Emerson Model 242 Flow-Through Toroidal Conductivity Sensor Instruction Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instruction Manual
PN 51-242/rev E
March 2012
Model 242
Flow-Through Toroidal Conductivity Sensor
ESSENTIAL INSTRUCTIONS
READ THIS PAGE BEFORE PROCEEDING!
Rosemount Analytical designs, manufactures, and tests its products to
meet many national and international standards. Because these instruments are sophisticated technical products, you must properly install,
use, and maintain them to ensure they continue to operate within their
normal specifications. The following instructions must be adhered to and
integrated into your safety program when installing, using, and maintaining Rosemount Analytical products. Failure to follow the proper/ instructions may cause any one of the following situations to occur: Loss of life;
personal injury; property damage; damage to this instrument; and
warranty invalidation.
• Read all instructions prior to installing, operating, and servicing the
product. If this Instruction Manual is not the correct manual, telephone 1-800-654-7768 and the requested manual will be provided.
Save this Instruction Manual for future reference.
• If you do not understand any of the instructions, contact your
Rosemount representative for clarification.
• Follow all warnings, cautions, and instructions marked on and
supplied with the product.
• Inform and educate your personnel in the proper installation, operation, and maintenance of the product.
• Install your equipment as specified in the Installation Instructions of
the appropriate Instruction Manual and per applicable local and
national codes, for example, ANSI B16.5. Connect all products to the
proper electrical and pressure sources.
• To ensure proper performance, qualified personnel should install,
operate, and maintain the product.
• When replacement parts are required, ensure that qualified people
use replacement parts specified by Rosemount Analytical.
Replacement of original components with those constructed from
alternative materials will void any CSA, FM, and BASEEFA/CENELEC agency approvals that were applicable to the original device.
Furthermore, replacement of original components with those constructed from alternative materials might change the pressure, temperature, and/or performance specifications from those of the original
configuration. Ensure replacement parts are compatible with process
requirements. Unauthorized parts and procedures can affect the
product’s performance, place the safe operation of your process at
risk, and may result in fire, electrical hazards, or improper operation.
• Ensure that all equipment doors are closed and protective covers are
in place, except when maintenance is being performed by qualified
persons, to prevent electrical shock and personal injury.
Emerson Process Management
Rosemount Analytical Inc.
2400 Barranca Parkway
Irvine, CA 92606 USA
Tel: (949) 757-8500
Fax: (949) 474-7250
http://www.rosemountanalytical.com
© Rosemount Analytical Inc. 2012
DANGER
HAZARDOUS AREA INSTALLATION
Installations near flammable liquids or in hazardous
area locations must be carefully evaluated by qualified on site safety personnel. This sensor is not
Intrinsically Safe or Explosion Proof.
To secure and maintain an intrinsically safe installation, the certified safety barrier, transmitter, and
sensor combination must be used. The installation
system must comply with the governing approval
agency (FM, CSA, BASEEFA/CENELEC, or ATEX)
hazardous area classification requirements.
Consult your analyzer/transmitter instruction manual for details.
Replacement of original components with those constructed from alternative materials will void any
CSA, FM, and BASEEFA/CENELEC agency
approvals that were applicable to the original device.
Proper installation, operation and servicing of this
sensor in a Hazardous Area Installation is entirely
the responsibility of the user.
CAUTION
SENSOR/PROCESS
APPLICATION COMPATIBILITY
The wetted sensor materials may not be compatible
with process composition and operating conditions.
Replacement of original components with those constructed from alternative materials might change the
pressure, temperature, and/or performance specifications from those of the original sensor configuration. Application compatibility is entirely the responsibility of the user.
MODEL 242
TABLE OF CONTENTS
MODEL 242
TOROIDAL CONDUCTIVITY SENSOR
TABLE OF CONTENTS
Section Title
Page
1.0
MODEL 242 SENSOR .............................................................................................
1
1.1
Features and Applications........................................................................................
1
1.2
Specifications ...........................................................................................................
2
1.3
Ordering Information ................................................................................................
5
1.4
Installation ................................................................................................................
7
1.5
Calibration ................................................................................................................
10
1.6
Maintenance ............................................................................................................
13
2.0
Troubleshooting .....................................................................................................
14
3.0
Replacement Parts.................................................................................................
16
3.1
General ....................................................................................................................
16
3.2
Remove the Sensor From the Process ....................................................................
16
3.3
Disassemble the Sensor ..........................................................................................
16
3.4
Re-assemble the Sensor .........................................................................................
19
3.5
Re-install the Sensor into the Process .....................................................................
19
4.0
Return of Materials ................................................................................................
20
LIST OF TABLES
Table No. Title
Page
1-1
Nominal Cell Constants for 242 Sensors.................................................................
10
2-1
Resistance vs. Temperature for RTD (Resistance Temperature Detector) .............
14
2-2
Sensor Resistance Check........................................................................................
14
3-1
Replacement Parts and Accessories .......................................................................
17
3-2
Sensor Bolt Removal & Installation Guide...............................................................
18
i
MODEL 242
TABLE OF CONTENTS
MODEL 242
TOROIDAL CONDUCTIVITY SENSOR
LIST OF FIGURES
Figure No. Title
Page
1-1
Pressure-Temperature Specs for 1”, 1.5”, & 2” Sensors: Models 242-02/03/04 ....
3
1-2
Pressure-Temperature Specs for 3” & 4” Sensors: Models 242-06/08 ...................
3
1-3
Pressure-Temperature Specs for 1” & 2” Sensors: Alumina Liner ..........................
4
1-4
Pressure-Temperature Specs for 3” & 4” Sensors: Alumina Liner ..........................
4
1-5
Dimensional Drawing ...............................................................................................
7
1-6
Installation and Torque Guidelines...........................................................................
8
1-7
Sensor to Junction Box Wiring ................................................................................
9
1-8
Sensor/Junction Box/RTD Assembly .......................................................................
9
1-9
Extension Cable ......................................................................................................
10
1-10
Extension Cable to Instrument Model 54eC Wiring................................................
11
1-11
Extension Cable to Instrument Model 1055 Wiring .................................................
11
1-12
Extension Cable to Instrument Models 3081T & 4081T Wiring...............................
12
1-13
Extension Cable to Instrument Model 81T Wiring ...................................................
12
1-14
Extension Cable to Instrument Model Xmt Pipe/Wall Mount Enclosure..................
12
1-15
Extension Cable to Instrument Model Xmt Panel Mount Enclosure........................
13
2-1
Sensor Circuit for Troubleshooting ..........................................................................
15
3-1
Model 242 Sensor - Exploded View ........................................................................
18
3-2
Flange Assembly......................................................................................................
19
About This Document
This manual contains instructions for installation and operation of the Model 242 Flow-Through
Toroidal Conductivity Sensor. The following list provides notes concerning all revisions of this document.
Rev. Level
Date
Notes
A
11/02
This is the initial release of the product manual. The manual has been
reformatted to reflect the Emerson documentation style and updated to reflect
any changes in the product offering.
B
8/03
Corrected wiring references in text and drawings. Added information regarding
ATEX approvals with Model 5081T.
C
5/04
Added information regarding the alumina liner, and updated wiring diagrams.
03/12
Update addresses pages 22 and 24
D
E
ii
MODEL 242
SECTION 1.0
242 SENSOR
SECTION 1.0
242 SENSOR
• FLOW THROUGH DESIGN is ideal for use with viscous,
abrasive, or fibrous process liquids.
• OVER 250 CONFIGURATIONS to meet customers' needs.
• REPLACEABLE LINER in glass-filled PEEK, TEFLON, or
ALUMINA reduces long-term operating costs.
• DIN and ANSI FLANGES compatible with all piping installations.
• LINE SIZES of 1 through 4 inches (DN 25, 40, 50, 80 and
100).
• IN-LINE CALIBRATION saves money by reducing labor
and down-time.
• TEMPERATURE SENSOR and JUNCTION-BOX included.
1.1 FEATURES AND APPLICATIONS
Rosemount Analytical Toroidal Conductivity Sensors
are ideal for use in processes where contacting sensors -- those with electrodes exposed to the measured
solution -- would corrode or become fouled.
The 242 Flow Through Toroidal conductivity sensor
consists of two toroids surrounding a pipe through
which the process liquid flows. One toroid acts as a
transmitter and the other as a receiver. Energizing the
transmitter toroid induces an electric current in the
process solution which induces an electric current in
the receiver toroid. The strength of the induced current
is directly proportional to the conductivity of the solution.
The 242 sensor is available in over two hundred fifty
configurations to meet the needs of many applications
and installations. Line sizes of 1, 1.5, 2, 3, and 4 inches (25, 40, 50, 80, and 100 mm) are available with
both ANSI and DIN compatible flanges. A variety of
liner materials and O-rings are available to ensure
compatibility with most process liquids.
The 242 sensor is easy to install. It fits in the process
piping between mounting flanges. Special grounding
rings are not needed because the sensor has contact rings built into it. Recessed bolts hold the sensor
together to ensure all internal parts stay in perfect
alignment. A junction box and a Pt 100 RTD are
included. The RTD slips easily into one of the sensor
contact rings. There is no need to install a separate
thermowell, and temperature measurements are
made at the same point as the conductivity measurements.
The sensor is not sensitive to flow rate or direction.
It does not obstruct the process flow. The sensor is
rugged and constructed from chemically resistant
materials. All these features make the sensor ideal
for applications in mining and metals processing,
pulp and paper processing, and the chemical processing industry.
The 242 Flow Through Conductivity Sensor is compatible with instrument instumentsL 54eC, 1055,
3081T, 4081T, 5081-T, and Xmt-T.
1
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
1.2 SPECIFICATIONS
The Model 242 Flow Through Sensor comprises a toroid
housing constructed from 316 stainless steel and polyethyleneterephthalate, process connection flanges of 316
stainless steel, two metal contact rings (available in choice
of three materials), an insulating liner (choice of three
materials), O-rings (choice of three materials), a Pt 100
RTD, and a sensor-mounted junction box. Only the liner,
contact rings, and O-rings are wetted by the process. The
Pt 100 RTD is designed for insertion into one pre-drilled
contact ring. The NEMA 7D junction box is constructed of
heavy duty epoxy-painted cast aluminum. The conductivity
range is user-selectable with the tapped toroid windings.
In-line calibration can be performed with resistors connected to an integral wire around the toroids that is terminated
in the junction box.
Pt 100 RTD
Flange
Contact Ring
Liner
O-ring (not visible)
Liners are available in Teflon, glass-filled Polyetheretherketone (PEEK), and alumina. These materials provide
excellent chemical resistance. PEEK is recommended for high pressure or high temperature applications.
Teflon is recommended when the process solution contains hydrofluoric acid or other strong oxidizing agents.
Alumina is recommended if the process solution is abrasive, such as in alumina/caustic ratio applications.
Installation Type
Flow Through
Conductivity Range
100 μS/cm to 2 S/cm
Process Connections
150# ANSI, 300# ANSI, PN16 DIN 2501 compatible flanges
Maximum Temperature
Depends on configuration. For plastic-lined sensors, see charts on facing page.
For alumina-lined sensors, see charts on page 4.
Maximum Pressure
Depends on configuration. For plastic-lined sensors, see charts on facing page.
For alumina-lined sensors, see charts on page 4.
Wetted Materials: Liner
Contact Rings
O-rings
Teflon® (PTFE), glass-filled PEEK, or alumina
316 SST, Carpenter 20Cb-3® SST, or Hastelloy® C-276
EPDM, Viton® (FKM), or Chemraz® (FFKM)
Shipping Weight
1” to 2”: 22 lbs. (10kg)
3” to 4”: 86 lbs. (39 kg)
Teflon is a registered trademark of E.I. du Pont de Nemours & Co.
Viton is a registered trademark of Du Pont Dow Elastomers.
Carpenter 20Cb-3 is a registered trademark of Carpenter Technologies.
Hastelloy is a registered trademark of Haynes International.
Chemraz is a registered trademark of Greene, Tweed, & Co.
2
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
m
ea
st
ste
am
FIGURE 1-1. Pressure - Temperature Specifications for 1”, 1.5”, and 2” (25, 40, and 50 mm) Sensors:
Models 242-02, 242-03, and 242-04
FIGURE 1-2. Pressure - Temperature Specifications for 3” and 4” (80 and 100 mm) Sensors:
Models 242-06 and 242-08
3
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
FIGURE 1-3. Pressure - Temperature Specifications for 1” and 2” Sensors: Alumina Liner
FIGURE 1-4. Pressure - Temperature Specifications for 3” and 4” Sensors: Alumina Liner
4
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
1.3 ORDERING INFORMATION
The 242 Flow-Through Sensor is configurable to meet the needs of many applications and installations (both
ANSI and DIN). After specifying line size and flange type, the customer selects the wetted materials most compatible with the process stream. A NEMA 7D junction box and Pt 100 RTD are also included. Compatible instruments
include Rosemount Analytical Models 54eC, 1055, 3081T, 4081T, 5081-T, and Xmt-T.
The extension cable required for wiring from the junction box to the instrument must be ordered separately. The
customer supplies the gaskets, mating flanges, and flange bolts.
242
FLOW THROUGH TOROIDAL CONDUCTIVITY SENSOR
CODE
02
03
04
06
08
LINE SIZE (Required Selection)
1”
DN 25
1-1/2”
DN 40
2”
DN 50
3”
DN 80
(no ATEX approval with 5081T)
4”
DN 100
(no ATEX approval with 5081T)
CODE
10
11
14
PROCESS CONNECTION (Required Selection)
150# ANSI Flange (Line sizes 1", 1-1/2", 2”, 3”, 4”)
300# ANSI Flange (Line sizes 1", 1-1/2", 2”, 3”, 4”)
PN 16 Metric Flange (Line sizes DN 25, 40, 50, 80, 100)
CODE
SS
H4
H8
C4
C8
CONTACT RING MATERIAL (Required Selection)
316 Stainless Steel
Hastelloy C-276 (Line Sizes 1", 1-1/2", 2”, 25mm, 40mm, 50mm)
Hastelloy C-276 (Line Sizes 3", 4", 80mm, 100mm)
Carpenter 20-Cb3 (Line Sizes 1", 1-1/2", 2”, 25mm, 40mm, 50mm)
Carpenter 20-Cb3 (Line Sizes 3", 4", 80mm, 100mm)
CODE
TE
G4
G8
A4
A8
LINER MATERIAL (Required Selection)
PTFE (Teflon®)
PEEK, 30% Glass-Filled (Line Sizes 1", 1-1/2", 2”, 25mm, 40mm, 50mm)
PEEK, 30% Glass-Filled (Line Sizes 3", 4", 80mm, 100mm)
Alumina (Line sizes 1”, 2”, 25 mm, 50 mm); available only with option F4
Alumina (Line sizes 3”, 4”, 80 mm, 100 mm); available only with option F8
CODE
EP
VT
F4
F8
PROCESS O-RING MATERIAL (Required Selection)
Ethylene Propylene Rubber
Fluorocarbon Rubber (Viton®)
High Temp. Perfluoroelastomer (Chemraz®) (Line Sizes 1", 1-1/2", 2”, 25mm, 40mm, 50mm)
High Temp. Perfluoroelastomer (Chemraz®) (Line Sizes 3", 4", 80mm, 100mm)
242
-0611SSG8VT
EXAMPLE
5
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
ACCESSORIES
PART NUMBER
23909-00
KIT PN
Extension cable, Pre-prepped, for connection to Instrument Models 54eC, 1055, 3081T,
4081T, 5081-T, and Xmt-T (Specify length)
DESCRIPTION
FOR SENSOR MODELS
24005-00
Kit, Liner, 1” DN 25, Teflon PTFE
242-02[ ]TE[ ]
24005-01
Kit, Liner, 1” DN 25, glass-filled PEEK
242-02[ ]G4[ ]
24005-02
Kit, Liner, 1” DN 25, Alumina
242-02[ ]A4[ ]
24006-00
Kit, Liner, 1-1/2” DN 40, Teflon PTFE
242-03[ ]TE[ ]
24006-01
Kit, Liner, 1-1/2” DN 40, glass-filled PEEK
242-03[ ]G4[ ]
24007-00
Kit, Liner, 2” DN 50, Teflon PTFE
242-04[ ]TE[ ]
24007-01
Kit, Liner, 2” DN 50, glass-filled PEEK
242-04[ ]G4[ ]
24007-02
Kit, Liner, 2” DN 50, Alumina
242-04[ ]A4[ ]
24008-00
Kit, Liner, 3” DN 80, Teflon PTFE
242-06[ ]TE[ ]
24008-01
Kit, Liner, 3” DN 80, glass-filled PEEK
242-06[ ]G8[ ]
24008-02
Kit, Liner, 3” DN 80, Alumina
242-06[ ]A8[ ]
24009-00
Kit, Liner, 4” DN 100, Teflon PTFE
242-08[ ]TE[ ]
24009-01
Kit, Liner, 4” DN 100, glass-filled PEEK
242-08[ ]G8[ ]
24009-02
Kit, Liner, 4” DN 100, Alumina
242-08[ ]A8[ ]
KIT PN
6
DESCRIPTION
DESCRIPTION
FOR SENSOR MODELS
24010-00
Kit, O-Ring, 1” DN 25, EPDM
242-02[ ]EP[ ]
24010-01
Kit, O-Ring, 1” DN 25, Viton
242-02[ ]VT[ ]
24010-02
Kit, O-Ring, 1” DN 25, Chemraz
242-02[ ]F4[ ]
24010-03
Kit, O-Ring, 1” DN 25, Chemraz for use with Alumina liner
242-02[ ]A4-F4
24011-00
Kit, O-Ring, 1-1/2” DN 40, EPDM
242-03[ ]EP[ ]
24011-01
Kit, O-Ring, 1-1/2” DN 40, Viton
242-03[ ]VT[ ]
24011-02
Kit, O-Ring, 1-1/2” DN 40, Chemraz
242-03[ ]F4[ ]
24012-00
Kit, O-Ring, 2” DN 50, EPDM
242-04[ ]EP[ ]
24012-01
Kit, O-Ring, 2” DN 50, Viton
242-04[ ]VT[ ]
24012-02
Kit, O-Ring, 2” DN 50, Chemraz
242-04[ ]F4[ ]
24012-03
Kit, O-Ring, 2” DN 50, Chemraz for use with Alumina liner
242-04[ ]A4-F4
24013-00
Kit, O-Ring, 3” DN 80, EPDM
242-06[ ]EP[ ]
24013-01
Kit, O-Ring, 3” DN 80, Viton
242-06[ ]VT[ ]
24013-02
Kit, O-Ring, 3” DN 80, Chemraz
242-06[ ]F8[ ]
24013-03
Kit, O-Ring, 3” DN 80, Chemraz for use with Alumina liner
242-06[ ]A8-F8
24014-00
Kit, O-Ring, 4” DN 100, EPDM
242-08[ ]EP[ ]
24014-01
Kit, O-Ring, 4” DN 100, Viton
242-08[ ]VT[ ]
24014-02
Kit, O-Ring, 4” DN 100, Chemraz
242-08[ ]F8[ ]
24014-03
Kit, O-Ring, 4” DN 100, Chemraz for use with Alumina liner
242-08[ ]A8-F8
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
1.4 INSTALLATION
In the instructions below, the Junction Box is installed
after the sensor is bolted into the process line. If appropriate for the site and final mounting configuration, the
Junction Box can be installed prior to bolting the sensor
into the process line.
CAUTION
The liner of the Model 242 sensor can be damaged if mishandled. Do NOT place any object through the liner for
the purpose of lifting the Model 242 sensor.
CAUTION
Support structures should be installed as appropriate on
or around process pipes and sensor location to sufficiently support the weight of the sensor during installation and
minimize strain on adjacent process pipes during the
operational life of the sensor.
Installation of the Model 242 Flow Through Sensor is similar to installation of a section of pipe. Consequently, be
prepared to use tools, supplies, equipment, and techniques similar to those used to install process pipes. Use
common piping practices to minimize torque and bending
loads on process connections. Observe all applicable
safety standards. Dimensional information is shown in
Figure 1-5 below. Refer to Figures 1-6 to 1-8 for assembly
and installation diagrams.
NOTES
1. Allow at least four pipe diameters of straight pipe run
on either side of the sensor.
2. Install the sensor so that it is filled with process liquid
at all times when measurements are being made.
Avoid downward flow as such a configuration might
leave the sensor partially empty.
3. Use a sling and hoist to lift and position the sensor.
INCH
MILLIMETER
FIGURE 1-5. DIMENSIONAL DRAWING
7
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
INSTALLING THE SENSOR IN THE PROCESS LINE
1. Install process flanges in accordance with applicable instructions, standards, and local regulations.
2. Position the sensor between the process mating flanges with flange gaskets inserted between each set of
flanges. Ensure that the locations of the junction box connection and the RTD hole in the contact ring are in
the correct position for easy wiring and use.
3. Align the bolt holes in the sensor and process flanges.
4. Lubricate the bolt threads. Using a torque wrench, bolt the sensor into place. Tighten the bolts in 1/3 increments of the final desired torque. Follow the bolt-tightening sequence and torque suggestions provided in
Figure 1-6.
5. Re-torque the bolts 12 to 24 hours after installation. Make a final check of torque values by moving consecutively from bolt to bolt.
Torque values in the table above are from Garlock Sealing Technologies. Other values might apply
when using different bolt and gasket materials.
Gylon® is a registered Trademark of Garlock Sealing Technologies.
FIGURE 1-6. Installation and Torque Guidelines
8
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
ATTACHING THE JUNCTION BOX
1.
2.
3.
Pull the sensor wires up into the junction box.
Screw the junction box onto the threaded male connection on
the sensor. Use of pipe sealing tape or other compound is at the
discretion of the customer.
Connect the sensor wires to the junction box terminal as indicated in Figure 1-7.
INSTALLING THE Pt100 RTD
1.
2.
3.
4.
5.
Use of the included Pt100 RTD is recommended. Use of a customer-supplied Pt100 or Pt1000 TC mounted in a separate thermowell is also acceptable. The accuracy specifications provided
by Rosemount Analytical apply only to situations wherein the
Pt100 RTD supplied with the sensor is used.
Refer to Figure 1-8. Screw the threaded nipple onto the conduit
connector of the junction box. Screw the tee onto the nipple, and
screw the RTD cable connector onto the tee.
Attach the bracket to the shaft of the RTD using the #10 washer
and small screw enclosed in the RTD kit. The purpose of the *For optimal performance below 10,000 µS/cm, connect
bracket is to retain the RTD in the contact ring after installation. green wire from extension cable to terminal indicated by *
Slide the Pt100 RTD into the pre-drilled hole in the contact ring.
Rotate the bracket to a position beneath the junction box, and
FIGURE 1-7. Sensor to Junction Box Wiring
tighten the set screw.
Thread the RTD wires through cable connector, tee, nipple, and into junction box. Wire the RTD to the junction box terminals as
indicated in Figure 1-7. Install the white jumper wire between terminals 1 and 2.
Items 1-9 are included with the Model 242
sensor. Items 3-9, the white jumper wire,
and Teflon tape are included in the TC kit.
Items 10 and 11 are sold separately as
accessories.
FIGURE 1-8. Sensor/J-box/RTD Assembly
9
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
EXTENSION CABLE HOOK UP
1. Do not run sensor cable in conduit or open trays
with A.C. power wiring. Do not route sensor cable
near heavy electrical equipment.
2. For best sensor/instrument loop performance, use
factory-terminated extension cable (PN 23909-00).
(Using a different cable can introduce noise into
the signal and/or reduce loop accuracy.)
3. One end of extension cable (PN 23909-00) has 8
wires, and the other end has 11 wires. Refer to
Figure 1-9. The end with 8 wires goes into the junction box. The end with 11 wires goes to the instrument. The extension cable enters the junction box
through the open side of the female threaded tee.
Use of conduit, the optional cable connector (PN
9310137), or other strain relief device to protect the
cable is at the discretion of the customer and
should comply with applicable agency guidelines.
NOTE
If starting with unprepped cable (PN 9200276), remove
only as much insulation as is necessary. The instrument end needs 11 leads: four leads from the greenwhite-black-drain bundle, three from each of the two
coaxial cable bundles (the inner conductor, the insulating braid, and the drain wire), and one from the outermost overall braided-copper shield. For the junction
box end, only 8 leads are used: the white coaxial conductor, its braided shield, the green coaxial conductor,
its braided shield, its drain wire, and the green, white,
and black conductors from the green-white-black-drain
bundle. The remaining shields and drain wires are not
used on the junction box end and should be removed - they should NOT be connected.
4. Connect the 8 wires of the extension cable to the
terminal block inside the sensor junction box as
indicated in Figure 1-7. Note: If all process measurements will be less than 10,000 µS/cm, connect
the green wire from the black-green-clear wire bundle of the extension cable to the terminal receiving
the orange sensor wire. See Figure 1-7.
5. Connect the 11 wires of the instrument-end of the
extension cable according to the applicable diagram from Figures 1-10 through 1-15.
1.5 CALIBRATION
After sensor and transmitter/analyzer wiring is completed, calibrate the sensor.
NOTE
Most analyzers require the input of the approximate
sensor cell constant before the analyzer calculates the
true cell constant. The nominal cell constant of the
Model 242 sensor depends on the size of the sensor
and the terminal to which the receive wire of the interconnecting cable is attached. Refer to Table 1-1 for
the appropriate nominal cell constant value.
TABLE 1-1: Nominal Cell Constants for 242 Sensors
Sensor Size
1”, DN 25
1.5”, DN 40
2”, DN 50
3”, DN 80
4”, DN 100
Cell Constant (/cm)*
Black
Orange
20
2.0
9.0
0.90
5.0
0.50
4.0
0.40
2.3
0.23
* The table gives the cell constant when the green receive
wire (from black-green-clear bundle) of the interconnecting cable is attached to either the black wire terminal or
the orange wire terminal in the sensor junction box. See
Figures 1-7 and 2-1.
FIGURE 1-9. Extension Cable
10
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
FIGURE 1-10. Extension Cable to
Model 54eC Wiring
NOTE: If wiring to a single
channel 1055-21 or to a dual
channel 1055-21-xx or 1055xx-31, the toroidal sensor is
wired only to Terminal Blocks
3 and 4. If wiring 2 sensors to
a dual toroidal 1055-21-31, use
TB 3, 4, and 5 as shown.
FIGURE1-11. Extension Cable to Model 1055 Wiring
11
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
SELECT
HI OR
LO
*
* Applies only to 3081T
and 4081T.
FIGURE 1-12. Extension Cable to Models 3081T,
4081T, and 5081T Wiring
FIGURE 1-13. Extension Cable to Model 81T
Wiring
FIGURE 1-14. Extension Cable to Model Xmt Pipe/Wall Mount Enclosure
12
MODEL 242
SECTION 1.0
MODEL 242 SENSOR
FIGURE 1-15. Extension Cable to Model Xmt Panel Mount Enclosure
A. To perform liquid calibration prior to installing the sensor in the process line, first seal one end of the sensor,
and then proceed with the following steps.
1. Stand the sensor on the sealed end.
2. Fill the sensor completely with a standard conductivity solution.
3. Insert the Pt100 RTD into the contact ring.
4. Adjust the analyzer reading so that it matches the conductivity of the standard solution at the solution temperature. Refer to the analyzer/ transmitter instruction manual for complete calibration procedures.
B. Use of the Integral Calibration Loop Wire: This internal wire can be used to facilitate future in-process loop calibration and to perform a quick verification that the loop is functioning properly. Performing this additional (but
optional) step is highly recommended.
1. The sensor must be empty of all fluids, reasonably clean, and preferably completely dry.
2. Attach a variable resistance decade box to the sensor yellow “Cal Loop” wires (in the junction box).
3. Adjust the applied resistance until the instrument reads the same conductivity value that it did during the
liquid calibration process. Record the conductivity, applied resistance value, and temperature for future reference.
4. To recalibrate the loop at a later date, optimal results will be achieved if the sensor is returned to a condition approximating its condition during the initial performance of steps C.1 to C.3 above. If this is not possible, the sensor must at least be empty of process fluids. Reapply the same resistance to the Cal Loop
and adjust the instrument reading.
1.6 MAINTENANCE
The only routine maintenance required during the operational life of the sensor is to ensure that there are no
deposits plugging the sensor or coating the inside of the contact rings. Some customers find it advantageous to
periodically replace process gaskets and/or re-tighten the flange bolts to ensure adequate process seals. Refer to
Figure 1-6 for flange bolting sequence and torque recommendations.
13
MODEL 242
SECTION 2.0
TROUBLESHOOTING
SECTION 2.0
TROUBLESHOOTING
2.1 TROUBLESHOOTING. The simplest method of troubleshooting is to run a resistance test on the inductive
sensing device. It is also recommended to check the
resistance of the RTD and resistance between various
pairs of the sensor wires.
To perform a quick resistance check of the sensor, recall
the data obtained during Part C of the Calibration
Process (Refer to Section 1.5) With the sensor empty of
process fluids (preferably also clean and dry), reapply
the resistance to the sensor yellow Cal Loop wires in the
junction box. The reading should be with ±20% of the
original value.
To check the RTD, measure the resistance across the
RTD wires. See Figure 1-4. The resistance value should
be close to the value shown in Table 2-1.
Refer to Figure 2-1 for a circuit diagram of the sensor to
use as an aid when performing the resistance checks.
Use Table 2-2 to determine the resistance values that
should be found across various pairs of sensor wires.
TABLE 2-1 Resistance Values for Pt100 RTD
Temperature
(°C/°F)
18 / 64.4
106.9
19 / 66.2
107.3
20 / 68.0
107.7
21 / 69.8
108.1
22 / 71.6
108.4
23 / 73.4
108.9
24 / 75.2
109.2
25 / 77.0
109.6
26 / 78.8
110.0
27 / 80.6
110.4
C = Celsius / F = Fahrenheit
TABLE 2-2 Sensor Wire Resistance Values
Connection
(Wire colors are for sensor wires unless indicated)
GREEN to ORANGE
GREEN to BLACK
GREEN to GROUND screw in J-box (GRAY wire)
GREEN to WHITE
GREEN to YELLOW
WHITE to GRAY
WHITE to GROUND screw in J-box (GRAY wire)
WHITE to YELLOW
WHITE to RED
YELLOW to YELLOW
YELLOW to GROUND screw in J-box (GRAY wire)
14
Resistance
(Ohms)
Resistance
< 1 Ohm
1 to 5 Ohms
> 20 MegOhms
> 20 MegOhms
> 20 MegOhms
< 1 Ohm
> 20 MegOhms
> 20 MegOhms
> 20 MegOhms
< 1 Ohm
> 20 MegOhms
MODEL 242
SECTION 2.0
MODEL 242 SENSOR
*The green wire from the extension cable’s black-green-clear bundle might be connected opposite the
sensor’s orange wire, as indicated by * to utilize the sensor’s alternative cell constant.
FIGURE 2-1. Sensor Circuit for Troubleshooting
15
MODEL 242
SECTION 3.0
REPLACEMENT PARTS
SECTION 3.0
REPLACEMENT PARTS
3.1 GENERAL
NOTE REGARDING O-RINGS
When replacement parts are required, ensure that
qualified people install the parts specified by
Rosemount. Replacement of original components with
those constructed from alternative materials might
change the temperature, pressure, and/or performance
specifications from those of the original configuration
and will void any CSA, FM, and BASEEFA/CENELEC
agency approvals that were applicable to the original
device. Table 3-1 lists the replacement parts kits for the
Model 242 Sensor. An instruction manual is included
with each kit.
There are two pairs of O-rings inside the sensor:
process O-rings (item 6) and secondary or backup
O-rings (item 7). Refer to Figure 3-1 to identify these
items. The two pairs of O-rings are not interchangeable.
Older O-ring replacement kits contained only the pair
of process O-rings. New O-ring replacement kits contain both pairs of O-rings. To distinguish the process
O-ring from the backup O-ring:
For sensors with plastic liners:
CAUTION
1. The process O-ring has a much smaller cross sectional area than the secondary O-ring. The crosssection diameter of the process O-ring is 0.07 in.
The cross-section diameter of the secondary O-ring
is 0.139 in.
Before removing the sensor from the process piping,
ensure that the process has been shut down and liquid drained from the sensor line. For personal safety,
2. The diameter of the process O-ring is less than
the secondary O-ring. The size difference is
immediately obvious when the two O-rings are
allowed to dangle from a pencil.
3.2 REMOVE THE SENSOR
For sensors with alumina liners:
1. The process and secondary O-rings have the
same cross sectional area. (0.139 in).
The RTD can be removed either before or after the
sensor is removed from the process. The junction box
should be left attached to the toroid subassembly. After
ensuring that it is safe to remove the sensor from the
process line, loosen the flange bolts in 1/3 increments
in the same order in which they were tightened as
shown in Figure1-4. Remove the bolts and sensor.
3.3 DISASSEMBLE THE SENSOR
Using the tool indicated in Table 3-2, remove the
Sensor Bolts (Item 2). Note that these bolts were
installed using a thread-locking adhesive. Any use of
heat to loosen the adhesive should not exceed the temperature ratings of the sensor. Figure 3-1 is an exploded view of the all the parts of the Model 242 sensor.
16
2. The diameter of the process O-ring is less than
the secondary O-ring. The size difference is
immediately obvious when the two O-rings are
allowed to dangle from a pencil.
MODEL 242
SECTION 3.0
MODEL 242 SENSOR
TABLE 3-1. Replacement Parts and Accessories
PART NUMBER
23909-00
KIT PN
DESCRIPTION
Extension cable, Pre-prepped, for connection to Instrument Models 54eC, 1055, 3081T,
4081T, 5081-T, and Xmt-T (Specify length)
DESCRIPTION
FOR SENSOR MODELS
24005-00
Kit, Liner, 1” DN 25, Teflon PTFE
242-02[ ]TE[ ]
24005-01
Kit, Liner, 1” DN 25, glass-filled PEEK
242-02[ ]G4[ ]
24005-02
Kit, Liner, 1” DN 25, Alumina
242-02[ ]A4[ ]
24006-00
Kit, Liner, 1-1/2” DN 40, Teflon PTFE
242-03[ ]TE[ ]
24006-01
Kit, Liner, 1-1/2” DN 40, glass-filled PEEK
242-03[ ]G4[ ]
24007-00
Kit, Liner, 2” DN 50, Teflon PTFE
242-04[ ]TE[ ]
24007-01
Kit, Liner, 2” DN 50, glass-filled PEEK
242-04[ ]G4[ ]
24007-02
Kit, Liner, 2” DN 50, Alumina
242-04[ ]A4[ ]
24008-00
Kit, Liner, 3” DN 80, Teflon PTFE
242-06[ ]TE[ ]
24008-01
Kit, Liner, 3” DN 80, glass-filled PEEK
242-06[ ]G8[ ]
24008-02
Kit, Liner, 3” DN 80, Alumina
242-06[ ]A8[ ]
24009-00
Kit, Liner, 4” DN 100, Teflon PTFE
242-08[ ]TE[ ]
24009-01
Kit, Liner, 4” DN 100, glass-filled PEEK
242-08[ ]G8[ ]
24009-02
Kit, Liner, 4” DN 100, Alumina
242-08[ ]A8[ ]
KIT PN
DESCRIPTION
FOR SENSOR MODELS
24010-00
Kit, O-Ring, 1” DN 25, EPDM
242-02[ ]EP[ ]
24010-01
Kit, O-Ring, 1” DN 25, Viton
242-02[ ]VT[ ]
24010-02
Kit, O-Ring, 1” DN 25, Chemraz
242-02[ ]F4[ ]
24010-03
Kit, O-Ring, 1” DN 25, Chemraz for use with Alumina liner
242-02[ ]A4-F4
24011-00
Kit, O-Ring, 1-1/2” DN 40, EPDM
242-03[ ]EP[ ]
24011-01
Kit, O-Ring, 1-1/2” DN 40, Viton
242-03[ ]VT[ ]
24011-02
Kit, O-Ring, 1-1/2” DN 40, Chemraz
242-03[ ]F4[ ]
24012-00
Kit, O-Ring, 2” DN 50, EPDM
242-04[ ]EP[ ]
24012-01
Kit, O-Ring, 2” DN 50, Viton
242-04[ ]VT[ ]
24012-02
Kit, O-Ring, 2” DN 50, Chemraz
242-04[ ]F4[ ]
24012-03
Kit, O-Ring, 2” DN 50, Chemraz for use with Alumina liner
242-04[ ]A4-F4
24013-00
Kit, O-Ring, 3” DN 80, EPDM
242-06[ ]EP[ ]
24013-01
Kit, O-Ring, 3” DN 80, Viton
242-06[ ]VT[ ]
24013-02
Kit, O-Ring, 3” DN 80, Chemraz
242-06[ ]F8[ ]
24013-03
Kit, O-Ring, 3” DN 80, Chemraz for use with Alumina liner
242-06[ ]A8-F8
24014-00
Kit, O-Ring, 4” DN 100, EPDM
242-08[ ]EP[ ]
24014-01
Kit, O-Ring, 4” DN 100, Viton
242-08[ ]VT[ ]
24014-02
Kit, O-Ring, 4” DN 100, Chemraz
242-08[ ]F8[ ]
24014-03
Kit, O-Ring, 4” DN 100, Chemraz for use with Alumina liner
242-08[ ]A8-F8
17
MODEL 242
SECTION 3.0
MODEL 242 SENSOR
Table 3-2. Sensor Bolt Removal & Installation Guide
Sensor Type
1", 150# flange
1", 300# flange
DN 25, PN 16
1.5", 150# flange
1.5", 300# flange
DN 40, PN 16
2", 150# flange
2", 300 # flange
DN 50, PN 16
3", 150# flange
3", 300 # flange
DN 80, PN 16
4", 150# flange
4", 300 # flange
DN 100, PN 16
Model
242-02-10
242-02-11
242-02-14
242-03-10
242-03-11
242-03-14
242-04-10
242-04-11
242-04-14
242-06-10
242-06-11
242-06-14
242-08-10
242-08-11
242-08-14
Wrench
5/16" Hex Allen
5/16" Hex Allen
5/16" Hex Allen
5/16" Hex Allen
3/8" Hex Allen
5/16" Hex Allen
5/16" Hex Allen
3/8" Hex Allen
3/8" Hex Allen
3/4" Socket
3/4" Socket
3/4" Socket
3/4" Socket
3/4" Socket
3/4" Socket
Torque (ft-lbs)
18 ft-lbs
18 ft-lbs
18 ft-lbs
18 ft-lbs
42 ft-lbs
18 ft-lbs
18 ft-lbs
42 ft-lbs
42 ft-lbs
42 ft-lbs
42 ft-lbs
42 ft-lbs
42 ft-lbs
42 ft-lbs
42 ft-lbs
Torque (N-m)
24 Nm
24 Nm
24 Nm
24 Nm
57 Nm
24 Nm
24 Nm
57 Nm
57 Nm
57 Nm
57 Nm
57 Nm
57 Nm
57 Nm
57 Nm
* REPLACEMENT PARTS AVAILABLE.
FIGURE 3-1. Exploded View of Model 242
18
MODEL 242
SECTION 3.0
MODEL 242 SENSOR
3.4 RE-ASSEMBLE THE SENSOR
It is recommended that a press be used during the assembly process to ensure tight seals between components.
Locate the part to be changed on the diagram and substitute the new part from the kit. Complete disassembly
of the sensor might not be necessary and in that case is not recommended. If new O-rings are to be used, they
should be lubricated prior to installation.
Assuming the sensor has been completely disassembled, begin by placing both Contact Rings (Item 1) side by
side on their flat faces. Set a Flange (Item 4) on each Contact Ring (Item 1). Install a Retainer Ring (Item 5)
onto the step on the outside of each Contact Ring (Item 1). Insert a lubricated Process O-ring (Item 6) in the
lower groove (closest to the flat face) located inside each Contact Ring (Item 1). Place a lubricated Secondary
Back-up O-ring (Item 7) on the upper step inside each Contact Ring (Item 1). The flange-assembly should look
like Figure 3-2.
Place one of these flange-assemblies onto a press and install the Liner (Item 8). It is advisable to place a flat
surface between the press and the liner to protect the liner from damage during pressing. Be careful to ensure
O-rings do not slip or twist. Slip the Toroid Housing (Item 9) over the Liner (Item 8) to nest inside the flangeassembly. The pins on the toroid housing must seat into the small holes in the flanges. Place the second flangeassembly on top of the first flange assembly with the Liner (Item 8) and Toroid Housing (Item 9) in between.
Check for pin alignment, pinched O-rings, and straight, even insertion. The Sensor Bolts (Item 2) can be temporarily preplaced in the bolt holes to align the two Flanges. Press the entire sensor together to begin assembly of all the components. Install and tighten the Sensor Bolts and Nuts (Items 2 and 3), using thread-locking
compound. Using the torquing sequence shown in Figure 1-6, tighten the bolts in 1/3 increments of their final
torque values as listed in Table 3-2.
Back-up O-ring
Contact Ring
Process O-ring
Retainer Ring
Flange
FIGURE 3-2. Flange Assembly: Contact Ring, Flange, and O-rings.
3.5 RE-INSTALL THE SENSOR INTO THE PROCESS
Please see Section 1.4 of this manual for instructions.
19
MODEL 242
SECTION 4.0
RETURN OF MATERIALS
SECTION 4.0
RETURN OF MATERIALS
4.1 GENERAL. To expedite the repair and return of
instruments, proper communication between the customer and the factory is important. A return material
authorization number is required. Call (949) 7578500. The “Return of Materials Request” form is provided for you to copy and use in case the situation
arises. The accuracy and completeness of this form
will affect the processing time of your materials.
5.
Rosemount Analytical Inc.
2400 Barranca Parkway
Irvine, CA 92606
Attn: Factory Repair
Mark the package: Returned for
Repair RMA No. __________
4.2 WARRANTY REPAIR. The following is the procedure for returning products still under warranty.
1.
Contact the factory for authorization.
2.
Complete a copy of the “Return of Materials
Request” form as completely and accurately as
possible.
3.
To verify warranty, supply the factory sales order
number or the original purchase order number. In
the case of individual parts or sub-assemblies, the
serial number on the mother unit must be supplied.
4.
Carefully package the materials and enclose your
“Letter of Transmittal” and the completed copy of
the “Return of Materials Request” form. If possible, pack the materials in the same manner as it
was received.
IMPORTANT
Please see second section of “Return of
Materials Request Form”. Compliance to
the OSHA requirements is mandatory for
the safety of all personnel. MSDS forms
and a certification that the instruments
have been disinfected or detoxified are
required.
20
Send the package prepaid to:
Model No. _________
4.3 NON-WARRANTY REPAIR.
1.
Contact the factory for authorization.
2.
Fill out a copy of the “Return of Materials Request”
form as completely and accurately as possible.
3.
Include a purchase order number and make sure
to include the name and telephone number of the
right individual to be contacted should additional
information be needed.
4.
Do Steps 4 and 5 of Section 4.2.
NOTE
Consult the factory for additional information regarding service or repair.
RETURN OF MATERIALS REQUEST
C
U
S
T
O
M
E
R
N
O
T
I
C
E
T
O
FROM:
•IMPORTANT!
This form must be completed to ensure expedient factory service.
RETURN
BILL TO:
_____________________________
_____________________________
_____________________________
_____________________________
_____________________________
_____________________________
_____________________________
_____________________________
_____________________________
S
E
N
D
E
R
CUSTOMER/USER MUST SUBMIT MATERIAL SAFETY SHEET (MSDS) OR COMPLETE STREAM COMPOSITION, AND/OR
LETTER CERTIFYING THE MATERIALS HAVE BEEN DISINFECTED AND/OR DETOXIFIED WHEN RETURNING ANY PRODUCT, SAMPLE OR MATERIAL THAT HAVE BEEN EXPOSED TO OR USED IN AN ENVIRONMENT OR PROCESS THAT CONTAINS A HAZARDOUS MATERIAL ANY OF THE ABOVE THAT IS SUBMITTED TO ROSEMOUNT ANALYTICAL WITHOUT
THE MSDS WILL BE RETURNED TO SENDER C.O.D. FOR THE SAFETY AND HEALTH OF OUR EMPLOYEES. WE THANK
YOU IN ADVANCE FOR COMPLIANCE TO THIS SUBJECT.
SENSOR OR CIRCUIT BOARD ONLY:
(Please reference where from in MODEL / SER. NO. Column)
1. PART NO.__________________________1. MODEL_________________________________1.
SER. NO. ________________
2. PART NO.__________________________2. MODEL_________________________________2.
SER. NO. ________________
3. PART NO.__________________________3. MODEL_________________________________3.
SER. NO. ________________
4. PART NO.__________________________4. MODEL_________________________________4.
SER. NO. ________________
R
E
A
S
O
N
PLEASE CHECK ONE:
F
O
R
n REPLACEMENT REQUIRED? n YES n NO
R
E
T
U
R
N
n REPAIR AND CALIBRATE
n DEMO EQUIPMENT NO. __________________________
n EVALUATION
n OTHER (EXPLAIN) _______________________________
_________________________________________________
DESCRIPTION OF MALFUNCTION:
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
R
E
P
A
I
R
S
T
A
T
U
S
WARRANTY REPAIR REQUESTED:
n YES-REFERENCE ORIGINAL ROSEMOUNT ANALYTICAL ORDER NO. ________________________________________
CUSTOMER PURCHASE ORDER NO. _________________________________________________
n NO-PROCEED WITH REPAIRS-INVOICE AGAINST P.O. NO. _________________________________________________
n NO-CONTACT WITH ESTIMATE OF REPAIR CHARGES: LETTER n __________________________________________
PHONE n ___________________________________________
NAME ____________________________________________________
PHONE _________________________________________
ADDRESS ___________________________________________________________________________________________________
______________________________________________________________
ZIP _________________________________________
RETURN AUTHORITY FOR CREDIT ADJUSTMENT [Please check appropriate box(s)]
n WRONG PART RECEIVED
n REPLACEMENT RECEIVED
n DUPLICATE SHIPMENT
REFERENCE ROSEMOUNT ANALYTICAL SALES ORDER NO.__________
n RETURN FOR CREDIT
RETURN AUTHORIZED BY: ______________________________________
WARRANTY DEFECT ___________________________________________________________________________________
24-6047
Emerson Process Management
Rosemount Analytical Inc.
2400 Barranca Parkway
Irvine, CA 92606 USA
Tel: (949) 757-8500
Fax: (949) 474-7250
http://www.raihome.com
© Rosemount Analytical Inc. 2003
The right people, the right answers, right now.
Immediate, Reliable Analytical Support
Now there’s a way to quickly get the right answers for your liquid analytical instrumentation questions: the Analytical
Customer Support Center.
Our staff of trained professionals is ready to provide the information you need. If you are placing an order, verifying delivery,
requesting application information, or just want to contact an Emerson Process Management representative, a call to the
Customer Support Center will provide you with the right people, the right answers, right now.
A Worldwide Network of Sales and Service
Emerson Process Management’s field sales offices are your source for more information on the fill line of Rosemount Analytical
products. Field sales personnel will work closely with you to supply technical data and application information.
For more information, please contact your nearest Emerson Process Management sales office.
THE AMERICAS HEADQUARTERS
Emerson Process Management
Rosemount Analytical Inc.
Liquid Center of Excellence
2400 Barranca Parkway
Irvine, CA 92606
Phone: +1.949.757.8500
Toll Free: +1.800.854.8257
Fax: +1.949.474.7250
ASIA-PACIFIC
Emerson Process Management
Asia Pacific Private Ltd.
1 Pandan Crescent
Singapore 0512
Republic of Singapore
Phone: 65.777.8211
Fax: 65.777.0947
GERMANY
Emerson Process Management Process
Gas Analyzer Center of Excellence
GmbH & Co. OHG
Industriestrasse 1
63594 Hasselroth
Germany
T 49.6055.884.0
F 49.6055.884.20
LATIN AMERICA
Emerson Process Management
Rosemount Analytical
10241 West Little York, Suite #200
Houston, TX 77040 USA
T 713.467.6000
F 713.827.3328
MIDDLE EAST AND AFRICA
EUROPE
Emerson Process Management AG
Blegistrasse 21
CH-6341 Baar-Walterswil
Switzerland
T 41.41.768.6111
T 41.41.761.8740
VISIT OUR WEBSITE AT
www.rosemountanalytical.com
Emerson Process Management
EPM Building
P. O. Box 17033
Jebe Ali Free Zone
Dubai, United Arab Emirates
T 971.4.8835235
F 971.4.8835312
WARRANTY
Seller warrants that the firmware will execute the programming instructions provided by Seller, and that the Goods manufactured
or Services provided by Seller will be free from defects in materials or workmanship under normal use and care until the expiration of the applicable warranty period. Goods are warranted for twelve (12) months from the date of initial installation or eighteen
(18) months from the date of shipment by Seller, whichever period expires first. Consumables, such as glass electrodes,
membranes, liquid junctions, electrolyte, o-rings, catalytic beads, etc., and Services are warranted for a period of 90
days from the date of shipment or provision.
Products purchased by Seller from a third party for resale to Buyer ("Resale Products") shall carry only the warranty extended by
the original manufacturer. Buyer agrees that Seller has no liability for Resale Products beyond making a reasonable commercial
effort to arrange for procurement and shipping of the Resale Products.
If Buyer discovers any warranty defects and notifies Seller thereof in writing during the applicable warranty period, Seller shall, at
its option, promptly correct any errors that are found by Seller in the firmware or Services, or repair or replace F.O.B. point of manufacture that portion of the Goods or firmware found by Seller to be defective, or refund the purchase price of the defective portion of the Goods/Services.
All replacements or repairs necessitated by inadequate maintenance, normal wear and usage, unsuitable power sources, unsuitable environmental conditions, accident, misuse, improper installation, modification, repair, storage or handling, or any other
cause not the fault of Seller are not covered by this limited warranty, and shall be at Buyer's expense. Seller shall not be obligated to pay any costs or charges incurred by Buyer or any other party except as may be agreed upon in writing in advance by an
authorized Seller representative. All costs of dismantling, reinstallation and freight and the time and expenses of Seller's personnel for site travel and diagnosis under this warranty clause shall be borne by Buyer unless accepted in writing by Seller.
Goods repaired and parts replaced during the warranty period shall be in warranty for the remainder of the original warranty period or ninety (90) days, whichever is longer. This limited warranty is the only warranty made by Seller and can be amended only
in a writing signed by an authorized representative of Seller. Except as otherwise expressly provided in the Agreement, THERE
ARE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE GOODS OR SERVICES.
RETURN OF MATERIAL
Material returned for repair, whether in or out of warranty, should be shipped prepaid to:
Emerson Process Management
Rosemount Analytical
2400 Barranca Parkway
Irvine, CA 92606
The shipping container should be marked:
Return for Repair
Model _______________________________
The returned material should be accompanied by a letter of transmittal which should include the following information (make a
copy of the "Return of Materials Request" found on the last page of the Manual and provide the following thereon):
1.
2.
3.
4.
5.
Location type of service, and length of time of service of the device.
Description of the faulty operation of the device and the circumstances of the failure.
Name and telephone number of the person to contact if there are questions about the returned material.
Statement as to whether warranty or non-warranty service is requested.
Complete shipping instructions for return of the material.
Adherence to these procedures will expedite handling of the returned material and will prevent unnecessary additional charges
for inspection and testing to determine the problem with the device.
If the material is returned for out-of-warranty repairs, a purchase order for repairs should be enclosed.
The right people,
the right answers,
right now.
ON-LINE ORDERING NOW AVAILABLE ON OUR WEB SITE
http://www.raihome.com
Specifications subject to change without notice.
8
Credit Cards for U.S. Purchases Only.
Emerson Process Management
2400 Barranca Parkway
Irvine, CA 92606 USA
Tel: (949) 757-8500
Fax: (949) 474-7250
http://www.rosemountanalytical.com
© Rosemount Analytical Inc. 2012