Det-Tronics Instructions IR Flame Detector with Pulse Output X9800
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions IR Flame Detector with Pulse Output X9800 6.1 Rev: 12/15 95-8555 Table of Contents DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . 16 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . 17 oi Plate Removal and Replacement . . . . . . . . . 17 Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Periodic Checkout Procedure . . . . . . . . . . . . . . 17 Integral Wiring Compartment . . . . . . . . . . . . . . . 3 Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 SIGNAL PROCESSING OPTIONS . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 GENERAL APPLICATION INFORMATION . . . . . . . . 4 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Response Characteristics . . . . . . . . . . . . . . . . . . 4 False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 4 REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 20 Factors Inhibiting Detector Response . . . . . . . . . 5 DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . . 20 IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 5 ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 20 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 6 X9800 Model Matrix . . . . . . . . . . . . . . . . . . . . . 21 Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 6 Protection Against Moisture Damage . . . . . . . . . 6 Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 7 APPENDIX A – FM APPROVAL AND PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 22 EOL Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . 15 APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 25 STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 15 Manual oi Test (Output to Controller) . . . . . . . . 15 APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 26 Count Test Mode (Output to Controller) . . . . . . . . 15 Fire Alarm Test (Pulse Output to Fire Alarm Panel) . 16 APPENDIX D – IECEx APPROVAL . . . . . . . . . . . . . 28 INSTRUCTIONS IR Flame Detector with Pulse Output X9800 IMPORTANT Be sure to read and understand the entire instruction manual before installing or operating the flame detection system. Any deviation from the recommendations in this manual may impair system performance and compromise safety. ATTENTION The X9800 includes the Automatic oi ® (Optical Integrity) feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. Testing with an external test lamp is not approved or required. When used as a field replacement, all operating features of the current controller are retained in addition to gaining the advanced features of the X9800 Flame Detector. In typical applications, the four wire X9800 can utilize all existing system wiring. DESCRIPTION The evolution continues with the new X9800 IR Flame Detector. The X9800 meets the most stringent requirements worldwide with advanced detection capabilities and immunity to extraneous sources, combined with a superior mechanical design. The detector is equipped with both automatic and manual oi test capability. The detector has Division and Zone explosion-proof ratings and is suitable for use in indoor and outdoor applications. The X9800 housing is available in copperfree aluminum or stainless steel, with NEMA/Type 4X and IP66/IP67 rating. The X9800 with pulse/relay output is designed for use in controller based systems. In addition to use in new systems, it can serve as a direct field replacement for Detector Electronics Corporation’s (Det-Tronics) controller based flame detectors that generate a pulse output (not compatible with R7484 and R7409B/C). 6.1 ©Detector Electronics Corporation 2016 A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Microprocessor controlled heated optics increase resistance to moisture and ice. 1 Rev: 12/15 95-8555 Magnetic oi / Manual oi OUTPUTS Relays CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test. The detector is furnished with fire and fault relays. The relays are rated 5 amperes at 30 Vdc. The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. The detector incorporates both Magnetic oi (Mag oi) and Manual oi (Man oi) test capabilities. These tests provide pulses (80 to 100 CPS) to the controller (R7404 or R7494) when the detector is not in fault. If the test is successful, the controller indicates a fire and the appropriate zone output is active. The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. NOTE If the detector is in a fault condition, a successful Mag oi or Man oi test cannot be performed. Latching relays can be reset by removing input power (0.1 second minimum). An alarm condition will normally override a fault condition, unless the nature of the fault condition impairs the ability of the detector to generate or maintain an alarm output, i.e., loss of operating power. The Mag oi test is performed by placing a magnet at the location marked “MAG OI” on the outside of the detector (see Figure 2). This action causes the detector to immediately send pulses to the controller. Controller response is as follows: LED A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Table 1 indicates the condition of the LED for each status. • The Zone LED blinks. • The digital display indicates which Zone is in alarm. • The status indicator shows “6” (fire). oi (OPTICAL INTEGRITY) Table 1—Detector Status Indicator Automatic oi Detector Status The X9800 includes the Automatic oi feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. No testing with an external test lamp is required. The detector automatically performs the same test that a maintenance person with a test lamp would perform — once every minute. However, a successful Automatic oi test does not produce an alarm condition. Power On/Normal Auto oi (no fault or fire alarm) Green Power On/Normal Man oi Green, flashing off for 0.5 sec. every 5 sec. Fault Pre-Alarm/Background IR Fire (Alarm) Yellow Red, flashing on for 1 sec. and off for 1 sec. Steady Red On Power-Up, The LED Flashes in Sequence as Follows, Indicating Sensitivity and Signal Processing Status The X9800 signals a fault condition when less than half of the detection range remains. This is indicated by the fault relay and is evident by the yellow color of the LED on the face of the detector. See the “Troubleshooting” section for further information. 6.1 LED Indicator 2 Low IR Sensitivity Medium IR Sensitivity High IR Sensitivity Very High IR Sensitivity One Green Flash Two Green Flashes Three Green Flashes Four Green Flashes Quick Fire / TDSA IR Signal TDSA only IR Signal Quick Fire only One Yellow Flash Two Yellow Flashes Three Yellow Flashes 95-8555 IMPORTANT Mag oi can be performed with the controller’s (R7404/R7494) keylock switch in either the NORMAL or TEST position. In NORMAL, the controller goes into alarm and activates its outputs. If no controller alarm output is desired, place the keylock switch in the TEST position before touching the magnet to the outside of the detector. Man oi operates only with the keylock switch in the TEST position. INTEGRAL WIRING COMPARTMENT All external wiring to the device is connected within the integral junction box. The detector is furnished with four conduit entries, with either 3/4 inch NPT or M25 threads. SIGNAL PROCESSING OPTIONS The X9800 features signal processing options. These options determine the type of logic that the detector will use for processing fire signals to customize the X9800 to the application. Two signal processing options are available for the X9800: During the entire test, the detector gives no indication of alarm. To reset the controller status and alarms, place the keylock switch in RESET. Return the keylock switch to NORMAL when testing is complete. –– TDSA enabled –– Both TDSA and Quick Fire enabled (either initiates fire alarm). The Man oi test is nearly identical to the Mag oi test, except for the manner in which the test is initiated: Time Domain Signal Analysis (TDSA) • Place the keylock switch on the controller (R7404/ R7494) in the TEST position. The TDSA signal processing technique analyzes the input signal in real time, requiring the IR signal to flicker randomly in order to recognize it as a fire condition. • Press the SELECT button to select the appropriate detector for test. • Press the TEST/ACCEPT button to initiate the test. Using TDSA signal processing, the X9800 ignores regularly chopped blackbody sources (occurring in areas where moving conveyors and hot objects in proximity to one another result in a regularly chopped IR signal), because it looks for a less uniform signal. However, in the presence of a regularly chopped signal, the unit is more susceptible to false alarms due to sporadic IR that functions as a trigger when occurring in conjunction with the regularly chopped signal. Controller and detector responses are identical to the Mag oi test described above. To reset the controller status and alarms, place the keylock switch in RESET. Return the keylock switch to NORMAL when testing is complete. Quick Fire (High Speed) NOTE Refer to Appendix A for FM verification of the Det-Tronics o i function. The Quick Fire (High Speed) feature can be used in conjunction with the TDSA signal processing method. This method overrides TDSA requirements in the event of an intense signal. When Quick Fire is activated, the detector is capable of responding to an intense fire signal in less than 30 milliseconds (0.030 seconds). Using the Quick Fire feature in conjunction with TDSA signal processing allows the detector to provide a high speed response to a large, non-flickering fire (such as in high pressure gas applications) while maintaining an ability to respond to smaller fires. COMMUNICATION The X9800 is furnished with an RS-485 interface for communicating status and other information with external devices. The RS-485 uses Modbus protocol, with the detector configured as a slave device. DATA LOGGING Data logging capability is also provided. Status conditions such as normal, power down, general and oi faults, prealarm, fire alarm, time, and temperature are recorded. Each event is time and date stamped, along with the temperature and input voltage. Event data is stored in non-volatile memory when the event becomes active, and again when the status changes. Data is accessible using the Det-Tronics Inspector Connector accessory or RS-485. 6.1 3 95-8555 GENERAL APPLICATION INFORMATION FALSE ALARM SOURCES The detector has been designed to ignore steady state infrared sources that do not have a flicker frequency characteristic of a fire, however, it should be noted that if these steady state infrared sources are hot enough to emit adequate amounts of infrared radiation in the response range of the IR sensor and if this radiation becomes interrupted from the view of the detector in a pattern characteristic of a flickering flame, the IR sensor can respond. RESPONSE CHARACTERISTICS Response is dependent on the detector’s sensitivity setting, distance, type of fuel, temperature of the fuel, and time required for the fire to come to equilibrium. As with all fire tests, results must be interpreted according to an individual application. See Appendix A for third-party approved fire test results. Additional fire test results are available from Det-Tronics. Any object having a temperature greater than 0° Kelvin (–273°C) emits infrared radiation. The hotter the object, the greater the intensity of the emitted radiation. The closer the infrared source is to the detector, the greater the potential for a false alarm. The IR sensor can respond to IR radiation sources that can meet the amplitude and flicker requirements of the detector such as vibrating hot objects. Welding It is recommended that the system be bypassed during welding operations in situations where the possibility of a false alarm cannot be tolerated. Gas welding mandates system bypass, since the gas torch is an actual fire. Arc welding rods can contain organic binder materials in the flux that burn during the welding operation and are detectable by the X9800. Welding rods with clay binders do not burn and will not be detected by the X9800. However, system bypass is always recommended, since the material being welded may be contaminated with organic substances (paint, oil, etc.) that will burn and possibly cause the X9800 to alarm. Although the detector is designed to reduce false actuations, certain combinations of ambient radiation must be avoided. For example, if IR radiation with an intensity that exceeds the fire threshold of the IR sensor should reach the detector as a flickering signal, and if at the same time an electric arc welding signal also reaches the detector, an alarm output will be generated. Artificial Lighting NOTE Radiation generated by false alarm sources such as periodic lightning or sparks in the area can be effectively ignored by the detector using the arc rejection feature or time delay. The X9800 should not be located within 3 feet (0.9 m) of artificial lights. Excess heating of the detector could occur due to heat radiating from the lights. EMI/RFI Interference The X9800 is resistant to interference by EMI and RFI, and is EMC Directive compliant and CE marked. It will not respond to a 5 watt walkie-talkie at distances greater than 1 foot (0.3 m). Non-Carbon Fires The response of the X9800 is limited to carbonaceous fuels. It should not be used to detect fires from fuels that do not contain carbon, such as hydrogen, sulfur, and burning metals. 6.1 4 95-8555 IMPORTANT SAFETY NOTES FACTORS INHIBITING DETECTOR RESPONSE Windows WARNING Do not open the detector assembly in a hazardous area when power is applied. The detector contains limited serviceable components and should never be opened. Doing so could disturb critical optical alignment and calibration parameters, possibly causing serious damage. This type of damage could be undetected and could result in failure to see a fire and/or false alarm. Glass and Plexiglas windows significantly attenuate radiation and must not be located between the detector and a potential flame source. If the window cannot be eliminated or the detector location changed, contact Det-Tronics for recommendations regarding window materials that will not attenuate radiation. Obstructions Radiation must be able to reach the detector in order for it to respond. Care must be taken to keep physical obstructions out of the line of view of the detector. CAUTION The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local ordinances. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person. Smoke Smoke will absorb radiation. If accumulations of dense smoke can be expected to precede the presence of a flame, then detectors that are used in enclosed areas should be mounted on the wall approximately 3 feet (0.9 m) from the ceiling where the accumulation of smoke is reduced. Detector Viewing Windows It is important to keep the detector viewing windows as free of contaminants as possible in order to maintain maximum sensitivity. Commonly encountered substances that can significantly attenuate IR radiation include, but are certainly not limited to, the following: –– Dust and dirt buildup –– Paint overspray –– Water and ice CAUTION To prevent unwanted actuation or alarm, extinguishing devices must be disabled prior to performing system tests or maintenance. CAUTION The IR flame detectors are to be installed in places where the risk of mechanical damages is low. ATTENTION Remove the protective cap from the front of the detector before activating the system. ATTENTION Observe precautions for handling electrostatic sensitive devices. 6.1 5 95-8555 INSTALLATION NOTE The recommended lubricant for threads and O‑rings is a silicone free grease (p/n 005003001) available from Detector Electronics. Under no circumstances should a lubricant containing silicone be used. • Dense fog and rain as well as certain gases and vapors can absorb IR radiation and reduce the sensitivity of the detector. • If possible, fire tests can be conducted to verify correct detector positioning and coverage. • For ATEX/IECEx installations, the X9800 Flame Detector housing must be electrically connected to earth ground. DETECTOR POSITIONING Detectors should be positioned to provide the best unobstructed view of the area to be protected. The following factors should also be taken into consideration: • Identify all high risk fire ignition sources. • Be sure that enough detectors are used to adequately cover the hazardous area. • Be sure that the unit is easily accessible for cleaning and other periodic servicing. • Verify that all detectors in the system are properly located and positioned so that any fire hazards are within both the Field of View (FOV) and detection range of the detector. The Det-Tronics Q1201C Laser Aimer is recommended for establishing the detector’s FOV. Refer to Appendix A for specific information regarding detector range and FOV. • The detector should be aimed downward at least 10 to 20 degrees to allow lens openings to drain (see Figure 1). The detector should be positioned so that its FOV does not cover areas outside the hazardous area. This will minimize the possibility of false alarms caused by activities outside the area requiring protection. • DETECTOR ORIENTATION Refer to Figure 2 and ensure that the oi plate will be oriented as shown when the X9800 is mounted and sighted. This will ensure proper operation of the oi system and will also minimize the accumulation of moisture and contaminants between the oi plate and the viewing windows. IMPORTANT If removed, the o i plate must be securely tightened to ensure proper operation of the o i system (40 oz./inches [28.2 N . cm] recommended). oi PLATE PLACE MAGNET HERE TO INITIATE MAGNETIC oi The detector must be mounted on a rigid surface in a low vibration area. IR VIEWING WINDOW oi MAGNET B2174 DETECTOR STATUS INDICATOR Figure 2—Front View of the X9800 CENTER AXIS OF DETECTOR FIELD OF VIEW PROTECTION AGAINST MOISTURE DAMAGE It is important to take proper precautions during installation to ensure that moisture will not come in contact with the electrical connections or components of the system. The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer. INCORRECT If conduit is used, we recommend installing drains, according to local codes, at water collection points to automatically drain accumulated moisture. It is also recommended to install at least one breather, according to local codes, at upper locations to provide ventilation and allow water vapor to escape. CENTER AXIS OF DETECTOR FIELD OF VIEW CORRECT D1974 NOTE: DETECTOR MUST ALWAYS BE AIMED DOWNWARD AT LEAST 10 TO 20 DEGREES. Figure 1—Detector Orientation Relative to Horizon 6.1 6 95-8555 Conduit raceways should be inclined so that water will flow to low points for drainage and will not collect inside enclosures or on conduit seals. If this is not possible, install conduit drains above the seals to prevent the collection of water or install a drain loop below the detector with a conduit drain at the lowest point of the loop. WARNING All entries must contain appropriately rated plugs or fittings. It is required that each plug or fitting be wrench-tightened to an appropriate installation torque and meet the minimum thread engagement requirements per the applicable local standards, codes, and practices in order to retain the defined ratings. PTFE sealant or equivalent should be used on NPT threads. Conduit seals are not required for compliance with explosion-proof installation requirements, but are highly recommended to prevent water ingress in outdoor applications. Units with M25 threads must use an IP66/IP67 washer to prevent water ingress. IMPORTANT Devices certified for hazardous locations shall be installed in accordance with EN/IEC 60079-14 and NEC 505. WIRING PROCEDURE Wire Size and Type Detector Installation The system should be wired according to local codes. The wire size selected should be based on the number of detectors connected, the supply voltage, and the cable length. Typically 16 AWG or 2.5 mm2 shielded cable is recommended. Wires should be stripped 3/8 inch, 9 mm. In some cases where the X9800 is replacing existing pulse output detectors, the wiring and power supplies may not be adequate. Consult the factory for assistance. Install the mounting arm assembly on a rigid surface. The ideal installation surface should be free of vibration and suitable to receive 3/8 inch (M9) bolts with a length of at least 1 inch (25 mm). The surface must also have sufficient capacity to hold the detector and mounting arm weights (See “Specifications” section). Refer to the Q9033 Mounting Arm manual , number 95-8686, for additional mounting information. See Figure 3 for dimensions. Detector Wiring IMPORTANT A minimum input voltage of 18 Vdc must be present at the X9800. IMPORTANT If installing an X9800 in place of an existing detector, be sure to move the “A” Lead (detector power) at the controller from the +290 Vdc source to the +24 Vdc source. Do not apply 290 Vdc to the X9800. The use of shielded cable is required to protect against interference caused by EMI and RFI. When using cables with shields, terminate the shields as shown in Figures 6 through 10. Consult the factory if not using shielded cable. 1. Make field connections following local ordinances and guidelines in this manual. The “B” (pulse output) and “D” (oi driver) leads from each detector should be shielded from the “B” and “D” leads of all other detectors in order to prevent false alarms resulting from crosstalk between zones. It is recommended that the “A” and “C” leads also be shielded to provide maximum immunity to EMI/RFI. (See Figures 6 to 10.) In applications where the wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical equipment. If disconnection of power is required, separate disconnect capability must be provided. Figure 4 shows the wiring terminal strip located inside the detector’s integral junction box. Figure 5 shows the wiring terminal identification for the X9800 detector with pulse output. Leave the shield open at the detector end and permanently isolate it from accidental contact with the case and/or other conductors. At the controller/ fire panel end, connect the shield and power minus (–) to chassis (earth) ground either directly or through a 0.47 µF 400 Volt non-polarized capacitor (not supplied). (Refer to Figures 6 through 10.) CAUTION Installation of the detector and wiring should be performed only by qualified personnel. 6.1 7 95-8555 4X ø0.42 (1.1) 3.0 (7.6) 4.0 (10.2) 13.1 (33.4) NOTE: THIS ILLUSTRATION SHOWS THE DETECTOR MOUNTED AT THE 10° MINIMUM. THESE DIMENSIONS WILL CHANGE BASED ON THE DETECTOR’S MOUNTING ANGLE. 3.0 (7.6) 4.0 (10.2) 10.6 (27.0) E2069 Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm) (See Figure 1 for Correct Detector Orientation.) Figures 11 and 12 provide examples of typical installations with a X9800 wired to a fire alarm panel. Figure 13 shows an EOL resistor installed within the integral wiring compartment of the detector (refer to “EOL Resistors” for details). 2. Check all field wiring to be sure that the proper connections have been made. IMPORTANT Do not test any wiring connected to the detector with a meg-ohmmeter. Disconnect wiring at the detector before checking system wiring for continuity. 3. Make the final sighting adjustments and use a 14 mm hex wrench to ensure that the mounting arm assembly is tight. 9 19 8 18 PULSE OUT 29 SPARE 28 SPARE 7 COM FIRE 17 COM FIRE 27 6 N.O. FIRE 16 N.O. FIRE 26 5 N.C. FIRE 15 N.C. FIRE 25 4 COM FAULT 14 COM FAULT 24 RS-485 A 3 N.O. FAULT 13 N.O. FAULT 23 RS-485 B 2 + Vin 12 + Vin 22 MAN Oi 1 – Vin 11 – Vin 21 – Vin D2070 Figure 5—X9800 Pulse Wiring Terminal Identification Figure 4—X9800 Terminal Block 6.1 8 95-8555 NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO TERMINAL J1-3 (290 VDC). X9800 #2 #1 #19 #22 #2 #1 #19 #22 DETECTOR 1 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-5 J1-13 DETECTOR 2 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-6 J1-14 DETECTOR 3 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-7 J1-15 DETECTOR 4 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-8 J1-16 DETECTOR 5 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-9 J1-17 DETECTOR 6 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-10 J1-18 DETECTOR 7 X9800 #2 #1 #19 #22 #2 #1 #19 #22 24 VDC J1 + 1 – 2 + – 3 J2 R7404 CONTROLLER } 10 TO 38 VDC ZONE OUTPUT 1 33 ZONE OUTPUT 2 34 (A) +290 VDC ZONE OUTPUT 3 35 4 B - INPUT 1 ZONE OUTPUT 4 36 5 B - INPUT 2 ZONE OUTPUT 5 37 6 B - INPUT 3 ZONE OUTPUT 6 38 7 B - INPUT 4 ZONE OUTPUT 7 39 8 B - INPUT 5 ZONE OUTPUT 8 40 9 B - INPUT 6 FIRE LOGIC “A” 41 10 B - INPUT 7 FIRE LOGIC “B” 42 11 B - INPUT 8 ALARM OUTPUT 43 12 D1-1 oi DRIVER EXTERNAL RESET/INHIBIT 44 13 D1-2 oi DRIVER OUTPUTS INHIBITED 45 14 D1-3 oi DRIVER FAULT OUTPUT 46 15 D1-4 oi DRIVER EXTERNAL ACCEPT 47 16 D1-5 oi DRIVER STATUS & DET. OUTPUT S1 48 17 D1-6 oi DRIVER STATUS & DET. OUTPUT S2 49 18 D1-7 oi DRIVER STATUS & DET. OUTPUT S3 50 19 D1-8 oi DRIVER STATUS & DET. OUTPUT S4 51 20 D2-1 oi DRIVER STATUS & DET. OUTPUT S5 52 21 D2-2 oi DRIVER STATUS & DET. OUTPUT S6 53 22 D2-3 oi DRIVER STATUS & DET. OUTPUT S7 54 23 D2-4 oi DRIVER STATUS & DET. OUTPUT S8 55 24 D2-5 oi DRIVER DATA BUS 0 56 25 D2-6 oi DRIVER DATA BUS 1 57 26 D2-7 oi DRIVER DATA BUS 2 58 27 D2-8 oi DRIVER DATA BUS 3 59 28 DMA OUT AVAILABLE DATA BUS 4 60 29 DMA OUT DATA BUS 5 61 30 DMA IN DATA BUS 6 62 31 DATA STROBE DATA BUS 7 63 32 DMA IN AVAILABLE CHASSIS (EARTH) GND 64 A2182 J1-11 J1-19 DETECTOR 8 TO J1-2 TERMINAL IDENTIFICATION FOR X9800 WITH PULSE OUTPUT. TERMINAL NO. FUNCTION 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. 62 63 0.47 μF / 400 VDC NON-POLARIZED 64 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 6—A Typical System, X9800 Detectors Wired to R7404 Controller 6.1 9 95-8555 NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO TERMINAL J1-3 (290 VDC). X9800 #2 #1 #19 #22 #2 #1 #19 #22 DETECTOR 1 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-5 J1-13 DETECTOR 2 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-6 J1-14 DETECTOR 3 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-7 J1-15 DETECTOR 4 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-8 J1-16 #2 #1 #19 #22 +24 VDC ZONE OUTPUT 1 33 – 2 CIRCUIT GROUND ZONE OUTPUT 2 34 3 +290 VDC ZONE OUTPUT 3 35 4 B1 - INPUT SIGNAL ZONE OUTPUT 4 36 5 B2 - INPUT SIGNAL ZONE OUTPUT 5 37 6 B3 - INPUT SIGNAL ZONE OUTPUT 6 38 7 B4 - INPUT SIGNAL ZONE OUTPUT 7 39 8 B5 - INPUT SIGNAL ZONE OUTPUT 8 40 9 B6 - INPUT SIGNAL FIRE LOGIC “A” 41 10 B7 - INPUT SIGNAL FIRE LOGIC “B” 42 11 B8 - INPUT SIGNAL ALARM OUTPUT 43 12 D1 oi DRIVER EXTERNAL RESET/INHIBIT 44 13 D2 oi DRIVER OUTPUTS INHIBITED 45 14 D3 oi DRIVER FAULT OUTPUT 46 15 D4 oi DRIVER EXTERNAL ACCEPT 47 16 D5 oi DRIVER STATUS & DET. OUTPUT S1 48 D6 oi DRIVER STATUS & DET. OUTPUT S2 49 STATUS & DET. OUTPUT S3 50 STATUS & DET. OUTPUT S4 51 STATUS & DET. OUTPUT S5 52 STATUS & DET. OUTPUT S6 53 STATUS & DET. OUTPUT S7 54 STATUS & DET. OUTPUT S8 55 DATA BUS 0 56 DATA BUS 1 57 DATA BUS 2 58 DATA BUS 3 59 DATA BUS 4 60 DATA BUS 5 61 DATA BUS 6 62 DATA BUS 7 63 17 18 #2 #1 #19 #22 21 22 23 24 25 J1-9 J1-17 26 27 28 #2 #1 #19 #22 #2 #1 #19 #22 29 30 J1-10 J1-18 DETECTOR 7 X9800 1 20 DETECTOR 6 X9800 J1 + 19 DETECTOR 5 X9800 24 VDC 31 32 J2 R7404 STAR LOGIC CONTROLLER D7 oi DRIVER D8 oi DRIVER DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT NOT USED NOT USED DATA STROBE IN NOT USED NOT USED EARTH GROUND 64 A2183 #2 #1 #19 #22 #2 #1 #19 #22 J1-11 J1-19 DETECTOR 8 TO J1-2 TERMINAL IDENTIFICATION FOR X9800 WITH PULSE OUTPUT. TERMINAL NO. FUNCTION 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. 62 63 0.47 μF / 400 VDC NON-POLARIZED 64 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 7—A Typical System, X9800 Detectors Wired to R7404 Star Logic Controller 6.1 10 95-8555 X9800 #2 #1 #19 #22 #2 #1 #19 #22 DETECTOR 1 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-5 J1-13 DETECTOR 2 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-6 J1-14 DETECTOR 3 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-7 J1-15 DETECTOR 4 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J1-8 J1-16 #2 #1 #19 #22 +24 VDC ZONE OUTPUT 1 33 – 2 CIRCUIT GROUND ZONE OUTPUT 2 34 3 +24 VDC ZONE OUTPUT 3 35 4 B1 - INPUT SIGNAL ZONE OUTPUT 4 36 5 B2 - INPUT SIGNAL ZONE OUTPUT 5 37 6 B3 - INPUT SIGNAL ZONE OUTPUT 6 38 7 B4 - INPUT SIGNAL ZONE OUTPUT 7 39 8 B5 - INPUT SIGNAL ZONE OUTPUT 8 40 9 B6 - INPUT SIGNAL FIRE LOGIC “A” 41 10 B7 - INPUT SIGNAL FIRE LOGIC “B” 42 11 B8 - INPUT SIGNAL ALARM OUTPUT 43 12 D1 oi DRIVER EXTERNAL RESET/INHIBIT 44 13 D2 oi DRIVER OUTPUTS INHIBITED 45 14 D3 oi DRIVER FAULT OUTPUT 46 15 D4 oi DRIVER EXTERNAL ACCEPT 47 16 D5 oi DRIVER STATUS & DET. OUTPUT S1 48 D6 oi DRIVER STATUS & DET. OUTPUT S2 49 STATUS & DET. OUTPUT S3 50 STATUS & DET. OUTPUT S4 51 STATUS & DET. OUTPUT S5 52 STATUS & DET. OUTPUT S6 53 STATUS & DET. OUTPUT S7 54 STATUS & DET. OUTPUT S8 55 DATA BUS 0 56 DATA BUS 1 57 DATA BUS 2 58 DATA BUS 3 59 DATA BUS 4 60 DATA BUS 5 61 DATA BUS 6 62 DATA BUS 7 63 17 18 #2 #1 #19 #22 21 22 23 24 25 J1-9 J1-17 26 27 28 #2 #1 #19 #22 #2 #1 #19 #22 29 30 J1-10 J1-18 DETECTOR 7 X9800 1 20 DETECTOR 6 X9800 J1 + 19 DETECTOR 5 X9800 24 VDC 31 32 J2 R7494 CONTROLLER D7 oi DRIVER D8 oi DRIVER DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT NOT USED NOT USED DATA STROBE IN NOT USED NOT USED EARTH GROUND 64 A2184 #2 #1 #19 #22 #2 #1 #19 #22 J1-11 J1-19 DETECTOR 8 TO J1-2 TERMINAL IDENTIFICATION FOR X9800 WITH PULSE OUTPUT. TERMINAL NO. FUNCTION 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 62 63 0.47 μF / 400 VDC NON-POLARIZED 64 NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 8—A Typical System, X9800 Detectors Wired to R7494 Controller 6.1 11 95-8555 R7495 CONTROLLER (NOT FM APPROVED) X9800 #2 #1 #19 #22 #2 #1 #19 #22 24 VDC J1 + 1 +24 VDC – 2 GROUND 3 DETECTOR 1 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-44 J2-36 4 J2 5 31 32 DETECTOR 2 X9800 #2 #1 #19 #22 #2 #1 #19 #22 33 34 J2-45 J2-37 DETECTOR 3 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-46 J2-38 DETECTOR 4 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-47 J2-39 DETECTOR 5 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-48 J2-40 35 D1 36 D2 37 D3 38 D4 39 D5 40 D6 41 D7 42 D8 43 B1 44 B2 45 B3 46 B4 47 B5 48 B6 49 B7 50 B8 DETECTOR 6 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-49 J2-41 DETECTOR 7 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-50 J2-42 DETECTOR 8 A2185 TO J1-2 TERMINAL IDENTIFICATION FOR X9800 WITH PULSE OUTPUT. TERMINAL NO. NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5. FUNCTION 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) 3 4 NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 0.47 μF / 400 VDC NON-POLARIZED 5 NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 9—A Typical System, X9800 Detectors Wired to R7495 Controller 6.1 12 95-8555 NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO TERMINAL J2-34 (290 VDC). R7405 CONTROLLER (NOT FM APPROVED) X9800 #2 #1 #19 #22 #2 #1 #19 #22 24 VDC J1 + 1 +24 VDC – 2 GROUND 3 DETECTOR 1 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-44 J2-36 4 J2 5 31 32 DETECTOR 2 X9800 #2 #1 #19 #22 #2 #1 #19 #22 33 J2-45 J2-37 DETECTOR 3 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-46 J2-38 DETECTOR 4 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-47 J2-39 DETECTOR 5 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-48 J2-40 34 +290 VDC 35 D1 36 D2 37 D3 38 D4 39 D5 40 D6 41 D7 42 D8 43 B1 44 B2 45 B3 46 B4 DETECTOR 6 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-49 J2-41 DETECTOR 7 X9800 #2 #1 #19 #22 #2 #1 #19 #22 J2-50 J2-42 DETECTOR 8 47 B5 48 B6 49 B7 50 B8 A2186 TO J1-2 TERMINAL IDENTIFICATION FOR X9800 WITH PULSE OUTPUT. TERMINAL NO. NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5. 3 FUNCTION 4 1/11 DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) 19 SIGNAL ("B" LEAD) 22 oi ("D" LEAD) NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 0.47 μF / 400 VDC NON-POLARIZED 5 NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS Figure 10—A Typical System, X9800 Detectors Wired to R7405 Controller 6.1 13 95-8555 X9800 DETECTOR FIRE ALARM PANEL 9 19 8 18 COM FIRE2 7 N.O. FAULT1 3 + 24 VDC + Vin 2 – 26 END OF LINE DEVICE 4 25 14 RS-485 A 24 13 RS-485 B 23 MAN Oi 22 12 – Vin 1 28 27 15 COM FAULT1 4 29 SPARE 16 N.C. FIRE2 5 SPARE 17 N.O. FIRE2 6 ALARM PULSE OUT – Vin 11 21 oi TEST 3 WIRING NOTES: B2187 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. (TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.) 4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION FOR INSTALLATION DETAILS. Figure 11—Ex d Wiring Option X9800 DETECTOR FIRE ALARM PANEL 9 19 8 ALARM EOL DEVICE 4 7 ALARM 6 5 4 3 + 24 VDC 2 – 1 PULSE OUT 18 COM FIRE2 N.O. FIRE2 N.C. FIRE2 COM FAULT1 N.O. FAULT1 + Vin – Vin SPARE 29 SPARE 28 17 27 16 26 15 25 14 RS-485 A 24 13 RS-485 B 23 MAN Oi 22 12 11 – Vin 21 oi TEST 3 B2188 WIRING NOTES: 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. (TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.) 4 EOL RESISTOR SUPPLIED BY PANEL. Figure 12—Ex e Wiring Option 6.1 14 95-8555 STARTUP PROCEDURE EOL RESISTORS To ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors, observe the following guidelines when installing the resistors: When installation of the equipment is complete, apply power and allow 20 to 30 minutes for the detector’s heated optics to reach equilibrium. Then perform one or more of the following tests: 1. Required EOL resistor power rating must be 5 watts minimum. Man oi Test — Tests detector output and wiring, without generating a fire alarm. NOTE EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. This applies to ATEX/IECEx installations only. Count Test Mode — Measures actual detector output to controller (cps), without generating a fire alarm. Fire Alarm Test — For complete system test including detector relays. Generates fire alarm output. MANUAL oi TEST (Output to Controller) 2. Resistor leads should be cut to a length of approximately 1 1/2 inches, 40 mm. 1. Place the keylock switch in the TEST position. 3. Bend the leads and install the EOL resistor as shown in Figure 13. 2. Press the SELECT button to display the desired zone on the ZONE indicator on the front panel of the controller. 4. Maintain a 3/8 inch, 10 mm minimum gap between the resistor body and the terminal block or any other neighboring parts. 3. Press and hold the TEST button. The ZONE OUTPUT LED for the tested zone flashes and the SYSTEM STATUS display indicates a “6” (fire condition) if the test is successful. NOTE The EOL resistor can only be used within the flameproof terminal compartment. Unused apertures shall be closed with suitable blanking elements. 4. Release the TEST button. The ZONE OUTPUT LED for the tested zone should remain on steadily. 5. Return to step 2 to test the next detector. If the system responds differently than indicated above, proceed with the count test for the problem zone to verify detector and wiring operation. 3/8 INCH (10 MM) GAP MINIMUM COUNT TEST MODE (Output to Controller) When in the Count Test mode, the frequency of the digital pulses from the detector is displayed on the ZONE and DETECTOR indicators on the controller faceplate. The Count Test mode may be used to check the signal (cps) from a test fire or false alarm source. This can be useful during system set-up for sensitivity and time delay settings. This test is performed in the following manner: 19 18 17 16 15 14 13 12 11 B2126 BULKHEAD 1. Place the keylock switch in the TEST position. 2. Simultaneously press and release the SELECT and TEST buttons. The Status display will change from a “1” to an “8” indicating that the controller is in the Count Test mode of operation. Figure 13—EOL Resistor Installation 6.1 15 95-8555 2. Inspect the viewing windows for contamination and clean as necessary. (Refer to the “Maintenance” section for complete information regarding cleaning of the detector viewing windows.) 3. Press the SELECT button until the desired zone is displayed on the ZONE indicator on the controller front panel. 4. Press and hold the TEST button. The DETECTOR/ ZONE display indicates the counts per second (cps) received from the detector. If the counts per second exceeds 99, the FIRE LOGIC LEDs are illuminated to indicate that the number shown on the display must be multiplied by 10. The normal reading for an oi test is 80 to 110 cps. For a live fire test, 270 - 330 cps will be generated. 3. Check input power to the unit. 4. Check system and detector logs. 5. Turn off the input power to the detector and check all wiring for continuity. Important: Disconnect wiring at the detector before checking system wiring for continuity. A zero reading may indicate a dirty window, oi problem, faulty detector, or defective wiring. 6. If all wiring checks out and cleaning of the oi plate/ window did not correct the fault condition, check for high levels of background IR radiation by covering the detector with the factory supplied cover or aluminum foil. If the fault condition clears, extreme background IR radiation is present. Re-adjust the view of the detector away from the IR source or relocate the detector. Release the Test button, the ZONE and DETECTOR display should drop to a reading of 0 to 1 counts per second. FIRE ALARM TEST (Pulse Output to Fire Alarm Panel) 1. Disable any extinguishing equipment that is connected to the system. If none of these actions corrects the problem, return the detector to the factory for repair. 2. Apply input power to the system. NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. 3. Initiate a live fire test or a Mag o i test. (See “Magnetic oi / Manual oi” under “Optical Integrity” in the “Description” section of this manual.) MAINTENANCE 4. Repeat this test for all detectors in the system. If a unit fails the test, refer to the “Troubleshooting” section. IMPORTANT Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t recommended, since the product is not intended to be serviced and provides proper ingress protection to eliminate potential deterioration of the flamepaths. WARNING To avoid a potential electrostatic discharge (ESD), the painted surface of the detector should only be cleaned with a damp cloth. 5. Verify that all detectors in the system are properly aimed at the area to be protected. (The Det-Tronics Q1201C Laser Aimer is recommended for this purpose.) 6. Enable extinguishing equipment when the test is complete. WARNING The sensor module (“front” half of the detector) contains no user serviceable components and should never be tampered with. TROUBLESHOOTING WARNING The sensor module (“front” half of the detector) contains no user serviceable components and should never be tampered with. To maintain maximum sensitivity and false alarm resistance, the viewing windows of the X9800 must be kept relatively clean. Refer to the following procedure for cleaning instructions. 1. Disable any extinguishing equipment that is connected to the unit. 6.1 16 95-8555 CLEANING PROCEDURE LOOSEN TWO CAPTIVE SCREWS CAUTION Disable any extinguishing equipment that is connected to the unit to prevent unwanted actuation. To clean the windows and oi plate, use the Det-Tronics window cleaner (p/n 001680-001) and a soft cloth, cotton swab, or tissue and refer to the following procedure: GRASP VISOR AND REMOVE oi PLATE 1. Disable any extinguishing equipment that is connected to the unit. B2175 Figure 14—oi Plate Removal NOTE Remove input power when cleaning the detector windows. The rubbing motion on the surface of the windows during cleaning can create static electricity that could result in unwanted output activation. oi PLATE REMOVAL AND REPLACEMENT 1. Disable any extinguishing equipment that is connected to the unit. 2. Loosen the two captive screws, then grasp the oi plate by the visor and remove it from the detector. See Figure 14. 2. Clean the viewing window and reflective surfaces of the oi plate using a clean cloth, cotton swab, or tissue, and the Det-Tronics window cleaning solution. Use Isopropyl alcohol for contaminations that the Det-Tronics window cleaning solution can not remove. If a fault condition is still indicated after cleaning, remove and clean the oi plate using the oi Plate Removal and Replacement procedure. 3. Install the new (or cleaned) oi plate. 4. Recalibrate the detector’s oi system. Refer to the Inspector Monitor manual, number 95-8581, for instructions regarding oi plate replacement and oi system recalibration. CAUTION Do not replace the oi reflector plate without also recalibrating the oi system. IMPORTANT When used in extreme environments, the reflective surface of the detector oi plate may eventually deteriorate, resulting in reoccurring oi faults and the need for oi plate replacement. Recalibration of the oi system requires the use of the Inspector Connector Cable and Inspector Monitor Software. These two items are included in the oi replacement kit, or they can be purchased separately. See the “Ordering Information” section for details. PERIODIC CHECKOUT PROCEDURE A checkout of the system using the Mag oi or Man oi feature should be performed on a regularly scheduled basis to ensure that the system is operating properly. To test the system, perform the “Manual oi Test,” “Count Test Mode,” or “Fire Alarm Test” as described in the “Startup Procedure” section of this manual. CLOCK BATTERY The real time clock has a backup battery that will operate the clock with no external power. Return the device to the factory for battery replacement if needed. NOTE If the backup battery is depleted, there is no effect on the operation of the flame detector, but the time stamping of the data log may be affected. 6.1 17 95-8555 FEATURES SPECIFICATIONS • Responds to a fire in the presence of modulated blackbody radiation (i.e., heaters, ovens, turbines) without false alarm OPERATING VOLTAGE— 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). Maximum ripple is 2 volts peak-to-peak. • High speed capability — 30 milliseconds • Built-in data logging / event monitoring, up to 1500 events (up to 1000 general, 500 alarms) • Pulse output for compatibility with controller based systems • Microprocessor controlled heated optics increased resistance to moisture and ice • Automatic, manual, or magnetic oi testing • Easily replaceable oi plate • Fire and fault relays • A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions • Operates under adverse weather conditions • Mounting arm allows easy sighting • Integral wiring compartment for ease of installation • Explosion-proof/flame-proof detector housing. Meets FM, CSA, ATEX, and IECEx certification requirements • Class A wiring per NFPA-72 (relay connections). (Pulse output is equivalent to class A when detectors are installed in a redundant configuration) • 3 year warranty • Advanced signal processing (TDSA) • RFI and EMC Directive Compliant ­ or CSA compliance, the power source must F utilize a SELV (Safety Extra Low Voltage) or Class 2 style power supply. POWER CONSUMPTION— Without heater: 2.1 watts at 24 Vdc nominal; 3.5 watts at 24 Vdc in alarm. 2.2 watts at 30 Vdc nominal; 4.0 watts at 30 Vdc in alarm. Heater only: 8 watts maximum. Total power: 16.5 watts at 30 Vdc with EOL resistor installed and heater on maximum. EOL resistor must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. for POWER UP TIME— Fault indication clears after 0.5 second; device is ready to indicate an alarm condition after 30 seconds. OUTPUT RELAYS— Fire Alarm relay, Form C, 5 amperes at 30 Vdc: The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or nonlatching operation. Fault relay, Form A, 5 amperes at 30 Vdc: The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. TEMPERATURE RANGE— Operating: –40°F to +167°F (–40°C to +75°C). Storage: –67°F to +185°F (–55°C to +85°C). Hazardous location ratings from -55°C to +75°C available on flameproof model. HUMIDITY RANGE— 0 to 95% relative humidity, can withstand 100% condensing humidity for short periods of time. CONE OF VISION— The detector has a 90° cone of vision (horizontal) with the highest sensitivity lying along the central axis. See Figure 15. RESPONSE TIME— 32 inch methane plume: < 10 seconds. 1 foot x 1 foot n-Heptane: < 15 seconds. (See “Appendix A” for details.) 6.1 18 95-8555 THREAD SIZE— Conduit connection: Four entries, 3/4 inch NPT or M25. Conduit seal not required. 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES. VIEWING ANGLE 15° 30° 0° 100 SHIPPING WEIGHT (Approximate)— Aluminum: 7 pounds (3.2 kilograms). Stainless Steel: 14.6 pounds (6.7 kilograms). Mounting Arm (AL): 6 pounds (2.75 kilograms). Mounting Arm (SS): 14 pounds (6.4 kilograms). 15° 30° 90 80 45° 45° 70 60 DETECTION DISTANCE (PERCENT) WARRANTY PERIOD— 3 years 50 40 CERTIFICATION— 30 20 FM 10 ® APPROVED A1288 For complete approval details, refer to the appropriate Appendix: Figure 15—Detector Cone of Vision Appendix A - FM Appendix B - CSA Appendix C - ATEX Appendix D - IECEx ENCLOSURE MATERIAL— Copper-free aluminum (painted) or Stainless Steel (316/ CF8M Cast). VIBRATION— Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW). DIMENSIONS— See Figure 16. WIRING— Field wiring screw terminals are UL/CSA rated for up to 14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire. Screw terminal required torque range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m). Important: 18 Vdc minimum must be available at the detector. For ambient temperatures below –10°C (14°F) and above +60°C (140°F) use field wiring suitable for both minimum and maximum ambient temperature. 4.7 (11.9) B2223 10.2 (25.9) 4.8 (12.2) Figure 16—Dimensions in Inches (cm) 6.1 19 95-8555 REPLACEMENT PARTS ORDERING INFORMATION The detector is not designed to be repaired in the field. If a problem should develop, refer to the “Troubleshooting” section. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair. When ordering, please specify: X9800 IR Flame Detector with Pulse Output Refer to the X9800 Model Matrix below for details Q9033 Mounting Arm is required: –– Q9033A for aluminum detectors only –– Q9033B for aluminum and stainless steel detectors REPLACEMENT PARTS Part Number Description 009208-002 oi Replacement kit for X52/X22/X98 (5 Reflector Plates) with Inspector Connector and Monitor Replacement oi Reflector Plate for X52/X22/X98 (requires Inspector Connector to calibrate) 007307-002 ACCESSORIES Part Number Description 000511-029 103881-001 Converter RS485 to RS232 Converter RS485 to USB W6300B1002 Serial Inspector Connector (Inspector Monitor software included) W6300B1003 USB Inspector Connector (Inspector Monitor software included) Flame Inspector Monitor CD Model 475 HART Communicator Magnet Magnet and Adapter for Extension Pole Magnet and Extension Pole Q1116A1001, Air Shield (AL) Q1118A1001 Aluminum Air Shield/Flange Mount (AL) Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS) Q1120A1001 Paint Shield mounting ring (AL) Q1198A1001 Dual Air Shield/Flange Mount (X9800 only)/(AL) Q1201 Laser Laser Battery, 3V Lithium (laser) Q1201C1001 X-Series Laser Holder (AL/Plastic) Q2000A1001 X-Series Weather Shield (AL) Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment Stop Plug, 3/4” NPT, AL Stop Plug, 3/4” NPT, SS Stop Plug, M25, AL, IP66 Stop Plug, M25, SS, IP66 Stop Plug, 20 Pack, 3/4”NPT, AL Stop Plug, 20 Pack, 3/4”NPT, SS Stop Plug, 20 Pack, M25, AL, IP66 Stop Plug, 20 Pack, M25, SS, IP66 14 mm Hex Wrench (Steel) Screwdriver Window cleaner (6 pack) O-ring - Rear Cover (Viton) - black or brown 1 oz grease for detectors (non-silicon) O-ring - Rear Cover (Fluorosilicone) - blue 1 oz PTFE silicone free lubricant 007819-001 007819-002 009207-001 103922-001 102740-002 008082-001 007739-001 007240-001 007818-001 007818-002 009177-001 009199-001 006097-001 102871-001 007255-001 007338-001 DEVICE REPAIR AND RETURN Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure. 007290-001 Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge. 007290-002 011385-001 101197-001 101197-004 101197-005 101197-003 010816-001 010817-001 010818-001 010819-001 103363-001 103406-001 001680-001 107427-040 005003-001 104346-154 012549-001 NOTE Det-Tronics reserves the right to apply a service charge for repairing returned product damaged as a result of improper packaging. Return all equipment transportation prepaid to the factory in Minneapolis. NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. 6.1 20 95-8555 X9800 MODEL MATRIX MODEL DESCRIPTION X9800 Single Frequency IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 4M 4 PORT, METRIC M25 4N 4 PORT, 3/4" NPT TYPE 15 OUTPUTS Relay and Pulse TYPE W APPROVALS FM/CSA/ATEX/IECEx TYPE 6.1 CLASSIFICATION 1 Division/Zone Ex d e 2 Division/Zone Ex d 21 95-8555 APPENDIX A FM APPROVAL AND PERFORMANCE REPORT THE FOLLOWING ITEMS, FUNCTIONS, AND OPTIONS DESCRIBE THE FM APPROVAL: • Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615. • Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T5) Hazardous (Classified) Locations per FM 3615. • Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611. • Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611. • Enclosure rating NEMA Type 4X per NEMA 250. • Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C). • Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000). Flameproof per ANSI/ISA 60079-0, -1, -7, -31 CL I, ZONE 1, AEx db eb IIC T6...T5 T6 (Tamb –40°C to +60°C) T5 (Tamb –40°C to +75°C) ZONE 21, AEx tb IIIC T80°C Tamb –40°C to +75°C IP66/IP67 CL I, ZONE 1, AEx db IIC T6...T5 T6 (Tamb –40°C to +60°C) T5 (Tamb –40°C to +75°C) ZONE 21, AEx tb IIIC T80°C Tamb –40°C to +75°C IP66/IP67 The following accessories are FM approved for use with the X9800 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 011385-001 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment The following performance criteria were verified: AUTOMATIC OPTICAL INTEGRITY TEST: The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated Automatic Optical Integrity (oi) test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector was verified to detect a fire. MANUAL OPTICAL INTEGRITY TEST: The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated. The oi test procedure, as described in the “Magnetic oi / Manual oi” section of this instruction manual, is the approved external optical test method for this detector to verify end-to-end detector function. This test replaces the function and need of a traditional external test lamp. 6.1 22 95-8555 FM Approval Description and Performance Report – Continued RESPONSE CHARACTERISTICS Very High Sensitivity Fuel Size / Flow Rate Distance feet (m) Typical Response Time (seconds) TDSA Quick Fire n-Heptane 1 x 1 foot 85 (25.9) 15 On Off Methane 32 inch plume 60 (18.3) 5 On Off Propane Torch 2 (0.6) 0.04 On On Fuel Size / Flow Rate Distance feet (m) Typical Response Time (seconds) TDSA Quick Fire n-Heptane 1 x 1 foot 50 (15.2) 8 On Off Methane 32 inch plume 35 (10.7) 3 On Off High Sensitivity Pyrodex 40 grams 10 (3) 0.1 On On Black Powder 40 grams 10 (3) 0.04 On On n-Heptane 1 x 1 foot 50 (15.2) 6 On On Fuel Size / Flow Rate Distance feet (m) Typical Response Time (seconds) TDSA Quick Fire n-Heptane 1 x 1 foot 15 (4.6) 8 On Off Low Sensitivity RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES High Sensitivity, TDSA On, Quick Fire Off Distance feet (m) Fire Source Distance feet (m) Typical Response Time (seconds) Sunlight, direct, modulated/unmodulated — 2 inch dia Heptane 10 (3) < 30 Sunlight, reflected, modulated/unmodulated — 2 inch dia Heptane 10 (3) < 30 70 w sodium vapor lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3 70 w sodium vapor lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3 250 w mercury vapor lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 2 250 w mercury vapor lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3 300 w incandescent lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3 300 w incandescent lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3 500 w shielded quartz halogen lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 2 500 w shielded quartz halogen lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 2 1500 w electric radiant heater, unmodulated 10 (3) 2 inch dia Heptane 5 (1.5) 3 1500 w electric radiant heater, modulated 10 (3) 2 inch dia Heptane 3 (0.9) 13 Two 34 w fluorescent lamps, unmodulated 3 (0.9) 2 inch dia Heptane 10 (3) 3 Two 34 w fluorescent lamps, modulated 3 (0.9) 2 inch dia Heptane 10 (3) 5 Arc welding 15 (4.6) 2 inch dia Heptane 5 (1.5) N/A False Alarm Souce 6.1 23 95-8555 FM Approval Description and Performance Report – Continued FALSE ALARM IMMUNITY High Sensitivity, TDSA On, Quick Fire Off False Alarm Souce Distance feet (m) Modulated Response Unmodulated Response — No alarm No alarm Sunlight, direct, reflected NA No alarm No alarm Arc welding 15 (4.6) No alarm No alarm 70 w sodium vapor lamp 3 (0.9) No alarm No alarm 250 w mercury vapor lamp 3 (0.9) No alarm No alarm 300 w incandescent lamp 3 (0.9) No alarm No alarm 500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm 1500 w electric radiant heater 10 (3) No alarm No alarm Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm Vibration FIELD OF VIEW Very High Sensitivity, Quick Fire Off Fuel Size Distance feet (m) Horizontal (degrees) Typical Horiz. Response Time (seconds) Vertical (degrees) Typical Vert. Response Time (seconds) n-Heptane 1 x 1 foot 42.5 (13) +45 –45 12 14 +45 –30 10 16 Methane 32 inch plume 30 (9.1) +45 –45 7 4 +45 –30 6 4 High Sensitivity, TDSA On, Quick Fire Off Fuel Size Distance feet (m) Horizontal (degrees) Typical Horiz. Response Time (seconds) Vertical (degrees) Typical Vert. Response Time (seconds) n-Heptane 1 x 1 foot 25 (7.6) +45 –45 7 7 +45 –30 6 5 Methane 32 inch plume 17.5 (5.3) +45 –45 6 3 +45 –30 4 4 High Sensitivity, TDSA On, Quick Fire On Fuel Size Distance feet (m) Horizontal (degrees) Typical Horiz. Response Time (seconds) Vertical (degrees) Typical Vert. Response Time (seconds) Black Powder 40 Grams 5 (1.5) +45 –45 0.04 0.03 +45 –30 0.04 0.04 6.1 24 95-8555 APPENDIX B CSA APPROVAL DIVISION CLASSIFICATION: Infrared Flame Detector/Controller X9800 series, rated 18-30 Vdc, 2.1 Watts to 16.5 Watts. Relay contacts rated 5 Amps @ 30 Vdc. CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5); Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3); Class III; Enclosure Type 4X; APPLICABLE REQUIREMENTS CAN/CSA-C22.2 No. 0-M91 – General requirements - Canadian Electrical Code. Part II CAN/CSA-C22.2 No. 25-1966 – Enclosures for use in Class II Groups E, F & G Hazardous Locations. CAN/CSA-C22.2 No. 30-M1986 – Explosion-Proof Enclosures for use in Class I Hazardous Locations. CAN/CSA-C22.2 No. 94-M91 – Special Purpose Enclosures. CAN/CSA-C22.2 No. 142-M1987 – Process Control Equipment. CAN/CSA-C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations. ZONE CLASSIFICATION: CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Ex db eb IIC T6...T5 T6 (Tamb = -50°C to +60°C) T5 (Tamb = -50°C to +75°C) Ex tb IIIC T95°C (Tamb = -50°C to +75°C) Seal required adjacent to enclosure IP66/IP67 Ex db IIC T6...T5 T6 (Tamb = -55°C to +60°C) T5 (Tamb = -55°C to +75°C) Ex tb IIIC T95°C (Tamb = -55°C to +75°C) Seal required adjacent to enclosure IP66/IP67 APPLICABLE REQUIREMENTS CAN/CSA-C22.2 No. 60079-0: 2007 – Electrical apparatus for explosive atmospheres. Part 0: General requirements CAN/CSA-C22.2 No. 60079-1: 2011 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures “d” CAN/CSA-C22.2 No. 60079-7: 2012 – Explosive atmospheres. Part 7: Equipment protection by increased safety “e” CAN/CSA-C22.2 No. 60079-31: 2012 – Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure “t” The following accessories are CSA approved for use with the X9800 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 011385-001 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 6.1 25 95-8555 APPENDIX C ATEX APPROVAL EC-TYPE EXAMINATION CERTIFICATE DEMKO 02 ATEX 132195X Increased Safety Model FM APPROVED Flameproof Model II 2 G II 2 G FM 0539 II 2 D II 2 D Ex db eb IIC T6...T5 Ex db IIC T6...T5 Ex tb IIIC T80°C Ex tb IIIC T80°C T6 (Tamb = –50°C to +60°C) T6 (Tamb = –55°C to +60°C) T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C) IP66/IP67. IP66/IP67. 0539 ® ® APPROVED Compliance with: EN 60079-0: 2012+A11:2013 EN 60079-1: 2014 EN 60079-7: 2007 EN 60079-31: 2009 EN 60529:1991+A1:2000+A2:2013 INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from 14-24 AWG or 2.5-0.2 mm2. The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the terminal compartment in type of explosion protection flameproof enclosure “d,” or in type of explosion protection increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e.” They shall be IP66/IP67 rated, suitable for the conditions of use, and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: • The EOL resistor can only be used within the flameproof terminal compartment. • EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. • The Infrared (IR) flame detector type X9800 is to be installed in places where there is a low risk of mechanical damage. • See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge. • Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of this manual for more information on conducting repairs.. 6.1 26 95-8555 NOTE Operational performance verified from –40°C to +75°C. NOTE An optional third party addressable module can only be used within the Ex d flameproof model unless the addressable module is component certified as Ex e for use within the Ex d e increased safety model. NOTE Refer to the “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable blanking elements. NOTE For ATEX installations, the X9800 detector housing must be electrically connected to earth ground. The following accessories are ATEX approved for use with the X9800 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 6.1 27 95-8555 APPENDIX D IECEx APPROVAL CERTIFICATE OF CONFORMITY IECEx ULD 06.0018X Ex db eb IIC T6...T5 Ex db IIC T6...T5 Ex tb IIIC T80°C Ex tb IIIC T80°C T6 (Tamb = –50°C to +60°C) or T6 (Tamb = –55°C to +60°C) T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C) IP66/IP67. IP66/IP67. Compliance with: IEC 60079-0: 2011, Ed. 6 IEC 60079-1: 2014, Ed. 7 IEC 60079-7: 2006, Ed. 4 IEC 60079-31: 2008, Ed. 1 IEC 60529: 2013, Ed. 2.2 INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from 14-24 AWG or 2.5-0.2 mm2. The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the terminal compartment in type of explosion protection flameproof enclosure “d,” or in type of explosion protection increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e.” They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: • The EOL resistor can only be used within the flameproof terminal compartment. • EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. • The Infrared (IR) flame detector type X9800 is to be installed in places where there is a low risk of mechanical damage. • See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge. • Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of this manual for more information on conducting repairs. The following accessories are IECEx approved for use with the X9800 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 6.1 28 95-8555 95-8555 FlexSonic ® Acoustic Leak Detector X3301 Multispectrum IR Flame Detector ­Corporate Office 6901 West 110th Street Minneapolis, MN 55438 USA www.det-tronics.com PointWatch Eclipse ® IR Combustible Gas Detector Phone: 952.946.6491 Toll-free: 800.765.3473 Fax: 952.829.8750 det-tronics@det-tronics.com FlexVu ® Universal Display with GT3000 Toxic Gas Detector Eagle Quantum Premier ® Safety System All trademarks are the property of their respective owners. © 2016 Detector Electronics Corporation. All rights reserved. Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.