Servomex FluegasExact (2700D) Combustion Gas Analyser Service Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
COMBUSTION ANALYSERS SERVOTOUGH FluegasExact (2700D) Combustion Gas Analyser Service Manual Part Number: Revision: Language: 02700002D 0 UK English This page intentionally blank SERVOTOUGH FluegasExact Service Manual TABLE OF CONTENTS 1  INTRODUCTION ................................................................................................ 1  1.1  1.2  1.3  1.4  1.5  1.6  1.7  1.8  1.9  1.10  Scope of this Manual .......................................................................................... 1  Safety Information ............................................................................................... 1  Service Philosophy ............................................................................................. 1  General Description ............................................................................................ 1  Location of External Components....................................................................... 4  Introduction to User Interface ............................................................................. 6  Displaying Faults or Alarms .............................................................................. 11  Displaying Diagnostics ...................................................................................... 12  Displaying Fault or Alarm Histories................................................................... 12  Software Revision History ................................................................................. 13  2  EQUIPMENT OVERVIEW ................................................................................ 14  2.1  2.1.1  Mechanical Overview ........................................................................................ 14  Sensor Head ..................................................................................................... 14  2.1.2  2.1.3  2.2  2.2.1  Flow Alarm Relay Box....................................................................................... 24  Control Unit ....................................................................................................... 26  Electrical Overview ........................................................................................... 28  Control Unit PCB............................................................................................... 28  2.2.2  Sensor Head Terminals PCB ............................................................................ 32  2.3  2.3.1  2.3.2  2.3.3  2.4  2.5  Operating Principles.......................................................................................... 34  Zr703 Oxygen Sensor Module .......................................................................... 34  Tfx1750 Combustibles Transducer Module ...................................................... 35  1760 Flow Alarm Sensor Module ...................................................................... 38  Electrical Connections ...................................................................................... 39  Sample Connections ......................................................................................... 48  3  SPARES LIST ................................................................................................... 49  3.1  3.2  3.3  3.4  3.5  Control Unit Spares........................................................................................... 49  Sensor Head Spares......................................................................................... 50  Flow Alarm Relay Box Spares .......................................................................... 51  Sample Probes ................................................................................................. 52  Manuals ............................................................................................................ 53  4  FAULT FINDING ............................................................................................... 54  4.1  4.2  Introduction ....................................................................................................... 54  Fault and Alarm Messages ............................................................................... 55  2.1.1.1  2.1.1.2  2.2.1.1  2.2.1.2  2.2.1.3  2.2.1.4  2.2.1.5  2.2.1.6  2.2.1.7  2.2.2.1  2.2.2.2  2.2.2.3  2.2.2.4  2.2.2.5  02700002D/0 Sensor Compartment ........................................................................................... 15  Terminal Compartment ......................................................................................... 22  Power Supplies and Relay Outputs ...................................................................... 28  Microcontroller ...................................................................................................... 28  Analogue Current Outputs .................................................................................... 29  ADC Subsystem ................................................................................................... 29  Zirconia Sensor Electronics .................................................................................. 30  Flow Alarm Sensor Electronics............................................................................. 30  Combustibles Sensor Electronics ......................................................................... 31  Power Supply ....................................................................................................... 32  Thermocouple Amplifier ....................................................................................... 32  Sensor Head Temperature Control ...................................................................... 32  Sensor Head Temperature Monitor ...................................................................... 33  Solenoid Valve Interlocks ..................................................................................... 33  i SERVOTOUGH FluegasExact Service Manual 4.3  4.4  4.5  4.5.1  4.5.2  4.5.3  4.5.4  4.5.5  4.6  4.6.1  4.6.2  4.6.3  4.6.4  4.6.5  4.6.6  4.6.7  4.7  4.7.1  4.7.2  4.7.3  4.7.4  4.7.5  Diagnostic Values ............................................................................................. 57  Fault Symptoms Shortcut Guide ....................................................................... 59  Initial Inspection / Start-up Problems ................................................................ 60  Initial Checks ..................................................................................................... 60  Control Unit AC Power Supply Checks............................................................. 61  Control Unit Display and DC Power Supply Checks ........................................ 63  Keypad Checks ................................................................................................. 65  Heater Checks .................................................................................................. 65  Measurement Problems .................................................................................... 74  Definitions ......................................................................................................... 74  Discussion ......................................................................................................... 75  Oxygen Measurement Checks ......................................................................... 77  Combustibles Measurement Checks ................................................................ 79  Flow Alarm Measurement Checks .................................................................... 81  Pneumatics System Checks ............................................................................. 85  Aspirator Interlock Failure ................................................................................. 87  Analyser Problems ............................................................................................ 88  Analogue (mA) Output Failure .......................................................................... 89  Relay Output Failure ......................................................................................... 91  Auto Calibration Failure .................................................................................... 91  Blow Back Failure ............................................................................................. 93  Analyser Does Not Keep Correct Time or Date ................................................ 93  5  PARTS REPLACEMENT PROCEDURES ....................................................... 94  5.1  5.2  5.3  5.4  5.5  5.6  5.7  5.8  5.9  5.10  5.11  5.12  5.13  5.14  5.15  5.16  5.17  5.18  5.19  Control Unit Access .......................................................................................... 94  Control PCB Removal and Replacement ......................................................... 95  Control Unit Transformer Removal and Replacement...................................... 99  Firmware Installation ....................................................................................... 100  Display Removal and Replacement................................................................ 101  Keypad Removal and Replacement ............................................................... 103  Sensor Head and Terminal Box Cover Removal and Replacement .............. 103  Terminals PCB Removal and Replacement ................................................... 107  Solenoid Valve Removal and Replacement ................................................... 111  Solid State Relay Removal and Replacement ................................................ 111  Zirconia Cell Removal and Replacement ....................................................... 112  Combustibles Cell Removal and Replacement .............................................. 114  Flow Alarm Removal and Replacement ......................................................... 116  Cell Connector Removal and Replacement ................................................... 120  Aspirator Removal and Replacement ............................................................. 122  Internal Filter / Sintered Flame Arrestor Removal and Replacement ............. 123  Thermostat Removal and Replacement ......................................................... 124  Thermistor Removal and Replacement .......................................................... 125  Band Heater Removal and Replacement ....................................................... 125  APPENDIX A  DETAILED ANALYSER PERFORMANCE TESTING .................................... 127  A.1  A.2  A.3  A.4  A.5  A.6  A.7  A.8  A.9  A.10  A.11  A.12  ii Notes and Conditions...................................................................................... 127  Gas Samples Required ................................................................................... 127  Visual Inspection ............................................................................................. 128  Sensor Head Leak Test .................................................................................. 129  Interconnection Tests...................................................................................... 129  Initial Power-Up............................................................................................... 129  Analogue Output Span Setup ......................................................................... 129  Relay Operation Test ...................................................................................... 130  Sensor Head Temperature Control................................................................. 130  Sensor Head Sample Flow and Vacuum Test ................................................ 130  Combustibles Sensor Zero Adjustment .......................................................... 131  Sensor Calibration .......................................................................................... 131  02700002D/0 SERVOTOUGH FluegasExact Service Manual APPENDIX B  ANALYSER SOFTWARE ‘SUPER-CALIBRATION’ MODE ........................... 132  B.1  B.2  B.3  B.4  B.5  B.6  B.7  02700002D/0 Introduction ..................................................................................................... 132  Menu Structure ............................................................................................... 132  Accessing Super-Calibration .......................................................................... 132  Configuring the Combustibles Sensor ............................................................ 133  Setting the Display Precision of the Combustibles Measurement .................. 134  Returning to Factory Default Settings ............................................................. 135  Exiting Super-Calibration ................................................................................ 135  iii SERVOTOUGH FluegasExact Service Manual LIST OF FIGURES Figure 1.1 FluegasExact Product Components ......................................................................... 2  Figure 1.2 Sensor Head Overview ............................................................................................. 4  Figure 1.3 Control Unit Overview ............................................................................................... 5  Figure 1.4 FluegasExact Keypad Display .................................................................................. 6  Figure 1.5 Menu Structure A ...................................................................................................... 8  Figure 1.6 Menu Structure B ...................................................................................................... 9  Figure 1.7 Menu Structure C .................................................................................................... 10  Figure 2.1 Sensor Head Overview ........................................................................................... 14  Figure 2.2 Dual Sensor Assembly ............................................................................................ 16  Figure 2.3 Dual Sensor Head Flow Schematic ........................................................................ 17  Figure 2.4 Dual Sensor Head with Flow Alarm Flow Schematic .............................................. 18  Figure 2.5 O2 Sensor Head Flow Schematic............................................................................ 19  Figure 2.6 O2 Sensor Head with Flow Alarm Flow Schematic ................................................. 20  Figure 2.7 COe Sensor Head Flow Schematic ......................................................................... 21  Figure 2.8 Sensor Head Terminal Enclosure Detail (Dual Configuration) ............................... 22  Figure 2.9 Sensor Head with Flow Alarm Terminal Enclosure Detail (Dual Configuration) ..... 23  Figure 2.10 Flow Alarm Relay Box ........................................................................................... 24  Figure 2.11 Flow Alarm PCB Assembly .................................................................................. 25  Figure 2.12 Control Unit Overview ........................................................................................... 27  Figure 2.13 Zirconia Sensor Construction ................................................................................ 34  Figure 2.14 Tfx1750 Sensor Construction ............................................................................... 36  Figure 2.15 Tfx1750 Sensor Element Detail ............................................................................ 37  Figure 2.16 1750 Flow Alarm Sensor Construction ................................................................. 38  Figure 2.17 Oxygen Sensor Only Interconnection Wiring Schematic ...................................... 40  Figure 2.18 Combustibles Sensor Only Interconnection Wiring Schematic ............................ 42  Figure 2.19 Dual Sensor Interconnection Wiring Schematic ................................................... 44  Figure 2.20 Flow Alarm Relay Box Interconnection Wiring Schematic .................................... 46  Figure 2.21 Sensor Head Sample Connections ....................................................................... 48  Figure 4.1 Initial Checks ........................................................................................................... 60  Figure 4.2 Control Unit AC Power Supply Checks ................................................................... 61  Figure 4.3 Display and DC Power Supply Checks ................................................................... 63  Figure 4.4 Initial Heater Checks ............................................................................................... 66  Figure 4.5 Sensor Head Heater Checks .................................................................................. 67  Figure 4.6 Thermistor Temperature Curve ............................................................................... 69  Figure 4.7 Zirconia Sensor Heater Checks .............................................................................. 70  Figure 4.8 COe Sensor Heater Checks.................................................................................... 72  Figure 4.9 Oxygen Measurement Checks ................................................................................ 77  Figure 4.10 Combustibles Measurement Checks .................................................................... 79  Figure 4.11 Flow Alarm Amplifier Board................................................................................... 82  Figure 4.12 Flow Alarm Relay Board ....................................................................................... 83  Figure 4.13 Pneumatics System Checks ................................................................................. 85  Figure 4.14 Final Analyser Checks .......................................................................................... 88  Figure 4.15 Analogue Output Checks ...................................................................................... 89  Figure 4.16 Relay Output Checks ............................................................................................ 91  Figure 5.1 Control Unit Access................................................................................................. 94  Figure 5.2 Control Unit Internals .............................................................................................. 96  Figure 5.3 Measurement Transducer DIP Switch Configurations ............................................ 98  Figure 5.4 Control Unit Transformer Detail .............................................................................. 99  Figure 5.5 Display and Keypad Mounting Details .................................................................. 102  Figure 5.6 Sensor Head Overview ......................................................................................... 104  Figure 5.7 Sensor Head Terminal Enclosure Detail (without Flow Alarm) ............................. 108  Figure 5.8 Zirconia Sensor Installation Details ....................................................................... 113  Figure 5.9 Combustibles Sensor Installation Details.............................................................. 115  Figure 5.10 Flow Alarm Installation Details ............................................................................ 117  Figure 5.11 Flow Alarm Signal Amplifier Board Installation Details ....................................... 118  Figure 5.12 Dual Sensor Configuration Layout ...................................................................... 120  iv 02700002D/0 SERVOTOUGH FluegasExact Service Manual LIST OF TABLES Table 2.1 Interconnecting Cable Requirements ....................................................................... 39  Table 2.2 Oxygen Sensor Only Interconnecting Wiring ........................................................... 41  Table 2.3 Combustibles Sensor Only Interconnecting Wiring .................................................. 43  Table 2.4 Dual Sensor Interconnecting Wiring......................................................................... 45  Table 2.5 Flow Alarm Relay Box Interconnecting Wiring ......................................................... 47  Table 4.1 Analyser AC Power Connections ............................................................................. 62  Table 4.2 Transformer Connection and Winding Details ......................................................... 62  Table 4.3 Keypad Connections ................................................................................................ 65  Table 4.4 Sensor Head Voltage Selection at TB9.................................................................... 68  Table 5.1 Control Unit Electrical Power Voltage Selection ...................................................... 98  Table 5.2 Terminal PCB Voltage Selection Links .................................................................. 109  Table 5.3 Sensor Head Internal Wiring Schedule .................................................................. 110  Table 5.4 Flow Alarm Internal Wiring – Flow Amplifier Board ................................................ 119  02700002D/0 v SERVOTOUGH FluegasExact Service Manual This page intentionally blank. vi 02700002D/0 SERVOTOUGH FluegasExact Service Manual 1 INTRODUCTION 1.1 Scope of this Manual This manual contains essential information for the servicing of the Servomex 2700D (FluegasExact) Combustion Gas Analysers. This service manual is intended for use by Servomex trained service personnel. The manual contains technical descriptions, fault diagnosis information, parts removal, refitting and test instructions. 1.2 Safety Information Important safety information is highlighted in this manual as WARNINGs and CAUTIONs, which are used as follows: WARNING Warnings highlight specific hazards which, if not taken into account, may result in personal injury or death. CAUTION Cautions highlight hazards which, if not taken into account, can result in damage to the analyser or to other equipment or property. This manual also incorporates “Be aware of” information, which is used as follows:  This highlights information which is useful for you to be aware of (for example, specific operating conditions, and so on). 1.3 Service Philosophy WARNING All servicing should be referred to qualified personnel. Repairs to printed circuit boards are affected by module replacement. Component replacement is not recommended. The only exceptions to this are the mains fuses on the Control Unit and terminal box PCB’s, and the heater fuses on the Control Unit PCB. 1.4 General Description  All Servomex adaptor flanges, interface flanges, probe support tubes, stand-offs and thermal spacers, including the integral flange on the Sensor Head, are suitable for fitting onto the standard flanges that their descriptive names imply, either raised face (<1.6mm) or flat faced. Servomex flanges do not comply with any national or international standards and the analyser’s maximum process pressure is limited to 5psig. 02700002D/0 1 SERVOTOUGH FluegasExact Service Manual The Servomex 2700D Combustion Gas Analyser measures combustion and similar gases to provide an analysis of the oxygen concentration and / or the level of unburned combustibles. The analyser comprises two separate core units:  A Sensor Head mounted directly onto the flue wall.  A Control Unit mounted remotely from the Sensor Head. These may be mounted up to 300m (975ft) apart, or 100m (325ft) when the combustible measurement option is fitted. In addition, optional utilities units and an integrated Flow Alarm are available. Utilities units supply the Sensor Head with calibration gases and instrument air. The integrated Flow Alarm offers indication of sample flow status and is supplied with an external Relay Box for customer connections. The Sensor Head is flange mounted on to the flue wall and houses the measurement sensors in a heated epoxy painted aluminium enclosure. A probe assembly projects through the duct wall into the process gas to extract a gas sample for analysis. A comprehensive range of sample probes and filters are available to enable the analyser to be used in a wide range of applications and process conditions. Electrical connections are made to a terminal enclosure located on the side of the Sensor Head. Key 1. 2. 3. 4. Description Key Terminals enclosure Sensor Head 4” mounting flange Sample probe 5. 6. 7. 8. Description Sample probe filter (optional) Control unit Wall mounting brackets Keypad and display Figure 1.1 FluegasExact Product Components 2 02700002D/0 SERVOTOUGH FluegasExact Service Manual The Control Unit houses the sensor electronics, microprocessor, keypad, display and user wiring connections in an epoxy painted aluminium enclosure. The Control Unit may be either wall or panel mounted (using an optional panel mount kit). Cable entries are located on the bottom of the Control Unit enclosure. 2700D units are available in five configurations based on the Servomex Zr703 zirconia oxygen sensor and the Servomex Tfx 1750 thick film calorimeter combustibles sensor.  Oxygen only.  Combustibles only.  Both oxygen and combustibles measurement (dual).  Oxygen only with Flow Alarm.  Both oxygen and combustibles measurement (dual) with Flow Alarm. Isolated current outputs (0-20mA or 4-20mA) are provided to allow the analyser to be connected to a chart recorder, data logger, PLC, PC, DCS or ESD system as required. The analyser is provided with a single analogue output for each measurement provided. Each output has a minimum and maximum output range. For the oxygen sensor 0-1% is the minimum range and 0-25% is the maximum. For the 1750702 combustibles sensor 0500ppm is the minimum range and 0-6000ppm is the maximum (over range of 30000ppm). The analogue outputs may be independently set to have live zero (4-20mA) or true zero (020mA), to freeze or follow during calibration and blow back, and to jam either high or low during analyser fault conditions. Oxygen only and dual analysers can be configured with an optional Flow Alarm that provides a low flow warning which can be used to detect plugging/blockage during operation. The analyser has four software configurable relay outputs. The user may assign any of these relay outputs to be either concentration alarms, analyser fault alarms, auto calibration relay drives, blow back relay drives, calibration in progress signals or blow back in progress signals. The analyser has two digital inputs, suitable for voltage free relay contact actuation, to trigger an auto calibration or a blow back sequence remotely. The 2700D is designed for use in modern industrial environments with emphasis on durable, rugged construction, low cost of ownership, reliable performance, simple operation and ease of service. A number of optional features are available for the 2700D. These include the following: 02700002D/0  Sample probes.  Differently threaded entries for electrical connections.  Corrosive purge ports.  Hazardous area purge.  Sensor Head flange mounting options.  Control unit mounting options.  Integrated Flow Alarm.  Utilities panels. 3 SERVOTOUGH FluegasExact Service Manual 1.5 Location of External Components Figures 1.2 and 1.3 identify the key features of the Sensor Head and Control Unit respectively. Refer to Section 5 for replacement procedures. Key 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Description Analyser mounting flange, 4” ANSI 150lb. Sample vent port, 1/8” NPT (INT). Sample probe connection, 1/2” NPT (INT). Calibration gas inlet, 1/4” OD compression fitting. Purge gas exit, 1/4” NPT (INT) or breather fitting. Spare inlet (Blanked). Purge gas entry, 1/4” NPT (INT) or blanking plug. Signal cable entry, 3/4” NPT (INT) or specified adaptor. Mains cable entry, 3/4” NPT (INT) or specified adaptor. Aspirator air supply inlet, 1/8” NPT (INT). Figure 1.2 Sensor Head Overview 4 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. Description LCD display and keypad. Door hinges. 3/4” NPT (INT) threaded cable conduit entries or optional adaptors as required. Wall mounting brackets. Enclosure breather fitting (optional) or blanking port. 1/4” NPT (INT) threaded enclosure purge fittings (optional) or blanking screws. Figure 1.3 Control Unit Overview 02700002D/0 5 SERVOTOUGH FluegasExact Service Manual 1.6 Introduction to User Interface Refer to Figure 1.4. 20.95 % Oxygen 50 ppm COe MENU ENTER MEASURE QUIT CALIBRATE / VIEW SERVICE / SETUP Key 1. 2. 3. 4. 5. 6. 7. Description LCD showing measurement display. ENTER key. ARROW keys. MENU key. MEASURE key. QUIT key. Main menu display. Figure 1.4 FluegasExact Keypad Display The 2700D Control Unit user interface consists of a tactile 8 button keypad and a back lit LCD (2 lines x 16 characters). During normal use the LCD will display either the measurement or menu display. A user can toggle between the measurement or menu display via the tactile keypad. The functions of the keys on the keypad are: 6 MEASURE Returns the analyser to the measurement display. MENU Activates the main menu display of the screen editor. QUIT Aborts the current activity and returns to the previous menu level.  In the menu, the arrow keys select the desired option. When entering numeric information, the left and right arrow keys are used to move between 02700002D/0 SERVOTOUGH FluegasExact Service Manual digits and the up and down arrow keys are used to change the value of each digit. The active digit is highlighted by blinking. The user presses the ‘ENTER’ key to indicate that the numeric input is complete and the data is to be saved. If the ‘QUIT’ key is pressed then the data is not saved and the input is aborted. In the measurement display the  scrolls through any alarm and/or fault messages active. ENTER Indicates that the menu selection is to be processed or that numerical input is complete. To initiate any menu operation the MENU key should be pressed. The LCD will then present the top level menu, which in turn leads on to other menus. At each menu, the user highlights the desired option using the arrow keys and then presses ENTER. Blinking is used to highlight the selected menu option. During any menu operation the fundamental measurements are still being made by the analyser and all relevant outputs, alarms and diagnostics remain active. Some menu operations require the use of a password. There are two passwords, a supervisor password (2700) which gives access to SETUP, SERVICE, VIEW and CALIBRATION and an operator password (2000) which gives access to CALIBRATION and VIEW only. Both passwords are factory set and may be changed if required. The measurement display is shown in figure 1.4. The top line of the display shows the current measured value (with its units) for each of the sensors fitted. In normal operation the bottom line of the display labels the gases measured. The MEASURE key may be used to return the analyser to the measurement display at any time. Further details on the operation of the user interface are available from the Quickstart manual. 02700002D/0 7 SERVOTOUGH FluegasExact Service Manual 1 2 VIEW Go to 2 CONFIGURE Go to 3 VIEW Software version Oxygen sensor output voltage in mV Oxygen sensor temperature in °C Oxygen sensor high calibration point in mV Oxygen sensor low calibration point in mV Combustibles sensor output voltage in mV Combustibles sensor temperature in °C Combustibles sensor high calibration point in mV Combustibles sensor low calibration point in mV Sensor head temperature in °C (if connected) DIAGNOSTICS HISTORY 3 4 ALARM Alarm history events FAULT HISTORY Fault history events CONFIGURE ENTER Operator Password – Go to 4 0000 Supervisor Password – Go to 5 CALIBRATE / VIEW CALIBRATE MANUAL CALIBRATE OXYGEN LOW CAL COe HIGH CAL AUTO CALIBRATE Calibration Procedure OXYGEN SETUP AUTO CAL Calibration Procedure COe OXYGEN & COe SETUP AUTO CAL 5 VIEW Go to 2 CALIBRATE / VIEW Go to 4 SERVICE / SETUP Go to 6 Initiate Automatic Calibration Figure 1.5 Menu Structure A 8 02700002D/0 SERVOTOUGH FluegasExact Service Manual 6 SERVICE SET OUTPUTS mA OUTPUTS SET TO 0mA / 4mA / 20mA RELAYS SET TO DISABLED SET TO ENABLED HISTORY DELETE HISTORY SET UP ASSIGN NONE AL1 ALARMS OXYGEN AL2 RELAYS COe A HIGH FOLLOW LOW Setup Alarm level & Hysteresis Setup Procedure 1/2/3/4 mA OUTPUTS FREEZE OXYGEN SET RANGE COe FREEZE A FOLLOW 0-20mA 4-20mA SET LOW POINT FILTER JAM HIGH / LOW / NONE OXYGEN Setup Filtration COe BLOWBACK SET UP BLOWBACK Blowback Setup Procedure START BLOWBACK Initiate Blowback CLOCK Clock Setting Procedure UTILITY PASSWORD AUX AIR SUPERVISOR Password Setting Procedure OPERATOR YES Always set to “YES” NO ENGLISH LANG FRANCAIS DEUTSCH Figure 1.6 Menu Structure B 02700002D/0 9 SERVOTOUGH FluegasExact Service Manual It is advised that the parameters for the Calibration Tolerances, Combustibles Output Ranges and Filters are set as follows. CONFIGURE ENTER 0000 CALIBRATE MANUAL CALIBRATE OXYGEN LOW CAL COe HIGH CAL CAL LEVEL CAL TOL Calibration Tolerance (Factory Default Settings) AUTO CALIBRATE Oxygen Low Oxygen High COe Low COe High SETUP AUTO CAL OXYGEN 0.2% 1.0% 150ppm 150ppm COe OXYGEN & COe LOW CAL LOW & HIGH CAL CAL LEVEL SET UP CAL TOL Minimum COe Output Range ASSIGN mA OUTPUTS 500ppm OXYGEN Maximum COe Output Range COe 30,000ppm* Minimum Oxygen Output Range 1.0% Maximum Oxygen Output Range COe 25.0% *Note: max working range of sensor is 10,000ppm FILTER OXYGEN COe Filter Settings (Factory Default Settings) Oxygen COe 4 5 Figure 1.7 Menu Structure C 10 02700002D/0 SERVOTOUGH FluegasExact Service Manual 1.7 Displaying Faults or Alarms In normal operation the bottom line of the measurement display shows each measurement gas name. Should a fault or alarm occur then the lower line of the display will detail the nature of the fault or alarm. Should more than one fault and/or alarm be active then arrows are shown in the last character of the bottom line. If both a fault and an alarm are present then the fault display will take precedence. It will not be possible to view any alarms present until the fault is cleared. The up and down arrow keys on the keypad may be used to scroll through these messages. The fault messages that may appear are as follows: OXYGEN LOW Oxygen too low for COe measurement. OXYGEN C LOW Oxygen sensor temperature low. OXYGEN C HIGH Oxygen sensor temperature high. COe mV LOW Combustibles sensor output voltage low. COe mV HIGH Combustibles sensor output voltage high. COe C LOW Combustibles sensor temperature low. COe C HIGH Combustibles sensor temperature high. COe mV OUTPUT LOW Combustibles sensor sensitivity low (updates after calibration only). COe CONC HI Combustibles sensor has been exposed to very high COe levels. SENSOR C LOW Sensor Head temperature low. SENSOR C HIGH Sensor Head temperature high. AUTO CAL FAIL Auto calibration out of tolerance error. COe WARMING Combustibles sensor is warming up. O2 WARMING Oxygen sensor warming up. DISP OVER RANGE Combustibles reading exceeds sensor f.s.d. mV OUT OF TOLERANCE Combustibles sensor coarse zero is incorrectly set. See section 4 of this manual for further details and remedial actions. 02700002D/0 11 SERVOTOUGH FluegasExact Service Manual 1.8 Displaying Diagnostics The VIEW function allows the user to interrogate the analyser diagnostics. No password is required to access the view function. The VIEW functions are updated dynamically and values may change while they are being viewed. To access this display, press the MENU key, select VIEW then select DIAGNOSTICS from the view menu. The VIEW option is also available from the CONFIGURE menu. The diagnostics appear as a scrollable list of values and associated descriptions. There are up to nine diagnostics depending on which sensors are fitted. The  keys are used to switch between the following diagnostic measurements: OXYGEN SENSOR mV Oxygen sensor output voltage in mV. OXYGEN SENSOR C Oxygen sensor temperature in C. COe SENSOR mV Combustibles sensor output voltage in mV. COe SENSOR C Combustibles sensor temperature in C. PROBE HEAD C Optional Sensor Head temperature in C. COe SENSOR HIGH Combustibles sensor output voltage in mV, at current high point calibration. COe SENSOR LOW Combustibles sensor output voltage in mV, at current low point calibration. OXYGEN SENSOR HIGH Oxygen sensor output voltage in mV, at current high point calibration. OXYGEN SENSOR LOW Oxygen sensor output voltage in mV, at current low point calibration.  The difference between SENSOR HIGH and SENSOR LOW mV values is the sensitivity (cell output). These values are only updated after a successful High or Low calibration is performed. Pressing the MEASURE key will return the analyser to the default measurement display. 1.9 Displaying Fault or Alarm Histories The VIEW function allows the user to interrogate the analyser alarm or fault histories in addition to the analyser diagnostics. No password is required to access the VIEW function. The VIEW functions are updated dynamically and values are live. To access this display, press the MENU key and then select VIEW. From the VIEW menu select HISTORY then choose between ALARM HISTORY and FAULT HISTORY. 12 02700002D/0 SERVOTOUGH FluegasExact Service Manual 1.10 Software Revision History The table below summarises the last revision of the software used in the 2700D. 02710/652/1 02700002D/0 December 2006 Release 13 SERVOTOUGH FluegasExact Service Manual 2 EQUIPMENT OVERVIEW 2.1 Mechanical Overview 2.1.1 Sensor Head Refer to Figure 2.1. Key 1. 2. 3. 4. Description Mounting flange Sensor Head base casting Insulation spacer Terminal box casting Key 5. 6. 7. 8. Description Terminal box cover Terminal cover screws Sensor Head cover Sensor cover screws Figure 2.1 Sensor Head Overview 14 02700002D/0 SERVOTOUGH FluegasExact Service Manual The Sensor Head assembly mounts directly onto the flue wall via a 4" flange (1). The Sensor Head assembly consists of two main components, the sensor compartment and the terminal box. The Sensor Head base casting (2) and cover casting (7) form a heated oven housing the sensors and sample pipe work. All gas sampling and measurement takes place within this heated sensor compartment. The terminal box casting (4) and terminal box cover casting (5) form an enclosure housing the Sensor Head PCB and all interconnecting and user connections. The terminal box casting (4) is screwed to the Sensor Head base casting (2) by two bolts. An insulating spacer (3) and two sealing gaskets provide thermal isolation between the sensor compartment and the terminal box. O-ring seals on the covers and appropriate cable glands (not supplied) make the two compartments weatherproof (IP66 and NEMA 4X). An electrical earth connection is provided (refer to Figure 2.8) on the outside of the terminals enclosure. 2.1.1.1 Sensor Compartment Refer to Figure 2.2. The sensor compartment cover is secured by four captive M6 screws and is sealed by an O-ring. With the cover removed, access is given to the gas sensors and sampling pipe work. Figure 2.2 describes a dual sensor analyser (oxygen and combustibles sensors). For other Sensor Head versions the sensor compartment construction is similar but with the unused sensor(s) removed. The Sensor Head base and cover form an insulated oven (insulation not shown for clarity). The oven is heated by a 500W band heater (1) located around the chest assembly (12). The temperature of the chest assembly is controlled at approximately 245C via the thermistor (13). An over temperature thermostat (4) is fitted to prevent overheating should the temperature control fail. The gas sample is extracted from the flue using an aspirator (2) screwed into the chest assembly. For analysers incorporating a Zr703 zirconia sensor, a reference air sample is derived from the aspirator supply, via a capillary tube (8). For analysers incorporating a Tfx1750 sensor, an auxiliary air supply is also derived from the aspirator supply, via a flame trap (5) and auxiliary air flow restrictor (7). Refer to Figure 2.3. A solenoid valve (8), interlocked to the Sensor Head and Zr703 zirconia sensor (where fitted) temperature, is provided as standard to prevent sample gases condensing in the Sensor Head pipe work when the Sensor Head temperature is too low. Flame traps (3) and a filter/flame arrestor (11) are provided to prevent accidental ignition of the flue by the hot sensors should the flue gas become flammable. The reference air capillary tube (7) also behaves as a flame arrestor. 02700002D/0 15 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. Description Band heater Aspirator assembly Flame trap Over temp thermostat Flame trap Tfx1750 combustibles sensor Key 7. 8. 9. 10. 11. 12. 13. Description Auxiliary air restrictor Aspirator / reference air pipe Zr703 oxygen sensor Base casting Sintered filter/flame arrestor Chest assembly Thermistor Figure 2.2 Dual Sensor Assembly 16 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. 8. Description Key Chest assembly Sample aspirator Flame trap Tfx1750 sensor Auxiliary air restrictor Flame trap Aspirator/reference air inlet Solenoid valve 9. 10. 11. 12. 13. 14. 15. 16. Description Zr703 sensor Breather Flame arrestor Calibration/blow back inlet Heated enclosure Internal filter Sample gas inlet Sample gas outlet Figure 2.3 Dual Sensor Head Flow Schematic 02700002D/0 17 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. 8. Description Chest assembly Sample aspirator Flame trap Tfx1750 sensor Auxiliary air restrictor Flame trap Aspirator/reference air inlet Solenoid valve Key 9. 10. 11. 12. 13. 14. 15. 16. 17. Description Zr703 sensor Breather Flame arrestor Calibration/blow back inlet Heated enclosure Internal filter Sample gas inlet Sample gas outlet Flow alarm Figure 2.4 Dual Sensor Head with Flow Alarm Flow Schematic 18 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. Description Chest assembly Sample aspirator Flame trap Aspirator/reference air inlet Solenoid valve Zr703 sensor Key 7. 8. 9. 10. 11. 12. 13. Description Breather Flame arrestor Calibration/blow back inlet Heated enclosure Internal filter Sample gas inlet Sample gas outlet Figure 2.5 O2 Sensor Head Flow Schematic 02700002D/0 19 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. Description Chest assembly Sample aspirator Flame trap Aspirator/reference air inlet Solenoid valve Zr703 sensor Breather Key 8. 9. 10. 11. 12. 13. 14. Description Flame arrestor Calibration/blow back inlet Heated enclosure Internal filter Sample gas inlet Sample gas outlet Flow Alarm Figure 2.6 O2 Sensor Head with Flow Alarm Flow Schematic 20 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. Description Chest assembly Sample aspirator Flame trap Tfx1750 sensor Auxiliary air restrictor Flame trap Aspirator/reference air inlet Key 8. 9. 10. 11. 12. 13. 14. 15. Description Solenoid valve Breather Flame arrestor Calibration/blow back inlet Heated enclosure Internal filter Sample gas inlet Sample gas outlet Figure 2.7 COe Sensor Head Flow Schematic 02700002D/0 21 SERVOTOUGH FluegasExact Service Manual 2.1.1.2 Key 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Terminal Compartment Description Solid state relay Terminal block TB2 Terminal block TB7 Solenoid valve Solenoid valve retaining nut Terminal PCB earth connection Terminal block TB9 Mains protection cover Terminal block TB8 Terminal block TB1 Key Description 11. 12. 13. 14. 15. 16. 17. 18. M4 cover fixing screw Mains fuse F1 Terminal block TB3 Terminal block TB4 Terminal block TB6 Terminal block TB5 M4 Terminal PCB fixing screws Wiring support P-clip + EMC ferrite 19. Transformer 20. Earth stud Figure 2.8 Sensor Head Terminal Enclosure Detail (Dual Configuration) 22 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. Description Fuse M4 PCB fixing screws Terminal block TB1 Terminal block TB3 Key 5. 6. 7. Description Flow sensor tuning potentiometer Signal amplifier PCB Terminal block TB2 Figure 2.9 Sensor Head with Flow Alarm Terminal Enclosure Detail (Dual Configuration) Removal of the 4 screws and lid gives access to the Sensor Head PCB and user electrical connections. Electrical cables fitted with suitable glands are fed through the appropriate entry holes and wired to the terminals shown in Figure 2.8 (Refer to Installation manual for user connections). Any unused cable entries should be fitted with appropriate blanking plugs. 02700002D/0 23 SERVOTOUGH FluegasExact Service Manual 2.1.2 Flow Alarm Relay Box Refer to Figure 2.10. The Flow Alarm Relay Box consists of a die cast aluminium enclosure (6) in which the threshold detector board (3) is mounted. The enclosure has two ¾” NPT gland entries (9), (which can be removed if M20 entries are required), and an EMC earth stud (8). A clear cover (10) protects the user from the mains rated relays (4). Interconnection to the Sensor Head is made via terminal block TB2 (2) and relay connections are made via terminal block TB1 (7). Key 1. 2. 3. 4. 5. Description Nylon spacer Terminal block TB2 Threshold detector board Relays Flow alarm set point adjustment Key 6. 7. 8. 9. Description Aluminium enclosure Terminal Block TB1 EMC earth stud Mains protection cover Figure 2.10 Flow Alarm Relay Box 24 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key Description 1. M6 Screw 2. M6 Washer 3. Mains protection cover Key 4. 5. 6. Description Spacer Flow alarm relay board M6 Washer Figure 2.11 Flow Alarm PCB Assembly 02700002D/0 25 SERVOTOUGH FluegasExact Service Manual 2.1.3 Control Unit Refer to Figure 2.12 Control Unit Overview The housing consists of a die cast aluminium enclosure (16) with a hinged die cast aluminium door (3) secured by four captive M6 screws (2) and sealed by an O-ring (5). This enclosure houses most of the control electronics for the 2700D analyser. Three holes into the enclosure are provided for optional purge connections (13), a breather fitting (15) or sealed plugs. An electrical earth connection is provided (not shown in figure 2.5) on the outside of the enclosure. Menu navigation is via a tactile keypad and backlit LCD (1) secured onto the hinged door using twelve M4 hex head screws and sealed using an O-ring (4). The control electronics and user wiring connections (7) are contained on a single PCB (10) screwed directly onto the enclosure casting. A toroidal transformer (11), attached to the enclosure casting, is mounted underneath the control PCB. A protection cover (6) protects the PCB from accidental damage. A transparent cover (8) is provided to protect the user from hazardous voltages. User and interconnecting wiring to the Control Unit is via the 3/4" NPT (internal) threaded entries (14) on the bottom side of the enclosure casting. The Control Unit may be mounted on to a wall via mounting straps (12) or alternatively into a rack or panel (panel mounting kit not shown). 26 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. 8. Description Display and keypad Captive screws for door Cast aluminium hinged lid Display O-ring seal Door O-ring seal PCB protection cover User wiring connections Mains protection cover Key 9. 10. 11. 12. 13. 14. 15. 16. Description PCB fixing screws Control PCB Transformer Wall mounting straps Optional purge ports Wiring entry ports Optional breather fitting Cast aluminium enclosure Figure 2.12 Control Unit Overview 02700002D/0 27 SERVOTOUGH FluegasExact Service Manual 2.2 Electrical Overview 2.2.1 Control Unit PCB 2.2.1.1 Power Supplies and Relay Outputs Mains power connects to the PCB via terminal block TB3. The ‘live’ side is fused by F1. Fused mains power is fed to connectors PL6 and PL7 where the mains transformer primary is connected. The transformer secondary windings connect to PL5, supplying a 18-0-18V heater supply, and a 10.5-0-10.5V supply for the ±5V regulated DC supplies. There is a dedicated regulated +5V DC supply for the relay coils, 4-20mA output DC-DC converters and the LCD backlight. The rest of the Control Unit electronics is powered from a separate +5V and -5V DC supply. Fuses F2, F3, F4 and F5 protect both sides of the 18-0-18V AC supplies to the Zirconia and Tfx cell heaters. There are four relay outputs controlled by the microcontroller. Each relay provides a singlepole changeover function on terminal block TB4 and is driven by an individual control line from the microcontroller. 2.2.1.2 Microcontroller The microcontroller has external flash EEPROM which contains the system software, the analyser configuration and calibration data. The microcontroller directly drives the LCD, an analogue input multiplexer and an analogue-to-digital converter. There are two PWM outputs from the microcontroller which are used to drive the isolated current outputs. A serial data chain monitors the keypad, ‘autocal’ and ‘blow back’ inputs, configuration links and drives the Zirconia and Tfx cell heater inhibit signals, ‘system OK’ LED and relay outputs. A real-time clock/calendar IC with its own 32.768kHz crystal is connected to the microcontroller via an SPI synchronous serial data link. A 0.1F “Supercap” capacitor provides power for the real-time clock when there is no mains power. A supply voltage supervisor/reset IC is used to drive the microcontroller reset line. The IC provides a clean power-up reset, brown out protection and a manual reset input (SW1). There is a red LED on the RESET line which turns on when the microcontroller is reset. The LED can be seen through a hole in the metal cover over the PCB. The green “System OK” LED is toggled on and off by the software to indicate correct operation. The LED can be seen through a hole in the metal cover over the PCB. Switch SW4 A and B is used by the software to determine the analyser configuration (O2, COe, or dual measurement). These are factory set to match the Sensor Head configuration and need only be altered when replacing the main PCB with a spare. Note that early Control Units were fitted with a main PCB whose configuration was determined by links (LK3 & LK4). The configuration links (LK3, LK4) are surface-mount links which tell the software whether the PCB is for an oxygen-only, combustibles-only or dual gas analysis. These links were fitted during manufacture and are not field-alterable. The Zirconia cell heater inhibit (ZINH) only enables the heater when the cell temperature is above 50C. This is to ensure that the Sensor Head is connected and working and the cell 28 02700002D/0 SERVOTOUGH FluegasExact Service Manual temperature measurement signals are working. The Zirconia cell will be heated to 50C by the Sensor Head heater. This interlock ensures that the cell heater controllers do not operate if their temperature feedback signals are broken, as this could damage the cell by overheating it. Note that if the system software is not running, both cell heating methods will be inhibited. Potentiometer RV2 adjusts the LCD contrast/viewing angle. The display may disappear altogether if this potentiometer is not correctly adjusted.  If the PCB is removed from the enclosure, the “Autocal” and “Blow Back” inputs will only work if the PCB centre mounting hole is electrically connected to the PCB earth tag.  Operation of the Sensor Head with the PCB removed from the enclosure is not recommended as the enclosure provides the heat sink. 2.2.1.3 Analogue Current Outputs There are two identical, galvanically isolated, current output circuits; one assigned to each gas measurement. Single-gas analysers only have one current output. The “Oxygen” current output will be described (also referred to as Channel A): An isolated ±15Vdc supply is generated by two DC-DC converters, with their outputs connected in series. The PWM output from the microcontroller is fed via an opto-isolator to control an analogue multiplexer. A voltage 3V above the -15V rail is generated and used as the “signal 0V”. This ensures that signals are always within the common-mode range of the multiplexer and op-amp. A 2.5V reference voltage (with respect to “signal 0V”), trimmed by RV4, is fed to one input of the multiplexer. The other multiplexer input is connected to “signal 0V”. The multiplexer output is fed to a passive low-pass filter which produces a DC voltage proportional to the duty cycle of the PWM waveform. The op-amp and MOSFET transistor convert this voltage to a current sink at TB2 pin 16. Current is sourced at TB2 pin 15 from the isolated +15V rail. The current output is calibrated by RV4 to give 20mA at 95% duty cycle, thus limiting the maximum current (even under fault conditions) to 21mA. The current output will work with load resistances up to 1kΩ (21V maximum output). 2.2.1.4 ADC Subsystem Five analogue signals are monitored by the microcontroller via the ADC subsystem.  Zirconia sensor output mV.  Zirconia sensor temperature.  Combustibles sensor output mV.  Combustibles sensor temperature.  Sensor Head temperature (optional). The five inputs and a reference 0V are fed to an analogue multiplexer. A 2.5V reference is provided for the ADC, a -0.25V level is derived from the 2.5V and the multiplexer output is amplified and offset by 2xVin+0.25V. This allows the ADC to handle slightly negative voltages from the multiplexer. The ADC is clocked at 245 kHz; this clock is derived from the microcontroller system clock output. The multiplexer and ADC are controlled by the microcontroller; the ADC output data is transmitted to the microcontroller via a serial data link. 02700002D/0 29 SERVOTOUGH FluegasExact Service Manual 2.2.1.5 Zirconia Sensor Electronics Sensor output signal processing: The zirconia cell output is amplified by an instrumentation amplifier with a gain of 6, and then filtered by a 4-pole active low pass filter with a cut off frequency of about 1Hz. The filter output is fed to the ADC subsystem. Heater control and temperature signal processing: The zirconia cell heater is powered by the 18-0-18V AC supply from the mains transformer, controlled by a triac on each side. The cell temperature is sensed by a thermocouple. The thermocouple amplifier is situated in the Sensor Head terminal box and provides a 10mV/°C temperature signal to the control PCB via TB2 pins 9 and 10. This signal is buffered and fed into the heater control loop, and attenuated to a level suitable for the ADC. The temperature set-point is defined by a -2.5V reference (derived from the ADC 2.5V reference) applied via a 3.57kΩ precision resistor. The temperature feedback is the thermocouple amplifier output voltage (1V/100°C) applied via a 10kΩ precision resistor. The error amplifier subtracts one from the other and gives an output of 1V/°C which is applied to a 267kΩ resistor to generate a heater demand current. A differentiator subtracts from the heater demand current if the rate of rise of cell temperature exceeds 250°C/minute. This is in order to prevent damage to the cell caused by extreme thermal shocks. The heater demand current is then inverted and integrated and the integrator output voltage is compared with 0V. To keep the cell electrically symmetrical the controller output is synchronised to the mains zero-crossings, so only complete cycles of AC are applied to the heater. If the integrator output is negative then power is applied to the heater; if the output is positive then no power is applied. When power is applied to the heater current is drawn from the integrator via a 267kΩ resistor which causes the integrator output to ramp positive. There is a hardware over temperature shutdown which disables the heater if the measured temperature goes above about 830°C. The heater may also be disabled by the microcontroller via a comparator and FET switch. A separate rectifier and voltage regulator provides a +10V supply for the cell temperature buffer amplifier. The Sensor Head temperature signal is buffered and attenuated and fed to the ADC via the analogue multiplexer. 2.2.1.6 Flow Alarm Sensor Electronics The Flow Alarm sensor electronics is split between the Sensor Head enclosure and an external Flow Alarm Relay Box. The flow sensor is in the form of a resistive bridge arranged so that, predominantly, one pair of resistors is exposed to the gas flow. This bridge is powered by a current source, set by RV1 to produce the required level of self-heating. The cooling effect produced by a gas flow unbalances the bridge and results in a differential output that is then amplified to give an indication of flow. Basic temperature compensation is applied to this signal in the form of an offset. Temperature sensing is performed by the bridge itself by measuring the voltage drop due to the current source. Compensation is set by RV2 for a typical operational flow rate. The compensated output is then corrected for zero offset by RV3 to produce the required flow signal. It should be noted that all adjustments described above are factory set to match 30 02700002D/0 SERVOTOUGH FluegasExact Service Manual the flow sensor and must not be subsequently altered. This means that the flow sensor and Signal Amplifier Board must only be replaced as a matched pair. The flow indication signal is connected from the Sensor Head to the external Flow Alarm Relay Box via customer field wiring. Here, the signal is fed into a threshold comparator where it is compared to a low Flow Alarm level set by switch S1. This switch is settable by the user between 10% and 90% of span flow. The thresholds representing zero flow and span flow are established by the flow calibration process and set using RV1 and RV2 respectively. During calibration, the correct setting of each potentiometer in turn is indicated by means of red and green LEDs. These voltage levels are also used by a window comparator that checks the flow signal is within the calibrated range. An in-range condition is indicated on a green LED and an out of range condition (flow fault) is indicated on a red LED. The low flow status and fault status signals are then used to drive relays RL2 and RL1 respectively via switches S2A and S2B. These switches allow the relay drives to be disabled, allowing calibration to be carried out without generating alarm or fault conditions. Switches S3A and S3B allow the operation of the relays to be inverted. 2.2.1.7 Combustibles Sensor Electronics Sensor output signal processing: The Combustibles sensor is in the form of a resistive bridge which is driven by a chopped constant-current supply. The supply is chopped at 218 Hz. The timing is controlled by a small microcontroller to ensure accurate timing of the glitch-blanking function (see below). The current source is mirrored to keep the bridge common-mode voltage low. The bridge output is buffered by a difference amplifier and then fed to two gain stages. The gain blocks have a DC gain of 1 so as not to amplify offset voltage errors. A synchronous detector is used to null out offset errors and amplifier noise. When the bridge is driven with current the synchronous detector has a gain of +1; when the bridge is not driven the synchronous detector is switched to a gain of -1. The output of the synchronous detector is integrated over several cycles by a second-order low-pass filter with a cut off frequency of 0.1 Hz. Thus the output is: ((signal + noise + offsets) - (noise + offsets)) = signal. An analogue switch is placed between the synchronous detector and the low-pass filter to provide blanking of the large transients which are generated when the bridge drive is switched on and off. The transients occur due to the finite response time of the current mirror. The switch is driven by the microcontroller to ensure that the blanking control is “locked” to the chopping of the bridge drive current, and to ensure that a constant percentage of the signal is blanked out since any variation in this would appear as a variation in system gain. A zero-offset adjustment circuit is provided which sinks a current from one side of the bridge to compensate for the coarse offset error inherent in the bridge. Rotary switch SW2 provides approximately 15000ppm of adjustment in 1000ppm steps, the exact step size depends on cell sensitivity and calibration. Switch SW3 selects which side of the bridge the current is taken from, and hence the polarity of the adjustment. The software zero calibration removes the remaining zero offset. 02700002D/0 31 SERVOTOUGH FluegasExact Service Manual Heater control and temperature signal processing: The cell temperature is controlled by a PID controller. The output of the controller is modified by the power applied to the heater to ensure that the controller is stable over the full range of heater supply voltage. A platinum resistance temperature (PRT) sensor monitors the cell temperature as part of a resistive bridge. The bridge output is an error voltage which is fed to the PID controller. The PRT voltage is buffered and fed to the ADC. The heater control set point is fixed at 305C. The set point is defined by the parallel combination of R19 and R20.  The High Sulphur (refer to section 4.6.2) variant operates at an elevated temperature of 400ºC. This is achieved by the addition of a shunt resistor (1.5kΩ) across Sensor Head terminals TB6 3 & 4. The combustibles temperature diagnostic will continue to show an operating temperature of 305ºC. The output of the PID controller (modified by the heater power) is integrated and fed to the heater drive circuit. The drive circuit is almost identical to that used in the Zirconia heater circuit (see section 2.2.1.5). 2.2.2 Sensor Head Terminals PCB 2.2.2.1 Power Supply Mains power connects to the board assembly via terminal block TB1. The “live” side is fused by F1. The fused mains power is routed to the primary winding of the mains transformer via the voltage selector terminals TB9. Fused mains power also connects to TB8 where the Sensor Head heater, solid state relay and over-temperature thermostat are connected in series. Capacitors C14, C15 and C18 provide RF suppression. The transformer secondary windings provide a nominal 15-0-15 Vac to the rectifier diodes D1 to D4. IC1 is a conventional linear regulator providing a nominal 12V dc at TP1 with respect to TP2. Note that 0V (TP2) is not connected to the ‘chassis’ at the Sensor Head. Vc is an unregulated supply of nominally 20Vdc connected only to IC5. +V is a rectified AC supply of nominally 14Vdc connected only to the solenoid valve via R13 and TB7. 2.2.2.2 Thermocouple Amplifier The thermocouple from the zirconia oxygen sensor connects to IC2 via TB2. IC2 is a thermocouple amplifier which incorporates the cold junction reference and provides an output of 10mV/C at TB3, terminals 7 and 8. Under normal operating conditions, the output is nominally 7.00Vdc and this signal is transmitted to the temperature control circuit located in the Control Unit. Should either or both of the zirconia sensor thermocouple wires become disconnected, the amplifier output will increase to some value within the range 8 to 12 V dc. This will cause the temperature control circuit to shut off to protect the cell from damage. 2.2.2.3 Sensor Head Temperature Control The chest assembly is temperature controlled at nominally 240C using a band heater (connected at TB8 terminals 1 and 2), and a thermistor sensor located in the block (connected at TB7 terminals 7 and 8). This sensor has a nominal value of 750 ohms at 240 C and is connected in a full bridge configuration with R1, RN1 and RN2. IC3a (1, 2 and 3) and IC3b (5, 6 and 7) form a voltage to pulse generator. While operating within the proportional control band, there will be a pulsed output from IC3 pin 7 which is inverted by one of the drivers of IC5. This output at IC5 pin 10 switches the solid state relay at TB7 terminals 3 and 4. Visual indication of the heater operation is provided by D10, which 32 02700002D/0 SERVOTOUGH FluegasExact Service Manual should be continuously illuminated during the initial warming phase, then pulsing on-off about one or two times per second when the temperature controller is controlling normally. 2.2.2.4 Sensor Head Temperature Monitor A voltage representing the Sensor Head temperature is available at TB3 terminals 1 and 2 and may be transmitted to the Control Unit for diagnostic purposes. This has a non-linear relationship with temperature and is approximately 1.6V dc at room temperature (and below), increasing to approximately 6.6V dc at the operating temperature of 240 C. 2.2.2.5 Solenoid Valve Interlocks The solenoid valve connected to TB7 terminals 1 and 2 is a 12Vdc coil which isolates the air supply to the aspirator when the Sensor Head and measurement sensor temperatures are below their operating temperatures. The solenoid valve is powered via the ‘driver’ circuit IC5 and diode logic D5, D6, D7 and D8. IC4 amplifiers are used as level comparators in which all 4 outputs must switch ‘high’ for the solenoid valve to be energised. IC4 pin 14 will switch ‘high’ when the chest assembly thermistor reaches approximately 215C (1.3kΩ). IC4 pin 1 will switch ‘high’ when the zirconia sensor exceeds 600C. For oxygen only assemblies, TB7 terminals 5 and 6 are linked. In each case, hysteresis is provided to ensure a clean transition at the switching threshold. Visual indication of solenoid operation is by D13. 02700002D/0 33 SERVOTOUGH FluegasExact Service Manual 2.3 Operating Principles 2.3.1 Zr703 Oxygen Sensor Module Key 1. 2. 3. 4. Description Zirconia heater Thermocouple Diaphragm suspension Reference gas inlet Key 5. 6. 7. 8. Description Zirconia crucible Zirconia disc Platinum electrode Sample gas inlet Figure 2.13 Zirconia Sensor Construction The Zr703 cell is a zirconia type oxygen transducer. The sensing element of the transducer is a disc manufactured from yttria stabilised zirconia. When this material is heated to a temperature above 600 C it becomes permeable to oxygen ions. The passage of oxygen ions through the zirconia produces an electric current that is sensed by electrodes measuring the voltage across the zirconia disc. Refer to Figure 2.13. The sensor consists of a yttria stabilised zirconia disc (6) mounted in a tube of the same material (5). The faces of the disc are coated with platinum electrodes (7) and the assembly is mounted in a small temperature controlled tubular oven (1). The temperature of the oven is measured with a thermocouple (2). When the two sides of the disc are exposed to gases containing differing concentrations of oxygen, oxygen ions pass through the zirconia disc giving rise to a potential difference across the two platinum electrodes (7). The magnitude of the potential difference is proportional to the logarithm of the ratio of the oxygen concentrations on the two sides of the disc. 34 02700002D/0 SERVOTOUGH FluegasExact Service Manual In the 2700D analyser ambient air is used as a reference on one side of the disc (4) while the sample gas extracted from the flue is presented to the other side (8). The oxygen content of air is very constant at 20.95%. The output difference from the cell is governed by the Nernst equation:  20.95  V = KT ln    C  V T C K = = = = Voltage across the zirconia disc in mV. Absolute temperature of the zirconia in K. Concentration of oxygen in the sample gas in %. Constant (0.0215 mV/K). The cell operating temperature in the 2700D is 700 C (973K). The output voltage from the cell is hence given by:  20.95  V = 20.9 ln   mV  C   When the sample gas contains combustible components then, due to the high temperature of the sensor, these will burn at the sensor disc consuming oxygen. The measured oxygen level will then be reduced accordingly. However, this measurement error is typically <500ppm O2 during normal operation. 2.3.2 Tfx1750 Combustibles Transducer Module Refer to Figure 2.14. The transducer operates by oxidation of the COe (carbon monoxide and its equivalents) in the gas stream to form CO2 at the surface of a heated catalyst coated sensor element (1). The process is exothermic and the heat generated raises the temperature of the sensor. The temperature increase is measured electrically to produce a signal that varies linearly with the COe concentration in the sample gas. Earlier pellistor sensors have been successfully used to measure the lower explosive limit (LEL) of gases. This involves the measurement of percentage levels of combustibles. The use of pellistor sensors for low level CO detection has been limited by cross sensitivity to other combustible gases in the gas sample and poor base line stability resulting in drift. 02700002D/0 35 SERVOTOUGH FluegasExact Service Manual In the Tfx 1750 thick film calorimeter transducer these problems have been reduced by the following means. a) Improved catalyst selection and lower operating temperature resulting in much higher selectivity to CO. b) Improved oven design with indirect heating of the sensor surface. This ensures that the sample gas is heated to the same temperature as the sensor element before reaching the catalyst surface. c) Better sample flow conditions so that the sensor surface is relatively free from convection cooling effects. The sensor element (1) is suspended from a ceramic disk (2). The sensor and mounting disc are mounted onto a metallic housing (4). The sensor housing assembly is located within an oven (9). The oven is heated by a band heater (7) and its temperature is measured by a platinum resistance thermometer (6). Key 1. 2. 3. 4. 5. Description Sensor element Ceramic disc Sample gas inlet Metallic housing Electrical connections Key 6. 7. 8. 9. Description Resistance thermometer Band heater Sample gas outlet Oven Figure 2.14 Tfx1750 Sensor Construction 36 02700002D/0 SERVOTOUGH FluegasExact Service Manual Sample gas flows in through the sample inlet (3). The sample gas passes through a heat exchanger formed by a narrow annular channel between the metallic housing (4) and the oven body (9). This ensures that the sample gas is heated to the same temperature as the catalyst before reaching the sensor element. The majority of the sample gas flows straight through the sample gas outlet (8). A small amount of the sample gas diffuses back to the sensor element (1) where the reaction occurs. The flow of sample gas through the sample gas outlet (8) forms an aspirator that removes combustion products away from the sensor surface. The temperature change of the element is measured via the four electrical connections (5). Refer to Figure 2.15. The sensor element consists of a ceramic disc (5) onto which is printed a platinum resistance electrode (6). The sensor is partitioned into 4 quadrants (1, 2, 3, 4). Two of the quadrants (1 and 3) are coated with the catalyst. The other two quadrants (2 and 4) are not coated with the catalyst. The combustion reaction occurs only at the catalyst coated quadrants of the sensor, changing the resistance of those quadrants, and thus changing the resistive balance of the circuit. The four quadrants of the sensor are electrically connected in a bridge configuration so that the temperature difference between the catalyst coated and non-catalyst coated quadrants can be measured. Key Description 1. Coated bridge quadrant 2. Uncoated bridge quadrant 3. Coated bridge quadrant Key Description 4. Uncoated bridge quadrant 5. Ceramic disc 6. Platinum electrode Figure 2.15 Tfx1750 Sensor Element Detail 02700002D/0 37 SERVOTOUGH FluegasExact Service Manual 2.3.3 1760 Flow Alarm Sensor Module Refer to Figure 2.16. The Flow Alarm Sensor consists of a housing in which a reference and a measure disc are mounted. Platinum tracks are printed on each of the discs to form a resistive bridge circuit. Initially, both discs are heated to a temperature set point above the sensor’s ambient temperature. The full flow of sample gas enters the sensor via the inlet pipe, flows past the measure disc, and cools it, thus unbalancing the bridge circuit. This bridge imbalance is measured and used to produce an output signal proportional to the sample gas flow. The output signal is then used to trigger a threshold alarm set point (set using the Relay Box) which, in turn, switches a relay in the connected Relay Box (refer to section 2.1.2). Figure 2.16 1750 Flow Alarm Sensor Construction 38 02700002D/0 SERVOTOUGH FluegasExact Service Manual 2.4 Electrical Connections The interconnecting wiring specification is given in Table 2.1. Wiring schedules for oxygen only, combustibles only, dual sensor, and Flow Alarm Relay Box are given in Table 2.2, Table 2.3, Table 2.4, and Table 2.5 respectively. The maximum loop resistance limit of 4Ω is required only for the sensor heater lines (2 lines per sensor). The sensor outputs, temperature signals and bridge supply wires need not be limited by this restriction on resistance. Depending on the installation environment it may prove more cost effective to use interconnecting cables with more twisted pairs but with a smaller cross section per core and, where necessary, to run heater wires in parallel to produce the required maximum loop resistance. Table 2.1 Interconnecting Cable Requirements Sensor Configuration Interconnection Type Conductor Size & Max Separation 1.0mm2 1.5mm2 2.5mm2 100m 150m 300m Oxygen Only 3 twisted pairs with overall screen. Maximum loop resistance 4 Ohms for heater connections Combustibles Only 6 twisted pairs individually screened, minimum 1.0mm2 cross section. Maximum loop resistance 4 Ohms for heater connections 100m Oxygen and Combustibles Minimum 9 twisted pairs individually screened, minimum 1.0mm2 cross section. Maximum loop resistance 4 Ohms for heater connections 100m Flow Alarm Relay Box Minimum 3 cores with overall screen 1.0mm2 100m  For optional Sensor Head temperature display at Control Unit add 1 extra twisted pair to cable specification. 02700002D/0 39 SERVOTOUGH FluegasExact Service Manual Figure 2.17 Oxygen Sensor Only Interconnection Wiring Schematic 40 02700002D/0 SERVOTOUGH FluegasExact Service Manual Table 2.2 Oxygen Sensor Only Interconnecting Wiring Sensor Head Terminal TB3-1 TB3-2 TB3-3 TB3-4 TB3-5 TB3-6 TB3-7 TB3-8 TB3-9 02700002D/0 Control Unit Terminal Function Optional Sensor Head temperature measurement Zirconia sensor output +ve TB1-9 -ve TB1-10 -ve TB1-7 +ve TB1-8 TB2-7 Zirconia sensor heater supply (polarity not important) Zirconia sensor temperature output Overall cable screen connection TB2-8 +ve TB2-9 -ve TB2-10 Connected to case (earth) 41 SERVOTOUGH FluegasExact Service Manual Figure 2.18 Combustibles Sensor Only Interconnection Wiring Schematic 42 02700002D/0 SERVOTOUGH FluegasExact Service Manual Table 2.3 Combustibles Sensor Only Interconnecting Wiring Sensor Head Terminal TB5-1 TB5-2 Combustibles sensor temperature output TB5-5 TB5-6 TB5-7 TB5-8 TB5-9 TB5-10 TB5-11 TB5-12 Stud Terminal “S” TB5-13 02700002D/0 TB2-1 Combustibles sensor heater supply (polarity not important) TB5-3 TB5-4 Control Unit Terminal Function Combustibles sensor bridge supply Combustibles sensor bridge output Combustibles Sensor Bridge offset correction TB2-2 Ground TB2-5 -ve TB2-4 +ve TB2-3 +ve TB1-1 -ve TB1-6 +ve TB1-3 -ve TB1-2 +ve TB1-4 -ve TB1-5 Combustibles sensor temperature ground TB2-6 Individual screens and unused cores Connected to case (earth) Overall cable screen connection Connected to case (earth) 43 SERVOTOUGH FluegasExact Service Manual Figure 2.19 Dual Sensor Interconnection Wiring Schematic 44 02700002D/0 SERVOTOUGH FluegasExact Service Manual Table 2.4 Dual Sensor Interconnecting Wiring Sensor Head Terminal TB5-1 TB5-2 Combustibles sensor temperature output TB5-5 TB5-6 TB5-7 TB5-8 TB5-9 TB5-10 TB5-11 TB2-1 Combustibles sensor heater supply (polarity not important) TB5-3 TB5-4 Control Unit Terminal Function Combustibles sensor bridge supply Combustibles sensor bridge output Combustibles Sensor Bridge offset correction TB2-2 Ground TB2-5 -ve TB2-4 +ve TB2-3 +ve TB1-1 -ve TB1-6 +ve TB1-3 -ve TB1-2 +ve TB1-4 -ve TB1-5 TB5-12 Combustibles sensor temperature ground TB2-6 TB5-13 Overall cable screen connection Connected to case (earth) TB3-1 Optional Sensor Head temperature measurement TB3-2 TB3-3 TB3-4 TB3-5 TB3-6 TB3-7 TB3-8 Stud Terminal “S” TB3-9 02700002D/0 Zirconia cell output +ve TB1-9 -ve TB1-10 -ve TB1-7 +ve TB1-8 TB2-7 Zirconia sensor heater supply (polarity not important) Zirconia sensor temperature output TB2-8 +ve TB2-9 -ve TB2-10 Individual screens and unused cores Connected to case (earth) Overall cable screen connection Connected to case (earth) 45 SERVOTOUGH FluegasExact Service Manual Figure 2.20 Flow Alarm Relay Box Interconnection Wiring Schematic 46 02700002D/0 SERVOTOUGH FluegasExact Service Manual Table 2.5 Flow Alarm Relay Box Interconnecting Wiring Flow Alarm Relay Box Function Flow Sensor PCB TB1-1 Relay Box +12Vdc supply TB3-1 TB1-2 Flow alarm signal output TB3-2 TB1-3 Relay Box 0V TB3-3 Not used Stud terminal ‘S’ of main Sensor Head PCB TB1-5 Not used - TB1-6 Not used - Screen Stud terminal ‘S’ of main Sensor Head PCB TB1-4 EMC earth stud 02700002D/0 47 SERVOTOUGH FluegasExact Service Manual 2.5 Sample Connections Refer to Figure 2.21 for the position and type of gas connections to the Sensor Head. Key 1. 2. 3. 4. 5. 6. 7. Description Sample vent port, 1/8” NPT (INT). Sample probe connection, 1/2” NPT (INT). Calibration gas / blow back inlet, 1/4” OD compression fitting. Purge gas exit, 1/4” NPT (INT) or breather fitting. Spare entry. Purge gas entry, 1/4” NPT (INT) or blanking plug. Aspirator air supply inlet, 1/8” NPT (INT). Figure 2.21 Sensor Head Sample Connections 48 02700002D/0 SERVOTOUGH FluegasExact Service Manual 3 SPARES LIST WARNING 2700D spares must be supplied by Servomex to comply with personal safety requirements and to maintain performance specification.  The spares listed in this section are for 2700D analysers only. For models prior to this, please refer to original documentation supplied with the analyser, or contact Servomex for assistance.  The spares lists below refer to all current spares for the 2700D, some of which are only available to Servomex Service Centres. Please contact Servomex for spares advice and availability. 3.1 Control Unit Spares Recommended Qty Description Spare Part Number No. of Analysers 1-3 4-9 10+ Complete Control Unit Consult Servomex 0 0 1 Control Unit PCB Kit (common board) S2710906A ** 0 1 2 Control Unit PCB – O2 Only S2710903A 0 1 2 Control Unit PCB – COe Only S2710913A 0 1 2 Control Unit PCB - Dual S2710923A 0 1 2 Transformer Kit S2710910 0 1 1 Keypad / Display Assembly S2710354 0 1 1 Complete Mains Protection Cover Kit S2700996 * 0 0 1 Corrosive Purge Kit S2710995 0 0 0 Enclosure Breather Kit S2700991 * 0 0 0 Wall Mounting Kit S2710997 0 0 0 Rack Mounting Kit S2710996 0 0 0 Complete Enclosure Gasket Kit S2700999 * 0 1 1 Complete Fuse Kit S2700998 * 1 1 2 * Spare part contains items used in the Control Unit, Sensor Head and Flow Alarm Relay Box. ** The ‘common board’ must only be fitted into 2700D Control Units with a serial number of 20,000 or higher. 02700002D/0 49 SERVOTOUGH FluegasExact Service Manual 3.2 Sensor Head Spares Description Complete Sensor Head Spare Part Number Consult Servomex S2720993 S2720992 S2720902A S2720912A S2720922A S2720906A S2720926A S2720995 Recommended Qty No. of Analysers 1-3 4-9 10+ 0 0 1 Solenoid Valve Kit 0 1 1 Solid State Relay Kit 0 1 1 0 1 2 Terminals PCB – O2 Only (No Flow Option) Terminals PCB – COe Only (No Flow Option) 0 1 2 Terminals PCB – Dual (No Flow Option) 0 1 2 Terminals PCB – O2 Only (Flow Option) 0 1 2 Terminals PCB – Dual (Flow Option) 0 1 2 Zr703 Zirconia Oxygen Sensor 1 1 2 Tfx1750 Combustibles Sensor – High S1750702 ** 1 1 2 Sensitivity (<1000vpm SOx) Tfx1750 Combustibles Sensor – High S2720831 ** 1 1 2 Sulphur (<2500vpm SOx) Flow Alarm Module S2720762A 1 1 2 Cell Connector – O2 Only (No Flow Option) S2720991 0 0 0 Cell Connector – COe Only (No Flow Option) S2720950 0 0 0 Cell Connector – Dual (No Flow Option) S2720949 0 0 0 S2720932 0 0 0 Cell Connector – O2 Only (Flow Option) Cell Connector – Dual (Flow Option) S2720930 0 0 0 Aspirator Inlet – O2 Only S2720988 0 0 0 Aspirator Inlet/Aux Air Feed Restrictor & S2720943 ** 0 0 0 Flame Trap Kit – COe Only Aspirator Inlet/Aux Air Feed Restrictor & S2720929 ** 0 0 0 Flame Trap Kit – Dual Calibration / Blow Back Inlet Pipe S2720456 0 0 0 Aspirator Kit S2720987 ** 1 2 2 Complete Flame Trap / Filter Kit S2720928 ** 1 2 3 Thermostat & Thermistor Kit S2720994 1 2 3 Band Heater – 120Vac S2720924 0 1 1 Band Heater – 240Vac S2720925 0 1 1 Thermal Spacer Spare S2720361 0 0 0 Mini pz Purge Controller – ATEX/IECEx S2760702 0 0 1 4" ANSI Flange Gasket Kit S2720985 1 2 3 4" Weld-On Flange Mounting Kit S2720984 0 0 0 Complete Enclosure Gasket Kit S2700999 * 0 1 1 Complete Fuse Kit S2700998 * 1 1 2 Complete Mains Protection Cover Kit S2700996 * 0 0 1 Aspirator & Filter/Flame Arrestor Seals Kit S2720927 1 1 1 Anti Scuff Grease (ROCOL ASP) S2700990 1 1 1 * Spare part contains items used in the Control Unit, Sensor Head and Flow Alarm Relay Box. ** Anti scuff grease (ROCOL ASP) application recommended to select parts in spares kit. 50 02700002D/0 SERVOTOUGH FluegasExact Service Manual 3.3 Flow Alarm Relay Box Spares Recommended Qty Description Spare Part Number No. of Analysers 1-3 4-9 10+ Complete Relay Box – Safe Area S2720933A 0 1 2 Complete Relay Box – ATEX/IECEx S2720935A 0 1 2 Relay Box PCB S2720905A 0 1 2 Complete Mains Protection Cover Kit S2700996 * 0 1 1 * Spare part contains items used in the Control Unit, Sensor Head and Flow Alarm Relay Box. 02700002D/0 51 SERVOTOUGH FluegasExact Service Manual 3.4 Sample Probes 2700D Sample Probes – Description Spare Part Number Silicon Carbide Filter Kit S2740998 Probe Tube Coupling 2344-2294 Probe Shroud S2740996A Probe Support Disc* S2740995 Thermal Spacer Flange Kit 02750997 High Temperature Standoff 02750995 Probe Retention Flange Kit 02750998 <700°C, Probe, Open Ended, 0.5m S2740701A <700°C, Probe, Open Ended, 1.0m S2740701B <700°C, Probe, Open Ended, 1.5m S2740701C <700°C, Probe, Filtered, 0.5m S2740702A <700°C, Probe, Filtered, 1.0m S2740702B <700°C, Probe, Filtered, 1.5m * S2740702C <700°C, Probe, Filtered, 2.0m * & ** S2740702D <700°C, Probe, Filtered, 2.5m * & ** S2740702E <700°C, Probe, Filtered, 3.0m * & ** S2740702F <1000°C, Probe, Open Ended, 0.5m S2740704A <1000°C, Probe, Open Ended, 1.0m S2740704B <800°C, Probe, Open Ended, 1.5m S2740704C <700°C, Probe, Open Ended, 2.0m S2740704D <1000°C, Probe, Filtered, 0.5m S2740705A <1000°C, Probe, Filtered, 1.0m S2740705B <700°C, Probe Support, 1.5m S2740997C <700°C, Probe Support, 2.0m S2740997D <700°C, Probe Support, 2.5m S2740997E <700°C, Probe Support, 3.0m S2740997F <1750°C, Ceramic Probe, 0.5m 02740707A <1750°C, Ceramic Probe, 1.0m 02740707B <1750°C, Ceramic Probe, 1.5m 02740707C * Item 4, Probe Support Disc is required for Items 13 to 16 when replacing the <700°C filtered probe in a Supported Probe Installation. ** 52 Items 14, 15 and 16. Filter probes exceeding 1.5m in length are only available as part of a supported probe installation and should not be used alone. 02700002D/0 SERVOTOUGH FluegasExact Service Manual 3.5 Manuals For the latest manuals, please consult your local Servomex Business Centre. 02700002D/0 53 SERVOTOUGH FluegasExact Service Manual 4 FAULT FINDING 4.1 Introduction This section is included as a guide to possible fault symptoms and their diagnosis. It is based, as far as possible, on field experience but it is acknowledged that guides such as these are never comprehensive. Constructive criticism and suggestions for additions and improvement are always welcome and should be sent to the Product Manager. Sections 4.2 and 4.3 provide guidance on the fault and diagnostic messages which may be displayed on the analyser Control Unit. These sections advise the meaning of the messages and the limits within which diagnostic signals should remain during normal operation. Fault finding advice is found from Section 4.5 onward and has been sequenced on the basis of an engineer attending site to fix a non-functioning analyser. Section 4.5 deals with powering up the analyser and getting the Sensor Head and sensors up to operating temperature. Section 4.6 deals with measurement performance problems. Section 4.7 deals with analyser faults (mainly in the Control Unit). The introductory flow charts in each section may also be useful as a set of checks to be carried out during initial commissioning. WARNING The electrical power used in this equipment is at a voltage high enough to endanger life. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. It may be necessary to fault find with the electrical power connected. Where this is necessary extreme caution should be exercised. Removal of the plastic insulating covers in the Control Unit and Sensor Head may expose the user to potentially lethal voltages resulting from external electrical connections to the relay contacts even when electrical power is disconnected from the Control Unit itself. The 2700D Sensor Head weighs approximately 17kg (38lbs), care must be taken when handling. The analyser may contain toxic, corrosive, flammable or asphyxiant gases. Vent the analyser to a safe area and flush with air before commencing work. The Sensor Head is heated and may be attached to a hot flue. The external surfaces will be uncomfortably hot even after power down for several hours. Exercise care when handling the Sensor Head even when un-powered on a hot flue. 54 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.2 Fault and Alarm Messages The 2700D software provides on-line monitoring for a number of fault conditions and also provides warning messages when certain parameters are outside normal limits which may result in poor instrument performance. The procedure to display any active fault messages is given in section 1.6 of this manual. The procedure to display fault and alarm histories is given in section 1.8 of this manual. Fault/Warning Message Notes DISP OVER RANGE This message occurs when the COe reading exceeds the preset limit of 30000vpm. OXYGEN LOW This warning message only applies when the auxiliary air software setting is configured to NO (factory set to YES). This warning is raised when the oxygen level in the measured sample gas is <1%. OXYGEN C LOW This indicates that the temperature of the zirconia oxygen sensor is too low. The fault will be displayed if the temperature of the zirconia sensor is less than 650C. OXYGEN C HIGH This indicates that the temperature of the zirconia oxygen sensor is too high. The fault will be displayed if the temperature of the zirconia sensor is greater than 750C. COe mV LOW This indicates that the combustibles sensor output voltage is low enough to result in saturation of the analogue to digital convertor. The fault will be displayed if the combustibles sensor output voltage is less than or equal to -109mV. COe mV HIGH This indicates that the combustibles sensor output voltage is high enough to result in saturation of the analogue to digital convertor. The fault will be displayed if the combustibles sensor output voltage is greater than or equal to +1113mV. COe C LOW This indicates that the temperature of the combustibles sensor is too low. The fault will be displayed if the temperature of the combustibles sensor is less than 275C. COe C HIGH This indicates that the temperature of the combustibles sensor is too high. The fault will be displayed if the temperature of the combustibles sensor is greater than 350C. COe mV OUTPUT LOW This indicates that combustibles sensor sensitivity (span) is too low (message clears after a successful High or Low calibration is performed) and needs replacement. This occurs when the sensor sensitivity falls below 5mV per 1000vpm of calibration gas. mV OUT OF TOLERANCE This indicates that the combustibles sensor mV signal was outside the range -60 to +60mV during the last low point (Zero) calibration, and that the combustibles sensor coarse zero setting needs adjustment. (Message clears after a successful low calibration is performed). 02700002D/0 55 SERVOTOUGH FluegasExact Service Manual Fault/Warning Message Notes COe CONC HI This indicates that the combustibles sensor has been exposed to a COe concentration exceeding 15000vpm. This message is logged in the fault history. If combustibles sensors are exposed to high levels of COe their performance and life will be impaired. SENSOR C HIGH This indicates that the Sensor Head temperature is too high. This fault should only be seen on analysers where the optional Sensor Head temperature interconnection is made between the Sensor Head and the Control Unit. The fault will be displayed if the temperature of the Sensor Head chest assembly is greater than 265C. SENSOR C LOW This indicates that the Sensor Head temperature is too low. This fault should only be seen on analysers where the optional Sensor Head temperature interconnection is made between the Sensor Head and the Control Unit. The fault will be displayed if the temperature of the Sensor Head chest assembly is lower than 225C and/or the correct conditions have not been met to energise the Sensor Head solenoid. AUTO CAL FAIL This indicates that an automatic calibration procedure has failed because the resultant change in the calibration parameters was outside of the defined tolerance value. The tolerance value is defined as part of the auto calibration set up procedure. (Message clears after a successful calibration is performed).  It is normal for the analyser to display an “OXYGEN C LOW” fault during power up of the Sensor Head. The fault will be displayed until the zirconia sensor achieves its normal operating temperature range.  It is normal for the analyser to display a “COe C LOW” fault during power up of the Sensor Head. The fault will be displayed until the combustibles sensor achieves its normal operating temperature range.  It is normal for the analyser to display a “SENSOR C LOW” fault during power up of the Sensor Head. The fault will be displayed until the Sensor Head and zirconia sensor achieve their normal operating temperature range. 56 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.3 Diagnostic Values The 2700D software allows the user to interrogate a number of critical diagnostic values. The procedure to display the diagnostic values is given in section 1.7 of this manual. Diagnostic Notes OXYGEN SENSOR mV This is a live measurement of the output voltage, in mV, across the zirconia disc in the oxygen sensor. The principles of operation of the oxygen sensor are given in section 2.3.1. The voltage is related logarithmically to the ratio of the oxygen concentrations at the reference air side, and the sample sides of the zirconia disc. The output will be very close to zero at ambient air levels and increases by 48mV per decade as the oxygen concentration falls (for more information refer to section 2.3.1). OXYGEN SENSOR C This is a live display of the temperature of the zirconia oxygen sensor as measured by its thermocouple. The normal operating value of the sensor is 70010C. The temperature displayed is inaccurate below 80C with a minimum value that can be displayed of approximately 38C, (due to saturation of the thermocouple amplifier IC on the Sensor Head terminal PCB). A fault condition will be generated should the temperature be outside of the range 650 to 750C. OXYGEN SENSOR HIGH mV This is the measurement of the output voltage, in mV, across the zirconia disc in the oxygen sensor at the time of the last successful high point (Span) calibration. OXYGEN SENSOR LOW mV This is the measurement of the output voltage, in mV, across the zirconia disc in the oxygen sensor at the time of the last successful low point (Zero) calibration. COe mV This is a live, amplified measurement of the output voltage (AC) across the combustibles sensor bridge circuit. The principles of operation of the combustibles sensor are given in section 2.3.2. The displayed value is in the range -125 to + 1125mV. The displayed voltage for a sample with no carbon monoxide should be in the range -60 to +60 mV. The sensitivity of individual combustibles sensors will vary widely depending on the sensor type, age and other factors. The change in the sensor output voltage display should be, typically, in the range 25 to 80mV for a 1000ppm change in the carbon monoxide concentration. COe C This displays the temperature of the combustibles sensor as measured by its platinum resistance thermometer. The normal operating temperature is 305C for the high sensitivity variant, and 400C for the high sulphur variant, (regardless of which variant is fitted, the COe C display will always reference the standard operating temperature of 305C). A fault condition will be generated should the temperature be outside of the range 275 to 350C. COe SENSOR HIGH mV This is the amplified COe sensor signal level at the time of the last successful high point (Span) calibration. COe SENSOR LOW mV This is the amplified COe sensor signal level at the time of the last successful low point (Zero) calibration. 02700002D/0 57 SERVOTOUGH FluegasExact Service Manual 58 Diagnostic Notes PROBE HEAD C This shows the temperature of the Sensor Head chest assembly as measured by its controlling thermistor. This is only available if the optional interconnecting wiring is fitted between the Sensor Head and the Control Unit. The normal operating temperature is 24510C. A fault will be generated if the chest assembly temperature exceeds 265C. Due to the logarithmic temperature response of the thermistor device (see Figure 4.6) the displayed temperature value is unreliable below 150C and has a minimum display limit of approximately 100C. SOFTWARE VERSION This shows the software part number and revision level fitted in the Control Unit. Refer to Section 1.8 for software revision history. 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.4 Fault Symptoms Shortcut Guide This section categorises the fault symptoms observed, however, it should be noted that certain faults listed under one sub-section may also occur at another phase of testing. Category/Symptom Reference Initial Inspection/Start Up See Section 4.5 Instrument does not power up See Section 4.5.1 Instrument blows fuses See Section 4.5.2 Display not illuminated and no text displayed See Sections 4.5.2 & 4.5.3 Text displayed but backlight not illuminated See Section 4.5.3 Display illuminated but no text Incorrect or no response to key presses See Section 4.5.4 Sensor Head temperature incorrect or will not warm up. Zirconia Sensor temperature incorrect or will not warm up. See Section 4.5.5 Combustibles Sensor temperature incorrect or will not warm up. Measurement Faults See Section 4.6 Oxygen reading incorrect or outside specification See Sections 4.6.2 and 4.6.3 Combustibles reading incorrect or outside specification See Sections 4.6.2 and 4.6.4 Analyser Faults See Section 4.7 Analogue output readings not working or inaccurate See Section 4.7.1 Relay outputs not operating See Section 4.7.2 Analyser does not start an Auto calibration Auto calibration fault indicated See Section 4.7.3 Analyser does not start Blow back Auto calibration or blow back timings slip See Sections 4.7.4 & 4.7.5 Analyser does not keep correct time and date 02700002D/0 59 SERVOTOUGH FluegasExact Service Manual 4.5 Initial Inspection / Start-up Problems 4.5.1 Initial Checks Start Step 1 Is power available at the analyser? No Yes Check wiring, circuit breakers and intermediate junction boxes Step 2 Check for the following: No text on display Backlight not illuminated mA outputs at 0mA Green watchdog LED on control unit PCB not illuminated Step 3 Are ALL the above true? Yes Go to Section 4.5.2 No Step 4 Does the display function normally? (text displayed + backlight illuminated) No Go to Section 4.5.3 Yes Step 5 Does the display respond to the keypad? No Go to Section 4.5.4 Yes Step 6 Are sensor and probe head operating temperatures correct? No Go to Section 4.5.5 Yes Step 7 End See Sections 4.6 and 4.7 for other symptoms Figure 4.1 Initial Checks 60 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.5.2 Control Unit AC Power Supply Checks Start With the power to the analyser turned off, check mains fuse F1 and its rating Put plug in correct position. Replace F1 Blown Ok Check AC power wiring is correctly terminated and ferruled. See Table 4.1 Ok Incorrect Incorrect Check that the transformer primary connector is plugged into the correct socket – PL6 for 220V, PL7 for 110V Ok Re-terminate wiring Replace transformer Replace Control Unit PCB Windings opencircuit or short-circuit Incorrect Check transformer primary winding. See Table 4.2 Ok Check continuity of Control Unit PCB. See Table 4.1 Ok Disconnect PL5. Replace F1 (if blown). Apply power and check transformer output. See Table 4.2 F1 blows or voltage incorrect Replace transformer Volts Ok Disconnect power. Reconnect PL5 then reconnect power. F1 blows Replace Control Unit PCB Ok Go to Figure 4.1 Step 4 Go to Figure 4.1 Step 2 Figure 4.2 Control Unit AC Power Supply Checks 02700002D/0 61 SERVOTOUGH FluegasExact Service Manual Table 4.1 Analyser AC Power Connections AC Power Terminals Function 110V Operation 220V Operation TB3 Pin 1 Live PL7 Pins 2 & 4 PL6 Pin 4 TB3 Pin 2 Neutral PL7 Pins 1 & 3 PL6 Pin 1 TB3 Pin 3 Earth Chassis/Case Chassis/Case PL6 Pins 2 & 3 are linked Table 4.2 Transformer Connection and Winding Details Winding Pin No Wire Colour Resistance Open-circuit Voltage @115 or 230V Connector 1 Secondary 1 7 Orange + Sleeve 6 Orange 5 Orange 4 NO CONNECTION 3 Green + Sleeve 2 Green 1 Green Centre-tap 0.5 10% Secondary 2 21V Centre-tap 0.8 10% 36V Connector 2 4 Blue 3 Red 2 Purple 1 Brown 9.3 10% Primary 1 N/A 9.3 10% Primary 2 62 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.5.3 Control Unit Display and DC Power Supply Checks Start Is text visible on the display? Check display connector is correctly located on Control Unit PCB and ribbon cable is properly crimped. See Note 1 No Yes Yes Is text visible now? >1Hz Check main 5V power rail. See Note 2 Incorrect Ok No Check watchdog LED flash rate <1Hz Replace Control Unit PCB Replace display module No Is processor RESET LED illuminated Is the display backlight illuminated? Yes Yes No Yes Replace Control Unit PCB firmware Check ribbon cable is secure and not damaged. See Note 1 Is backlight illuminated now? No Check aux 5V power rail. See Note 3 Ok Incorrect Are ALL diagnostics correct? No Yes Check -5V power rail. See Note 4 Replace display module Replace Control Unit PCB Incorrect Ok Go to Figure 4.1 Step 5 Figure 4.3 Display and DC Power Supply Checks 02700002D/0 63 SERVOTOUGH FluegasExact Service Manual DC power is distributed through the Control Unit by 3 major supply rails. Their function is as follows: Main +5V Provides power to the microcontroller, LCD and signal processing circuitry. If this rail fails, no text will be displayed on the LCD, the microcontroller watchdog LED will not flash and mA outputs will read 0mA. Auxiliary +5V Provides power to the LCD backlight, relay coils and mA output circuits. If this rail fails, display text will not be backlit, no relays will energise and mA outputs will read 0mA. -5V Provides power to the signal processing circuitry. If this rail fails the LCD and watchdog LED can work normally, but all measurements and diagnostic values will be incorrect. Unless the display module is working correctly, the remainder of the analyser will not function properly. This is because of the way in which display functions are handled in the microcontroller operating system. If the display module is disconnected or unable to respond to display write commands, the microcontroller cannot function normally. In this event, the mA outputs will fall to 0mA and the flash rate of the Watchdog LED decreases from 5 times per second to approximately once every 2 to 3 seconds. 64 Note 1: Check the setting of contrast control RV2 (adjacent to the LCD connector). If this is adjusted incorrectly, the display can appear to be blank. Check insulating washers are fitted between the display PCB and retaining screws and spacers (refer to Section 5.5). Note 2: With the power to the analyser turned on, measure the voltage between pin 3 of the LCD connector (positive) and TB2 terminal 5 (0V). Pin 1 of the LCD connector is identified by the red stripe on the cable. The voltage should be 5V 5%. Note 3: With the power to the analyser turned on, measure the voltage between pin 1 of the LCD connector (positive) and TB2 terminal 5 (0V). Pin 1 of the LCD connector is identified by the red stripe on the cable. The voltage should be 4.2V 10%. Note 4: With the power to the analyser turned off, disconnect all field wiring and remove the metal cover over the Control Unit PCB. Reconnect the mains supply, keypad and LCD, power up the unit, then measure the voltage between pin 3 of U2 (negative) and test point TP3 (0V). U2 is mounted on the heat sink in the top-left corner of the PCB. Pin 3 is the rightmost pin of U2. The voltage should be -5V 5%. 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.5.4 Keypad Checks 1. Check that the keypad connector is correctly plugged into PL2 on the Control Unit PCB. The flexible tail of the keypad should not be twisted or damaged. Ensure that the connector is correctly aligned with PL2. It is possible to misalign the connector if care is not taken. 2. Check that the analyser software is operating. A green LED should be visible through one of the small holes in the bottom-left corner of the Control Unit PCB cover. This LED flashes at about 5Hz when the software is operating correctly. A red LED is visible through another small hole in the bottom-left corner. This LED should not be illuminated if the software is operating correctly. If the red LED is flashing or on all the time then there is a fault on the PCB or in the software and the PCB should be replaced. 3. Check the operation of the keypad. Disconnect the keypad connector from the Control Unit PCB. Connect one lead of a continuity tester to pin 3 of the keypad connector. (Pin 1 is identified by a small triangle moulded into the connector body). Check that each key operates correctly. Each key should connect one pin to the common pin 3 according to the following table: Table 4.3 Keypad Connections Quit 1 Right 6 Down 2 Up 7 Left 4 Menu 8 Enter 5 Measure 9 If the keypad is faulty it must be replaced. Otherwise replace the Control Unit PCB. 4.5.5 Heater Checks Having ensured that basic Control Unit functions are working, the next priority is to ensure that the Sensor Head and sensor(s) are at satisfactory and stable operating temperatures. This is an essential pre-condition for satisfactory measurement performance. Heater Control Algorithms and Interlocks 1. From a cold start, heater power is applied immediately to the Sensor Head band heater and combustibles sensor. The Control Unit does not apply power to the zirconia sensor until the zirconia has naturally heated to approximately 65ºC. 2. The aspirator air solenoid valve is interlocked with the Sensor Head and zirconia sensor temperatures. The solenoid is not energised until the Sensor Head temperature reaches 235C and the zirconia sensor (if fitted) reaches 650C. 3. The same rules also apply for a warm start, but the following should be noted to prevent false diagnosis. When the Control Unit first applies power to a sensor, it monitors the rate at which it heats. If the rate is too slow, the processor inhibits heating, waits for a period and then tries again. This means that during a warm start, the sensor temperatures can fall for a few minutes before warming normally. This period is usually less than 15 minutes, but depends upon ambient conditions and starting temperatures. 02700002D/0 65 SERVOTOUGH FluegasExact Service Manual Start Step 1 Check the following: Sensor Head temperature diagnostic (if connected) Zirconia sensor temperature diagnostic (if fitted) Combustibles sensor temperature diagnostic (if fitted) Step 2 Is Sensor Head temperature OK? No Go to Figure 4.5 Yes Step 3 Is the Zirconia Sensor temperature OK? No Go to Figure 4.7 Yes Step 4 Is the combustibles sensor temperature OK? No Go to Figure 4.8 Yes End See Sections 4.6 and 4.7 for other symptoms Figure 4.4 Initial Heater Checks 66 02700002D/0 SERVOTOUGH FluegasExact Service Manual Start Check wiring, terminations, circuit breakers and intermediate junction boxes Remove Sensor Head terminals box lid. Are either LEDs D10 or D13 illuminated. See Note 1. No No Is AC power available at the Sensor Head? See Note 2. Yes Yes Measure voltage between TP1 and TP2 on Terminals PCB. Voltage = 12 ± 0.7V? Yes Ok No Blown Replace Terminals PCB Check that the transformer primary is wired correctly at TB9. See Table 4.4 Check state of LED D10 Off On Is Sensor Head over / under temperature? Over With the power to the Sensor Head turned off, check fuse F1 Put link wire in correct position. Replace F1. Are diagnostics Ok? Yes No No Check voltage between TB3 pins 1 and 2. Voltage = 6.6 ± 0.7V? Under Incorrect Ok Flashing Check heater wiring is isolated from earth. See Note 3 Yes Check wiring between Sensor Head and Control Unit. See Section 2.4 Go to Figure 4.4 Step 3 Is Sensor Head under temperature? No Yes See Note 5 See Note 6 See Note 4 Temporarily short out TB7 pins 7 and 8. Does LED D10 turn off? No Replace Terminals PCB Yes Check temperature control thermistor and wiring are not open circuit. Replace if needed. Figure 4.5 Sensor Head Heater Checks 02700002D/0 67 SERVOTOUGH FluegasExact Service Manual NOTE 1 The heater status indicator LED on the terminal PCB should be flashing if the heater is controlling the temperature correctly. The LED will be ON if the Sensor Head is under temperature and OFF if the Sensor Head is above the control temperature. NOTE 2 The power wiring of the 2700D differs from earlier Servomex combustion analysers (the 700B and 700EX). Power for the 2700D Control Unit and Sensor Head should generally be wired from a common isolating switch. WARNING Powering down the Control Unit does not automatically remove power from the Sensor Head (unless both have been wired from a common isolating switch). If the Sensor Head is powered down separately from the Control Unit, then the Control Unit will continue to supply heater power to the zirconia and combustibles sensors. Table 4.4 Sensor Head Voltage Selection at TB9 Pin Number Function 1 220/240V Tap 2 AC Supply Input A link wire is fitted to TB9 to select the operating voltage. 3 110/120V Tap For 110/120V operation link Pins 2 and 3. 4 100V Tap For 220/240V operation link Pins 1 and 2. NOTE 3 Disconnect AC power wiring from TB1. Check insulation resistance between both Live and Earth, and Neutral and Earth via TB1. If earth is not fully isolated, check the isolation of the band heater, thermostat and solid state relay. The wiring to each may be isolated via TB8. Replace damaged components and/or wiring as needed. If these 3 components are fully isolated but the fault persists at TB1, replace the Terminals PCB. Reconnect AC power wiring to TB1 only when all associated faults are cleared. NOTE 4 If the heater status LED is ON but the Sensor Head fails to heat correctly, verify the following: The voltage at TB-7 terminal 4 with respect to terminal 3 is in the range +5 V dc to +9Vdc. If necessary change the solid state relay.  The over temperature thermostat connected at TB-8 terminals 5 and 6 is closed. If necessary replace the thermostat.  The heater connected at TB-8 terminals 1 and 2 is not open circuit or intermittent. The ‘240Vac’ heater has a resistance of approximately 110Ω at room temperature and the ‘120Vac’ heater has a resistance of approximately 28Ω at room temperature. If necessary replace the heater.  If the heater status LED is ON, the solid state relay should also be ON. Check the voltage drop across the solid state relay, connected at TB-8 terminals 3 and 4, is not greater than 2 Vac. If necessary replace the solid state relay.  68 02700002D/0 SERVOTOUGH FluegasExact Service Manual NOTE 5 If the heater status LED is OFF and the Sensor Head fails to get hot, verify the following:  Check the resistance of the chest assembly thermistor (TB7 terminals 7 and 8) against the curve shown in Figure 4.6. (At least one lead of the thermistor will need to be disconnected for this check.). A low impedance or short-circuit thermistor will cause the control circuit to switch off and the Sensor Head will fail to heat. Replace the thermistor if necessary.  Check the control circuit operation. A short circuit between TB7 terminals 7 and 8 will cause the control LED to switch off, and an open circuit (or high impedance) will cause the control LED to switch ON. Replace the PCB if necessary. If the heater status LED is OFF but the Sensor Head is over temperature, proceed as follows. Fit a temporary short circuit connection between TB-7 terminals 7 and 8, verify the following:  If the voltage at TB-7 terminal 4 with respect to terminal 3 exceeds 3.0 V dc replace the terminal PCB.  If the voltage at TB-7 terminal 4 with respect to terminal 3 is less than 3.0 V dc replace the SSR.  Remove the temporary short circuit link and ensure correct operation. 1000000 100000 10000 1000 100 0 50 100 150 Temperature in C 200 250 300 Figure 4.6 Thermistor Temperature Curve 02700002D/0 69 SERVOTOUGH FluegasExact Service Manual Start Check Oxygen Sensor ºC Diagnostic. Is temperature 700 ± 10ºC and stable to ± 1ºC Yes Go to Figure 4.4 Step 4 No Yes Is temperature >150ºC No Blown Disconnect zirconia heater wires from TB2 pins 7 and 8 at Control Unit Ok Check zirconia cell heater resistance. See Note 6. Sensor replaced Check fuses F2 and F4 in Control Unit Ok Check zirconia temperature signal. See Note 7. Check each wire is isolated from earth (1MΩ) Ok <1MΩ Check wiring, junction boxes, Sensor Head Terminals PCB and zirconia sensor for faults. Repair or replace parts as needed. Replace Control Unit PCB Fix carried out Figure 4.7 Zirconia Sensor Heater Checks NOTE 6 With the power to the analyser turned off, measure the resistance between terminals 7 and 8 of terminal block TB2 on the Control Unit. The heater resistance should be 8 10%. Note that the measured resistance will include the heater cable which could be up to 4. If the heater cable is long and the resistance reading is low, check the heater resistance at the Sensor Head, terminals 3 & 4 of terminal block TB4, to ensure that the heater is not short-circuit. If the heater is faulty, replace the Zirconia cell. If the temperature diagnostic is unstable, check that the zirconia heater and temperature signal wiring (as described in Note 7) are isolated from earth. 70 02700002D/0 SERVOTOUGH FluegasExact Service Manual CAUTION If a zirconia cell is found to have an open circuit heater coil, ensure correct operation of the zirconia heater control circuit in the Control Unit and thermocouple amplifier in the Sensor Head. This may be checked as follows:  With the zirconia cell disconnected, fit a temporary short circuit between pins 1 and 2 of TB2 in the Sensor Head, then power up the analyser. The output voltage of the thermocouple amplifier between Sensor Head TB3 pins 7 and 8 should be 0.4 to 0.7V DC and the heater voltage at TB3 pins 5 and 6 should be approximately 36V AC.  Now remove the temporary short circuit. The output of the thermocouple amplifier should rise to between 8 and 12V DC and the heater voltage should fall to zero.  If the thermocouple amplifier does not switch as described, replace the Sensor Head Terminals PCB.  If the heater drive does not react as described, replace the Control Unit PCB. NOTE 7 Check the zirconia temperature measurement at the Sensor Head.    Ensure the thermocouple connected at TB2 terminals 1 and 2 is securely connected with the correct polarity (refer to Table 5.3). Ensure the thermocouple is not damaged or open circuit. Correct as necessary and verify performance. Temporarily disconnect the thermocouple wires from TB2 terminals 1 and 2 and temporarily fit a short circuit link. The correct voltage at TB3 terminal 7 with respect to 8 is 0.4 to 0.7Vdc. If necessary replace the Terminal PCB. Temporarily open-circuit TB2 terminals 1 and 2. The correct voltage at TB3 terminal 7 with respect to 8 is between 8.0 and 12.0Vdc. If necessary replace the Terminal PCB. Check the zirconia cell temperature measurement at the Control Unit TB2 terminals 9 and 10. This voltage must be the same as measured at the Sensor Head. 02700002D/0 71 SERVOTOUGH FluegasExact Service Manual Start Check COe Sensor ºC Diagnostic. Is temperature 305 ± 5ºC and stable to ± 1ºC Yes End See Sections 4.6 and 4.7 for other symptoms No Yes Is temperature >150ºC Check fuses F3 and F5 in Control Unit No Disconnect COe heater wires from TB2 pins 1 and 2 at Control Unit Ok Check COe band heater resistance. See Note 8. Sensor replaced Blown Check each wire is isolated from earth (1MΩ) Ok Ok Check Coe PRT. See Note 9. <1MΩ Check wiring, junction boxes, Sensor Head Terminals PCB and COe sensor for faults. Repair or replace parts as needed. Replace Control Unit PCB Fix carried out Figure 4.8 COe Sensor Heater Checks 72 02700002D/0 SERVOTOUGH FluegasExact Service Manual Note 8: With the power to the analyser turned off, measure the resistance between terminals 1 and 2 of terminal block TB2 on the Control Unit. The heater resistance should be 11.4 10%. Note that the measured resistance will include the heater cable which could be up to 4. If the heater cable is long and the resistance reading is low, check the heater resistance at the Sensor Head, terminals 1 & 2 of terminal block TB6, to ensure that the heater is not short-circuit. If the heater is faulty, replace the sensor If the temperature diagnostic is unstable, check that the sensor heater and platinum resistance thermometer wiring (as described in Note 9) are isolated from earth. Also visually inspect the sensor and verify that the gap in its band heater is not located over the platinum resistance thermometer. If so, rotate the band heater until the gap is approximately 90º from the platinum resistance thermometer. Note 9: 02700002D/0 With the power to the analyser turned off, measure the resistance between terminals 3 and 4 of terminal block TB2 on the Control Unit. The resistance should be between 100 and 200 depending on the temperature of the transducer. If the measured resistance is about 3.3k then the PRT is opencircuit. Measure the resistance between TB2 terminals 4 and 5. The resistance should be less than 10. More than 10 indicates an open circuit in the Sensor Head or interconnecting cable. If the PRT is faulty, replace the Tfx sensor. 73 SERVOTOUGH FluegasExact Service Manual 4.6 Measurement Problems This section assumes that:  Both the Control Unit and Sensor Head are powered.  The Control Unit display and keypad are operational.  The Sensor Head and sensor(s) are stable at their respective operating temperatures. Work through Section 4.5 if any of the above assumptions are untrue. 4.6.1 Definitions When investigating reported measurement problems it is critical that the customer’s terminology matches the examples shown below. Drift is a general long term movement (trend) of the output signal level at constant concentration which appears unrelated to ambient temperature but is systematic (i.e. constant, in one direction). In order to differentiate drift from other potential effects (shown below), a minimum 36 hour period on chart is required before drift may be diagnosed. Other fault symptoms as indicated below should be diagnosed and eliminated before attempting to deal with drift only problems. Other Phenomena: 74 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.6.2 Discussion Since the 2700D uses faster measurement technology than in-situ zirconia, pellistor-based CO or cross-stack infra-red analysers, there is considerable scope for confusion because the 2700D will reveal trends in the combustion process which were previously invisible. In some instances the performance of the 2700D is so much at variance to customer expectations that it can be perceived as operating incorrectly. Drift - The most problematic definition is drift - customers often describe any deviation from expected behaviour as ‘drift’. Language also causes problems - for example the literal translation of the German term used to describe the effect of temperature on the reading is ‘temperature drift’. Variable Span Sensitivity - To date this phenomenon has only been reported on the Combustibles measurement. Some reports have been erroneous because customers have not understood that the Tfx sensor is a partial pressure measurement device and that therefore the span sensitivity is directly proportional to variations in flue and ambient pressure. The majority of remaining instances have been due to poor installation of the utilities panel (check for leaks and pressure drop; particularly if the utilities panel is not colocated with the Sensor Head) and/or inconsistencies in the calibration method. If this problem is reported, ensure that the aspirator pressure at the Sensor Head is correct. If the utilities panel is not co-located with the Sensor Head, you must take account of the pressure drop in the aspirator air supply line. Check that the calibration gas flow rate and settling time are consistent each time the analyser is calibrated. Failure to observe these precautions can lead to inconsistent calibration results. Decreasing Span Sensitivity - Again, this complaint is predominantly made about the combustibles measurement. The Tfx catalyst now has improved stability and resistance to poisoning and carbonisation. Tfx sensors may lose 10% of span sensitivity is the first few days on process as the catalyst conditions itself. This is entirely normal and is not grounds for replacing the sensor. Although catalyst sensitivity can be adversely affected by poisons such as SO2, the simplest way to kill a Tfx sensor is to leave it on a process with consistently high levels of CO. This combination of factors is guaranteed to reduce Tfx sensitivity to zero in a short period of time. Two versions of the Tfx sensor are available to suit differing process conditions. For well controlled processes where the COe concentration does not routinely exceed 1500ppm for long periods, and SOx concentrations do not exceed 1000vpm, the high sensitivity sensor should be used. For less well controlled applications (typically coal or heavy oil burning plant) where SOx concentrations exceed 1000vpm, the high sulphur sensor should be used. Refer to technical datasheet for detailed information on combustibles sensor variant applications. 02700002D/0 75 SERVOTOUGH FluegasExact Service Manual Temperature Following - In the majority of cases, this will not be visible while the analyser is on process except if the analyser is subject to large daily temperature swings (30ºC or more) and the process is known to be well controlled. The temperature co-efficient of the analyser has been improved from earlier models. If the Sensor Head build is correct and the problem persists, check that the COe coarse zero is set correctly (i.e. 0V  60mV, refer to Appendix A). If the coarse zero is outside these limits, the temperature co-efficient of the analyser will be degraded. Noise - Complaints regarding noise generally have two causes: 1. The fast analyser response exceeds customer expectations or the ability of the combustion control system to respond. If the control system is not fast enough, the analyser response time can be slowed by the use of the software filter. 2. Poor electrical installation, particularly between the Control Unit and Sensor Head. If non-recommended cables are used or the screens are incorrectly terminated then the combustibles measurement can be susceptible to EMI. Spiking - The issues discussed in Noise also apply to reports of spiking. Spiking on the combustibles measurement can only be detected when the unit is running on calibration gas or when the combustion process is off. If spiking is only said to occur when the combustibles measurement is on process, then it is most likely that the analyser is working correctly and revealing variations in the process which have not been visible to the customer before. Instability, Steps and Ramps - There have been relatively few reports of these phenomena. Like drift, the term ‘instability’ can be used imprecisely. Likely causes of instability in the oxygen measurement have already been covered under the headings of Temperature Following, Noise and Spiking. However, there is one additional issue which affects only the combustibles measurement. If the aspirator air supply pressure is changed during operation, this could lead to a step change in COe reading. Slow Speed of Response / No Response to Process Changes - If either of these are reported, the pneumatics system must be checked before presuming that either or both sensors need to be replaced (see Section 4.6.6 for details). The 2700D Sensor Head design has significantly reduced instances of blocked internal pipework compared to earlier Servomex combustion analysers. The only known instances have occurred when the Sensor Head has been left unheated on the process for a long period. Blockages will affect the Tfx sensor most since its output is more flow dependent than the zirconia sensor. By contrast, because changes in the oxygen level on most processes is relatively slow, sample diffusion within the Sensor Head will allow the zirconia sensor to track process trends quite closely. 76 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.6.3 Oxygen Measurement Checks Start Does the oxygen reading appear to be valid? No Check zirconia cell wiring. See Section 2.4 Ok Yes Check operation of zirconia electronics. See Note 1 Check zirconia cell output. See Note 2 Faulty Replace Control Unit PCB Faulty Replace zirconia cell Ok Fix carried out Is response time satisfactory on calibration gas? No Check pneumatics system. See Section 4.6.6 Yes Does the analyser respond to process changes? No Yes Does the oxygen measurement perform to specification? No See Section 4.6.2 Yes End See Sections 4.6 and / or 4.7 for other symptoms Figure 4.9 Oxygen Measurement Checks  The instructions opposite assume that manual calibration gas valves are fitted. If the system uses solenoid valves, use the analyser to drive the valves and monitor the oxygen mV readings via TB1 terminals 7 and 8 in the Control Unit. 02700002D/0 77 SERVOTOUGH FluegasExact Service Manual Note 1: With the analyser operating and the Zirconia sensor at operating temperature, monitor the oxygen sensor output voltage diagnostic. Apply the high calibration gas (air), wait 5 minutes, then check that the diagnostic reading is zero  5mV. Next apply the O2 low calibration gas (0.3% O2), wait 5 minutes, then check the diagnostic reading. The reading should be as predicted by the Nernst equation (see section 2.3.1)  5mV. If all is in order, perform a manual high and low calibration of the oxygen sensor, overriding any “out of tolerance” warnings. If the diagnostic readings are not correct, turn off the power to the Control Unit and disconnect the wiring from terminal block TB1 terminals 7 and 8. Fit a wire link between terminals 7 and 8. Turn on the power to the Control Unit and monitor the oxygen sensor output voltage diagnostic. The reading should be close to 0V and stable to 0.1mV (drift less than 0.1mV per minute). Remove the wire link and reconnect the field wiring to TB1. If the Control Unit electronics are faulty, replace the Control Unit PCB. Note 2: With the analyser operating and the Zirconia sensor at operating temperature, measure the zirconia sensor output voltage at the Control Unit TB1 terminals 8 (positive) and 7 (negative), or at the Sensor Head TB3 terminals 4 (positive) and 3 (negative). Apply the high calibration gas (air), wait 5 minutes, then check that the cell output is zero  5mV. Next apply the oxygen low calibration gas (0.3% O2 typical), wait 5 minutes, then check that the change in the cell output is as predicted by the Nernst equation (see section 2.3.1)  5mV. If the cell output is outside specification it must be replaced.  A lower than expected oxygen reading is a normal instrument response to the presence of combustibles components in the sample gas stream and may not be an instrument fault. The reduction in the oxygen reading reported is dependent on the combustibles level present and cell type. If there is sufficient combustibles in the sample gas to consume all of the oxygen present, resulting in oxygen reducing conditions at the cell electrode, then a zero oxygen reading may occur.  The 2700D analyser is designed to withstand conducted and radiated RF interference in accordance with the European EMC directive. However, higher field strengths may affect the oxygen reading, usually offsetting the reading from its true value. Good EMC wiring practice and separation / screening of 2700D cables from RF sources should prevent EMC problems from arising 78 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.6.4 Combustibles Measurement Checks Start Are COe mV LOW or COe mV HIGH alarms active? Yes Check Tfx sensor wiring and cell resistance. See Note 1 No Fault Corrected Ok Ok Check operation of Tfx electronics. See Note 2 Faulty Replace Control Unit PCB Check pneumatics system. See section 4.6.6 No adjustment Insert air @ 600ml/min at calibration port. Is Coe mV = 0V ± 60mV? No Adjust Tfx cell coarse zero. See Note 3 Yes Ok Check response to span calibration gas? See Note 4 Low sensitivity Replace Tfx sensor Ok Does the combustibles measurement perform to specification? No See section 4.6.2 Yes End See Section 4.7 for other symptoms Figure 4.10 Combustibles Measurement Checks 02700002D/0 79 SERVOTOUGH FluegasExact Service Manual  The point at which the pneumatics are checked is different from the Oxygen measurement because the response of the Tfx sensor is highly dependent on sample flow rate. Whereas diffusion from the calibration port will allow the zirconia sensor to be checked (albeit slowly), the pneumatics system must be fully functional to obtain representative results from the Tfx sensor. Note 1: With the power to the analyser turned off, check the wiring between the Sensor Head and Control Unit conforms to Section 2.4. If no faults are found, check the Tfx sensor resistance to verify that it is not faulty. Measure the resistance between Sensor Head terminal TB6 terminals 5 and 6, and 7 and 8. Each pair of terminals should measure the same resistance within a few Ohms, from 35 at 25C to 70 at 300C (all 20%). Measure the resistance between TB6 terminals 6 and 8, and 6 and 9. Each pair of terminals should measure the same resistance within a few Ohms, from 26 at 25C to 52 at 300C (all 20%). Measure the resistance between Control Unit TB1 terminals 2 and 5, 3 and 4. Each pair of terminals should measure less than 10. Any incorrect measurement indicates a wiring problem in the Sensor Head or faulty sensor. Note 2: With the power to the analyser turned on, check the drive to the Tfx sensor to verify that it is not faulty. Measure the voltage across TB1 terminals 1 and 6. Use a voltmeter on its DC mV range. The voltmeter will measure the average voltage across the Tfx sensor, which should be between 170mV and 560mV depending on the resistance of the sensor as measured in Note 1 above. Higher resistance gives a higher voltage. If the cell resistances are OK but there is no voltage, replace the Control Unit PCB. If the cell drive voltage is OK, then with the analyser operating and the Tfx sensor at operating temperature, monitor the combustibles sensor output voltage diagnostic. Turn the Tfx coarse zero adjust switch SW2 and check that the voltage display changes. The minimum displayed voltage is -125mV and the maximum displayed voltage is +1125mV. Between these two points the voltage should change by approximately 60mV per switch step. Return SW2 to its original setting. If the diagnostic voltage does not change, replace the Control Unit PCB. Note 3: Refer also to section A11 in Appendix A. With the analyser operating and the Tfx sensor at operating temperature, monitor the combustibles sensor output voltage diagnostic. Apply the zero calibration gas (air), wait 5 minutes, then check that the diagnostic reading is 0mV 60mV. Adjust SW2 and SW3 to improve the zero reading if necessary. There may be a delay of up to 30 seconds between a switch change and an update to the displayed diagnostic value. If the displayed voltage is below 125mV or greater than +1125mV the analogue to digital convertor input is saturated, so the switch settings may need to be moved several positions before a valid reading can be displayed. If the coarse zero cannot be set within the required limits, change the Control Unit PCB. 80 02700002D/0 SERVOTOUGH FluegasExact Service Manual Note 4: Refer also to section A12 in Appendix A. Next apply the CO span calibration gas, wait 5 minutes, then check the diagnostic reading. The difference between the zero and span readings should be 15mV. If the difference is less than this value, change the Tfx cell. If all is in order, perform a manual high and low calibration of the combustibles sensor, overriding any “out of tolerance” warnings.  The output signal from the combustibles sensor is proportional to the sample and ambient pressures. Should the process or ambient pressures change the combustibles sensor output will change proportionally.  The Sensor Head will frequently be operating at a pressure just below ambient atmospheric pressure. Therefore any gas leakage through calibration fittings, pipe work, valves, gas regulators and flow metres may affect the measured reading.  The Tfx1750 sensor will have a small cross sensitivity to other gas species that may be present in the sample stream. Some variation in both zero and span is to be expected if the composition of the sample stream changes.  The 2700D analyser is designed to withstand conducted and radiated RF interference in accordance with the European EMC directive. However, higher field strengths may affect the combustibles reading, usually offsetting the reading from its true value. Good EMC wiring practice and separation/screening of 2700D cables from RF sources should prevent EMC problems from arising. 4.6.5 Flow Alarm Measurement Checks Refer to Figure 4.11. Symptoms  Flow alarm Relay Box has no illuminated LED’s.  Flow alarm cannot be calibrated.  Flow alarm relay in ‘Fault’ condition.  Relays not activating correctly. 02700002D/0 81 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. Description Terminal Block 1 (12Vdc power) Terminal Block 2 (flow alarm sensor connections) Terminal Block 3 (connections to Relay Box) Fuse FS11 (250mA) Figure 4.11 Flow Alarm Amplifier Board Measurement and Diagnosis  Check 12Vdc present at TB1 terminals1 and 2 with respect to 0Vdc on TB3 terminal4.  Check Flow Alarm Relay Box supply fuse FS11.  Check 12Vdc is present on at TB3 terminal1 with respect to TB3 terminal4.  Check the voltage at TB3 terminal 2 with respect to TB3 terminal 3. This should be between approximately 3Vdc (no flow) and 9Vdc (normal flow) in operation.  Check flow alarm sensor wires are correctly terminated on TB2 terminals 1 to 4. Refer to Table 5.4.  Check resistance of flow alarm sensor bridge circuit. Flow alarm sensor wires should be removed from TB2 for the purposes of this test.  Check resistance between blue / red & green / yellow wires is between 50-60Ω at 20°C, or 78-94Ω when Sensor Head is at operating temperature.  The Flow Alarm Signal Amplifier Board and 1760 flow alarm sensor are factory paired/matched. They should only be replaced as a matched pair.  The Flow Alarm Signal Amplifier board has three potentiometers fitted (RV1, 2 & 3). RV1 & RV2 are factory set and sealed with red sealing varnish. These should not be adjusted. RV3 is also factory set so that a signal voltage of 3.0Vdc is present with no flow of sample gas. There should be no need to adjust this, but if adjustment is required it should only be performed under the instruction of a Servomex Engineer.  The Flow Alarm Relay Box electronics board is powered from the Flow Alarm Signal Amplifier Board. The +12Vdc supply to the Flow Alarm Relay Box is protected by Fuse FS11. 82 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Description Zero calibration potentiometer, DS1 & DS2 LED’s Span calibration potentiometer, DS3 & DS4 LED’s Low Flow Alarm status potentiometers DS5 & DS6 LED’s Low Flow Alarm set point adjustment S1 Terminal Block TB1 (connections to Sensor Head Flow Alarm Signal Amplifier Board) Low Flow status relay Flow Fault status relay Terminal Block TB2 (relay terminals) Relay enable switch S2 Relay phase switch S3 Figure 4.12 Flow Alarm Relay Board  Check interconnecting wiring between the Flow Alarm Signal Amplifier board and the Flow Alarm Relay Box board. Refer to Table 2.5.  Check 12Vdc is present at TB1 terminal1 with respect to TB1 terminal 3.  Check the voltage at TB1 terminal 2 with respect to TB3 terminal 3. This should be between approximately 3Vdc (no flow) and 9Vdc (normal flow) in operation.  Check that one LED of each Green / Red LED pair is ON.  Check Relay operation enable switch (S2) is set to ON to allow relays ‘Flow Fault’ and ‘Flow Alarm’ to operate. 02700002D/0 83 SERVOTOUGH FluegasExact Service Manual  Force the ‘Alarm’ relay to operate (indicating low flow) by adjusting the alarm setpoint rotary switch (S1) anticlockwise until DS5 (red) is ON and DS6 (green) is OFF. Check relay contact status changes on TB2 terminals 4, 5 and 6. Changeover operation of this relay will depend on the setting of the phase selection switch S3.  Check ‘Phase’ selection switch (S3) is set to the required operational state as required by the customer control system.  Check Zero and Span potentiometers RV1 and RV2 operate correctly following instructions defined in installation manual for Flow Alarm calibration and set-up. LED COLOUR LED ON STATUS DUTY DS1 DS2 DS3 DS4 DS5 DS6 RED GREEN RED GREEN RED GREEN Calibration set-point low Calibration set-point OK Calibration set-point high Calibration set-point OK Low Flow Alarm ‘ACTIVE’ Low Flow Alarm ‘OFF’ Zero calibration threshold set-point Span calibration threshold set-point Flow alarm status indication  Should either DS1 or DS3 (red LED’s) be illuminated then a ‘FAULT’ condition will exist and the relay will operate (flow measurement outside of calibrated set-points). Its mode of operation depends on the setting of the phase switch S1. DS1 or DS3 red LED’s indicate that current sample flow is outside of calibrated settings. The Flow Alarm should be recalibrated following the instructions in the Installation manual.  DS5 red LED ON indicates the sample flow has fallen below the flow % threshold set by the Flow Alarm set point switch S1. DS6 green LED ON indicates the flow is above the threshold set by the switch S1.  The terminals on the Flow Alarm amplifier board are labelled TB1, 2 and 3. These should not be confused with TB1, 2 and 3 on the lower Terminals PCB.  The 12Vdc supply to TB1 terminal 1 is from the lower terminals board TB7 terminal 4. The 12Vdc supply to TB1 terminal 2 connects to Solid State Relay Terminal 3.  The 0Vdc supply to TB3 terminal 4 is from the lower terminals board TB7 terminals 5 and 6.  The Terminals TB3 terminal1, 2 and 3 are for customer connection wires to the associated Flow Alarm Relay Box. 84 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.6.6 Pneumatics System Checks Start Check flue pressure is not less than -200mmWG See Note 1 Flue pressure too low Application problem. Consult Servomex Ok Check aspirator pressure and flow rate. See Note 2 Outside limits Check aspirator. See Note 3 Ok Low flow Check sample flow. See Note 4 Inspect internal filter for evidence of blockage Dust present Check probe for damage. Add or replace filter as necessary Flow Ok End Go back to Sections 4.6.3 or 4.6.4 or see Section 4.7 for other symptoms Check pipework in Sensor Head for evidence of blockage Blocked No Clear Check probe tube Condensate Did previous test reveal Sensor Head temperature Consult Servomex Yes Replace pipework Dust Add or replace filter as necessary Application problem. Consult Servomex Figure 4.13 Pneumatics System Checks 02700002D/0 85 SERVOTOUGH FluegasExact Service Manual Note 1: Connect a manometer to the calibration gas port on the Sensor Head and measure the flue pressure relative to atmosphere. For a completely accurate reading the aspirator air supply should be turned off, however in normal circumstances the influence of the aspirator is minimal. The internal aspirator is not designed to overcome flue pressures below 200mmWG. If the flue pressure is below this limit then an alternative method of extracting a sample is required. Note 2: Connect a flow meter in series with the aspirator air supply together with a pressure gauge. Check that the aspirator pressure at the Sensor Head is equal to the pressure marked in the Sensor Head terminals compartment; adjust the pressure regulator on the utilities panel if necessary. Once the aspirator pressure is set correctly, check the flow rate is between 1.0 and 1.5 litres/min. Note 3: If the aspirator flow rate is >1.5 litres/min, there is probably a leak at the seating of the aspirator assembly. If the flow rate is <1.0 litres, the aspirator jet is blocked. Clean or replace the aspirator jet as necessary. Also check that the filters in the air line and the line itself are clear of oil before reconnecting the air supply. If contamination is found, verify that the air supply is instrument grade air. If there is no flow at all, check that the Sensor Head solenoid valve is open. Refer to Section 4.6.6 and clear any faults as necessary. Note 4: This test estimates the sample flow by introducing a check gas whose composition is markedly different to the sample being drawn by the analyser. The test is best performed with the oxygen measurement (if fitted) since the response of the zirconia sensor is far less flow dependent than the Tfx sensor. With process sample flowing through the analyser, make a note of the current value of oxygen and/or combustibles on the display. Select a calibration gas which is significantly different from the value given by the process sample (instrument air is normally suitable). Pass 600cc/min of this calibration gas through a flow meter and needle valve into the calibration port, the analyser display should now display the calibration gas value. Gradually reduce the flow of the calibration gas in steps, allowing time for the change in measurement on the display. Now increase the calibration gas flow gradually until the reading approaches the original calibration gas value. At this point, the calibration gas flow is approximately equal to the normal sample gas flow. The process sample flow through the 2700D should be approximately 300cc/minute for an oxygen only analyser. The combustibles only and dual sensor analysers should have a sample flow of approximately 240cc/minute. Flows significantly below this indicate a partially blocked sample path (sample probe, internal filter, etc) or an incorrectly set aspirator air supply. If the analyser reading goes directly to the check gas value then the analyser is not drawing a sample and the cause must be investigated. 86 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.6.7 Aspirator Interlock Failure The solenoid valve on the terminal enclosure must be energised for the aspirator air supply to be applied to the aspirator. In order for the solenoid valve to be energised, the gas sensor(s) and the Sensor Head must all have reached a satisfactory temperature. Use the VIEW menu to determine the temperature of the Sensor Head (if the optional probe head temperature connections are installed) and also the temperature of the gas sensor(s). Verify the following: The oxygen sensor (if fitted) is at or above 650C.  The Sensor Head temperature is at or above 235C. If any of these conditions are unsatisfactory, refer to Section 4.5.5 and correct the fault. If all the temperatures are satisfactory, check the operation of the solenoid valve as follows: Remove the Sensor Head terminal enclosure cover. (Do not remove any protective covers within the terminal enclosure).  Temporarily disconnect the solenoid valve wire at TB7 terminal 2 and ensure the solenoid valve is closed.  Temporarily reconnect the above solenoid valve wire to TP2 (0V) on the terminal PCB. The solenoid valve should be heard to energise and be open. The resistance of the solenoid valve coil is approximately 80Ω at room temperature.  Re-connect the solenoid valve wire to TB7 terminal 2 or replace the valve if necessary. If the temperatures are satisfactory and the solenoid valve still operates incorrectly, replace the terminal PCB. 02700002D/0 87 SERVOTOUGH FluegasExact Service Manual 4.7 Analyser Problems Fault finding guidance within this section assumes that:  Both the Control Unit and Sensor Head are powered.  The Control Unit display and keypad are operational.  The Sensor Head and sensor(s) are stable at normal operating temperatures.  Oxygen and/or combustibles measurements are stable when viewed at the Control Unit display. Work through Sections 4.5 and 4.6 if any of the above assumptions are untrue. Start Step 1 Do analogue (mA) outputs work correctly? No Go to Section 4.7.1 Yes Step 2 Do relays operate correctly? No Go to Section 4.7.2 Yes Step 3 Does manually initiated auto calibration operate correctly? No Go to Section 4.7.3 Yes Step 4 Does manually initiated blow back operate correctly? No Go to Section 4.7.4 Yes Step 5 Does timed auto calibration and/or blow back operate correctly? No Go to Section 4.7.5 Yes End Figure 4.14 Final Analyser Checks 88 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.7.1 Analogue (mA) Output Failure Before carrying out any fault finding, check the following at the Control Unit:  Check that the analogue output assignments are correctly configured and enabled within the analyser software.  In the “Setup” menu, check the range, “0-20/4-20", “freeze/follow” and “jam high/low/none” settings for each analogue output.  If an output is set to jam high or low, check that there is no condition prevailing that is causing the output to jam.  If an output is set to freeze, it will freeze during calibration (both manual and automatic) and blow back. Start Is analogue output load resistance less than 1000Ω and interconnecting cable correctly installed within the screw terminal block on the control PCB? No Check wiring and intermediate junction boxes Incorrec t Replace Control Unit PCB No Set up analogue outputs as per Appendix A.7 Yes Verify basic operation of analogue output(s). See Note 1 Ok Is accuracy ± 0.1mA Yes Go to Figure 4.13 Step 2 Figure 4.15 Analogue Output Checks  The analyser is provided with a jam on fault facility for the analogue outputs. The jam facility operates by forcing the analogue output to a user configurable high (21mA) or low (0mA) level should any of the possible fault conditions occur. The two possible analogue outputs can be separately configured to either jam high, jam low or not to jam in the analyser software. 02700002D/0 89 SERVOTOUGH FluegasExact Service Manual Note 1: 90 Verify operation of the analogue outputs using the “SET OUTPUTS” option in the “SERVICE” menu in the analyser software as follows:  Disconnect the field wiring from the analogue output terminals and connect a mA meter across each pair of terminals. If a mA meter is not available, fit a resistor of 1k or less across each pair of terminals and measure the voltage across the resistor. Divide the measured voltage by the resistance to obtain the current.  Using the “Service” menu, set the analogue outputs to 0mA and check that each output measures 0.1mA or less.  Set the analogue outputs to 20mA and check that the readings are 20mA 0.1mA. If resistors and a voltmeter are used, the calculated current must be based on the measured resistance of the resistor and not its nominal value. The analogue output span can be adjusted with RV3 and RV4, but this should be done with the analogue outputs connected to the equipment that they are to be used with (also see Appendix A7).  Set the analogue outputs to 4mA and check the readings are 4mA 0.1mA. 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.7.2 Relay Output Failure Before carrying out any other fault finding, check that the relay assignments are correctly configured and enabled within the analyser software. Start Is all interconnecting wiring correctly installed within the screw terminal block on the control PCB? No Check wiring and intermediate junction boxes Yes Verify basic operation of relay outputs. See Appendix A.8 Incorrec t Replace Control Unit PCB Go to Figure 4.13 Step 3 Figure 4.16 Relay Output Checks 4.7.3 Auto Calibration Failure Symptoms  Auto calibration fault indicated.  Analyser does not start an auto calibration.  Poor accuracy following calibration.  Auto calibration is not activated by closure of external contacts. Measurements and Diagnosis 02700002D/0  Check that the auto calibration configuration is correctly configured and enabled within the analyser software. Check that the contents of the calibration gas samples have been correctly entered into the analyser software.  Check that the time and date have been correctly set in the analyser software. Check that the auto calibration start time and date have been correctly configured. Check that a blow back procedure has not been configured to start at the same time, or immediately before, the auto calibration. If an auto calibration attempts to start while a blow back is in progress then the auto calibration will be aborted.  For remote auto calibration actuation via remote contact closure, check that connecting wiring is correctly installed and that the external initiation contacts are closed for at least 15 seconds.  Check that the calibration gases have been correctly connected to the calibration gas port. Check that the calibration gases are not empty and have been turned on. Check that the calibration gas flow rate is 600 20ml/min. 91 SERVOTOUGH FluegasExact Service Manual  Check that there are no leaks in the interconnecting calibration gas piping and that any flow meters and needle valves fitted operate correctly.  Check for correct operation of the calibration gas solenoid valves. Perform a leak test to verify cross seat leakages. Check the wiring between the solenoid valves and the relay outputs. Check that the relay outputs are correctly allocated in the analyser software.  Check for inappropriate calibration tolerance values (too tight) stored in the software parameters. Increase the calibration tolerances if necessary. Otherwise refer to the particular transducer measurement error faults in Section 4.6.  If an “AUTO CAL FAIL” fault has occurred then the only way to disable the fault is to perform a successful automatic calibration. Perform a single cycle immediate auto calibration to clear the fault. 92 02700002D/0 SERVOTOUGH FluegasExact Service Manual 4.7.4 Blow Back Failure Symptoms  Analyser does not start a blow back process.  Blow back is not activated by closure of external contacts. Measurements and Diagnosis 4.7.5  Check that the blow back configuration is correctly configured and enabled within the analyser software.  Check that the time and date have been correctly set in the analyser software. Check that the blow back start time and date have been correctly configured. Check that an auto calibration has not been configured to start at the same time, or immediately before, the blow back. If a blow back attempts to start while an auto calibration is in progress then the blow back will be aborted.  For remote blow back actuation via remote contact closure check that connecting wiring is correctly installed and that the external initiation contacts are closed for at least 15 seconds.  Check that there are no leaks in the interconnecting calibration gas piping and that any flow meters and needle valves fitted operate correctly.  Check for correct operation of the blow back solenoid valve. Perform a leak test to verify cross seat leakage. Check the wiring between the solenoid valves and the relay outputs. Check that the relay outputs are correctly allocated in the analyser software. Analyser Does Not Keep Correct Time or Date Symptoms  Time and/or date requires frequent correction or does not work. Measurements and diagnosis 02700002D/0  Check that the internal clock has been correctly set and the instrument has not been powered down for a period exceeding one month.  Replace the control PCB and re-validate analyser performance. 93 SERVOTOUGH FluegasExact Service Manual 5 PARTS REPLACEMENT PROCEDURES 5.1 Control Unit Access Key Description 1. Door 2. Captive M6 screws (4 off) 3. M4 retaining screws (4 off) Key Description 4. Plastic insulating cover 5. Hinge pins (2 off) Figure 5.1 Control Unit Access 94 02700002D/0 SERVOTOUGH FluegasExact Service Manual The Control Unit is fitted with a hinged die cast aluminium door sealed by a silicon rubber O-ring and secured by four captive M6 screws. Inside of the Control Unit a transparent plastic insulating cover protects the user from access to electrical terminals that may be exposed to hazardous high voltages. Removal Refer to Figure 5.1. 1. Undo the 4 captive M6 screws (2) and open the hinged door (1). WARNING Removal of the plastic insulating cover exposes the user to potentially lethal voltages. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 2. To gain access to the electrical power and relay contact terminals, remove the 4 M4 retaining screws (3) and lift out the clear plastic cover (4) which insulates the terminals. Refitting 1. Check that all the electrical connections are secure and refit the clear plastic cover (4) and secure it with the 4 retaining screws (3). Do not use any thread lock on these screws. 2. Check that the O-ring seal in the door is correctly located and undamaged. Wipe the Oring and mating surfaces to remove any dust or grease. 3. Close the hinged door (1) and secure it with the 4 captive screws (2). 5.2 Control PCB Removal and Replacement There are four versions of the control PCB that may be fitted to the analyser defined by the sensor configuration and build date of the product. 2700D Control Units with a serial number of 20,000 or later are fitted with a common control board that can be configured for the three sensor configurations, set by DIP switches. 2700D Control Units with a serial number below 20,000 still require one of three control boards which are listed in Section 3.  The common control board must not be fitted into an older Control Unit for compliance reasons. Refer to Figure 5.2. 02700002D/0 95 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Description Keypad ribbon cable connection LCD ribbon cable connection Metal protection cover M4 mains protection cover retaining screws (4 off) M4 PCB retaining screws (8 off) Transformer secondary connection Transformer primary connection M4 PCB earth wire connection FLASH memory chip M4 Transformer earth connection Sensor configuration DIP switches Figure 5.2 Control Unit Internals 96 02700002D/0 SERVOTOUGH FluegasExact Service Manual Removal 1. If a new control PCB is to be fitted after removal, then note the analyser software settings and sensor configuration before proceeding. 2. Switch off all electrical power to both the Control Unit and Sensor Head. Isolate any power sources connected to the relay terminals. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages resulting from external electrical connections to the relay contacts even when electrical power is disconnected from the Control Unit itself. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 3. Refer to Section 5.1. Open the Control Unit door and remove the transparent plastic insulation cover. 4. Disconnect all the wires from the terminals and withdraw the cables to allow clearance for removal of the metal protection cover and the PCB. 5. Unplug the keypad ribbon cable (1) and the LCD ribbon cable (2) from the control PCB. 6. Remove the 5 off M4 cover retaining screws (4) retaining the metal cover (3) to the control box casting. Remove the metal cover (3) from the control box. 7. Remove the M4 screw (8) for the PCB earth wire connection. 8. Unplug the transformer primary (7) and secondary (6) connectors from the control PCB. 9. Remove the 7 off M4 PCB retaining screws (5) and the hexagonal pillar and lift out the control PCB. Refitting 1. Replace using the reverse procedure.  Locate and secure the PCB earth connection onto the cast boss on the Control Unit enclosure before locating the PCB in the Control Unit.  When refitting the PCB ensure that the heat sink plate locates securely on the bosses on the Control Unit casting before tightening fixings.  Ensure that the transformer wires, transformer earth and PCB earth wires are not trapped under the PCB before tightening fixings. 2. Ensure that the transformer primary connection (PL6 or PL7 in Figure 5.2) and the main power fuse rating are appropriate for the electrical supply voltage (see Table 5.1). 02700002D/0 97 SERVOTOUGH FluegasExact Service Manual Table 5.1 Control Unit Electrical Power Voltage Selection Nominal Voltage Transformer primary connection Main power fuse (F1) rating 100 / 110 / 120 Vac PL7 T 3.15A HRC 220 / 240 Vac PL6 T 1.6A HRC 3. If a new control PCB has been fitted, then this will have a default software configuration. Refer to the 2700D Quickstart manual for detailed instructions on setting software parameters. 4. Refer to Figure 5.3. Ensure the measurement transducer configuration DIP switches are set to the correct positions for the sensors located in the sensor enclosure of the Sensor Head. Sensor ON is when the switch is positioned away from the text “O2” and/or “CO” (the down position). 5. Refer to Appendix A for detailed analyser performance checking. ON ON CO COe ONLY O2 CO OXYGEN & COe O2 CO O2 OXYGEN ONLY ON Figure 5.3 Measurement Transducer DIP Switch Configurations 98 02700002D/0 SERVOTOUGH FluegasExact Service Manual 5.3 Control Unit Transformer Removal and Replacement The Control Unit is provided with a toroidally wound twin primary, dual secondary, transformer mounted underneath the control PCB in the Control Unit. Key Description 1. Transformer 2. M6 retaining screw Key Description 3. Earth connection Figure 5.4 Control Unit Transformer Detail Removal and refitting 1. Refer to Section 5.2. Remove the control PCB from the Control Unit. 2. Disconnect the M4 transformer earth connection (3) from the boss inside of the control box enclosure. 3. Remove the M6 retaining screw (2) and lift out the transformer. 4. Replace using the reverse procedure. When refitting the transformer, rotate the transformer so that the wires route towards the top right hand corner of the Control Unit enclosure. 02700002D/0 99 SERVOTOUGH FluegasExact Service Manual 5.4 Firmware Installation The 2700D analyser is supplied with firmware, with a user selectable interface in English, French or German. The firmware is supplied preloaded into a FLASH memory chip. Refer to Figure 5.2. Removal and refitting 1. Switch off all electrical power to both the Control Unit and Sensor Head. Isolate any power sources connected to the relay terminals. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages resulting from external electrical connections to the relay contacts even when electrical power is disconnected from the Control Unit itself. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 2. Refer to Section 5.1. Open the Control Unit door and remove the transparent plastic insulation cover. 3. Disconnect all the wires from the terminals and withdraw the cables to allow clearance for removal of the metal protection cover. 4. Unplug the keypad ribbon cable (1) and the LCD ribbon cable (2) connectors from the control PCB. 5. Remove the 5 off M4 cover retaining screws (4) retaining the metal cover (3) to the Control Unit casting. Remove the metal cover (3) from the control box. 6. Using an appropriate extraction tool remove the microcontroller chip from the control PCB.  When fitting a new memory chip in the control PCB ensure that the chamfered corner on the chip is correctly located within the socket on the PCB. 7. Replace using the reverse procedure. 100 02700002D/0 SERVOTOUGH FluegasExact Service Manual 5.5 Display Removal and Replacement Refer to Figure 5.5. Removal and refitting 1. Switch off all electrical power to the Control Unit. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages resulting from external electrical connections to the relay contacts even when electrical power is disconnected from the Control Unit itself. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 2. Refer to Section 5.1. Open the Control Unit door. Do not remove the transparent mains protection cover. 3. Remove the 2 off M3 cover retaining screws and washers (2) and remove the display protection cover (1) from the display( 4). 4. Unplug the display ribbon cable (8) from the control PCB. Release the display ribbon cable (8) from the ribbon cable clamp (9). 5. Remove the 2 off M3 cover spacers and washers (3). Remove the 2 off M3 display retaining screws and washers (5). Lift off the liquid crystal display (4) from the keypad (7). 6. Replace using the reverse procedure; ensure that the display module is fitted with the cable at the bottom of the module. 02700002D/0 101 SERVOTOUGH FluegasExact Service Manual Key Description 1. Display protection cover 2. M3 cover retaining screws (2) 3. M3 cover spacers + insulation washers (2) 4. Liquid crystal display 5. M3 display retaining screws + insulation washers(2) 6. M4 keypad retaining screws (2) Key 7. 8. 9. 10. 11. 12. Description Keypad Display ribbon cable Display ribbon cable clamp Keypad ribbon cable Keypad retaining frame O-ring seal Figure 5.5 Display and Keypad Mounting Details  When refitting the LCD/display with the 2 off M3 retaining screws (5) and M3 cover spacers (3) ensure that the washers are fitted in order to prevent the screws bottoming out in the threaded spacers. Also ensure the insulating washers are fitted between the LCD and stainless steel washers.  When fitting the protection cover (1) with the 2 off M3 retaining screws (2) then ensure that the washers are fitted in order to prevent the screws bottoming out in the threaded spacers. Do not use thread lock on these screws.  Examine the ribbon cable clamp (9) and replace if damaged. If the keypad has been replaced then fit a new ribbon cable clamp in all cases. 102 02700002D/0 SERVOTOUGH FluegasExact Service Manual 5.6 Keypad Removal and Replacement Refer to Figure 5.5. Removal and refitting WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages resulting from external electrical connections to the relay contacts even when electrical power is disconnected from the Control Unit itself. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 1. Switch off all electrical power to the Control Unit. 2. Refer to Section 5.5. Remove the display. 3. Unplug the keypad ribbon cable (10) from the control PCB. 4. Remove the 12 off M4 keypad retaining screws (6). Remove the keypad retaining frame (11) and lift out the keypad (7) from the recess in the hinged door 5. To replace, check that the O-ring seal (12) in the door is correctly located and undamaged. Wipe the O-ring and mating surfaces with a damp cloth to remove any dust or grease. Replace the keypad using the reverse procedure. 5.7 Sensor Head and Terminal Box Cover Removal and Replacement Refer to Figure 5.6. The Sensor Head is designed to be flange mounted directly on to the flue wall and is heated. Service access to the Sensor Head and its terminal enclosure may be restricted. Depending on installation location it may be advisable to remove the Sensor Head from the flue wall to provide convenient service access. The installation details for the Sensor Head vary depending on the sample probe type in use and the specific flange mounting arrangement. Refer to the 2700D Installation manual for specific details on the mounting arrangement in use. The terminals compartment is sealed for dust and moisture ingress by an O-ring secured into the terminal compartment lid. The sensor compartment is similarly sealed by an O-ring located in the Sensor Head base. 02700002D/0 103 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. Description Mounting flange Sensor head base casting Insulation spacer Terminal box casting Key 5. 6. 7. 8. Description Terminal box cover Terminal cover screws Sensor head cover Sensor cover screws Figure 5.6 Sensor Head Overview 104 02700002D/0 SERVOTOUGH FluegasExact Service Manual Removal WARNING The 2700D Sensor Head, excluding the probe assembly, weighs approximately 17Kg (38 lbs), care must be taken when handling. The analyser may contain toxic, corrosive, flammable or asphyxiant gases. Vent the analyser to a safe area and flush with air before commencing work. The Sensor Head is heated and may be attached to a hot flue. The external surfaces will be uncomfortably hot even after power down for several hours. Exercise care when handling the Sensor Head even when un-powered on a hot flue. 1. Connect an air supply or other inert gas to the calibration gas port at a flow rate of 600 ml/min. Allow the Sensor Head to flush for 10 minutes to remove potentially toxic and flammable gases from the Sensor Head pipe work. 2. Turn off the aspirator air supply and then isolate the electrical supply to the Sensor Head and Control Unit. The Sensor Head can then be left to cool while the flow of air or other inert gas is maintained. 3. If service access to the Sensor Head is limited when attached to the flue then remove the Sensor Head from the flue. 4. To gain access to the Sensor Head terminal PCB and the electrical terminations proceed as follows: Undo the 4 off captive M6 screws (6) and remove the terminal box cover (5). To gain access to the electrical power terminals remove the M4 retaining screw and lift out the clear plastic cover which insulates the terminals. WARNING Removal of the plastic insulating cover when the Sensor Head is powered exposes the user to potentially lethal voltages. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 5. To gain access to the Sensor Head oven compartment proceed as follows: Undo the 4 off captive M6 screws (8) and remove the sensor compartment cover (7). WARNING The sensor compartment is heated to a temperature of 250C and may be attached to a hot flue. Removal of the sensor compartment cover exposes the user to potentially hazardous hot components. If the sensor compartment cover is to be removed then it is recommended that the Sensor Head be left for 2 hours to cool down first after electrical isolation. 02700002D/0 105 SERVOTOUGH FluegasExact Service Manual Replacement 1. Check that the electrical connections to the Terminals PCB are secure and refit the clear plastic insulating cover. Do not use thread lock on these screws. 2. Check the O-ring seals in the terminal compartment lid and in the Sensor Head base are correctly located and undamaged. Wipe the O-rings and mating surfaces with a damp cloth to remove any dust or grease. 3. Refit the terminal compartment lid and sensor compartment lid and secure with the M6 captive screws. 4. If necessary remount the Sensor Head to the flue and power up the Sensor Head using the procedure detailed in the installation manual. CAUTION If the sensor is mounted with the terminal box vertically above the Sensor Head body then the accuracy and service life may be reduced.  Ensure that mounting bolts are tightened evenly to ensure the Sensor Head and any mounting flanges seal properly. Particular care must be taken if the Sensor Head is mounting onto a raised face flange.  When refitting a Sensor Head always check the integrity of the flange sealing gasket. Servomex always recommend this gasket is replaced when refitting a Sensor Head.  The Sensor Head must not be left unpowered when mounted on an active (hot) flue. If the sample probe is not to be fitted immediately then a suitable blanking flange should be used. Do not plug the hole with the Sensor Head.  A sachet of anti-seize compound (part number 1761-3211) is supplied as standard as part of the analyser’s ‘loose items’ kit and is available for use on the Sensor Head mounting bolts and studs. Failure to use the anti-seize compound may make the fixings difficult to remove in the future.  When refitting the Sensor Head onto an active (hot) flue, ensure a continuous flow of air or other inert gas is supplied to the calibration port. This flow should be maintained until the Sensor Head is powered and has reached operating temperature. 106 02700002D/0 SERVOTOUGH FluegasExact Service Manual 5.8 Terminals PCB Removal and Replacement Refer to Figure 5.7. There are five versions of the Terminals PCB that may be fitted to the analysers defined by the sensor configuration fitted. Section 3 lists the part numbers of the five spare PCB’s.  It is critical that the correct Terminals PCB is fitted to maintain correct operation of the Sensor Head. Please note the optional Flow Alarm module also dictates which Terminals PCB type should be fitted. Removal 1. Refer to Section 5.7 (and Figure 5.11 if a Flow Alarm module is fitted). Remove terminal compartment cover and disconnect the electrical power from both the Control Unit and Sensor Head. Remove the M4 protection cover retaining screw (11) and remove the protection cover (8) that insulates the mains rated electrical power connection beneath it. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages if the electrical supply is not disconnected first. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 02700002D/0 107 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Description Solid state relay Terminal block TB2 Terminal block TB7 Solenoid valve Solenoid valve retaining nut Terminal PCB earth connection Terminal block TB9 Transparent protection cover Terminal block TB8 Terminal block TB1 Key 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Description M4 cover fixing screw Mains fuse F1 Terminal block TB3 Terminal block TB4 Terminal block TB6 Terminal block TB5 M4 Terminal PCB fixing screws Wiring support P clip + EMC ferrite Transformer Earth stud Figure 5.7 Sensor Head Terminal Enclosure Detail (without Flow Alarm)  If the Sensor Head is fitted with a Flow Alarm module, the Flow Alarm signal amplifier PCB sits above items (3) and (19). See Section 5.13 for Flow Alarm PCB removal. 108 1. Disconnect all mains power and electrical interconnecting wiring from terminal blocks TB1, TB3 and TB5 and withdraw the cables to allow clearance for removal of the PCB. Disconnect any interconnecting wiring shield connections from the ground post at the bottom edge of the PCB. Make a note of the schedule of the interconnecting wiring to facilitate later reconnection. 2. Remove the clip (18) and EMC ferrite supporting the internal sensor wiring. Disconnect all internal wiring to the sensor compartment from terminal blocks TB2, TB4, TB6, TB7, 02700002D/0 SERVOTOUGH FluegasExact Service Manual TB8 and the sensor wiring screen from PCB fixing screws (if fitted). Withdraw the internal wiring to allow clearance for removal of the PCB. 3. Disconnect the terminal PCB earth wire from the terminal box casting (6). 4. Remove the remaining 5 off M4 PCB fixing screws (17) and lift out the terminal PCB. Replacement 1. The mains operating voltage is set by connecting together the appropriate terminals in terminal block TB9 (see Table 5.2). If a new Terminals PCB is being fitted then set the correct mains operating voltage. Table 5.2 Terminal PCB Voltage Selection Links Nominal Voltage Configuration Set Up 100V ac Link TB9-2 to TB9-4 110 / 120V ac Link TB9-2 to TB9-3 220 / 240 V ac Link TB9-2 to TB9-1 2. Locate the Terminals PCB over the mounting holes and secure with 5 of the 6 M4 fixing screws (17). Do not fit the remaining screw that locates the wiring support P clip (18) until the internal sensor wiring is completed. 3. Internal combustibles cell wiring must pass through the EMC ferrite. 4. Reconnect the internal sensor wiring in accordance with the wiring schedule in Table 5.3. 5. Reconnect the mains power and interconnecting wiring. Connection details should have been noted on disconnection. Interconnecting wiring schedules and diagrams are given in Section 2.4. 6. Check that all electrical connections are secure then refit the clear plastic cover (8) and secure it with the retaining screw (11). Do not use any thread lock on this screw. 7. Replace the terminal compartment cover as detailed in Section 5.7. 8. Follow the start-up procedure listed in the installation manual and the basic operational checks detailed in Appendix A. 02700002D/0 109 SERVOTOUGH FluegasExact Service Manual Table 5.3 Sensor Head Internal Wiring Schedule Terminal TB2-1 TB2-2 TB4-1 TB4-2 TB4-3 TB4-4 TB6-1 TB6-2 TB6-3 TB6-4 TB6-5 TB6-6 TB6-7 TB6-8 Function Zirconia thermocouple Zirconia cell outputs Colour -ve WHITE +ve GREEN -ve BLUE +ve YELLOW RED Zirconia heater output Polarity not important RED BEIGE/BLACK Combustibles cell heater Polarity not important BEIGE/BLACK RED Combustibles cell temperature Polarity not important. Combustibles cell supply voltage Combustibles cell output RED +ve BROWN -ve GREEN +ve BLUE -ve YELLOW PCB MOUNTING Combustibles cell braided screen (chassis earth) CRIMP LUG TB7-1 Solenoid valve Polarity not important BLACK TB7-2 TB7-3 TB7-4 TB7-5 TB7-6 TB7-7 TB7-8 TB8-1 TB8-2 TB8-3 TB8-4 TB8-5 TB8-6 Solid state relay drive connections BLACK -ve BLUE +ve RED Not used Link fitted BLUE Block temperature thermistor Used on all versions Polarity not important WHITE Block band heater Polarity not important BEIGE Solid state relay power output connection Polarity not important Over-temperature thermostat Polarity not important BLUE WHITE BEIGE GREY GREY BEIGE BEIGE  Earlier 2700D builds were fitted with over-temperature thermostats with mauve wiring. 110 02700002D/0 SERVOTOUGH FluegasExact Service Manual 5.9 Solenoid Valve Removal and Replacement Refer to Figure 5.7. The 2700D solenoid valve is fitted with a 12Vdc actuating coil. Removal and refitting 1. Refer to Section 5.7. Remove the terminal compartment cover and switch off the electrical power to the Sensor Head and Control Unit. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages if the electrical supply is not disconnected first. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 2. Disconnect the compressed air supply to the solenoid valve. Remove the interconnecting pipe to the Sensor Head aspirator air inlet and associated 1/4" OD compression fitting. 3. Depending on the type of tool at hand it may be necessary to remove the Terminals PCB (and Flow Alarm PCB if fitted) in order to access the solenoid valve retaining nut (5). Check with the tool being used that the retaining nut can be removed without the tool fouling the Terminals PCB. If necessary remove the Terminals PCB as described in Section 5.8. 4. Disconnect the electrical supply to the solenoid valve from terminal block TB7 terminals 1 and 2. 5. Remove the solenoid valve retaining nut (5). Lift out the solenoid valve body through the hole machined in the casting. Lift out the solenoid valve actuating coil from the inside of the terminal box. 6. Replace using the reverse procedure. Ensure that a new fibre sealing washer (supplied with kit) is refitted between the valve body and the enclosure. 5.10 Solid State Relay Removal and Replacement Refer to Figure 5.7. Removal and refitting 1. Refer to Section 5.7. Remove the terminal compartment cover and disconnect the electrical power from the Sensor Head. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages if the electrical supply is not disconnected first. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. 02700002D/0 111 SERVOTOUGH FluegasExact Service Manual 2. Remove the transparent insulation cover from the top of the solid state relay. Disconnect the four electrical connections from the solid state relay. Remove the 2 off M4 retaining screws and lift out the solid state relay. 3. Replace using the reverse procedure. Ensure that the solid state relay and its transparent insulation cover are fitted in the correct orientation, and that the red wire is connected to terminal 3 and the blue wire to terminal 4. 5.11 Zirconia Cell Removal and Replacement Refer to Figure 5.8. WARNING When undoing or retightening the pipe work associated with the oxygen sensor, always use two spanners and take care not to twist the cell otherwise it may be damaged. The zirconia cell is provided with machined flats to assist in removing fittings without stressing the cell. Removal and refitting 1. Refer to Section 5.7. Switch off the electrical power to both the Sensor Head and Control Unit and remove the terminal compartment cover and sensor compartment cover. WARNING Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Refer to Figure 5.7. Disconnect the zirconia sensor wiring from terminal blocks TB2 (2) (thermocouple wires) and TB4 (14) (heater and signal wires) on the Terminals PCB. Withdraw the signal wires into the sensors compartment. Take note of the wire positions and ensure that the new sensor wires are routed in the same manner. 3. Refer to Figure 5.8. Disconnect the reference air pipe (8) compression fittings at the bulk head, auxiliary air restrictor (9) and the flame trap (10) and remove the reference air pipe. 4. Disconnect zirconia cell (4) from the cell connector (1) by undoing the 3/8" compression fitting nut (2). Release this cell nut by using an appropriate spanner on the nut (2) and on the adjacent flats (3) on the oxygen cell so as not to twist the cell. If the cell connection is stuck, keep undoing the compression nut (2) and use the jacking shoulder to pull the stuck ferrules from the cell. 5. A course mesh filter (7) is attached to the reference side of the zirconia cell using a second 3/8" compression fitting nut (6). Remove the nut (6), and filter (7) using two spanners and the machined flats on the cell (5) in the same manner as above. Retain the filter for reuse on the new cell. 6. Replace using the reverse procedure. The new sensor will be provided with a fibreglass sleeve insulating the cell wires. Refer to Table 5.3 for cell wiring connection details. 7. Follow the start-up procedure listed in the installation manual and the basic operational checks detailed in Appendix A. 112 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key 1. 2. 3. 4. 5. Description Cell connector 3/8” nut, sample side Flats on cell Zirconia cell Flats on cell Key 6. 7. 8. 9. 10. Description 3/8” nut, reference side Mesh filter Reference air pipe Auxiliary air restrictor Flame trap Figure 5.8 Zirconia Sensor Installation Details  Figure 5.8 shows a dual sensor configuration without a Flow Alarm module fitted. 02700002D/0 113 SERVOTOUGH FluegasExact Service Manual 5.12 Combustibles Cell Removal and Replacement Refer to Figure 5.9. Removal and refitting 1. Refer to Section 5.7. Switch off the electrical power to both the Sensor Head and Control Unit and remove the terminal compartment cover and sensor compartment cover. WARNING Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Refer to Figure 5.7. Disconnect the combustibles sensor wiring from terminal block TB6 (15) on the Terminals PCB. Withdraw the signal wires through the EMC ferrite and back into the sensors compartment. Take note of the wire positions within the Sensor Head and ensure that the new sensor wires are routed in the same manner. 3. Refer to Figure 5.9. Disconnect the 1/8" compression fitting (4) at the junction between the combustibles sensor (3) and the cell connector (6). Use two spanners on the 1/8" nut (4) and the hexagonal section on the cell connector (5). Avoid twisting the cell connector fitting. 4. Disconnect the 1/8" compression fitting (2) at the junction between the combustibles sensor (3) and the flame trap (1). Use two spanners as above to avoid twisting the flame trap. 5. Replace using the reverse procedure. The new sensor comes complete with PTFE sleeving and braided screen over the cell wires. Refer to Table 5.3 for cell wiring connection details. Ensure that the wires are routed away from the filter block and the band heater, and are passed through the EMC ferrite. CAUTION When fitting a new combustibles sensor ensure that the gap in the combustibles sensor band heater is not located directly over the platinum resistance thermometer. Failure to do this may result in drifting performance. 6. Follow the start-up procedure listed in the installation manual and the basic operational checks detailed in Appendix A.  When fitting the high sulphur variant of the combustibles cell, ensure the high temperature shunt assembly is replaced in TB6 terminals 3 and 4 (refer to Figure 5.7). To aid removal of the combustibles cell, it may be necessary to remove the zirconia cell and aspirator air pipe. 114 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key Description 1. Flame trap 2. 1/8” compression fitting, outlet 3. Combustibles sensor Key Description 4. 1/8” compression fitting, inlet 5. Hexagonal section 6. Cell connector Figure 5.9 Combustibles Sensor Installation Details 02700002D/0 115 SERVOTOUGH FluegasExact Service Manual 5.13 Flow Alarm Removal and Replacement Refer to Figure 5.8. WARNING When undoing or retightening the pipe work associated with the Flow Alarm Sensor, always use two spanners and take care not to twist the cell otherwise it may be damaged. Removal and refitting  The Flow Alarm Sensor and associated signal amplifier board must be replaced together as they make up a paired/matched module. 1. Refer to Section 5.7. Switch off the electrical power to both the Sensor Head and Control Unit and remove the terminal compartment cover and sensor compartment cover. WARNING Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Refer to Figure 2.9 (in Section 2.1.1.2). Disconnect the flow alarm sensor wiring from terminal block TB2 (7) on the Flow Alarm signal amplifier board. Disconnect the Relay Box interconnecting wiring from terminal block TB3 (4). Also disconnect supply wiring from terminal block TB1 (3). Withdraw the Flow Alarm signal wires through into the sensors compartment. Take note of the wire positions and ensure that the new sensor wires are routed in the same manner. 3. Refer to Figure 5.10. Using two spanners, disconnect the 1/8” compression fittings at the junction between the flow sensor (1) and the Flow Alarm mounting arms (3). Avoid twisting the Flow Alarm mounting arms. 4. Lift flow sensor away from the cell connector (2). 5. Replace with the new flow sensor using the reverse procedure. Refer to Table 5.4 for flow alarm sensor wiring. Ensure the flow alarm sensor wiring is routed away from the chest assembly and band heater. 6. Refer to Figure 5.11. Remove 2 off M4x12 screws (3), 1 off M4x8 screw (1), and washers (4). If EMC ferrite is fitted, move to one side to allow the removal of the Flow Alarm signal amplifier board. 7. Remove Flow Alarm signal amplifier board by carefully lifting away from the terminals enclosure. 8. Refit new PCB using the reverse procedure. Refer to Table 5.4 for flow alarm sensor wiring. 9. Follow the start-up procedure listed in the installation manual and the basic operational checks detailed in Appendix A. 116 02700002D/0 SERVOTOUGH FluegasExact Service Manual Key Description 1. Flow alarm 2. Cell connector Key Description 3. Flow alarm 1/8” welding fitting (2) Figure 5.10 Flow Alarm Installation Details 02700002D/0 117 SERVOTOUGH FluegasExact Service Manual Key Description 1. M4x8 Screw (2) 2. Wiring support P-clip 3. M4x12 Screw Key Description 4. M4 Washer (3) 5. Flow Alarm signal amplifier board Figure 5.11 Flow Alarm Signal Amplifier Board Installation Details 118 02700002D/0 SERVOTOUGH FluegasExact Service Manual Table 5.4 Flow Alarm Internal Wiring – Flow Amplifier Board Terminal TB1-1 TB1-2 Function +12Vdc Supply Colour +ve RED/WHITE +ve RED TB2-1 TB2-2 TB2-3 BLUE YELLOW Flow alarm signals from 1760 sensor GREEN TB2-4 TB3-4 RED 0Vdc Supply -ve BLUE  The terminals on the Flow Alarm amplifier board are labelled TB1, 2 and 3. These should not be confused with TB1, 2 and 3 on the lower Terminals PCB.  The 12Vdc supply to TB1 terminal 1 is from the lower terminals board TB7 terminal 4. The 12Vdc supply to TB1 terminal 2 connects to Solid State Relay Terminal 3.  The 0Vdc supply to TB3 terminal 4 is from the lower terminals board TB7 terminals 5 and 6.  The Terminals TB3 terminal1, 2 and 3 are for customer connection wires to the associated Flow Alarm Relay Box. 02700002D/0 119 SERVOTOUGH FluegasExact Service Manual 5.14 Cell Connector Removal and Replacement Key 1. 2. 3. 4. 5. 6. 7. 8. Description Band heater Aspirator assembly Flame trap Chest assembly Over temperature thermostat Combustibles sensor Reference air pipe Zirconia oxygen sensor Key 9. 10. 11. 12. 13. 14. 15. 16. 17. Description O-ring seal Internal filter / sintered flame trap Base casting Thermistor retaining screw Calibration / blow back pipe Cell connector mounting nut Auxiliary air restrictor Flame trap Link pipe Figure 5.12 Dual Sensor Configuration Layout 120 02700002D/0 SERVOTOUGH FluegasExact Service Manual Removal and refitting 1. Refer to Section 5.7. Switch off the electrical power to both the Sensor Head and Control Unit and remove the sensor compartment cover. WARNING Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Refer to Figure 5.12. Disconnect the reference air pipe (7) compression fittings at the bulkhead, restrictor (15) and aspirator (2). Remove the reference air pipe (7). 3. For the oxygen only and dual sensor configurations refer to Figure 5.8. Disconnect zirconia cell (4) from the cell connector (1) by undoing the 3/8" compression fitting nut (2). Release this cell nut by using an appropriate spanner on the nut (2) and on the adjacent flats (3) on the oxygen cell, so as not to twist the cell. If the cell connection is stuck, keep undoing the compression nut (2) and use the jacking shoulder to pull the stuck ferrules from the cell. Temporarily support the zirconia cell to prevent rotation so as not to unduly stress the cell wiring. 4. For the combustibles only and dual sensor configurations refer to Figure 5.9. Disconnect the 1/8" compression fitting (4) at the junction between the combustibles sensor (3) and the cell connector (6). Use two spanners on the 1/8" nut (4) and the hexagonal section on the cell connector (5). Avoid twisting the cell connector fitting.  Refer to Section 5.13 if a Flow Alarm module is fitted. 5. Refer to Figure 5.12. Undo the lower 3/8" compression fitting (14) at the junction between the cell connector and the sintered flame arrestor internal filter (10). Use two spanners to prevent the sintered flame arrestor (10) from twisting during initial breaking of the joint. If the ferrule is stuck, keep undoing the compression nut and use the jacking shoulder to pull the stuck ferrule from the flame arrestor. Temporarily support the cell connector to prevent rotation during this operation. 6. Replace using the reverse procedure. Ensure that the sintered flame arrestor (10) is fully tightened before refitting the cell connector.  If the sintered flame arrestor (10) is loosened during cell connector replacement, the copper seal between the sintered flame arrestor and chest assembly should be replaced. 02700002D/0 121 SERVOTOUGH FluegasExact Service Manual 5.15 Aspirator Removal and Replacement Refer to Figure 5.12. Removal and refitting 1. Refer to Section 5.7. Disconnect the electrical power from both the Sensor Head and Control Unit and remove the sensor compartment cover. WARNING Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Undo the compression fittings connecting the aspirator / reference air pipe (7) to its bulk head fitting, restrictor (15) (if fitted) and to the aspirator (2). Lift out the aspirator / reference air pipe. 3. Unscrew and remove the aspirator (2) from the chest assembly (4). Remove and discard the old annealed copper sealing washer. 4. Check that the vent hole, (underneath the aspirator), through the chest assembly is not blocked. Clean the assembly if necessary. 5. Replace using the reverse procedure. Ensure a new annealed copper sealing washer is fitted.  If a new aspirator is fitted, lightly smear some release compound (spare part number S2700990) on the threads entering the chest assembly. Failure to do this may make the aspirator difficult to remove in the future.  An annealed copper washer is used as a seal between the aspirator and the chest assembly. These may only be used once and must be replaced when the aspirator is refitted. CAUTION Use only the recommended release compound, ROCOL ASP dry film anti scuffing paste (spare part number S2700990), on any heated components. The use of ‘Silver Goop’ or other similar release agents may result in permanent damage to the combustibles sensor (if fitted). 122 02700002D/0 SERVOTOUGH FluegasExact Service Manual 5.16 Internal Filter / Sintered Flame Arrestor Removal and Replacement Refer to Figure 5.12. Removal and Refitting 1. Refer to Section 5.7. Disconnect the electrical power from both Sensor Head and Control Unit and remove the sensor compartment cover. WARNING Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Disconnect the 1/8" compression fitting at the flame trap (3). 3. Disconnect the reference air pipe (7) compression fittings at the bulkhead, restrictor (15) (if fitted) and the aspirator assembly (2) and remove the reference air pipe. 4. Disconnect the lower 3/8" compression fitting (14) at the junction between the cell connector and the sintered flame arrestor internal filter (10). If the ferrule is stuck, keep undoing the compression nut and use the jacking shoulder to pull the stuck ferrule from the flame arrestor. Temporarily support the cell connector to prevent rotation during this operation. 5. Pull back the sensor assembly and temporarily support in order not to over stress the sensor wiring.  The internal filter / sintered flame arrestor may be difficult to remove due to long durations of operation at 245C. It must be removed using a suitable long reach socket. 6. Unscrew the sintered flame arrestor internal filter (10) from the chest assembly (4). Discard the used annealed copper sealing washer. 7. Replace using the reverse procedure, using a new annealed copper washer.  If a new sintered flame arrestor internal filter is fitted, lightly smear some release compound (spare part number S2700990) on the threads entering the filter block. Failure to do this may make the flame arrestor / internal filter difficult to remove in the future.  An annealed copper washer is used as a seal between the flame arrestor and the filter block. These may only be used once and must be replaced when the flame arrestor is refitted. CAUTION Use only the recommended release compound, ROCOL ASP dry film anti scuffing paste (spare part number S2700990), on any heated components. The use of ‘Silver Goop’ or other similar release agents may result in permanent damage to the combustibles sensor (if fitted). 02700002D/0 123 SERVOTOUGH FluegasExact Service Manual 5.17 Thermostat Removal and Replacement Removal and Refitting 1. Refer to Section 5.7. Disconnect the electrical power from both Sensor Head and Control Unit and remove both the sensor compartment cover and terminal compartment cover. Remove the transparent insulating cover from the terminal enclosure. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages if the electrical supply is not disconnected first. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Refer to Figure 5.7. Disconnect the thermostat wires from terminal block TB8 (9) on the Terminals PCB. Withdraw the wires back into the sensors compartment. Take note of the wire routing within the Sensor Head and ensure that the new thermostat wires are routed in the same manner. 3. Refer to Figure 5.12. Remove the two M3 screws that retain the over temperature thermostat (5) to the chest assembly (4). Lift out the over temperature thermostat. 4. Replace using the reverse procedure. The new thermostat will be provided with a fibre glass sleeve insulating the cell wires. This is a safety feature and should not be omitted. Refer to Table 5.3 for cell wiring connection details. Ensure that the wires are routed away from the chest assembly, band heater, and combustibles sensor body (if fitted). 124 02700002D/0 SERVOTOUGH FluegasExact Service Manual 5.18 Thermistor Removal and Replacement The thermistor is located within a hole in the chest assembly and is used to monitor the temperature control of the band heater. Removal and Refitting 1. Refer to Section 5.7. Disconnect the electrical power from both Sensor Head and Control Unit and remove both the sensor compartment cover and the terminals compartment cover. WARNING Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 2. Refer to Figure 5.7. Disconnect the white wires from terminal block TB7 (3) on the Terminals PCB. Withdraw the wires back into the sensors compartment. Take note of the wire route within the Sensor Head and ensure that the new thermistor wires are routed in the same manner. 3. Refer to Figure 5.12. Remove the M4 screw (12) and washer then lift out the thermistor. The washer is designed to overlap a small area of the hole to trap the thermistor in place. 4. Replace using the reverse procedure. Ensure that the wires are routed away from the chest assembly, band heater, and combustibles sensor body (if fitted). Ensure that the leads to the block thermistor are not pinched by the washer retaining the thermistor within the chest assembly.  One of the thermistor wires is identified with a black band. However, when refitting the thermistor, polarity is not important. 5.19 Band Heater Removal and Replacement Removal and refitting 1. Refer to Section 5.7. Disconnect the electrical power from both Sensor Head and Control Unit and remove both the sensor compartment cover and terminal compartment cover. Remove the transparent insulating cover from the terminal enclosure. WARNING Removal of the plastic insulating cover may expose the user to potentially lethal voltages if the electrical supply is not disconnected first. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. Removal of the sensor compartment cover may expose heated parts. Ensure that the internal temperature has dropped to a safe level before working on them. 02700002D/0 125 SERVOTOUGH FluegasExact Service Manual 2. Refer to Figure 5.7. Disconnect the band heater wires from terminal block TB8 on the Terminals PCB. Withdraw the heater wires into the sensor compartment. Take note of the wire route within the Sensor Head and ensure that the new heater wires are routed in the same manner. 3. Refer to Figure 5.12. Undo the 2 off 1/8" compression fittings and remove the calibration / blow back pipe (13). 4. Refer to Section 5.11 and remove the zirconia cell (if fitted). 5. Refer to Section 5.12 and remove the combustibles cell (if fitted). 6. Refer to Section 5.14 and remove the cell connector. 7. Refer to Section 5.17 and remove the over temperature thermostat. 8. Refer to section 5.18 and remove the thermistor.  To remove the band heater it may be necessary to remove the Sensor Head enclosure breather fitting (refer to Figure 1.2 (5)). This will allow easier access to the band heater tensioning screw. 9. Note the orientation of the band heater tensioning screw. Loosen the band heater tensioning screw and slide the band heater off the filter block. 10. Replace using the reverse procedure.  When refitting the band heater over the filter block, orientate the tensioning screw at the 45 position as shown in Figure 5.12. For optimum band heater reliability torque the tensioning screw to 3-5Nm.  The top of the band heater should be between 0 and 5mm below the top face of the chest assembly. 126 02700002D/0 SERVOTOUGH FluegasExact Service Manual APPENDIX A DETAILED ANALYSER PERFORMANCE TESTING A.1 Notes and Conditions The performance tests detailed in this section are based on the factory test specification for the 2700D analyser. WARNING The electrical power used in this equipment is at a voltage high enough to endanger life. It is essential that only suitably trained and competent personnel are allowed access to hazardous live parts. It may be necessary to fault find with the electrical power connected. Where this is necessary extreme caution should be exercised. Removal of the plastic insulating covers in the Control Unit may expose the user to potentially lethal voltages resulting from external electrical connections to the relay contacts even when the electrical power is disconnected from the Control Unit itself. Carbon monoxide is a toxic gas. When sampling gases containing carbon monoxide ensure that adequate precautions are taken to ensure that any vented gases are safely extracted. The Sensor Head is heated and may be attached to a hot flue. The external surfaces will be uncomfortably hot even after power down for several hours. Exercise care when handling the Sensor Head even when un-powered on a hot flue. A.2 Gas Samples Required The gas samples required to adjust and test the analyser depend on the configuration of the analyser under test. Refer to table A.1. The gas samples are introduced via the calibration gas inlet port. The inlet pressure and flow should be controlled externally to give a gas flow rate of 600 50 ml/min. 02700002D/0 127 SERVOTOUGH FluegasExact Service Manual Table A.1 Utility Gas Sample Requirements Service Aspirator supply Gas Regulated clean dry instrument air * Press. (psig) 0-10 Flow (L/min) 0-2 O2 COe Dual    * Oxygen only Sensor Heads can be configured for nitrogen aspiration as standard builds. Dual build Sensor Heads can be configured for nitrogen aspiration as special builds, (consult Servomex for details). Pressure and flow rates remain as per instrument air. Calibration gas O2 ‘HIGH CAL’ COe ‘LOW CAL’ Regulated clean dry air 0-10 0.6 0.020    Calibration gas O2 ‘LOW CAL’ 0.3% O2 balance N2 ** 0-10 0.6 0.020  X    **Calibration gas composition can be between 0.25% and 2.5% O2 in N2 Calibration gas COe ‘HIGH CAL’ 1,000 ppm(v) CO balance air *** 0-10 0.6 0.020 X *** Calibration gas composition can be between 500ppm(v) and 1,000ppm(v) in air depending on the measuring range selected. A.3 Visual Inspection Check that all wiring is neatly dressed and securely terminated. Check both Sensor Head and Control Unit for loose or damaged O-ring enclosure seals. In the Sensor Head terminal box:  Check voltage selection link is set to the appropriate supply voltage and the correct voltage label is fitted.  Check fuse F1 fitted is 6.3A (voltage independent). In the Control Unit: 128  Check that the transformer primary flying lead is connected to the correct socket. PL7 for 110V (nominal) or PL6 for 240V (nominal).  Check that the fuse F1 fitted is 3.15 A for 110V (nominal) or 1.6 A for 240V (nominal). 02700002D/0 SERVOTOUGH FluegasExact Service Manual A.4 Sensor Head Leak Test Seal the calibration gas inlet, the aspirator air inlet, sample vent port and the internal reference air pipe (not applicable for COe only or N2 aspirated versions). Connect a manometer to the sample inlet port and pressurise the internal pipework to between 500 and 600mmWG. Seal the manometer and ensure that the level does not fall by more than 5mm in 2 minutes. CAUTION Extreme care should be exercised when using leak detection fluids such as ‘SNOOP’ with the Sensor Head assembly. Avoid wetting any electrical components. Special care should be exercised to avoid wetting the band heaters, thermistors, thermostats, Tfx ceramics and glass fibre insulated wires. A.5 Interconnection Tests Connect the Control Unit to the Sensor Head using test cable looms. Ensure that all interconnections are correctly wired and terminated in accordance with interconnection drawings in section 2 of this manual. A.6 Initial Power-Up Connect the Sensor Head to nominal required power supply. If necessary adjust RV2 on the control PCB (viewing angle adjustment for the LCD display) to give the best display contrast when viewed perpendicularly from the front. From a cold start, verify that the aspirator solenoid valve operates after a time interval of not less than 15 minutes and not more than 60 minutes after power on. The precise time interval will depend on the Sensor Head configuration. A.7 Analogue Output Span Setup Perform the following tests. 02700002D/0  If a zirconia sensor is fitted then select the ‘set analogue outputs’ option in the service menu and select 20mA for the oxygen analogue output. If necessary adjust RV4 on the control PCB until the analogue output reads 20.00 0.01mA.  If a combustibles sensor is fitted then select the ‘set analogue outputs’ option in the service menu and select 20mA for the combustibles output. If necessary adjust RV3 on the control PCB until the analogue output reads 20.00 0.01mA. 129 SERVOTOUGH FluegasExact Service Manual A.8 Relay Operation Test Perform the following tests.  Select the ‘set relay outputs’ option in the service menu and select ‘disable’. Verify that terminals 2 and 3, 5 and 6, 8 and 9, 11 and 12 on terminal block TB4 are short circuit. Verify that terminals 1 and 3, 4 and 6, 7 and 9, 10 and 12 are open circuit.  Select the ‘set relay outputs’ option in the service menu and select ‘enable’. Verify that terminals 2 and 3, 5 and 6, 8 and 9, 11 and 12 on terminal block TB4 are open circuit. Verify that terminals 1 and 3, 4 and 6, 7 and 9, 10 and 12 are short circuit. A.9 Sensor Head Temperature Control Wait until both the Sensor Head and Control Unit have been switched on for a minimum of 90 minutes. Perform the following tests:  Verify that the green LED (D10) on the terminal PCB is flashing at equal intervals, indicating that the chest assembly temperature is under control.  Check the final stabilised Sensor Head temperature by measuring the voltage between TB3 terminals 1 and 2 (ground) in the Sensor Head terminal box. This voltage should be 6.6 0.4V.  Select the VIEW option from the main menu. Check that the zirconia sensor temperature is 700 10C.  Check that the combustibles sensor temperature is 300 20C. A.10 Sensor Head Sample Flow and Vacuum Test With the Sensor Head power on and at stable temperature perform the following tests: 130  Blank off the calibration gas inlet. Attach a manometer to the sample inlet. Increase the compressed air pressure at the sample inlet to 4psig. The vacuum at the sample inlet should be greater than 210mmWG (O2 only) or 140mmWG (COe only and dual).  Attach a 500ml/min flow meter to the sample inlet. With the aspirator supply pressure set to 4psig the sample flow rate should be in the range 200 to 450ml/min.  Adjust the aspirator air supply pressure until the flow meter indicates a flow of 300ml/min (O2 only) or 240ml/min (COe only or dual sensor). Check that the aspirator air supply pressure is in the range 3 to 7psig. 02700002D/0 SERVOTOUGH FluegasExact Service Manual A.11 Combustibles Sensor Zero Adjustment If a combustibles sensor is fitted then perform the following adjustments:  Ensure that the unit has been sampling ambient air (COe zero calibration gas) for at least 5 minutes before making the following adjustments.  Check that switch SW2 on the control PCB is set to the zero position.  Select the VIEW option in the main menu and observe the combustibles sensor output voltage. If the voltage measured is negative then set switch SW3 on the control PCB to the upper position. If the voltage is positive then set switch SW3 to the lower position.  Adjust switch SW2 clockwise one step at a time until the voltage is within the range -60 to +60mV. Note that there may be a delay of up to 30 seconds between a switch change and a voltage change seen on the display. A.12 Sensor Calibration WARNING Connect analyser probe inlet and vent to an extraction system for the remainder of this test. With the Sensor Head power on and at stable temperature perform the following adjustments. 02700002D/0  Ensure the aspirator is running with a pressure between 3 and 5psig.  With an air sample applied to the calibration gas inlet at 600 50ml/min flow rate perform a HIGH point calibration of the zirconia sensor (if fitted) and a LOW point calibration of the combustibles sensor (if fitted).  With a nominal 0.3% O2 in N2 sample applied to the calibration gas inlet at 600 50ml/min flow rate perform a LOW point calibration of the zirconia sensor (if fitted). Verify that the analyser display reads within 0.02% O2 of the given gas concentration.  If a combustibles sensor is fitted perform the following tests. With a nominal 500ppm CO in air sample applied to the calibration gas inlet at 600 20ml/min flow rate perform a HIGH point calibration of the combustibles sensor (if fitted). Verify that the analyser display reads within 10ppm CO of the certified gas concentration.  The analyser can be removed from its extraction system for the final test.  Disconnect the calibration gases. With the analyser sampling instrument air through the sample inlet port verify that the analyser display reads 20.95 0.2% O2 and/or 0 10ppm combustibles. 131 SERVOTOUGH FluegasExact Service Manual APPENDIX B ANALYSER SOFTWARE ‘SUPER-CALIBRATION’ MODE B.1 Introduction This section details the super calibration (supercal) functions of the Servomex 2700D analyser. This includes configuration of the analyser, i.e. installing transducers, as well as the functions available for service and calibration use. B.2 Menu Structure To enter supercal mode, use the procedure described in Section B.3. CONFIGURE COe COe RANGE RESTORE DEFAULTS PRECISION B.3 Accessing Super-Calibration Access to the supercal function is via a special key sequence. Starting from the Measure screen, the sequence is as follows:  Press , select the CONFIGURE option.  Press .  Key ‘1812’ as the password in the space provided and then press . This causes the top level supercal menu to be displayed.  If 1812 is entered as a password and the key is pressed instead of the analyser will enter the normal configuration menu. 132 02700002D/0 SERVOTOUGH FluegasExact Service Manual B.4 Configuring the Combustibles Sensor From the top level supercal menu: CONFIGURE COe RESTORE DEFAULTS Select CONFIGURE COe and press the screen will show: COe RANGE PRECISION Select COe RANGE and press  This is the COe Range setting and must not be confused with the working range of the combustibles sensor. If the combustibles measurement exceeds the value set via this menu, then the DISP OVER RANGE fault message will appear. Recommended COe RANGE 01750702 From October 2008 For all Units 30,000ppm 150mV The software default display range is always 10,000ppm. Manually setting the 01750702 sensor RANGE can be done as follows: Set the display to "0 - 030000ppm" and press the screen will show: mV/30000ppm 150mV This sets the level at which the COe mV OUTPUT LOW fault message appears. Key 150mV and press The analyser will then return to the top level super calibration menu CONFIGURE COe/RESTORE DEFAULTS. 02700002D/0 133 SERVOTOUGH FluegasExact Service Manual B.5 Setting the Display Precision of the Combustibles Measurement The combustibles measurement defaults to a display resolution of 1ppm. If this level of resolution is not required, or process conditions are noisy, the display resolution may be rounded to the nearest 10ppm or 100ppm. To alter the default setting select CONFIGURE COe. The screen will then show: COe RANGE PRECISION Select PRECISION. The display will then show: PRECISION 1/10/100 Move the cursor to 10 for 10ppm resolution, (i.e. 1 digit blanked), or 100 for 100ppm resolution. Press . The analyser will then return to the CONFIGURE COe/RESTORE DEFAULTS menu. 134 02700002D/0 SERVOTOUGH FluegasExact Service Manual B.6 Returning to Factory Default Settings The analyser may be returned to its factory default settings through the supercal menu.  This will restore all default settings including relay and analogue output assignments, calibration targets and tolerances and alarm settings in addition to the combustibles sensor settings. From the CONFIGURE COe/RESTORE DEFAULTS menu, select RESTORE DEFAULTS. The display will then show: RESTORE DEFAULTS ACCEPT Y/N Select Y and press to restore factory default settings. If this is done the display will then show: RESTORING DATA PLEASE WAIT The display will then return automatically to the CONFIGURE COe/RESTORE DEFAULTS menu. B.7 Exiting Super-Calibration Press at any time to leave the supercal menu. 02700002D/0 135