
RELAY 6
28 NO
NC 38
27 C
26 NC
RELAY 5
NO 37
THE DEVICE’S CHASSIS GROUND
TERMINAL SHOULD BE
CONNECTED TO EARTH GROUND.
VALID FOR AIM, RM, EDIO.
SEE INDIVIDUAL DEVICE FOR
CHANNEL TERMINALS.
* LON AND POWER TERMINALS ALSO
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
+
–
24 VDC
BATTERY
H
N
AC LINE
24 VDC
SUPPLY
–
+
CH 4
25 NO
NC 35
24 C
23 NC
NO 34
DIGITAL INPUTS
22 NO
P5
C 33
CH 7
21 C
8– 20
8+ 19
7– 18
7+ 17
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
P3
1
CH 3
P4
12 4–
11 4+
10 3–
6– 16
6+ 15
CH 6
9 3+
8 2–
7 2+
4
2
3
CH 2
5– 14
P3
5+ 13
A
5
A + SUPPLY A
B
6
P4
1
2
3
COM1
SHIELD
P2
24 VDC +
4
COM2
24 VDC –
5
P1
SHIELD
6
EQ3700DCIO*
CH 1
6 1–
5 1+
B 55
A 56
CH 5
P2
59 TxD
58 RxD
57 GND GND 54
P9
A
52
C 45
B
51
COM1
SHIELD
P7
1
24 VDC +
3
COM2
2
24 VDC –
4
P1
CONTROLLER
+
+
–
–
POWER
–
–
+ DISTRIBUTION +
+
–
+ –
+ –
24 VDC +
5
SHIELD
B
A
12
11
10
2
B
H
5
8
7
SHIELD
B
A
12
11
10
2
3
1
COM1
24 VDC +
6
COM2
SHIELD
24 VDC –
4
9
AC LINE
N
EQ24xxNE
4
3
P3
1
2
3
1
SHUNT
C
8
7
9
COM1
24 VDC –
6
COM2
SHIELD
4
EQ2100PSM
CH 8
RELAY 8
RELAY 4
95-8533
9
10
5
6
7
SHIELD
A
B
2
7
8
9
COM1
24 VDC +
1
3
5
4
6
– 4
+
4
SENSOR
POWER
– 2
+ 1
9
10
+ 3
A
B
8
COM1
SHIELD
3
5
6
7
COM2
11 24 VDC + 12
13 24 VDC – 14
EQ25xxARM
A
B
SHIELD
COM1
2
CALIBRATE 13
10
11
12
SHIELD
24 VDC –
15
14
16
COM2
12 24 VDC + 2
–
G2100
5
4
6
5
4
PIRECL
COM2
A
B
6
COM1
SHIELD
3
4 TO 20 MA IN
9
10
15
14
16
COM2
12 24 VDC + 2
SHIELD
11 24 VDC – 1
13
1
A
B
8
COM1
SHIELD
3
POINTWATCH
CALIBRATE
COM2
11 24 VDC + 12
13 24 VDC – 14
EQ22xxDCU
CIRCUIT 2 – 4
CIRCUIT 2 + 3
CIRCUIT 1 – 2
CIRCUIT 1 + 1
A
B
8
COM1
SHIELD
SHIELD
11 24 VDC – 1
13
Figure 3-57—A Typical System
5
6
7
COM2
11 24 VDC + 12
13 24 VDC – 14
EQ2200IDC
X3301 / X5200 / X2200 / X9800
Flame Detectors
4
4
5
6
2
1
B
A
SHIELD
A
5
9
10
OUTPUT 2 – 4
OUTPUT 2 + 3
OUTPUT 1 – 2
OUTPUT 1 + 1
B
6
8
A
B
6
5
8
CALIBRATE 9
16
15
SHIELD
COM1
COM2
SHIELD
7
17
COM2
COM1
13 24 VDC + 12
2
14
11 24 VDC + 12
24 VDC –
3
4
LS2000
RECEIVER
13 24 VDC – 14
EQ25xxSAM
3
SHIELD
COM1
5
24 VDC +
P2
6
P1
SHIELD
24 VDC –
COM2
1
2
3
EQ3720RM
SINGLE SOLENOID
DUAL SOLENOIDS
SYSTEM CONFIGURATION
SETTING DEVICE NETWORK
ADDRESSES
Overview of Network Addresses
Each device on the LON must be assigned a
unique address. Addresses 1 to 4 are reserved
for the controller. Valid addresses for field
devices are from 5 to 250.
Figure 3-58—Field Device Address Switches for
ARM, SAM, DCU and IDC
IMPORTANT
If the address is set to zero or an
address above 250, the communication
module will ignore the switch setting.
Duplicated addresses are not automatically
detected. Modules given the same address
will use the number given and report to the
controller using that address. A "Rogue
Device" message will be displayed when
two LON devices have duplicate addresses
assigned to them. The status word will show
the latest update, which could be from any of
the reporting modules using that address.
Figure 3-59—Address Switch for DCIO and Relay Module
Setting Field Device Addresses
Selection of the node address for field devices
is done by setting rocker switches on an
8 switch “DIP Switch” within each device’s
housing.
NOTE
Only the first eight of the 12 switches are
used for selecting the device address.
The address number is binary encoded with
each switch having a specific binary value with
switch 1 being the LSB (Least Significant Bit).
(See Figure 3-58) The device’s LON address is
equal to the added value of all closed rocker
switches. All “Open” switches are ignored.
NOTE
The field device sets the LON address
only when power is applied to the
device. Therefore, it is important to set
the switches before applying power. If an
address is ever changed, system power
must be cycled before the new address
will take effect.
After setting address switches, record the
address number and device type on the
“Address Identification Chart” provided with
this manual. Post the chart in a convenient
location near the Controller for future reference.
NOTE
The address switches in the DCIO
module and relay module appear slightly
different than those in other devices.
Refer to Figure 3-59.
Example: for node No. 5, close rocker switches
1 and 3 (binary values 1 + 4); for node No. 25,
close rocker switches 1, 4 and 5 (binary values
1 + 8 + 16).
18.2
3-50
95-8533
Rocker Switch Table
Node
Rocker Switch
Address 1 2 3 4 5 6 7 8
Node
Rocker Switch
Address 1 2 3 4 5 6 7 8
1
2
3
4
5
6
7
8
9
10
X O O O O O O O
O X O O O O O O
X X O O O O O O
O O X O O O O O
X O X O O O O O
O X X O O O O O
X X X O O O O O
O O O X O O O O
X O O X O O O O
O X O X O O O O
61
62
63
64
65
66
67
68
69
70
X O X X X X O O
O X X X X X O O
X X X X X X O O
O O O O O O X O
X O O O O O X O
O X O O O O X O
X X O O O O X O
O O X O O O X O
X O X O O O X O
O X X O O O X O
11
12
13
14
15
16
17
18
19
20
X X O X O O O O
O O X X O O O O
X O X X O O O O
O X X X O O O O
X X X X O O O O
O O O O X O O O
X O O O X O O O
O X O O X O O O
X X O O X O O O
O O X O X O O O
71
72
73
74
75
76
77
78
79
80
X X X O O O X O
O O O X O O X O
X O O X O O X O
O X O X O O X O
X X O X O O X O
O O X X O O X O
X O X X O O X O
O X X X O O X O
X X X X O O X O
O O O O X O X O
21
22
23
24
25
26
27
28
29
30
X O X O X O O O
O X X O X O O O
X X X O X O O O
O O O X X O O O
X O O X X O O O
O X O X X O O O
X X O X X O O O
O O X X X O O O
X O X X X O O O
O X X X X O O O
81
82
83
84
85
86
87
88
89
90
X O O O X O X O
O X O O X O X O
X X O O X O X O
O O X O X O X O
X O X O X O X O
O X X O X O X O
X X X O X O X O
O O O X X O X O
X O O X X O X O
O X O X X O X O
31
32
33
34
35
36
37
38
39
40
X X X X X O O O
O O O O O X O O
X O O O O X O O
O X O O O X O O
X X O O O X O O
O O X O O X O O
X O X O O X O O
O X X O O X O O
X X X O O X O O
O O O X O X O O
91
92
93
94
95
96
97
98
99
100
X X O X X O X O
O O X X X O X O
X O X X X O X O
O X X X X O X O
X X X X X O X O
O O O O O X X O
X O O O O X X O
O X O O O X X O
X X O O O X X O
O O X O O X X O
41
42
43
44
45
46
47
48
49
50
X O O X O X O O
O X O X O X O O
X X O X O X O O
O O X X O X O O
X O X X O X O O
O X X X O X O O
X X X X O X O O
O O O O X X O O
X O O O X X O O
O X O O X X O O
101
102
103
104
105
106
107
108
109
110
X O X O O X X O
O X X O O X X O
X X X O O X X O
O O O X O X X O
X O O X O X X O
O X O X O X X O
X X O X O X X O
O O X X O X X O
X O X X O X X O
O X X X O X X O
51
52
53
54
55
56
57
58
59
60
X X O O X X O O
O O X O X X O O
X O X O X X O O
O X X O X X O O
X X X O X X O O
O O O X X X O O
X O O X X X O O
O X O X X X O O
X X O X X X O O
O O X X X X O O
111
112
113
114
115
116
117
118
119
120
X X X X O X X O
O O O O X X X O
X O O O X X X O
O X O O X X X O
X X O O X X X O
O O X O X X X O
X O X O X X X O
O X X O X X X O
X X X O X X X O
O O O X X X X O
18.2
3-51
95-8533
Rocker Switch Table
Node
Rocker Switch
Address 1 2 3 4 5 6 7 8
Node
Rocker Switch
Address 1 2 3 4 5 6 7 8
121
122
123
124
125
126
127
128
129
130
X O O X X X X O
O X O X X X X O
X X O X X X X O
O O X X X X X O
X O X X X X X O
O X X X X X X O
X X X X X X X O
O O O O O O O X
X O O O O O O X
O X O O O O O X
191
192
193
194
195
196
197
198
199
200
X X X X X X O X
O O O O O O X X
X O O O O O X X
O X O O O O X X
X X O O O O X X
O O X O O O X X
X O X O O O X X
O X X O O O X X
X X X O O O X X
O O O X O O X X
131
132
133
134
135
136
137
138
139
140
X X O O O O O X
O O X O O O O X
X O X O O O O X
O X X O O O O X
X X X O O O O X
O O O X O O O X
X O O X O O O X
O X O X O O O X
X X O X O O O X
O O X X O O O X
201
202
203
204
205
206
207
208
209
210
X O O X O O X X
O X O X O O X X
X X O X O O X X
O O X X O O X X
X O X X O O X X
O X X X O O X X
X X X X O O X X
O O O O X O X X
X O O O X O X X
O X O O X O X X
141
142
143
144
145
146
147
148
149
150
X O X X O O O X
O X X X O O O X
X X X X O O O X
O O O O X O O X
X O O O X O O X
O X O O X O O X
X X O O X O O X
O O X O X O O X
X O X O X O O X
O X X O X O O X
211
212
213
214
215
216
217
218
219
220
X X O O X O X X
O O X O X O X X
X O X O X O X X
O X X O X O X X
X X X O X O X X
O O O X X O X X
X O O X X O X X
O X O X X O X X
X X O X X O X X
O O X X X O X X
151
152
153
154
155
156
157
158
159
160
X X X O X O O X
O O O X X O O X
X O O X X O O X
O X O X X O O X
X X O X X O O X
O O X X X O O X
X O X X X O O X
O X X X X O O X
X X X X X O O X
O O O O O X O X
221
222
223
224
225
226
227
228
229
230
X O X X X O X X
O X X X X O X X
X X X X X O X X
O O O O O X X X
X O O O O X X X
O X O O O X X X
X X O O O X X X
O O X O O X X X
X O X O O X X X
O X X O O X X X
161
162
163
164
165
166
167
168
169
170
X O O O O X O X
O X O O O X O X
X X O O O X O X
O O X O O X O X
X O X O O X O X
O X X O O X O X
X X X O O X O X
O O O X O X O X
X O O X O X O X
O X O X O X O X
231
232
233
234
235
236
237
238
239
240
X X X O O X X X
O O O X O X X X
X O O X O X X X
O X O X O X X X
X X O X O X X X
O O X X O X X X
X O X X O X X X
O X X X O X X X
X X X X O X X X
O O O O X X X X
171
172
173
174
175
176
177
178
179
180
X X O X O X O X
O O X X O X O X
X O X X O X O X
O X X X O X O X
X X X X O X O X
O O O O X X O X
X O O O X X O X
O X O O X X O X
X X O O X X O X
O O X O X X O X
241
242
243
244
245
246
247
248
249
250
X O O O X X X X
O X O O X X X X
X X O O X X X X
O O X O X X X X
X O X O X X X X
O X X O X X X X
X X X O X X X X
O O O X X X X X
X O O X X X X X
O X O X X X X X
181
182
183
184
185
186
187
188
189
190
X O X O X X O X
O X X O X X O X
X X X O X X O X
O O O X X X O X
X O O X X X O X
O X O X X X O X
X X O X X X O X
O O X X X X O X
X O X X X X O X
O X X X X X O X
18.2
3-52
95-8533
Section 4
Operation
Enter chooses the menu item selected, and
advances the menu to the next options list.
(See “Controller Menu Options“ in this section
for additional information.)
SYSTEM CONTROLLER
NOTE
PUSHBUTTONS
Pressing Enter while alarms are actively
scrolling returns the display to the Main
Menu.
The Controller has seven pushbuttons (located
on the front panel) for user interface. These
pushbuttons allow the operator to interact with
the Controller to respond to alarms and system
status conditions, access system status
reports, and configure Controller time and date
settings.
Next allows the operator to scroll through
options listed within each menu. Each time
the NEXT pushbutton is pushed, the current
options list indexes up one list item. (See
“Controller Menu Options” in this section for
additional information)
The following paragraphs describe the function
of each pushbutton. Refer to Figure 4-1 for
Controller pushbutton locations.
Previous allows the operator to scroll through
options listed within each menu. Each time the
PREVIOUS pushbutton is pushed, the current
options list indexes down one list item. (See
“Controller Menu Options” in this section for
additional information)
Cancel cancels the selected command,
and returns the menu to the last option list
displayed.
Reset resets all controller latched outputs that
are no longer active.
Acknowledge silences the internal beeper.
Silence turns on the Silence LED and sets
Silence status in user logic.
DET-TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Cancel
Enter
Next
Enter
Next
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Previous
Previous
Reset
Power
Acknowledge Silence
Reset
Acknowledge Silence
Figure 4-1—EQP Controller Pushbutton Locations
18.2
4-1
95-8533
CONTROLLER STATUS INDICATORS
CONTROLLER MENU OPTIONS
System status is visually displayed on the
Controller in two ways — through the use of
a Text Display (see Figure 4-2), and through
colored LED’s (see Table 4-1). The following
paragraphs describe these indicators and the
function of each.
The Controller is designed to display system
status and device related information. The
following paragraphs describe how to move
around within the controller’s menu structure
to access this information and perform minor
system settings (see Figure 4-3).
TEXT DISPLAY
NOTE
The Controller uses a text based display to
show current system status, active Alarms and
Faults.
During normal operation (no alarms or
trouble conditions occurring), the display
scrolls current system time and date.
When an alarm or trouble condition occurs,
the display scrolls a detailed message of the
condition, including tag number, condition
(alarm, trouble, supervisory etc.) and time/
date. If multiple alarms or trouble conditions
exist, the display scrolls through all active
status conditions until they go inactive and are
reset using the controller pushbutton.
Main Menu displays a list of options to access
information types available for display through
the Controller. This list also includes access to
options used to set system date and time, and
diagnostics options.
DET-TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Enter
Next
Previous
Eagle Quantum Premier
Time & Date
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
Power
Acknowledge Silence
Fire Alarm
Trouble
Inhibit
Power
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Figure 4-2—EQP Controller Message Display and System Status Indicator Location
Table 4-1—EQP Controller LED System Status Indicators
LED
Green
Red
Amber
Amber
Amber
Amber
Amber
Red
Red
Amber
Amber
Amber
18.2
Function
Power
Fire Alarm
Trouble
Ack
Silence
Inhibit
Out Inhibit
High Gas
Low Gas
Supr
LON Fault
Contrl Fault
Status
On when power is applied.
On (latched) when any fire alarm is active (Fire detected).
On (latched) when a fault is detected in the system. (Indicates "Trouble" relay state.)
On when the Acknowledge button is pressed.
On when Silence pushbutton is pressed.
On when any input channel is inhibited.
On when any output is inhibited.
On (latched) when any gas detector is at or above the High gas alarm value.
On (latched) when any gas detector is at or above the Low gas alarm value.
On (latched) when any Supervisory input is active.
On when a LON fault is detected (open or short).
On when a processor fault occurs.
4-2
95-8533
Marque Display
Alarm
Display Current Time/Date
(no active alarms)
Cancel
Reset
Enter
Next
Prev
Enter / Cancel
Display Alarms Screen
Display Alarms
Enter
Next
Prev
Display Alarms
Display Devices*
Device Tagname
Add: xxx Device Type
Fault/ No Fault
Device dependent info
Main Menu
Next
Previous
Display Alarms
Display Devices
Device Tagnames
Set Time & Date
Communication Ports
Diagnostics
Redundancy Info
User Logic
Auto Scrolling Alarm
Screen
Fire Alarms
Gas Alarms
Trouble
Supervisory
Inhibits
Output Inhibits
User Events
All Alarms
Pressing the ack
switch acknowledges
the visible alarm.
Current
Input State
Device Tagnames*
Enter
Cancel
Alarm Type
Off/On
Tag Name
Alarm Description
Time and Date
ack
Tag Name for Device n
Tag Name for Device n
Tag Name for Device n
Set Time and Date
Visible if the
alarm was
acknowledged
Next and Previous buttons are used to scroll the lists.
The Enter button is used to navigate to the next level.
The Cancel button is used to back out a level.
Edit Time/Date
Communication Ports*
Configuration Port
Serial Port 1
Serial Port 2
Serial Port 3
Serial Port 4
Redundancy Port
Ethernet Port 3
Ethernet Port 4
LON 1
LON 2
Redundancy Info
Diagnostics
Lamp Test – Enter
Display: Traditional
HW Version: X
Extra Device: 0
Watchdog Count: 0
SRR0 = XXXXXXXX
Run Time = 66 Hrs
CNET Rev = 002.000
CNET Error Code = 0
OSC Value = XXXXXXX
SIL: False
Reduced Nodes: False
HW Option Board: 3
OS 0000
DR 0000
LLF = False (6) Sec
Rx 0 0
Fault: No Fault
Lst Flt: Cntr LON
Cntr Mode: Master
My Config: Primary
Mem Tx: 304 ms
Mem Blk: 9 of 200
HSSL Status: Good
Version Match: Good
SIL Constant: Good
Reduced Node: Good
Parser: Good
Comm Ack: Good
Cntr LON: Good
Msg Error: Good
--Master Errors-Program Flow: Good
LON A Inf: Good
LON B Inf: Good
User Logic CS: Good
User Logic: Good
Config: Good
Dead LON: Good
Cntrl Fault: Good
--Standby Errors-Program Flow: Good
LON A Inf: Good
LON B Inf: Good
User Logic CS: Good
User Logic: Good
Config: Good
Dead LON: Good
Cntrl Fault: Good
Power 1: Good
Power 2: Good
Option Bd: Good
RTC: Good
LON Gnd: Good
LON Fault: Good
RS485 Gnd Flt: Good
Comm Bd: Good
Rx State: Good
My State: Sending
User Logic
General Info
Program Memory
View Time
Figure 4-3—EQP Controller Message Display Menu Outline
18.2
4-3
95-8533
Pressing the NEXT or PREVIOUS pushbuttons
allows cycling through devices. Pressing the
CANCEL pushbutton will return the display to
the Main Menu.
Main Menu
>Display Alarms
Display Devices
Device Tagnames
Moving within the Main Menu is done by using
the NEXT or PREVIOUS pushbuttons located
on the controller’s front panel. The menu
options will scroll upward (NEXT Pushbutton)
or downward (Previous Pushbutton) while the
Main Menu name remains stationary. When
the desired menu option is selected by the “>”
indicator, the ENTER pushbutton is pressed
to advance the menu display to the desired
information set.
NOTE
Pressing the CANCEL pushbutton from
within any sub-menu returns the display
to the Main Menu. The display will also
return to the Main Menu if left unattended
for a period of 20 minutes. If an alarm
or trouble condition is present after 20
minutes, the display will change to the
existing Alarm or Trouble message.
Device Tagnames
Controller
Z398-80 X
Pressing the NEXT or PREVIOUS pushbutton
allows cycling through devices. Pressing the
CANCEL pushbutton will return the display to
the Main Menu.
SET TIME AND DATE provides access to
configuration controls for system clock and
date settings.
Set Time & Date
DISPLAY ALARMS displays a list of existing
Alarms and Trouble conditions. Moving within
this menu is done by using the NEXT or
PREVIOUS pushbuttons.
Alarm Type
Tag Name
Alarm Description
Time & Date
DEVICE TAG NAMES displays device tag
name information for all devices on the LON
loop.
11:20:52
Jul 29 / 2002
NOTE
When the Set Time and Date menu
opens, the current hour will flash.
Off/On
ack
NOTE
Multiple alarm information can be viewed
by pressing the NEXT or PREVIOUS
pushbuttons. Pressing CANCEL will
return the menu to the DISPL AY
ALARMS menu.
DISPLAY
DEVICES
displays
device
information on all devices on the LON loop.
Device tag name, type, and node address are
displayed.
To move within this menu, press the ENTER
pushbutton until the desired property is
flashing. To set the desired property value,
press the NEXT Pushbutton to increase or
PREVIOUS Pushbutton to decrease the value.
When the desired value is displayed, press the
ENTER pushbutton. This will advance the menu
to the next property and it will flash. When all
desired properties have been entered, press
the ENTER pushbutton until the message
“Press ENTER to Save” is displayed. When
the ENTER pushbutton is pressed, the settings
are saved and the menu changes back to the
MAIN MENU.
Z398-63 U / I
Add:63 UV / IR Detect
No Fault
18.2
4-4
95-8533
SERIAL PORTS displays port information on
all available ports.
Serial Ports
Configuration Port
Serial Port 1
Serial Port 2
Pressing the NEXT or PREVIOUS pushbutton
allows cycling through ports. Pressing the
CANCEL pushbutton will return the display to
the Main Menu.
DIAGNOSTICS displays information for factory
field service.
Diagnostics
Lamp Test -EnterDisplay: Traditional
HW Version: 2
REDUNDANCY INFO displays the current
status of all redundancy related faults. It can
be used to monitor the health of the master
and standby controllers. It can also be used
for diagnostic purposes.
Redundancy faults originate from three general
areas:
• Self detected internal failures of the master
controller
• Inter-controller communications
• A failure in the standby controller.
Any redundancy fault is annunciated by the
master controller, and the redundancy fault
code of the highest priority fault is displayed.
The controller also provides a diagnostic menu
for more detailed information on the source
of a redundancy problem. All redundancy
related faults must be cleared to insure proper
redundancy operation.
Fault
Displays the current redundancy fault.
Lst Flt
Displays the last redundancy fault that
occurred.
18.2
Cntr Mode
Indicates whether the controller is in master or
standby mode.
My Config
Indicates whether the controller is the primary
or secondary controller.
Redun Mem
Displays how long it takes to transfer the local
and global memory between controllers.
HSSL Status
An error is generated when a problem is
detected on the high-speed communication link
between controllers. This fault is annunciated
when the standby controller is offline.
Version Match
To ensure proper redundant operation, the
firmware versions of redundant controllers
must match. This error is set when a mismatch
is detected. Consult the factory for firmware
upgrades.
SIL Rating
To ensure proper redundant operation, the SIL
rating of redundant controllers must match. An
error is indicated if a SIL controller is paired
with a non‑SIL rated controller. Consult the
factory for details.
Parser
As the master controller configures a standby
controller, configuration information is extracted
from non-volatile memory and checked for
errors.
Comm Ack
Critical information is exchanged between
controllers on the HSSL using acknowledged
messages. The master sends data packets that
contain an embedded CRC and a transaction
number. The standby validates the message
by calculating and comparing the CRC values.
If the CRC is correct the standby saves the data
and returns an acknowledge message with
the transaction number. If an acknowledge
message with the proper transaction number
is not received by the master within the allotted
time the message is resent. When all retries
are used the acknowledge error is indicted and
acknowledged communication is terminated.
4-5
95-8533
Lon Comm
Table 4-2—EQP Controller Alarm Tone Patterns
Redundant controllers exchange information
across the LON network. This is primarily done
to prevent both controllers from becoming the
master in the event that the HSSL fails. The fault
is annunciated when a controller fails to receive
any information from the other controller.
Priority
Controller Tone
Tone Pattern
1
Fire Alarm
Temporal
2
Supervisory
Supervisory
3
Trouble
Trouble
4
High Gas
Gas
Msg Error
5
Low Gas
Gas
If the standby controller receives a message
from the master that has the correct CRC but
invalid data an error message is returned. This
master will indicate the error with this fault.
6
Normal
Off
Program Flow
Program flow checking ensures that essential
functions execute in the correct sequence.
If any functions don’t execute properly, or
execute in the wrong order, the program flow
error is set and control is transferred to the
standby controller.
LON A/B Inf
Controllers utilize neuron co-processors to
interface with the field device network. If an
error is detected in the operation of the coprocessor, a LON interface fault is annunciated.
User Logic CS
Controllers continually conduct a checksum
test of the user logic program to ensure that the
data remains unchanged. A user checksum
fault is annunciated if the result is incorrect.
App CS
When the controller firmware is generated a
checksum of the program is calculated and
saved in memory. Each controller is continually
conducting a checksum test of the program to
ensure that the data remains unchanged. The
application checksum fault is annunciated if
the result is incorrect.
Power 1
Displays the power 1 status on the standby
controller.
Power 2
Displays the power 2 status on the standby
controller.
Option Bd
Indicates whether there is a fault on the
ControlNet or EtherNet DLR option board of the
standby controller.
CONTROLLER AUDIBLE ALARM
The Controller features an internal audible
alarm for local system status notification (see
Table 4-2 and Figure 4-4). When the system
is operating in the normal mode (no Alarm or
Fault conditions occurring), the alarm is silent
(off). If an event (any alarm or trouble condition)
occurs, the alarm will remain active until it is
acknowledged by pressing the Acknowledge
pushbutton or reset by pressing the Reset
pushbutton on the Controller front panel.
NOTE
If multiple alarms exist, “Acknowledging”
will silence the audible alarms.
0.5 SEC
1.5 SEC
FIRE
ALARM
0.1 SEC
User Logic
0.1 SEC
2.0 SEC
Many checks are conducted while the controller
interprets and executes the user program. The
user logic error is generated if invalid or out of
range data is detected.
SUPERVISORY
0.5 SEC
5.0 SEC
TROUBLE
Config
0.5 SEC
This fault is annunciated when a controller
has not been configured or the configuration
information has been corrupted.
18.2
0.5 SEC
4-6
0.5 SEC
3.0 SEC
HIGH/LOW
GAS
B1855
Figure 4-4—Tone Pattern for Controller Buzzer
95-8533
Table 4-3—Status of ControlNet LED Indicators
A and B
Cause
Action
Off
No power
None or power up.
Steady red
Faulted unit
Cycle power. If fault persists, contact
the factory.
Alternating red/green
Self-test
None
Alternating red/off
Incorrect node configuration
Check network address and other
ControlNet configuration parameters.
A or B
Cause
Action
Off
Channel disabled
Program network for redundant media,
if required.
Steady green
Normal operation
None
Flashing green/off
Temporary errors
None; unit will self-correct.
Listen only
Cycle power.
Flashing red/off
Media fault
Check media for broken cables, loose
connectors,missing terminators, etc.
No other nodes present on network
Add other nodes to the network.
Flashing red/green
Incorrect network configuration
Cycle power or reset unit. If fault
persists, contact the factory.
CONTROLNET STATUS INDICATORS
(Optional)
The optional ControlNet status indicator LEDs
function as follows: (see Table 4-3)
Module Status
Steady - The indicator is on continuously in the
defined state.
Network Status
Link Status 1
Alternating - The two indicators alternate
between the two defined states at the same
time (applies to both indicators viewed
together). The two indicators are always in
opposite states, out of phase.
Module Status
Network Status
Link Status 1
Link Status 2
1
DET-TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
2
Eagle Quantum Premier
Link Status 2
Fire Alarm
Time & Date
Cancel
Enter
Next
Previous
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Reset
Power
Acknowledge Silence
Figure 4-5—Location of EtherNet DLR Status LEDs
Flashing - The indicator alternates between
the two defined states (applies to each
indicator viewed independent of the other). If
both indicators are flashing, they must flash
together, in phase.
Table 4-4—EtherNet DLR Module Status LED
ETHERNET DLR STATUS INDICATORS
(Optional)
LED State
Description
Off
No power.
The EtherNet DLR has 4 status indicators:
Module Status, Network Status, Link Status 1
and Link Status 2. See Figure 4-5 for location.
The status indicator LEDs function as defined
in Tables 4-4 through 4-6. A test sequence is
performed on the Network Status and Module
Status LEDs during startup.
Green
Controlled by a Scanner in
Run state.
Green, flashing
Not configured, or Scanner in
idle state.
Red
Major fault (EXCEPTION state,
FATAL error, etc.)
Red, flashing
Recoverable fault(s)
18.2
4-7
95-8533
Table 4-5—EtherNet DLR Network Status LED
Table 4-6—EtherNet DLR Link Status 1 and Link Status 2 LEDs
LED State
Description
LED State
Description
Off
No power or no IP address.
Off
No link, no activity.
Green
Online, one or more
connections established (CIP
Class 1 or 3).
Green
Link (100 Mbit/s) established.
Green, flickering
Activity (100 Mbit/s)
Yellow
Link (10 Mbit/s) established.
Yellow, flickering
Activity (10 Mbit/s)
Green, flashing
Online, no connections
established.
Red
Duplicate IP address, FATAL
error.
Red, flashing
One or More connections
timed out (CIP Class 1 or 3).
SEQUENCE OF EVENTS DURING A
CONFIGURATION DATA DOWNLOAD
During a configuration download, the controller
receives configuration data that is stored into
flash memory. During the download process,
the controller halts normal operation and
resets a number of controller functions. Items
affected and displayed during a configuration
data download are listed in the following steps:
c) "Writing to Flash" indicates that
configuration data stored in memory is
being written down into Flash memory.
d) "Flash Lock" indicates that the controller
is locking the configuration data into the
Flash memory.
CAUTION
1. Halt the static logic and user logic
programs.
The controller’s configuration data will
be corrupted if power is removed during
a download. Contact the factory if this
occurs.
2. Ignore field device LON communications.
However, the controller continues to
generate the LON heartbeat.
11. Initialize the RS-485 and configuration
serial ports with new parameters.
3. Silence
the
annunciator.
audible
12. Initialize the ControlNet or EtherNet DLR
option board with new parameters.
4. Initiate a Trouble condition that is signaled
by the amber Trouble LED and relay.
13. Enable static logic and user logic programs to
operate. The first scan program is run first.
5. Clear all Alarm and Fault events.
14. Accept field device LON communications.
6. De-energize all 8 Controller relays.
15. Poll the device type variable from LON field
devices.
Controller’s
7. Ignore Modbus communication.
8. ControlNet communication continues.
EtherNet DLR communication goes
through reset and configuration. DLR
communication remains offline during this
sequence (approximately 30 seconds).
16. Configure LON field devices.
17. Clear the Trouble condition.
18. Text display shows a normal operation
marquee message.
9. Text display’s first line indicates "***
Program Mode ***"
a) Text display’s first line indicates "DetTronics Eagle Quantum Premier."
10. Text display’s third line displays download
status.
b) Text display’s third line displays time
(24 hour format) and date (month/day/
year).
a) "Config Download" indicates the serial
transfer into memory from the PC to the
Controller.
b) "Erasing Flash" indicates that the
controller is electronically erasing the
contents of the Flash memory.
18.2
NOTE
Depending on the condition of the LON
devices, faults may persist for a number
of minutes.
4-8
95-8533
CONTROLLER REDUNDANCY
Pushbuttons
The pushbuttons are active on the master
controller and inactive on the standby
controller.
Controller Status Indicators
The status indicators are active on the master
controller. All LEDs except the power LED are
off and the trouble relay is in the no trouble
state.
5. The controller that is connected with the
secondary end of the HSSL is assigned
address 2.
6. If there are no faults present, the primary
controller defaults to the master controller
and the secondary controller defaults to
the standby controller.
7. The master controller executes user logic
and communicates with the connected
LON devices.
Controller Relay Operation
8. The standby controller indicates that it is
in standby mode and monitors the master
controller.
The controller relays are fully functional on the
master controller and the standby controller.
9. The master and standby controller go
through a synchronization process.
10. The power-up sequence is complete.
Text Display
The text display on the master controller is fully
functional as explained in the previous section.
The text display on the standby controller
reads **Standby Mode**, Ready.
Controller Menu Options
Synchronization
When a master controller detects a standby
controller on the HSSL, it performs the following
synchronization process:
The menu options are active on the master
controller and inactive on the standby
controller.
1. Compare controller firmware versions and
SIL rating. If they are not an exact match,
the process stops and a fault is generated.
Consult the factory for details.
ControlNet or EtherNet DLR Status
Indicators
2. Standby
controller
synchronization steps.
The ControlNet or EtherNet DLR status
indicators are active on the master and
standby controller. See Table 4-3 for status
of ControlNet LED indicators and Tables 4-4
through 4-6 for EtherNet DLR LED indicators.
3. Compare the user application programs.
If there is a mis-match, the master will
configure the standby controller via the
HSSL.
Power-up Sequence
5. Transfer the status of device inhibits and
device removes.
The power-up sequence for a redundant
controller pair is as follows:
1. Make sure the LON and HSSL are
connected correctly.
2. Apply power to both controllers.
3. Controllers
routine.
go
through
their
boot-up
indicates
the
4. Initiate the data synchronization process.
6. Transfer the complete alarm list, including
alarm history.
7. Transfer the real time clock (RTC) value.
8. Copy the local and global memory to the
standby controller.
9. Synchronization is complete and
standby controller indicates “Ready.”
the
4. The controller that is connected with the
primary end of the HSSL is identified as the
primary controller and is assigned address
1.
18.2
4-9
95-8533
5. The controller indicates “Device Download
Active” until the LON devices have been
successfully updated.
Sequence of Events During a
Configuration Download
WARNING
Automatic Switchover
The system is inactive and not executing
logic/alarm functions during a program
download (in both single and redundant
controller configurations).
When downloading a new configuration to the
master controller, the following sequence is
executed:
1. The S³ software must be connected to the
master controller.
2. Alter the configuration and execute the
download command from S³.
3. The master controller goes into ‘Program’
mode and passes mastership to the
standby controller.
4. The updated configuration file is loaded into
the controller.
5. The controllers are automatically forced to
switch over.
6. The master controller puts the standby
controller into ‘Program’ mode and
downloads the configuration.
7. The controller indicates “Device Download
Active” until the LON devices have been
successfully updated.
8. The configuration
complete.
download
is
now
An automatic transfer will be initiated if the
master controller goes into an error (self
detected internal controller failure, program
flow error in the controller, user logic checksum
error or application checksum error). An
automatic switchover executes the following
sequence:
1. Check that the standby controller is online
by verifying that HSSL communication is
good and there are no internal faults in the
standby controller.
2. Verify that the synchronization process is
complete.
3. The master requests the standby to take
control.
4. The standby takes control and becomes the
master.
Replacing a Faulty Controller
If the master controller fails and the standby
controller is healthy, an automatic switchover
will occur. To replace the failed controller,
perform the following steps:
1. Remove power. Disconnect plugs and
remove the failed controller.
2. Mount the new controller.
Manual Switchover
3. Connect the LON to the new controller.
The user can request a manual switchover
from an externally wired switch. The request
executes the following sequence:
4. Connect the HSSL.
1. Verify that HSSL communication is good and
there are no internal faults in the standby
controller.
7. A controller synchronization occurs and the
new controller is configured and indicates
“Ready” as the standby controller.
2. Verify that the synchronization process is
complete.
8. If preferred, perform a manual switchover to
return the primary controller to the master
status.
3. The master requests the standby to take
control.
5. Connect any other I/O used.
6. Apply power to the controller.
4. The standby takes control and becomes the
master.
18.2
4-10
95-8533
ENHANCED DISCRETE I/O
MODULE
STATUS INDICATOR LEDs
The EDIO Module (see Figure 4-6) has 18 LED
status indicators, two for the device and two
for each channel, located on the front panel.
Refer to Tables 4-7 and 4-8 for a description of
the LED indicators.
POWER-UP SEQUENCE
Figure 4-6—EDIO Module Status Indicator Location
Set the module address switch prior to applying
power.
EDIO module power-up sequence illuminates
the LEDs for the device and all of its channels.
First the power and fault LEDs are illuminated,
indicating that the device is in a power-up
mode. Next the LEDs are illuminated in the
following sequences:
Table 4-7—EDIO Module - Device Status Indicators
• Sequentially each channel active red LED
is illuminated, starting with channel 1 and
continuing through channel 8.
• When the red LED for channel 8 is
illuminated, sequentially each channel
active red LED is turned off, starting with
channel 1 and continuing through channel
8.
• Next, the channel fault amber LEDs are
tested in the same manner as the channel
active red LEDs.
LED
Device Status
Green
On when power is present.
Amber
When On steady indicates device
is disabled or must be replaced.
Possible Watchdog Timer problem.
NOTE
Blinks one time at power-up.
Table 4-8—EDIO Module - Channel Status Indicators
When all the LEDs have been illuminated,
the EDIO module displays the device’s LON
address by illuminating the channel active
red LED. LON dip switches 1 though 8 will be
displayed on channels 1 through 8. When a
dip switch is set to the ON position, the channel
active red LED will be illuminated. The address
is displayed for two seconds.
LED
Channel Status
Red
When On steady indicates the input
circuit is closed or the output circuit
is active
Amber
When Blinking indicates a low power
condition is present or channel is not
properly configured. Steady indicates
a channel fault.
Once the address has been displayed, the
device’s fault LED will turn off.
After the power-up sequence, the device will
either display an unconfigured state or normal
operation state. In the unconfigured state, the
channel fault amber LEDs flash ON and OFF at
the same rate for all channels.
18.2
4-11
95-8533
8 CHANNEL DCIO MODULE
STATUS INDICATOR LEDs
The DCIO Module (see Figure 4-7) has 18 LED
status indicators, two for the device and two
for each channel, located on the front panel.
Refer to Tables 4-9 and 4-10 for a description
of the LED indicators.
POWER-UP SEQUENCE
Figure 4-7—DCIO Module Status Indicator Location
Set the module address switch prior to applying
power.
DCIO module power-up sequence illuminates
the LEDs for the device and all of its channels.
First the power and fault LEDs are illuminated,
indicating that the device is in a power-up
mode. Next the LEDs are illuminated in the
following sequences:
• Sequentially each channel active red LED
is illuminated, starting with channel 1 and
continuing through channel 8.
• When the red LED for channel 8 is
illuminated, sequentially each channel
active red LED is turned off, starting with
channel 1 and continuing through channel
8.
• Next, the channel fault amber LEDs are
tested in the same manner as the channel
active red LEDs.
Table 4-9—DCIO Module - Device Status Indicators
LED
Device Status
Green
On when power is present.
Amber
When On steady indicates device
is disabled or must be replaced.
Possible Watchdog Timer problem.
NOTE
Blinks one time at power-up.
Table 4-10—DCIO Module - Channel Status Indicators
When all the LEDs have been illuminated,
the DCIO module displays the device’s LON
address by illuminating the channel active
red LED. LON dip switches 1 though 8 will be
displayed on channels 1 through 8. When a dip
switch is set to the ON position, the channel
active red LED will be illuminated. The address
is displayed for two seconds.
LED
Channel Status
Red
When On steady indicates the input
circuit is closed or the output circuit
is active
Amber
When Blinking indicates a low power
condition is present or channel is not
properly configured. Steady indicates
a channel fault.
Once the address has been displayed, the
device’s fault LED will turn off.
After the power-up sequence, the device will
either display an unconfigured state or normal
operation state. In the unconfigured state, the
channel fault amber LEDs flash ON and OFF at
the same rate for all channels.
18.2
4-12
95-8533
8 CHANNEL RELAY MODULE
STATUS INDICATOR LEDs
The Relay Module (see Figure 4-8) has 18 LED
status indicators, two for the device and two
for each channel, located on the front panel.
Refer to Tables 4-11 and 4-12 for a description
of the LED indicators.
POWER-UP SEQUENCE
Figure 4-8—Relay Module Status Indicator Location
Set the module address switch prior to applying
power.
Relay module power-up sequence illuminates
the LEDs for the device and all of its channels.
First the power and fault LEDs are illuminated,
indicating that the device is in a power-up
mode. Next the LEDs are illuminated in the
following sequences:
Table 4-11—Relay Module - Device Status Indicators
• Sequentially each channel active red LED
is illuminated, starting with channel 1 and
continuing through channel 8.
• When the red LED for channel 8 is
illuminated, sequentially each channel
active red LED is turned off, starting with
channel 1 and continuing through channel
8.
• Next, the channel fault amber LEDs are
tested in the same manner as the channel
active red LEDs.
LED
Device Status
Green
On when power is present.
Amber
When On steady indicates device
is disabled or must be replaced.
Possible Watchdog Timer problem.
NOTE
Blinks one time at power-up.
Table 4-12—Relay Module - Channel Status Indicators
When all the LEDs have been illuminated,
the relay module displays the device’s LON
address by illuminating the channel active
red LED. LON dip switches 1 through 8 will be
displayed on channels 1 through 8. When a dip
switch is set to the ON position, the channel
active red LED will be illuminated. The address
is displayed for two seconds.
LED
Channel Status
Red
When On steady indicates the input
circuit is active
Amber
When Blinking indicates a low power
condition is present or channel is not
properly configured.
Once the address has been displayed, the
device’s fault LED will turn off.
After the power-up sequence, the device will
either display an unconfigured state or normal
operation state. In the unconfigured state, the
channel fault amber LEDs flash ON and OFF at
the same rate for all channels.
18.2
4-13
95-8533
ANALOG INPUT MODULE
STATUS INDICATOR LEDs
The Analog Input Module (see Figure 4-9) has
18 LED status indicators, two for the device
and two for each channel, located on the front
panel. Refer to Tables 4-13 and 4-14 for a
description of the LED indicators.
POWER-UP SEQUENCE
Set the module address switch prior to applying
power.
The Analog Input Module power-up sequence
illuminates the LEDs for the device and all of its
channels. First the power and fault LEDs are
illuminated, indicating that the device is in a
power-up mode. Next the LEDs are illuminated
in the following sequences:
• Sequentially each channel active red LED
is illuminated, starting with channel 1 and
continuing through channel 8.
• When the red LED for channel 8 is
illuminated, sequentially each channel
active red LED is turned off, starting with
channel 1 and continuing through channel
8.
• Next, the channel fault amber LEDs are
tested in the same manner as the channel
active red LEDs.
Figure 4-9—Analog Input Module Status Indicator Location
Table 4-13—Analog Input Module - Device Status Indicators
LED
Device Status
Green
On when power is present.
Amber
When On steady indicates device
is disabled or must be replaced.
Possible Watchdog Timer problem.
NOTE
Blinks one time at power-up.
Table 4-14— Analog Input Module - Channel Status Indicators
When all the LEDs have been illuminated, the
analog input module displays the device’s
LON address by illuminating the channel
active red LED. LON dip switches 1 through
8 will be displayed on channels 1 through 8.
When a dip switch is set to the ON position, the
channel active red LED will be illuminated. The
address is displayed for two seconds.
LED
Channel Status
Red
When Blinking indicates a low alarm.
When On Steady indicates a high
alarm.
Amber
When Blinking indicates a low power
condition is present or channel is
not properly configured. On steady
indicates out of range condition
Once the address has been displayed, the
device’s fault LED will turn off.
After the power-up sequence, the device will
either display an unconfigured state or normal
operation state. In the unconfigured state, the
channel fault amber LEDs flash ON and OFF at
the same rate for all channels.
18.2
4-14
95-8533
EQ21XXPSM POWER SUPPLY
MONITOR
EQ2220GFM GROUND FAULT
MONITOR
The power supply monitor (see Figure 4-10)
has three LEDs used to provide a visual
indication of device status:
The ground fault monitor (see Figure 4-11) has
three LEDs used to provide a visual indication
of device status:
+ GND FLT LED
+
+
1
+
1
+
+
+
+
+
– GND FLT LED
+
1
+
+
+
+
+
+
1
AMBER LED
+
RED LED
GREEN LED
PWR LED
Figure 4-10—EQ21xxPSM Status Indicator Location
A2243
Table 4-15—Power Supply Monitor Status Indicators
LED
Device Status
Green
When On indicates power is supplied
to device
Red
When Flashing indicates an alarm or
fault condition is present.
Amber
When On indicates device is disabled.
Module must be replaced.
Figure 4-11—Ground Fault Monitor Status Indicator Location
NOTE
The Ground Fault Monitor LED will
respond immediately to a ground fault
condition. The relay contact requires the
condition to exist for 10 seconds before
it activates.
Table 4-16—Ground Fault Monitor Status Indicators
18.2
4-15
LED
Device Status
+ GND FLT LED
Indicates Amber in the
presence of a "+" ground fault.
- GND FLT LED
Indicates Amber in the
presence of a "-" ground fault.
POWER LED
Indicates Green when the unit
is powered.
95-8533
EQ22XXDCU AND
EQ22XXDCUEX DIGITAL
COMMUNICATION UNITS
EQ24XXNE NETWORK
EXTENDER
The DCUs have three LEDs to provide a visual
indication of device status. They are visible
through the window on the enclosure cover.
The EQ24xxNE has three LEDs (one green, two
amber) for indicating device status.
NOTE
Table 4-21—Network Extender Status Indicators
If the communication module has not
been configured, the red LED blinks at a
4 Hz rate.
LED
Device Status
Green
When On indicates device has power.
Flashes to indicate messages are
being transferred over the LON.
NOTE
The amber LED is provided for factory
diagnostic purposes and is not used in
the system. Illumination of the amber
LED normally indicates a failure in the
communication chip. Replacement of
the communication module circuit board
is required.
Amber
When On indicates a malfunction
in the electronic circuitry. Module
replacement is required.
NOTE
When a network extender has
an internal fault, the message
display will only indicate that
there is a LON fault condition
existing somewhere on the LON.
Table 4-18—DCU Status Indicators
Device
Status
LED Status
Power-up
Pulsed at a rate of 0.5 Hz
Calibration
Pulsed at a rate of 1 HZ or on
steady
Fault
Pulsed at a rate of 4 Hz
Alarm
On steady
18.2
4-16
95-8533
SYSTEM STARTUP
Redundant Controller
PRE-OPERATION CHECKS
General
The I/O and LON wiring is correctly installed,
observing polarity. All cable shields are
properly terminated and insulated.
Insulate all shields to prevent shorts to device
housing or to any other conductor.
Power wiring is installed and power source is
operational.
Place alarm/release output in “Bypass/Isolate”
when servicing devices.
Chassis ground stud must be connected to
earth ground.
Maintain a log book containing the type and
serial numbers of devices as well as the
location and date of installation.
The HSSL cable is connected between the two
controllers.
Maintain a log of maintenance activities.
Observe normal precautions for handling
electrostatic sensitive devices.
EDIO/DCIO Module
Verify correct address setting.
Check signal circuits for correct polarity.
LON
Check for correct installation of EOL resistors.
Rocker switches for each LON device must be
set to the desired address prior to power-up.
Relay Module
Test the loop with no power applied. DC
resistance should be equal on A and B.
Check polarity on A and B (no rolls). COM
1 connects to COM 2; COM 2 connects to
COM 1. A connects to A and B to B.
Measure voltage. A to chassis ground
measures approximately +7.5 Vdc. B to
ground measures approximately –7.5 Vdc.
Measure signal (400 mv P-P min.). (Use
oscilloscope if possible.)
Check fault tolerance by introducing a short.
Controller
The I/O and LON wiring is correctly installed,
observing polarity. All cable shields are
properly terminated and insulated.
Power wiring is installed and power source is
operational.
Verify correct address setting.
Check for correct output connections.
Analog Input Module
Verify correct address setting.
Check for correct input connections.
Check each channel with a loop current input.
Power Supplies and Power Monitors
Verify all earth ground connections as specified
in the wiring instructions.
Verify correct ac power to supply.
Check power distribution to ensure that all
devices are receiving power.
Check power trouble indicator by introducing
an open to the battery.
Chassis ground stud must be connected to
earth ground.
18.2
4-17
95-8533
Ground Fault Monitor
GENERAL START-UP PROCEDURES
Verify earth ground connections as specified in
the wiring instructions.
1. Output loads that are controlled by the
system should be secured (remove
power from all output devices) to prevent
actuation.
Check power distribution to ensure that all
devices are receiving power.
DCUs
2. Check all system
connection.
wiring
for
proper
3. Inspect all devices to verify that they
have not been physically damaged in
shipment.
Verify correct address setting.
Check modules for correct orientation.
Check for the presence of contaminants or
poisoning agents.
Device should be oriented with the sensor
pointing down.
IDCs
Verify correct address setting.
Check for correct installation of EOL resistors.
ARMs
Verify correct address setting.
4. Apply power to the system.
NOTE
To prevent the network modules from
going into a fault isolation condition,
apply power to the EQP Controller
prior to applying power to the network
devices.
5. Program the system for the desired
operation using Det-Tronics Safety System
Software (S³). Download configuration data
to all devices.
NOTE
Check jumpers.
After system configuration has been
completed, the entire system should be
tested for proper operation to ensure that
configuration was performed properly.
SAMs
Verify correct address setting.
Check signal circuits for correct polarity.
6. Calibrate the sensors.
Check for correct installation of EOL resistors.
7. Ensure that all trouble and alarm conditions
have been cleared and the EQP Controller
is reset, then remove mechanical blocking
devices (if used) and restore power to the
output loads.
Check jumpers.
NOTE
Please reference EQP Large Scale
Installation manual (95-8770) for more
information on legac products, including
DCUs, IDCs, ARMs, and SAMs.
18.2
4-18
95-8533
START-UP PROCEDURE FOR
CONTROLLER
STARTUP PROCEDURE FOR EDIO
MODULE
The Controller is powered-up when the Power
Supply is turned on. When the Power Supply has
been powered-up, verify power at the Controller by
verifying that the Green LED indicator is on. This
indicator is located on the front of the Controller.
Configuration
The EDIO Module is an eight-channel device.
Each channel is capable of being configured
as an input or output, independent of any other
channel.
To verify that the Controller is powered-up and
operating properly, ensure that:
1. When power is first applied, all LEDs are on.
The ACK LED flashes while the memory test
is running. When initialization is complete, only
the green power LED remains lit.
2. The Ethernet/Serial communication indicators
continuously flash (if active).
NOTE
For the Ethernet Interface Board, the blue
LEDs associated with ports 3 and 4 will
remain on when the ports are ready for
communication. Flashing green and amber
LEDs indicate active transmit and receive.
The amber indicator on the front of the
RJ45 connector indicates a 10 Mb/s link
is established. The green indicator on the
front of the RJ45 connector indicates a 100
Mb/s link is established.
3. The Text display runs an initialization routine.
When initialization is complete and if all alarms
and trouble conditions are cleared, the text
display shows the current time and date. If
the controller has been unpowered for more
than 12 hours, the time and date may have
to be set. If an alarm or trouble condition
exists, it will be displayed until the condition
is corrected and the Reset button is pressed.
NOTE
The module is configured using Det-Tronics
Safety System Software.
Activation Time
Timers are made available for output circuits
only. Timers are used primarily to set the timing
of output release in a suppression system. Timers
provide a pulse timed output for the time period
specified in the configuration of the channel. The
channel output goes active when commanded by
the system logic and remains on until the timer
expires.
Static Logic Mode
Each input channel can be configured as a
Fire Alarm, Trouble, Low Gas Alarm, High Gas
Alarm, Supervisory, or Other type of channel,
independent of any other channel configuration.
The type selected determines the logic the
system uses to configure Indicators, Alarms and
Messages.
For example: When an input is selected as Fire
type, the Fire LED on the Controller and Audible
alarm will automatically actuate when that input
channel is active.
If the controller has not been software
configured, unconfigured devices will be
displayed. Configuration must be done using S³
Safety System Software before proceeding.
4. The LEDs on the front panel provide an
indication of the system status.
5. Ensure
configuration
properly.
was
performed
6. After any modifications have been made either
to the installation or to configuration software,
always check the entire system for proper
operation in order to ensure that the changes
were performed properly.
18.2
4-19
95-8533
EDIO Startup
1. The Power-on LED should be illuminated. The
Fault LED should blink once on power up, then
remain off.
2. The input circuits should indicate the proper
state of the input device (channel active LED
illuminates when the circuit is closed). Check
the input power supply and associated wiring.
Verify proper voltage per the Troubleshooting
matrix.
3. The output circuits should indicate the
proper state for the programmed device
(channel active LED illuminates when the
circuit is active). Check the power supply and
associated wiring. Verify proper voltage per
the Troubleshooting matrix.
4. The circuits should not indicate a fault
condition (channel fault LED illuminates when
the circuit is in fault). Check the end-of-line
devices and associated wiring. Verify proper
voltage per the Troubleshooting matrix.
5. Test the entire system for proper operation to
ensure that the configuration was performed
properly.
STARTUP PROCEDURE FOR
DCIO MODULE
Configuration
The DCIO Module is an eight-channel device.
Each channel is capable of being configured
as an input or output, independent of any other
channel.
NOTE
The module is configured using
Det-Tronics Safety System Software.
Activation Time
Timers are made available for output circuits
only. Timers are used primarily to set the timing
of output release in a suppression system.
Timers provide a pulse timed output for the
time period specified in the configuration of the
channel. The channel output goes active when
commanded by the system logic and remains
on until the timer expires.
Static Logic Mode
Each input channel can be configured as a
Fire Alarm, Trouble, Low Gas Alarm, High
Gas Alarm, Supervisory, or Other type of
channel, independent of any other channel
configuration. The type selected determines
the logic the system uses to configure
Indicators, Alarms, and Messages.
For example: When an input is selected as
Fire type, the Fire LED on the Controller and
Audible alarm will automatically actuate when
that input channel is active.
18.2
4-20
95-8533
DCIO Startup
Relay Module Startup
1. The Power-on LED should be illuminated.
The Fault LED should blink once on power
up, then remain off.
1. The Power-on LED should be illuminated.
The Fault LED should blink once on power
up, then remain off.
2. The input circuits should indicate the
proper state of the input device (channel
active LED illuminates when the circuit is
closed). Check the input power supply and
associated wiring. Verify proper voltage per
the Troubleshooting matrix.
2. The output circuits should indicate the
proper state for the programmed device
(channel active LED illuminates when the
circuit is active).
3. The output circuits should indicate the
proper state for the programmed device
(channel active LED illuminates when the
circuit is active). Check the power supply
and associated wiring. Verify proper voltage
per the Troubleshooting matrix.
4. The circuits should not indicate a fault
condition (channel fault LED illuminates
when the circuit is in fault). Check the endof-line devices and associated wiring. Verify
proper voltage per the Troubleshooting
matrix.
5. Test the entire system for proper operation
to ensure that the configuration was
performed properly.
18.2
3. Test the entire system for proper operation
to ensure that the configuration was
performed properly.
Analog Input Module Startup
1. The Power-on LED should be illuminated.
The Fault LED should blink once on power
up, then remain off.
2. The input circuits should indicate the proper
state for the programmed device (channel
active LED illuminates when the circuit is
active).
3. The circuits should not indicate a fault
condition (channel fault LED illuminates
when the circuit is in fault).
4. Test the entire system for proper operation
to ensure that the configuration was
performed properly.
4-21
95-8533
Section 5
Maintenance
should be opened periodically, and the O-ring
inspected for breaks, cracks and dryness.
NOTE
Refer to the Eagle Quantum Premier
Sy s te m S a fe t y M a n u a l ( n u m b e r
95-8599) for specific requirements
and recommendations applicable to
the proper installation, operation, and
maintenance of all SIL-Certified EQP
systems.
ROUTINE MAINTENANCE
To ensure reliable protection, it is important to
check and calibrate the system on a regularly
scheduled basis. The frequency of checks
is determined by the requirements of the
particular installation.
BATTERIES
Batteries must be replaced every 48 months,
or sooner if required by local codes.
IMPORTANT
Only sealed batteries are to be used.
MANUAL CHECK OF OUTPUT DEVICES
It is important that response devices be
checked initially when the system is installed,
as well as periodically during an on-going
maintenance program.
CAUTION
To test O-ring: remove it from the enclosure and
stretch it slightly. If cracks are visible, replace
it. If it feels dry, a thin coating of lubricant
should be applied. When re-installing the
O-ring, be sure that it is properly seated in the
housing groove. It is imperative that this O-ring
be properly installed and in good condition.
Failure to properly maintain it can allow water
to enter the enclosure and cause premature
failure. A coating of lubricant should also be
applied to the threads on the cover before
re-assembling the enclosure. This will both
lubricate the cover threads and help prevent
moisture from entering the enclosure.
CAUTION
The O-rings should be lubricated with
a silicone free grease. The use of
other lubricants is not recommended,
since they can adversely affect the
performance of some sensors. Under
no circumstances should a lubricant
or compound containing silicone be
used on systems using catalytic type
combustible gas sensors.
GAS SENSOR MAINTENANCE
All gas sensors must be calibrated on a
regular basis. Calibration should typically be
performed every 90 days for catalytic and
electrochemical sensors.
Catalytic sensors have a finite lifespan. If a
successful calibration cannot be performed,
replace the sensor and recalibrate following
the procedure described in the “Calibration”
section below. Always compare part numbers
to be sure that the correct replacement
sensor is being used.
Be sure to secure all output devices that
are actuated by the system to prevent
unwanted activation of equipment, and
remember to place these output devices
back into service when the checkout is
complete.
O-RING MAINTENANCE
CAUTION
WARNING
The hazardous area must be
de-classified prior to removing a junction
box cover with power applied.
A rubber O-ring is used to ensure that the
junction box cover will seal tightly and provide
protection against water entry. The enclosure
18.2
5-1
E x p o s u re o f t h e s e n s o r to h i g h
concentrations of combustible gases
for extended periods of time can
introduce stress to the sensing element
and seriously affect its performance.
After exposure, recalibration should
immediately be performed, and the
sensor should be replaced if necessary.
95-8533
NOTE
magnet in place for approximately
four seconds to initiate the calibration
procedure.
Electrochemical sensors have a finite
lifespan. If a successful calibration
cannot be performed, inspect the
hydrophobic filter. If the filter is plugged,
replace it and recalibrate the sensor. If
the filter is in good condition, replace
the sensor. Recalibrate following the
procedure described in the “Calibration”
section.
GND
11
12
To ensure optimum performance, calibration
must be performed on a regularly scheduled
basis. Since each application is different, the
length of time between regularly scheduled
recalibrations can vary from one installation
to the next. In general, the more frequently a
system is checked, the greater the reliability.
IMPORTANT
4–20 mA devices not manufactured by
Det-Tronics must be pre-calibrated. To
ensure adequate protection, calibration
must be performed on a regularly
scheduled basis.
NOTE
If the calibration procedure is not
completed within 12 minutes, the
detector will revert back to the previous
calibration values. The red LED will blink.
The calibration will be logged as aborted.
NOTE
The “Sensor Replacement” calibration
procedure must be used for the initial
calibration of a new sensor. The “Routine
Calibration” procedure can be used for
all subsequent calibrations.
NOTE
Some calibration procedures require
the operator to activate the reed switch
located on a circuit board inside the
junction box. See Figure 5-1 for reed
switch location. To activate the switch,
hold the calibration magnet against the
side of the junction box near the switch
location approximately one inch above
the mounting surface. (Do not open
the junction box.) Hold the calibration
18.2
*
1
MAGNETIC REED SWITCH
2
3
4
5
SW1
6
7
8
9
14
10
13
CALIBRATION AND
ADJUSTMENTS
A1881
* TO
ACTIVATE THE MAGNETIC REED SWITCH,
HOLD THE CALIBRATION MAGNET AGAINST THE SIDE OF THE ENCLOSURE
AT THE LOCATION OF THE REED SWITCH,
APPROXIMATELY ONE INCH ABOVE THE MOUNTING SURFACE.
Figure 5-1—
DCU Terminal Wiring Board Mounted in Six-Port Junction Box
CALIBRATION ALGORITHM A
FOR MANUAL CALIBRATION OF
UNIVERSAL DCU
Normal Calibration
1. Activate the reed switch. (The red LED
blinks while the reed switch is closed.)
2. After the reed switch has been closed for
three seconds, the calibrate LED blinks,
indicating it is ready for the zero input.
3. Enter the zero input (4 mA).
4. Activate the reed switch. (The red LED
blinks while the switch is closed.)
5. After the reed switch has been closed
for three seconds, the communication
module records the uncalibrated value
in the calibration log and calibrates the
zero value. (The calibrate LED stays on
steady.)
6. Apply the calibration gas.
7. The calibrate LED blinks as the input
increases.
8. Activate the reed switch. (The red LED
blinks while the reed switch is closed.)
9. The communication module records the
uncalibrated value in the calibration log
and calibrates the span value after the reed
switch is on for three seconds.
10. The calibrate LED stays on steady.
5-2
95-8533
11. Remove the span gas, and return the
analog input to normal.
11. Remove the span gas and return the
analog input to normal.
12. Activate the reed switch. (The red LED
blinks for three seconds while the reed
switch is closed)
12. Activate the reed switch. (The red LED
flashes for three seconds while the switch
is closed.)
13. The calibration is complete. The calibrate
LED turns off.
13. The calibration is complete. (The calibrate
LED turns off.)
NOTE
NOTE
If the calibration is not completed within
12 minutes, the previous calibration
values are restored and the calibration
is logged as aborted. The calibrate LED
will flash.
Pressing the Sensor Replacement
Switch aborts calibration and starts over.
NOTE
Resetting the communication module will
abort the sensor replacement.
Sensor Replacement
CALIBRATION ALGORITHM C
FOR COMBUSTIBLE GAS DCUS AND
AUTOMATIC CALIBRATION OF
UNIVERSAL DCUs
WARNING
The hazardous area must be
de-classified prior to removing a junction
box cover with power applied.
CAUTION
1. Open the junction box cover and press the
Sensor Replacement Switch.
2. The calibrate LED on the communication
module will flash, indicating it is ready for
the zero input.
3. Replace the sensor and apply the zero
input (4 mA).
4. Activate the reed switch. (The red LED
flashes for three seconds while the switch
is closed.)
5. The communication module records
the uncalibrated value in position one
of the calibration log and calibrates the
zero value. (The calibrate LED stays on
steady.)
6. Apply the calibration gas.
Routine Calibration
1. Apply the zero gas.
2. Activate the reed switch for at least four
seconds. (The red LED flashes for three
seconds while the switch is activated.)
3. The calibrate LED on the communication
module flashes, indicating it is ready for
the zero input.
4. Wait until the calibrate LED stays on steady
(approximately four seconds).
NOTE
7. The calibrate LED flashes when the input
increases.
8. Activate the reed switch. (The red LED
flashes for three seconds while the reed
switch is closed.)
9. The communication module records the
uncalibrated value in the first register of
the calibration log and calibrates the span
value.
10. The calibrate LED stays on steady.
18.2
After exposing the H2S sensor to
high concentrations of gas, it should
be exposed to fresh air for at least 30
minutes, and re-calibrated.
5-3
The communication module records the
uncalibrated value in the calibration log and
calibrates the zero value during this time.
5. Apply the calibration gas. (The calibrate
LED flashes when the sensor detects
gas.)
6. When the sensor input has been stable for
30 seconds, the communication module
records the uncalibrated value in the
calibration log, and calibrates the span
value.
95-8533
7. The calibrate LED stays on steady.
8. Remove the calibration gas.
9. The communication module waits until the
sensor input drops below 4% full scale.
10. The calibration is complete. (The calibrate
LED turns off.)
5. Connect a volt meter to the test points on
the transmitter board. Connect the “+” lead
to TP1 (red). Connect the “–” lead to TP2
(black).
6. Wait at least five minutes for the sensor
output to stabilize, then adjust R2 for a
reading of 0.40 Vdc (4 mA) on the meter.
NOTE
NOTE
If the calibration procedure is not
completed within 12 minutes, calibration
will be aborted and the detector will
revert back to the previous calibration
values. The red LED will flash and the
calibration will be logged as aborted.
Do not make adjustments to R1 when
calibrating the sensor.
Initial Installation and Sensor
Replacement — Combustible Gas
(CGS Sensor)
NOTE
When replacing a sensor, compare part
numbers to be sure that the correct
replacement sensor is used.
7. Move the Calibrate Switch to the “normal”
position.
8. Activate the reed switch for four seconds.
(The red LED flashes for three seconds
while the switch is activated.) The
communication module records the
uncalibrated value in position one of
the calibration log and calibrates the
zero value. The calibrate LED goes on
steady.
9. Move the Calibration
“calibrate” position.
Switch
to
the
10. Apply the calibration gas and wait for the
output to stabilize.
WARNING
The hazardous area must be
de-classified prior to removing a junction
box cover with power applied.
1. Remove the cover from the DCUEX
enclosure.
2. Press the Sensor Replacement Switch
on the communication module for
approxImately one second. (The calibrate
LED on the communication module
flashes, indicating that it is ready for the
zero input.)
NOTE
Pressing the sensor replacement switch
prevents the communication module
from generating a fault signal when
the input drops to zero due to sensor
removal. The calibration will not be
aborted if the calibration procedure is not
completed within 12 minutes.
3. Move the Calibration
“calibrate” position.
Switch
to
11. With 50% LFL calibration gas applied to
sensor, adjust R3 for a reading of 1.2 Vdc
(12 mA) on the volt meter.
12. Move the Calibrate Switch to the “normal”
position. (The red LED flashes.)
13. Activate the reed switch. The red LED
flashes for three seconds while the switch
is activated.
14. The communication module records the
uncalibrated value in the first register
of the calibration log and calibrates the
span value. The calibrate LED stays on
steady.
15. Remove the calibration gas and replace
the DCU enclosure cover.
16. The communication module waits until the
analog value drops below 4% full scale.
The calibration is complete. (The calibrate
LED turns off.)
NOTE
Pressing the Sensor Replacement
Switch aborts the current calibration.
the
4. Replace the sensor.
18.2
5-4
95-8533
9. Remove the calibration gas and replace
the DCU enclosure cover.
Sensor Replacement — Toxic Gas
NOTE
10. The communication module waits until the
analog value drops below 4% full scale.
The calibration is complete. (The calibrate
LED turns off.)
When replacing a sensor, compare
part numbers to be sure the correct
replacement sensor is being used.
NOTE
WARNING
Pressing the Sensor Replacement
Switch aborts the calibration and starts
over.
The hazardous area must be
de-classified prior to removing a junction
box cover with power applied.
1. Remove the
enclosure.
cover
from
the
DCU
Normal Calibration
2. Press the Sensor Replacement Switch
on the communication module for
approximately one second. (The calibrate
LED flashes, indicating it is ready for the
zero input.)
1. Apply clean air (20.9% oxygen).
2. Activate the reed switch for at least four
seconds. (The red LED flashes for three
seconds while the switch is closed.)
3. The calibrate LED flashes, indicating
calibration has begun.
NOTE
Pressing the Sensor Replacement
Switch prevents the communication
module from generating a fault signal
when the input drops to zero due to
sensor removal. The calibration will not
be aborted if the calibration procedure is
not completed within 12 minutes.
4. The communication module waits three
seconds.
5. The communication module records the
uncalibrated value in the calibration log
and calibrates the span value.
6. The calibrate LED stays on steady.
3. Replace the sensor.
4. Wait at least five minutes for the sensor
output to stabilize.
5. Activate the reed switch. (The red LED
flashes for three seconds while the switch
is activated.) The communication module
records the uncalibrated value in position
one of the calibration log and calibrates
the zero value. (The calibrate LED stays on
steady.)
6. Apply the calibration gas. (The calibrate
LED flashes when the input increases.)
7. Activate the reed switch. (The red LED
flashes for three seconds while the switch
is activated.)
8. The communication module records the
uncalibrated value in the first register
of the calibration log and calibrates the
span value. (The calibrate LED stays on
steady.)
18.2
CALIBRATION ALGORITHM D
FOR UNIVERSAL DCUs WITH O2 SENSOR
5-5
7. The communication module waits three
seconds.
8. Calibration is complete. (The calibrate LED
turns off.)
Sensor Replacement
WARNING
The hazardous area must be
de-classified prior to removing a junction
box cover with power applied.
1. Open the junction box cover and press the
Sensor Replacement Switch.
2. The calibrate LED on the communication
module flashes, indicating it is ready for
the zero input.
3. Replace the sensor and set the Sensor
Switch (located on the sensor cell) to
zero.
95-8533
4. Activate the reed switch. (The red LED
flashes for three seconds while the switch
is closed.)
5. The communication module records
the uncalibrated value in position one
of the calibration log and calibrates the
zero value. The calibrate LED stays on
steady.
7. The calibrate LED stays on steady.
8. Remove the calibration gas.
9. The communication module waits until the
sensor input drops below 4% full scale.
10. The calibration is complete. (The calibrate
LED turns off.)
NOTE
6. Set the Zero Switch on the sensor to the
“normal” position. Apply clean air (20.9%
oxygen) to set the sensor analog span
value.
Calibration is aborted if not complete
within 12 minutes. If not completed, the
detector will revert back to the previous
calibration values. The red LED will flash
and the calibration will be logged as
aborted.
7. The calibrate LED flashes when the input
goes high.
8. Activate the reed switch. (The red LED
flashes for 3 seconds while the switch is
closed.)
Sensor Replacement
9. The communication module records the
uncalibrated value in the first register of
the calibration log and calibrates the span
value.
10. The calibration is complete. The calibrate
LED turns off.
NOTE
Pressing the sensor replacement switch
aborts the calibration.
CALIBRATION ALGORITHM G
FOR DCUs WITH POINTWATCH
OR DUCTWATCH
WARNING
The hazardous area must be
de-classified prior to removing a junction
box cover with power applied.
1. Remove power from the DCU and
PointWatch/DuctWatch unit.
Replace
the PointWatch unit. Apply power. Press
the Sensor Replacement Switch on the
communication module for approximately
1 second.
NOTE
Allow at least 10 minutes for the sensor
to warm up.
Routine Calibration
1. Apply the zero gas.
NOTE
2. Activate the reed switch for at least 4
seconds. (The red LED flashes for 3
seconds while the switch is activated.)
Pressing the Sensor Replacement
Switch prevents the communication
module from generating a fault signal
when the input drops to zero.
3. The calibrate LED flashes, indicating it is
ready for the zero input.
4. When a steady zero reading is obtained,
the communication module records the
uncalibrated value in the calibration log
and calibrates the zero value during this
time. The LED stays on steady.
5. Apply calibration gas. (The calibrate LED
flashes when the sensor detects gas.)
6. When the sensor input has been stable for
30 seconds, the communication module
records the uncalibrated value in the
calibration log and calibrates the span
value.
18.2
NOTE
The calibration will not be aborted if the
calibration procedure is not completed
within 12 minutes
.
2. Apply zero gas.
3. The calibrate LED flashes, indicating that it
is ready for the zero input.
4. Continue from step 4 of the PointWatch/
DuctWatch routine calibration procedure
described above.
5-6
95-8533
DEVICE CALIBRATION LOGS
AND RECORDS
The DCU keeps a calibration log in non-volatile
memory that can be used by the operator to
evaluate the remaining life of some sensors.
This log includes the zero, span, date and
time for each successful calibration. An
aborted calibration is indicated by zeros in the
zero and span values. The calibration log is
cleared when the sensor replacement switch
is pressed and the calibration is successfully
completed.
The initial calibration is logged in position
one, where it remains for the life of the
sensor. If more than eight calibrations are
performed without the sensor replacement
switch being pressed, the newest calibration
data will replace the second oldest so that
the initial calibration data can be saved. The
old calibration data will be lost. This feature
enables sensor sensitivity trending to aid in
maintenance or troubleshooting.
The analog value for the sensor is represented
in raw analog-to-digital counts 0 to 4095,
where 0 represents 0 ma and 4095 represents
24 mA.
check for proper wiring, programming and
calibration. If it is determined that the problem
is caused by an electronic defect, the device
must be returned to the factory for repair.
NOTE
When replacing a device, be sure that
all rocker switches on the replacement
are set the same as the original device.
Consult the settings documented
during system installation and setup to
determine proper settings for the new
device. Remove power before removing
a device or plugging in a replacement
unit. When a device is replaced,
configuration is done automatically.
DEVICE REPAIR AND
RETURN
Prior to returning devices or components,
contact the nearest local Detector Electronics
office so that a Service Order number can be
assigned. A written statement describing the
malfunction must accompany the returned
device or component to expedite finding the
cause of the failure.
Tables 5-1 and 5-2 are provided to assist in
locating the source of a system problem.
Pack the unit or component properly. Use
sufficient packing material in addition to an
antistatic bag or aluminum-backed cardboard
as protection from electrostatic discharge.
REPLACEMENT PARTS
Return all equipment transportation prepaid to
the factory in Minneapolis.
TROUBLESHOOTING
Eagle Quantum Premier devices are not
designed to be repaired in the field. If a
problem should develop, first carefully
Table 5-1—Troubleshooting Guide - DCIO Module
I/O Type
Normal
(Off)
Normal
(On)
Open
(Off)
Open
(On)
Short
(Off)
Short
(On)
0
Unsupervised Input
–15.4
0
–15.4
–15.4
0
Supervised Input (EOL Resistor)
–14.4
0
–15.4
–15.4
0
0
Supervised Input (EOL/Inline Resistors)
–15.4
–15
–15.4
–15.4
0
0
Unsupervised Output
–15.4
23.9
–15.4
23.9
0
0
0 to 2.1
Note 2
23.9
–15.4
23.9
0
0
–14.4
23.9
–15.4
23.9
0
0
Supervised Output (Agent Release)
Supervised Output (Notification)
Notes:
1. All measurements are in Volts and are measured in reference to the common terminal and 24.0 Vdc is the
module’s input.
2. Value is dependent on the resistance of the solenoid attached.
18.2
5-7
95-8533
Table 5-2—System Controller Troubleshooting Guide
Symptom
Possible Cause
Corrective Action
Controller Power
LED/
Text Display OFF
No Power to Input.
–– Measure input voltage (18 to 30 Vdc).
–– Check that P1 is fully inserted.
If voltage is present and P1 is fully inserted,
replace controller.
LON Fault – LED
lit.
LON wiring is shorted or open.
–– Check that P7 is fully inserted.
–– Using the EQ Safety System Software,
determine the location of open or short via
LON Diagnostics screen.
–– Use a multimeter to determine wiring fault.
Trouble Relay is
Active.
Any monitored device in the
system including ground fault
in fault condition.
–– Using the front panel display/controls, view
all points in alarm/fault and identify faulted
device.
–– Repair or replace faulted device as
necessary.
Digital inputs
are not
responding.
––
––
––
––
–– Check that P2 and P3 are fully inserted.
–– Using a voltmeter, measure input terminals
with contact closed to the input (measures 0
vdc when input contact is closed, measures
approximately 23 Vdc with circuit open and 24
vdc input at the controller).
–– If input does not respond to a contact closure,
replace module (verify response with EQ
Safety System Software/textual display).
–– Verify configuration.
Relay Outputs are
not respond to an
output command
–– Bad relay channel.
–– Faulty output wiring.
–– User logic.
–– Check that P4 and P5 are fully inserted.
–– When output should be energized, measure
contact resistance using an ohm meter.
–– Verify that wiring from output is not open.
–– Using EQ Safety System Software, verify that
logic is trying to operate the channel.
Serial links are not
responding.
–– Faulty wiring.
–– Incorrect serial link
configuration.
–– Text display shows "Invalid
Configuration"
–– Check that P8 and P9 are fully inserted.
–– Verify that communication LEDs are
flashing.
–– Verify that serial link configuration matches the
host device.
–– Verify that wiring is not open or shorted.
Ethernet link are
not responding
–– Faulty wiring.
–– Incorrect Ethernet link
configuration.
–– Text display shows "Invalid
Configuration"
–– Check that P3 and P4 are fully inserted.
–– Verify that communication LEDs are
flashing.
–– Verify that Ethernet link configuration is
correct.
–– Verify that wiring is not open or shorted.
Front panel
pushbuttons are
not working
–– Power OFF.
–– Controller is faulted.
–– Verify that power is present and P1 is fully
inserted.
–– Cycle power to controller.
Text dispaly
indicates a RTC
Fault
Power loss for more than 12
hours
–– Using the Safety System Software, execute
“Set RTC”, which downloads the current
time into the Controller’s real time clock.
Alternatively, use the “Set Time and Date”
menu in the Controller.
18.2
Bad input switch.
Faulty input channel.
Faulty wiring.
Configuration error.
5-8
95-8533
ORDERING INFORMATION
LON DEVICES
When ordering, please specify:
Part Number Description
006607-xxx
Refer to the appropriate model matrix in
Appendix G for the following devices:
EQ3XXX EQP Controller
EQ3700DCIO Discrete Input/Output Module
EQ3710AIM Analog Input Module
EQ3720RM Relay Module
EQ3730EDIO Enhanced Discrete Input/Output
Module
008981-001
Part Number Description
000604-013
000604-014
000604-015
000604-035
000604-036
007941-001
010988-001
010988-002
010892-001
010892-002
009934-001
009934-002
18.2
REDUNDANCY
Part Number Description
POWER SUPPLIES
006979-001
006941-xxx
008056-001
008982-001
EQ22xxDCU Digital
Communication Unit (specify
gas)
EQ24xxNE Network Extender
HART Interface Module
EQ3LTM LON Termination
Module
EQ21xxPSM Power Supply
Monitor
EQ2110PS Power Supply
(10 A / 60 Hz)
EQ2130PS Power Supply
(30 A / 60 Hz)
EQ2175PS Power Supply
(75 A / 60 Hz)
EQ2131PS Power Supply
(30 A / 50 Hz)
EQ2176PS Power Supply
(75 A / 50 Hz)
EQ2220GFM Ground Fault
Monitor
EQP2120PS–B Power Supply,
20A/50-60 Hz, Panel Mount
EQP2120PS Power Supply,
20A/50-60 Hz, DIN Rail Mount
EQ2410PS–P Converter,
10A/24 Vdc, Panel Mount
EQ2410PS Converter,
10A/24 Vdc, DIN Rail Mount
Diode Redundancy Module,
with Mounting Bracket
Diode Redundancy Module,
DIN Rail Mount
008982-001
Controller to Controller
High-Speed Serial Link Cable
(4 ft)
EQ3LTM LON Termination
Module
CONTROLLER
COMMUNICATION CABLES
Part Number Description
007633-001
007633-002
007633-003
5-9
Controller RS-232 Cable,
DB9 Female PC Connection,15
ft. (4.57 m)
Controller RS-232 Cable,
DB9 Female PC Connection,
30 ft. (9.14 m)
Controller RS-232 Cable,
DB9 Female PC Connection,
50 ft. (15.24 m)
95-8533
Section 6
Specifications
NOTE
Fo r U S C G A p p rov e d Sys te m
specifications, refer to Appendix D.
EQ3XXX CONTROLLER
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 Vdc. 10%
overvoltage will not cause damage to the
equipment.
INPUT POWER—
9 watts nominal, 12 watts maximum.
LON COMMUNICATION—
Digital communication, transformer isolated
(78.5 kbps).
RS-485 COMMUNICATION—
Modbus Master/Slave capability.
Digital communication, transformer isolated
(up to 115 kbps).
SERIAL INTERFACE BOARD—
RS-485 Communication: Modbus master/
slave capability, ground fault monitored.
Digital communication, transformer isolated
(up to 230 kbps).
RS-232 Communication: Modbus master/
slave or S³ configuration capability.
Digital communication, non-isolated (up to
230 kbps).
RS-232 Communication: Modbus master/
slave capability.
Digital communication, non-isolated (up to
230 kbps).
High Speed Serial Link (HSSL): Port used
only for redundant controller to controller
communication.
UNSUPERVISED OUTPUTS—
Dry Contact Rating: 1 ampere at 30 Vdc
maximum. SPDT normally open/normally
closed contact, Configurable for normally
energized or de-energized (de-energized is
the default mode).
RS-232 COMMUNICATION—
S³ configuration only.
Digital communication, optically isolated.
UNSUPERVISED INPUTS—
Two State input (on/off). User selectable
normally open or normally closed contact
(N.O. is the default).
CONTROLNET—
Digital communication, transformer isolated
(5 Mbps).
TROUBLE OUTPUT—
SPDT normally open/normally closed contact,
Non-Configurable, normally energized only.
ETHERNET DLR—
10/100 Mbps EtherNet DLR capability.
TEMPERATURE RANGE—
Operating (Certified Rating):
See Certification section below.
Storage: –40°F to +185°F (–40°C to +85°C).
Excluding communication port optional
modules.
ETHERNET INTERFACE BOARD—
RS-485 Communication: Modbus master/
slave capability, ground fault monitored.
Digital communication, transformer isolated
(up to 230 kbps).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
10/100 Mbps BASE-T Ethernet Communication:
Modbus TCP master/slave or S³ configuration
capability.
VIBRATION—
FM 3260, FM 6310/6320.
10/100 Mbps BASE-T Ethernet Communication:
Modbus TCP master/slave capability.
DIMENSIONS—
See Figure 6-1.
High Speed Serial Link (HSSL): Port used
only for redundant controller to controller
communication.
SHIPPING WEIGHT—
5 pounds (2.3 kilograms).
18.2
6-1
95-8533
FM
PPROVED
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Tamb = –40°C to +80°C.
Performance verified.
Refer to Appendix A for FM Approval details,
including Protected Premises Fire Alarm
Systems and EQP Supervising Systems.
Refer to Appendix B for CSA Certification
details.
Refer to Appendix D for USCG Approval
details.
CE:
ATEX/EMC Directive Compliant.
FM
10.75
(27.3)
DET-TRONICS
®
APPROVED
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Enter
Next
FM
®
IECEx:
®
II 3 G.
Ex nAc nCc IIC T4.
EN 60079-29-1 & EN 60079-29-4.
DEMKO 02 ATEX 133867X.
Tamb* = –40°C to +80°C.
Tamb = –40°C to +70°C.
5.95
(15.1)
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Previous
Reset
Power
5.5
(14.0)
Acknowledge Silence
PANEL MOUNTING DIMENSIONS
2.70
(6.86)
10.75
(27.3)
DET-TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
Fire Alarm
Time & Date
APPROVED
®
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
ATEX:
2.45
(6.22)
7.0
(17.78)
Cancel
Enter
Next
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Previous
Reset
Power
5.5
(14.0)
Acknowledge Silence
DIN RAIL MOUNTING DIMENSIONS
10.75
(27.3)
IECEx ULD 10.0004X.
Ex nAc nCc IIC T4.
Tamb* = –40°C to +80°C.
Tamb = –40°C to +70°C.
2.70
(6.86)
DET-TRONICS
®
6.7
(17.0)
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Note:
Refer to Appendix C for ATEX and
IECEx approval details and Special Conditions
for Safe Use.
*Applicable only if relays 1-7 (terminals 21-41)
are configured such that the relay contacts
are normally open and de-energized (refer to
Figures 3-8 and 3-9 for relay wiring information).
Enter
Next
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Previous
Reset
Power
5.5
(14.0)
Acknowledge Silence
DIMENSIONS OF DIN RAIL MOUNT CONTROLLER
WITH ETHERNET OR SERIAL INTERFACE BOARD
10.75
(27.3)
0.35
(0.89)
8.2
(20.8)
DET-TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
Eagle Quantum Premier
Fire Alarm
Time & Date
Cancel
Enter
Next
5.95
(15.1)
Trouble
Inhibit
High Gas
Cntrl Flt
Out Inhibit
Supr
Low Gas
Lon Fault
Ack
Silence
Previous
Reset
2.1
(5.3)
Power
6.7
(17.0)
Acknowledge Silence
7.0
(17.78)
DIMENSIONS OF PANEL MOUNT CONTROLLER
WITH ETHERNET OR SERIAL INTERFACE BOARD
K2103
Figure 6-1—Dimensions of EQP Controller in Inches
(Centimeters)
18.2
6-2
95-8533
EQ3LTM LON TERMINATION
MODULE
EQ3730EDIO ENHANCED
DISCRETE INPUT/OUTPUT
MODULE
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
POWER REQUIREMENTS—
3 watts nominal, 11 watts maximum.
INPUT POWER—
1 watt maximum.
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –-67°F to +185°F (–55°C to +85°C).
Note: Pre-action and deluge applications
further limit the lower operating voltage range,
refer to EDIO installation instructions in section
3.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
OUTPUT CURRENT—
10.0 amperes maximum total current, 2.0
amperes maximum per channel.
DIMENSIONS—
See Figure 6-2.
SHIPPING WEIGHT—
0.5 pounds (0.2 kilograms)
SLC OUTPUT—
Digital communication, transformer isolated
(78.5 kbps).
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
CE:
HUMIDITY RANGE—
5% to 95% RH, non-condensing.
ATEX/EMC Directive Compliant.
ATEX:
FM
APPROVED
®
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –67°F to +185°F (–55°C to +85°C).
IECEx:
®
VIBRATION—
FM 3260-2000 (clause 4.9).
II 3 G.
Ex nA IIC T4 Gc.
DEMKO 04 ATEX 138345X.
Tamb = –40°C to +85°C.
DIMENSIONS—
Refer to Figure 6-3.
SHIPPING WEIGHT—
1 pound (0.45 kilograms).
IECEx ULD 10.0004X.
Ex nA IIC T4 Gc.
Tamb = –40°C to +85°C.
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
Note: Refer to Appendix C for ATEX and IECEx
approval details and Special Conditions for
Safe Use.
2.95
(7.5)
CE:
0.7
(1.75)
ATEX/EMC Directive Compliant.
ATEX:
FM
APPROVED
2.16
(5.5)
1.87
(4.75)
FM
®
APPROVED
II 3 G.
Ex nA nC IIC T4 GC EN 60079-29-1.
DEMKO 05 ATEX 138864X.
Tamb = –40°C to +85°C.
A2253
Figure 6-2—Dimensions of LON Termination Module and
HART Interface Module in Inches (Centimeters)
18.2
6-3
95-8533
2.5
(6.4)
1.35
(3.4)
1
A
1
6
1
B
2
C
A2449
A
B
4
3
C
A
B
C
A
B
5
C
A
B
7
6
C
A
B
6
C
A
B
1
8
C
A
B
C
4.5
(11.3)
5.2
(13.2)
A
1
6
1
5.02
(12.7)
B
2
C
A
B
4
3
C
A
B
C
A
B
5
C
A
B
7
6
C
A
B
6
C
A
B
4.5
(11.3)
8
C
A
B
C
5.2
(13.2)
1.66
(4.2)
PANEL MOUNTING DIMENSIONS
1.9
(4.8)
DIN RAIL MOUNTING DIMENSIONS
Figure 6-3—Dimensions of the EDIO / DCIO / Relay Module / AIM in Inches (Centimeters)
IECEx:
IECEx ULD 10.0004X.
Ex nA nC IIC T4 GC.
Tamb = –40°C to +85°C.
For Class A wiring on inputs, configure adjacent
channels for Class A wiring and connect both
channels to single contact device(s).
Note: Refer to Appendix C for ATEX and IECEx
approval details and Special Conditions for
Safe Use.
Refer to Appendix D for USCG Approval details.
INPUT / INITIATING DEVICE CIRCUITS
UNSUPERVISED INPUT—
Two state input (on/off).
Normally open contact.
INPUT CIRCUITS – TWO WIRE SMOKE/HEAT
TYPE—
Supervised Input, Class B:
Up to 15 two wire detectors per circuit.
Maximum line resistance 50 ohms.
5K ohm EOL.
Open circuit fault impedance 22k ohms.
OUTPUT / NOTIFICATION / RELEASING
OR UNSUPERVISED DEVICE CIRCUITS
SUPERVISED INPUT (OPEN CIRCUIT)—
For Class A and Class B wiring.
Two state input (active/trouble):
– End of Line Resistor 10 K ohms nominal
– Open Circuit > 45 K ohms
– Active Circuit < 5 K ohms.
UNSUPERVISED OUTPUT RATING
(Per Channel)—
2 amperes at 30 Vdc maximum.
Automatic short circuit protection provided.
Instantaneous short circuit current < 15
amperes.
Note: Voltage available at outputs is dependent
on input voltage (Vout ≈ Vin – 0.5 Vdc).
SUPERVISED INPUT
(OPEN AND SHORT CIRCUIT)—
For Class A and Class B wiring.
Three State input (active/short/open):
– End of Line Resistor 10 K ohms nominal
– In Line Resistor 3.3 K ohms nominal
– Open Circuit > 45 K ohms
– Short Circuit < 250 ohms
– Active Circuit 2.5 K ohms to 5 K ohms.
OUTPUT STYLE—
Form "A" normally off.
RESPONSE TIME—
Output actuates in <0.15 second after
acknowledging
an
alarm
command
message.
INPUT, TYPES—
Configurable for static logic applications:
– Fire Alarm
– Supervisory
– Trouble
– High Gas Alarm
– Low Gas Alarm
– Other.
18.2
6-4
95-8533
SUPERVISED OUTPUT RATING-SIGNALING CIRCUIT
MAXIMUM OUTPUT CURRENT
(Per Channel)—
2 amperes at 30 Vdc maximum.
Automatic short circuit protection provided.
Instantaneous short circuit current < 15
amperes.
SUPERVISORY CURRENT (Per Channel)—
Reverse current monitored at 1.5 mA, ± 0.5
mA.
RESPONSE TIME—
Output actuates in <0.15 second after
acknowledging an alarm command message.
EOL RESISTORS—
10 K ohms ±2 K ohms. Each circuit must have
an EOL resistor.
SIGNALING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– 60 beats per minute
– 120 beats per minute
– Temporal Pattern.
Note: All eight channels are synchronized
when programmed as a signaling output.
SUPERVISED OUTPUT RATINGRELEASING CIRCUIT
MAXIMUM OUTPUT CURRENT
(Per Channel)—
2 amperes at 30 Vdc maximum.
Automatic short circuit protection provided.
Instantaneous short circuit current < 15
amperes.
SUPERVISORY CURRENT (Per Channel)—
Monitored at 1.3 mA ±0.2 mA.
RESPONSE TIME—
Output actuates in <0.15 second after
acknowledging an alarm command message.
RELEASING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– Timed.
For Class A wiring on outputs, configure
adjacent channels for Class A wiring and
connect both channels to single output
device(s).
18.2
NOTE
EDIO SIL has the capability of monitoring
solenoid circuits for shorts. The minimum
solenoid inductance for correct operation
is 100 mH. See Table 3-10 for a list of
recommended solenoids.
EQ3700 DISCRETE IO
(DCIO) MODULE
POWER REQUIREMENTS—
3 watts nominal, 11 watts maximum.
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
NOTE: Pre-action and deluge applications
further limit the lower operatring voltage range,
refer to DCIO installation instructions in section
3.
OUTPUT VOLTAGE—
(Input voltage – 0.5 Vdc) @ 2 amperes.
OUTPUT CURRENT—
10.0 amperes maximum total current, 2.0
amperes maximum per channel.
LON COMMUNICATION—
Digital communication, transformer isolated
(78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
Refer to Figure 6-3.
SHIPPING WEIGHT—
1 pound (0.45 kilograms).
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
FM
®
APPROVED
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
6-5
95-8533
FM
PPROVED
CE:
ATEX/EMC Directive Compliant.
ATEX:
FM
APPROVED
®
IECEx:
®
MAXIMUM OUTPUT CURRENT—
2 amperes maximum, 15 Amp inrush.
Automatic short circuit protection provided.
II 3 G.
Ex nA nC IIC T4 Gc.
DEMKO 02 ATEX 133864X.
Tamb = –40°C to +85°C.
SUPERVISORY CURRENT—
Reverse current monitored at 3.0 mA, ± 2.0
mA.
IECEx ULD 10.0004X.
Ex nA nC IIC T4 Gc.
Tamb = –40°C to +85°C.
RESPONSE TIME—
Output actuates in <0.15 second after
acknowledging an alarm command message.
Note: Refer to Appendix C for ATEX and IECEx
approval details and Special Conditions for
Safe Use.
INPUT / INITIATING DEVICE CIRCUITS
UNSUPERVISED INPUT—
Two state input (on/off).
Normally open contact.
SUPERVISED INPUT, CLASS B—
Two state input (active/trouble):
– End of Line Resistor 10 K ohms nominal
– Open Circuit > 45 K ohms
– Active Circuit < 5 K ohms.
EOL RESISTORS—
10 K ohms ±2 K ohms.
SIGNALING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– 60 beats per second
– 120 beats per second
– Temporal Pattern.
NOTE
All eight channels are synchronized
when programmed as a signaling output.
SUPERVISED OUTPUT RATING—
RELEASING CIRCUIT
SUPERVISED INPUT, CLASS B—
Three State input (active/short/open):
– End of Line Resistor 10 K ohms nominal
– In Line Resistor 3.3 K ohms nominal
– Open Circuit > 45 K ohms
– Short Circuit < 1.4 K ohms
– Active Circuit 2.5 K ohms to 5 K ohms.
MAXIMUM OUTPUT CURRENT
(Per Channel)—
2 amperes maximum, 15 Amp inrush.
Automatic short circuit protection provided.
SUPERVISORY CURRENT—
Monitored at 3.0 mA ±2.0 mA.
INPUT, TYPES—
Configurable for fixed logic applications:
– Fire Alarm
– Supervisory
– Trouble
– High Gas Alarm
– Low Gas Alarm
– Other.
RESPONSE TIME—
Output actuates in <0.15 second after
acknowledging an alarm command message.
OUTPUT / NOTIFICATION / RELEASING
CIRCUITS
UNSUPERVISED OUTPUT RATING—
Short circuit protected: 2 amperes at 30 Vdc
maximum.
RELEASING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– Timed.
SUPERVISED OUTPUT RATING—
SIGNALING CIRCUIT
18.2
6-6
95-8533
EQ3720 RELAY MODULE
EQ3710AIM ANALOG
INPUT MODULE
POWER REQUIREMENTS—
3 watts nominal, 4 watts maximum.
POWER REQUIREMENTS—
Module power consumption: 6 watts.
When supplying power to three-wire
transmitters:
Maximum current at power input: 7.4 amperes.
Output current: 900 mA per channel maximum.
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
RELAY CONTACTS—
30 Vdc, 1 amps resistive.
INPUT/OUTPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
LON COMMUNICATION—
Digital communication, transformer isolated
(78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –67°F to +185°F (–55°C to +85°C).
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
0 to 95% RH, non-condensing.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
CHANNEL ACCURACY—
Zero:
±0.3% full scale from –40°C to +85°C.
Span: ±0.5% full scale from –40°C to +85°C.
DIMENSIONS—
Refer to Figure 6-3.
SHIPPING WEIGHT—
1 pound (0.45 kilograms).
RESPONSE TIME—
1 to 100 LON devices:
101 to 200 LON devices:
201 to 246 LON devices:
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T3C).
Class I, Zone 2, Group IIC (T3).
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
Refer to Appendix D for USCG Approval details.
CE:
®
ATEX:
LON COMMUNICATION—
Digital communication, transformer isolated
(78.5 kbps).
DIMENSIONS—
Refer to Figure 6-3.
ATEX/EMC Directive Compliant.
FM
APPROVED
IECEx:
SHIPPING WEIGHT—
1 pound (0.45 kilograms).
II 3 G.
Ex nA nC IIC T3 Gc.
DEMKO 03 ATEX 135246X.
Tamb = –40°C to +75°C.
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
IECEx ULD 10.0004X.
Ex nA nC IIC T3 Gc.
Tamb = –40°C to +75°C.
CE:
Note: Refer to Appendix C for ATEX and IECEx
approval details and Special Conditions for
Safe Use.
FM
APPROVED
RESPONSE TIME—
Actuates in <0.15 second after acknowledging
an alarm command message.
18.2
< 2 seconds
< 3 seconds
< 4 seconds
ATEX/EMC Directive Compliant.
ATEX:
II 3 G.
Ex nA nC IIC T4 Gc EN60079-29-1.
DEMKO 03 ATEX 136207X.
Tamb = –40°C to +85°C.
FM
APPROVED
®
IECEx:
IECEx ULD 10.0004X.
Ex nA nC IIC T4 Gc.
Tamb = –40°C to +85°C.
6-7
95-8533
Note: Refer to Appendix C for ATEX and IECEx
approval details and Special Conditions for
Safe Use.
Refer to Appendix D for USCG Approval details.
HART INTERFACE MODULE
(HIM)
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
INPUT POWER—
1.0 watt maximum.
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –-67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
See Figure 6-2.
SHIPPING WEIGHT—
0.5 pounds (0.2 kilograms)
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
CE:
ATEX/EMC Directive Compliant.
®
IECEx:
IECEx ULD 10.0004X.
Ex nA IIC T4 Gc.
Tamb = –40°C to +85°C.
10 amperes at
24 Vdc
30 amperes at
24 Vdc
75 amperes at
24 Vdc
POWER CONSUMPTION—
EQ2110PS / EQ2111PS:
EQ2130PS / EQ2131PS:
EQ2175PS / EQ2176PS:
46 Watts
140 Watts
349 Watts
TEMPERATURE RANGE—
Operating: +32°F to +122°F (0°C to +50°C)
Storage:
-40°F to +185°F (-40°C to +85°C)
NOTE
Note: Refer to Appendix C for ATEX and IECEx
approval details and Special Conditions for
Safe Use.
18.2
OUTPUT CURRENT—
EQ2110PS / EQ2111PS:
EQ2130PS / EQ2131PS:
EQ2175PS / EQ2176PS:
DIMENSIONS—
in Inches (Centimeters)
Width
Height Depth
EQ211xPS: 19 (48.3) 7 (17.8) 15 (38.1)
EQ213xPS: 19 (48.3) 14 (35.6) 15 (38.1)
EQ217xPS: 19 (48.3) 14 (35.6) 15 (38.1)
II 3 G.
ATEX
Ex nA IIC T4 Gc.
DEMKO 04 ATEX 136507X.
Tamb = –40°C to +85°C.
FM
®
4 amps at 120 VAC
6 amps at 240 VAC
12 amps at 240 VAC
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
APPROVED
FM
INPUT CURRENT—
60 Hz Models:
EQ2110PS: 4 amps at 120 VAC
EQ2130PS: 11 / 6 / 6 amps at 120 / 208 /
240 VAC
EQ2175PS: 24 / 15 / 12 amps at 120 / 208 /
240 VAC.
®
APPROVED
APPROVED
INPUT VOLTAGE—
Selectable for 120, 208 or 240 vac input power,
±10%.
50 Hz Models:
EQ2111PS:
EQ2131PS:
EQ2176PS:
INPUT/OUTPUT CURRENT—
Operating: 4 -20 mA.
Maximum: 0-30 mA.
FM
EQ21XXPS POWER
SUPPLIES
6-8
Power supplies are designed for
mounting in a standard 19 inch rack.
Optional mounting hardware is available
for floor or wall mount applications.
CERTIFICATION—
FM / CSA: Ordinary locations.
95-8533
EQP2XX0PS(–X) POWER
SUPPLIES
REDUNDANCY MODULE
QUINT–DIODE/40
INPUT VOLTAGE—
EQP2120PS(-B): Auto selectable for 120/220
Vac, –15%, +10%; 60/50 Hz, single phase;
EQP2410PS(-P) Converter: 24 Vdc, –15%,
+10%.
TEMPERATURE RANGE—
Operating: –13°F to +131°F (–25°C to +55°C)
(All Applications)
Storage: –40°F to +185°F (–40°C to +85°C).
INPUT CURRENT—
EQP2120PS(-B):
6.6 A max @ 120 Vac
3.6 A max @ 220 Vac
EQP2410PS(-P):
15.7 A @ max @ 24 Vdc
OUTPUT VOLTAGE—
24.5 Vdc nominal, 24.5 to 28.0 Vdc.
OUTPUT CURRENT—
EQP2120PS(-B):
20 A
EQP2410PS(-P):
10 A
TEMPERATURE RANGE (ALL MODELS)—
Operating: –13°F to +131°F (–25°C to +55°C)
(All Applications)
Storage:
–40°F to +185°F (–40°C to +85°C)
HUMIDITY RANGE—
5 to 95% RH at 25°C, non-condensing.
DIMENSIONS—
In Inches (Centimeters)
Width Height Depth
EQP2120PS(-B): 3.54(9) 5.2(13.0) 5.0(12.5)
EQP2410PS(-P): 3.2(8.0) 5.2(13.0) 5.0(12.5)
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
in Inches (Centimeters)
Width Height Depth
2.4 (6.2) 4 (10.2) 3.3 (8.4)
EQ2230RSP MODULE
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –-67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
See Figure 6-2.
SHIPPING WEIGHT—
0.5 pounds (0.2 kilograms)
NOTE
Power supplies are designed for DIN rail
or panel mounting (–B or –P suffix).
CERTIFICATION—
FM / CSA: Ordinary locations.
USCG:
Refer to Appendix D for details.
18.2
6-9
95-8533
EQ21XXPSM POWER SUPPLY
MONITOR
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc.
EQ2220GFM GROUND
FAULT MONITOR
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
POWER CONSUMPTION—
2.0 watts maximum.
INPUT POWER—
1.0 watt maximum.
MEASUREMENT RANGE—
AC Voltage: 240 vac maximum.
DC Battery Charging Current:
75 amperes
maximum.
OUTPUT—
Form C NO/NC relay contact rated 1 ampere
(resistive) at 30 Vdc maximum.
TEMPERATURE RANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –-67°F to +185°F (–55°C to +85°C).
OUTPUT—
Digital communication, transformer isolated
(78.5 k bps).
TEMPERATURE RANGE—
Operating: +32°F to +122°F (0°C to +50°C)
Storage: –67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
See Figure 6-6.
SHIPPING WEIGHT—
0.5 pounds (0.2 kilograms)
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
See Figure 6-4.
CERTIFICATION—
FM / CSA: Ordinary locations.
9
(22.9)
8.5
(21.6)
J3
J1
2.25
(5.7)
4
(10.2)
B
C
2.5
(6.4)
A2038
Figure 6-4—Dimensions of Power Supply Monitor in Inches
(CM)
18.2
6-10
95-8533
CERTIFICATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
FM
®
APPROVED
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
CE:
ATEX/EMC Directive Compliant.
ATEX:
FM
APPROVED
®
IECEx:
®
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
POWER CONSUMPTION—
DCU with toxic gas sensor/transmitter: 95 mA
max.
II 3 G
Ex nA nC IIC T4 Gc
DEMKO 03 ATEX 136222X
Tamb = –40°C to +85°C
DCU with transmitter and combustible gas
sensor: 180 mA maximum during normal
operation, 500 mA during startup.
IECEx ULD 10.0004X
Ex nA nC IIC T4 Gc
Tamb = –40°C to +85°C
Note:
Refer to Appendix C for ATEX
Approval and Appendix E for CE Mark details
and Special Conditions for Safe Use.
Refer to Appendix D for USCG Approval
details.
2.9
(7.4)
EQ22XXDCU AND
EQ22XXDCUEX DIGITAL
COMMUNICATION UNIT
1.2
(3.0)
INPUTS—
4–20 mA
calibration.
analog
signal,
non-intrusive
OUTPUTS—
Digital communication, transformer isolated
(78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
2.1
(5.3)
1.75
(4.4)
VIBRATION—
FM 6310/6320.
A2237
Figure 6-6—Dimensions of Ground Fault Monitor
in Inches (Centimeters)
18.2
DIMENSIONS—
See Figure 6-5.
6-11
95-8533
FM
PPROVED
FM
APPROVED
EQ24xxNE NETWORK
EXTENDER
CERTIFICATION—
FM / CSA: Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Class II/III, Div. 1 & 2 (for use
with Model STB).
NEMA/Type
4X
(for
use
with Model STB).
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage
will not cause damage to the equipment.
®
POWER CONSUMPTION—
2.2 watts nominal at 24 Vdc, 2.7 watts
maximum.
INPUTS/OUTPUTS—
Digital, transformer isolated (78.5k Baud).
ATEX: 0539
II 2 G
Ex db IIC T4-T6 EN 60079-29-1
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
IP66
Refer to Appendix C for ATEX Approval details.
FM
®
APPROVED
®
Special Conditions for Safe Use (X):
The device has an ambient temperature rating
for performance of –40°C to +75°C.
IEC:
IECEx ULD 10.0010
Ex d IIC T4-T6 Gb
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
Refer to Appendix D for USCG Approval
details.
Refer to Appendix E for CE Mark details.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C)
Storage:
–67°F to +185°F (–55°C to +85°C).
HUMIDITY—
5 to 95% RH at 70°C.
DIMENSIONS—
See Figure 6-7.
FM
APPROVED
CERTIFICATION—
FM / CSA: Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Class II/III, Div. 2, Groups F & G (T4).
NEMA/Type 4X.
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
®
CE:
3.77
(9.6)
ATEX/EMC Directive Compliant.
0539
II 2 G.
ATEX:
Ex db IIC T4-T6
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
IP66
Refer to Appendix C for ATEX Approval details.
FM
APPROVED
1.28
(3.3)
FM
®
APPROVED
5.86
(14.9)
5.2
(13.2)
2.7
(6.9)
IEC:
4.7
(11.9)
3.46
(8.8)
Refer to Appendix D for USCG Approval
details.
Refer to Appendix E for CE Mark details.
A2531
Figure 6-7—Dimensions of Short Cover Junction Box
in Inches (Centimeters)
18.2
IECEx ULD 10.0010
Ex d IIC T4-T6 Gb
T6 (Tamb = –55°C to +50°C)
T5 (Tamb = –55°C to +65°C)
T4 (Tamb = –55°C to +75°C)
6-12
95-8533
EQ3750 ASH ADDRESSABLE
SMOKE & HEAT MODULE
For complete information regarding the ASH
Module, refer to instruction manual number
95-8654.
EQ3760ASM ADDRESSABLE
SMOKE MODULE
For complete information regarding the ASM
Module, refer to instruction manual number
95-8755.
COMBUSTIBLE GAS SENSOR
Refer to the Combustible Gas Sensor
Specification Data sheet, form 90-1041, for
specifications.
ELECTROCHEMICAL
SENSORS
EQ21XXPS POWER SUPPLY
The EQ21xxPS Rectifier / Power Supply has
many inherent advantages such as voltage
regulation, high efficiency, high power factor
and short circuit protection.
These chargers provide separate adjustable
voltages for floating or equalizing lead or
nickel-cadmium cells. An equalize switch is
located on the front panel of the charger for
manual activation or a multi-mode electronic
timer can be used for automatic activation.
Steady state output voltage remains within
+/- 1/2% of the setting from no load to full load
and for AC input voltages within +/- 10% of the
nominal input voltage. The power supply is
internally filtered to be no greater than 32dBrn
(“C” message weighting) and 30 millivolts RMS
for all conditions on input voltage and output
load with or without batteries connected.
This allows the A36D to be used as a battery
eliminator.
Refer to the Electrochemical Gas Sensor
Specifications in the UD10DCU manual (958656) and EQ22xxDCU Specification Data (901118) for additional information.
18.2
6-13
95-8533
Section 7
Ordering Information
CONTROLLER MODEL MATRIX
MODEL
DESCRIPTION
EQ3001
EQP Controller - 246 Nodes
EQ3016
EQP Controller - 16 Nodes
TYPE
MOUNTING OPTION
D
Din Rail
P
Panel Mount
TYPE
COM BOARD 1
N
None
C
ControlNet
D
EtherNet DLR
TYPE
COM BOARD 2
N
None
E
Ethernet Port Expansion
S
Serial Port Expansion
TYPE
APPROVALS*
S
SIL
T
SIL/FM/CSA/ATEX/IECEx
T-C
W
W-C
T plus US Coast Guard
FM/CSA/ATEX/IECEx
W plus US Coast Guard
*Type "APPROVALS" can use one or more letters to designate the approvals of the product.
Some configurations are not available. Check with factory for additional information.
For USCG approved controller models, refer to Appendix D.
NOTE: Contact Customer Service when ordering replacement EQ3XXX Controllers for redundant systems.
EDIO MODEL MATRIX
MODEL
DESCRIPTION
EQ3730
8 Channel Enhanced Discrete Input/Output (EDIO) Module
TYPE
MOUNTING OPTION
D
DIN Rail
P
Panel
TYPE
APPROVALS*
S
SIL
T
SIL/FM/CSA/ATEX/IECEx
W
FM/CSA/ATEX*/IECEx
*Type "APPROVALS" can use one or more letters to designate the approvals of the product.
Some configurations are not available. Check with factory for additional information.
18.2
7-1
95-8533
DCIO MODEL MATRIX
MODEL
DESCRIPTION
EQ3700
8 Channel Discrete Input/Output (DCIO) Module
TYPE
MOUNTING OPTION
D
DIN Rail
P
Panel
TYPE
W
APPROVALS*
FM/CSA/ATEX/IECEx
*Type "APPROVALS" can use one or more letters to designate the approvals of the product.
Some configurations are not available. Check with factory for additional information.
AIM MODEL MATRIX
MODEL
DESCRIPTION
EQ3710
8 Channel Analog Input (AIM) Module
TYPE
MOUNTING OPTION
D
Din Rail
P
Panel
TYPE
APPROVALS*
S
SIL
T
SIL/FM/CSA/ATEX/IECEx
W
FM/CSA/ATEX/IECEx
*Type "APPROVALS" can use one or more letters to designate the approvals of the product.
Some configurations are not available. Check with factory for additional information.
RELAY MODULE MODEL MATRIX
MODEL
DESCRIPTION
EQ3720
8 Channel Relay Module (RM)
TYPE
MOUNTING OPTION
D
Din Rail
P
Panel
TYPE
W
APPROVALS*
FM/CSA/ATEX/IECEx
*Type "APPROVALS" can use one or more letters to designate the approvals of the product.
Some configurations are not available. Check with factory for additional information.
18.2
7-2
95-8533
ORDERING INFORMATION
POWER SUPPLY, DIODE, CONTROLLER, DUCT MOUNT KIT
DEC Part Number
Model
Description
010988-001
EQP2120PS-B
(Replacement)
Phoenix Contact
QUINT–PS-1AC/24DC/20
Panel Mount
010892-001
EQP2410PS-P
Phoenix Contact
QUINT–PS-24DC/24DC/10
Panel Mount
009934-001
Diode Redundancy Module
Phoenix Contact
QUINT–DIODE/40
Panel Mount
007609-269
EQ3XXXPCSW-C
EQP System Controller,
panel mount
009931-001
Q900C1001
Duct Mount Kit
000523-009
000523-009
See description on page D-6
000523-010
000523-010
See description on page D-6
For other USCG Approved EQP System components, refer to Table D-1 or contact Det-Tronics
Customer Service.
Refer to Section 3 of this manual for determining power requirements.
18.2
7-3
95-8533
APPENDIX A
FM APPROVAL DESCRIPTION
FIRE DETECTION & RELEASING
• National Fire Alarm Code performance verified per NFPA 72-2013. Refer to Table A-1 for
device and circuit supervision characteristics.
• See section 2 "Field Devices Flame Detectors" for information regarding Det-Tronics approved
flame detectors and associated manuals. Additional two second response time applied for
system communication.
• I/O Modules EQ3700 DCIO series (Class B IDC/NAC) and EQ3730 EDIO series (Class A or B
IDC/NAC) Reference Table 3-10 for compatible solenoids used for automatic release of preaction and deluge sprinkler and extinguishing systems.
GAS DETECTION
FM Certificate No. FM17US0258X
Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM
6320. Accuracy: ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL. For the Model
PIRECL, refer to the PIRECL manual (form number 95-8526) for further FM gas performance
details.
NOTE: Detector Electronics combustible gas detection K factors are not FM verified.
• H2S Toxic Gas Performance verified 0 to 20, 50 or 100 ppm per FM requirements. Accuracy:
±2 ppm from 0 to 20 ppm, ±10% of concentration from 21 to 100 ppm. Models C7064E4012
and C7064E5012 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups
C and D Hazardous (Classified) Locations per FM 3615. Model C7064E5014 Hydrogen Sulfide
(H2S) Sensors Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous (Classified)
Locations per FM 3615. Operating temperature limits are –40°C to +40°C.
NOTE: Sensor cross sensitivity has not been verified by FM.
• Calibration of the above listed sensors has been FM verified using the respective
EQ22xxDCU, EQ22xxDCUEX, and PIRECL with the Det-Tronics 225130-001 (50% LFL
methane) and/or 227115-001 H2S Calibration Kits.
• The EQ22xxDCU Series can be used with any FM Approved 4–20 mA device including UD10
DCU and CGS.
NOTE
FM Approval of the 4–20 mA input does not include or imply approval of the gas detection
apparatus such as sensors, transmitters, or devices connected to the system. In order to
maintain FM Approval of the system, all 4–20 mA gas detection instruments connected to
the input must also be FM Approved.
NOTE
FM Approval allows the presence and operation of serial/Ethernet communications
software in the Controller (Modbus TCP/IP, Allen Bradley protocols, etc.); however, the
communications functions are not included in the Approval.
18.2
A-1
95-8533
EAGLE QUANTUM PREMIER FIRE AND GAS ALARM CONTROL PANELS:
Hazardous Locations:
Non-Incendive Solutions (Class 1, Div 2):
EQ3900N - See Manual 95-8559
Explosion Proof Solution (Class 1, Div 1):
EQ3900E - See Manual 95-8763
EQ3900RPS Remote Power Supply Enclosure - See Manual 95-8745
EQ3770EIO - Remote I/O Module Enclosure - See Manual 95-8761
Ordinary Locations:
EQ3900G - See Manual 95-8641
18.2
A-2
95-8533
Table A-1—Circuit Classifications
Signaling Path
NFPA 72 Supervision
Local Operating Network (LON)
Signaling Line Circuit (SLC): Class X
Power Distribution Module, Input
Power
Supervised. Loss of power per ANSI/NFPA 72, Cl. 10.6.9
Power Distribution Module,
Controller Power Output
Supervised. Loss of power per ANSI/NFPA 72, Cl. 10.6.9
Power Distribution Module, Field
Device Power Output
Class B
Power Distribution Module, Local
Field Device Power Output
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Power Supply Monitor, Input Power
Supervised. Loss of power per ANSI/NFPA 72, Cl. 10.6.9
Power Supply Monitor, Output
Power
Supervised (via Controller for opens).
Class B
Power Supply Monitor, Charger
Supervised. Loss of charger per NFPA Cl. 10.6.10.6
Power Supply Monitor, Battery
Supervised. Loss of battery per NFPA Cl. 10.6.9
Controller, Digital Input
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Controller, Relay Output
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Controller, Trouble Relay Output
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Controller, 232 Expansion Output
(SIL or Non-SIL)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Controller, Ethernet Expansion
Output (SIL or Non-SIL)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Controller, SLC485 Expansion
Output, including
optional fiber optic equipment (SIL
or Non-SIL)
Class B (Single Channel Single-Mode Fiber)
Class X (Multi-Mode Fiber or Dual Channel Single-Mode Fiber
or Dual Channel Wire)
Redundant Controller Connector,
RS-232 (SIL or Non-SIL)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Relay Module, Output
Unsupervised, for connection with ancillary equipment only.
Enhanced Discrete I/O, Input
(software configurable, SIL or
Non-SIL)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Enhanced Discrete I/O, Output
(software configurable, SIL or
Non-SIL)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Initiating Device Circuit (IDC): Class A or Class B
Notification Appliance Circuit (NAC): Class A or Class B
Supervised Solenoids (Class A or Class B):
Parker (Viking): 11591 NC, 11592 NC, 71395SN2#NJ1NOH111C2,
73218BN4TNLVNOC322C2, 73212BN4TNLVNOC322C2, and
73212BN4TN00N0C111C2
ASCO RedHat: R8210A107, 8210A107, 8210G207, 11601, 11602
Viking PN: HV274608 N.C., HV2740607 N.C.
Kidde-Fenwall: 897494, 895630, 890181
Cat #: 202-749-260563, 202-749-260563
Det-Tronics PN: 00219-209
Ansul: 570537
Macron: 304.209.001
18.2
A-3
95-8533
Table A-1—Circuit Classifications-Continued
Signaling Path
NFPA 72 Supervision
Discrete I/O, Input (software
configurable)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Discrete I/O, Output (software
configurable)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Initiating Device Circuit (IDC): Class B
Notification Appliance Circuit (NAC): Class B
Supervised Solenoids (Class B):
Group B: ASCO T8210A107
Group D: ASCO 8210G207
Group E: Skinner 73218BN4UNLVNOC111C2
Group F: Skinner 73212BN4TNLVNOC322C2
Group G: Skinner 71395SN2ENJ1NOH111C2
Group H: Viking 11601
Analog Input Module (SIL or
Non-SIL)
Initiating Device Circuit (IDC): Class B
IDCGF Input (Channel 2 only)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
ASM/ASH Loop (Smoke & Heat
Loop)
Signaling Line Circuit (SLC): Class A or Class B (single spur)
ASM/ASH Loop (Smoke & Heat
Loop) with Isolators
Signaling Line Circuit (SLC): Class X
ASM/ASH Loop (Smoke & Heat
Loop) with Isolators
Signaling Line Circuit (SLC): Class B (single spur)
ASM/ASH - Addressable Smoke and
Heat Module
Input (software configurable)
ASM/ASH - Addressable Smoke and
Heat Module
Input - Smoke detector inputs
ASM/ASH - Addressable Smoke and
Heat Module
Output (software configurable)
18.2
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Initiating Device Circuit (IDC): Class A
Initiating Device Circuit (IDC): Class A (Apollo)
Unsupervised per ANSI/NFPA 72, Cl. 12.6.9
Notification Appliance Circuit (Apollo): Class A
A-4
95-8533
Figure A-1 (FM Drawing 007545-001)
18.2
A-5
95-8533
APPENDIX B
CSA INTERNATIONAL CERTIFICATION DESCRIPTION
CLASS – 4818 04 – Signal Appliances – System – For Hazardous Locations
CLASS – 4828 01 – Signal Appliances – Combustible Gas Detection Instruments for Hazardous Locations
CLASS – 4828 02 – Signal Appliances – Toxic Gas Detection Instruments for Hazardous Locations
HAZARDOUS LOCATIONS
Eagle Quantum Premier (EQP) System and Components
Class I Division 2 Groups A, B, C & D, T4
Class I Zone 2 IIC, T4, When installed in a suitable CSA Certified labeled Type rated enclosure:
EQ3xxx Controller Series, EQ3700DCIO Series, EQ3710AIM Series, EQ3730EDIO Series, HIM,
EQ2220GFM, EQ2230RSP, EQ3750ASH Series, EQ3760ASM Series, EQ3LTM
Class I Division 2, Groups A, B, C & D, T3C
Class I Zone 2 IIC, T3, When installed in a suitable CSA Certified labeled Type rated enclosure:
EQ3720RM Series
Class I Division 1 Groups B, C & D, T4
Class I Division 2 Groups A, B, C & D, T4
Class II Division 1 Groups E, F & G, T4
Class II Division 2 Groups F & G, T4
Class III Division 1, T4
Class III Division 2, T4, TYPE 4X:
EQ22abDCU Series, EQ22abDCUEX Series, EQ22xxUVHT Series, EQ22xxIDC &
EQ22abIDCGF Series, EQ24xxNE Series, EQ24abPLR Series, EQ25abARM Series,
Q25abSAM Series
EQP System Power Supply(s) and Components
Class I Division 2 Groups A, B, C & D (UL & ULC), When installed in a suitable CSA Certified
labeled Type rated enclosure:
EQP2120PS(-B), EQP2410PS(-P), Diode Redundancy Module
Class I Division 2 Groups A, B, C & D, T3A
Class I Zone 2 IIC, T3, When installed in a suitable CSA Certified labeled Type rated enclosure:
EQ3800PDM
Ordinary Location:
EQ21xxPS, EQ2100PSM
EQP System Enclosure Solutions
Class I Division 1 Groups C & D, T6
Class I Division 2 Groups A, B, C & D, T4
Class II Division 1 Groups E, F & G, T4, Class III Division 1 T4, TYPE 4X:
EQ3900RPS
Class I Division 1 Groups B, C & D, T5
Class I Zone 1 IIB, T5
Class II Division 1 Groups E, F & G, T5
Class III, T5, TYPE 4X:
EQ3900E Series
18.2
B-1
95-8533
Class I Division 1 Groups B, C & D, T6, TYPE 4X:
EQ3770EIO Series
Class I Division 2 Groups A, B, C & D T3A
Class I Zone 2, IIC T3, TYPE 4X:
EQ3900N Series
Ordinary Locations :
EQ3900G Series
EQP System Gas Detector / Sensors Class 4828-01 & 4828-02 (See individual Certificates)
PIRECL® Series, PIR9400 Series, PIRDUCT Series, OPECL Series, LS2000 Series , GT3000 Series
, NTM Series , C7064E Series, CGS Series (Note: EQ22abDCUEX and UD10xxxxxC are required
for use with CGS catalytic sensor.), PIRTB Series, STB Series, UD10 Series.
EQP System Flame Detectors Equipment Class 4818 04 (See individual Certificates)
X3301 Series, X3302 Series, X2200 Series, X9800 Series, X5200 Series
Notes:
Note 1: Any CSA certified Combustible or Toxic Gas Sensor / detector with 4-20mA
(industry standard) output may be used with EQ3710AIM, UD10 and EQ22abDCU.
Note 2: Detector Electronics combustible gas detection K factors are not CSA verified.
Note 3: CSA Certification of the 4-20mA input does not include or imply approval of the gas
detection apparatus such as sensors, transmitters, or devices connected to the system. In order
to maintain CSA Certification of the system, all 4-20mA gas detection instruments connected to the
input must also be CSA Certified.
Note 4: CSA Certification allows the presence and operation of serial/Ethernet communications
software in the Controller (Modbus TCP/IP, Allen Bradley protocols, etc.); however, the
communications functions are not included in the Certification.
18.2
B-2
95-8533
APPENDIX C
ATEX AND IECEX CERTIFICATION
ATEX AND IECEX CERTIFICATION DETAILS
The Eagle Quantum Premier Fire and Gas Detection / Releasing System was tested and certified to
hazardous location and combustible gas performance standards. Refer to Figure C-1 for system
classification details.
The ATEX/IECEx certified Eagle Quantum Premier System field devices EQ22..., EQ24... and
EQ25... are in compliance with the following standards, as applicable:
IEC 60079-0: 2011
EN 60079-0: 2012
IEC/EN 60079-1: 2010
EN 60079-29-1: 2007
EN 60079-29-4: 2010
The ATEX/IECEx certified Ex n modules of the EQP system are in compliance with the following
standards, as applicable:
IEC 60079-0: 6th Edition
EN 60079-0: 2012, A11:2013
IEC 60079-15: 4th Edition
EN 60079-15: 2010
EN 60079-29-1: 2007
EN 60079-29-4: 2010
SPECIAL CONDITIONS FOR SAFE USE
1. The equipment shall only be used in an area of not more than pollution degree 2, as defined in
IEC/EN 60664-1.
2. The equipment shall be installed in an enclosure that provides a degree of protection not less
than IP 54 in accordance with IEC/EN 60079-15. The equipment shall only be accessible with
use of a tool. This provision applies only to Ex n devices.
3. Transient protection shall be provided that is set at a level not exceeding 140% of the peak
rated voltage value at the supply terminals to the equipment.
FOR ALL ATEX/IECEX CERTIFIED EX N MODULES IN THE EQP SYSTEM, THE FOLLOWING SPECIAL CONDITIONS FOR SAFE USE APPLY:
The ambient temperature range is limited for EQ3XXX:
From –40°C to +70°C if any of the output relays 1-7 (terminals 21-41) is used (energized).
From –40°C to +80°C if all output relays 1-7 (terminals 21-41) remain open-contacted and
de-energized.
For compliance to EN 60079-29-1/-4, the relevant Ex n module must be used with gas detection
apparatus that are certified for compliance to EN60079-29-1/-4 and that provide a suitable linear
4-20 mA output, relay contact output or LON communication output relative to the %LFL of the
available gas in the area of the gas detection apparatus. See the Manual for details on the required
connection parameters.
The EQP Ex n modules shall be used in an area of no more than pollution degree 2 conforming to
IEC/EN 60664-1, and in an enclosure with a tool removable cover that complies with all relevant
requirements of IEC/EN 60079-15, rated at least IP54, and shall be connected to supply circuits
where the rated voltage cannot be exceeded by 140% caused by transient disturbances.
18.2
C-1
95-8533
PERFORMANCE TESTING TO EN 60079-29-1: 2007 AND EN 60079-29-4: 2010
The measuring function of the EQ3XXX Controller, according to Annex II paragraph 1.5.5, 1.5.6
and 1.5.7 of the Directive 94/9/EC, was covered in this Type Examination Certificate in the following
configurations:
4. Controller Model EQ3XXX with EQ3710AIM or EQ3700DCIO or EQ3730EDIO or EQ22XXDCU
(tested as a stand-alone control unit with a calibrated linear 4-20mA simulator input signal or
relay contacts (as applicable).
5. Controller Model EQ3XXX with CTB and PIRECL (tested as a gas detection system with methane
applied to the PIRECL).
6. Controller Model EQ3XXX with UD10/DCU Emulator and CGS Conditioning Board, in
combination with the Det‑Tronics gas sensor Model CGS (tested as a gas detection system
with methane applied to the CGS).
7. Controller Model EQ3XXX with OPECL or LS2000.
FOR THE ATEX CERTIFIED EAGLE QUANTUM PREMIER SYSTEM FIELD DEVICES
EQ22XXDCU AND EQ22XXDCUEX, THE FOLLOWING SPECIAL CONDITION FOR SAFE
USE APPLIES:
The field devices EQ22XXDCU and EQ22XXDCUEX have an ambient temperature rating for
performance of –40°C to +75°C.
IMPORTANT NOTE
All applied gas detectors must be ATEX certified to EN60079-29-1/-4 and the configuration
must comply with the gas performance parameters stated in the Installation Manual.
18.2
C-2
95-8533
APPENDIX D
EAGLE QUANTUM PREMIER SYSTEM
MARINE APPLICATIONS DNV AND
U.S. COAST GUARD APPROVAL NUMBER 161.002/49/0
Approved System Description
Refer to Table D-1 for a complete list of DNV and USCG approved equipment.
Table D-1— List of Approved Equipment
Equip.
No.
Manufacturer
Equipment type
Series/Model Description
1
Det-Tronics
EQ3XXX Controller
EQ3XXXP N(C) N(S) W(T)-C, panel mount only;
installed inside Rittal cabinet or equivalent NEMA 12
enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
2
Det-Tronics
EQ3LTM
LON Termination
Module
Optional module used in the Controller Redundancy
configuration, installed inside Rittal cabinet or equivalent
NEMA 12 enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
3
Det-Tronics
EQ3710AIM
Analog Input
Module
EQ3710D(P) W, installed inside Rittal cabinet or
equivalent NEMA 12 enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
4
Det-Tronics
EQ3720RM
Relay Module
EQ3720D(P) W, installed inside Rittal cabinet or
equivalent NEMA 12 enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
5
Det-Tronics
EQ3730EDIO
Enhanced Discrete
Input/Output
Module
EQ3730D(P) W(T); installed inside Rittal cabinet or
equivalent NEMA 12 enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
6
Det-Tronics
EQ3750ASH
Addressable
Smoke & Heat
Module
EQ3750ASHP W; panel mount only, installed inside Rittal
cabinet or equivalent NEMA 12 enclosure in controlled
environments; NEMA 4X enclosure for open area
installations.
7
Det-Tronics
EQ24xxNE Network
Extender Module
EQ245(6) 3NE;
Enclosure material: 5 – Aluminum, 6 –SS.
8
Det-Tronics
EQ22xxDCUEX
Digital
Communication
Unit, Combustible
EQ225(6)3DCUEX;
Enclosure material: 5 – Aluminum, 6 –SS.
(Uses CGS Gas Sensor)
9
Det-Tronics
CGS Combustible
Gas Sensor
CGSS1A6C2R1X
(Used with the EQ22xxDCUEX)
10
Det-Tronics
PIRECLAx4
PointWatch
Hydrocarbon Gas
Detector
PIRECLA (1) 4 A (B) 1 (2) W (T) 1 (2)
Det-Tronics
PIRECLAx4
PointWatch
Hydrocarbon Gas
Detector “Duct
Mount”
PIRECLA (1) 4 A (B) 1 (2) W (T) 1 (2);
with DEC Q900C1001 Duct Mount kit
GT3000
Toxic Gas Detector
Model GTXS N (M) W 4 (5) Transmitter
with Model GTSH2S 20P (50P,100P) Sensor
or
Model GTSO2 25V Sensor
or
Model GTSCO 100P (500P) Sensor
11
12
18.2
Det-Tronics
D-1
95-8533
Table D-1— List of Approved Equipment (Continued)
Equip.
No.
Manufacturer
Equipment type
Series/Model Description
13
Det-Tronics
UD10 Universal
Display
UD10A (S) 5N (5M) 25 (28) W 2
14
Det-Tronics
X3301
Multispectrum
Flame Detector
X3301A (S) 4N (4M) 11 (13, 14, 23) W (T) 1 (2) ;
with Q9033A Al (Q9033B SS) swivel
15
Det-Tronics
X3302
Multispectrum
Flame Detector
X3302A (S) 4N (4M) 11 (13, 14, 23) W 1 (2);
with Q9033A Al (Q9033B SS) swivel
16
Det-Tronics
STB Sensor
Termination Box
STB4 (5) A (S) 2N (2U, 3N, 5N, 6N) W
(Used with the Fenwal DAF Vertical Heat Detector)
17
Det-Tronics
EQ2220GFM
Ground Fault
Monitor
EQ2220GFM is installed in the same enclosure
with EQ3XXX Controller
18
Phoenix
Contact
(Germany)
EQP2120PS-B
Power Supply
(Discontinued)
Model Quint PS-100-240VAC/24Vdc/20;
panel mount only, installed in the same enclosure
with EQ3XXX Controller
19
Phoenix
Contact
(Germany)
EQP2120PS-B
Power Supply
(Replacement)
Model QUINT PS-1AC/24 DC/20
panel mount only, installed in the same enclosure
with EQ3XXX Controller
21
Phoenix
Contact
(Germany)
EQP2410PS-P
Converter
Model QUINT PS-24 DC/24 DC/10
panel mount only, installed in the same enclosure
with EQ3XXX Controller
22
Phoenix
Contact
(Germany)
QUINTDIODE/40Diode
Redundancy
Module
Model QUINT-DIODE/40; panel mount only;
installed in the same enclosure with EQ3XXX Controller
and Approved Phoenix Power Supplies
23
Kidde-Fenwal
(Fenwal)
DAF
Vertical Heat
Detector
Model 12-E27121-020-xx rated 140°F (60°C) {160°F
(71°C), 190°F (88°C), 225°F (107°C)};
used with STB Sensor Termination Box, item 15
24
Fenwal
THD-7052
Heat Detector
Uses 2-wire base 2WRLT.
25
Fenwal
CPD-7054
Ionization Type
Smoke Detector
Uses 2-wire base 2WRLT.
26
Fenwal
PSD-7157 and
PSD-7157D
Photoelectric Type
Smoke Detectors
Uses 2-wire base 2WRLT.
27
Fenwal
MT-12/24-R Horn
24 Vdc model; installed in Fenwal IOB-R box.
28
Fenwal
MTWP-2475W – FR
Horn/Strobe
Multitone Weatherproof Horn-Strobe;
installed in Fenwal IOB-R box.
29
Fenwal
Manual Call
Stations Series
3300
Model 84-330001-002 pull station;
uses Fenwal SGB-32S interior surface mount backbox
(compatible mounting with B-11).
30
Fenwal
RA-911 Remote
Indicator
Remote indicator for use with Fenwal Heat
or Smoke detectors.
31
MEDC (UK)
Manual Fire Alarm
Call Point PB Range
Model PB-UL-4C-6C-4-DC-D-7-R call point
18.2
D-2
95-8533
Table D-1— List of Approved Equipment (Continued)
Equip.
No.
Manufacturer
Equipment type
Series/Model Description
32*
Cooper
Crouse Hinds
CCH ETH 2416
Horn
Uses CCH EAJC26 conduit outlet box with cover,
3/4 NPT hub size.
33
Applied
Strobe
Technology
(Canada)
AST-4-1030 Strobe
AST-4-10-30-DC-CL-CM-75-ULC;
with clear lenses
34
Air Products
&
Controls
SL-2000-P
Duct Smoke
Detector
SL-2000-P; installed in Hoffman LWC204015SS6
NEMA 4X enclosure; uses Apollo 55000-328A
photoelectric head w/ RW-268A base.
35
Apollo Fire
Detectors
Ltd.
Discovery
Ionization Smoke
Detector
Apollo P/N 58000-550NA
(with 4" Base Model P/N 45681-210)
36
Apollo Fire
Detectors
Ltd.
Discovery Optical
Smoke Detector
Apollo P/N 58000-650NA
(with 4" Base Model P/N 45681-210)
37
Apollo Fire
Detectors
Ltd.
Discovery
Multisensor
Detector
Apollo P/N 58000-750NA
(with 4" Base Model P/N 45681-210)
38
Apollo Fire
Detectors
Ltd.
Discovery Heat
Detector
Apollo P/N 58000-450NA
(with 4" Base Model P/N 45681-210)
39
Apollo Fire
Detectors
Ltd.
XP95A Sounder
Control Module
Apollo P/N 55000-825NA
40
Apollo Fire
Detectors
Ltd.
Mini Switch Monitor
Apollo P/N 55000-765NA**
41
Apollo Fire
Detectors
Ltd.
Priority Mini Switch
Monitor
Apollo P/N 55000-765NA**
* Horn item 32 is for use in gas applications only.
** The device type depends on the priority switch setting on the device.
NA = North American Approvals
18.2
D-3
95-8533
IMPORTANT
The EQP2120PS-B Power Supply providies EQP System devices with power from input supply 120
to 220 Vac. The EQP2120PS-B Power Supply is used in pairs where primary source of input supply
is connected to one and the secondary source is connected to the other. Use of these power
supplies may provide the source of the secondary supply. The EQP2410PS-P Converter provides
the EQP system with power from input supply 24 Vdc and provides the source if secondary supply
only.
NOTE
The customer may provide other sources of the secondary supply such as secondary
source batteries, their supervision or charging, or UPS. Per NFPA 72-2013 requirements,
such power supply related requirements must be separately provided for and be accepted
by the local Authority Having Jurisdiction (AHJ).
HAZARDOUS LOCATIONS
Refer to Figure D-1 (Drawing 007545-001) for System Classification details.
SYSTEM SPECIFICATION
EQP2120PS-B POWER SUPPLY (DISCONTINUED)—
Number of units:
16 (8 pairs) max
Input voltage:
120 – 220 Vac, -15%, +10%, 60/50 Hz single phase
Output voltage:
Nominal–
24.5 Vdc ± 1% Vdc
Range–
24.5….28.0 Vdc
Input current:
Vout = 24.5 Vdc: 4.9 Amps @ 120 Vac
2.9 Amps @ 220 Vac.
Vout = 28.0 Vdc: 5.6 Amps @ 120 Vac
3.2 Amps @ 220 Vac.
Output current, each:
20 A
EQP2120PS-B POWER SUPPLY (REPLACEMENT)—
Number of units:
16 (8 pairs) max
Input voltage:
120 – 220 Vac, -15%, +10%, 60/50 Hz single phase
Output voltage:
Nominal–
24.5 Vdc ± 1% Vdc
Range–
24.5….28.0 Vdc
Input current:
6.6 A max @120 Vac
3.6 A max @220 Vac.
Output current, each:
20 A
EQP2410PS-P CONVERTER—
Number of units:
16 (8 pairs) max
Input voltage:
24 Vdc, -15%, +10%
Output voltage:
Nominal–
24.5 Vdc ± 1% Vdc
Range–
24.5….28.0 Vdc
Input current:
15.7 A max @ 24 Vdc.
Output current, each:
10 A
18.2
D-4
95-8533
QUINT-DIODE/40 REDUNDANCY MODULE
Number of units:
8 (2 Power Supplies can be connected to each module) max
Input voltage:
24.5….28.0 Vdc
IMPORTANT
The output voltage is adjustable. An even current distribution must be ensured by precisely
setting all power supply units that are operated in parallel to the same output voltage ±10
mV.
IMPORTANT
To ensure symmetrical current distribution it is recommended that all cable connections
from all power supply units/diode redundancy modules to the power distribution bus are the
same length and have the same cross section.
POWER REQUIREMENT—
Refer to Section 6 of this manual and individual device manuals for details.
NOTE
The Power Supplies, Converter, and Diode Redundancy Module electrical specifications
for EQP marine applications represent a reduction in the rating range with respect to that
specified by the manufacturer. The manufacturer’s published electrical specifications may
be viewed as reference only.
TEMPERATURE AND HUMIDITY RANGE—
See Table D-2 for details.
NOTE
The operating temperature and relative humidity specification of EQP System components
including Power Supplies, Converter, and Diode Redundancy Module in EQP marine
applications represent a reduction in the rating range for some components and an
increase in the rating range for other components with respect to that specified by their
manufacturers. The manufacturer’s published operating temperature and relative humidity
specifications may be viewed as reference only.
INSTALLATION—
The EQP2120PS-B Power Supply, EQP2410PS-P Converter, and Diode Redundancy Module are
Panel mounted and intended to be installed within the same cabinet as the EQ3XXX Controller
of the EQP System. Note: Ensure sufficient convection. Refer to Phoenix Contact manuals as
listed below for additional installation and mounting details. For other EQP System components
installation, operation and maintenance refer to appropriate sections of this manual and to
individual device manuals.
18.2
D-5
95-8533
NOTE
SHCS # 10-24 SST screws are recommended for the Power Supply and Diode
Redundancy Module panel mounting.
NOTE
Terminal End Brackets DEC P/N 000133-517 are recommended for use with EQ371(2)(3)0D
(DIN rail mount) and EQ2220GFM Modules.
POWER SUPPLY SUPERVISION—
The EQP2120PS-B Power Supply and EQP2410PS-P Converter shall be monitored for Trouble.
The power supply provides an internal relay contact DC OK signal output, floating. All power
supply unit relay contacts shall be connected in series and connected to the EQ3730EDIO input. A
Trouble signal will be initiated in case of a power supply failure. The Trouble signal will not identify
the specific power supply unit that failed. See Figure D-2 for connecting diagram.
EQP SYSTEM MODEL 000523-009 & 000523-010
• The System consists of:
1 x EQP2120PS-B Power Supply, primary
2 x EQP2410PS-P Converter, secondary
2 x QUINT–DIODE/40 Redundancy module
1 x EQ2220GFM Ground Fault Monitor
1 x EQ3XXX Controller (000523-009)
0 x EQ3XXX Controller (000523-010)
0 x EQ3710AIM Module & 1 x EQ3730EDIO Module (000523-009)
2 x EQ3710AIM Modules & 2 x EQ3730EDIO Modules (000523-010)
• The System is mounted within 60H x 36W x 16D Stainless Steel (type 316), NRTL labeled
NEMA 4X rated enclosure. The enclosure shall be lockable by key lock or padlock.
• EQP system models 000523-009 & 000523-010 are suitable for Cl I, Div. 2, GRPS A, B, C & D
(T4); Cl I, Zone 2, GRP IIC (T4) Hazardous (Classified) Locations; Tamb = –20°C to +49°C.
• Modifications to enclosure (such as conduit entry holes, windows etc.) are permitted when
implemented by the manufacturer of the enclosure.
18.2
D-6
95-8533
ORDERING INFORMATION
DEVICES MARKED WITH USCG INSIGNIA
Model
Description
EQP2120PS-B
(Discontinued)
Phoenix Contact
QUINT–PS-100-240AC/24DC/20 Panel Mount
EQP2120PS-B
(Replacement)
Phoenix Contact
QUINT–PS-1AC/24DC/20
Panel Mount
EQP2410PS-P
Phoenix Contact
QUINT–PS-24DC/24DC/10
Panel Mount
Diode Redundancy Module
Phoenix Contact
QUINT–DIODE/40
Panel Mount
EQ3XXXP N(C) N(S) W(T)-C
EQP System Controller,
panel mount
Q900C1001
Duct Mount Kit
000523-009
See description on page D-6
000523-010
See description on page D-6
For other USCG Approved EQP System components, refer to Table D-1 or contact Det-Tronics
Customer Service.
Refer to Section 3 of this manual for determining power requirements.
USCG insignia marked on the controller and power supplies indicates USCG certification of a
system made-up of components in Table D-1.
18.2
D-7
95-8533
Table D-2—Temperature and Humidity Ranges
Temperature & RH Non-Condensing
Installation Category
Controlled
environment
Installation in
consoles,
housings, etc.;
Non-weather
protected or cold
locations
Weather exposed
areas (Salt mist)
EQ3XXX Controller
with or without
EQ3LTM Module
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
2*
EQ3710AIM
Analog Input Module
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
3*
EQ3720RM
Relay Module
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
4*
EQ3730EDIO
Enhanced
DiscreteInput/Output
Module
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
5
EQ3750ASH
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
EQ3760ASM
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
6
EQ24xxNE
Network Extender
Module
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
7
EQ22xxDCUEX Digital
Communication Unit,
Combustible
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
8
CGS Combustible Gas
Sensor
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
9
PIRECLAx4
PointWatch
Hydrocarbon Gas
Detector
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
10
PIRECLAx4
PointWatch
Hydrocarbon Gas
Detector “Duct Mount”
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
11
GT3000
Toxic Gas Detector
0°C to +50°C
5-95%RH
-20°C to +50°C
5-95%RH
-20°C to +50°C
5-95%RH
12
UD10 Universal Display
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
13
X3301
Multispectrum Flame
Detector
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
14
X3302
Multispectrum Flame
Detector
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
15
STB
Sensor Termination Box
0°C to +55vC
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
Equip.
No.
Product
1*
18.2
D-8
95-8533
Table D-2—Temperature and Humidity Ranges (Continued)
Temperature & RH Non-Condensing
Installation Category
Controlled
environment
Installation in
consoles,
housings, etc.;
Non-weather
protected or cold
locations
Weather exposed
areas (Salt mist)
EQ2220GFM
Ground Fault Monitor
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
17*
EQP2120PS-B
Power supply
0°C to +55°C
5-95%RH
-25°C to +55°C
5-95%RH
-25°C to +55°C
5-95%RH
19*
EQP2410PS-P
Converter
0°C to +55°C
5-95%RH
-25°C to +55°C
5-95%RH
-25°C to +55°C
5-95%RH
20*
QUINT-DIODE/40Diode
redundancy
module
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +55°C
5-95%RH
21
DAF Vertical Heat
Detector
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
22
THD-7052
Heat Detector
0°C to +55°C
5-95%RH
N/A
N/A
23
CPD-7054
Ionization Type
Smoke Detector
0°C to +55°C
5-95%RH
N/A
N/A
24
PSD-7157 and
PSD-7157D
Photoelectric Type
Smoke Detectors
0°C to +55°C
5-95%RH
N/A
N/A
25
MT-12/24-R Horn
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
N/A
26
MTWP-2475W – FR
Horn/Strobe
0°C to +55°C
5-95%RH
-25°C to +55°C
5-95%RH
N/A
27
Manual Call
Stations
Series 3300
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
N/A
28
RA-911
Remote Indicator
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
N/A
29
Manual Fire
Alarm Call Point
PB Range
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
30
CCH ETH 2416 Horn
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
Equip.
No.
Product
16*
18.2
D-9
95-8533
Table D-2—Temperature and Humidity Ranges (Continued)
Temperature & RH Non-Condensing
Installation Category
Controlled
environment
Installation in
consoles,
housings, etc.;
Non-weather
protected or cold
locations
Weather exposed
areas (Salt mist)
AST-4-1030 Strobe
0°C to +55°C
5-95%RH
-25°C to +70°C
5-95%RH
-25°C to +70°C
5-95%RH
32
SL-2000-P Duct Smoke
Detector
0°C to +55°C
5-95%RH
0°C to +70°C
5-95%RH
0°C to +70°C
5-95%RH
33
Discovery Ionization
Smoke Detector
5°C to +55°C
5-95%RH
N/A
N/A
34
Discovery Optical
Smoke Detector
5°C to +55°C
5-95%RH
N/A
N/A
35
Discovery Multisensor
Detector
5°C to +55°C
5-95%RH
N/A
N/A
36
Discovery Heat Detector
5°C to +55°C
5-95%RH
N/A
N/A
37
XP95A Sounder Control
Module
5°C to +55°C
5-95%RH
N/A
N/A
38
Mini Switch Monitor
5°C to +55°C
5-95%RH
N/A
N/A
39
Priority Mini Switch
Monitor
5°C to +55°C
5-95%RH
N/A
N/A
Equip.
No.
Product
31
* For use in controlled environment, install in NEMA 12 rated enclosure or cabinet.
For use in non-weather protected, cold and salt mist exposed areas, install in NEMA 4X stainless
steel enclosure or cabinet.
18.2
D-10
95-8533
18.2
D-11
95-8533
TO EDIO
A2555
13
14
QUINT-PS
PHOENIX
DC
OK
14
DC
OK
+
13
+
–
L
N
13
14
QUINT-PS
PHOENIX
QUINT-PS
PHOENIX
+
N
L
PS
–
PS
+
–
–
DC
OK
+
+
–
–
N
L
13
14
QUINT-PS
DC
OK
PHOENIX
PS n
+
+
–
–
Figure D-2—Power Supply and Converter Relays Wired in Series for Trouble Monitoring (up to 16 Power Supplies/Converters)
No supervision is necessary, since the EDIO modules must be installed in the same cabinet with EQP21X0PS
and EQP2410PS.
Note: Contacts are closed during normal operation. The circuit shall be wired to an input on the EQP system (EDIO).
In Logic, the selected input must be inverted and used to activate an alarm trigger gate, which initiates a
fault message on the Controller and activates the fault relay output.
N
L
PS 1
95-8533
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110 th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2017 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.