Det-Tronics Instructions Multispectrum IR Flame Detector with Pulse Output X3301
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions Multispectrum IR Flame Detector with Pulse Output X3301 1.1 Rev: 10/15 95-8736 Table of Contents DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . oi (Optical Integrity) . . . . . . . . . . . . . . . . . Communication . . . . . . . . . . . . . . . . . . . . . Data Logging . . . . . . . . . . . . . . . . . . . . . . . Integral Wiring Compartment . . . . . . . . . . . Detector Sensitivity Levels . . . . . . . . . . . . 1 2 2 2 3 3 3 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . 17 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 17 REPLACEMENT PARTS . . . . . . . . . . . . . . . 19 Replacement Parts List . . . . . . . . . . . . . . 19 DEVICE REPAIR AND RETURN . . . . . . . . . 19 GENERAL APPLICATION INFORMATION . . 4 Response Characteristics . . . . . . . . . . . . . 4 Important Application Considerations . . . . 4 ORDERING INFORMATION . . . . . . . . . . . . . 19 Accessories . . . . . . . . . . . . . . . . . . . . . . . 19 X3301 Model Matrix . . . . . . . . . . . . . . . . . 20 IMPORTANT SAFETY NOTES . . . . . . . . . . . . 4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . Detector Positioning . . . . . . . . . . . . . . . . . . Detector Orientation . . . . . . . . . . . . . . . . . . Protection Against Moisture Damage . . . . Wiring Procedure . . . . . . . . . . . . . . . . . . . . 5 5 5 6 6 HIGH RESOLUTION FIELD OF VIEW DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . 21 APPENDIX A – FM APPROVAL AND PERFORMANCE REPORT . . . . . . . . . . . . . 25 APPENDIX B – CSA APPROVAL . . . . . . . . . 33 STARTUP PROCEDURE . . . . . . . . . . . . . . . 14 Manual oi Test (Output to Controller) . . . 14 Count Test Mode (Output to Controller) . 14 Fire Alarm Test (Pulse Output to Fire Alarm Panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 TROUBLESHOOTING . . . . . . . . . . . . . . . . . 15 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . Cleaning Procedure . . . . . . . . . . . . . . . . . oi Plate Removal and Replacement . . . . Periodic Checkout Procedure . . . . . . . . . Clock Battery . . . . . . . . . . . . . . . . . . . . . . 16 16 16 17 17 APPENDIX C – ATEX APPROVAL . . . . . . . . 34 APPENDIX D – IECEx APPROVAL . . . . . . . 36 APPENDIX E – EN54 APPROVALS . . . . . . . 37 APPENDIX F – ADDITIONAL APPROVALS . . . 38 INSTRUCTIONS Multispectrum IR Flame Detector with Pulse Output X3301 WARNING Be sure to read and understand the entire instruction manual before installing or operating the flame detection system. Any deviation from the recommendations in this manual may impair system performance and compromise safety. ATTENTION The X3301 includes the Automatic o i ® (Optical Integrity) feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. Testing with an external test lamp is not approved or required. The X3301 contains three IR sensors and provides unsurpassed detection of flames from light to heavy hydrocarbon fuels combined with the highest degree of false alarm rejection. The detector has Division and Zone explosionproof ratings and is suitable for use in indoor and outdoor applications. The X3301 housing is available in copper-free aluminum or stainless steel, with NEMA/Type 4X and IP66/IP67 rating. DESCRIPTION The X3301 with pulse/relay output is a multispectrum infrared (IR) flame detector that is designed for use in controller based systems. In addition to use in new systems, it can serve as a direct field replacement for Det-Tronics controller based flame detectors that generate a pulse output (not compatible with R7484 and R7409B/C). A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Microprocessor controlled heated optics increase resistance to moisture and ice. When used as a field replacement, all operating features of the current controller are retained in addition to gaining the advanced features of the X3301 Flame Detector. In typical applications, the four wire X3301 can utilize all existing system wiring. 1.1 ©Detector Electronics Corporation 2015 1 Rev: 10/15 95-8736 indicated by the Fault output and is evident by the yellow color of the LED on the face of the detector. The oi fault condition is self-clearing if the optical contamination is temporary. If the contamination is not automatically cleared and the oi fault remains, the detector may require cleaning or service. See the "Troubleshooting" section for further information. OUTPUTS Relays The detector is furnished with fire and fault relays. The relays are rated 5 amperes at 30 Vdc. The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. Magnetic oi / Manual oi The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test. An alarm condition will normally over-ride a fault condition, unless the nature of the fault condition impairs the ability of the detector to generate or maintain an alarm output, i.e. loss of operating power. The detector incorporates both Magnetic oi (Mag oi) and Manual oi (Man oi) test capabilities. These tests provide pulses (80 to 100 CPS) to the controller (R7404 or R7494) when the detector is not in fault. If the test is successful, the controller indicates a fire and the appropriate zone output is active. LED A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Table  2 indicates the condition of the LED for each status. NOTE If the detector is in a fault condition, a successful Mag o i or Man o i test cannot be performed. Table 1—Detector Status Indicator Detector Status Power On/Normal Operation (no fault or fire alarm) Fault Fire (Alarm) Low Sensitivity T-Low Sensitivity Medium Sensitivity Very High Sensitivity LED Indicator The Mag oi test is initiated by placing a magnet at the location marked “MAG OI” on the outside of the detector (see Figure 2). This action causes the detector to immediately send pulses to the controller. Controller response is as follows: Green Yellow Red One Yellow Flash During Power-up Three Yellow Flashes During Power-up Two Yellow Flashes During Power-up Four Yellow Flashes During Power-up • The Zone LED blinks. • The digital display indicates which Zone is in alarm. • The status indicator shows “6” (fire). NOTE: See "Detector Sensitivity Levels" for additional information. IMPORTANT Mag o i can be performed with the controller’s (R7404/R7494) keylock switch in either the NORMAL or TEST position. In NORMAL, the controller goes into alarm and activates its outputs. If no controller alarm output is desired, place the keylock switch in the TEST position before touching the magnet to the outside of the detector. Man o i operates only with the keylock switch in the TEST position. During the entire test, the detector gives no indication of alarm. oi (OPTICAL INTEGRITY) Automatic oi The X3301 includes the Automatic oi feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. No testing with an external test lamp is required. The detector automatically performs the same test that a maintenance person with a test lamp would perform — once every minute, 60 times per hour. However, a successful Automatic oi test does not produce an alarm condition. To reset the controller status and alarms, place the keylock switch in RESET. Return the keylock switch to NORMAL when testing is complete. The detector signals a fault condition when less than half of the detection range remains. This is 1.1 2 95-8736 The Man oi test is nearly identical to the Mag oi test, except for the manner in which the test is initiated: DETECTOR SENSITIVITY LEVELS There are four factory configured sensitivity levels available for the X3301 Flame Detector: • Place the keylock switch on the controller (R7404/R7494) in the Test position. • Press the Select button to select the appropriate detector for test. • Press the Test/Accept button to initiate the test. Very High, Medium, Low, and T-Low. The following criteria should be considered when choosing a sensitivity level for the intended application: • Detector placement • Speed of response based on fuel type and fire size (see Appendix A for examples of response times) • Distance between the hazard and the flame detector Controller and detector responses are identical to the Mag oi test described above. To reset the controller status and alarms, place the keylock switch in RESET. Return the keylock switch to NORMAL when testing is complete. Additional information on X3301 Flame Detector performance results and sensitivities can be found in Appendix A, the FM Approval and Performance Report. NOTE Refer to Appendix A for FM verification of the o i function. COMMUNICATION Consult the factory with any questions on how to choose the optimum sensitivity level for the intended application. The X3301 is furnished with an RS-485 interface for communicating status and other information with external devices. The RS-485 supports MODBUS protocol, with the detector configured as a slave device. DATA LOGGING Data logging capability is also provided. Status conditions such as normal, power down, general and oi faults, fire alarm, time and temperature are recorded. Each event is time and date stamped, along with the temperature and input voltage. Event data is stored in non-volatile memory when the event becomes active, and again when the status changes. Data is accessible using Det-Tronics' Inspector Connector accessory or RS-485. INTEGRAL WIRING COMPARTMENT All external wiring to the device is connected within the integral junction box. The detector is furnished with four conduit entries, with either 3/4 inch NPT or M25 threads. 1.1 3 95-8736 GENERAL APPLICATION INFORMATION Non-Carbon Fires The X3301 is a multiple spectrum IR device with detection limited to carbonaceous fuels. It should not be used to detect fires from fuels that do not contain carbon, such as hydrogen, sulfur, and burning metals. RESPONSE CHARACTERISTICS Response is dependent on the detector's sensitivity setting, distance, type of fuel, temperature of the fuel, and time required for the fire to come to equilibrium. As with all fire tests, results must be interpreted according to an individual application. IMPORTANT SAFETY NOTES WARNING Do not open the detector assembly in a hazardous area when power is applied. The detector contains limited serviceable components and should never be opened. Doing so could disturb critical optical alignment and calibration parameters, possibly causing serious damage. See Appendix A for third-party approved fire test results. Additional fire test results are available from Det-Tronics. IMPORTANT APPLICATION CONSIDERATIONS In applying any type of sensing device as a fire detector, it is important to know of any conditions that can prevent the device from responding to fire, and also to know what other sources besides fire can cause the device to respond. CAUTION The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local ordinances. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person. Welding It is recommended that the system be bypassed during welding operations in situations where the possibility of a false alarm cannot be tolerated. Gas welding mandates system bypass, since the gas torch is an actual fire. Arc welding rods can contain organic binder materials in the flux that burn during the welding operation and are detectable by the X3301. Welding rods with clay binders do not burn and will not be detected by the X3301. However, system bypass is always recommended, since the material being welded may be contaminated with organic substances (paint, oil, etc.) that will burn and possibly cause the X3301 to alarm. CAUTION To prevent unwanted actuation or alarm, extinguishing devices must be disabled prior to per forming system tests or maintenance. Due to the possibility of an alarm condition, arc welding should not be performed within 40 feet (12.2 m) of the detector configured to very high sensitivity, within 10 feet (3.0 m) at medium sensitivity, within 5 feet (1.5 m) at T-Low sensitivity, or at Low sensitivity. CAUTION The multispectrum IR flame detectors are to be installed in places where the risk of mechanical damage is low. Artificial Lighting The X3301 should not be located within 3 feet (0.9 m) of artificial lights. Excess heating of the detector could occur due to heat radiating from the lights. ATTENTION Remove the protective cap from the front of the detector before activating the system. ATTENTION O b s e rv e p re ca u t i o n s fo r h a n d l i n g electrostatic sensitive devices. EMI/RFI Interference The X3301 is resistant to interference by EMI and RFI, and is EMC Directive compliant. It will not respond to a 5 watt walkie-talkie at distances greater than 1 foot (0.3 m). Do not operate a walkie-talkie within 1 foot (0.3 m) of the X3301. 1.1 4 95-8736 INSTALLATION • Dense fog, rain or ice can absorb IR radiation and reduce the sensitivity of the detector. To ensure optimum performance, be certain that the internal optical heater is enabled on detectors that are used in applications where snow, ice, and condensation are likely to occur. • Although IR detectors are less affected by smoke than other detectors, the X3301 should not be placed where rising combustion products can obscure its vision. If smoke is expected before fire, smoke or other alternative detectors should be used in conjunction with the X3301. For indoor applications, if dense smoke is expected to accumulate at the onset of a fire, install the detector on a side wall at least a few feet (approximately 1 meter) down from the ceiling. • If possible, fire tests can be conducted to verify correct detector positioning and coverage. • For ATEX/IECEx installations, the X3301 Flame Detector housing must be electrically connected to earth ground. NOTE The recommended lubricant for threads and O-rings is a silicone free grease (p/n 005003-001) available from Det-Tronics. Under no circumstances should a lubricant containing silicone be used. DETECTOR POSITIONING Detectors should be positioned to provide the best unobstructed view of the area to be protected. The following factors should also be taken into consideration: • Identify all high risk fire ignition sources. • Be sure that enough detectors are used to adequately cover the hazardous area. • Be sure that the unit is easily accessible for cleaning and other periodic servicing. • Verify that all detectors in the system are properly located and positioned so that any fire hazards are within both the Field of View (FOV) and detection range of the detector. The Q1201C Laser Aimer is recommended for establishing the detector's FOV. Refer to the "High Resolution Field of View Diagrams" section for specific information regarding detector range and FOV. • The detector should be aimed downward at least 10 to 20 degrees to allow lens openings to drain. See Figure 1. The detector should be positioned so that its FOV does not cover areas outside the hazardous area. This will minimize the possibility of false alarms caused by activities outside the area requiring protection. • The detector must be mounted on a rigid surface in a low vibration area. DETECTOR ORIENTATION Refer to Figure  2 and ensure that the oi plate will be oriented as shown when the X3301 is installed and sighted. This will ensure proper operation of the oi system and will also minimize the accumulation of moisture and contaminants between the oi plate and the viewing windows. IMPORTANT If removed, the o i plate must be securely tightened to ensure proper operation of the o i system (40 oz./inches [28.2 N . cm] recommended). oi PLATE CENTER AXIS OF DETECTOR FIELD OF VIEW PLACE MAGNET HERE TO INITIATE MAGNETIC oi VIEWING WINDOW (3) INCORRECT oi MAGNET F2068 DETECTOR STATUS INDICATOR Figure 2—Front View of the X3301 CENTER AXIS OF DETECTOR FIELD OF VIEW CORRECT D1974 NOTE: DETECTOR MUST ALWAYS BE AIMED DOWNWARD AT LEAST 10 TO 20 DEGREES. Figure 1—Detector Orientation Relative to Horizon 1.1 5 95-8736 PROTECTION AGAINST MOISTURE DAMAGE IMPORTANT A minimum input voltage of 18 Vdc must be present at the X3301. It is important to take proper precautions during installation to ensure that moisture will not come in contact with the electrical connections or components of the system. The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer. The use of shielded cable is required to protect against interference caused by EMI and RFI. When using cables with shields, terminate the shields as shown in Figures 6 through 10. Consult the factory if not using shielded cable. If conduit is used, we recommend installing drains, according to local codes, at water collection points to automatically drain accumulated moisture. It is also recommended to install at least one breather, according to local codes, at upper locations to provide ventilation and allow water vapor to escape. The “B” (pulse output) and “D” (oi driver) leads from each detector should be shielded from the “B” and “D” leads of all other detectors in order to prevent false alarms resulting from crosstalk between zones. It is recommended that the “A” and “C” leads also be shielded to provide maximum immunity to EMI/RFI. (See Figures 6 to 10.) Conduit raceways should be inclined so that water will flow to low points for drainage and will not collect inside enclosures or on conduit seals. If this is not possible, install conduit drains above the seals to prevent the collection of water or install a drain loop below the detector with a conduit drain at the lowest point of the loop. In applications where the wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical equipment. If disconnection of power is required, separate disconnect capability must be provided. Conduit seals are not required for compliance with explosion-proof installation requirements, but are highly recommended to prevent water ingress in outdoor applications. Units with M25 threads must use an IP66/IP67 washer to prevent water ingress. WARNING All entries must contain appropriately rated plugs or fittings. It is required that each plug or fitting be wrench-tightened to an appropriate installation torque and meet the minimum thread engagement requirements per the applicable local standards, codes, and practices in order to retain the defined ratings. PTFE sealant or equivalent should be used on NPT threads. WIRING PROCEDURE Wire Size and Type The system should be wired according to local codes. The wire size selected should be based on the number of detectors connected, the supply voltage, and the cable length. Typically 16 AWG or 2.5 mm2 shielded cable is recommended. Wires should be stripped 3/8 inch (9 mm). In some cases where the X3301 is replacing existing pulse output detectors, the wiring and power supplies may not be adequate. Consult the factory for assistance. 4X ø0.42 (1.1) 3.0 (7.6) IMPORTANT Devices certified for hazardous locations shall be installed in accordance with EN/ IEC 60079-14 and NEC 505. CAUTION Installation of the detector and wiring should be performed only by qualified personnel. 4.0 (10.2) 13.1 (33.3) NOTE: THIS ILLUSTRATION SHOWS THE DETECTOR MOUNTED AT THE 10° MINIMUM. THESE DIMENSIONS WILL CHANGE BASED ON THE DETECTOR’S MOUNTING ANGLE. 3.0 (7.6) 4.0 (10.2) 10.6 (27.0) F2069 Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm) (See Figure 1 for Correct Detector Orientation.) 1.1 6 95-8736 Detector Installation Install the mounting arm assembly on a rigid surface. The ideal installation surface should be free of vibration and suitable to receive 3/8 inch or M10 bolts with a length of at least 1 inch (25 mm). The surface must also have sufficient capacity to hold the detector and mounting arm weights (see "Specifications" section). Refer to the Q9033 Mounting Arm and Collar Attachment manual (958686) for additional installation information. See Figure 3 for dimensions. 9 19 8 18 PULSE OUT 29 SPARE 28 SPARE 7 COM FIRE 17 COM FIRE 27 6 NO FIRE 16 NO FIRE 26 5 NC FIRE 15 NC FIRE 25 4 COM FAULT 14 COM FAULT 24 RS485 A 3 NO FAULT 13 NO FAULT 23 RS485 B 2 +Vin 12 +Vin 22 MAN Oi 1 –Vin 11 –Vin 21 –Vin Detector Wiring C2070 Figure 5—X3301 Pulse Wiring Terminal Identification IMPORTANT If installing an X3301 in place of an existing detector, be sure to move the “A” Lead (detector power) at the controller from the +290 Vdc source to the +24 Vdc source. Do not apply 290 Vdc to the X3301. Leave the shield open at the detector end and permanently isolate it from accidental contact with the case and/or other conductors. At the controller/fire panel end, connect the shield and power minus (–) to chassis (earth) ground either directly or through a 0.47 µF 400 Volt non-polarized capacitor (not supplied). (Refer to Figures 6 through 10.) Figures 11 and 12 provide examples of typical installations with a X3301 wired to a fire alarm panel. Figure 13 shows an EOL resistor installed within the integral wiring compartment of the detector (refer to “EOL Resistors” for details). 1. Make field connections following local ordinances and guidelines in this manual. Figure 4 shows the wiring terminal strip located inside the detector’s integral junction box. Figure 5 shows the wiring terminal identification for the X3301 detector with pulse output. 2. Check all field wiring to be sure that the proper connections have been made. IMPORTANT Do not test any wiring connected to the detector with a meg-ohmmeter. Disconnect wiring at the detector before checking system wiring for continuity. 3. Make the final sighting adjustments and use a 14 mm hex wrench to ensure that the mounting arm assembly is tight. Figure 4—X3301 Terminal Block 1.1 7 95-8736 NOTE: DO NOT CONNECT THE X3301 "A" LEAD (#2/12) TO TERMINAL J1-3 (290 VDC). X3301 #2 #1 #19 #22 #2 #1 #19 #22 DETECTOR 1 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-5 J1-13 DETECTOR 2 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-6 J1-14 DETECTOR 3 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-7 J1-15 DETECTOR 4 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-8 J1-16 DETECTOR 5 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-9 J1-17 DETECTOR 6 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-10 J1-18 DETECTOR 7 X3301 #2 #1 #19 #22 #2 #1 #19 #22 24 VDC J1 + 1 – 2 + – 3 (A) +290 VDC 4 J2 R7404 CONTROLLER } 10 TO 38 VDC ZONE OUTPUT 1 33 ZONE OUTPUT 2 34 ZONE OUTPUT 3 35 B - INPUT 1 ZONE OUTPUT 4 36 5 B - INPUT 2 ZONE OUTPUT 5 37 6 B - INPUT 3 ZONE OUTPUT 6 38 7 B - INPUT 4 ZONE OUTPUT 7 39 8 B - INPUT 5 ZONE OUTPUT 8 40 9 B - INPUT 6 FIRE LOGIC “A” 41 10 B - INPUT 7 FIRE LOGIC “B” 42 11 B - INPUT 8 ALARM OUTPUT 43 12 D1-1 oi DRIVER EXTERNAL RESET/INHIBIT 44 13 D1-2 oi DRIVER OUTPUTS INHIBITED 45 14 D1-3 oi DRIVER FAULT OUTPUT 46 15 D1-4 oi DRIVER EXTERNAL ACCEPT 47 16 D1-5 oi DRIVER STATUS & DET. OUTPUT S1 48 17 D1-6 oi DRIVER STATUS & DET. OUTPUT S2 49 18 D1-7 oi DRIVER STATUS & DET. OUTPUT S3 50 19 D1-8 oi DRIVER STATUS & DET. OUTPUT S4 51 20 D2-1 oi DRIVER STATUS & DET. OUTPUT S5 52 21 D2-2 oi DRIVER STATUS & DET. OUTPUT S6 53 22 D2-3 oi DRIVER STATUS & DET. OUTPUT S7 54 23 D2-4 oi DRIVER STATUS & DET. OUTPUT S8 55 24 D2-5 oi DRIVER DATA BUS 0 56 25 D2-6 oi DRIVER DATA BUS 1 57 26 D2-7 oi DRIVER DATA BUS 2 58 27 D2-8 oi DRIVER DATA BUS 3 59 28 DMA OUT AVAILABLE DATA BUS 4 60 29 DMA OUT DATA BUS 5 61 30 DMA IN DATA BUS 6 62 31 DATA STROBE DATA BUS 7 32 DMA IN AVAILABLE CHASSIS (EARTH) GND 63 64 B2071 J1-11 J1-19 DETECTOR 8 TO J1-2 TERMINAL IDENTIFICATION FOR X3301 WITH PULSE OUTPUT. TERMINAL NO. 1/11 FUNCTION DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. 62 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 64 63 0.47 µF / 400 VDC NON-POLARIZED NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 6—A Typical System, X3301 Detectors Wired to R7404 Controller 1.1 8 95-8736 NOTE: DO NOT CONNECT THE X3301 "A" LEAD (#2/12) TO TERMINAL J1-3 (290 VDC). X3301 #2 #1 #19 #22 #2 #1 #19 #22 DETECTOR 1 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-5 J1-13 DETECTOR 2 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-6 J1-14 DETECTOR 3 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-7 J1-15 DETECTOR 4 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-8 J1-16 +24 VDC ZONE OUTPUT 1 33 – 2 CIRCUIT GROUND ZONE OUTPUT 2 34 3 +290 VDC ZONE OUTPUT 3 35 4 B1 - INPUT SIGNAL ZONE OUTPUT 4 36 5 B2 - INPUT SIGNAL ZONE OUTPUT 5 37 6 B3 - INPUT SIGNAL ZONE OUTPUT 6 38 7 B4 - INPUT SIGNAL ZONE OUTPUT 7 39 8 B5 - INPUT SIGNAL ZONE OUTPUT 8 40 9 B6 - INPUT SIGNAL FIRE LOGIC “A” 41 10 B7 - INPUT SIGNAL FIRE LOGIC “B” 42 11 B8 - INPUT SIGNAL ALARM OUTPUT 43 12 D1 oi DRIVER EXTERNAL RESET/INHIBIT 44 13 D2 oi DRIVER OUTPUTS INHIBITED 45 14 D3 oi DRIVER FAULT OUTPUT 46 15 D4 oi DRIVER EXTERNAL ACCEPT 47 16 D5 oi DRIVER STATUS & DET. OUTPUT S1 48 17 D6 oi DRIVER STATUS & DET. OUTPUT S2 49 D7 oi DRIVER STATUS & DET. OUTPUT S3 50 STATUS & DET. OUTPUT S4 51 STATUS & DET. OUTPUT S5 52 STATUS & DET. OUTPUT S6 53 STATUS & DET. OUTPUT S7 54 STATUS & DET. OUTPUT S8 55 DATA BUS 0 56 DATA BUS 1 57 DATA BUS 2 58 DATA BUS 3 59 DATA BUS 4 60 NOT USED DATA BUS 5 61 DATA STROBE IN NOT USED NOT USED DATA BUS 6 62 DATA BUS 7 63 18 #2 #1 #19 #22 #2 #1 #19 #22 21 22 23 24 25 J1-9 J1-17 26 27 28 #2 #1 #19 #22 #2 #1 #19 #22 29 30 J1-10 J1-18 DETECTOR 7 X3301 1 20 DETECTOR 6 X3301 J1 + 19 DETECTOR 5 X3301 24 VDC 31 32 J2 R7404 STAR LOGIC CONTROLLER D8 oi DRIVER DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT NOT USED EARTH GROUND 64 B2072 #2 #1 #19 #22 #2 #1 #19 #22 J1-11 J1-19 DETECTOR 8 TO J1-2 TERMINAL IDENTIFICATION FOR X3301 WITH PULSE OUTPUT. TERMINAL NO. FUNCTION 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) 62 NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. 63 0.47 µF / 400 VDC NON-POLARIZED 64 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 7—A Typical System, X3301 Detectors Wired to R7404 Star Logic Controller 1.1 9 95-8736 X3301 #2 #1 #19 #22 #2 #1 #19 #22 DETECTOR 1 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-5 J1-13 DETECTOR 2 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-6 J1-14 DETECTOR 3 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J1-7 J1-15 DETECTOR 4 X3301 #2 #1 #19 #22 #2 #1 #19 #22 X3301 #2 #1 #19 #22 J1-8 J1-16 J1-9 J1-17 DETECTOR 6 X3301 1 +24 VDC ZONE OUTPUT 1 33 – 2 CIRCUIT GROUND ZONE OUTPUT 2 34 3 +24 VDC ZONE OUTPUT 3 35 4 B1 - INPUT SIGNAL ZONE OUTPUT 4 36 5 B2 - INPUT SIGNAL ZONE OUTPUT 5 37 6 B3 - INPUT SIGNAL ZONE OUTPUT 6 38 7 B4 - INPUT SIGNAL ZONE OUTPUT 7 39 8 B5 - INPUT SIGNAL ZONE OUTPUT 8 40 9 B6 - INPUT SIGNAL FIRE LOGIC “A” 41 10 B7 - INPUT SIGNAL FIRE LOGIC “B” 42 11 B8 - INPUT SIGNAL ALARM OUTPUT 43 12 D1 oi DRIVER EXTERNAL RESET/INHIBIT 44 13 D2 oi DRIVER OUTPUTS INHIBITED 45 14 D3 oi DRIVER FAULT OUTPUT 46 15 D4 oi DRIVER EXTERNAL ACCEPT 47 16 D5 oi DRIVER STATUS & DET. OUTPUT S1 48 17 #2 #1 #19 #22 #2 #1 #19 #22 J1-10 J1-18 J2 R7494 CONTROLLER D6 oi DRIVER STATUS & DET. OUTPUT S2 49 18 D7 oi DRIVER STATUS & DET. OUTPUT S3 50 19 D8 oi DRIVER STATUS & DET. OUTPUT S4 51 STATUS & DET. OUTPUT S5 52 STATUS & DET. OUTPUT S6 53 STATUS & DET. OUTPUT S7 54 STATUS & DET. OUTPUT S8 55 DATA BUS 0 56 DATA BUS 1 57 DATA BUS 2 58 DATA BUS 3 59 DATA BUS 4 60 61 DATA BUS OUT 21 DATA BUS OUT 22 DATA BUS OUT 23 DATA BUS OUT 24 DATA BUS OUT 25 DATA BUS OUT 26 DATA BUS OUT 27 DATA BUS OUT 28 DETECTOR 7 X3301 J1 + 20 DETECTOR 5 #2 #1 #19 #22 24 VDC NOT USED 29 NOT USED DATA BUS 5 30 DATA STROBE IN NOT USED NOT USED DATA BUS 6 62 DATA BUS 7 63 31 32 EARTH GROUND 64 B2073 #2 #1 #19 #22 #2 #1 #19 #22 J1-11 J1-19 DETECTOR 8 TO J1-2 TERMINAL IDENTIFICATION FOR X3301 WITH PULSE OUTPUT. TERMINAL NO. 1/11 FUNCTION DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. 62 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 64 63 0.47 µF / 400 VDC NON-POLARIZED NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 8—A Typical System, X3301 Detectors Wired to R7494 Controller 1.1 24 VDC X3301 #2 #1 #19 #22 #2 #1 #19 #22 R7495 CONTROLLER (NOT FM APPROVED) J1 + 1 +24 VDC – 2 GROUND 3 DETECTOR 1 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-44 J2-36 4 J2 5 31 32 DETECTOR 2 X3301 #2 #1 #19 #22 #2 #1 #19 #22 #2 #1 #19 #22 #2 #1 #19 #22 33 34 J2-45 J2-37 DETECTOR 3 X3301 J2-46 J2-38 DETECTOR 4 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-47 J2-39 DETECTOR 5 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-48 J2-40 DETECTOR 6 X3301 #2 #1 #19 #22 #2 #1 #19 #22 #2 #1 #19 #22 #2 #1 #19 #22 J2-49 J2-41 DETECTOR 7 X3301 J2-50 J2-42 DETECTOR 8 35 D1 36 D2 37 D3 38 D4 39 D5 40 D6 41 D7 42 D8 43 B1 44 B2 45 B3 46 B4 47 B5 48 B6 49 B7 50 B8 B2074 TO J1-2 TERMINAL IDENTIFICATION FOR X3301 WITH PULSE OUTPUT. TERMINAL NO. FUNCTION 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5. 3 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 4 NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). 0.47 µF / 400 VDC NON-POLARIZED 5 oi ("D" LEAD) GROUND FAULT PROTECTED SYSTEMS Figure 9—A Typical System, X3301 Detectors Wired to R7495 Controller 1.1 11 95-8736 NOTE: DO NOT CONNECT THE X3301 "A" LEAD (#2/12) TO TERMINAL J2-34 (290 VDC). R7405 CONTROLLER (NOT FM APPROVED) X3301 #2 #1 #19 #22 #2 #1 #19 #22 24 VDC J1 + 1 +24 VDC – 2 GROUND 3 DETECTOR 1 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-44 J2-36 4 J2 5 31 32 DETECTOR 2 X3301 #2 #1 #19 #22 #2 #1 #19 #22 33 J2-45 J2-37 DETECTOR 3 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-46 J2-38 DETECTOR 4 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-47 J2-39 DETECTOR 5 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-48 J2-40 34 +290 VDC 35 D1 36 D2 37 D3 38 D4 39 D5 40 D6 41 D7 42 D8 43 B1 44 B2 45 B3 46 B4 47 B5 48 B6 49 B7 50 B8 DETECTOR 6 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-49 J2-41 DETECTOR 7 X3301 #2 #1 #19 #22 #2 #1 #19 #22 J2-50 J2-42 DETECTOR 8 B2075 TO J1-2 TERMINAL IDENTIFICATION FOR X3301 WITH PULSE OUTPUT. TERMINAL NO. FUNCTION 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5. 3 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 4 NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). 0.47 µF / 400 VDC NON-POLARIZED 5 GROUND FAULT PROTECTED SYSTEMS Figure 10—A Typical System, X3301 Detectors Wired to R7405 Controller 1.1 X3301 DETECTOR FIRE ALARM PANEL SHIELD 9 19 8 18 COM FIRE2 7 NO FAULT1 3 + 24 VDC +Vin 2 – –Vin 1 28 27 26 END OF LINE DEVICE 4 15 COM FAULT1 4 29 SPARE 16 NC FIRE2 5 ALARM SPARE 17 NO FIRE2 6 PULSE OUT 25 14 RS485 A 24 13 RS485 B 23 12 MAN Oi 22 –Vin 11 21 oi TEST 3 WIRING NOTES: C2062 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION FOR INSTALLATION DETAILS. 5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE REQUIRED TO FILL ALL CONDUIT ENTRIES. 6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING. Figure 11—Ex d Wiring Option SHIELD X3301 DETECTOR FIRE ALARM PANEL EOL RESISTOR4 9 19 8 18 ALARM 7 ALARM 6 5 4 3 + 24 VDC 2 – 1 COM FIRE2 NO FIRE2 NC FIRE2 COM FAULT1 NO FAULT1 +Vin –Vin PULSE OUT SPARE 29 SPARE 28 17 27 16 26 15 25 14 RS485 A 24 13 RS485 B 23 12 MAN Oi 22 11 –Vin 21 oi TEST 3 B2108 WIRING NOTES: 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 4 EOL RESISTOR SUPPLIED BY PANEL. 5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE REQUIRED TO FILL ALL CONDUIT ENTRIES. 6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING. Figure 12—Ex e Wiring Option 1.1 13 95-8736 EOL Resistors STARTUP PROCEDURE To ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors, observe the following guidelines when installing the resistors. When installation of the equipment is complete, perform one or more of the following tests: 1. • Man oi Test — Tests detector output and wiring, without generating a fire alarm. • Count Test Mode — Measures actual detector output to controller (cps), without generating a fire alarm. • Fire Alarm Test — For complete system test including detector relays. Generates fire alarm output. Required EOL resistor power rating must be 5 watts minimum. NOTE EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. This applies to ATEX/IEC installations only. 2. Resistor leads should be cut to a length of approximately 1 1/2 inches (40 mm). 3. Bend the leads and install the EOL resistor as shown in Figure 13. MANUAL oi TEST (Output to Controller) 1. 2. 3. 3/8 INCH (10 MM) GAP MINIMUM 4. 5. 19 18 17 16 15 14 13 12 11 If the system responds differently than indicated above, proceed with the count test for the problem zone to verify detector and wiring operation. B2126 BULKHEAD COUNT TEST MODE (Output to Controller) Figure 13—EOL Resistor Installation (For Ex d Wiring only) 4. When in the Count Test mode, the frequency of the digital pulses from the detector is displayed on the ZONE and DETECTOR indicators on the controller faceplate. The Count Test mode may be used to check the signal (cps) from a test fire or false alarm source. This can be useful during system set-up for sensitivity and time delay settings. This test is performed in the following manner: Maintain a 3/8 inch (10 mm) minimum gap between the resistor body and the terminal block or any other neighboring parts. NOTE The EOL resistor can only be used within the flameproof terminal compartment. Unused apertures shall be closed with suitable blanking elements. 1. 2. 3. 1.1 Place the keylock switch in the TEST position. Press the SELECT button to display the desired zone on the ZONE indicator on the front panel of the controller. Press and hold the TEST button. The ZONE OUTPUT LED for the tested zone flashes and the SYSTEM STATUS display indicates a “6” (fire condition) if the test is successful. Release the TEST button. The ZONE OUTPUT LED for the tested zone should remain on steadily. Return to step 2 to test the next detector. 14 Place the keylock switch in the TEST position. Simultaneously press and release the SELECT and TEST buttons. The Status display will change from a “1” to an “8” indicating that the controller is in the Count Test mode of operation. Press the SELECT button until the desired zone is displayed on the ZONE indicator on the controller front panel. 95-8736 4. TROUBLESHOOTING Press and hold the TEST button. The DETECTOR/ZONE display indicates the counts per second (cps) received from the detector. If the counts per second exceeds 99, the FIRE LOGIC LEDs are illuminated to indicate that the number shown on the display must be multiplied by 10. The normal reading for an oi test is 80 to 110 cps. For a live fire test, 270 - 330 cps will be generated. WARNING The sensor module (“front” half of the detector) contains no user serviceable components and should never be tampered with. A zero reading may indicate a dirty window, oi problem, faulty detector or defective wiring. 1. Disable any extinguishing equipment that is connected to the unit. 2. Inspect the viewing windows for contamination and clean as necessary. The detector is relatively insensitive to airborne contaminants, however, thick deposits of ice, dirt, or oil will reduce sensitivity. (Refer to the “Maintenance” section for complete information regarding cleaning of the detector viewing windows.) Release the Test button, the ZONE and DETECTOR display should drop to a reading of 0 to 1 counts per second. FIRE ALARM TEST (Pulse Output to Fire Alarm Panel) 1. Disable any extinguishing equipment that is connected to the system. 3. Check input power to the unit. 4. Check system and detector logs. 2. Apply input power to the system. 5. 3. Initiate a live fire test or a Mag oi test (see “Magnetic oi / Manual oi” under “Optical Integrity” in the Description section of this manual). Turn off the input power to the detector and check all wiring for continuity. Important: Disconnect wiring at the detector before checking system wiring for continuity. 6. If all wiring checks out and cleaning of the oi plate/window did not correct the fault condition, check for high levels of background IR radiation by covering the detector with the factory supplied cover or aluminum foil. If the fault condition clears within 6 minutes or less, extreme background IR is present. Re-adjust the view of the detector away from the IR source or relocate the detector. 4. Repeat this test for all detectors in the system. If a unit fails the test, refer to the “Troubleshooting” section. 5. Verify that all detectors in the system are properly aimed at the area to be protected. (The Q1201C Laser Aimer is recommended for this purpose.) 6. Enable extinguishing equipment when the test is complete. If these actions do not correct the problem, return the detector to the factory for repair. NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. NOTE For additional troubleshooting guides, refer to the Flame Inspector Monitor manual (95-8581). 1.1 15 95-8736 MAINTENANCE LOOSEN TWO CAPTIVE SCREWS IMPORTANT Periodic flamepath inspections are not recommended, since the product is not intended to be serviced and provides proper ingress protection to eliminate potential deterioration of the flamepaths. GRASP VISOR AND REMOVE oi PLATE WARNING The sensor module (“front” half of the detector) contains no user serviceable c o m p o n e n t s a n d s h o u l d n ev e r b e tampered with. B2106 oi Plate Removal Figure 14— To maintain maximum sensitivity and false alarm resistance, the viewing windows of the X3301 must be kept relatively clean. Refer to the following procedure for cleaning instructions. IMPORTANT When used in extreme environments, the reflective surface of the detector oi plate may eventually deteriorate, resulting in reoccurring oi faults and the need for oi plate replacement. CLEANING PROCEDURE CAUTION Disable any extinguishing equipment that is connected to the unit to prevent unwanted actuation. oi PLATE REMOVAL AND REPLACEMENT To clean the windows and oi plate, use the window cleaner (p/n 001680-001) and a soft cloth, cotton swab, or tissue and refer to the following procedure: 1. Disable any extinguishing equipment that is connected to the unit. 1.1 Disable any extinguishing equipment that is connected to the unit. 2. Loosen the two captive screws, then grasp the oi plate by the visor and remove it from the detector. See Figure 14. 3. Install the new (or cleaned) oi plate. NOTE When installing the stainless steel plate, ensure that the gasket is present and correctly seated to prevent moisture or contaminants from penetrating behind the plate. To ensure even seating, tighten both screws equally. 2. Since the X3301 is less affected by contamination than other detectors, removal of the oi plate is needed only under extreme conditions. In addition, it is not necessary to achieve perfect cleanliness, because IR is not significantly absorbed by slight films of oil and/or salt. If a fault condition is still indicated after cleaning, remove and clean the oi plate using the oi Plate Removal and Replacement procedure. 3. 1. 4. In all environments, clean all three viewing windows and reflector surfaces thoroughly. Use a cotton swab and the Det-Tronics window cleaning solution. Use Isopropyl alcohol for contaminations that the DetTronics window cleaning solution can not remove. Recalibrate the detector’s oi system. Refer to the Inspector Monitor Manual (95-8581) for instructions regarding oi plate replacement and oi system recalibration. CAUTION Do not replace the o i reflector plate without also recalibrating the oi system. Recalibration of the oi system requires the use of the Inspector Connector Cable and Inspector Monitor Software. These two items are included in the oi replacement kit, or they can be purchased separately. See Ordering Information for details. 16 95-8736 • Class A wiring per NFPA-72 (Pulse output version is equivalent to class A when detectors are installed in a redundant configuration) • 5 year warranty X3301 Reflector Plates X3301 models are supplied with either a black or a stainless steel reflector plate. These plates are not interchangeable. Order the replacement that matches the reflector plate on your X3301 Flame Detector. • RFI and EMC Directive compliant SPECIFICATIONS PERIODIC CHECKOUT PROCEDURE OPERATING VOLTAGE— 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). Maximum ripple is 2 volts peak-to-peak. A checkout of the system using the Mag oi or Man oi feature should be performed on a regularly scheduled basis to ensure that the system is operating properly. To test the system, perform the “Manual oi Test,” “Count Test Mode” or “Fire Alarm Test” as described in the “Startup Procedure” section of this manual. For CSA compliance, the power source must utilize a SELV (Safety Extra Low Voltage) or Class 2 style power supply. CLOCK BATTERY POWER CONSUMPTION— Without heater: 4 watts at 24 Vdc nominal; 5.2 watts at 24 Vdc in alarm. 4.5 watts at 30 Vdc nominal; 6.5 watts at 30 Vdc in alarm. Heater only: 8 watts maximum. Total power: 17 watts at 30 Vdc with EOL resistor installed and heater on maximum. EOL resistor must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. The real time clock has a backup battery that will operate the clock with no external power. Return the device to the factory for battery replacement if needed. NOTE If the backup battery is depleted, there is no effect on the operation of the flame detector, but the time stamping of the data log may be affected. FEATURES POWER UP TIME— Fault indication clears after 0.5 second; device is ready to indicate an alarm condition after 30 seconds. • Long detection range to carbonaceous fires • Unequaled false alarm rejection • Responds to a fire in the presence of modulated blackbody radiation (i.e. heaters, ovens, turbines) without false alarm • Pulse output for compatibility with controller based systems • Microprocessor controlled heated optics for increased resistance to moisture and ice • Automatic, manual or magnetic oi testing • Easily replaceable oi plate • Fire and fault relays • Multiple sensitivity levels • A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions • Operates under adverse weather conditions and in dirty environments. • Mounting arm allows easy sighting • Integral wiring compartment for ease of installation • Explosion-proof/flame-proof detector housing. Meets FM, CSA, ATEX, IECEx Directive and CE certification requirements 1.1 OUTPUT RELAYS— Fire Alarm relay, Form C, 5 amperes at 30 Vdc: The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. Fault relay, Form A, 5 amperes at 30 Vdc: The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. TEMPERATURE RANGE— Operating: –40°C to +75°C (–40°F to +167°F). Storage: –55°C to +85°C (–67°F to +185°F). Hazardous location ratings from –55°C to +125°C. HUMIDITY RANGE— 0 to 95% relative humidity, can withstand 100% condensing humidity for short periods of time. 17 95-8736 CONE OF VISION— The detector has a 90° cone of vision (horizontal) with the highest sensitivity lying along the central axis. Unlike conventional detectors, the X3301 provides full coverage at a minimum of 70% of the maximum detection distance. SHIPPING WEIGHT (Approximate)— Aluminum: 7 pounds (3.2 kilograms). Stainless Steel: 13.8 pounds (6.3 kilograms). Mounting Arm (AL): 6 pounds (2.75 kilograms). Mounting Arm (SS): 14 pounds (6.4 kilograms). WARRANTY PERIOD— 5 years. Perfect cone of vision for methane fire detection — 100 feet (30.5 m) on and off axis on “very high” setting. CERTIFICATION— Refer to Appendix A for FM Approved cone of vision data. ® RESPONSE TIME— Typical response times are under 10 seconds. See Appendix A for actual response times. VdS DIMENSIONS— See Figure 15. For complete approval details, refer to the appropriate Appendix: ENCLOSURE MATERIAL— Copper-free aluminum (painted) or Stainless Steel (316/CF8M Cast). Appendix A - FM Appendix B - CSA Appendix C - ATEX Appendix D - IECEx Appendix E - EN54 Appendix F - Additional approvals VIBRATION— Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW). WIRING— Field wiring screw terminals are UL/CSA rated for up to 14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire. Screw terminal required torque range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m). Important: 18 Vdc minimum must be available at the detector. For ambient temperatures below –10°C (14°F) and above +60°C (140°F) use field wiring suitable for both minimum and maximum ambient temperature. THREAD SIZE— Conduit connection: Four entries, 3/4 inch NPT or M25. Conduit seal not required. 4.7 (11.9) B2067 10.0 (25.4) 4.8 (12.2) Figure 15—X3301 Dimensions in Inches (cm) 1.1 18 95-8736 REPLACEMENT PARTS ORDERING INFORMATION The detector is not designed to be repaired in the field. If a problem should develop, refer to the Troubleshooting section. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair. When ordering, please specify: X3301 Multispectrum IR Flame Detector with Pulse Output Refer to the X3301 Model Matrix for details Q9033 Mounting Arm is required: –– Q9033A for aluminum detectors only –– Q9033B for aluminum and stainless steel detectors REPLACEMENT PARTS LIST Part Number 009208-001 010831-001 007307-001 010830-001 Description oi Replacement kit for X3301 (5 Black Reflector Plates) with Inspector Connector and Monitor oi Replacement kit for X3301 (5 Stainless Steel Reflector Plates) with Inspector Connector and Monitor Replacement oi Reflector Plates for X3301 with Black plate (requires Inspector Connector to calibrate) Replacement oi Reflector Plates for X3301 with Stainless Steel plate (requires Inspector Connector to calibrate) ACCESSORIES NOTE: Refer to instruction manual 95-8530 to determine the correct oi Replacement Plate. Part Number Description 000511-029 103881-001 Converter RS485 to RS232 Converter RS485 to USB W6300B1002 Serial Inspector Connector (Inspector Monitor software included) 007819-001 007819-002 009207-001 103922-001 102740-002 008082-001 007739-001 007240-001 007818-001 DEVICE REPAIR AND RETURN Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure. 007818-002 009177-001 010857-001 006097-001 102871-001 007255-001 007338-001 007338-010 007338-020 007338-030 007912-010 007912-020 007912-030 Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge. NOTE Det-Tronics reserves the right to apply a service charge for repairing returned product damaged as a result of improper packaging. 007290-001 NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. 1.1 19 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors 011385-001 101197-001 101197-004 101197-005 101197-003 010816-001 010817-001 010818-001 010819-001 103363-001 103406-001 001680-001 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment Stop Plug, 3/4” NPT, AL Stop Plug, 3/4” NPT, SS Stop Plug, M25, AL, IP66 Stop Plug, M25, SS, IP66 Stop Plug, 20 Pack, 3/4”NPT, AL Stop Plug, 20 Pack, 3/4”NPT, SS Stop Plug, 20 Pack, M25, AL, IP66 Stop Plug, 20 Pack, M25, SS, IP66 14 mm Hex Wrench (Steel) Screwdriver Window cleaner (6 pack) 107427-040 005003-001 O-ring - Rear Cover (Viton) - black 1 oz grease for detectors (silicone-free) 104346-154 012549-001 O-ring - Rear Cover (Fluorosilicone) - blue 1 oz PTFE silicone-free lubricant 007290-002 Return all equipment transportation prepaid to the factory in Minneapolis. W6300B1003 USB Inspector Connector (Inspector Monitor software included) Flame Inspector Monitor CD Model 475 HART Communicator Magnet Magnet and Adapter for Extension Pole Magnet and Extension Pole Q1116A1001, Air Shield (AL) Q1118A1001 Aluminum Air Shield/Flange Mount (AL) Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS) Q1120A1001 Paint Shield mounting ring (AL) Q1130A1001 Flange Mount Assembly Q1201 Laser Laser Battery, 3V Lithium (laser) Q1201C1001 X-Series Laser Holder (AL/Plastic) Q2000A1001 X-Series Weather Shield (AL) Q2033A10R X3301/X3302 FOV Limiter 10° (AL) Q2033A20R X3301/X3302 FOV Limiter 20° (AL) Q2033A30R X3301/X3302 FOV Limiter 30° (AL) Spare Restrictor Plate 10° (AL) Spare Restrictor Plate 20° (AL) Spare Restrictor Plate 30° (AL) 95-8736 X3301 MODEL MATRIX MODEL X3301 DESCRIPTION Multispectrum IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT TYPE 15 OUTPUTS Relay and Pulse TYPE APPROVALS B INMETRO (Brazil) W FM/CSA/ATEX/IECEx TYPE 1.1 20 CLASSIFICATION 1 Division/Zone Ex d e 2 Division/Zone Ex d 95-8736 HIGH RESOLUTION FIELD OF VIEW DIAGRAMS 0° 15° 265 (80.7) 30° 0° 15° 70 (21.3) 15° 30° 240 (73.1) 45° 30° 45° 200 (60.9) 40 (12.2) 30 (9.1) 80 (24.3) 20 (6.1) 40 (12.1) 10 (3.0) 10 (3.0) 30° 20 (6.1) 30° 30 (9.1) 120 (36.8) 15° 160 (48.7) 200 (60.9) 15° 30° 45° 50 (15.2) 30° 0° 15° 100 (30.5) 15° 90 (27.4) 80 (24.4) 70 (21.3) 60 (18.3) 50 (15.2) 40 (12.2) 30 (9.1) 20 (6.1) 10 (3.0) 70 (21.3) 45° 30° 30° 45° 45° 20 (6.1) 40 (12.1) 60 (18.2) 80 (24.3) 100 (30.4) 120 (36.5) 140 (42.6) 160 (48.7) 175 (53.3) 45° 15° 0° 15° 15° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for Isopropanol at Very High Sensitivity (6 in. x 6 in.) 30° 30° 0° 60 (18.3) DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for n-Heptane at Very High Sensitivity (1 x 1 foot) 45° 15° 40 (12.2) 0° 240 (73.1) 265 (80.7) DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. 0° 15° 175 (53.3) 15° 160 (48.7) 140 (42.6) 120 (36.5) 100 (30.4) 80 (24.3) 60 (18.2) 40 (12.1) 20 (6.1) 30° 45° 30° 15° 0° 15° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for Diesel at Very High Sensitivity (1 x 1 foot) Field of View at Indicated Distance in Feet (m) for n-Heptane at Very High Sensitivity (6 in. x 6 in.) 1.1 45° 50 (15.2) 120 (36.8) 40 (12.1) 45° 30° 60 (18.3) 45° 160 (48.7) 80 (24.3) 10 (3.0) 20 (6.1) 30 (9.1) 40 (12.2) 50 (15.2) 60 (18.3) 70 (21.3) 80 (24.4) 90 (27.4) 100 (30.5) 15° 21 95-8736 High Resolution Field of View Diagrams – Continued 0° 15° 125 (38.1) 15° 120 (36.6) 105 (32) 90 (27.4) 75 (22.9) 60 (18.3) 45 (13.7) 30 (9.1) 15 (4.6) 30° 45° 15 (4.6) 30 (9.1) 45 (13.7) 60 (18.3) 75 (22.9) 90 (27.4) 105 (32) 120 (36.6) 125 (38.1) 45° 30° 30° 45° 15 (4.6) 10 (3) 5 (1.5) 5 (1.5) 10 (3) 20 (6.1) 15° 25 (7.6) 30 (9.1) DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. 0° 210 (64) 0° 35 (10.7) 40 (12.2) 45° 30° 30° 45° 45° 150 (45.7) 120 (36.5) 90 (27.4) 60 (18.3) 30 (9.1) 30 (9.1) 15 (4.6) 30 (9.1) 45 (13.7) 60 (18.3) 75 (22.9) 90 (27.4) 105 (32) 120 (36.5) 135 (41.2 150 (45.7) 30° 60 (18.3) 90 (27.4) 15° 120 (36.5) 150 (45.7) 0° 180 (54.9) 210 (64) 45° 15° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for Ethanol at Very High Sensitivity (1 x 1 foot) 1.1 15° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for Methanol at Very High Sensitivity (6 in. x 6 in.) 15° 180 (54.9) 45° 30° 15 (4.6) Field of View at Indicated Distance in Feet (m) for Propane at Very High Sensitivity (32 inch plume) 15° 45° 20 (6.1) 0° 30° 30° 30 (9.1) 25 (7.6) 15° 30° 15° 35 (10.7) 45° 30° 15° 0° 15° 40 (12.2) 0° 15° 150 (45.7) 15° 135 (41.2 120 (36.5) 105 (32) 90 (27.4) 75 (22.9) 60 (18.3) 45 (13.7) 30 (9.1) 15 (4.6) 30° 45° 30° 15° 0° 15° 45° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for Methanol at Very High Sensitivity (1 x 1 foot) 22 95-8736 High Resolution Field of View Diagrams – Continued 15° 30° 45° 10 (3) 20 (6.1) 30 (9.1) 40 (12.2) 50 (15.2) 60 (18.3) 70 (21.3) 80 (24.4) 90 (27.4) 100 (30.5) 125 (38.1) 45° 0° 15° 125 (38.1) 100 (30.5) 90 (27.4) 80 (24.4) 70 (21.3) 60 (18.3) 50 (15.2) 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) 0° 15° 30° 30° 45° 15° 30° 210 (64) 180 (54.9) 45° 45° 150 (45.7) 120 (36.5) 90 (27.4) 60 (18.3) 30 (9.1) 30 (9.1) 60 (18.3) 30° 30° 90 (27.4) 15° 120 (36.5) 15° 150 (45.7) 0° 15° 30° 0° 180 (54.9) DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. 210 (64.0) 235 (71.6) 45° Field of View at Indicated Distance in Feet (m) for Methane at Very High Sensitivity (32 inch plume) 1.1 235 (71.6) 15° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for JP-5 at Very High Sensitivity (2 x 2 feet) 23 95-8736 High Resolution Field of View Diagrams – Continued 30° 45° 0° 15° 100 (30.5) 15° 90 (27.4) 80 (24.4) 70 (21.3) 60 (18.3) 50 (15.2) 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) 30° 30° 45° 0° 15° 70 (21.3) 45° 45° 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) Field of View at Indicated Distance in Feet (m) for Methanol at Medium Sensitivity (1 x 1 foot) 15° 30° 30° 45° 50 (15.2) 45° 0° 70 (21.3) 15° 60 (18.3) 30° 45° 50 (15.2) 40 (12.2) 40 (12.2) 30 (9.1) 30 (9.1) 20 (6.1) 20 (6.1) 10 (3) 10 (3) Field of View at Indicated Distance in Feet (m) for Diesel at Medium Sensitivity (1 x 1 foot) Field of View at Indicated Distance in Feet (m) for Methane at Medium Sensitivity (32 inch plume) 30° 45° 0° 15° 85 (25.9) 80 (24.4) 75 (22.9) 65 (19.8) 55 (16.8) 45 (13.7) 35 (10.7) 25 (7.6) 15 (4.6) 5 (1.5) 15° 30° 30° 45° 45° Field of View at Indicated Distance in Feet (m) for Ethanol at Medium Sensitivity (1 x 1 foot) 15° 30° 45° 30° 50 (15.2) 15° 60 (18.3) 15° 60 (18.3) 45° Field of View at Indicated Distance in Feet (m) for n-Heptane at Medium Sensitivity (1 x 1 foot) 30° 0° 15° 70 (21.3) 0° 75 (22.8) 70 (21.3) 0° 15° 150 (45.7) 15° 135 (41.2 120 (36.5) 105 (32) 90 (27.4) 75 (22.9) 60 (18.3) 45 (13.7) 30 (9.1) 15 (4.6) 30° 45° Field of View at Indicated Distance in Feet (m) for JP-5 at Medium Sensitivity (2 x 2 feet) 15° 30° 60 (18.3) 50 (15.2) 45° 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) Field of View at Indicated Distance in Feet (m) for Propane at Medium Sensitivity (32 inch plume) 1.1 24 95-8736 APPENDIX A FM APPROVAL AND PERFORMANCE REPORT THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL: • Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615. • Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615. • Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611. • Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611. • Enclosure rating NEMA/Type 4X per NEMA 250. • Ambient Temperature Limits: –40°C to +75°C (–40°F to +167°F). • Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000). Flameproof per ANSI/ISA 60079-0, -1, -7, -31 for Class I, Zone 1 AEx d e IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C) AEx d IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C) for Zone 21 AEx tb T130°C Db Tamb –40°C to +75°C Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S. The following accessories are FM approved for use with the X3301 Flame Detector: Part Number 102740-002 007739-001 010857-001 007290-001 007290-002 011385-001 Description Magnet Magnet and Extension Pole Q1130A1001 Flange Mount Assembly Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment The following performance criteria were verified: AUTOMATIC OPTICAL INTEGRITY TEST: The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector was verified to detect a fire. MANUAL OPTICAL INTEGRITY TEST: The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated. The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual, is the approved external optical test method for this detector to verify end-to-end detector function. This test replaces the function and need of a traditional external test lamp. 1.1 25 95-8736 FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS Very High Sensitivity Fuel n-Heptane Gasoline Kerosene Isopropanol Diesel Ethanol Methanol Xylene Toluene Methane Propane Ethane Ethylene Butane Jet A JP-5 JP-8 Class A Size Distance feet (m) Average Response Time (seconds) 1 x 1 foot 1 x 1 foot 1 x 1 foot 6 in. x 6 in. 1 x 1 foot 1 x 1 foot 6 in. x 6 in. 1 x 1 foot 1 x 1 foot 6 in. x 6 in. 1 x 1 foot 1 x 1 foot 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume 32 inch plume 32 inch plume 32 inch plume 1 x 1 foot 2 x 2 feet 1 x 1 foot Ø12 in. x 7 in. 265 (80.7)* 250 (76.2) 100 (30.5) 100 (30.5) 250 (76.2) 150 (45.7) 70 (21.3) 175 (53.3) 210 (64.0) 40 (12.2) 150 (45.7) 150 (45.7) 200 (60.9) 200 (60.9) 125 (38.1) 125 (38.1) 125 (38.1) 125 (38.1) 125 (38.1) 150 (45.7) 235 (71.6) 150 (45.7) 150 (45.7) 22 17 3 7 6 7** 6 6** 11 3 7 5** 8** 7** 5 5 5 8 5 4** 3** 5** 3** Size Distance feet (m) Average Response Time (seconds) 1 x 1 foot 1 x 1 foot 6 in. x 6 in. 1 x 1 foot 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume 32 inch plume 32 inch plume 32 inch plume 32 inch plume 2 x 2 feet Ø12 in. x 7 in. 100 (30.5) 50 (15.24) 45 (13.72) 70 (21.3) 85 (25.9) 70 (21.3) 70 (21.3) 55 (16.7) 75 (22.8) 75 (22.8) 75 (22.8) 75 (22.8) 150 (45.7) 50 (15.24) 7 <2 7 4** 7 6 6 4 <5 5 6 4 3** 4** * Outdoor test condition ** Pre-burn from ignition Ø Diameter Medium Sensitivity Fuel n-Heptane Isopropanol Diesel Ethanol Methanol Methane Propane Ethane Ethylene Butane JP-5 Class A ** Ø 1.1 Pre-burn from ignition Diameter 26 95-8736 FM Approval and Performance Report – Continued T-Low Sensitivity Fuel Size Distance feet (m) Average Response Time (seconds) n-Heptane Methanol Methane Propane 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume 50 (15.24) 30 (9.14) 30 (9.14) 30 (9.14) <4 5 3 5 Fuel Size Distance feet (m) Average Response Time (seconds) n-Heptane Methanol Methane Propane 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume 50 (15.24) 30 (9.14) 30 (9.14) 30 (9.14) <10 10 10 9 Low Sensitivity 1.1 27 95-8736 FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES Very High Sensitivity Sunlight, direct, modulated, reflected Sunlight, direct, unmodulated, reflected Radio frequency interference Distance feet (m) — — 1 (0.3) 6-inch propane 6-inch propane 3-inch propane Arc welding, #7014 40 (12.2) 1 x 1 foot n-Heptane LED Lamp, modulated LED Lamp, unmodulated 70 w sodium vapor lamp, modulated 70 w sodium vapor lamp, unmodulated 250 w vapor lamp, modulated 250 w vapor lamp, unmodulated 300 w incandescent lamp, modulated 300 w incandescent lamp, unmodulated 500 w shielded quartz halogen lamp, modulated 500 w shielded quartz halogen lamp, unmodulated 500 w unshielded quartz halogen lamp, modulated 500 w unshielded quartz halogen lamp, unmodulated 1500 w electric radiant heater, modulated 1500 w electric radiant heater, unmodulated Two 34 w fluorescent lamps, modulated Two 34 w fluorescent lamps, unmodulated 5 (1.5) 5 (1.5) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 8 (2.4) 8 (2.4) 8 (2.4) 8 (2.4) 10 (3.0) 10 (3.0) 3 (0.9) 3 (0.9) 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane False Alarm Source Fire Source Distance Average Response Time feet (m) (seconds) 6 (1.8) 12 6 (1.8) 2 12 (3.7) <10 3 unmodulated / 40 (12.2) 2 modulated 6 210 (64) 210 (64) 7 80 (24.4) 3 80 (24.4) 3 80 (24.4) 4 80 (24.4) 3 80 (24.4) 9 80 (24.4) 3 80 (24.4) 4 80 (24.4) 3 80 (24.4) 3 80 (24.4) 3 80 (24.4) 3 80 (24.4) 3 80 (24.4) 3 80 (24.4) 3 Medium Sensitivity Distance feet (m) Sunlight, direct, modulated, reflected — Sunlight, direct, unmodulated, reflected — Radio frequency interference 1 (0.3) Arc welding, #7014 15 (4.57) LED Lamp, modulated 3 (0.9) LED Lamp, unmodulated 3 (0.9) 70 w sodium vapor lamp, unmodulated 3 (0.9) 250 w vapor lamp, modulated 3 (0.9) 250 w vapor lamp, unmodulated 3 (0.9) 300 w incandescent lamp, modulated 3 (0.9) 300 w incandescent lamp, unmodulated 3 (0.9) 500 w shielded quartz halogen lamp, modulated 8 (2.4) 500 w shielded quartz halogen lamp, unmodulated 8 (2.4) 500 w unshielded quartz halogen lamp, modulated 8 (2.4) 500 w unshielded quartz halogen lamp, unmodulated 8 (2.4) 1500 w electric radiant heater, modulated 10 (3.0) 1500 w electric radiant heater, unmodulated 10 (3.0) Two 34 w fluorescent lamps, modulated 3 (0.9) Two 34 w fluorescent lamps, unmodulated 3 (0.9) False Alarm Source 1.1 28 Fire Source 6-inch propane 6-inch propane 6-inch propane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane Distance Average Response Time feet (m) (seconds) 6 (1.8) 9 6 (1.8) 5 6 (1.8) <1 40 (12.2) 2 modulated 9 100 (30.5) 100 (30.5) 7 60 (18.3) 3 60 (18.3) 3 60 (18.3) 4 60 (18.3) 9 60 (18.3) 4 60 (18.3) 6 60 (18.3) 4 60 (18.3) 5 60 (18.3) 4 60 (18.3) 6 60 (18.3) 4 60 (18.3) 4 60 (18.3) 4 95-8736 FM Approval and Performance Report – Continued T-Low Sensitivity False Alarm Source Sunlight, direct, unmodulated, reflected* Sunlight, direct, modulated, reflected* Arc welding, modulated, #7014 LED Lamp, modulated LED Lamp, unmodulated 70 w sodium vapor, unmodulated 70 w sodium vapor, modulated 250 w vapor lamp, unmodulated 250 w vapor lamp, modulated 300 w incandescent lamp, unmodulated 300 w incandescent lamp, modulated 500 w shielded quartz halogen lamp, unmodulated 500 w shielded quartz halogen lamp, modulated 1500 w electric radiant heater, unmodulated 1500 w electric radiant heater, modulated Two 34 w fluorescent lamps, unmodulated Two 34 w fluorescent lamps, modulated Distance feet (m) — — 8 (2.4) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 10 (3.0) 3 (0.9) 10 (3.0) 3 (0.9) 3 (0.9) Fire Source 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane Distance feet (m) 35 (10.7) 15 (4.6) 30 (9.1) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) Average Response Time (seconds) 9 8 3 2 3 4 5 6 5 4 6 5 5 3 5 2 6 Distance feet (m) 35 (10.7) 15 (4.6) 30 (9.1) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24) Average Response Time (seconds) 12 19 10 9 12 11 11 11 10 10 8 12 10 * Outdoor test conditions Low Sensitivity False Alarm Source Sunlight, direct, unmodulated, reflected* Sunlight, direct, modulated, reflected* Arc welding, modulated, #7014 LED Lamp, modulated LED Lamp, unmodulated 70 w sodium vapor, modulated 250 w vapor lamp, modulated 300 w incandescent lamp, modulated 500 w shielded quartz halogen lamp, unmodulated 500 w shielded quartz halogen lamp, modulated 1500 w electric radiant heater, unmodulated 1500 w electric radiant heater, modulated Two 34 w fluorescent lamps, modulated Distance feet (m) — — 5 (1.5) 3 (0.9) 3 (0.9) 3 (0.9) 5 (1.5) 5 (1.5) 3 (0.9) 10 (3.0) 3 (0.9) 10 (3.0) 3 (0.9) Fire Source 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane 1 x 1 foot n-Heptane * Outdoor test conditions 1.1 29 95-8736 FM Approval and Performance Report – Continued FALSE ALARM IMMUNITY Very High Sensitivity False Alarm Source Sunlight, direct, reflected Vibration Radio frequency interference Arc welding LED Lamp 70 w sodium vapor lamp 250 w vapor lamp 300 w incandescent lamp 500 w unshielded quartz halogen lamp 500 w shielded quartz halogen lamp 1500 w electric radiant heater Two 34 w fluorescent lamps Distance feet (m) — N/A 1 (0.3) 40 (12.2) 5 (1.5) 3 (0.9) 3 (0.9) 3 (0.9) 8 (2.4) 8 (2.4) 3 (0.9) 5 (1.5) Modulated Response Unmodulated Response No alarm No alarm No alarm (keyed) No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm N/A No alarm (steady) No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm Modulated Response Unmodulated Response No alarm No alarm No alarm (keyed) No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm N/A No alarm (steady) No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm Modulated Response Unmodulated Response No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm Medium Sensitivity False Alarm Source Sunlight, direct, reflected Vibration Radio frequency interference Arc welding LED Lamp 70 w sodium vapor lamp 250 w vapor lamp 300 w incandescent lamp 500 w unshielded quartz halogen lamp 500 w shielded quartz halogen lamp 1500 w electric radiant heater Two 34 w fluorescent lamps Distance feet (m) — N/A 1 (0.3) 10 (3) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) T-Low Sensitivity False Alarm Source Sunlight, direct, reflected Vibration Arc welding LED Lamp 70 w sodium vapor 250 w vapor lamp 300 w incandescent lamp 500 w shielded quartz halogen lamp 500 w unshielded quartz halogen lamp 1500 w electric radiant heater Two 34 w fluorescent lamps 1.1 Distance feet (m) — N/A 5 (1.5) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 30 95-8736 FM Approval and Performance Report – Continued Low Sensitivity False Alarm Source Sunlight, direct, reflected Vibration Radio frequency interference Arc welding LED Lamp 70 w sodium vapor lamp 250 w vapor lamp 300 w incandescent lamp 500 w shielded quartz halogen lamp 500 w unshielded quartz halogen lamp 1500 w electric radiant heater Two 34 w fluorescent lamps Distance feet (m) — N/A — 5 (1.5) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) 3 (0.9) Modulated Response No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm Unmodulated Response No alarm No alarm N/A No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm No alarm FIELD OF VIEW Very High Sensitivity Fuel n-Heptane Gasoline Kerosene Isopropanol Diesel Ethanol Methanol Xylene Toluene Methane Propane Ethane Ethylene Butane Jet A JP-5 JP-8 Class A Size 1 x 1 foot 1 x 1 foot 1 x 1 foot 1 x 1 foot 6 x 6 inches 1 x 1 foot 1 x 1 foot 6 x 6 inches 1 x 1 foot 1 x 1 foot 6 x 6 inches 1 x 1 foot 1 x 1 foot 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume 32 inch plume 32 inch plume 32 inch plume 1 x 1 foot 2 x 2 feet 1 x 1 foot Ø12 in. x 7 in. Distance Horizontal feet (m) L, R (°) 190 (57.9) +/– 45 180 (54.9) +/– 45 180 (54.9) +/– 45 100 (30.5) +/– 45 100 (30.5) +/– 45 190 (57.9) +/– 45 110 (33.5) +/– 45 70 (21.3) +/– 45 150 (45.7) +/– 45 150 (45.7) +/– 45 40 (12.2) +/– 45 110 (33.5) +/– 45 110 (33.5) +/– 45 150 (45.7) +/– 45 150 (45.7) +/– 45 100 (30.5) +/– 45 90 (27.4) +/– 45 90 (27.4) +/– 45 90 (27.4) +/– 45 90 (27.4) +/– 45 100 (30.5) +/– 45 180 (54.9) +/– 45 100 (30.5) +/– 45 80 (24.4) +/– 45 Avg. Resp Time (s) 11 8 6** 4 11 7 5 8 10** 15 3 8 8** 7** 8** 7 7 5 7 5 4** 6** 5** 4** Vertical Down (°) +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 +45 Avg. Resp Time (s) 11 11 6** 3 11 9 5 6 7** 13 3 13 4** 6** 8** 8 9 6 9 4 3** 4** 5** 2** Vertical Up (°) –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 Avg. Resp Time (s) 8 3 3** 2 7 5 4 5 7** 10 2 3 3** 3** 4** 4 5 3 5 2 2** 2** 3** 2** * Outdoor test condition ** Pre-burn from ignition Ø Diameter 1.1 31 95-8736 FM Approval and Performance Report – Continued Medium Sensitivity Fuel Size 1 x 1 foot 1 x 1 foot 6 x 6 inches 1 x 1 foot 1 x 1 foot 1 x 1 foot 32 inch plume 2 x 2 feet 32 inch plume 32 inch plume 32 inch plume 32 inch plume Ø12 in. x 7 in. n-Heptane Isopropanol Diesel Ethanol Methanol Methane JP-5 Propane Ethane Ethylene Butane Class A Distance Horizontal Avg. Resp Vertical feet (m) L, R (°) Time (s) Down (°) 75 (22.9) +/– 45 5 +45 50 (15.2) +/– 45 3 +45 45 (13.7) +/– 45 11 +45 60 (18.2) +/– 45 4** +45 60 (18.2) +/– 45 7 +45 50 (15.2) +/– 45 5 +45 50 (15.2) +/– 45 5 +45 110 (33.5) +/– 45 7 +45 55 (16.7) +/– 45 5 +45 55 (16.7) +/– 45 6 +45 55 (16.7) +/– 45 7 +45 55 (16.7) +/– 45 6** +45 40 (12.2) +/– 45 3** +45 Avg. Resp Time (s) 4 2 8 6** 8 2 6 4 4 5 5 4** 3** Vertical Up (°) –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 –30 Avg. Resp Time (s) 5 3 6 4** 5 6 3 5 5 5 5 3** 3** ** Pre-burn from ignition Ø Diameter T-Low Sensitivity Fuel Size n-Heptane Methanol Methane Propane 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume Distance feet (m) 35 (10.7) 20 (6.1) 20 (6.1) 20 (6.1) Horizontal L, R (°) +/– 45 +/– 45 +/– 45 +/– 45 Avg. Resp Time (s) 4 4 4 4 Vertical Down (°) +45 +45 +45 +45 Avg. Resp Time (s) 4 4 4 4 Vertical Up (°) –30 –30 –30 –30 Avg. Resp Time (s) 3 2 4 5 Distance feet (m) 35 (10.7) 20 (6.1) 20 (6.1) 20 (6.1) Horizontal L, R (°) +/– 45 +/– 45 +/– 45 +/– 45 Avg. Resp Time (s) 8 9 9 9 Vertical Down (°) +45 +45 +45 +45 Avg. Resp Time (s) 9 9 9 9 Vertical Up (°) –30 –30 –30 –30 Avg. Resp Time (s) 10 9 8 11 Low Sensitivity Fuel Size n-Heptane Methanol Methane Propane 1 x 1 foot 1 x 1 foot 32 inch plume 32 inch plume 1.1 32 95-8736 APPENDIX B CSA APPROVAL Multispectrum IR Flame Detector/Controller X3301 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts. Relay contacts rated 30 Vdc, 5 Amps. NOTE Hazardous location testing has been successfully completed on the Model X3301 series from an ambient temperature range of –55°C to +125°C; however, the detector label marking indicates –40°C to +75°C. The following accessories are CSA approved for use with the X3301 Flame Detector: Part Number 102740-002 007739-001 010857-001 007290-001 007290-002 011385-001 Description Magnet Magnet and Extension Pole Q1130A1001 Flange Mount Assembly Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment DIVISION CLASSIFICATION: CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A); Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C); Class III; Enclosure NEMA/Type 4X; Conduit seal not required. APPLICABLE REQUIREMENTS CAN/CSA-C22.2 No. 0-M91 – General Requirements — Canadian Electrical Code, Part II CAN/CSA Std C22.2 No. 25-1966 – Enclosures for use in Class II Groups E, F & G Hazardous Locations CAN/CSA-C22.2 No. 30-M1986 – Explosion-Proof Enclosures for use in Class I Hazardous Locations CAN/CSA-C22.2 No. 94-M91 – Special Purpose Enclosures CAN/CSA-C22.2 No. 142-M1987 – Process Control Equipment CAN/CSA-C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations ZONE CLASSIFICATION: CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Ex d e IIC T5-T6 T6 (Ta -50oC to +60oC) T5 (Ta -50oC to +75oC) Seal required adjacent to enclosure IP66/IP67. Ex d IIC T4-T6 T6 (Ta -55oC to +60oC) T5 (Ta -55oC to +75oC) T4 (Ta -55oC to +125oC) Seal required adjacent to enclosure IP66/IP67. APPLICABLE REQUIREMENTS CAN/CSA-C22.2 No. 60079-0:2007 – Electrical apparatus for explosive gas atmospheres. Part 0: General requirements CAN/CSA-C22.2 No. 60079-1:2011 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d" CAN/CSA-C22.2 No. 60079-7:2012 – Explosive atmospheres. Part 7: Equipment protection by increased safety "e" 1.1 33 95-8736 APPENDIX C ATEX APPROVAL EC-TYPE EXAMINATION CERTIFICATE DEMKO 01 ATEX 130204X Increased Safety Model 0539 II 2 G II 2 D Flameproof Model II 2 G II 2 D 0539 Ex d e IIC T6...T5 Gb Ex d IIC T6...T4 Gb Ex tb IIIC T130°C Ex tb IIIC T130°C T6 (Tamb = –50°C to +60°C) T6 (Tamb = –55°C to +60°C) T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C) IP66/IP67. T4 (Tamb = –55°C to +125°C) IP66/IP67. Compliance with: EN 60079-0: 2009 EN 60079-1: 2007 EN 60079-7: 2007 EN 60079-31: 2009 EN/IEC 60529: 2001. INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from 14-24 AWG or 2.5-0.2 mm2. The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: The front window assembly contains a special cemented joint construction. In accordance with EN600791 clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector Electronics Corporation only. The EOL resistor can only be used within the flameproof terminal compartment. EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk of mechanical damage. 1.1 34 95-8736 NOTE Operational performance verified from –40°C to +75°C. NOTE An optional third party addressable module can only be used within the Ex d flameproof model unless the addressable module is component certified as Ex e for use within the Ex d e increased safety model. NOTE Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable blanking elements. NOTE For ATEX installations, the X3301 Flame Detector housing must be electrically connected to earth ground. The following accessories are ATEX approved for use with the X3301 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 1.1 35 95-8736 APPENDIX D IECEx APPROVAL IECEx CERTIFICATE OF CONFORMITY DEMKO IECEx ULD 06.0017X Ex d e IIC T6...T5 Gb Ex tb IIIC T130°C T6 (Tamb = –50°C to +60°C) T5 (Tamb = –50°C to +75°C) IP66/IP67. or Ex d IIC T6...T4 Gb Ex tb IIIC T130°C T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) T4 (Tamb = –55°C to +125°C) IP66/IP67. Compliance with: IEC 60079-0: 2007, Ed. 5 IEC 60079-1: 2007, Ed. 6 IEC 60079-7: 2006, Ed. 4 IEC 60079-31: 2008, Ed. 1 EN/IEC 60529: 2001. INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from 14-24 AWG or 2.5-0.2 mm2. The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal compartment in type of explosion protection flameproof enclosure "d" or in type of explosion protection increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: The front window assembly contains a special cemented joint construction. In accordance with IEC 60079-1 clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector Electronics Corporation only. The EOL resistor can only be used within the flameproof terminal compartment. EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk of mechanical damage. The following accessories are IECEx approved for use with the X3301 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 1.1 36 95-8736 APPENDIX E EN54 APPROVALS Certification Bodies VdS – Constructive Product Regulation Conventional Output Basis of Approval Certificate/Approval Number 0786 – CPR – 20453 EN 54-10 + A1 — — LPCB Basis of Approval G 202136 VdS 2344 VdS 2504 EN 54-10 + A1 G 212019 VdS 2344 VdS 2504 EN 54-10 + A1 EN 54-17 S 212002 VdS 2344 EN 54-13 S 212002 VdS 2344 EN 54-13 — — 0832 – CPR – F0892 EN 54-10 + A1 EN 54-17 973e/03 EN 54-10 + A1 973a/03 EN 54-10 + A1 EN 54-17 VdS* BRE – Constructive Product Regulation LON Output Certificate/Approval Number * Approval of all sensitivities. INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM The installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view angle in this direction is <90°. The IR-flame detector configured to all sensitivity levels corresponds to class 1. The following accessories are EN54-10, EN54-13, and EN54-17 approved for use with the X3301 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only 011385-001 1.1 Q9033 Collar Attachment 37 95-8736 APPENDIX F ADDITIONAL APPROVALS BRAZIL UL-BR 12.0093X Ex d e IIC T6-T5 Gb IP66/IP67 Ex tb IIIC T130°C T6 (Tamb = –50°C to +60°C) T5 (Tamb = –50°C to +75°C). – OR – Ex d IIC T6-T4 Gb IP66/IP67 Ex tb IIIC T130°C T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) T4 (Tamb = –55°C to +125°C). 1.1 38 95-8736 95-8736 FlexSonic ® Acoustic Leak Detector X3301 Multispectrum IR Flame Detector ­Corporate Office 6901 West 110 th Street Minneapolis, MN 55438 USA www.det-tronics.com PointWatch Eclipse ® IR Combustible Gas Detector Phone: 952.946.6491 Toll-free: 800.765.3473 Fax: 952.829.8750 det-tronics@det-tronics.com FlexVu ® Universal Display with GT3000 Toxic Gas Detector Eagle Quantum Premier ® Safety System All trademarks are the property of their respective owners. © 2015 Detector Electronics Corporation. All rights reserved. Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.