Det-Tronics Instructions IR Flame Detector with Pulse Output X9800
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
IR Flame Detector with Pulse Output
X9800
6.1
Rev: 12/15
95-8555
Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . 16
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . 17
oi Plate Removal and Replacement . . . . . . . . . 17
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Periodic Checkout Procedure . . . . . . . . . . . . . . 17
Integral Wiring Compartment . . . . . . . . . . . . . . . 3
Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SIGNAL PROCESSING OPTIONS . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
GENERAL APPLICATION INFORMATION . . . . . . . . 4
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Response Characteristics . . . . . . . . . . . . . . . . . . 4
False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 4
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 20
Factors Inhibiting Detector Response . . . . . . . . . 5
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . . 20
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 5
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 20
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 6
X9800 Model Matrix . . . . . . . . . . . . . . . . . . . . . 21
Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 6
Protection Against Moisture Damage . . . . . . . . . 6
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 7
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 22
EOL Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . 15
APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 25
STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 15
Manual oi Test (Output to Controller) . . . . . . . . 15
APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 26
Count Test Mode (Output to Controller) . . . . . . . . 15
Fire Alarm Test (Pulse Output to Fire Alarm Panel) . 16
APPENDIX D – IECEx APPROVAL . . . . . . . . . . . . . 28
INSTRUCTIONS
IR Flame Detector
with Pulse Output
X9800
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X9800 includes the Automatic oi ® (Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
When used as a field replacement, all operating features
of the current controller are retained in addition to gaining
the advanced features of the X9800 Flame Detector. In
typical applications, the four wire X9800 can utilize all
existing system wiring.
DESCRIPTION
The evolution continues with the new X9800 IR
Flame Detector. The X9800 meets the most stringent
requirements worldwide with advanced detection
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
detector is equipped with both automatic and manual
oi test capability.
The detector has Division and Zone explosion-proof
ratings and is suitable for use in indoor and outdoor
applications. The X9800 housing is available in copperfree aluminum or stainless steel, with NEMA/Type 4X and
IP66/IP67 rating.
The X9800 with pulse/relay output is designed for use
in controller based systems. In addition to use in new
systems, it can serve as a direct field replacement
for Detector Electronics Corporation’s (Det-Tronics)
controller based flame detectors that generate a pulse
output (not compatible with R7484 and R7409B/C).
6.1
©Detector Electronics Corporation 2016
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
1
Rev: 12/15
95-8555
Magnetic oi / Manual oi
OUTPUTS
Relays
CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
The detector is furnished with fire and fault relays. The
relays are rated 5 amperes at 30 Vdc.
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or non-latching
operation.
The detector incorporates both Magnetic oi (Mag oi)
and Manual oi (Man oi) test capabilities. These tests
provide pulses (80 to 100 CPS) to the controller (R7404
or R7494) when the detector is not in fault. If the test
is successful, the controller indicates a fire and the
appropriate zone output is active.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
NOTE
If the detector is in a fault condition, a successful
Mag oi or Man oi test cannot be performed.
Latching relays can be reset by removing input power
(0.1 second minimum).
An alarm condition will normally override a fault
condition, unless the nature of the fault condition
impairs the ability of the detector to generate or
maintain an alarm output, i.e., loss of operating power.
The Mag oi test is performed by placing a magnet at
the location marked “MAG OI” on the outside of the
detector (see Figure 2). This action causes the detector
to immediately send pulses to the controller. Controller
response is as follows:
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions. Table 1 indicates the condition of the
LED for each status.
•
The Zone LED blinks.
•
The digital display indicates which Zone is in
alarm.
•
The status indicator shows “6” (fire).
oi (OPTICAL INTEGRITY)
Table 1—Detector Status Indicator
Automatic oi
Detector Status
The X9800 includes the Automatic oi feature — a
calibrated performance test that is automatically
performed once per minute to verify complete detector
operation capabilities. No testing with an external test
lamp is required. The detector automatically performs
the same test that a maintenance person with a test
lamp would perform — once every minute. However, a
successful Automatic oi test does not produce an alarm
condition.
Power On/Normal Auto oi
(no fault or fire alarm)
Green
Power On/Normal Man oi
Green, flashing off for
0.5 sec. every 5 sec.
Fault
Pre-Alarm/Background IR
Fire (Alarm)
Yellow
Red, flashing on for
1 sec. and off for 1 sec.
Steady Red
On Power-Up, The LED Flashes in Sequence as Follows,
Indicating Sensitivity and Signal Processing Status
The X9800 signals a fault condition when less than half of
the detection range remains. This is indicated by the fault
relay and is evident by the yellow color of the LED on the
face of the detector. See the “Troubleshooting” section
for further information.
6.1
LED Indicator
2
Low IR Sensitivity
Medium IR Sensitivity
High IR Sensitivity
Very High IR Sensitivity
One Green Flash
Two Green Flashes
Three Green Flashes
Four Green Flashes
Quick Fire / TDSA IR Signal
TDSA only IR Signal
Quick Fire only
One Yellow Flash
Two Yellow Flashes
Three Yellow Flashes
95-8555
IMPORTANT
Mag oi can be performed with the controller’s
(R7404/R7494) keylock switch in either the
NORMAL or TEST position. In NORMAL, the
controller goes into alarm and activates its outputs.
If no controller alarm output is desired, place
the keylock switch in the TEST position before
touching the magnet to the outside of the detector.
Man oi operates only with the keylock switch in
the TEST position.
INTEGRAL WIRING COMPARTMENT
All external wiring to the device is connected within
the integral junction box. The detector is furnished with
four conduit entries, with either 3/4 inch NPT or M25
threads.
SIGNAL PROCESSING OPTIONS
The X9800 features signal processing options. These
options determine the type of logic that the detector will
use for processing fire signals to customize the X9800
to the application. Two signal processing options are
available for the X9800:
During the entire test, the detector gives no indication
of alarm.
To reset the controller status and alarms, place the
keylock switch in RESET. Return the keylock switch to
NORMAL when testing is complete.
––
TDSA enabled
––
Both TDSA and Quick Fire enabled (either initiates
fire alarm).
The Man oi test is nearly identical to the Mag oi test,
except for the manner in which the test is initiated:
Time Domain Signal Analysis (TDSA)
•
Place the keylock switch on the controller (R7404/
R7494) in the TEST position.
The TDSA signal processing technique analyzes the
input signal in real time, requiring the IR signal to flicker
randomly in order to recognize it as a fire condition.
•
Press the SELECT button to select the appropriate
detector for test.
•
Press the TEST/ACCEPT button to initiate the test.
Using TDSA signal processing, the X9800 ignores
regularly chopped blackbody sources (occurring in areas
where moving conveyors and hot objects in proximity
to one another result in a regularly chopped IR signal),
because it looks for a less uniform signal. However, in
the presence of a regularly chopped signal, the unit is
more susceptible to false alarms due to sporadic IR that
functions as a trigger when occurring in conjunction with
the regularly chopped signal.
Controller and detector responses are identical to the
Mag oi test described above.
To reset the controller status and alarms, place the
keylock switch in RESET. Return the keylock switch to
NORMAL when testing is complete.
Quick Fire (High Speed)
NOTE
Refer to Appendix A for FM verification of the
Det-Tronics o i function.
The Quick Fire (High Speed) feature can be used in
conjunction with the TDSA signal processing method.
This method overrides TDSA requirements in the event
of an intense signal. When Quick Fire is activated, the
detector is capable of responding to an intense fire signal
in less than 30 milliseconds (0.030 seconds). Using
the Quick Fire feature in conjunction with TDSA signal
processing allows the detector to provide a high speed
response to a large, non-flickering fire (such as in high
pressure gas applications) while maintaining an ability to
respond to smaller fires.
COMMUNICATION
The X9800 is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 uses Modbus protocol, with the
detector configured as a slave device.
DATA LOGGING
Data logging capability is also provided. Status conditions
such as normal, power down, general and oi faults, prealarm, fire alarm, time, and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active,
and again when the status changes. Data is accessible
using the Det-Tronics Inspector Connector accessory or
RS-485.
6.1
3
95-8555
GENERAL APPLICATION
INFORMATION
FALSE ALARM SOURCES
The detector has been designed to ignore steady state
infrared sources that do not have a flicker frequency
characteristic of a fire, however, it should be noted that
if these steady state infrared sources are hot enough
to emit adequate amounts of infrared radiation in the
response range of the IR sensor and if this radiation
becomes interrupted from the view of the detector in a
pattern characteristic of a flickering flame, the IR sensor
can respond.
RESPONSE CHARACTERISTICS
Response is dependent on the detector’s sensitivity
setting, distance, type of fuel, temperature of the fuel,
and time required for the fire to come to equilibrium. As
with all fire tests, results must be interpreted according to
an individual application.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics.
Any object having a temperature greater than 0° Kelvin
(–273°C) emits infrared radiation. The hotter the object,
the greater the intensity of the emitted radiation. The
closer the infrared source is to the detector, the greater
the potential for a false alarm. The IR sensor can respond
to IR radiation sources that can meet the amplitude and
flicker requirements of the detector such as vibrating hot
objects.
Welding
It is recommended that the system be bypassed during
welding operations in situations where the possibility of a
false alarm cannot be tolerated. Gas welding mandates
system bypass, since the gas torch is an actual fire. Arc
welding rods can contain organic binder materials in
the flux that burn during the welding operation and are
detectable by the X9800. Welding rods with clay binders
do not burn and will not be detected by the X9800.
However, system bypass is always recommended, since
the material being welded may be contaminated with
organic substances (paint, oil, etc.) that will burn and
possibly cause the X9800 to alarm.
Although the detector is designed to reduce false
actuations, certain combinations of ambient radiation
must be avoided. For example, if IR radiation with an
intensity that exceeds the fire threshold of the IR sensor
should reach the detector as a flickering signal, and if at
the same time an electric arc welding signal also reaches
the detector, an alarm output will be generated.
Artificial Lighting
NOTE
Radiation generated by false alarm sources such
as periodic lightning or sparks in the area can be
effectively ignored by the detector using the arc
rejection feature or time delay.
The X9800 should not be located within 3 feet (0.9 m)
of artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
EMI/RFI Interference
The X9800 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE marked. It will
not respond to a 5 watt walkie-talkie at distances greater
than 1 foot (0.3 m).
Non-Carbon Fires
The response of the X9800 is limited to carbonaceous
fuels. It should not be used to detect fires from fuels that
do not contain carbon, such as hydrogen, sulfur, and
burning metals.
6.1
4
95-8555
IMPORTANT SAFETY NOTES
FACTORS INHIBITING DETECTOR RESPONSE
Windows
WARNING
Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage. This type of damage
could be undetected and could result in failure to
see a fire and/or false alarm.
Glass and Plexiglas windows significantly attenuate
radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Det-Tronics for recommendations regarding window
materials that will not attenuate radiation.
Obstructions
Radiation must be able to reach the detector in order
for it to respond. Care must be taken to keep physical
obstructions out of the line of view of the detector.
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be done
by a properly trained person.
Smoke
Smoke will absorb radiation. If accumulations of dense
smoke can be expected to precede the presence of a flame,
then detectors that are used in enclosed areas should be
mounted on the wall approximately 3 feet (0.9 m) from the
ceiling where the accumulation of smoke is reduced.
Detector Viewing Windows
It is important to keep the detector viewing windows as
free of contaminants as possible in order to maintain
maximum sensitivity. Commonly encountered substances
that can significantly attenuate IR radiation include, but
are certainly not limited to, the following:
––
Dust and dirt buildup
––
Paint overspray
––
Water and ice
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing system tests or maintenance.
CAUTION
The IR flame detectors are to be installed in
places where the risk of mechanical damages is
low.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.
6.1
5
95-8555
INSTALLATION
NOTE
The recommended lubricant for threads and
O‑rings is a silicone free grease (p/n 005003001) available from Detector Electronics. Under
no circumstances should a lubricant containing
silicone be used.
•
Dense fog and rain as well as certain gases and
vapors can absorb IR radiation and reduce the
sensitivity of the detector.
•
If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
•
For ATEX/IECEx installations, the X9800 Flame
Detector housing must be electrically connected to
earth ground.
DETECTOR POSITIONING
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:
•
Identify all high risk fire ignition sources.
•
Be sure that enough detectors are used to adequately
cover the hazardous area.
•
Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
•
Verify that all detectors in the system are properly
located and positioned so that any fire hazards are
within both the Field of View (FOV) and detection
range of the detector. The Det-Tronics Q1201C
Laser Aimer is recommended for establishing the
detector’s FOV. Refer to Appendix A for specific
information regarding detector range and FOV.
•
The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain (see
Figure 1). The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.
•
DETECTOR ORIENTATION
Refer to Figure 2 and ensure that the oi plate will be
oriented as shown when the X9800 is mounted and
sighted. This will ensure proper operation of the oi
system and will also minimize the accumulation of
moisture and contaminants between the oi plate and the
viewing windows.
IMPORTANT
If removed, the o i plate must be securely
tightened to ensure proper operation of
the o i system (40 oz./inches [28.2 N . cm]
recommended).
oi PLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
The detector must be mounted on a rigid surface in
a low vibration area.
IR VIEWING WINDOW
oi MAGNET
B2174
DETECTOR
STATUS INDICATOR
Figure 2—Front View of the X9800
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
PROTECTION AGAINST MOISTURE DAMAGE
It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
operation and is the responsibility of the installer.
INCORRECT
If conduit is used, we recommend installing drains,
according to local codes, at water collection points
to automatically drain accumulated moisture. It is
also recommended to install at least one breather,
according to local codes, at upper locations to provide
ventilation and allow water vapor to escape.
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
D1974
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon
6.1
6
95-8555
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
WARNING
All entries must contain appropriately rated plugs
or fittings. It is required that each plug or fitting
be wrench-tightened to an appropriate installation
torque and meet the minimum thread engagement
requirements per the applicable local standards,
codes, and practices in order to retain the defined
ratings. PTFE sealant or equivalent should be used
on NPT threads.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are
highly recommended to prevent water ingress in
outdoor applications. Units with M25 threads must use
an IP66/IP67 washer to prevent water ingress.
IMPORTANT
Devices certified for hazardous locations shall be
installed in accordance with EN/IEC 60079-14 and
NEC 505.
WIRING PROCEDURE
Wire Size and Type
Detector Installation
The system should be wired according to local codes.
The wire size selected should be based on the number
of detectors connected, the supply voltage, and the
cable length. Typically 16 AWG or 2.5 mm2 shielded
cable is recommended. Wires should be stripped 3/8
inch, 9 mm. In some cases where the X9800 is replacing
existing pulse output detectors, the wiring and power
supplies may not be adequate. Consult the factory for
assistance.
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 inch (M9) bolts with a length
of at least 1 inch (25 mm). The surface must also have
sufficient capacity to hold the detector and mounting arm
weights (See “Specifications” section). Refer to the Q9033
Mounting Arm manual , number 95-8686, for additional
mounting information. See Figure 3 for dimensions.
Detector Wiring
IMPORTANT
A minimum input voltage of 18 Vdc must be
present at the X9800.
IMPORTANT
If installing an X9800 in place of an existing
detector, be sure to move the “A” Lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source. Do not apply 290 Vdc to
the X9800.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures
6 through 10. Consult the factory if not using shielded
cable.
1. Make field connections following local ordinances
and guidelines in this manual.
The “B” (pulse output) and “D” (oi driver) leads from
each detector should be shielded from the “B” and
“D” leads of all other detectors in order to prevent
false alarms resulting from crosstalk between zones.
It is recommended that the “A” and “C” leads also be
shielded to provide maximum immunity to EMI/RFI.
(See Figures 6 to 10.)
In applications where the wiring cable is installed in
conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate disconnect
capability must be provided.
Figure 4 shows the wiring terminal strip located
inside the detector’s integral junction box.
Figure 5 shows the wiring terminal identification for
the X9800 detector with pulse output.
Leave the shield open at the detector end and
permanently isolate it from accidental contact with
the case and/or other conductors. At the controller/
fire panel end, connect the shield and power minus
(–) to chassis (earth) ground either directly or
through a 0.47 µF 400 Volt non-polarized capacitor
(not supplied). (Refer to Figures 6 through 10.)
CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.
6.1
7
95-8555
4X ø0.42
(1.1)
3.0
(7.6)
4.0
(10.2)
13.1
(33.4)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
3.0
(7.6)
4.0
(10.2)
10.6
(27.0)
E2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
Figures 11 and 12 provide examples of typical
installations with a X9800 wired to a fire alarm
panel.
Figure 13 shows an EOL resistor installed within the
integral wiring compartment of the detector (refer to
“EOL Resistors” for details).
2. Check all field wiring to be sure that the proper
connections have been made.
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
3. Make the final sighting adjustments and use a 14
mm hex wrench to ensure that the mounting arm
assembly is tight.
9
19
8
18
PULSE OUT
29
SPARE
28
SPARE
7
COM FIRE
17
COM FIRE
27
6
N.O. FIRE
16
N.O. FIRE
26
5
N.C. FIRE
15
N.C. FIRE
25
4
COM FAULT
14
COM FAULT
24
RS-485 A
3
N.O. FAULT
13
N.O. FAULT
23
RS-485 B
2
+ Vin
12
+ Vin
22
MAN Oi
1
– Vin
11
– Vin
21
– Vin
D2070
Figure 5—X9800 Pulse Wiring Terminal Identification
Figure 4—X9800 Terminal Block
6.1
8
95-8555
NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X9800
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
DETECTOR 5
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-9
J1-17
DETECTOR 6
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-10
J1-18
DETECTOR 7
X9800
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
–
2
+
–
3
J2
R7404 CONTROLLER
} 10 TO 38 VDC
ZONE OUTPUT 1
33
ZONE OUTPUT 2
34
(A) +290 VDC
ZONE OUTPUT 3
35
4
B - INPUT 1
ZONE OUTPUT 4
36
5
B - INPUT 2
ZONE OUTPUT 5
37
6
B - INPUT 3
ZONE OUTPUT 6
38
7
B - INPUT 4
ZONE OUTPUT 7
39
8
B - INPUT 5
ZONE OUTPUT 8
40
9
B - INPUT 6
FIRE LOGIC “A”
41
10
B - INPUT 7
FIRE LOGIC “B”
42
11
B - INPUT 8
ALARM OUTPUT
43
12
D1-1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D1-2 oi DRIVER
OUTPUTS INHIBITED
45
14
D1-3 oi DRIVER
FAULT OUTPUT
46
15
D1-4 oi DRIVER
EXTERNAL ACCEPT
47
16
D1-5 oi DRIVER
STATUS & DET. OUTPUT S1
48
17
D1-6 oi DRIVER
STATUS & DET. OUTPUT S2
49
18
D1-7 oi DRIVER
STATUS & DET. OUTPUT S3
50
19
D1-8 oi DRIVER
STATUS & DET. OUTPUT S4
51
20
D2-1 oi DRIVER
STATUS & DET. OUTPUT S5
52
21
D2-2 oi DRIVER
STATUS & DET. OUTPUT S6
53
22
D2-3 oi DRIVER
STATUS & DET. OUTPUT S7
54
23
D2-4 oi DRIVER
STATUS & DET. OUTPUT S8
55
24
D2-5 oi DRIVER
DATA BUS 0
56
25
D2-6 oi DRIVER
DATA BUS 1
57
26
D2-7 oi DRIVER
DATA BUS 2
58
27
D2-8 oi DRIVER
DATA BUS 3
59
28
DMA OUT AVAILABLE
DATA BUS 4
60
29
DMA OUT
DATA BUS 5
61
30
DMA IN
DATA BUS 6
62
31
DATA STROBE
DATA BUS 7
63
32
DMA IN AVAILABLE
CHASSIS (EARTH) GND
64
A2182
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X9800
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
62
63
0.47 μF / 400 VDC
NON-POLARIZED
64
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 6—A Typical System, X9800 Detectors Wired to R7404 Controller
6.1
9
95-8555
NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X9800
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
#2
#1
#19
#22
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+290 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
STATUS & DET. OUTPUT S3
50
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
DATA BUS 5
61
DATA BUS 6
62
DATA BUS 7
63
17
18
#2
#1
#19
#22
21
22
23
24
25
J1-9
J1-17
26
27
28
#2
#1
#19
#22
#2
#1
#19
#22
29
30
J1-10
J1-18
DETECTOR 7
X9800
1
20
DETECTOR 6
X9800
J1
+
19
DETECTOR 5
X9800
24
VDC
31
32
J2
R7404 STAR LOGIC CONTROLLER
D7 oi DRIVER
D8 oi DRIVER
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED
EARTH GROUND
64
A2183
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X9800
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
62
63
0.47 μF / 400 VDC
NON-POLARIZED
64
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 7—A Typical System, X9800 Detectors Wired to R7404 Star Logic Controller
6.1
10
95-8555
X9800
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
#2
#1
#19
#22
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+24 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
STATUS & DET. OUTPUT S3
50
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
DATA BUS 5
61
DATA BUS 6
62
DATA BUS 7
63
17
18
#2
#1
#19
#22
21
22
23
24
25
J1-9
J1-17
26
27
28
#2
#1
#19
#22
#2
#1
#19
#22
29
30
J1-10
J1-18
DETECTOR 7
X9800
1
20
DETECTOR 6
X9800
J1
+
19
DETECTOR 5
X9800
24
VDC
31
32
J2
R7494 CONTROLLER
D7 oi DRIVER
D8 oi DRIVER
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED
EARTH GROUND
64
A2184
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X9800
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
62
63
0.47 μF / 400 VDC
NON-POLARIZED
64
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 8—A Typical System, X9800 Detectors Wired to R7494 Controller
6.1
11
95-8555
R7495 CONTROLLER
(NOT FM APPROVED)
X9800
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X9800
#2
#1
#19
#22
#2
#1
#19
#22
33
34
J2-45
J2-37
DETECTOR 3
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-46
J2-38
DETECTOR 4
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
47
B5
48
B6
49
B7
50
B8
DETECTOR 6
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-50
J2-42
DETECTOR 8
A2185
TO J1-2
TERMINAL IDENTIFICATION FOR X9800
WITH PULSE OUTPUT.
TERMINAL NO.
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
3
4
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
0.47 μF / 400 VDC
NON-POLARIZED
5
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 9—A Typical System, X9800 Detectors Wired to R7495 Controller
6.1
12
95-8555
NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO
TERMINAL J2-34 (290 VDC).
R7405 CONTROLLER
(NOT FM APPROVED)
X9800
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X9800
#2
#1
#19
#22
#2
#1
#19
#22
33
J2-45
J2-37
DETECTOR 3
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-46
J2-38
DETECTOR 4
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
34
+290 VDC
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
DETECTOR 6
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X9800
#2
#1
#19
#22
#2
#1
#19
#22
J2-50
J2-42
DETECTOR 8
47
B5
48
B6
49
B7
50
B8
A2186
TO J1-2
TERMINAL IDENTIFICATION FOR X9800
WITH PULSE OUTPUT.
TERMINAL NO.
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
3
FUNCTION
4
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
0.47 μF / 400 VDC
NON-POLARIZED
5
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 10—A Typical System, X9800 Detectors Wired to R7405 Controller
6.1
13
95-8555
X9800 DETECTOR
FIRE ALARM PANEL
9
19
8
18
COM FIRE2
7
N.O. FAULT1
3
+
24 VDC
+ Vin
2
–
26
END OF
LINE DEVICE 4
25
14
RS-485 A
24
13
RS-485 B
23
MAN Oi
22
12
– Vin
1
28
27
15
COM FAULT1
4
29
SPARE
16
N.C. FIRE2
5
SPARE
17
N.O. FIRE2
6
ALARM
PULSE OUT
– Vin
11
21
oi TEST 3
WIRING NOTES:
B2187
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
Figure 11—Ex d Wiring Option
X9800 DETECTOR
FIRE ALARM PANEL
9
19
8
ALARM
EOL
DEVICE 4
7
ALARM
6
5
4
3
+
24 VDC
2
–
1
PULSE OUT
18
COM FIRE2
N.O. FIRE2
N.C. FIRE2
COM FAULT1
N.O. FAULT1
+ Vin
– Vin
SPARE
29
SPARE
28
17
27
16
26
15
25
14
RS-485 A
24
13
RS-485 B
23
MAN Oi
22
12
11
– Vin
21
oi TEST 3
B2188
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
4 EOL RESISTOR SUPPLIED BY PANEL.
Figure 12—Ex e Wiring Option
6.1
14
95-8555
STARTUP PROCEDURE
EOL RESISTORS
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
by EOL resistors, observe the following guidelines when
installing the resistors:
When installation of the equipment is complete, apply
power and allow 20 to 30 minutes for the detector’s
heated optics to reach equilibrium. Then perform one or
more of the following tests:
1. Required EOL resistor power rating must be 5 watts
minimum.
Man oi Test — Tests detector output and wiring, without
generating a fire alarm.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies to
ATEX/IECEx installations only.
Count Test Mode — Measures actual detector output to
controller (cps), without generating a fire alarm.
Fire Alarm Test — For complete system test including
detector relays. Generates fire alarm output.
MANUAL oi TEST (Output to Controller)
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches, 40 mm.
1. Place the keylock switch in the TEST position.
3. Bend the leads and install the EOL resistor as
shown in Figure 13.
2. Press the SELECT button to display the desired
zone on the ZONE indicator on the front panel of the
controller.
4. Maintain a 3/8 inch, 10 mm minimum gap between
the resistor body and the terminal block or any
other neighboring parts.
3. Press and hold the TEST button. The ZONE
OUTPUT LED for the tested zone flashes and
the SYSTEM STATUS display indicates a “6” (fire
condition) if the test is successful.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused
apertures shall be closed with suitable blanking
elements.
4. Release the TEST button. The ZONE OUTPUT LED
for the tested zone should remain on steadily.
5. Return to step 2 to test the next detector.
If the system responds differently than indicated
above, proceed with the count test for the problem
zone to verify detector and wiring operation.
3/8 INCH (10 MM) GAP MINIMUM
COUNT TEST MODE (Output to Controller)
When in the Count Test mode, the frequency of the digital
pulses from the detector is displayed on the ZONE
and DETECTOR indicators on the controller faceplate.
The Count Test mode may be used to check the signal
(cps) from a test fire or false alarm source. This can be
useful during system set-up for sensitivity and time delay
settings. This test is performed in the following manner:
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
1. Place the keylock switch in the TEST position.
2. Simultaneously press and release the SELECT and
TEST buttons. The Status display will change from
a “1” to an “8” indicating that the controller is in the
Count Test mode of operation.
Figure 13—EOL Resistor Installation
6.1
15
95-8555
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
3. Press the SELECT button until the desired zone is
displayed on the ZONE indicator on the controller
front panel.
4. Press and hold the TEST button. The DETECTOR/
ZONE display indicates the counts per second
(cps) received from the detector. If the counts per
second exceeds 99, the FIRE LOGIC LEDs are
illuminated to indicate that the number shown on
the display must be multiplied by 10. The normal
reading for an oi test is 80 to 110 cps. For a live
fire test, 270 - 330 cps will be generated.
3. Check input power to the unit.
4. Check system and detector logs.
5. Turn off the input power to the detector and check
all wiring for continuity. Important: Disconnect
wiring at the detector before checking system
wiring for continuity.
A zero reading may indicate a dirty window, oi problem,
faulty detector, or defective wiring.
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
high levels of background IR radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears, extreme
background IR radiation is present. Re-adjust the
view of the detector away from the IR source or
relocate the detector.
Release the Test button, the ZONE and DETECTOR
display should drop to a reading of 0 to 1 counts per
second.
FIRE ALARM TEST (Pulse Output to Fire Alarm Panel)
1. Disable any extinguishing equipment that is
connected to the system.
If none of these actions corrects the problem, return the
detector to the factory for repair.
2. Apply input power to the system.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
3. Initiate a live fire test or a Mag o i test. (See
“Magnetic oi / Manual oi” under “Optical Integrity”
in the “Description” section of this manual.)
MAINTENANCE
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
WARNING
To avoid a potential electrostatic discharge (ESD),
the painted surface of the detector should only be
cleaned with a damp cloth.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Det-Tronics
Q1201C Laser Aimer is recommended for this
purpose.)
6. Enable extinguishing equipment when the test is
complete.
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
TROUBLESHOOTING
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X9800
must be kept relatively clean. Refer to the
following procedure for cleaning instructions.
1. Disable any extinguishing equipment that is
connected to the unit.
6.1
16
95-8555
CLEANING PROCEDURE
LOOSEN TWO CAPTIVE SCREWS
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
To clean the windows and oi plate, use the Det-Tronics
window cleaner (p/n 001680-001) and a soft cloth, cotton
swab, or tissue and refer to the following procedure:
GRASP VISOR AND
REMOVE oi PLATE
1. Disable any extinguishing equipment that is
connected to the unit.
B2175
Figure 14—oi Plate Removal
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.
oi PLATE REMOVAL AND REPLACEMENT
1. Disable any extinguishing equipment that is
connected to the unit.
2. Loosen the two captive screws, then grasp the oi
plate by the visor and remove it from the detector.
See Figure 14.
2. Clean the viewing window and reflective surfaces
of the oi plate using a clean cloth, cotton swab,
or tissue, and the Det-Tronics window cleaning
solution. Use Isopropyl alcohol for contaminations
that the Det-Tronics window cleaning solution can
not remove. If a fault condition is still indicated after
cleaning, remove and clean the oi plate using the oi
Plate Removal and Replacement procedure.
3. Install the new (or cleaned) oi plate.
4. Recalibrate the detector’s oi system. Refer to the
Inspector Monitor manual, number 95-8581, for
instructions regarding oi plate replacement and oi
system recalibration.
CAUTION
Do not replace the oi reflector plate without also
recalibrating the oi system.
IMPORTANT
When used in extreme environments, the reflective
surface of the detector oi plate may eventually
deteriorate, resulting in reoccurring oi faults and
the need for oi plate replacement.
Recalibration of the oi system requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See the “Ordering Information” section for details.
PERIODIC CHECKOUT PROCEDURE
A checkout of the system using the Mag oi or Man oi
feature should be performed on a regularly scheduled
basis to ensure that the system is operating properly. To
test the system, perform the “Manual oi Test,” “Count Test
Mode,” or “Fire Alarm Test” as described in the “Startup
Procedure” section of this manual.
CLOCK BATTERY
The real time clock has a backup battery that will
operate the clock with no external power. Return the
device to the factory for battery replacement if needed.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
6.1
17
95-8555
FEATURES
SPECIFICATIONS
•
Responds to a fire in the presence of modulated
blackbody radiation (i.e., heaters, ovens, turbines)
without false alarm
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
•
High speed capability — 30 milliseconds
•
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms)
•
Pulse output for compatibility with controller based
systems
•
Microprocessor controlled heated optics
increased resistance to moisture and ice
•
Automatic, manual, or magnetic oi testing
•
Easily replaceable oi plate
•
Fire and fault relays
•
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
•
Operates under adverse weather conditions
•
Mounting arm allows easy sighting
•
Integral wiring compartment for ease of installation
•
Explosion-proof/flame-proof
detector
housing.
Meets FM, CSA, ATEX, and IECEx certification
requirements
•
Class A wiring per NFPA-72 (relay connections).
(Pulse output is equivalent to class A when detectors
are installed in a redundant configuration)
•
3 year warranty
•
Advanced signal processing (TDSA)
•
RFI and EMC Directive Compliant
or CSA compliance, the power source must
F
utilize a SELV (Safety Extra Low Voltage) or Class
2 style power supply.
POWER CONSUMPTION—
Without heater: 2.1 watts at 24 Vdc nominal;
3.5 watts at 24 Vdc in alarm.
2.2 watts at 30 Vdc nominal;
4.0 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power: 16.5 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
for
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or nonlatching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from -55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 15.
RESPONSE TIME—
32 inch methane plume: < 10 seconds.
1 foot x 1 foot n-Heptane: < 15 seconds.
(See “Appendix A” for details.)
6.1
18
95-8555
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
VIEWING ANGLE
15°
30°
0°
100
SHIPPING WEIGHT (Approximate)—
Aluminum:
7 pounds (3.2 kilograms).
Stainless Steel:
14.6 pounds (6.7 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).
15°
30°
90
80
45°
45°
70
60
DETECTION
DISTANCE
(PERCENT)
WARRANTY PERIOD—
3 years
50
40
CERTIFICATION—
30
20
FM
10
®
APPROVED
A1288
For complete approval details, refer to the appropriate
Appendix:
Figure 15—Detector Cone of Vision
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMENSIONS—
See Figure 16.
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
4.7
(11.9)
B2223
10.2
(25.9)
4.8
(12.2)
Figure 16—Dimensions in Inches (cm)
6.1
19
95-8555
REPLACEMENT PARTS
ORDERING INFORMATION
The detector is not designed to be repaired in the field. If
a problem should develop, refer to the “Troubleshooting”
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the
factory for repair.
When ordering, please specify:
X9800 IR Flame Detector with Pulse Output
Refer to the X9800 Model Matrix below for details
Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel detectors
REPLACEMENT PARTS
Part Number
Description
009208-002
oi Replacement kit for X52/X22/X98 (5 Reflector Plates)
with Inspector Connector and Monitor
Replacement oi Reflector Plate for X52/X22/X98
(requires Inspector Connector to calibrate)
007307-002
ACCESSORIES
Part Number
Description
000511-029
103881-001
Converter RS485 to RS232
Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
Flame Inspector Monitor CD
Model 475 HART Communicator
Magnet
Magnet and Adapter for Extension Pole
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
Q1120A1001 Paint Shield mounting ring (AL)
Q1198A1001 Dual Air Shield/Flange Mount (X9800 only)/(AL)
Q1201 Laser
Laser Battery, 3V Lithium (laser)
Q1201C1001 X-Series Laser Holder (AL/Plastic)
Q2000A1001 X-Series Weather Shield (AL)
Q9033B Stainless Steel Mounting Arm Assembly is for
aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum
detectors only
Q9033 Collar Attachment
Stop Plug, 3/4” NPT, AL
Stop Plug, 3/4” NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4”NPT, AL
Stop Plug, 20 Pack, 3/4”NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
Window cleaner (6 pack)
O-ring - Rear Cover (Viton) - black or brown
1 oz grease for detectors (non-silicon)
O-ring - Rear Cover (Fluorosilicone) - blue
1 oz PTFE silicone free lubricant
007819-001
007819-002
009207-001
103922-001
102740-002
008082-001
007739-001
007240-001
007818-001
007818-002
009177-001
009199-001
006097-001
102871-001
007255-001
007338-001
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure.
007290-001
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
007290-002
011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
001680-001
107427-040
005003-001
104346-154
012549-001
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.
Return all equipment transportation prepaid to the factory
in Minneapolis.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
6.1
20
95-8555
X9800 MODEL MATRIX
MODEL DESCRIPTION
X9800
Single Frequency IR Flame Detector
TYPE
MATERIAL
A
Aluminum
S
Stainless Steel (316)
TYPE
THREAD TYPE
4M
4 PORT, METRIC M25
4N
4 PORT, 3/4" NPT
TYPE
15
OUTPUTS
Relay and Pulse
TYPE
W
APPROVALS
FM/CSA/ATEX/IECEx
TYPE
6.1
CLASSIFICATION
1
Division/Zone Ex d e
2
Division/Zone Ex d
21
95-8555
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS, AND OPTIONS DESCRIBE THE FM APPROVAL:
•
Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615.
•
Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T5) Hazardous (Classified) Locations per FM 3615.
•
Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611.
•
Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
•
Enclosure rating NEMA Type 4X per NEMA 250.
•
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
•
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
CL I, ZONE 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
CL I, ZONE 1, AEx db IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
The following accessories are FM approved for use with the X9800 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic Optical Integrity (oi) test for each sensor. Upon removal of the contamination, the detector fault was cleared
and the detector was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
The oi test procedure, as described in the “Magnetic oi / Manual oi” section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.
6.1
22
95-8555
FM Approval Description and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
Size / Flow Rate
Distance
feet (m)
Typical Response Time
(seconds)
TDSA
Quick Fire
n-Heptane
1 x 1 foot
85 (25.9)
15
On
Off
Methane
32 inch plume
60 (18.3)
5
On
Off
Propane
Torch
2 (0.6)
0.04
On
On
Fuel
Size / Flow Rate
Distance
feet (m)
Typical Response Time
(seconds)
TDSA
Quick Fire
n-Heptane
1 x 1 foot
50 (15.2)
8
On
Off
Methane
32 inch plume
35 (10.7)
3
On
Off
High Sensitivity
Pyrodex
40 grams
10 (3)
0.1
On
On
Black Powder
40 grams
10 (3)
0.04
On
On
n-Heptane
1 x 1 foot
50 (15.2)
6
On
On
Fuel
Size / Flow Rate
Distance
feet (m)
Typical Response Time
(seconds)
TDSA
Quick Fire
n-Heptane
1 x 1 foot
15 (4.6)
8
On
Off
Low Sensitivity
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
High Sensitivity, TDSA On, Quick Fire Off
Distance
feet (m)
Fire Source
Distance
feet (m)
Typical Response Time
(seconds)
Sunlight, direct, modulated/unmodulated
—
2 inch dia Heptane
10 (3)
< 30
Sunlight, reflected, modulated/unmodulated
—
2 inch dia Heptane
10 (3)
< 30
70 w sodium vapor lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
70 w sodium vapor lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
250 w mercury vapor lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
250 w mercury vapor lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
300 w incandescent lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
300 w incandescent lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
500 w shielded quartz halogen lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
500 w shielded quartz halogen lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
1500 w electric radiant heater, unmodulated
10 (3)
2 inch dia Heptane
5 (1.5)
3
1500 w electric radiant heater, modulated
10 (3)
2 inch dia Heptane
3 (0.9)
13
Two 34 w fluorescent lamps, unmodulated
3 (0.9)
2 inch dia Heptane
10 (3)
3
Two 34 w fluorescent lamps, modulated
3 (0.9)
2 inch dia Heptane
10 (3)
5
Arc welding
15 (4.6)
2 inch dia Heptane
5 (1.5)
N/A
False Alarm Souce
6.1
23
95-8555
FM Approval Description and Performance Report – Continued
FALSE ALARM IMMUNITY
High Sensitivity, TDSA On, Quick Fire Off
False Alarm Souce
Distance feet
(m)
Modulated Response
Unmodulated Response
—
No alarm
No alarm
Sunlight, direct, reflected
NA
No alarm
No alarm
Arc welding
15 (4.6)
No alarm
No alarm
70 w sodium vapor lamp
3 (0.9)
No alarm
No alarm
250 w mercury vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
10 (3)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Vibration
FIELD OF VIEW
Very High Sensitivity, Quick Fire Off
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)
Vertical
(degrees)
Typical Vert. Response
Time (seconds)
n-Heptane
1 x 1 foot
42.5
(13)
+45
–45
12
14
+45
–30
10
16
Methane
32 inch plume
30
(9.1)
+45
–45
7
4
+45
–30
6
4
High Sensitivity, TDSA On, Quick Fire Off
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)
Vertical
(degrees)
Typical Vert. Response
Time (seconds)
n-Heptane
1 x 1 foot
25
(7.6)
+45
–45
7
7
+45
–30
6
5
Methane
32 inch plume
17.5
(5.3)
+45
–45
6
3
+45
–30
4
4
High Sensitivity, TDSA On, Quick Fire On
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)
Vertical
(degrees)
Typical Vert. Response
Time (seconds)
Black
Powder
40 Grams
5
(1.5)
+45
–45
0.04
0.03
+45
–30
0.04
0.04
6.1
24
95-8555
APPENDIX B
CSA APPROVAL
DIVISION CLASSIFICATION:
Infrared Flame Detector/Controller X9800 series, rated 18-30 Vdc, 2.1 Watts to 16.5 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);
Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3);
Class III; Enclosure Type 4X;
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91
–
General requirements - Canadian Electrical Code. Part II
CAN/CSA-C22.2 No. 25-1966
–
Enclosures for use in Class II Groups E, F & G Hazardous Locations.
CAN/CSA-C22.2 No. 30-M1986
–
Explosion-Proof Enclosures for use in Class I Hazardous Locations.
CAN/CSA-C22.2 No. 94-M91
–
Special Purpose Enclosures.
CAN/CSA-C22.2 No. 142-M1987
–
Process Control Equipment.
CAN/CSA-C22.2 No. 213-M1987
–
Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations.
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex db eb IIC T6...T5
T6 (Tamb = -50°C to +60°C)
T5 (Tamb = -50°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -50°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
Ex db IIC T6...T5
T6 (Tamb = -55°C to +60°C)
T5 (Tamb = -55°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -55°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0: 2007
–
Electrical apparatus for explosive atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1: 2011
–
Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures “d”
CAN/CSA-C22.2 No. 60079-7: 2012
–
Explosive atmospheres. Part 7: Equipment protection by increased safety “e”
CAN/CSA-C22.2 No. 60079-31: 2012
–
Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure “t”
The following accessories are CSA approved for use with the X9800 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
6.1
25
95-8555
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 02 ATEX 132195X
Increased Safety Model
FM
APPROVED
Flameproof Model
II 2 G
II 2 G
FM
0539
II 2 D
II 2 D
Ex db eb IIC T6...T5
Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
0539
®
®
APPROVED
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-31: 2009
EN 60529:1991+A1:2000+A2:2013
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the
terminal compartment in type of explosion protection flameproof enclosure “d,” or in type of explosion protection
increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e.” They
shall be IP66/IP67 rated, suitable for the conditions of use, and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Infrared (IR) flame detector type X9800 is to be installed in places where there is a low risk of mechanical
damage.
•
See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of this manual for
more information on conducting repairs..
6.1
26
95-8555
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to the “EOL Resistors” section for installation details. All cable entry devices and blanking elements
shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or
flameproof enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall
maintain the degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed
with suitable blanking elements.
NOTE
For ATEX installations, the X9800 detector housing must be electrically connected to earth ground.
The following accessories are ATEX approved for use with the X9800 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
6.1
27
95-8555
APPENDIX D
IECEx APPROVAL
CERTIFICATE OF CONFORMITY
IECEx ULD 06.0018X
Ex db eb IIC T6...T5
Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
or
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
Compliance with:
IEC 60079-0: 2011, Ed. 6
IEC 60079-1: 2014, Ed. 7
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
IEC 60529: 2013, Ed. 2.2
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the
terminal compartment in type of explosion protection flameproof enclosure “d,” or in type of explosion protection
increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e.” They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Infrared (IR) flame detector type X9800 is to be installed in places where there is a low risk of mechanical
damage.
•
See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of this manual for
more information on conducting repairs.
The following accessories are IECEx approved for use with the X9800 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
6.1
28
95-8555
95-8555
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2016 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.