Det-Tronics Instructions Multispectrum IR Flame Detector with Pulse Output X3301
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
Multispectrum IR Flame Detector
with Pulse Output
X3301
1.1
Rev: 10/15
95-8736
Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . .
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
oi (Optical Integrity) . . . . . . . . . . . . . . . . .
Communication . . . . . . . . . . . . . . . . . . . . .
Data Logging . . . . . . . . . . . . . . . . . . . . . . .
Integral Wiring Compartment . . . . . . . . . . .
Detector Sensitivity Levels . . . . . . . . . . . .
1
2
2
2
3
3
3
3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 17
REPLACEMENT PARTS . . . . . . . . . . . . . . . 19
Replacement Parts List . . . . . . . . . . . . . . 19
DEVICE REPAIR AND RETURN . . . . . . . . . 19
GENERAL APPLICATION INFORMATION . . 4
Response Characteristics . . . . . . . . . . . . . 4
Important Application Considerations . . . . 4
ORDERING INFORMATION . . . . . . . . . . . . . 19
Accessories . . . . . . . . . . . . . . . . . . . . . . . 19
X3301 Model Matrix . . . . . . . . . . . . . . . . . 20
IMPORTANT SAFETY NOTES . . . . . . . . . . . . 4
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .
Detector Positioning . . . . . . . . . . . . . . . . . .
Detector Orientation . . . . . . . . . . . . . . . . . .
Protection Against Moisture Damage . . . .
Wiring Procedure . . . . . . . . . . . . . . . . . . . .
5
5
5
6
6
HIGH RESOLUTION FIELD OF VIEW
DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . 21
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT . . . . . . . . . . . . . 25
APPENDIX B – CSA APPROVAL . . . . . . . . . 33
STARTUP PROCEDURE . . . . . . . . . . . . . . . 14
Manual oi Test (Output to Controller) . . . 14
Count Test Mode (Output to Controller) . 14
Fire Alarm Test (Pulse Output to Fire Alarm
Panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
TROUBLESHOOTING . . . . . . . . . . . . . . . . . 15
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . .
Cleaning Procedure . . . . . . . . . . . . . . . . .
oi Plate Removal and Replacement . . . .
Periodic Checkout Procedure . . . . . . . . .
Clock Battery . . . . . . . . . . . . . . . . . . . . . .
16
16
16
17
17
APPENDIX C – ATEX APPROVAL . . . . . . . . 34
APPENDIX D – IECEx APPROVAL . . . . . . . 36
APPENDIX E – EN54 APPROVALS . . . . . . . 37
APPENDIX F – ADDITIONAL APPROVALS . . . 38
INSTRUCTIONS
Multispectrum IR Flame Detector
with Pulse Output
X3301
WARNING
Be sure to read and understand the entire
instruction manual before installing or
operating the flame detection system. Any
deviation from the recommendations in this
manual may impair system performance
and compromise safety.
ATTENTION
The X3301 includes the Automatic o i ®
(Optical Integrity) feature — a calibrated
performance test that is automatically
performed once per minute to verify
complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
The X3301 contains three IR sensors and
provides unsurpassed detection of flames from
light to heavy hydrocarbon fuels combined with
the highest degree of false alarm rejection.
The detector has Division and Zone explosionproof ratings and is suitable for use in indoor
and outdoor applications. The X3301 housing
is available in copper-free aluminum or stainless
steel, with NEMA/Type 4X and IP66/IP67 rating.
DESCRIPTION
The X3301 with pulse/relay output is a
multispectrum infrared (IR) flame detector that
is designed for use in controller based systems.
In addition to use in new systems, it can serve
as a direct field replacement for Det-Tronics
controller based flame detectors that generate
a pulse output (not compatible with R7484 and
R7409B/C).
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire
alarm or fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
When used as a field replacement, all operating
features of the current controller are retained in
addition to gaining the advanced features of the
X3301 Flame Detector. In typical applications,
the four wire X3301 can utilize all existing system
wiring.
1.1
©Detector Electronics Corporation 2015
1
Rev: 10/15
95-8736
indicated by the Fault output and is evident by the
yellow color of the LED on the face of the detector.
The oi fault condition is self-clearing if the optical
contamination is temporary. If the contamination
is not automatically cleared and the oi fault
remains, the detector may require cleaning or
service. See the "Troubleshooting" section for
further information.
OUTPUTS
Relays
The detector is furnished with fire and fault relays.
The relays are rated 5 amperes at 30 Vdc.
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Magnetic oi / Manual oi
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
CAUTION
These tests require disabling of all
extinguishing devices to avoid release
resulting from a successful test.
An alarm condition will normally over-ride a fault
condition, unless the nature of the fault condition
impairs the ability of the detector to generate or
maintain an alarm output, i.e. loss of operating
power.
The detector incorporates both Magnetic
oi (Mag oi) and Manual oi (Man oi) test
capabilities. These tests provide pulses (80 to
100 CPS) to the controller (R7404 or R7494)
when the detector is not in fault. If the test is
successful, the controller indicates a fire and
the appropriate zone output is active.
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire
alarm or fault conditions. Table 2 indicates the
condition of the LED for each status.
NOTE
If the detector is in a fault condition, a
successful Mag o i or Man o i test cannot
be performed.
Table 1—Detector Status Indicator
Detector Status
Power On/Normal Operation
(no fault or fire alarm)
Fault
Fire (Alarm)
Low Sensitivity
T-Low Sensitivity
Medium Sensitivity
Very High Sensitivity
LED Indicator
The Mag oi test is initiated by placing a
magnet at the location marked “MAG OI” on
the outside of the detector (see Figure 2). This
action causes the detector to immediately send
pulses to the controller. Controller response is
as follows:
Green
Yellow
Red
One Yellow Flash
During Power-up
Three Yellow Flashes
During Power-up
Two Yellow Flashes
During Power-up
Four Yellow Flashes
During Power-up
• The Zone LED blinks.
• The digital display indicates which Zone is in
alarm.
• The status indicator shows “6” (fire).
NOTE: See "Detector Sensitivity Levels" for additional information.
IMPORTANT
Mag o i can be performed with the
controller’s (R7404/R7494) keylock switch
in either the NORMAL or TEST position. In
NORMAL, the controller goes into alarm
and activates its outputs. If no controller
alarm output is desired, place the keylock
switch in the TEST position before touching
the magnet to the outside of the detector.
Man o i operates only with the keylock
switch in the TEST position.
During the entire test, the detector gives no
indication of alarm.
oi (OPTICAL INTEGRITY)
Automatic oi
The X3301 includes the Automatic oi feature — a
calibrated performance test that is automatically
performed once per minute to verify complete
detector operation capabilities. No testing with
an external test lamp is required. The detector
automatically performs the same test that a
maintenance person with a test lamp would
perform — once every minute, 60 times per hour.
However, a successful Automatic oi test does not
produce an alarm condition.
To reset the controller status and alarms, place
the keylock switch in RESET. Return the keylock
switch to NORMAL when testing is complete.
The detector signals a fault condition when less
than half of the detection range remains. This is
1.1
2
95-8736
The Man oi test is nearly identical to the Mag
oi test, except for the manner in which the test
is initiated:
DETECTOR SENSITIVITY LEVELS
There are four factory configured sensitivity levels
available for the X3301 Flame Detector:
• Place the keylock switch on the controller
(R7404/R7494) in the Test position.
• Press the Select button to select the appropriate
detector for test.
• Press the Test/Accept button to initiate the
test.
Very High, Medium, Low, and T-Low.
The following criteria should be considered
when choosing a sensitivity level for the intended
application:
• Detector placement
• Speed of response based on fuel type and
fire size (see Appendix A for examples of
response times)
• Distance between the hazard and the flame
detector
Controller and detector responses are identical
to the Mag oi test described above.
To reset the controller status and alarms, place
the keylock switch in RESET. Return the keylock
switch to NORMAL when testing is complete.
Additional information on X3301 Flame Detector
performance results and sensitivities can be
found in Appendix A, the FM Approval and
Performance Report.
NOTE
Refer to Appendix A for FM verification
of the o i function.
COMMUNICATION
Consult the factory with any questions on how
to choose the optimum sensitivity level for the
intended application.
The X3301 is furnished with an RS-485 interface
for communicating status and other information
with external devices. The RS-485 supports
MODBUS protocol, with the detector configured
as a slave device.
DATA LOGGING
Data logging capability is also provided. Status
conditions such as normal, power down,
general and oi faults, fire alarm, time and
temperature are recorded. Each event is time
and date stamped, along with the temperature
and input voltage. Event data is stored in
non-volatile memory when the event becomes
active, and again when the status changes.
Data is accessible using Det-Tronics' Inspector
Connector accessory or RS-485.
INTEGRAL WIRING COMPARTMENT
All external wiring to the device is connected
within the integral junction box. The detector is
furnished with four conduit entries, with either
3/4 inch NPT or M25 threads.
1.1
3
95-8736
GENERAL APPLICATION
INFORMATION
Non-Carbon Fires
The X3301 is a multiple spectrum IR device
with detection limited to carbonaceous fuels.
It should not be used to detect fires from fuels
that do not contain carbon, such as hydrogen,
sulfur, and burning metals.
RESPONSE CHARACTERISTICS
Response is dependent on the detector's
sensitivity setting, distance, type of fuel,
temperature of the fuel, and time required for
the fire to come to equilibrium. As with all fire
tests, results must be interpreted according to
an individual application.
IMPORTANT SAFETY NOTES
WARNING
Do not open the detector assembly in a
hazardous area when power is applied.
The detector contains limited serviceable
components and should never be opened.
Doing so could disturb critical optical
alignment and calibration parameters,
possibly causing serious damage.
See Appendix A for third-party approved fire test
results. Additional fire test results are available
from Det-Tronics.
IMPORTANT APPLICATION CONSIDERATIONS
In applying any type of sensing device as
a fire detector, it is important to know of any
conditions that can prevent the device from
responding to fire, and also to know what other
sources besides fire can cause the device to
respond.
CAUTION
The wiring procedures in this manual are
intended to ensure proper functioning of the
device under normal conditions. However,
because of the many variations in wiring
codes and regulations, total compliance to
these ordinances cannot be guaranteed.
Be certain that all wiring complies with
the NEC as well as all local ordinances.
If in doubt, consult the authority having
jurisdiction before wiring the system.
Installation must be done by a properly
trained person.
Welding
It is recommended that the system be
bypassed during welding operations in
situations where the possibility of a false
alarm cannot be tolerated. Gas welding
mandates system bypass, since the gas torch
is an actual fire. Arc welding rods can contain
organic binder materials in the flux that burn
during the welding operation and are detectable
by the X3301. Welding rods with clay binders
do not burn and will not be detected by the
X3301. However, system bypass is always
recommended, since the material being welded
may be contaminated with organic substances
(paint, oil, etc.) that will burn and possibly cause
the X3301 to alarm.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled
prior to per forming system tests or
maintenance.
Due to the possibility of an alarm condition,
arc welding should not be performed within
40 feet (12.2 m) of the detector configured
to very high sensitivity, within 10 feet (3.0 m)
at medium sensitivity, within 5 feet (1.5 m) at
T-Low sensitivity, or at Low sensitivity.
CAUTION
The multispectrum IR flame detectors are
to be installed in places where the risk of
mechanical damage is low.
Artificial Lighting
The X3301 should not be located within 3 feet
(0.9 m) of artificial lights. Excess heating of the
detector could occur due to heat radiating from
the lights.
ATTENTION
Remove the protective cap from the front of
the detector before activating the system.
ATTENTION
O b s e rv e p re ca u t i o n s fo r h a n d l i n g
electrostatic sensitive devices.
EMI/RFI Interference
The X3301 is resistant to interference by EMI
and RFI, and is EMC Directive compliant. It will
not respond to a 5 watt walkie-talkie at distances
greater than 1 foot (0.3 m). Do not operate a
walkie-talkie within 1 foot (0.3 m) of the X3301.
1.1
4
95-8736
INSTALLATION
• Dense fog, rain or ice can absorb IR radiation
and reduce the sensitivity of the detector. To
ensure optimum performance, be certain that the
internal optical heater is enabled on detectors
that are used in applications where snow, ice,
and condensation are likely to occur.
• Although IR detectors are less affected by
smoke than other detectors, the X3301 should
not be placed where rising combustion products
can obscure its vision. If smoke is expected
before fire, smoke or other alternative detectors
should be used in conjunction with the X3301.
For indoor applications, if dense smoke is
expected to accumulate at the onset of a fire,
install the detector on a side wall at least a few
feet (approximately 1 meter) down from the
ceiling.
• If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
• For ATEX/IECEx installations, the X3301 Flame
Detector housing must be electrically connected
to earth ground.
NOTE
The recommended lubricant for threads
and O-rings is a silicone free grease (p/n
005003-001) available from Det-Tronics.
Under no circumstances should a lubricant
containing silicone be used.
DETECTOR POSITIONING
Detectors should be positioned to provide
the best unobstructed view of the area to be
protected. The following factors should also be
taken into consideration:
• Identify all high risk fire ignition sources.
• Be sure that enough detectors are used to
adequately cover the hazardous area.
• Be sure that the unit is easily accessible for
cleaning and other periodic servicing.
• Verify that all detectors in the system are
properly located and positioned so that any
fire hazards are within both the Field of View
(FOV) and detection range of the detector.
The Q1201C Laser Aimer is recommended
for establishing the detector's FOV. Refer to
the "High Resolution Field of View Diagrams"
section for specific information regarding
detector range and FOV.
• The detector should be aimed downward at
least 10 to 20 degrees to allow lens openings
to drain. See Figure 1. The detector should
be positioned so that its FOV does not
cover areas outside the hazardous area.
This will minimize the possibility of false alarms
caused by activities outside the area requiring
protection.
• The detector must be mounted on a rigid
surface in a low vibration area.
DETECTOR ORIENTATION
Refer to Figure 2 and ensure that the oi plate
will be oriented as shown when the X3301 is
installed and sighted. This will ensure proper
operation of the oi system and will also minimize
the accumulation of moisture and contaminants
between the oi plate and the viewing windows.
IMPORTANT
If removed, the o i plate must be securely
tightened to ensure proper operation of
the o i system (40 oz./inches [28.2 N . cm]
recommended).
oi PLATE
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
VIEWING WINDOW (3)
INCORRECT
oi MAGNET
F2068
DETECTOR
STATUS INDICATOR
Figure 2—Front View of the X3301
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
D1974
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon
1.1
5
95-8736
PROTECTION AGAINST MOISTURE DAMAGE
IMPORTANT
A minimum input voltage of 18 Vdc must be
present at the X3301.
It is important to take proper precautions during
installation to ensure that moisture will not come
in contact with the electrical connections or
components of the system. The integrity of
the system regarding moisture protection must
be maintained for proper operation and is the
responsibility of the installer.
The use of shielded cable is required to protect
against interference caused by EMI and RFI.
When using cables with shields, terminate the
shields as shown in Figures 6 through 10. Consult
the factory if not using shielded cable.
If conduit is used, we recommend installing drains,
according to local codes, at water collection
points to automatically drain accumulated
moisture. It is also recommended to install at least
one breather, according to local codes, at upper
locations to provide ventilation and allow water
vapor to escape.
The “B” (pulse output) and “D” (oi driver) leads
from each detector should be shielded from the
“B” and “D” leads of all other detectors in order
to prevent false alarms resulting from crosstalk
between zones. It is recommended that the
“A” and “C” leads also be shielded to provide
maximum immunity to EMI/RFI. (See Figures 6
to 10.)
Conduit raceways should be inclined so that
water will flow to low points for drainage and
will not collect inside enclosures or on conduit
seals. If this is not possible, install conduit drains
above the seals to prevent the collection of water
or install a drain loop below the detector with a
conduit drain at the lowest point of the loop.
In applications where the wiring cable is installed
in conduit, the conduit must not be used for wiring
to other electrical equipment.
If disconnection of power is required, separate
disconnect capability must be provided.
Conduit seals are not required for compliance
with explosion-proof installation requirements, but
are highly recommended to prevent water ingress
in outdoor applications. Units with M25 threads
must use an IP66/IP67 washer to prevent water
ingress.
WARNING
All entries must contain appropriately rated
plugs or fittings. It is required that each
plug or fitting be wrench-tightened to an
appropriate installation torque and meet the
minimum thread engagement requirements
per the applicable local standards, codes,
and practices in order to retain the defined
ratings. PTFE sealant or equivalent should
be used on NPT threads.
WIRING PROCEDURE
Wire Size and Type
The system should be wired according to
local codes. The wire size selected should be
based on the number of detectors connected,
the supply voltage, and the cable length.
Typically 16 AWG or 2.5 mm2 shielded cable is
recommended. Wires should be stripped 3/8
inch (9 mm). In some cases where the X3301
is replacing existing pulse output detectors,
the wiring and power supplies may not be
adequate. Consult the factory for assistance.
4X ø0.42
(1.1)
3.0
(7.6)
IMPORTANT
Devices certified for hazardous locations
shall be installed in accordance with EN/
IEC 60079-14 and NEC 505.
CAUTION
Installation of the detector and wiring should
be performed only by qualified personnel.
4.0
(10.2)
13.1
(33.3)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
3.0
(7.6)
4.0
(10.2)
10.6
(27.0)
F2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
1.1
6
95-8736
Detector Installation
Install the mounting arm assembly on a rigid
surface. The ideal installation surface should be
free of vibration and suitable to receive 3/8 inch or
M10 bolts with a length of at least 1 inch (25 mm).
The surface must also have sufficient capacity
to hold the detector and mounting arm weights
(see "Specifications" section). Refer to the Q9033
Mounting Arm and Collar Attachment manual (958686) for additional installation information. See
Figure 3 for dimensions.
9
19
8
18
PULSE OUT
29
SPARE
28
SPARE
7
COM FIRE
17
COM FIRE
27
6
NO FIRE
16
NO FIRE
26
5
NC FIRE
15
NC FIRE
25
4
COM FAULT
14
COM FAULT
24
RS485 A
3
NO FAULT
13
NO FAULT
23
RS485 B
2
+Vin
12
+Vin
22
MAN Oi
1
–Vin
11
–Vin
21
–Vin
Detector Wiring
C2070
Figure 5—X3301 Pulse Wiring Terminal Identification
IMPORTANT
If installing an X3301 in place of an existing
detector, be sure to move the “A” Lead
(detector power) at the controller from the
+290 Vdc source to the +24 Vdc source.
Do not apply 290 Vdc to the X3301.
Leave the shield open at the detector end
and permanently isolate it from accidental
contact with the case and/or other
conductors. At the controller/fire panel
end, connect the shield and power minus
(–) to chassis (earth) ground either directly
or through a 0.47 µF 400 Volt non-polarized
capacitor (not supplied). (Refer to Figures 6
through 10.)
Figures 11 and 12 provide examples of
typical installations with a X3301 wired to a
fire alarm panel.
Figure 13 shows an EOL resistor installed
within the integral wiring compartment of
the detector (refer to “EOL Resistors” for
details).
1. Make field connections following local
ordinances and guidelines in this manual.
Figure 4 shows the wiring terminal strip
located inside the detector’s integral
junction box.
Figure 5 shows the wiring terminal
identification for the X3301 detector with
pulse output.
2. Check all field wiring to be sure that the
proper connections have been made.
IMPORTANT
Do not test any wiring connected to the
detector with a meg-ohmmeter. Disconnect
wiring at the detector before checking
system wiring for continuity.
3.
Make the final sighting adjustments and
use a 14 mm hex wrench to ensure that the
mounting arm assembly is tight.
Figure 4—X3301 Terminal Block
1.1
7
95-8736
NOTE: DO NOT CONNECT THE X3301 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X3301
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
DETECTOR 5
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-9
J1-17
DETECTOR 6
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-10
J1-18
DETECTOR 7
X3301
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
–
2
+
–
3
(A) +290 VDC
4
J2
R7404 CONTROLLER
} 10 TO 38 VDC
ZONE OUTPUT 1
33
ZONE OUTPUT 2
34
ZONE OUTPUT 3
35
B - INPUT 1
ZONE OUTPUT 4
36
5
B - INPUT 2
ZONE OUTPUT 5
37
6
B - INPUT 3
ZONE OUTPUT 6
38
7
B - INPUT 4
ZONE OUTPUT 7
39
8
B - INPUT 5
ZONE OUTPUT 8
40
9
B - INPUT 6
FIRE LOGIC “A”
41
10
B - INPUT 7
FIRE LOGIC “B”
42
11
B - INPUT 8
ALARM OUTPUT
43
12
D1-1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D1-2 oi DRIVER
OUTPUTS INHIBITED
45
14
D1-3 oi DRIVER
FAULT OUTPUT
46
15
D1-4 oi DRIVER
EXTERNAL ACCEPT
47
16
D1-5 oi DRIVER
STATUS & DET. OUTPUT S1
48
17
D1-6 oi DRIVER
STATUS & DET. OUTPUT S2
49
18
D1-7 oi DRIVER
STATUS & DET. OUTPUT S3
50
19
D1-8 oi DRIVER
STATUS & DET. OUTPUT S4
51
20
D2-1 oi DRIVER
STATUS & DET. OUTPUT S5
52
21
D2-2 oi DRIVER
STATUS & DET. OUTPUT S6
53
22
D2-3 oi DRIVER
STATUS & DET. OUTPUT S7
54
23
D2-4 oi DRIVER
STATUS & DET. OUTPUT S8
55
24
D2-5 oi DRIVER
DATA BUS 0
56
25
D2-6 oi DRIVER
DATA BUS 1
57
26
D2-7 oi DRIVER
DATA BUS 2
58
27
D2-8 oi DRIVER
DATA BUS 3
59
28
DMA OUT AVAILABLE
DATA BUS 4
60
29
DMA OUT
DATA BUS 5
61
30
DMA IN
DATA BUS 6
62
31
DATA STROBE
DATA BUS 7
32
DMA IN AVAILABLE
CHASSIS (EARTH) GND
63
64
B2071
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X3301
WITH PULSE OUTPUT.
TERMINAL NO.
1/11
FUNCTION
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
62
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
64
63
0.47 µF / 400 VDC
NON-POLARIZED
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 6—A Typical System, X3301 Detectors Wired to R7404 Controller
1.1
8
95-8736
NOTE: DO NOT CONNECT THE X3301 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X3301
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+290 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
17
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
D7 oi DRIVER
STATUS & DET. OUTPUT S3
50
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
NOT USED
DATA BUS 5
61
DATA STROBE IN
NOT USED
NOT USED
DATA BUS 6
62
DATA BUS 7
63
18
#2
#1
#19
#22
#2
#1
#19
#22
21
22
23
24
25
J1-9
J1-17
26
27
28
#2
#1
#19
#22
#2
#1
#19
#22
29
30
J1-10
J1-18
DETECTOR 7
X3301
1
20
DETECTOR 6
X3301
J1
+
19
DETECTOR 5
X3301
24
VDC
31
32
J2
R7404 STAR LOGIC CONTROLLER
D8 oi DRIVER
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
EARTH GROUND
64
B2072
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X3301
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
62
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
63
0.47 µF / 400 VDC
NON-POLARIZED
64
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 7—A Typical System, X3301 Detectors Wired to R7404 Star Logic Controller
1.1
9
95-8736
X3301
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X3301
#2
#1
#19
#22
#2
#1
#19
#22
X3301
#2
#1
#19
#22
J1-8
J1-16
J1-9
J1-17
DETECTOR 6
X3301
1
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+24 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
17
#2
#1
#19
#22
#2
#1
#19
#22
J1-10
J1-18
J2
R7494 CONTROLLER
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
18
D7 oi DRIVER
STATUS & DET. OUTPUT S3
50
19
D8 oi DRIVER
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
61
DATA BUS OUT
21
DATA BUS OUT
22
DATA BUS OUT
23
DATA BUS OUT
24
DATA BUS OUT
25
DATA BUS OUT
26
DATA BUS OUT
27
DATA BUS OUT
28
DETECTOR 7
X3301
J1
+
20
DETECTOR 5
#2
#1
#19
#22
24
VDC
NOT USED
29
NOT USED
DATA BUS 5
30
DATA STROBE IN
NOT USED
NOT USED
DATA BUS 6
62
DATA BUS 7
63
31
32
EARTH GROUND
64
B2073
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X3301
WITH PULSE OUTPUT.
TERMINAL NO.
1/11
FUNCTION
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
62
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
64
63
0.47 µF / 400 VDC
NON-POLARIZED
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 8—A Typical System, X3301 Detectors Wired to R7494 Controller
1.1
24
VDC
X3301
#2
#1
#19
#22
#2
#1
#19
#22
R7495 CONTROLLER
(NOT FM APPROVED)
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X3301
#2
#1
#19
#22
#2
#1
#19
#22
#2
#1
#19
#22
#2
#1
#19
#22
33
34
J2-45
J2-37
DETECTOR 3
X3301
J2-46
J2-38
DETECTOR 4
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
DETECTOR 6
X3301
#2
#1
#19
#22
#2
#1
#19
#22
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X3301
J2-50
J2-42
DETECTOR 8
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
47
B5
48
B6
49
B7
50
B8
B2074
TO J1-2
TERMINAL IDENTIFICATION FOR X3301
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
3
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
4
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
0.47 µF / 400 VDC
NON-POLARIZED
5
oi ("D" LEAD)
GROUND FAULT PROTECTED SYSTEMS
Figure 9—A Typical System, X3301 Detectors Wired to R7495 Controller
1.1
11
95-8736
NOTE: DO NOT CONNECT THE X3301 "A" LEAD (#2/12) TO
TERMINAL J2-34 (290 VDC).
R7405 CONTROLLER
(NOT FM APPROVED)
X3301
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X3301
#2
#1
#19
#22
#2
#1
#19
#22
33
J2-45
J2-37
DETECTOR 3
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-46
J2-38
DETECTOR 4
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
34
+290 VDC
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
47
B5
48
B6
49
B7
50
B8
DETECTOR 6
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X3301
#2
#1
#19
#22
#2
#1
#19
#22
J2-50
J2-42
DETECTOR 8
B2075
TO J1-2
TERMINAL IDENTIFICATION FOR X3301
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
3
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
4
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
0.47 µF / 400 VDC
NON-POLARIZED
5
GROUND FAULT PROTECTED SYSTEMS
Figure 10—A Typical System, X3301 Detectors Wired to R7405 Controller
1.1
X3301 DETECTOR
FIRE ALARM PANEL
SHIELD
9
19
8
18
COM FIRE2
7
NO FAULT1
3
+
24 VDC
+Vin
2
–
–Vin
1
28
27
26
END OF
LINE DEVICE 4
15
COM FAULT1
4
29
SPARE
16
NC FIRE2
5
ALARM
SPARE
17
NO FIRE2
6
PULSE OUT
25
14
RS485 A
24
13
RS485 B
23
12
MAN Oi
22
–Vin
11
21
oi TEST 3
WIRING NOTES:
C2062
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 11—Ex d Wiring Option
SHIELD
X3301 DETECTOR
FIRE ALARM PANEL
EOL
RESISTOR4
9
19
8
18
ALARM
7
ALARM
6
5
4
3
+
24 VDC
2
–
1
COM FIRE2
NO FIRE2
NC FIRE2
COM FAULT1
NO FAULT1
+Vin
–Vin
PULSE OUT
SPARE
29
SPARE
28
17
27
16
26
15
25
14
RS485 A
24
13
RS485 B
23
12
MAN Oi
22
11
–Vin
21
oi TEST 3
B2108
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 EOL RESISTOR SUPPLIED BY PANEL.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 12—Ex e Wiring Option
1.1
13
95-8736
EOL Resistors
STARTUP PROCEDURE
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat
generated by EOL resistors, observe the following
guidelines when installing the resistors.
When installation of the equipment is complete,
perform one or more of the following tests:
1.
• Man oi Test — Tests detector output and
wiring, without generating a fire alarm.
• Count Test Mode — Measures actual detector
output to controller (cps), without generating
a fire alarm.
• Fire Alarm Test — For complete system test
including detector relays. Generates fire
alarm output.
Required EOL resistor power rating must be
5 watts minimum.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual
power dissipation not to exceed 2.5 watts.
This applies to ATEX/IEC installations
only.
2.
Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3.
Bend the leads and install the EOL resistor
as shown in Figure 13.
MANUAL oi TEST (Output to Controller)
1.
2.
3.
3/8 INCH (10 MM) GAP MINIMUM
4.
5.
19 18 17 16 15 14 13 12 11
If the system responds differently than indicated
above, proceed with the count test for the problem
zone to verify detector and wiring operation.
B2126
BULKHEAD
COUNT TEST MODE (Output to Controller)
Figure 13—EOL Resistor Installation (For Ex d Wiring only)
4.
When in the Count Test mode, the frequency of
the digital pulses from the detector is displayed
on the ZONE and DETECTOR indicators on the
controller faceplate. The Count Test mode may
be used to check the signal (cps) from a test fire
or false alarm source. This can be useful during
system set-up for sensitivity and time delay
settings. This test is performed in the following
manner:
Maintain a 3/8 inch (10 mm) minimum gap
between the resistor body and the terminal
block or any other neighboring parts.
NOTE
The EOL resistor can only be used within
the flameproof terminal compartment.
Unused apertures shall be closed with
suitable blanking elements.
1.
2.
3.
1.1
Place the keylock switch in the TEST
position.
Press the SELECT button to display the
desired zone on the ZONE indicator on the
front panel of the controller.
Press and hold the TEST button. The ZONE
OUTPUT LED for the tested zone flashes and
the SYSTEM STATUS display indicates a “6”
(fire condition) if the test is successful.
Release the TEST button.
The ZONE
OUTPUT LED for the tested zone should
remain on steadily.
Return to step 2 to test the next detector.
14
Place the keylock switch in the TEST
position.
Simultaneously press and release the
SELECT and TEST buttons. The Status
display will change from a “1” to an “8”
indicating that the controller is in the Count
Test mode of operation.
Press the SELECT button until the desired
zone is displayed on the ZONE indicator on
the controller front panel.
95-8736
4.
TROUBLESHOOTING
Press and hold the TEST button. The
DETECTOR/ZONE display indicates the
counts per second (cps) received from the
detector. If the counts per second exceeds
99, the FIRE LOGIC LEDs are illuminated
to indicate that the number shown on the
display must be multiplied by 10. The
normal reading for an oi test is 80 to 110
cps. For a live fire test, 270 - 330 cps will
be generated.
WARNING
The sensor module (“front” half of the
detector) contains no user serviceable
components and should never be tampered
with.
A zero reading may indicate a dirty window, oi
problem, faulty detector or defective wiring.
1.
Disable any extinguishing equipment that is
connected to the unit.
2.
Inspect
the
viewing
windows
for
contamination and clean as necessary. The
detector is relatively insensitive to airborne
contaminants, however, thick deposits of
ice, dirt, or oil will reduce sensitivity. (Refer
to the “Maintenance” section for complete
information regarding cleaning of the
detector viewing windows.)
Release the Test button, the ZONE and
DETECTOR display should drop to a reading of 0
to 1 counts per second.
FIRE ALARM TEST (Pulse Output to Fire Alarm
Panel)
1.
Disable any extinguishing equipment that is
connected to the system.
3.
Check input power to the unit.
4.
Check system and detector logs.
2.
Apply input power to the system.
5.
3.
Initiate a live fire test or a Mag oi test (see
“Magnetic oi / Manual oi” under “Optical
Integrity” in the Description section of this
manual).
Turn off the input power to the detector and
check all wiring for continuity. Important:
Disconnect wiring at the detector before
checking system wiring for continuity.
6.
If all wiring checks out and cleaning of
the oi plate/window did not correct the
fault condition, check for high levels of
background IR radiation by covering the
detector with the factory supplied cover
or aluminum foil. If the fault condition
clears within 6 minutes or less, extreme
background IR is present. Re-adjust the
view of the detector away from the IR source
or relocate the detector.
4. Repeat this test for all detectors in the
system. If a unit fails the test, refer to the
“Troubleshooting” section.
5. Verify that all detectors in the system are
properly aimed at the area to be protected.
(The Q1201C Laser Aimer is recommended
for this purpose.)
6. Enable extinguishing equipment when the
test is complete.
If these actions do not correct the problem, return
the detector to the factory for repair.
NOTE
It is highly recommended that a complete
spare be kept on hand for field replacement
to ensure continuous protection.
NOTE
For additional troubleshooting guides, refer
to the Flame Inspector Monitor manual
(95-8581).
1.1
15
95-8736
MAINTENANCE
LOOSEN TWO CAPTIVE SCREWS
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not
intended to be serviced and provides
proper ingress protection to eliminate
potential deterioration of the flamepaths.
GRASP VISOR AND
REMOVE oi PLATE
WARNING
The sensor module (“front” half of the
detector) contains no user serviceable
c o m p o n e n t s a n d s h o u l d n ev e r b e
tampered with.
B2106
oi Plate Removal
Figure 14—
To maintain maximum sensitivity and false
alarm resistance, the viewing windows of the
X3301 must be kept relatively clean. Refer to the
following procedure for cleaning instructions.
IMPORTANT
When used in extreme environments, the
reflective surface of the detector oi plate
may eventually deteriorate, resulting in
reoccurring oi faults and the need for oi
plate replacement.
CLEANING PROCEDURE
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
oi PLATE REMOVAL AND REPLACEMENT
To clean the windows and oi plate, use the
window cleaner (p/n 001680-001) and a soft
cloth, cotton swab, or tissue and refer to the
following procedure:
1.
Disable any extinguishing equipment that
is connected to the unit.
1.1
Disable any extinguishing equipment that
is connected to the unit.
2.
Loosen the two captive screws, then grasp
the oi plate by the visor and remove it from
the detector. See Figure 14.
3.
Install the new (or cleaned) oi plate.
NOTE
When installing the stainless steel plate,
ensure that the gasket is present and
correctly seated to prevent moisture or
contaminants from penetrating behind the
plate. To ensure even seating, tighten both
screws equally.
2. Since the X3301 is less affected by
contamination than other detectors, removal
of the oi plate is needed only under extreme
conditions. In addition, it is not necessary
to achieve perfect cleanliness, because IR
is not significantly absorbed by slight films
of oil and/or salt. If a fault condition is still
indicated after cleaning, remove and clean
the oi plate using the oi Plate Removal and
Replacement procedure.
3.
1.
4.
In all environments, clean all three viewing
windows and reflector surfaces thoroughly.
Use a cotton swab and the Det-Tronics
window cleaning solution. Use Isopropyl
alcohol for contaminations that the DetTronics window cleaning solution can not
remove.
Recalibrate the detector’s oi system. Refer
to the Inspector Monitor Manual (95-8581) for
instructions regarding oi plate replacement
and oi system recalibration.
CAUTION
Do not replace the o i reflector plate
without also recalibrating the oi system.
Recalibration of the oi system requires the use
of the Inspector Connector Cable and Inspector
Monitor Software. These two items are included in
the oi replacement kit, or they can be purchased
separately. See Ordering Information for details.
16
95-8736
• Class A wiring per NFPA-72 (Pulse output
version is equivalent to class A when detectors
are installed in a redundant configuration)
• 5 year warranty
X3301 Reflector Plates
X3301 models are supplied with either a black or
a stainless steel reflector plate. These plates are
not interchangeable. Order the replacement that
matches the reflector plate on your X3301 Flame
Detector.
• RFI and EMC Directive compliant
SPECIFICATIONS
PERIODIC CHECKOUT PROCEDURE
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc
maximum).
Maximum ripple is 2 volts
peak-to-peak.
A checkout of the system using the Mag oi or
Man oi feature should be performed on a
regularly scheduled basis to ensure that the
system is operating properly. To test the system,
perform the “Manual oi Test,” “Count Test Mode”
or “Fire Alarm Test” as described in the “Startup
Procedure” section of this manual.
For CSA compliance, the power source
must utilize a SELV (Safety Extra Low
Voltage) or Class 2 style power supply.
CLOCK BATTERY
POWER CONSUMPTION—
Without heater: 4 watts at 24 Vdc nominal;
5.2 watts at 24 Vdc in alarm.
4.5 watts at 30 Vdc nominal;
6.5 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power: 17 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts.
The real time clock has a backup battery that will
operate the clock with no external power. Return
the device to the factory for battery replacement
if needed.
NOTE
If the backup battery is depleted, there is no
effect on the operation of the flame detector,
but the time stamping of the data log may
be affected.
FEATURES
POWER UP TIME—
Fault indication clears after 0.5 second; device
is ready to indicate an alarm condition after 30
seconds.
• Long detection range to carbonaceous fires
• Unequaled false alarm rejection
• Responds to a fire in the presence of
modulated blackbody radiation (i.e. heaters,
ovens, turbines) without false alarm
• Pulse output for compatibility with controller
based systems
• Microprocessor controlled heated optics for
increased resistance to moisture and ice
• Automatic, manual or magnetic oi testing
• Easily replaceable oi plate
• Fire and fault relays
• Multiple sensitivity levels
• A tri-color LED on the detector faceplate
indicates normal condition and notifies
personnel of fire alarm or fault conditions
• Operates under adverse weather conditions
and in dirty environments.
• Mounting arm allows easy sighting
• Integral wiring compartment for ease of
installation
• Explosion-proof/flame-proof detector
housing. Meets FM, CSA, ATEX, IECEx
Directive and CE certification requirements
1.1
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching
operation.
TEMPERATURE RANGE—
Operating: –40°C to +75°C (–40°F to +167°F).
Storage:
–55°C to +85°C (–67°F to +185°F).
Hazardous location ratings from –55°C to +125°C.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
17
95-8736
CONE OF VISION—
The detector has a 90° cone of vision (horizontal)
with the highest sensitivity lying along the central
axis. Unlike conventional detectors, the X3301
provides full coverage at a minimum of 70% of the
maximum detection distance.
SHIPPING WEIGHT (Approximate)—
Aluminum: 7 pounds (3.2 kilograms).
Stainless Steel: 13.8 pounds (6.3 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).
WARRANTY PERIOD—
5 years.
Perfect cone of vision for methane fire detection
— 100 feet (30.5 m) on and off axis on “very high”
setting.
CERTIFICATION—
Refer to Appendix A for FM Approved cone of
vision data.
®
RESPONSE TIME—
Typical response times are under 10 seconds.
See Appendix A for actual response times.
VdS
DIMENSIONS—
See Figure 15.
For complete approval details, refer to the
appropriate Appendix:
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel
(316/CF8M Cast).
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - EN54
Appendix F - Additional approvals
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD
810C (Curve AW).
WIRING—
Field wiring screw terminals are UL/CSA rated
for up to 14 AWG wire, and are DIN/VDE rated
for 2.5 mm2 wire. Screw terminal required torque
range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m).
Important: 18 Vdc minimum must be available
at the detector. For ambient temperatures below
–10°C (14°F) and above +60°C (140°F) use field
wiring suitable for both minimum and maximum
ambient temperature.
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or
M25. Conduit seal not required.
4.7
(11.9)
B2067
10.0
(25.4)
4.8
(12.2)
Figure 15—X3301 Dimensions in Inches (cm)
1.1
18
95-8736
REPLACEMENT PARTS
ORDERING INFORMATION
The detector is not designed to be repaired in the
field. If a problem should develop, refer to the
Troubleshooting section. If it is determined that
the problem is caused by an electronic defect, the
device must be returned to the factory for repair.
When ordering, please specify:
X3301 Multispectrum IR Flame Detector with
Pulse Output
Refer to the X3301 Model Matrix for details
Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel
detectors
REPLACEMENT PARTS LIST
Part Number
009208-001
010831-001
007307-001
010830-001
Description
oi Replacement kit for X3301 (5 Black Reflector Plates)
with Inspector Connector and Monitor
oi Replacement kit for X3301 (5 Stainless Steel Reflector
Plates) with Inspector Connector and Monitor
Replacement oi Reflector Plates for X3301 with Black plate
(requires Inspector Connector to calibrate)
Replacement oi Reflector Plates for X3301 with Stainless
Steel plate (requires Inspector Connector to calibrate)
ACCESSORIES
NOTE: Refer to instruction manual 95-8530 to determine the correct oi
Replacement Plate.
Part Number
Description
000511-029
103881-001
Converter RS485 to RS232
Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
007819-001
007819-002
009207-001
103922-001
102740-002
008082-001
007739-001
007240-001
007818-001
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest
local Detector Electronics office so that a Return
Material Identification (RMI) number can be
assigned. A written statement describing the
malfunction must accompany the returned
device or component to assist and expedite
finding the root cause of the failure.
007818-002
009177-001
010857-001
006097-001
102871-001
007255-001
007338-001
007338-010
007338-020
007338-030
007912-010
007912-020
007912-030
Pack the unit properly. Always use sufficient
packing material. Where applicable, use an
antistatic bag as protection from electrostatic
discharge.
NOTE
Det-Tronics reserves the right to apply a
service charge for repairing returned
product damaged as a result of improper
packaging.
007290-001
NOTE
It is highly recommended that a complete
spare be kept on hand for field replacement
to ensure continuous protection.
1.1
19
Q9033B Stainless Steel Mounting Arm Assembly
is for aluminum and stainless steel detectors
011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
001680-001
Q9033A Aluminum Mounting Arm Assembly is for
aluminum detectors only
Q9033 Collar Attachment
Stop Plug, 3/4” NPT, AL
Stop Plug, 3/4” NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4”NPT, AL
Stop Plug, 20 Pack, 3/4”NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
Window cleaner (6 pack)
107427-040
005003-001
O-ring - Rear Cover (Viton) - black
1 oz grease for detectors (silicone-free)
104346-154
012549-001
O-ring - Rear Cover (Fluorosilicone) - blue
1 oz PTFE silicone-free lubricant
007290-002
Return all equipment transportation prepaid to the
factory in Minneapolis.
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
Flame Inspector Monitor CD
Model 475 HART Communicator
Magnet
Magnet and Adapter for Extension Pole
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange
Mount (SS)
Q1120A1001 Paint Shield mounting ring (AL)
Q1130A1001 Flange Mount Assembly
Q1201 Laser
Laser Battery, 3V Lithium (laser)
Q1201C1001 X-Series Laser Holder (AL/Plastic)
Q2000A1001 X-Series Weather Shield (AL)
Q2033A10R X3301/X3302 FOV Limiter 10° (AL)
Q2033A20R X3301/X3302 FOV Limiter 20° (AL)
Q2033A30R X3301/X3302 FOV Limiter 30° (AL)
Spare Restrictor Plate 10° (AL)
Spare Restrictor Plate 20° (AL)
Spare Restrictor Plate 30° (AL)
95-8736
X3301 MODEL MATRIX
MODEL
X3301
DESCRIPTION
Multispectrum IR Flame Detector
TYPE
MATERIAL
A
Aluminum
S
Stainless Steel (316)
TYPE
THREAD TYPE
4M
4 Port, Metric M25
4N
4 Port, 3/4" NPT
TYPE
15
OUTPUTS
Relay and Pulse
TYPE
APPROVALS
B
INMETRO (Brazil)
W
FM/CSA/ATEX/IECEx
TYPE
1.1
20
CLASSIFICATION
1
Division/Zone Ex d e
2
Division/Zone Ex d
95-8736
HIGH RESOLUTION FIELD OF VIEW DIAGRAMS
0°
15° 265 (80.7)
30°
0°
15° 70 (21.3)
15°
30°
240 (73.1)
45°
30°
45°
200 (60.9)
40 (12.2)
30 (9.1)
80 (24.3)
20 (6.1)
40 (12.1)
10 (3.0)
10 (3.0)
30°
20 (6.1)
30°
30 (9.1)
120 (36.8)
15°
160 (48.7)
200 (60.9)
15°
30°
45°
50 (15.2)
30°
0°
15° 100 (30.5) 15°
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3.0)
70 (21.3)
45°
30°
30°
45°
45°
20 (6.1)
40 (12.1)
60 (18.2)
80 (24.3)
100 (30.4)
120 (36.5)
140 (42.6)
160 (48.7)
175 (53.3)
45°
15°
0°
15°
15°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Isopropanol at Very High Sensitivity (6 in. x 6 in.)
30°
30°
0°
60 (18.3)
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (1 x 1 foot)
45°
15°
40 (12.2)
0°
240 (73.1)
265 (80.7)
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
0°
15° 175 (53.3) 15°
160 (48.7)
140 (42.6)
120 (36.5)
100 (30.4)
80 (24.3)
60 (18.2)
40 (12.1)
20 (6.1)
30°
45°
30°
15°
0°
15°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Diesel at Very High Sensitivity (1 x 1 foot)
Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (6 in. x 6 in.)
1.1
45°
50 (15.2)
120 (36.8)
40 (12.1)
45°
30°
60 (18.3)
45°
160 (48.7)
80 (24.3)
10 (3.0)
20 (6.1)
30 (9.1)
40 (12.2)
50 (15.2)
60 (18.3)
70 (21.3)
80 (24.4)
90 (27.4)
100 (30.5)
15°
21
95-8736
High Resolution Field of View Diagrams – Continued
0°
15° 125 (38.1) 15°
120 (36.6)
105 (32)
90 (27.4)
75 (22.9)
60 (18.3)
45 (13.7)
30 (9.1)
15 (4.6)
30°
45°
15 (4.6)
30 (9.1)
45 (13.7)
60 (18.3)
75 (22.9)
90 (27.4)
105 (32)
120 (36.6)
125 (38.1)
45°
30°
30°
45°
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
20 (6.1)
15°
25 (7.6)
30 (9.1)
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
0°
210 (64)
0°
35 (10.7)
40 (12.2)
45°
30°
30°
45°
45°
150 (45.7)
120 (36.5)
90 (27.4)
60 (18.3)
30 (9.1)
30 (9.1)
15 (4.6)
30 (9.1)
45 (13.7)
60 (18.3)
75 (22.9)
90 (27.4)
105 (32)
120 (36.5)
135 (41.2
150 (45.7)
30°
60 (18.3)
90 (27.4)
15°
120 (36.5)
150 (45.7)
0°
180 (54.9)
210 (64)
45°
15°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Ethanol at Very High Sensitivity (1 x 1 foot)
1.1
15°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Methanol at Very High Sensitivity (6 in. x 6 in.)
15°
180 (54.9)
45°
30°
15 (4.6)
Field of View at Indicated Distance in Feet (m) for
Propane at Very High Sensitivity (32 inch plume)
15°
45°
20 (6.1)
0°
30°
30°
30 (9.1)
25 (7.6)
15°
30°
15°
35 (10.7)
45°
30°
15°
0°
15° 40 (12.2)
0°
15° 150 (45.7) 15°
135 (41.2
120 (36.5)
105 (32)
90 (27.4)
75 (22.9)
60 (18.3)
45 (13.7)
30 (9.1)
15 (4.6)
30°
45°
30°
15°
0°
15°
45°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Methanol at Very High Sensitivity (1 x 1 foot)
22
95-8736
High Resolution Field of View Diagrams – Continued
15°
30°
45°
10 (3)
20 (6.1)
30 (9.1)
40 (12.2)
50 (15.2)
60 (18.3)
70 (21.3)
80 (24.4)
90 (27.4)
100 (30.5)
125 (38.1)
45°
0°
15°
125 (38.1)
100 (30.5)
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
0°
15°
30°
30°
45°
15°
30°
210 (64)
180 (54.9)
45°
45°
150 (45.7)
120 (36.5)
90 (27.4)
60 (18.3)
30 (9.1)
30 (9.1)
60 (18.3)
30°
30°
90 (27.4)
15°
120 (36.5)
15°
150 (45.7)
0°
15°
30°
0°
180 (54.9)
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
210 (64.0)
235 (71.6)
45°
Field of View at Indicated Distance in Feet (m) for
Methane at Very High Sensitivity (32 inch plume)
1.1
235 (71.6)
15°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
JP-5 at Very High Sensitivity (2 x 2 feet)
23
95-8736
High Resolution Field of View Diagrams – Continued
30°
45°
0°
15° 100 (30.5) 15°
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
30°
30°
45°
0°
15° 70 (21.3)
45°
45°
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
Field of View at Indicated Distance in Feet (m) for
Methanol at Medium Sensitivity (1 x 1 foot)
15°
30°
30°
45°
50 (15.2)
45°
0°
70 (21.3)
15°
60 (18.3)
30°
45°
50 (15.2)
40 (12.2)
40 (12.2)
30 (9.1)
30 (9.1)
20 (6.1)
20 (6.1)
10 (3)
10 (3)
Field of View at Indicated Distance in Feet (m) for
Diesel at Medium Sensitivity (1 x 1 foot)
Field of View at Indicated Distance in Feet (m) for
Methane at Medium Sensitivity (32 inch plume)
30°
45°
0°
15° 85 (25.9)
80 (24.4)
75 (22.9)
65 (19.8)
55 (16.8)
45 (13.7)
35 (10.7)
25 (7.6)
15 (4.6)
5 (1.5)
15°
30°
30°
45°
45°
Field of View at Indicated Distance in Feet (m) for
Ethanol at Medium Sensitivity (1 x 1 foot)
15°
30°
45°
30°
50 (15.2)
15°
60 (18.3)
15°
60 (18.3)
45°
Field of View at Indicated Distance in Feet (m) for
n-Heptane at Medium Sensitivity (1 x 1 foot)
30°
0°
15° 70 (21.3)
0°
75 (22.8)
70 (21.3)
0°
15° 150 (45.7) 15°
135 (41.2
120 (36.5)
105 (32)
90 (27.4)
75 (22.9)
60 (18.3)
45 (13.7)
30 (9.1)
15 (4.6)
30°
45°
Field of View at Indicated Distance in Feet (m) for
JP-5 at Medium Sensitivity (2 x 2 feet)
15°
30°
60 (18.3)
50 (15.2)
45°
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
Field of View at Indicated Distance in Feet (m) for
Propane at Medium Sensitivity (32 inch plume)
1.1
24
95-8736
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:
• Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA/Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°C to +75°C (–40°F to +167°F).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
for Class I, Zone 1 AEx d e IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
AEx d IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
for Zone 21 AEx tb T130°C Db
Tamb –40°C to +75°C
Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S.
The following accessories are FM approved for use with the X3301 Flame Detector:
Part Number
102740-002
007739-001
010857-001
007290-001
007290-002
011385-001
Description
Magnet
Magnet and Extension Pole
Q1130A1001 Flange Mount Assembly
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of
lens surfaces resulting in a loss of approximately 50% of its detection range, verifying that the detector
performs a calibrated Automatic oi test for each sensor. Upon removal of the contamination, the
detector fault was cleared and the detector was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally
actuates the alarm relay to verify output operation. If there is a 50% loss of its detection range, an alarm
signal is not generated.
The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual,
is the approved external optical test method for this detector to verify end-to-end detector function. This
test replaces the function and need of a traditional external test lamp.
1.1
25
95-8736
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
n-Heptane
Gasoline
Kerosene
Isopropanol
Diesel
Ethanol
Methanol
Xylene
Toluene
Methane
Propane
Ethane
Ethylene
Butane
Jet A
JP-5
JP-8
Class A
Size
Distance feet (m)
Average Response Time (seconds)
1 x 1 foot
1 x 1 foot
1 x 1 foot
6 in. x 6 in.
1 x 1 foot
1 x 1 foot
6 in. x 6 in.
1 x 1 foot
1 x 1 foot
6 in. x 6 in.
1 x 1 foot
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
32 inch plume
32 inch plume
32 inch plume
1 x 1 foot
2 x 2 feet
1 x 1 foot
Ø12 in. x 7 in.
265 (80.7)*
250 (76.2)
100 (30.5)
100 (30.5)
250 (76.2)
150 (45.7)
70 (21.3)
175 (53.3)
210 (64.0)
40 (12.2)
150 (45.7)
150 (45.7)
200 (60.9)
200 (60.9)
125 (38.1)
125 (38.1)
125 (38.1)
125 (38.1)
125 (38.1)
150 (45.7)
235 (71.6)
150 (45.7)
150 (45.7)
22
17
3
7
6
7**
6
6**
11
3
7
5**
8**
7**
5
5
5
8
5
4**
3**
5**
3**
Size
Distance feet (m)
Average Response Time (seconds)
1 x 1 foot
1 x 1 foot
6 in. x 6 in.
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
32 inch plume
32 inch plume
32 inch plume
32 inch plume
2 x 2 feet
Ø12 in. x 7 in.
100 (30.5)
50 (15.24)
45 (13.72)
70 (21.3)
85 (25.9)
70 (21.3)
70 (21.3)
55 (16.7)
75 (22.8)
75 (22.8)
75 (22.8)
75 (22.8)
150 (45.7)
50 (15.24)
7
<2
7
4**
7
6
6
4
<5
5
6
4
3**
4**
* Outdoor test condition
** Pre-burn from ignition
Ø Diameter
Medium Sensitivity
Fuel
n-Heptane
Isopropanol
Diesel
Ethanol
Methanol
Methane
Propane
Ethane
Ethylene
Butane
JP-5
Class A
**
Ø
1.1
Pre-burn from ignition
Diameter
26
95-8736
FM Approval and Performance Report – Continued
T-Low Sensitivity
Fuel
Size
Distance feet (m)
Average Response Time (seconds)
n-Heptane
Methanol
Methane
Propane
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
50 (15.24)
30 (9.14)
30 (9.14)
30 (9.14)
<4
5
3
5
Fuel
Size
Distance feet (m)
Average Response Time (seconds)
n-Heptane
Methanol
Methane
Propane
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
50 (15.24)
30 (9.14)
30 (9.14)
30 (9.14)
<10
10
10
9
Low Sensitivity
1.1
27
95-8736
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
Very High Sensitivity
Sunlight, direct, modulated, reflected
Sunlight, direct, unmodulated, reflected
Radio frequency interference
Distance
feet (m)
—
—
1 (0.3)
6-inch propane
6-inch propane
3-inch propane
Arc welding, #7014
40 (12.2)
1 x 1 foot n-Heptane
LED Lamp, modulated
LED Lamp, unmodulated
70 w sodium vapor lamp, modulated
70 w sodium vapor lamp, unmodulated
250 w vapor lamp, modulated
250 w vapor lamp, unmodulated
300 w incandescent lamp, modulated
300 w incandescent lamp, unmodulated
500 w shielded quartz halogen lamp, modulated
500 w shielded quartz halogen lamp, unmodulated
500 w unshielded quartz halogen lamp, modulated
500 w unshielded quartz halogen lamp, unmodulated
1500 w electric radiant heater, modulated
1500 w electric radiant heater, unmodulated
Two 34 w fluorescent lamps, modulated
Two 34 w fluorescent lamps, unmodulated
5 (1.5)
5 (1.5)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
8 (2.4)
8 (2.4)
8 (2.4)
8 (2.4)
10 (3.0)
10 (3.0)
3 (0.9)
3 (0.9)
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
False Alarm Source
Fire Source
Distance Average Response Time
feet (m)
(seconds)
6 (1.8)
12
6 (1.8)
2
12 (3.7)
<10
3 unmodulated /
40 (12.2)
2 modulated
6
210 (64)
210 (64)
7
80 (24.4)
3
80 (24.4)
3
80 (24.4)
4
80 (24.4)
3
80 (24.4)
9
80 (24.4)
3
80 (24.4)
4
80 (24.4)
3
80 (24.4)
3
80 (24.4)
3
80 (24.4)
3
80 (24.4)
3
80 (24.4)
3
80 (24.4)
3
Medium Sensitivity
Distance
feet (m)
Sunlight, direct, modulated, reflected
—
Sunlight, direct, unmodulated, reflected
—
Radio frequency interference
1 (0.3)
Arc welding, #7014
15 (4.57)
LED Lamp, modulated
3 (0.9)
LED Lamp, unmodulated
3 (0.9)
70 w sodium vapor lamp, unmodulated
3 (0.9)
250 w vapor lamp, modulated
3 (0.9)
250 w vapor lamp, unmodulated
3 (0.9)
300 w incandescent lamp, modulated
3 (0.9)
300 w incandescent lamp, unmodulated
3 (0.9)
500 w shielded quartz halogen lamp, modulated
8 (2.4)
500 w shielded quartz halogen lamp, unmodulated
8 (2.4)
500 w unshielded quartz halogen lamp, modulated
8 (2.4)
500 w unshielded quartz halogen lamp, unmodulated
8 (2.4)
1500 w electric radiant heater, modulated
10 (3.0)
1500 w electric radiant heater, unmodulated
10 (3.0)
Two 34 w fluorescent lamps, modulated
3 (0.9)
Two 34 w fluorescent lamps, unmodulated
3 (0.9)
False Alarm Source
1.1
28
Fire Source
6-inch propane
6-inch propane
6-inch propane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
Distance Average Response Time
feet (m)
(seconds)
6 (1.8)
9
6 (1.8)
5
6 (1.8)
<1
40 (12.2)
2 modulated
9
100 (30.5)
100 (30.5)
7
60 (18.3)
3
60 (18.3)
3
60 (18.3)
4
60 (18.3)
9
60 (18.3)
4
60 (18.3)
6
60 (18.3)
4
60 (18.3)
5
60 (18.3)
4
60 (18.3)
6
60 (18.3)
4
60 (18.3)
4
60 (18.3)
4
95-8736
FM Approval and Performance Report – Continued
T-Low Sensitivity
False Alarm Source
Sunlight, direct, unmodulated, reflected*
Sunlight, direct, modulated, reflected*
Arc welding, modulated, #7014
LED Lamp, modulated
LED Lamp, unmodulated
70 w sodium vapor, unmodulated
70 w sodium vapor, modulated
250 w vapor lamp, unmodulated
250 w vapor lamp, modulated
300 w incandescent lamp, unmodulated
300 w incandescent lamp, modulated
500 w shielded quartz halogen lamp, unmodulated
500 w shielded quartz halogen lamp, modulated
1500 w electric radiant heater, unmodulated
1500 w electric radiant heater, modulated
Two 34 w fluorescent lamps, unmodulated
Two 34 w fluorescent lamps, modulated
Distance
feet (m)
—
—
8 (2.4)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
10 (3.0)
3 (0.9)
10 (3.0)
3 (0.9)
3 (0.9)
Fire Source
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
Distance
feet (m)
35 (10.7)
15 (4.6)
30 (9.1)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
Average Response Time
(seconds)
9
8
3
2
3
4
5
6
5
4
6
5
5
3
5
2
6
Distance
feet (m)
35 (10.7)
15 (4.6)
30 (9.1)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
50 (15.24)
Average Response Time
(seconds)
12
19
10
9
12
11
11
11
10
10
8
12
10
* Outdoor test conditions
Low Sensitivity
False Alarm Source
Sunlight, direct, unmodulated, reflected*
Sunlight, direct, modulated, reflected*
Arc welding, modulated, #7014
LED Lamp, modulated
LED Lamp, unmodulated
70 w sodium vapor, modulated
250 w vapor lamp, modulated
300 w incandescent lamp, modulated
500 w shielded quartz halogen lamp, unmodulated
500 w shielded quartz halogen lamp, modulated
1500 w electric radiant heater, unmodulated
1500 w electric radiant heater, modulated
Two 34 w fluorescent lamps, modulated
Distance
feet (m)
—
—
5 (1.5)
3 (0.9)
3 (0.9)
3 (0.9)
5 (1.5)
5 (1.5)
3 (0.9)
10 (3.0)
3 (0.9)
10 (3.0)
3 (0.9)
Fire Source
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
* Outdoor test conditions
1.1
29
95-8736
FM Approval and Performance Report – Continued
FALSE ALARM IMMUNITY
Very High Sensitivity
False Alarm Source
Sunlight, direct, reflected
Vibration
Radio frequency interference
Arc welding
LED Lamp
70 w sodium vapor lamp
250 w vapor lamp
300 w incandescent lamp
500 w unshielded quartz halogen lamp
500 w shielded quartz halogen lamp
1500 w electric radiant heater
Two 34 w fluorescent lamps
Distance
feet (m)
—
N/A
1 (0.3)
40 (12.2)
5 (1.5)
3 (0.9)
3 (0.9)
3 (0.9)
8 (2.4)
8 (2.4)
3 (0.9)
5 (1.5)
Modulated Response
Unmodulated Response
No alarm
No alarm
No alarm (keyed)
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
N/A
No alarm (steady)
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
Modulated Response
Unmodulated Response
No alarm
No alarm
No alarm (keyed)
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
N/A
No alarm (steady)
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
Modulated Response
Unmodulated Response
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
Medium Sensitivity
False Alarm Source
Sunlight, direct, reflected
Vibration
Radio frequency interference
Arc welding
LED Lamp
70 w sodium vapor lamp
250 w vapor lamp
300 w incandescent lamp
500 w unshielded quartz halogen lamp
500 w shielded quartz halogen lamp
1500 w electric radiant heater
Two 34 w fluorescent lamps
Distance
feet (m)
—
N/A
1 (0.3)
10 (3)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
T-Low Sensitivity
False Alarm Source
Sunlight, direct, reflected
Vibration
Arc welding
LED Lamp
70 w sodium vapor
250 w vapor lamp
300 w incandescent lamp
500 w shielded quartz halogen lamp
500 w unshielded quartz halogen lamp
1500 w electric radiant heater
Two 34 w fluorescent lamps
1.1
Distance
feet (m)
—
N/A
5 (1.5)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
30
95-8736
FM Approval and Performance Report – Continued
Low Sensitivity
False Alarm Source
Sunlight, direct, reflected
Vibration
Radio frequency interference
Arc welding
LED Lamp
70 w sodium vapor lamp
250 w vapor lamp
300 w incandescent lamp
500 w shielded quartz halogen lamp
500 w unshielded quartz halogen lamp
1500 w electric radiant heater
Two 34 w fluorescent lamps
Distance
feet (m)
—
N/A
—
5 (1.5)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
Modulated
Response
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
Unmodulated Response
No alarm
No alarm
N/A
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
FIELD OF VIEW
Very High Sensitivity
Fuel
n-Heptane
Gasoline
Kerosene
Isopropanol
Diesel
Ethanol
Methanol
Xylene
Toluene
Methane
Propane
Ethane
Ethylene
Butane
Jet A
JP-5
JP-8
Class A
Size
1 x 1 foot
1 x 1 foot
1 x 1 foot
1 x 1 foot
6 x 6 inches
1 x 1 foot
1 x 1 foot
6 x 6 inches
1 x 1 foot
1 x 1 foot
6 x 6 inches
1 x 1 foot
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
32 inch plume
32 inch plume
32 inch plume
1 x 1 foot
2 x 2 feet
1 x 1 foot
Ø12 in. x 7 in.
Distance Horizontal
feet (m)
L, R (°)
190 (57.9)
+/– 45
180 (54.9)
+/– 45
180 (54.9)
+/– 45
100 (30.5)
+/– 45
100 (30.5)
+/– 45
190 (57.9)
+/– 45
110 (33.5)
+/– 45
70 (21.3)
+/– 45
150 (45.7)
+/– 45
150 (45.7)
+/– 45
40 (12.2)
+/– 45
110 (33.5)
+/– 45
110 (33.5)
+/– 45
150 (45.7)
+/– 45
150 (45.7)
+/– 45
100 (30.5)
+/– 45
90 (27.4)
+/– 45
90 (27.4)
+/– 45
90 (27.4)
+/– 45
90 (27.4)
+/– 45
100 (30.5)
+/– 45
180 (54.9)
+/– 45
100 (30.5)
+/– 45
80 (24.4)
+/– 45
Avg. Resp
Time (s)
11
8
6**
4
11
7
5
8
10**
15
3
8
8**
7**
8**
7
7
5
7
5
4**
6**
5**
4**
Vertical
Down (°)
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
+45
Avg. Resp
Time (s)
11
11
6**
3
11
9
5
6
7**
13
3
13
4**
6**
8**
8
9
6
9
4
3**
4**
5**
2**
Vertical
Up (°)
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
Avg. Resp
Time (s)
8
3
3**
2
7
5
4
5
7**
10
2
3
3**
3**
4**
4
5
3
5
2
2**
2**
3**
2**
* Outdoor test condition
** Pre-burn from ignition
Ø Diameter
1.1
31
95-8736
FM Approval and Performance Report – Continued
Medium Sensitivity
Fuel
Size
1 x 1 foot
1 x 1 foot
6 x 6 inches
1 x 1 foot
1 x 1 foot
1 x 1 foot
32 inch plume
2 x 2 feet
32 inch plume
32 inch plume
32 inch plume
32 inch plume
Ø12 in. x 7 in.
n-Heptane
Isopropanol
Diesel
Ethanol
Methanol
Methane
JP-5
Propane
Ethane
Ethylene
Butane
Class A
Distance Horizontal Avg. Resp Vertical
feet (m)
L, R (°)
Time (s) Down (°)
75 (22.9)
+/– 45
5
+45
50 (15.2)
+/– 45
3
+45
45 (13.7)
+/– 45
11
+45
60 (18.2)
+/– 45
4**
+45
60 (18.2)
+/– 45
7
+45
50 (15.2)
+/– 45
5
+45
50 (15.2)
+/– 45
5
+45
110 (33.5)
+/– 45
7
+45
55 (16.7)
+/– 45
5
+45
55 (16.7)
+/– 45
6
+45
55 (16.7)
+/– 45
7
+45
55 (16.7)
+/– 45
6**
+45
40 (12.2)
+/– 45
3**
+45
Avg. Resp
Time (s)
4
2
8
6**
8
2
6
4
4
5
5
4**
3**
Vertical
Up (°)
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
–30
Avg. Resp
Time (s)
5
3
6
4**
5
6
3
5
5
5
5
3**
3**
** Pre-burn from ignition
Ø Diameter
T-Low Sensitivity
Fuel
Size
n-Heptane
Methanol
Methane
Propane
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
Distance
feet (m)
35 (10.7)
20 (6.1)
20 (6.1)
20 (6.1)
Horizontal
L, R (°)
+/– 45
+/– 45
+/– 45
+/– 45
Avg. Resp
Time (s)
4
4
4
4
Vertical
Down (°)
+45
+45
+45
+45
Avg. Resp
Time (s)
4
4
4
4
Vertical
Up (°)
–30
–30
–30
–30
Avg. Resp
Time (s)
3
2
4
5
Distance
feet (m)
35 (10.7)
20 (6.1)
20 (6.1)
20 (6.1)
Horizontal
L, R (°)
+/– 45
+/– 45
+/– 45
+/– 45
Avg. Resp
Time (s)
8
9
9
9
Vertical
Down (°)
+45
+45
+45
+45
Avg. Resp
Time (s)
9
9
9
9
Vertical
Up (°)
–30
–30
–30
–30
Avg. Resp
Time (s)
10
9
8
11
Low Sensitivity
Fuel
Size
n-Heptane
Methanol
Methane
Propane
1 x 1 foot
1 x 1 foot
32 inch plume
32 inch plume
1.1
32
95-8736
APPENDIX B
CSA APPROVAL
Multispectrum IR Flame Detector/Controller X3301 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts.
Relay contacts rated 30 Vdc, 5 Amps.
NOTE
Hazardous location testing has been successfully completed on the Model X3301 series from an ambient
temperature range of –55°C to +125°C; however, the detector label marking indicates –40°C to +75°C.
The following accessories are CSA approved for use with the X3301 Flame Detector:
Part Number
102740-002
007739-001
010857-001
007290-001
007290-002
011385-001
Description
Magnet
Magnet and Extension Pole
Q1130A1001 Flange Mount Assembly
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
DIVISION CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A);
Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C);
Class III; Enclosure NEMA/Type 4X;
Conduit seal not required.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91
–
General Requirements — Canadian Electrical Code, Part II
CAN/CSA Std C22.2 No. 25-1966
–
Enclosures for use in Class II Groups E, F & G Hazardous Locations
CAN/CSA-C22.2 No. 30-M1986
–
Explosion-Proof Enclosures for use in Class I Hazardous Locations
CAN/CSA-C22.2 No. 94-M91
–
Special Purpose Enclosures
CAN/CSA-C22.2 No. 142-M1987
–
Process Control Equipment
CAN/CSA-C22.2 No. 213-M1987
–
Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex d e IIC T5-T6
T6 (Ta -50oC to +60oC)
T5 (Ta -50oC to +75oC)
Seal required adjacent to enclosure
IP66/IP67.
Ex d IIC T4-T6
T6 (Ta -55oC to +60oC)
T5 (Ta -55oC to +75oC)
T4 (Ta -55oC to +125oC)
Seal required adjacent to enclosure
IP66/IP67.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0:2007
– Electrical apparatus for explosive gas atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1:2011
– Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7:2012
– Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
1.1
33
95-8736
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 01 ATEX 130204X
Increased Safety Model
0539
II 2 G
II 2 D
Flameproof Model
II 2 G
II 2 D
0539
Ex d e IIC T6...T5 Gb
Ex d IIC T6...T4 Gb
Ex tb IIIC T130°C
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67.
T4 (Tamb = –55°C to +125°C)
IP66/IP67.
Compliance with:
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-31: 2009
EN/IEC 60529: 2001.
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring
specifications from 14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with
the terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with EN600791 clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by
Detector Electronics Corporation only.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk
of mechanical damage.
1.1
34
95-8736
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof
model unless the addressable module is component certified as Ex e for use within the Ex d e
increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking
elements shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection
increased safety “e” or flameproof enclosure “d” (as applicable), suitable for the conditions of
use and correctly installed. They shall maintain the degree of ingress protection IP66/IP67 for
the apparatus. Unused conduit entries shall be closed with suitable blanking elements.
NOTE
For ATEX installations, the X3301 Flame Detector housing must be electrically connected to earth
ground.
The following accessories are ATEX approved for use with the X3301 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
1.1
35
95-8736
APPENDIX D
IECEx APPROVAL
IECEx CERTIFICATE OF CONFORMITY
DEMKO
IECEx ULD 06.0017X
Ex d e IIC T6...T5 Gb
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C)
IP66/IP67.
or
Ex d IIC T6...T4 Gb
Ex tb IIIC T130°C
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C)
IP66/IP67.
Compliance with:
IEC 60079-0: 2007, Ed. 5
IEC 60079-1: 2007, Ed. 6
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
EN/IEC 60529: 2001.
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring
specifications from
14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use
with the terminal compartment in type of explosion protection flameproof enclosure "d" or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with IEC 60079-1
clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector
Electronics Corporation only.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed
2.5 watts.
The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk
of mechanical damage.
The following accessories are IECEx approved for use with the X3301 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
1.1
36
95-8736
APPENDIX E
EN54 APPROVALS
Certification Bodies
VdS –
Constructive Product Regulation
Conventional Output
Basis of Approval
Certificate/Approval
Number
0786 – CPR – 20453
EN 54-10 + A1
—
—
LPCB
Basis of Approval
G 202136
VdS 2344
VdS 2504
EN 54-10 + A1
G 212019
VdS 2344
VdS 2504
EN 54-10 + A1
EN 54-17
S 212002
VdS 2344
EN 54-13
S 212002
VdS 2344
EN 54-13
—
—
0832 – CPR – F0892
EN 54-10 + A1
EN 54-17
973e/03
EN 54-10 + A1
973a/03
EN 54-10 + A1
EN 54-17
VdS*
BRE –
Constructive Product Regulation
LON Output
Certificate/Approval
Number
* Approval of all sensitivities.
INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM
The installation shall take into account, that the orientation arrow on the flame detector is directed
upwards, as the view angle in this direction is <90°.
The IR-flame detector configured to all sensitivity levels corresponds to class 1.
The following accessories are EN54-10, EN54-13, and EN54-17 approved for use with the X3301 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
1.1
Q9033 Collar Attachment
37
95-8736
APPENDIX F
ADDITIONAL APPROVALS
BRAZIL
UL-BR 12.0093X
Ex d e IIC T6-T5 Gb IP66/IP67
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C).
– OR –
Ex d IIC T6-T4 Gb IP66/IP67
Ex tb IIIC T130°C
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C).
1.1
38
95-8736
95-8736
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110 th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2015 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.