Det-Tronics Instructions FlexSonic™ Acoustic Detector AC100 Sensor ATX10 Transmitter
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
FlexSonic™ Acoustic Detector
AC100 Sensor
ATX10 Transmitter
2.5
Rev: 6/13
95-8657
Table of Contents
overview.............................................................................................. 1
Features............................................................................................... 1
Benefits................................................................................................ 1
SPECIFICATIONS.................................................................................... 2
Description......................................................................................... 3
AC100................................................................................................ 3
ATX10................................................................................................. 4
Operation............................................................................................. 6
Basic Mode........................................................................................ 6
Profile Mode....................................................................................... 7
Data Storage/Management................................................................ 7
IMPORTANT SAFETY NOTES................................................................11
INSTALLATION........................................................................................11
Sensor Termination Box....................................................................11
Grease/Lubrication............................................................................12
Protection Against Moisture Damage................................................12
Foam Insert.......................................................................................12
Identification of Detector Mounting Locations...................................12
Detector Coverage............................................................................13
Power Supply Requirements.............................................................14
Wiring Cable Requirements..............................................................14
External Bonding...............................................................................14
Shield Connections...........................................................................14
Sensor Installation............................................................................14
Wiring Procedure...............................................................................16
Startup............................................................................................... 21
Basic Mode...................................................................................... 21
Profile Mode..................................................................................... 21
PreAlarm Configuration.................................................................... 23
Password Protection......................................................................... 24
General Application Information............................................. 24
Nuisance Sources............................................................................ 24
Friendly Leaks.................................................................................. 24
Maintenance..................................................................................... 25
Routine Inspection........................................................................... 25
Cleaning........................................................................................... 25
Troubleshooting............................................................................ 26
Device Repair and Return............................................................ 27
Ordering Information.................................................................. 27
Replacement Parts........................................................................... 27
Accessories...................................................................................... 27
Assistance........................................................................................ 27
APPENDIX A — FM Approval description.................................. 29
appendix b — csa certification description........................ 30
appendix C — atex approval description.............................. 31
appendix d — iecEx approval description............................. 32
Appendix E — Maritime Approval............................................... 33
appendix f — Approved Adjoining Assemblies..................... 34
INSTRUCTIONS
FlexSonic™ Acoustic Detector
AC100 Sensor
ATX10 Transmitter
Overview
The FlexSonic™ Acoustic Detector is designed to
recognize the unique ultrasonic frequency content
of events such as gas leaks. When a pressurized
gas leak occurs, the frequency content of the sound
being generated extends beyond the audible portion
of the spectrum into the ultrasonic region (above 20
kHz). The intensity of the sound generated by a leak is
determined by several factors including pressure, leak
rate, gas viscosity, and distance from the leak source.
Acoustic detection is less susceptible to environmental
factors (such as high winds) that can degrade the
ability of traditional sensing technology based on gas
concentration to detect the presence of a leak. When
combined with line of sight and/or point gas detectors,
the additional layer of protection provided by the
FlexSonic Acoustic Detector offers the ultimate solution
for gas leak detection.
ATX10 Transmitter
AC100 Sensor
Features
• Long range response
• Nearly instantaneous response
• Gas leak detection without contact
• Adjustable detection range
• Superior false alarm discrimination
• Patented technology
• Suitable for harsh outdoor applications
• Stand alone capability from the ATX10 Transmitter
• 4-20 mA output combined with HART
• Globally approved explosion-proof 316 stainless
steel housing
Benefits
• Ideally suited for use in open or highly ventilated
areas where traditional detectors are limited due to
dilution
• Single detector can cover a large area
• Resistant to corrosion from most commonly
encountered environmental contaminants
• Minimum maintenance required
• No routine calibration required
• Wide acoustic dynamic range
• Not affected by poisoning
• Integrated Acoustic Integrity Check (AIC)
• Functions with all gas types
• Can detect small gas leaks at or below 6 bar (87 psi)
• Fail-safe operation
• Extensive data logging with removable storage
• Certified SIL 2 Capable
2.5 © Detector Electronics Corporation 2013
Rev: 6/13
95-8657
specifications
Certification—
For complete approval details, refer to the appropriate
Appendix:
ATX10 and AC100
Operating Voltage—
24 Vdc nominal; Operating range is 9 to 30 Vdc.
Um=250 V (Intrinsic Safety Rating).
FM
®
APPROVED
Power Consumption—
AC100: 1.25 watts @ 9 Vdc
1.25 watts @ 24 Vdc
1.25 watts @ 30 Vdc.
ATX10: 0.75 watts @ 9 Vdc
1.25 watts @ 24 Vdc
1.75 watts @ 30 Vdc.
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - Maritime
SIL Approval - IEC 61508
Certified SIL 2 Capable.
For specific information regarding SIL, refer to the
Safety Reference Manual (form 95-8658) for details.
Temperature Range—
Operating: –55°C to +75°C (–67°F to +167°F)
Storage:
–55°C to +85°C (–67°F to +185°F).
electro-magnetic compatibility—
EMC Directive 2004/108/EC
Humidity—
5 to 95% RH, non-condensing (Det-Tronics verified).
Emissions: EN61000-6.3
EN61000-6.4
Ingress Protection—
IP66, NEMA/Type 4X.
Immunity: EN61000-6.1
EN61000-6.2
Conduit Entries—
3/4” NPT or M25.
AC100 only
ENCLOSURE MATERIAL—
316 stainless steel, electropolished.
Acoustic—
Dynamic Range: 40 to 139 dB
Ultrasonic Band: 24 individual bands over the
ultrasonic frequency range (20 kHz
to 80 kHz).
SHIPPING WEIGHT—
AC100:
6.2 pounds (2.8 kilograms).
ATX10:
11.5 pounds (5.2 kilograms).
Self-Diagnostic Test (AIC)—
Automatic acoustic integrity check performed once
every 10 (factory default) minutes.
DIMENSIONS—
See Figure 1.
Warm-Up—
Upon power-up, device performs self-test and
initialization procedures, then automatically enters
normal operating mode.
WARRANTY—
3 years.
2.5
2
95-8657
5.16
(13.1)
4.7
(11.9)
3.77
(9.6)
3.46
(8.8)
5.2
(13.2)
5.86
(14.9)
2.7
(6.9)
12.33
(31.3)
A2610
AC100 WITH ATX10
AC100 WITH ATX10 OR STB
AC100 WITH STB
Figure 1—Dimensions of Acoustic Detector in Inches (Centimeters)
ATX10 only
DESCRIPTION
Current Output—
4-20 mA with HART (non-isolated, sourcing*)
20 mA indicates Alarm condition
16 mA indicates Pre-Alarm condition
4 mA indicates Normal condition
2 mA or less indicates a Fault condition.
* Isolated or sinking operation requires the use of a
FlexVu® Model UD10 Display.
The FlexSonic Acoustic Detector is comprised of two
main components: the AC100 Acoustic Sensor, and the
ATX10 Acoustic Transmitter.
AC100
The AC100 Acoustic Sensor detects events such as
gas leaks by looking for changes in the spectrum of
the received acoustic signal. To do this, the AC100
employs a high performance microphone and digital
signal processing (DSP) technology to continuously
monitor the acoustic signal.
Maximum Loop Resistance—
300 ohms at 18 Vdc; 600 ohms at 24 Vdc.
Wiring terminals—
Rated for 14 to 18 AWG (2.5 to 0.75 mm2) wire.
The wide dynamic range and spectral resolution enable
the sensor to provide both superior sensitivity and false
alarm discrimination.
LED Status Indicators—
Power (Green)
Steady = Power on
20 kHz):
A2611
Coverage Range of FlexSonic Acoustic Detector (Low Level Leak)
Leak Source:
Leak Rate:
0.004 Kg/Sec
Gas Type:
Compressed Air
Gas Pressure:
6 Bar (87 psi)
Leak Orifice:
2 mm round
Orientation:
Straight up
2.5
13
95-8657
power SUPPLY requirements
caution
The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent
water ingress and/or maintain the explosion-proof
rating.
Calculate the total gas detection system power
consumption rate in watts from cold start-up. Select a
power supply with adequate capability for the calculated
load. Ensure that the selected power supply provides
sufficient regulated and filtered output power for the
entire system. If a back-up power system is required,
a float‑type battery charging system is recommended.
If an existing source of power is being used, verify that
system requirements are met.
External Bonding (AC100 and atx10)
Per ATEX/IECEx requirements, 4 mm2 wire shall be
attached to external ground connection.
Shield Connections
note
The power supply must meet the noise
requirements for HART systems. If noise or ripple
on the main power source could interfere with
the HART function, an isolated power source is
recommended. (For detailed information regarding
power supply specifications, refer to the HART
Communication Foundation’s document “FSK
Physical Layer Specification” HCF_SPEC-54.)
The ATX10 provides terminals for proper grounding
of wiring cable shields. These shield terminals are
not connected internally, but are connected to ground
through capacitors. The capacitors ensure an RF
ground, while preventing 50/60 Hz ground loops.
Ground all shields as shown in the wiring examples
throughout this manual.
Wiring cable requirements
important
For proper grounding, all junction boxes / metal
enclosures must be connected to earth ground.
Always use proper temperature rated cabling type
and diameter for input power as well as output signal
wiring. 14 to 18 AWG shielded stranded copper wire is
recommended.
The following are required for installations requiring CE
Mark compliance:
• For shielded cable installed in conduit, attach the wire
shields to the “shield” connections on the terminal
blocks, or to earth ground on the case.
The field wiring terminal connections are certified for a
single wire in size from 0.2 to 2.5 mm2 (or two conductors
with same cross section 0.2 to 0.75 mm2). The screws
must be tightened down with a torque 0.4 to 0.5 Nm. The
metal housing must be electrically connected to earth
ground.
• For installations without conduit, use double shielded
cable. Terminate the outer shield to earth ground on
the case. Terminate the inner shield to the “shield”
connection on the terminal blocks.
A minimum of 9 Vdc must be present at the ATX10 to
ensure proper operation. The maximum cable length from
power source to ATX10 is 2000 feet. When the AC100
Sensor is mounted remotely using an STB termination
box, maximum cable length from ATX10 to AC100 is 500
feet.
Sensor installation
3/4” NPT Models
3/4” NPT models have tapered threads and a connector
assembly. Install the sensor as follows:
note
The AC100 has an Intrinsic Safety (IS) Barrier.
Proper NEC/CEC IS grounding must be ensured.
1. Screw the sensor into the appropriate entry on
the termination box. Ensure a minimum of 5 fully
engaged threads. Use of Teflon tape on NPT
threads is recommended to prevent thread damage.
note
In applications where the wiring is installed in
conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and
non‑signaling conductors to prevent nuisance
EMI problems.
2.5
2. When the sensor gets tight, note the position of
the set screw on the sensor housing. It should be
oriented away from the mounting surface to ensure
adequate clearance between the sensor and
mounting surface. See Figure 8.
14
95-8657
ORIENT SET SCREW AWAY FROM
MOUNTING SURFACE TO ENSURE
ADEQUATE CLEARANCE BETWEEN
SENSOR AND SURFACE
A2618
Figure 8—AC100 Connected to Termination Box
(M25 Model Shown)
4. Tighten the lock nut against the termination box.
See Figure 10.
M25 Models
M25 models have straight threads and a removable
connector assembly with lock nut. Install the sensor
as follows:
5. Insert the sensor wires through the connector
assembly into the termination box, then secure the
sensor to the termination box by tightening the ring
on the connector assembly. Prior to tightening the
ring, orient the sensor with the set screw away from
the detector mounting surface to ensure adequate
clearance between the sensor and mounting
surface. See Figure 8.
1. Remove the connector assembly from the AC100
Sensor. See Figure 9.
2. Screw the lock nut as far back as it will go (finger
tight only), then screw the connector assembly into
the appropriate entry on the termination box. A light
coating of grease on the threads is recommended.
6. Tighten the connector ring, then install set screws to
prevent movement.
3. Screw the assembly into the termination box as far
as it will go and tighten with a 35mm socket wrench.
note
There are a total of six set screw holes on the
connector ring, three on the lower level and three
on the upper level. Install at least one set screw
on each level. See Figure 11.
AC100 SENSOR
CONNECTOR ASSEMBLY
SCREW THE LOCK NUT AS FAR BACK AS POSSIBLE
(FINGER TIGHT ONLY)
A2619
Figure 9—AC100 with Connector Assembly Removed
2.5
15
95-8657
TIGHTEN LOCK NUT AGAINST TERMINATION BOX
TIGHTEN WITH 35MM SOCKET WRENCH
A2620
Figure 10—Connector Assembly Attached to Termination Box
Figure 15 shows power and signal wiring for an ATX100
wired to a PLC.
wiring PROCEDURE
Ensure that all cables are terminated properly.
Conductor insulation should be stripped off with a bare
conductor length of 0.2 inch (5 mm) minimum and 0.7
inch (18 mm) maximum. Ensure that cable shield is
properly terminated and that bare shield wire is not
allowed to accidentally contact the metal housing or
any other wire.
Figure 16 shows an ATX10 with AC100 wired to a FlexVu
UD10 Universal Display.
See Figure 17 for benchtop test wiring.
note
For proper HART communication, a signal loop
resistance of 250 ohms must be present at the
4-20 mA output terminals.
Important
The AC100 GND wire (green, 16 AWG, 1.31 mm2)
must be properly grounded inside the STB
or ATX10 to maintain proper Intrinsic Safety
connections. A lug is provided and must be
properly crimped to the wire and secured with
the provided screw and washer at the location
marked by the GND symbol. The AC100 and the
adjoining STB/ATX10 are also provided with an
external GND connection (lug screw and washer
provided) that must be bonded to a suitable earth
GND connection. In addition, the power supply
GND must be terminated at the STB/ATX10 to
ensure 1 ohm or less resistance.
SET SCREWS
Figure 12 shows the wiring terminals on the ATX10
Transmitter.
Figure 13 shows an AC100 wired directly to an ATX10
Transmitter.
A2621
Figure 14 shows an AC100 connected to an STB
termination box and wired to an ATX10 Transmitter.
2.5
Figure 11—Set Screw Locations on Connector Ring
16
95-8657
TO
R
PE
M
JU
D
N
G
B
-2
P3
-1
P3
-3
P3
-4
P3
INTERFACE TO
SOFTWARE CONFIGURATOR
+
D
N
G
A
–
C
IE
LD
SH
C
VD
C
J3
B
VD
IEL
SH
24
P1
-2
P1
-3
-1
J3
+
J3
-2
–
-3
J3
D
J3
SENSOR
-4
-5
P1
-1
POWER AND 4-20 mA OUTPUT
24
VD
P1
-4
420
m
A
24
VD
C
A
24
A2605
Figure 12—ATX10 Transmitter Wiring Terminals
INTERFACE
TO SOFTWARE
CONFIGURATOR
ATX10
TRANSMITTER
BOARD
-4
P3
R
TO
B
-1
D
N
PE
G
M
JU
-3
P3
P3
-2
P3
+
D
N
G
A
–
C
P1
-2
LD
SH
IE
P1
-3
24
VD
P1
-4
42
0
m
A
24
VD
C
A
24
24
SH
C
VD
C
IEL
J3
B
VD
-1
J3
+
J3
–
-4
J3
-5
P1
-1
GRAY
-3
J3
D
ORANGE
-2
RED
BLACK
SENSOR
POWER
AND OUTPUT
GREEN
IS GROUND
NOTES: DEVICE HOUSINGS MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.
CONNECT THE GREEN WIRE FROM THE AC100 TO THE GROUND SCREW
INSIDE THE ATX10 HOUSING.
AC100
ACOUSTIC
SENSOR
A2606
Figure 13—AC100 Acoustic Sensor Wired to ATX10 Transmitter
2.5
17
95-8657
INTERFACE
TO SOFTWARE
CONFIGURATOR
ATX10
TRANSMITTER
BOARD
-4
P3
JU
R
TO
B
D
PE
M
N
G
-1
P3
-2
P3
-3
P3
N
G
A
D
+
STB TERMINATION BOX
C
–
24
D
IE
L
SH
P1
-2
P1
-3
24
VD
P1
-4
420
m
A
24
VD
C
A
24
SH
C
VD
C
IEL
J3
B
VD
-1
J3
+
-2
J3
–
-3
J3
D
-4
J3
IS GROUND
ORANGE
GRAY
RED
BLACK
P1
-1
-5
SENSOR
GRAY
ORANGE
BLACK
RED
POWER
AND OUTPUT
GREEN
NOTES: DEVICE HOUSINGS MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.
CONNECT THE GREEN WIRE FROM THE AC100 TO THE GROUND SCREW
INSIDE THE STB HOUSING. EARTH GROUND CONNECTION REQUIRED.
SHIELDED TWISTED PAIR IS RECOMMENDED FOR SIGNAL WIRING,
500 FEET MAXIMUM.
AC100
ACOUSTIC
SENSOR
A2607
Figure 14—AC100 Acoustic Sensor Connected to STB and Wired to ATX10 Transmitter
2.5
18
95-8657
ATX10
TRANSMITTER
BOARD
INTERFACE
TO SOFTWARE
CONFIGURATOR
P3
-4
P3
JU
-3
R
TO
B
-1
D
PE
N
G
-2
M
P3
P3
N
G
A
PLC 4-20 mA INPUT CARD
D
+
INPUT
VD
C
–
24
VD
D
SH
P1
-2
C
VD
C
IE
L
J3
B
VD
IEL
SH
24
+
24
m
A
24
P1
-4
24 VDC
420
–
P1
-3
250
OHMS
MINIMUM
A
C
4-20 mA
-1
J3
+
-2
J3
–
-3
J3
D
-4
J3
P1
-1
-5
SENSOR
POWER
AND OUTPUT
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum
for HART communication.
A2608
Device housings must be electrically connected to earth ground.
Figure 15—ATX10 Transmitter Wired to PLC
INTERFACE
TO SOFTWARE
CONFIGURATOR
ATX10
TRANSMITTER
BOARD
-4
P3
R
TO
B
D
N
PE
M
JU
G
-1
P3
-2
P3
-3
P3
+
D
N
G
A
C
P1
-2
LD
SH
IE
P1
-3
24
VD
P1
-4
4-
–
20
m
A
24
VD
C
A
24
24
SH
C
VD
C
IEL
J3
B
VD
-1
J3
+
J3
-2
–
-3
J3
D
-4
J3
P1
-1
-5
ORANGE
GRAY
RED
BLACK
SENSOR
POWER
AND OUTPUT
GREEN
J3-5
P1
J4-8
LOW ALARM NO
J4-9
FAULT COM
J4-10
SHIELD
J4-7
LOW ALARM NC
P2-1
J4-6
LOW ALARM COM
24 VDC +
J4-5
AUX ALARM NO
P2-2
J4-4
AUX ALARM NC
24 VDC –
MODBUS
Connector
AUX ALARM COM
SHIELD
RS485 B
J4-3
P2-3
J2-1
HIGH ALARM NO
P2-4
RS485 A
J4-2
24 VDC –
J2-2
J4-1
HIGH ALARM NC
24 VDC +
COM
HIGH ALARM COM
P2-5
J2-3
IS GROUND
P2-6
J2
J3
Power Supply Connector
B2609
FAULT NC
J4-11
FAULT NO
J4-12
UD10
DISPLAY UNIT
Relay Connector
J3-4
24 VDC +
SHIELD
J3-3
P1-1
4-20 mA
4-20 mA –
J3-2
P1-2
24 VDC –
4-20 mA +
J3-1
P1-3
SHIELD
Output Loop
Connector
CALIBRATE
Sensor Connector
AC100
ACOUSTIC
SENSOR
J4
NOTES: DEVICE HOUSINGS MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.
P2
CONNECT THE GREEN WIRE FROM THE AC100 TO THE GROUND SCREW
INSIDE THE ATX10 HOUSING.
SHIELDED TWISTED PAIR IS RECOMMENDED FOR SIGNAL WIRING,
500 FEET MAXIMUM.
Figure 16—ATX10 Transmitter with AC100 Wired to FlexVu UD10 Display
2.5
19
95-8657
ATX10
TRANSMITTER
P3
-4
P3
JU
-3
R
TO
B
-1
D
PE
N
G
P3
-2
M
P3
N
G
A
+
D
–
D
IE
L
SH
24
VD
C
–
24
SH
C
VD
IEL
C
J3
B
VD
-1
J3
+
J3
-2
–
-3
J3
D
-4
J3
-5
P1
-1
P1
-2
P1
-3
250 OHMS
24 VDC
420
P1
-4
+
m
A
24
VD
C
A
24
IS GROUND
HART
HANDHELD
COMMUNICATOR
AC100
ACOUSTIC
SENSOR
A2617
Figure 17—Wiring the Acoustic Detector for Benchtop Testing/Programming Using HART Protocol
2.5
20
95-8657
Startup
ALARM SETUP
MODE
BASIC/
PROFILE/
ADVANCED
LATCHING
BASIC MODE
PROFILE MODE
The following section describes configuration of the
acoustic detector (using a HART handheld device) for
the following modes of operation:
• Basic
BASIC MODE
LEVEL (dB)
DELAY (SEC)
AUTO LEVEL
AUTO LEVEL
ENABLED?
ENABLE
• Profile ‑ Level / Learn
3. AUTO LEVEL can be set as follows:
Enable AUTO LEVEL via the ENABLE command
in the AUTO LEVEL submenu. The detector will
automatically select a new LEVEL (dB) setting
based on the background noise picked up during a
10 second (not field adjustable) interval.
The ATX10 is factory programmed to run in Basic
operating mode. This mode of operation uses the
simplest setup process, but offers the fewest options
for adjusting sensitivity.
Profile mode is an alternate option that allows access
to additional configuration parameters, as well as the
ability to “Learn” background profiles.
4. Set the DELAY (SEC): This delay represents the
time that an alarm condition must be held in order
to annunciate an alarm (adjustment range = 0-30
seconds, default = 5 seconds). It is normally not
necessary to change this value. However, it can be
useful to increase the delay if there are false alarms
due to momentary events.
BASIC mode
Basic mode uses a simple alarm detection technique.
The detector searches the ultrasonic spectrum for
bands that exceed a fixed threshold. When a sufficient
number of these bands exceeds the pre-set level, an
alarm condition is detected (adjustment range = 40-120
dB, default = 59 dB). If the alarm condition continues
for a fixed period of time, an alarm output is generated
(adjustment range = 0-30 seconds, default = 5 seconds).
The fixed threshold level and the fixed time period are
field selectable, and are the only variables that need
to be considered in Basic mode. Use the following
procedure to configure the detector for Basic operating
mode.
PROFILE mode
In the Profile operating mode, the detector still uses the
same alarm detection techniques. However, several
additional options and capabilities are offered. Use the
following procedure to configure the detector for Profile
operating mode.
1. Navigate the HART menu as follows:
DEVICE MENU > DEVICE SETUP > ALARM SETUP
> MODE > PROFILE.
1. Navigate the HART menu as follows:
DEVICE MENU > DEVICE SETUP > ALARM SETUP
> MODE > BASIC.
DEVICE SETUP
ALARM SETUP
ALARM SETUP
SD MENU
SET RTC
CALIBRATION MENU
WRITE PROTECT
HART SETUP
MODE
BASIC/
PROFILE/
ADVANCED
LATCHING
BASIC MODE
PROFILE MODE
PROFILE MODE
BASIC MODE
LEVEL (dB)
DELAY (SEC)
AUTO LEVEL
ALARM SETUP
ALARM SETUP
SD MENU
SET RTC
CALIBRATION MENU
WRITE PROTECT
HART SETUP
MODE
BASIC/
PROFILE/
ADVANCED
LATCHING
BASIC MODE
PROFILE MODE
ALARM MODE LEVEL/LEARN
LEVEL (dB)
SENSITIVITY (dB)
BAND COUNT
DELAY (SEC)
RECOVER (SEC)
LEARN MENU
PREALARM ON
PREALARM LVL
2. In the PROFILE MODE menu, select ALARM MODE,
and then either LEVEL or LEARN. (The following
sections describe the differences between LEVEL
and LEARN.)
2. In the BASIC MODE menu, set the LEVEL (dB): This
should be set to a numeric value between 40 and 120
(factory default is 59). This represents the threshold at
which a leak will be detected and an alarm declared.
Lower numbers represent greater sensitivity and
higher numbers will result in less sensitivity to alarm.
This value can be set manually, or by using the AUTO
LEVEL function.
2.5
DEVICE SETUP
21
95-8657
Profile‑Level
Profile‑Learn
The Profile‑Level mode uses the same fixed threshold
concept as Basic mode. There is a LEVEL (dB)
setting, but no AUTO LEVEL function. The benefit of
using Profile‑Level is that some additional settings are
available for increased flexibility.
The Profile‑Learn mode uses variable thresholds. Each
frequency band has its own threshold level, rather than
a fixed level that is applied to all bands.
The Profile‑Learn mode uses a recorded set of band
thresholds called a “Profile.” The process for generating
a profile is referred to as “Learn.”
In some applications the use of the factory default
settings in the Profile‑Level mode may be adequate,
however, it is possible to customize the acoustic
detection using the additional settings. The following
additional settings are available in Profile‑Level:
The detector is commanded to start and stop the
“Learn” process to record the maximum sound level
detected in each band during the recording period.
This data can be used to reduce sensitivity at the
frequency bands where background noise and events
are prevalent while increasing sensitivity in the bands
that are relatively silent.
BAND COUNT – In Basic mode, the number of
frequency bands that exceed the LEVEL (dB) threshold
are counted. An alarm condition exists when this
count exceeds 14 bands. This number is fixed in
Basic mode. In Profile‑Level mode it can be adjusted
(adjustment range = 1-24, default = 14). Lower numbers
tend to make the detector more sensitive to narrow
band signals, including pure tones or other ultrasonic
emitting devices. Higher numbers tend to decrease
the sensitivity of the detector and require broadband
ultrasonic sound to exceed the LEVEL(dB) threshold in
more bands.
To perform the Learn process:
1. Navigate to DEVICE SETUP > ALARM SETUP >
PROFILE MODE > LEARN MENU.
PROFILE MODE
ALARM SETUP
MODE
BASIC/
PROFILE/
ADVANCED
LATCHING
BASIC MODE
PROFILE MODE
RECOVER (SEC) – This setting specifies the time (in
seconds) that elapses from the moment the alarm
criteria are no longer met until the alarm is cleared.
ALARM MODE LEVEL/LEARN
LEARN MENU
LEVEL (dB)
SENSITIVITY (dB)
BAND COUNT
DELAY (SEC)
RECOVER (SEC)
LEARN MENU
PREALARM ON
PREALARM LVL
LEARN ENABLED?
START LEARN
STOP LEARN
RECORDED
CLR RECORDED
ALARM PROFILE
SAVED PROFILE
2. Select CLR RECORDED to clear any previous learn
data, if desired. Any future learn data will build
upon previous results unless this step is performed.
3. Select the START LEARN command to start the
learn process. LEARN ENABLED? will indicate ‘Y’
4. Select STOP LEARN to stop the learn process. At
this point the sequence of START LEARN/STOP
LEARN and/or CLR RECORDED may be repeated
until the desired profile data is collected. The profile
should be characteristic of typical background
sounds that may occur during normal operation. If
there are periodic events that cause false alarms,
it is desirable to conduct the learn process during
these events.
2.5
22
95-8657
5. Once the RECORDED data represents the desired
profile, navigate to the SAVED PROFILE menu.
The SAVED PROFILE menu provides a preview of
several slots for permanently storing the RECORDED
profile. Navigate to a slot to overwrite. (Use SLOT 1
for a new unit).
PREALARM configuration
The PREALARM option is available in Profile-Level/Learn
mode (not Basic), and can be configured as follows
through the PROFILE MODE menu.
1. Set PREALARM ON to ‘Y’
PROFILE MODE
ALARM MODE LEVEL/LEARN
LEARN MENU
LEVEL (dB)
SENSITIVITY (dB)
BAND COUNT
DELAY (SEC)
RECOVER (SEC)
LEARN MENU
PREALARM ON
PREALARM LVL
LEARN ENABLED?
START LEARN
STOP LEARN
RECORDED
CLR RECORDED
ALARM PROFILE
SAVED PROFILE
2. Set PREALARM LVL.
SAVED PROFILE
NAME
DATE
TIME
The alarm threshold for each band is lowered by this
value, effectively making the band more sensitive.
PREALARM is intended to be more sensitive than
the normal alarm and can be used as a warning that
a potential alarm condition may be imminent.
The number of bands that exceed this lower
threshold are counted. When they reach the BAND
COUNT setting used for normal alarms, PREALARM
will annunciate, resulting in a 16 mA output.
6. Select the slot. The menu that appears shows the
options of SELECT and SAVE. First select SAVE
to copy the RECORDED profile into the SAVED
PROFILE slot. Select SELECT to tell the ATX10 to
use this SAVED PROFILE slot as its profile for the
alarm function.
7. Navigate back to the LEARN MENU and confirm
that the selected slot’s name appears as the ALARM
PROFILE.
8. Return to the PROFILE MODE menu and set the
following parameters as desired:
SENSITIVITY (dB) - The actual alarm threshold used
in each band is a combination of the profile and
this fixed offset. (i.e. a value of 3 would mean each
band is counted towards alarm if it exceeds a level
3 higher than its corresponding level in the profile).
RECOVER (SEC) – This setting specifies the time (in
seconds) that elapses from the moment the alarm
criteria are no longer met until the alarm is cleared.
BAND COUNT – Similar to Basic and Profile‑Level
operation, the band count can be adjusted in
Profile‑Learn. It is preferable to leave the count at
the default of 14 or perhaps somewhat higher in
Profile‑Learn mode, since a large sensitivity gain is
already realized with the use of a profile. A lower
band count may make the detector susceptible to
narrow band false alarm sources.
2.5
23
95-8657
GENERAL APPLICATION
INFORMATION
Password protection
The ATX10 allows the use of a password for restricting
changes to configuration parameters and limiting
access to safety critical commands.
Nuisance Sources
Most industrial or processing environments are
relatively free from the higher frequency sound energy
that is characteristic of a gas leak, however, there are
instances where high frequency nuisance sources
exist. The sources may include, but are not limited to:
The ATX10 is shipped from the factory with the password
protection (Write Protect) feature enabled. Refer to the
AC100/ATX10 HART Addendum (number 95-8698) for
complete information regarding use of the Write Protect
feature.
• Rotating machinery / gear meshes
• Bearings/fans motors
• Metal-to-metal contact / chains
• High velocity wind through rigging
The FlexSonic Acoustic Detector can be effectively
employed to record the acoustic background
environment unique to an installation and provide a
clear display of the information using the Acoustic
Inspector software package. The ability to view the
actual acoustic environment enables users of the
FlexSonic Acoustic Detector to make intelligent, databased decisions on how to best address nuisance
sources in the alarm profile.
Friendly Leaks
The FlexSonic Acoustic Detector recognizes the
acoustic signature of pressurized gas escaping.
Therefore, so called ‘friendly’ sources of compressed
gas leaks such as air lines and relief stacks may be
detected as well.
While some non-hazardous pressurized gas escapes
may be effectively ignored through the patented learn
function, the expected hazardous leak SPL must
be greater than the non-hazardous leak SPL for the
detector to effectively discriminate between the two
sources.
If the time duration of the non-hazardous source is
relatively short, the user settable alarm delay setting
can be adjusted to reject short duration leaks. Refer
to the “Operation” section of this manual for details on
alarm adjustments.
2.5
24
95-8657
Maintenance
Routine Inspection
Periodically or during scheduled maintenance, the
AC100 cover should be inspected to ensure that
obstructions such as plastic bags, litter, heavy oil and
tar, paint, mud, snow, or other materials do not block
sound from reaching the sensor and thereby impairing
the performance of the device.
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of
the flamepaths.
When using the optional foam insert in dirty or dusty
environments, check to ensure the insert is clean and
free of buildup. Replace the insert if torn or damaged.
The AC100 Sensor contains no user serviceable
components and should never be opened. The
ATX10 wiring compartment is the only part of the
acoustic detector that should be opened by the
user in the field.
Cleaning
To clean the AC100 Acoustic Sensor cover, ensure that
the device is powered off, then simply grasp the cover
assembly and twist counterclockwise. See Figure 18.
The stainless steel mesh can be cleaned with warm
soapy water and rinsed. Remove any excess water
with a cloth, then air dry.
Note
Refer to the FlexSonic Acoustic Detector Safety
Manual 95-8658 for specific requirements and
recommendations applicable to the proper
installation, operation, and maintenance of all
SIL-Certified acoustic detectors.
The foam insert (if used) can also be cleaned with
warm, soapy water and rinsed. Hand wring any excess
water by simply squeezing the foam insert to remove
excess water.
To maintain maximum sensitivity and detection range,
the AC100 Acoustic Sensor cover (and optional
foam insert) must be kept relatively clean and free of
debris. Refer to the following procedure for cleaning
instructions.
When re-installing the foam insert / AC100 cover, use
care not to over tighten.
caution
The AC100 sensor head (microphone and AIC
acoustic source) does not require cleaning
and should not be contacted with any cleaning
materials.
NO SERVICEABLE COMPONENTS
WITHIN SENSOR HOUSING.
DO NOT OPEN.
MICROPHONE
AIC ACOUSTIC SOURCE
ATX10 TRANSMITTER
SENSOR COVER
AC100 SENSOR
FOAM INSERT
A2615
Figure 18—Acoustic Detector with Protective Sensor Cover Removed
2.5
25
95-8657
TROUBLESHOOTING
If a Fault condition is indicated by the LED on the ATX10
faceplate, the nature of the fault can be determined by
navigating to the STATUS INFO MENU. See Table 3 for
additional information.
Table 3—Troubleshooting Guide
Fault Indication
Description
Corrective Action
AI FAULT
AIC has failed. Microphone or emitter is
degraded.
Provide data log information to Det-Tronics for analysis.
SD ADVISORY
SD Memory Module has an issue
that requires intervention via the SD
ADVISORY menu.
SD card is out-of-sync with the ATX10 on-board flash. It
will be necessary to either UPLOAD the data to the SD
card or DOWNLOAD the data to the ATX10 if the SD
card contains valid data (via SD ADVISORY MENU).
SNSR HDWR FAULT
Hardware fault on the AC100 Sensor.
Return to factory for repair.
TX HDWR FAULT
Hardware fault on the ATX10
Transmitter.
Return to factory for repair.
VOLTAGE FAULT
Detector operating voltage is out of
tolerance.
Check output voltage at the power source. Check power
wiring to the detector.
2.5
26
95-8657
DEVICE REPAIR AND RETURN
replacement Parts
Part Number
011355-001
010969-001
011365-002
104155-001
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure.
103028-027
103028-028
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag
as protection from electrostatic discharge. The RMI
number should be clearly marked on the outside of the
box.
ACCESSORIES
Part Number Description
226365-603 STB7S5YW M25 Sensor Termination
Box, (Stainless Steel model only)
226365-604 STB7S5NW 3/4 NPT Sensor Termination
Box, (Stainless Steel model only)
012402-001
W6300S1004 Inspector Connector
(software not included)
012400-001
Acoustic Inspector Package
012401-001
Acoustic Configurator Package
009700-001 Magnetic Tool
101197-004* Stop Plug, 3/4” NPT, SS
101197-003
Stop Plug, M25, SS, IP66
010817-001* Stop Plug, 20 Pack, 3/4” NPT, SS
010819-001
Stop Plug, 20 Pack, M25, SS, IP66
005003-001 Lubriplate grease, 1 oz.
*NEMA Type 4X/IP66 rating requires Teflon tape.
note
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged
as a result of improper packaging.
Return all equipment transportation prepaid to the
factory in Minneapolis.
NOTE
It is highly recommended that a spare be kept on
hand for field replacement to ensure continuous
protection.
ORDERING INFORMATION
One AC100 Acoustic Sensor with its associated ATX10
Transmitter is required for each detection point. The
two devices can be ordered separately, or as a kit (Kit
includes individually packaged AC100 and ATX10).
Refer to the appropriate Model Matrix for ordering
details. Note: the ATX10 is supplied with memory
module and SD card.
Assistance
For assistance in ordering a system to meet the needs
of a specific application, please contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.det-tronics.com
E-mail: det-tronics@det-tronics.com
Part Number Description
012152-001
AC100/ATX Kit, 3/4” NPT
AC100SNT2 & ATX10S5N26T
012153-001
AC100/ATX Kit, M25
AC100SMT2 & ATX10S5M26T
2.5
Description
Foam Insert for AC100
ATX10 Replacement Module
Memory Module (w/o SD card)
Micro SDHC Card, 4G, Industial
Temperature Rating
Plug, 5.0 mm, 4 Position (P1)
Plug, 5.0 mm, 5 Position (J3)
27
95-8657
FlexSonic™ AC100 Acoustic Sensor Model Matrix
MODEL
DESCRIPTION
AC100
Acoustic sensor
TYPE
S
Material
Stainless Steel
TYPE
THREAD TYPE
N
3/4” NPT
M
M25
TYPE
T
APPROVALS
SIL/FM/CSA/ATEX/CE/IECEx
TYPE
CLASSIFICATION
2
Division/Zone Ex d
FlexSonic™ ATX10 Transmitter Model Matrix
MODEL
DESCRIPTION
ATX10
Transmitter for AC100
TYPE
S
Material
Stainless Steel
TYPE
5
# OF OPEN PORTS
5 Port
TYPE
THREAD TYPE
N
3/4” NPT
M
M25
TYPE
26
OUTPUT
4-20 mA with HART Protocol
TYPE
T
2.5
28
APPROVALS
SIL/FM/CSA/ATEX/CE/IECEx
95-8657
Appendix A
FM APPROVAL DESCRIPTION
AC100
ATX10
Class I, Div1, Groups B, C & D
Class II/III, Div1/Div2, Groups E, F & G
Class I, Div2, Groups A, B, C & D
Temperature code T4
Tamb: –55°C to +75°C
NEMA 4X
Class I, Div1, Groups B, C & D
Class II/III, Div1/Div2, Groups E, F & G
Temperature code T5
Class I, Div2, Groups A, B, C & D
Temperature code T4
Tamb: –55°C to +75°C
NEMA 4X
Applicable Documents:
FM 3810
Elec. and Electronic Test, Measuring and Process Control Equipment
FM 3600
Electrical Equipment for use in Hazardous (Classified) Locations
FM 3610
(ANSI/ISA 60079-11)
Intrinsically Safe, Class I, II, III, Div I, Haz. Loc.
FM 3611
Elec. Equip. for use in Cl. I/II, Div. 2 and Cl. III, Div. 1/2 Haz. Loc.
FM 3615
Explosionproof Electrical Equipment
NEMA 250
Enclosures for Electrical Equipment (1000 Volts Maximum)
2.5
29
95-8657
Appendix B
CSA CERTIFICATION DESCRIPTION
AC100
ATX10
Class I, Div1, Groups B, C & D
Class II/III, Div1/Div2, Groups E, F & G
Class I, Div2, Groups A, B, C & D
Temperature code T4
Tamb: –55°C to +75°C
Type 4X
Class I, Div1, Groups B, C & D
Class II/III, Div1/Div2, Groups E, F & G
Temperature code T5
Class I, Div2, Groups A, B, C & D
Temperature code T4
Tamb: –55°C to +75°C
Type 4X
Applicable Documents:
C22.2 #0-10
General Requirements – Canadian Electrical Code, Part II
C22.2 #25
Enclosures for use in Class II Groups E, F, G Haz. Loc.
C22.2 #30
Explosionproof Enclosures for Use in Class I Haz. Loc.
C22.2 #94-M91
Special Purpose Enclosures (NEMA)
C22.2 #142
Process Control Equipment
C22.2 #157
Intrinsically Safe and Non-incendive Equipment for Haz. Loc.
C22.2 #213
Nonincendive Elec. Equip. for Use in Class I, Div 2 Haz. Loc.
2.5
30
95-8657
Appendix C
ATEX APPROVAL DESCRIPTION
FM
APPROVED
AC100
ATX10
DEMKO 12 ATEX 1263479X
II 2 G
0539
II 2 D
Ex d ib IIC T4 Gb
Ex tb IIIC T80°C Db
Tamb: –55°C to +75°C
IP66
DEMKO 12 ATEX 1263925X
II 2 G
0539
II 2 D
Ex d IIC T6 Gb
Ex tb IIIC T80°C Db
Tamb: –55°C to +75°C
IP66
®
FM
APPROVED
®
EN Standards:
EN60079-0: 2012
Electrical apparatus for explosive atmospheres, General Requirements
EN60079-1: 2007
Electrical apparatus for explosive atmospheres, Flameproof enclosure “d”
EN60079-11: 2012
Explosive atmospheres Equip protection by Intrinsic Safety
EN60079-31: 2009
2008 Explosive atmospheres Equip. Dust Ignition Protection by enclosure “t”
EN60529:2004
Degrees of Protection Provided by Enclosures (IP Code)
ATEX Special Conditions for Safe Use (‘X’):
AC100
• The AC100 Acoustic Sensor must always be installed with the detection head pointing down vertically.
• The AC100 Acoustic Sensor must only be installed in areas where there is a low risk of mechanical damage.
• The AC100 is only to be used connected to the ATX10 Acoustic Transmitter or Model STB Sensor Termination Box.
ATX10
• The ATX10 must only be installed in areas where there is a low risk of mechanical damage.
Additional Safety Notes:
• The following warning is on the product: Warning: Do not open when an explosive gas atmosphere may be
present. For ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For
temperature below –10°C use suitable field wiring for the lowest temperature.
• Cable, bushings and the conduit entries shall be of a flameproof type already certified according to relevant
ATEX standard, rated IP66, so the protection principle employed will not be impaired.
• Unused conduit entries shall be closed using flameproof stop plugs certified for the conditions of use (IP66
minimum). The stop plugs should be removable only with the aid of a tool.
• Shielded cable is required.
2.5
31
95-8657
Appendix D
IECEx APPROVAL DESCRIPTION
AC100
ATX10
IECEx ULD13.0002X
Ex d ib IIC T4 Gb
Ex tb IIIC T80°C Db
Tamb: –55°C to +75°C
IP66
IECEx ULD13.0003X
Ex d IIC T6 Gb
Ex tb IIIC T80°C Db
Tamb: –55°C to +75°C
IP66
IEC Standards:
IEC60079-0: 2011
Electrical apparatus for explosive atmospheres, General Requirements
IEC60079-1: 2007
Electrical apparatus for explosive atmospheres, Flameproof enclosure “d”
IEC60079-11: 2011
Intrinsic Safety explosive atmospheres Equip protection by Intrinsic Safety
IEC60079-31: 2008
Explosive atmospheres Equip. Dust Ignition Protection by enclosure “t”
IEC60529: 2001
Degrees of Protection Provided by Enclosures (IP Code)
IEC Special Conditions for Safe Use (X):
AC100
• The AC100 Acoustic Sensor must always be installed with the detection head pointing down vertically.
• The AC100 Acoustic Sensor must only be installed in areas where there is a low risk of mechanical damage.
• The AC100 is only to be used connected to the ATX10 Acoustic Transmitter or Model STB Sensor Termination Box.
ATX10
• The ATX10 must only be installed in areas where there is a low risk of mechanical damage.
WARNING
Always ensure that the detector/junction box hazardous (classified) location ratings are applicable for the
intended use.
Additional Safety Notes:
• The following warning is on the product: Warning: Do not open when an explosive gas atmosphere may be
present. For ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For
temperature below –10°C use suitable field wiring for the lowest temperature.
• Cable, bushings and the conduit entries shall be of a flameproof type already certified according to relevant IEC
standard, rated IP66, so the protection principle employed will not be impaired.
• Unused conduit entries shall be closed using flameproof stop plugs certified for the conditions of use (IP66
minimum). The stop plugs should be removable only with the aid of a tool.
• Shielded cable is required.
2.5
32
95-8657
Appendix E
Maritime Approval
DNV
Type Approval Certificate No. A-11023.
Subject Matter of the Approval
Model AC100 Acoustic Sensor, ATX10 Transmitter, and STB Termination Box are found to comply with Det Norske
Veritas’ Rules for Classification of Ships and Det Norske Veritas’ Offshore Standards.
Application/Limitation
Location Classes
MODEL
TEMPERATURE
HUMIDITY
VIBRATION
EMC
ENCLOSURE
AC100/ATX10
D
B
B
B
C
Relevant tests according to “Standard for Certification No. 2.4”.
Line Filter
A line filter is required for all maritime installations. Phoenix Contact model ME-MAX-NEF/QUINT20A is approved
for use with the AC100/ATX10 Acoustic Detector and must be installed within 12 inches (30 centimeters) of the
detector.
INTERFACE
TO SOFTWARE
CONFIGURATOR
ATX10
TRANSMITTER
BOARD
-4
P3
R
D
B
PE
M
JU
N
G
-1
P3
-2
P3
-3
P3
PLC 4-20 mA INPUT CARD
TO
A
D
N
G
24
m
N
–
C
SH
IE
LD
VD
4-
20
N
24
L
PE
P1
-2
L
PE
P1
-1
+
P1
-4
24 VDC
24
A
VD
C
LINE FILTER*
–
P1
-3
250
OHMS
MINIMUM
+
INPUT
4-20 mA
24
SH
A
VD
C
VD
IEL
C
J3
B
+
-1
J3
–
-2
J3
D
J3
-3
-4
J3
-5
SENSOR
POWER
AND OUTPUT
* LINE FILTER MUST BE LOCATED LESS THAN
12 INCHES (30 CM) FROM ACOUSTIC DETECTOR.
2.5
33
95-8657
Appendix F
Approved Adjoining assemblies
DIRECT CONNECTION
AC100 with ATX10
Maximum Separation
Distance 500 Feet
REMOTE SENSOR
AC100 with STB
ATX10
WITH UNIVERSAL DISPLAY
AC100 with ATX10
FlexVu Model UD10
Warning
The AC100 must be connected as shown above for compliance with hazardous (classified) location
requirements.
2.5
34
95-8657
95-8657
FlexSonicTM Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2014 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.