Compur Monitors Statox 505 Sensor Head Instruction Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Statox 505 Sensor Head
Operations Manual
Statox 505 Sensor Head
Operations Manual
1
SAFETY INSTRUCTIONS
3
2
STATOX 505 CONSTRUCTION
4
3
INSTALLATION AND CONNECTION
5
3.1
3.2
3.3
Warning
Installation
Electrical connection
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
4
4.1
4.2
4.3
4.4
4.5
4.6
4.7
Statox 505 cable connection
Connection diagram with Statox 501 Control Module in the 2-wire mode
Connection diagram with Statox 501 Control Module in the 3-wire mode
Connection diagram with Statox 502 Control Module in the 2-wire mode
Connection diagram with Statox 502 Control Module in the 3-wire mode
START –UP AND SERVICE
Start - up and measuring mode
Setting the realtime clock
Setting the “service mode“ output signal
Calibrating the sensor
Prooftest
Info menu
Test menu
5
5
6
7
8
10
12
13
14
15
16
17
18
20
21
22
5
SENSOR REPLACEMENT
23
6
MAINTENANCE
24
7
SPARE PARTS AND ACCESSORIES
24
8
STATUS- AND ERROR MESSAGES
25
8.1
8.2
9
9.1
9.2
Status messages
Error messages
25
26
TECHNICAL DATA
27
General transmitter data
Sensor specific data
10 CE-DECLARATION OF CONFORMITY
2
27
28
29
1 Safety Instructions
The Statox 505 sensor head is certified as explosion-proof safety equipment for group II category 2.
The intended use is the measurement of toxic gas and oxygen concentration. Due to its intrinsically safe
design it is safe to install and operate this product in zone 1 and zone 2.
All relevant sensor parameters will be set automatically as soon as the sensor is connected.
The following safety guidelines must be observed in particular:
When installing and connecting the transmitter, the safety relevant electrical parameters and the
protection class of the sensor head must comply with local standards (e.g. IEC 60079-14).
If installed in a hazardous area, the power supply of the sensor heads must be intrinsically safe.
Recommended products see connection diagrams in chapter 3.3 and in chapter 7 (accessories).
The sensor head may only be operated within the specified environmental conditions.
Damaged or not tightly closed housings may cause malfunction or loss of accuracy.
All of the above warnings must be observed. Incorrect installation or connection will void the
explosion proof rating and thus be dangerous to life and assets.
3
2 Statox 505 construction
The housing cover is attached with 4 bayonet screws. To open it, just turn these screws 90° counter clockwise. The cover is secured to the housing with a steel strap.
3
2
4
5
R
1
6
7
11
8
10
9
1
2
3
4
5
6
7
8
9
10
11
4
Mounting plate with 4 holes 10 mm
Push buttons
Display
LED
Programming interface (not for customer use)
Cable terminal X1
Ground terminal
Clamp for cable shield
cable gland M16x1,5
Sensor cover including filter support
Securing strap for sensor cover
3 Installation and connection
3.1
Warning
If the sensor head is installed in hazardous areas, the power supply must be intrinsically safe. Observe
the safety - relevant specifications of sensor head, cable and barrier respectively intrinsically safe
repeater.
Caution:
Do not install the sensor unless the sensor head has been connected to the power supply.
The following specifications must be observed:
Uo ≤
Io ≤
Co ≥
Lo ≥
Ui
Ii
Ci + l . CL
Li + l . LL
Uo, Io, Co, Lo : certified repeater specifications
Ui, Ii, Ci, Li : sensor head specifications ( technical data)
CL = cable capacity in pF/m
LL = cable inductivity in nH/m
l = cable length in m
The allowable cable length is defined in most cases by the cable capacity:
l max = Co / CL (Ci is negligible).
Example:
Cable type LiYCY 0,75mm² : CL = 110 pF/m
Repeater: Co = 63 nF
l max = 573 m
Recommended cable type: see chapter 3.3.
3.2
Installation
Install the sensor head sensor downwards. Use stainless steel screws or insulate screws from mounting
plate to avoid corrosion. In case of potential static voltage, ground the sensor head.
The sensor head can be mounted to a wall with
2 or 4 screws without opening the housing:
Alternatively it can be mounted to a horizontal
or vertical pipe. Statox 505 pipe mounting kits
are listed in chapter 7 accessories.
5
Sataox 505 drilling plan and dimensions
3.3
Electrical connection
Use cable with 2 or 3 x 0,75 mm² with close - mashed shield, outer diameter ca. 6 mm
(e.g. type Oelflex 415 CP3 X 0,75).
Advantage of 3 - wire operation:
In the two wire mode, the output signal for service and system failure is the same (2 mA).
In the 3 - wire mode you can differentiate between “service” (non - critical = 2 mA) and “failure”
(critical = 0 mA).
If connecting the Statox 505 sensor head to a Statox 501 control module, follow the connecting
diagrams in the chapters 3.3.2 and 3.3.3.
If connecting the Statox 505 sensor head to a Statox 502 control module, follow the connecting
diagrams in the chapters 3.3.4 and 3.3.5.
If connecting the Statox 505 sensor head directly to a PCS, observe the following connecting diagram.
In case of 2-wire-mode use only terminals 1 and 2.
X1
V+
1
2-22mA
2
Sensor
I=0mA
Statox 505
6
3
0V
PCS
3.3.1
Statox 505 cable connection
Use cable with 2 or 3 x 0,75 mm² with close – mashed shield, outer diameter ca. 6 mm
(e.g. type Oelflex 415 CP3 X 0,75).
Do not install the sensor unless the sensor head is connected to the power supply.
Run 20 cm (8 in) of cable through the cable gland.
Strip the cable down to the shield. (A)
Shorten the shield to 10 mm (0,4 in) and bend it backward. Make sure it does not touch the
housing. (B)
Connect the wires as shown in the schematics. The terminal is plugged in. Remove it for easy
installation.
Draw the cable back until the shield matches the clamp
Fasten the cable gland.
Secure the shield with the clamp. Good contact provides best protection from electromagnetic
interference.
Plug the terminal in.
When the sensor head is connected to the power supply, the LED starts flashing for a short time
and the display shows the software index.
Now install the sensor (see chapter 4).
A
B
C
7 mm
1 2 3
X1
40-50 mm
10 mm max.
Ø 5 - 7 mm
7
3.3.2
Connection diagram with Statox 501 Control Module in the 2-wire mode
Before connecting the sensor head, select the appropriate program. Refer to the Statox 501 operations
manual and the program overview.
3.3.2.1
2-wire mode installation in non hazardous areas
A1
Remark:
The relays are shown
in ex-works setting in
normal operation.
A2
SF 4-20mA
A1
A2
Horn
SF
17 18 9 7 8 16 14 15 6 13 5 4
9 18 8 17 7 16 12 11
+ -
1
+ -
+24V/DC
+
2 -
Control module
4
+
5
Power
supply
L N PE
A1
A2
SF
+24V
Common alarm module
(optional)
Non hazardous area
Plant = Non hazardous area
-
+
1
2
3
Statox 505
8
X1
3.3.2.2
2-wire mode installation in hazardous areas
Caution: Incorrect connection of the intrinsically safe repeater might destroy it. Please take care for
correct polarity and avoid short circuits.
Repeater forms a current source: the terminal numbers on the drawing below refer to repeater type
9160/13-11-11s from manufacturer R.Stahl Schaltgeräte GmbH (or Siemens type 7NG4124-0AA00).
It requires an extra power supply and forms a current source at clamps 1 and 2.
A1
A2
A1
SF 4-20mA
A2
Horn
SF
17 18 9 7 8 16 14 15 6 13 5 4
9 18 8 17 7 16 12 11
Remark:
The relays are shown
in ex-works setting in
normal operation.
+ -
+24V/DC
1
A1
A2
SF
+24V
+
2 -
Control module
+ -
Power
supply
4
L N PE
repeater
(current source)
Common alarm module
(optional)
11
2
1
+
-
+
12
10
+
9
+24V/DC
7
Non hazardous area
Plant = hazardous area
1
X1
3
2
Statox 505
Repeater forms a current sink: the terminal numbers on the drawing below refer to repeater type
9160/13-10-11s from manufacturer R.Stahl Schaltgeräte GmbH. It requires an extra power supply and
forms a current sink at clamps 1 and 2.
A1
A2
A1
SF 4-20mA
9 18 8 17 7 16 12 11
A2
Horn
SF
17 18 9 7 8 16 14 15 6 13 5 4
Remark:
The relays are shown
in ex-works setting in
normal operation.
+ -
+24V/DC
1
2 Power
supply
A1
A2
SF
+24V
+
Control module
+ -
L N PE
43
repeater
(current sink)
Common alarm module
(optional)
11
4
1
+
-
2
+
12
10
+
9
7
+24V/DC
Non hazardous area
Plant = hazardous area
1
2
3
X1
Statox 505
9
3.3.3
Connection diagram with Statox 501 Control Module in the 3-wire mode
Before connecting the sensor head select the appropriate program. Refer to the Statox 501 operations
manual and the program overview.
3.3.3.1
3-wire mode installation in non – hazardous areas
A1
A2
SF
4-20mA
9 18 8 17 7 16 12 11
A1
A2
Horn
SF
17 18 9 7 8 16 14 15 6 13 5 4
Remark:
The relays are shown
in ex-works setting in
normal operation.
+ -
1
+ -
+24V/DC
A1
A2
SF
+24V
+
2 -
Control module
4
+
5
Power
supply
Common alarm module
(optional)
11
L N PE
Non hazardous area
Plant = Non hazardous area
-
+
1
2
3
Statox 505
10
X1
3.3.3.2
3-wire mode installation in hazardous areas
Caution: Incorrect connection of the intrinsically safe repeater might destroy it. Please take care for
correct polarity and avoid short circuits.
Repeater forms a current source: the terminal numbers on the drawing below refer to repeater type
9160/13-11-11s from manufacturer R.Stahl Schaltgeräte GmbH (or Siemens type 7NG4124-0AA00).
It requires an extra power supply and forms a current source at clamps 1 and 2.
A1
A2
A1
SF 4-20mA
9 18 8 17 7 16 12 11
A2
Horn
SF
17 18 9 7 8 16 14 15 6 13 5 4
+ -
+24V/DC
1
A1
A2
SF
+24V
+
Control module
2 + -
power
supply
L N PE
repeater
(current source)
4
11
1
+
2
+
12
10
11
1
2
3
+
9
7
Remark:
The relays are shown
in ex-works setting in
normal operation.
common alarm module
(optional)
+24V/DC
Non hazardous area
Plant = hazardous area
X1
Statox 505
Repeater forms a current sink: the terminal numbers on the drawing below refer to repeater type
9160/13-10-11s from manufacturer R.Stahl Schaltgeräte GmbH. It requires an extra power supply and
forms a current sink at clamps 1 and 2.
A1
A2
A1
SF 4-20mA
9 18 8 17 7 16 12 11
A2
Horn
SF
17 18 9 7 8 16 14 15 6 13 5 4
+ -
+24V/DC
1
A1
A2
SF
+24V
+
2 -
control module
+ -
power
supply
L N PE
repeater
(current sink)
3
4
1
+
2
+
12
10
11
1
2
3
+
9
7
X1
Remark:
The relays are shown
in ex-works setting in
normal operation.
common alarm module
(optional)
+24V/DC
Non hazardous area
Plant = hazardous area
Statox 505
11
3.3.4
Connection diagram with Statox 502 Control Module in the 2-wire mode
Before connecting the sensor head select the appropriate program. Refer to the Statox 502 operations
manual and the program overview.
3.3.4.1 2-wire mode installation in non-hazardous areas
Power
supply
X1
3.3.4.2 2-wire mode installation in hazardous areas
Caution:
Incorrect connection of the intrinsically safe
repeater might destroy it. Please take care for
correct polarity and avoid short circuits.
The terminal numbers on the drawing refer to
repeater type 9160/13-11-11s from manufacturer
R.Stahl Schaltgeräte GmbH (or Siemens type
7NG4124-0AA00).
It requires an extra power supply and forms a
current source at clamps 1 and 2.
Power
supply
Repeater
Non hazardous area
X1
12
Plant = hazardous area
3.3.5
Connection diagram with Statox 502 Control Module in the 3-wire mode
Before connecting the sensor head select the appropriate program. Refer to the Statox 502 operations
manual and the program overview.
3.3.5.1 3-wire mode installation in non-hazardous areas
Power
supply
X1
3.3.5.2 3-wire mode installation in hazardous areas
Caution:
Incorrect connection of the intrinsically safe
repeater might destroy it. Please take care for
correct polarity and avoid short circuits.
The terminal numbers on the drawing refer to
repeater type 9160/13-11-11s from manufacturer
R.Stahl Schaltgeräte GmbH (or Siemens type
7NG4124-0AA00).
It requires an extra power supply and forms a
current source at clamps 1 and 2.
Power
supply
Non hazardous area
Repeater
Plant = hazardous area
X1
13
4 Start –up and service
Sensor head keyboard:
+
Press UP and DOWN at the same time to enter the menu.
Increase / decrease the displayed parameter.
Press and hold button for fast forward.
R
RESET: One level up in the menu.
ENTER
Timeout: The sensor head returns automatically into the measuring mode if no key is pressed for more
than 5 minutes.
14
4.1
Start - up and measuring mode
As soon as the sensor head is connected to the power supply, it starts a self test and shows the
software index.
Now install the sensor and filter. Please observe the handling instructions in chapter 5 !
Remove the yellow protection cap from the sensor cover!
As soon as the sensor is connected, the sensor head displays the parameter version, the gas to be
detected, the measuring range and the best before date of the sensor. As soon as zero has stabilized,
the instrument goes into the measuring mode. The green LED starts flashing.
As long as the sensor head is not ready, the output signal is in the system fail mode, i. e. 2 mA
when operated in the 2 wire mode, 0 mA when operated in the 3 wire mode.
When the sensor head has completed the start – up sequence, you can start setting the real time
clock (see chapter 4.2) and the service mode output signal (see chapter 4.3).
START
Program version
no
Sensor
detected?
yes
Parameter
version
Gas
Measuring
range
best before
Initialization
successful
no
yes
MEASURING MODE
Reading
15
4.2
Setting the realtime clock
The clock is set ex works to CET. Please set it to your local time to make sure you get correct
protocols of calibration and alarms.
The clock has a back-up battery to save the time setting when power is disconnected.
The segments flashing can be set with the up / down buttons.
You can leave the time set menu by pushing the reset button.
MEASURING MODE
R
+
CODE=00
44
R
R
R
hh:mm
dd-mm-yy
hh:mm
dd-mm-yy
hh:mm
dd-mm-yy
dd-mm-yy
16
4.3
Setting the “service mode“ output signal
The following table shows the potential modes and outputs.
2-wire operation
Failure
(critical failure)
2 mA
Service
(non critical failure)
2 mA
4 mA
0 mA
3-wire operation
2 mA
4 mA
Display on the Statox 501
control module
“SerU” (Service)
“0”
“Er 2” (Error 2)
“SerU” (Service)
“0”
Notice: During the sensor replacement in the REPLACE menu, the sensor head remains in the service
mode - even if no sensor is connected!
If the sensor head is operated as a safety relevant device according to EN 50402 (Functional Safety)
the output in the service mode must be 2 mA !
MEASURING MODE
R
+
CODE=00
24
R
R
I-SERV
2 MA
2 MA SET
4 MA
4 MA SET
17
4.4
Calibrating the sensor
Sensor head and sensor must have the same temperature!
You need a Statox 505 calibration adapter (art.no. 570505), a gas tubing 4x1 mm (art.no. 556710) and
span gas (acceptable gas concentrations see chapter 9.2). If the environment is not clean, you need
synthetic air for zeroing.
In case the calibration fails for whatever reason, the sensor head will continue to operate with the
existing parameters, but the display will alternate showing the measured value and ZERO ADJ or
CALIB until a calibration procedure has been completed.
O2-sensors do not require a zero adjustment, as their output in pure nitrogen is nearly 0 nA. The span
calibration can be done with clean ambient air or synthetic air.
Gas
Filter
Calibration
adapter
Procedure
Affix the adapter on the sensor cover until it catches (clockwise rotation).
Connect the calibration adapter to the span gas cylinder.
Enter the service menu and select code 11 to enter the calibration routine. Set Zero.
Push ENTER button. As soon as the display shows GAS ON, open the valve. The gas flow should be
ca. 20 l/h (300 ml/min). If you want to avoid span gas to be released into the environment, you can
connect an active carbon filter art.no. 806488 to the exhaust of the gas adapter. Make sure there is no
pressure building up in the adapter!
The display will show GAS.IS.ON until the reading is stable. Then it will show CONCENT?
Now press ENTER. The display will now show the concentration of the recently used span gas. If you
have used a gas with different concentration, adjust with the up / down buttons and confirm with
ENTER.
When the display shows DONE, press ENTER to display the present concentration. Now close the
regulator and remove the calibration adapter (clockwise rotation).
To return to the measuring mode, press ENTER again. The green LED starts flashing.
If you fail to press ENTER, the sensor head will return to the measuring mode automatically after a
timeout of 5 minutes.
18
MEASURING MODE
R
+
CODE =00
R
11
R
present
reading
CALIB
O2
Sensor
yes
no
DONE
ERR 7
yes
20.9 VP
Calibration
successful?
xxx PPM
Setting of span gas
concentration
CONCENT?
no
ZEROING
000
R
flashing during
zeroing time
R
GAS ON
GAS.IS.ON
19
4.5
Prooftest
A prooftest provides a verification of the transmitter performance under field conditions. It must be
performed in regular intervals, if the transmitter is used as a safety relevant device. As long as the
menu “Prooftest” is active, the output signal is set to 2 or 4 mA. In case the entire alarm chain must be
tested, this must be done in the measuring mode.
You need the Statox 505 calibration adapter art.no. 570505, a gas tubing 4x1 mm , art.no. 556710 and
span gas with a concentration within the measuring range, preferably close to the alarm threshold.
Affix the adapter on the sensor cover until it catches (clockwise rotation).
Connect the gas adapter to the span gas cylinder.
Enter the service menu and choose code 99 to enter the proof test routine.
As soon as the display shows PROOF, open the valve and press ENTER. The gas flow should be ca.
20 l/h (300 ml/min). If you want to avoid span gas to be released into the environment, you can
connect an active carbon filter art.no. 806488 to the exhaust of the gas adapter. Make sure there is no
pressure building up in the adapter!
The display will show the present concentration. Wait until the signal is stable before reading.
Close the gas regulator and remove the calibration adapter (clockwise rotation).
Return to the measuring mode by pushing the RESET button, stepping upward in the menu until you
reach the measuring mode.
If a new calibration is necessary proceed according chapter 4.4.
Special timeout: If you do not push a button for 30 minutes, the transmitter returns automatically to the
measuring mode.
A 2- or 3-time LED flashing during the proof test signalizes a periodical hardware test.
MEASURING MODE
R
+
CODE=00
99
R
R
PROOF
xxx PPM
20
R
4.6
Info menu
This menu provides information about alarm history and sensor parameters.
The exposure recording starts as soon as the end of the measuring range is exceeded.
You can access the most recent 3 alarm events (start, end of range and end). The alarm events are
not listed chronologically. For oxygen sensors only: the exposure recording starts as soon as the
measured value drops below the detectable limit (see chapter 9.2).
The total exposure information (DOSIS) is not updated permanently. Exposure by calibration is
neglected. The maximum exposure reading depends on the measuring range. It is either 9,99 or
99,9 or 999 ppm * min.
The total exposure recording is inactive for oxygen sensors.
The calibration factor is a parameter used by the microprocessor. It cannot be used to obtain
information about the sensor signal.
MEASURING MODE
R
+
CODE=00
R
33
R
R
ALARM
R
R
R
START 1
dd.mm.yy
hh:mm
DOSIS
alternating
xxx PPMH
R
SENSOR
Gas type
Measuring
range
ALARM 1
xxx PPM
alternating
END 1
dd.mm.yy
hh:mm
alternating
Calibration
factor FJ
JUSTDATE
last calibration date
dd.mm.yy
R
END 3
dd.mm.yy
hh:mm
alternating
Sensor
serial number
Sensor
Best before
Week / Year
21
4.7
Test menu
In order to check the signal loop, the sensor head can generate 4, 12 and 20 mA.
Caution: this might trigger an external alarm!
The display can be tested by displaying a sequence of fonts and patterns.
The sensor head can also display temperature.
MEASURING MODE
+
R
CODE=00
R
22
R
R
I-TEST
R
4.00 MA
LCD-TEST
Segments
13x
R
12.00 MA
Decimal points
5x
R
22
20.00 MA
Font
R
TEMP
xy.z °C
5 Sensor replacement
Please observe the precautions to avoid electrostatic voltage, when handling electronic devices. To avoid
the sensor from being removed, while exchanging data with the sensor head, enter the service menu
before you remove it. In the menu REPLACE the sensor can be replaced without generating a system
failure alarm (see chapter 4.3). During the sensor replacement the sensor head will remain in the service
mode.
Handling instructions:
MEASURING MODE
+
R
Unscrew the sensor cover counterclockwise. Take care not to twist
the safety strap.
CODE=00
R
05
R
Pull the sensor downwards to
remove it.
The sensor head remains
in the service mode.
In case there is a shunt on the
new sensor remove it.
REPLACE
Remove sensor
REPLACE
flashing
Install sensor
Install the new sensor.
An initialization follows as
described in chapter 4.1.
Parameter
Version
Tighten the sensor cover
hand tight.
Do not jam the strap!
Gas
Loosen the filter holder
with a screw driver
and pull it downwards.
FS
best before
Initialization
successful ?
yes
REPLACED
Current gas
concentration
no
Remove the old filter.
If necessary use a screw driver
at the recess of the filter.
A fresh filter comes with every
sensor. Insert it as shown
in the picture. It must be placed
close to the sensor.
Clean the filter holder,
sensor cover and O-Ring
if necessary.
Press the filter holder in place.
The Statox 505 displays the actual concentration while
still remaining in the service mode. After pushing the
ENTER button, or after a timeout of 30 min the sensor
head returns to the measuring mode.
23
6 Maintenance
Clean the Statox 505 with a humid wipe. Do not use detergents, solvents or steam jet.
Inspect the housing for damage and pollution so that gas can securely access the sensor.
If the sensor head is used in extremely harsh environment an extra spray shield can be installed.
Calibrate the sensor with the spray shield installed. Contact Compur Monitors for technical support!
If the Statox 505 sensor head is used as a safety relevant device in terms of functional safety standard
(EN 50402, IEC 61508), a regular proof test is mandatory (see chapter 4.5).
7 Spare parts and accessories
Description
Statox 505 Calibration adapter
Statox 505 Spray shield
Pipe mounting kit 1“ outer diameter 32-37 mm / 1,25 -1,45 in
Pipe mounting kit 1,5“ outer diameter 48-53 mm / 1,90 – 2,08 in
Pipe mounting kit 2“ outer diameter 59-63 mm / 2,32 - 2,48 in
Intrinsically safe repeater 2- or 3 –wire, current source
(type 9160/13-11-11s)
Statox 505 functional safety document
Active carbon filter
Gas tube 1m
Statox 505 Filter holder
Spare sensors and technical data see chapter 9.2 !
24
Article number
570505
570560
570578
570565
570589
803360
570555
806488
556710
570510
8 Status- and Error messages
8.1
Status messages
Display
Description
Code request
Enter concentration
Zeroing
Apply span gas
Span gas has been detected
Flashing: zeroing in progress, steady: zero found
Calibration menu.
If alternating with measured value: calibration required
If alternating with measured value: zeroing required
Calibration completed
Prooftest
Set signal output in the service mode
Output signal = 2 mA in the service mode
Confirmation of the set value
Error message, details see chapter 8.2
Test of the signal loop
Display test
Temperature inside the sensor head
Alarm history
Total exposure of the sensor
Exposure in ppm*h
Exposure is in excess of the display range
Sensor information menu
Date of the most recent calibration resp. initial operation of the sensor
Sensor serial no.
Sensor best before ww/yy
Real time clock date dd/mm/yy
Real time clock date in the info menu dd/mm/yy
Real time clock time hh/mm
permanent: request for sensor removal
flashing: request for sensor installation
Successful sensor replacement
25
8.2
Error messages
If there is no display at all, check fuse and polarity. Fuse replacement by authorised personnel only.
Error
Ranking
critical
critical
non
critical
critical
non
critical
non
critical
non
critical
critical
critical
critical
critical
critical
critical
./.
critical
Reason
The sensor diagnostics (heart beat)
has detected a faulty sensor.
Faulty 4-20 mA signal output
(nominal and actual value do not
match).
Correction
Press ENTER, if problem persists replace
sensor.
Press ENTER, if problem persists call
Compur Monitors service center.
Press ENTER. The instrument returns to the
measuring mode using the old parameters,
but will alternatingly display CALIB and the
measured value. Replace sensor as
necessary.
Zero drift warning – negative zero.
Press ENTER. The software goes to the
Error occurs only during measuring CALIB menu. Start a zeroing procedure.
mode.
Replace sensor as necessary.
Press ENTER. The software goes to the
CALIB menu. Start a new zeroing procedure.
Unable to zero (during zeroing
Unless a correct zeroing has been
procedure).
completed, the display will alternate
displaying the measured value and
ZEROADJ. Replace sensor as necessary.
Press ENTER. The instrument returns to the
measuring mode using the old parameters,
Timeout, no stable zero found during but will alternatingly display ZEROADJ and
zeroing procedure.
the measured value. Repeat zeroing
procedure with synthetic air.
Replace sensor as necessary.
Press ENTER. The instrument returns to the
While calibrating: Sensor is not
measuring mode using the old parameters,
sensitive enough, or span gas with
but will alternating display CALIB and the
wrong concentration has been used. measured value.
Replace sensor as necessary.
Transmitter is operating outside the
Press ENTER.
temperature specifications.
F-RAM Error, occurs only with
Press ENTER. If problem persists, replace
mounted sensor.
sensor.
Press ENTER, if problem persists call
Hardware error - amplifier.
Compur service center.
Press ENTER, if problem persists call
Hardware error - potentiostat.
Compur service center.
Press ENTER, if problem persists call
Hardware error- power supply.
Compur service center.
Press ENTER, if problem persists call
Flash - error
Compur service center.
CPU / RAM
This error creates a repeated reset. Call Compur service center.
It cannot be displayed.
Timeout, no plateau found during
calibration (span gas flow incorrect,
flow instable, sensor out of specs).
Critical errors set the output signal to 2 mA in the 2 – wire mode or to 0 mA in the 3 – wire mode. Non
critical errors normally occur during maintenance or calibration. They have no impact on the system
status.
26
9 Technical data
9.1
General transmitter data
Product name:
Type:
Manufacturer:
Measuring principle:
Operating temperature:
Storage temperature:
Humidity:
Pressure:
Accuracy at calibration point:
Power supply:
Connection:
Output signal:
In service mode:
In system fail mode:
Overrange:
Display:
Dimensions (HxWxD):
Weight:
Housing material:
Protection class EN 60529:
Operation position:
EMC:
Statox 505 Transmitter
5375
COMPUR Monitors GmbH & Co. KG, D-81539 München
electrochemical
-30°C to +60°C / -22° F to 140° F
-30°C to +60°C / -22° F to 140° F
0 to 99% r.h. (non condensing)
900 to 1100 hPa
+/- 10%
12 -28 VDC, max. 22mA
2- or 3-Wire
4 - 20 mA, max. load 700 Ohm
2 or 4 mA adjustable
0 mA in 3 - wire mode, 2 mA in 2 - wire mode
22 mA
8-digits, 14 segments
225 x 180 x 90 mm / 8,9 x 7,1 x 3,5 in (incl. mounting plate)
1040 g / 36,7 ounce (incl. mounting plate)
ABS chromium plated / stainless steel
IP 65
Sensor downwards
EN 50270
ATEX:
Application:
EC type examination certificate:
Parameters:
Ui :
Ii:
Internal capacity Ci:
Internal inductance Li:
Ex ib IIC T4 (EN 60079-0 and EN 60079-11)
II 2 G
BVS 09 ATEX E 104
max. 28 VDC
max. 93 mA , Pi = 650 mW
neglectible
neglectible
Functional safety:
SIL 2
More detailed information with regards to functional safety see
Statox 505 functional safety document art.no. 570555.
27
HCl
HCl
SO2
O2
Cl2
Cl2
Cl2
CO
NO2
NO2
NO2
50 ppm
5 ppm
100 ppm
10 ppm
5 ppm
300 ppm
15 ppm
10 ppm
5 ppm
COCl2 20 ppm
COCl2 15 ppm
COCl2 0,5 ppm
COCl2 0,5 ppm
HCN 100 ppm
20 ppm
H2S 100 ppm
H2S
100 ppm
35 Vol%
COCl2
150 ppm
COCl2 100ppm
HCN
300 ppm
530765
530677
530617
530522
530511
530508
530509
530520
530537
530507
530505
530515
530564
530504
530502
530688
530682
530702
530694
530692
530503
530673
530501
530571
0 to +50
-10 to +40
-10 to +40
-30 to +50
-20 to +50
-20 to +50
-20 to +50
-30 to +55
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
-20 to +50
Temperature
range [°C]
15 - 90
30 - 95
20 - 95
20 - 95
15 - 90
20 - 95
20 - 95
20 - 95
5 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
20 - 95
Humidity range
[% r.h.]
(non
condensing)
< 10
<5
< 60
< 10
< 10
< 10
<5
<5
<5
<5
<5
<5
<5
< 10
<5
<5
<5
< 10
< 10
< 10
< 10
< 10
< 10
<5
<5
<5
<5
typical
response
time
t20 [s] at 20°C
1.0 – 9.0
0.10 – 1.00
0.10 – 1.00
100 – 500
100 – 300
20 – 100
10 – 100
5.0 – 50.0
0.50 – 5.00
20.9 Vol%
10 – 50
4.0 – 6.0
0.50 – 4.50
20 – 270
3.0 – 10.0
1.0 – 10.0
0.50 – 4.50
10 – 90
3.0 – 10.0
3.0 – 15.0
0.10 – 0.80
0.10 - 0.50
0.10 - 0.40
10 - 90
1.9 – 18.0
10 - 90
1.9 – 18.0
Span gas
concentration
[ppm]
0.2
0.02
0.02
5
5
3
1
0.3
0.02
2 Vol%
1
0.3
0.03
3
0.2
0.2
0.02
2
0.2
0.2
0.02
0.02
0.02
2
0.3
2
0.3
min.
detectable
concentration
[ppm]
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
<-3%
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
< - 10 %
< - 10 %
< - 10 %
< - 10 %
< - 10 %
< - 10 %
< - 15 %
< - 15 %
< - 15 %
< - 15 %
Sensitivity
drift within 6
months
< 0.1
< 0.01
< 0.01
<3
<3
< 1 (T=const)
< 0.3
< 0.3
< 0.05
0
< 0.1
< 0.1
< 0.02
<3
< 0.01
< 0.01
< 0.01
< 0.2
< 0.05
< 0.05
< 0.01
< 0.01
< 0.01
< 0.2
< 0.2
< 0.2
< 0.2
Zeropoint
drift / month
[ppm]
span gas ≥ 5 ppm recommended
warm-up time > 1h possible
best before date = date of manufacture
warm-up time > 1h possible
warm-up time > 1h possible
warm-up time > 1h possible
Calibration only from 0°C to 50°C
Calibration only from 0°C to 50°C
with H2S filter
warm-up time > 1h possible
10 - 95
<5
0.05 – 0.50
0.01
< - 15 %
< 0.01
warm-up time > 1h possible
Calibration with ambient air
-20 to +50
1 ppm
Remarks
NH3
1000 ppm
530506
-20 to +40
15 - 90
530619
Articlenumber
H2
1 ppm
530625
-20 to +40
Gas type and
Measuring
range
H2
1 ppm
530615
20 ppm
O3
10 ppm
0,5 ppm
N2H4
HF
AsH3
warm-up time > 1h possible
bump test with approx. 1 ppm NO2 possible
< 0.01
< 0.01
bump test with approx. 5 ppm NO2 possible
< - 15 %
< - 15 %
< 0.05
0.01
0.02
< - 15 %
0.10 – 1.00
0.10 – 0.50
0.05
<5
< 10
0.50 – 3.00
10 - 95
20 - 95
< 10
-20 to +50
-20 to +50
20 - 95
530720
530523
-20 to +50
1 ppm
ClO2 1 ppm
530723
PH3
ClO2 5 ppm
28
Sensor specific data
9.2
10 CE-Declaration of conformity
29
Specifications are subject to change without notice, and are provided only for comparison of products. The conditions
under which our products are used, are beyond our control. Therefore, the user must fully test our products and / or
information to determine suitability for any intended use, application, condition or situation. All information is given
without warranty or guarantee. Compur Monitors disclaims any liability, negligence or otherwise, incurred in
connection with the use of the products and information. Any statement or recommendation not contained herein is
unauthorized and shall not bind Compur Monitors. Nothing herein shall be construed as a recommendation to use
any product in conflict with patents covering any material or device or its use. No licence is implied or in fact granted
under the claims of any patent. Instruments are manufactured by Compur Monitors GmbH & Co. KG, Munich.
The General Conditions of Supply and Service of Compur Monitors GmbH & Co. KG, Munich, are applicable.
Compur Monitors GmbH & Co. KG
Weißenseestraße 101
D-81539 München
Tel.: ++49/89/ 6 20 38 268
Fax : ++49/89/ 6 20 38 184
http://www.compur.com
E-Mail: compur@compur.de
5375 000 998 07 07 / 07.15
30
570553