Det-Tronics Multispectrum IR Flame Detector X3301 Safety Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
SAFETY MANUAL
Multispectrum IR Flame Detector
X3301
SAFETY-CERTIFIED MODEL X3301
MULTISPECTRUM INFRARED DETECTOR
QUALITY POLICY STATEMENT
All quality assurance control measures necessary
for safety management as specified in IEC 61508
Part 1 have been implemented. The quality
management system of Det‑Tronics is based on
the requirements of EN ISO 9001 and ANSI/ASQC
Q9001 through the application of the United
Technologies Company Achieving Competitive
Excellence (ACE) program. In addition, the
Quality Management System complies with
the European ATEX Directive requirements per
EN 13980, the International Electrotechnical
Commission requirements per OD005/V2, and the
supervised testing requirements per ISO 17025.
This manual addresses the specific requirements
and recommendations applicable to the proper
installation,
operation,
and
maintenance
of all Safety‑Certified (SIL‑Certified) X3301
Multispectrum Infrared Flame Detectors. The
safety function of the X3301 is to detect a variety
of fires and to provide present alarm status to
its relay, analog or LON outputs. For complete
information regarding performance, installation,
operation, maintenance, and specifications, refer
to instruction manual 95-8704.
1.1
©Detector Electronics Corporation 2015
1
Rev: 1/15
95-8720
When using the 0‑20 mA output with HART as a
safety output, it is required that Write Protect be set
to “on” to ensure that the HART is non‑interfering.
SAFETY MESSAGES
Procedures and instructions in this section may
require special precautions to ensure the safety of
personnel performing the operations. Information
that raises potential safety issues is indicated by
the word “Warning”. Always read and understand
these safety messages.
NOTE
All configuration changes to the X3301
must be verified by the user via a proof test,
power cycle and re-check of settings, or
other appropriate method.
WARNING
The X3301 is intended for use in hazardous
environments that may include explosive
levels of flammable gases and vapors.
This product must be properly installed,
operated and maintained. Improper
installation or use could result in an
explosion or fire resulting in death or
serious injury.
• Do not remove the detector cover in
explosive environments when device
power is on and circuits are live.
• Detector must be properly installed,
and wiring compartment cover must
be fully engaged to meet hazardous
area explosion-proof/ nonincendive
requirements.
The EQP model is designed for use exclusively
with the Det‑Tronics Eagle Quantum Premier
system. The detector communicates with the
system controller over a digital communication
network or EQPSL/SLC (Eagle Quantum Premier
Safety Loop / Signalling Line Circuit). The
EQPSL/SLC is a fault tolerant, two wire digital
communication network arranged in a loop
configuration. Analog and relay outputs are not
available on this model. For information regarding
the use of the SIL 2 Certified X3301 in an EQP
system, refer to the EQP Safety Manual 95‑8599.
The X3301 is designed for operation with a supply
voltage from 18‑30 volts DC. Proper operation
outside this range cannot be assumed.
Safety‑Certification of the X3301 includes:
• Analog Output
• Relay Output
• EQP LON Output version for X3301 only HART
Output as non-interfering
• xWatch Surveillance Camera output as
non-interfering*
DESIGN
The X3301 is a multispectrum infrared flame
detector that is classified as a Type B smart device
according to IEC61508. The standard model
provides an isolated 4‑wire, 0‑20 mA output,
together with on‑board Alarm and Fault relay
contacts. These outputs serve to indicate normal
operating condition of the detector, fault, or the
presence of a flame alarm. The X3301 contains
extensive self‑diagnostics and is programmed to
send the current output to a specified state (1 mA,
2 mA or 3 mA) upon internal detection of a failure
or fault condition.
Safety‑Certification of the X3301 does not
include:
Pulse Output
RS-485 Modbus signal
*
HART communication is available as an option.
The HART option allows the operator to monitor
the status of the detector, determine factory
settings, adjust field settings, and initiate field
tests. For complete information regarding HART
communication, refer to the HART Addendum
95‑8577.
1.1
2
The xWatch Surveillance Camera has been
evaluated as a non‑interfering device and is
approved for use with a Safety‑Certified X3301.
The xWatch camera can be attached directly
to the X3301 through a factory installed
integral connection adapter. The addition
of the xWatch does not affect the safety
performance of the X3301. Refer to manual
number 95‑8603 for details regarding the
xWatch camera.
95-8720
VALID INPUT RANGE
INSTALLATION
X3301 fault annunciation is provided on the 0‑20
mA signal output loop by signaling to a 1 mA, 2
mA, or 3 mA current output level. The receiving
device must be programmed to indicate a fault
condition when current levels reach over‑current
(≥ 21 mA) or undercurrent (≤ 3.6 mA).
NOTE
For complete information regarding
per formance, installation, operation,
maintenance and specifications, refer to
instruction manual 95-8704.
Tools Required:
• 14 mm hexagonal wrench
DIAGNOSTIC RESPONSE TIME
NOTE
The X3301 analog signal and relay outputs
are not safety-rated during detector warmup or signal output loop testing (including
proof testing). Alternative means should be
used at the job site to ensure facility safety
during these activities.
No special installation requirements exist
above and beyond the standard installation
practices documented in the instruction manual.
Environmental specification limits are also as
published in the general specifications section in
the instruction manual.
The X3301 will perform all critical diagnostic
functions within 58 minutes, worst case diagnostic
detection time. The user must not configure the
automatic oi test interval and failure annunciation
count combination to be greater than 58 minutes
(default setting is one minute intervals, with failure
annunciation after three failed oi tests).
The operating power distribution system must be
designed and installed so the terminal voltage
does not drop below 18 Vdc when measured
at any specific location. The maximum current
limit must be less than 2 amperes. The external
system providing power to the X3301 must
have overvoltage protection that ensures supply
voltage does not exceed 33 Vdc.
OPTICAL INTEGRITY TEST
The oi test is designed to generate a fault when
the unit’s detection range has been reduced
by 50% or more. This factor should be carefully
considered during detector placement with
regard to the required safety function.
CERTIFICATION
The X3301 Safety‑Certified version is certified to
IEC61508:2010 for single input use in low demand
SIL 2 Safety Instrumented Systems.
SAFETY-CERTIFIED PRODUCT
IDENTIFICATION
Safety Certification of all X3301 models meeting
SIL 2 safety standards is clearly identified on the
product label.
1.1
3
95-8720
Common Misuse Scenarios
START-UP AND COMMISSIONING
Refer to the General Application Information
section of the instruction manual for detailed
information on common misuse scenarios.
Application environment considerations
include the following:
All safety functions of the X3301 are active within
30 seconds of power‑up without any user action
required.
• Intense IR sources should not be present in
detection area.
The Safety Certified X3301 Flame Detector can
be commissioned by any qualified person with
knowledge of flame detection instruments and
the configuration device being used. Refer to
the Start‑Up section provided in the instruction
manual.
Commissioning Personnel
NOTE
The above scenarios will cause the X3301
relay or 4-20 mA outputs to annunciate a
high background fault and/or false alarm
depending on the intensity of the radiation
and the relay configuration.
Relay Configuration Requirements
The end user must provide transient and current
limiting on the output contacts of the relays. The
maximum relay contact output must be limited to
2 amperes at 30 Vdc. The load must be a resistive
load. The user must protect against transients
by using standard protection methods such as
proper grounding of shielded wire and separation
of relay load wires from other lines carrying
rapidly switched high current (e.g. large motor
power supply lines).
• Glass and Plexiglas windows attenuate
radiation and should not be located between
the detector and detection area.
• The detector must have a direct line-of-sight to
any potential flame source in the detection
area. Care must be taken to keep physical
obstructions out of the line of view of the
detector.
If the 0‑20 mA analog output is not being
monitored for fault conditions, the status of the
Fault relay must be monitored and appropriate
action taken. The fault relay is configured for
normally energized operation.
• The multispectrum IR flame detectors are to
be installed in locations where the risk of
mechanical damage is low.
NOTE
If the user suspects that damage or misuse
has occurred to the X3301, a full proof test
shall be performed.
NOTE
The black plastic shipping cap must be
removed prior to placing the detector into
service.
1.1
4
95-8720
Configuration
OPERATION, MAINTENANCE, INSPECTION
AND PROOF TESTING
Digital communication with the X3301 can be
used to monitor internal status and to modify
the factory settings. For specific information
regarding HART communication, refer to the
HART Addendum 95‑8577.
Tools Required:
• Magnetic oi test tool (p/n 102740‑002)
• Window cleaner (p/n 001680-001 or
isopropanol)
• Lens tissue and cotton swabs
• 4 mm flat blade screwdriver
NOTE
Prior to device configuration (setting
alarm thresholds, latch/non-latch function,
etc.) all alarm outputs must be bypassed.
The device is not safety certified during
configuration change activities.
After normal installation and start‑up have been
completed as recommended within the instruction
manual, Proof Tests must be performed for every
Safety‑Certified X3301 detector installed.
NOTE
All configuration changes to the X3301
must be verified by the user via a proof
test, power cycle and re-check of settings,
or other appropriate method. The LED flash
rate during power-up should be checked to
verify proper setting.
Personnel performing Proof Test procedures shall
be competent to perform the task. All Proof Test
results must be recorded and analyzed. Any
corrective actions taken must be documented
in the event that an error is found in the safety
functionality. The Proof Tests must be performed
at a frequency as shown in Table 1.
Configuration Protection
WARNING
Failure to perform the specified testing and
inspection may lower or void the SIL rating
for the product or system.
When using the 0‑20 mA output with HART as a
safety output, it is required that Write Protect be set
to “on” to ensure that the HART is non‑interfering.
If HART Write Protect is temporarily disabled,
the user must take specific action to re‑enable
Write Protect to ensure that HART communication
remains non‑interfering.
Table 1—Frequency of Proof Tests
Proof Test Name
Commissioning
Frequency
Visual Field Inspection Proof Test
Yes
As needed, depending on level and
type of contaminants present
Detector Response Mag oi Proof Test
Yes
Yearly
1.1
5
95-8720
VISUAL FIELD INSPECTION PROOF TEST
FAULT/FAILURE ACTION PLAN
Visual inspection of all Safety‑Certified X3301
Flame Detectors shall be conducted as needed
to confirm that there are no obstructions in the
optical field of view. Corrective action will include
removal of such impediments should they exist.
In the event of a non‑alarm condition result with
the Mag oi test, the standard Maintenance and
Troubleshooting procedures listed in the X3301
instruction manual must be followed. In the
event that the condition cannot be resolved, the
standard Device Repair and Return procedures
listed in the X3301 instruction manual must be
followed.
Completion of Visual Field Inspection Proof test
will be recorded and documented in the SIS
logbook.
Any and all failures to successfully complete the
alarm test must be recorded and documented in
the SIS logbook.
DETECTOR RESPONSE PROOF TEST
WARNING
Any external alarm equipment, systems
or signaling devices that could be
automatically initiated by performing this
test must be disabled or bypassed before
performing this test!
WARNING
Any external alarm equipment, systems or
signaling devices that were disabled must
be re-activated at the conclusion of proof
testing activities.
Tools Required:
• Magnetic oi test tool (part number 102740‑002),
HART Communicator, or hard wire trigger
capability
PRODUCT REPAIR
The X3301 is not field‑repairable, and any internal
device repairs must be conducted at the factory.
No firmware changes are permitted or authorized.
All failures indicated by internal diagnostics or
Proof Tests that cannot be resolved through the
troubleshooting and maintenance procedures
described in the X3301 manual must be reported
to the manufacturer.
All flame detectors must be performance tested
using the Magnetic oi / Manual oi Procedure
and inspected to ensure that they are capable
of providing expected performance and
protection. Manual oi tests may be initiated via
hard wire trigger or HART communication. Note
that the Mag oi Procedure and Manual oi Tests
are not interference free. During these tests the
unit is not performing normal flame detection
functions. Model X3301 provides an onboard
status LED, which indicates Green color when
internal operational parameters are normal.
See instruction or HART manuals for details on
performing Mag and Manual oi tests.
OPERATING, ENVIRONMENTAL AND
PERFORMANCE SPECIFICATIONS
The operating temperature range for the
Safety Certified X3301 is –40°C to +75°C.
The Safety‑Certified X3301 product versions
fully comply with, and must be operated in
accordance with the functional and performance
specifications provided in the instruction manual.
A 24 hour mean time to repair should be assumed
for safety availability calculations.
To indicate a successful proof test, the LED
changes to a red color, the Alarm and Auxiliary
relays change state to indicate an alarm condition,
and the current output indicates 20 mA. These
results should be verified on the control device.
SPARE PARTS
Refer to the spare parts section of the X3301
manual. Safety certification is based on a
sufficient number of spares to achieve a 24 hour
mean time to repair.
To indicate an unsuccessful proof test, the LED
changes to yellow, the Fault relay becomes
de‑energized, and the current output indicates
2 mA. The fault indication can be reset by
momentarily applying the magnet or manual oi
switch.
1.1
6
95-8720
CERTIFICATION AND FAILURE RATE DATA
Product Certifications
All Safety‑Certified X3301 models are certified
compliant to:
FM
®
APPROVED
IEC61508: 2010
Type B Device
FM, CSA, ATEX, CE, exida, and others.
Refer to the X3301 Instruction Manual for details.
Systematic Capability: SIL 2 certified
FMEDA Report available.
HFT: 0
For complete information regarding performance,
installation, operation, maintenance, and
specifications, refer to the instruction manual:
Low Demand Mode
PFDavg should be calculated for any safety
instrumented function using the X3301.
(Refer to FMEDA report for necessary information,
including DU rate).
X3301 95‑8704
Safety Accuracy: Not applicable.
Safety Response Time: See appendix A of the
instruction manual for
response time details.
Product Life: 13‑22 years, based on manufacturer
data.
All failure rate data for SIL verification is in the
FMEDA report, which is available upon request.
IEC 61508 Failure Rates in FIT1
Failure Category
lsd
lsu2
ldd
ldu
SFF3
X3301 IR Flame Detector,
Analog Output
0 FIT
115 FIT
921 FIT
74 FIT
92.1%
X3301 IR Flame Detector,
Relay Output
404 FIT
129 FIT
488 FIT
88 FIT
93.3%
X3301 IR Flame Detector,
Analog Output with HART
0 FIT
120 FIT
1147 FIT
93 FIT
93.2%
1
FIT = 1 Failure / 109 Hours
2
It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to IEC
61508, ed2, 2010.
3
Safe Failure Fraction needs to be calculated on (sub)system level.
1.1
7
95-8720
TERMS AND DEFINITIONS
EQP
Eagle Quantum Premier System
EQPSL/SLC Eagle Quantum Premier Safety
Loop / Signaling Line Circuit
FMEDA
Failure Mode Effects and
Diagnostics Analysis
HART
Highway Addressable Remote
Transducer
HFT
Hardware Fault Tolerance
PFD
Probability of Failure on Demand
(Probability of Dangerous Failure)
PFDavg
Average Probability of Failure on
Demand
SFF
Safe Failure Fraction
SIF
Safety Instrumented Function
SIL
Safety Integrity Level
SIS
Safety Instrumented System
X3301
Multispectrum IR Flame Detector
1.1
8
95-8720