Det-Tronics Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) and Sensor Module (GTS) Instruction Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
Electrochemical Gas Detector
GT3000 Series
Includes Transmitter (GTX)
and Sensor Module (GTS)
11.1
Rev: 8/15
95-8616
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
GTS Sensor Module . . . . . . . . . . . . . . . . . . . . . .
GTX Transmitter . . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Clock . . . . . . . . . . . . . . . . . . . . . . . . .
History/Event Logs . . . . . . . . . . . . . . . . . . . . . . .
HART Communication . . . . . . . . . . . . . . . . . . . .
Magnetic Switch . . . . . . . . . . . . . . . . . . . . . . . . .
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
2
2
2
3
3
3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Important Safety Notes . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Identification of Vapor(s) to be Detected . . . . . . .
Identification of Detector Mounting Locations . . .
Device Mounting Orientation . . . . . . . . . . . . . . . .
Detector Installation . . . . . . . . . . . . . . . . . . . . . .
Sensor Termination Box . . . . . . . . . . . . . . . . . . .
6
6
6
7
7
calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
GT3000 Calibration . . . . . . . . . . . . . . . . . . . . . . 12
Calibration Procedure . . . . . . . . . . . . . . . . . . . . 13
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Routine Inspection . . . . . . . . . . . . . . . . . . . . . . 14
Sensor Module Replacement . . . . . . . . . . . . . . 14
Device Repair and Return . . . . . . . . . . . . . . . 15
Ordering Information . . . . . . . . . . . . . . . . . . 15
GTS Gas Sensors . . . . . . . . . . . . . . . . . . . . . . . 15
Calibration Kits for Gas Sensors . . . . . . . . . . . . 15
Parts & Accessories . . . . . . . . . . . . . . . . . . . . . 15
APPENDIX A — FM APPROVAL DESCRIPTION . . . . 18
APPENDIX B — CSA CERTIFICATION DESCRIPTION . 20
APPENDIX C — ATEX APPROVAL DESCRIPTION . . 21
wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power Supply Requirements . . . . . . . . . . . . . . . .
Wiring Cable Requirements . . . . . . . . . . . . . . . .
Intrinsic Safety Barriers . . . . . . . . . . . . . . . . . . . .
Guidelines for Intrinsic Safety Wiring . . . . . . . . .
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . .
7
7
8
8
8
APPENDIX D — IECEx APPROVAL DESCRIPTION . 22
APPENDIX E — OTHER APPROVALS . . . . . . . . . . . . . 23
Appendix F — Declaration of Conformity . 24
Appendix G — sensor comparison /
cross sensitivity . . . . . . . . . . . . 25
Appendix H — HART COMMUNICATION . . . . . . . . . 27
Appendix I — CONTROL DRAWINGs . . . . . . . . . . . 29
INSTRUCTIONS
Electrochemical Gas Detector
GT3000 Series
Includes Transmitter (GTX)
and Sensor Module (GTS)
Sensor
Module
(GTS)
Transmitter
(GTX)
Important
Be sure to read and understand the entire
instruction manual before installing or operating
the gas detection system. This product is
intended to provide early warning of the presence
of a toxic or explosive gas mixture, or of oxygen
depletion. Proper device installation, operation,
and maintenance are required to ensure safe
and effective operation. If this equipment is used
in a manner not specified in this manual, safety
protection may be impaired.
Description
The GT3000 Electrochemical Gas Detector is an
intelligent stand-alone industrial gas detector, designed
to provide continuous monitoring of the atmosphere for
hazardous gas leaks or oxygen depletion. It is fully
performance tested and approved by Factory Mutual.
Refer to Appendix F for individual gas specifications.
The GT3000 Gas Detector consists of a replaceable
sensor module (Model GTS) connected to a transmitter
module (Model GTX).
A single transmitter is
compatible with all GTS sensor modules. A variety of
electrochemical sensor models are available in various
concentration ranges.
The GT3000 is a 2-wire device that generates a 4-20
mA output signal with HART communication that is
proportional to the concentration of the target gas.
The GT3000 is compatible with FlexVu® Model UD10 and
UD20 Universal Display Units, as well as other devices
11.1 © Detector Electronics Corporation 2015
Detector (GT3000)
that are able to monitor a linear 4-20 mA dc signal. All
alarm functions are provided by the monitoring device.
The GT3000 is designed and approved as a stand
alone unit for use in hazardous locations. It is suitable
for outdoor applications that require IP66 rating and
uses a hydrophobic filter that is easily replaced without
opening the device or use of tools. The GT3000 is
furnished as either explosion-proof or intrinsically safe.
The GT3000 supports local one-person calibration
with the use of a magnet and on-board LED.
GTS SENSOR Module
The GTS’s electrochemical sensor cell uses capillary
diffusion barrier technology for monitoring gas
concentrations in ambient air.
Live Maintenance
The hot swappable GTS sensor module is intrinsically
safe and allows live maintenance while under power,
without de‑classifying the hazardous area. When the
sensor is removed, the transmitter generates a fault
output. If a new sensor of the same type and range is
installed, the fault self-clears. However, if the type or
range of the new sensor module does not match the
old, the transmitter generates a fault until a successful
calibration or acceptance of the new sensor type is
completed. For additional information regarding Live
Maintenance, refer to “Sensor Module Replacement” in
the Maintenance section of this manual.
Rev: 8/15
95-8616
Automatic Sensor Module Recognition
HISTORY/Event Logs
The transmitter provides automatic gas sensor
recognition, allowing the operator to access the
following information via HART, or a UD10 or UD20
Universal display:
• Date of manufacture of the sensor module
Both the transmitter and sensor are able to store 256
history logs, which are saved in non-volatile memory
and retained through power cycles. A UD10/UD20
Universal Display Unit, a HART communication device,
or AMS software is required to view the history logs.
• Sensor module serial number
Sensor Logging Capability
• Gas type
The sensor module logs the following operating
parameters in non‑volatile memory:
• Measurement range
• Running Hours - The sensor module maintains the
total operating hours, and cannot be reset.
The sensor module is factory programmed for the gas
type and measurement range. When the sensor module
powers up, the transmitter reads and acknowledges
the gas type and measurement range.
• Min/Max Temperature - The sensor module
maintains the minimum and maximum temperatures
with a date and time stamp.
GTX TRANSMITTER
• Calibration - The sensor module logs the calibration
history with a date and time stamp, along with the
success or cause of failure codes. See Table 1. The
zero and span values (AD converter values recorded at
the time of calibration) are also saved. This allows the
logs to follow the sensor module when it is calibrated
separately from the transmitter. (Calibration data is
available via a UD10/UD20, a HART communication
device, or AMS software.)
The transmitter output is a linear 4-20 mA dc signal
with HART communication that directly corresponds to
0-100% full scale.
A 3.8 mA output indicates sensor calibration in progress
(17.3 mA for O2 sensor). The GT3000 comes with one
of two pre-programmed fault output levels: 2.45 mA or
3.5 mA.
The sensor module gets the current time and date
from the transmitter and provides calibration log
information to the transmitter. See Figure 1.
Priority of output signals from highest to lowest is:
1
Calibration
(In progress)
2
Fault
3
Gas Level
Table 1—Calibration Status Codes
Number
0
1
2
3
4
5
6
7
8
9
10
11
Transmitter Wiring
The GTX transmitter is a two-wire loop powered device
that uses a three-wire cable (power, signal, and earth
ground) for connecting to a controller or monitoring
device. The use of shielded cable is required.
Real Time Clock (RTC)
The GTX transmitter has a real time clock with battery
back‑up, that is used for time stamping the event logs.
The time and date are set and read using a UD10/
UD20 Universal Display Unit, a HART communication
device, or AMS software. The time stamp on the logs
will not be correct if the RTC in the transmitter is not set
correctly.
11.1
2
Definition
EMPTY LOG
NOT USED
NOT USED
ZERO CAL
SPAN CAL
ABORT CAL
FAILED CAL
NOT USED
NOT USED
INIT CAL LOG
NOT USED
CLR CAL FAULTS
95-8616
GT3000
Gas Detector
Transmitter
RTC
HART Interface
Event Logs
Transmitter updates
sensor module
time / date
Transmitter reads
calibration logs
from sensor
Sensor Module
Calibration Logs
GREEN LED (ON)
YELLOW LED (OFF)
Figure 1—GT3000 Logging
A2450
Transmitter Logging Capability
Figure 3— Location of LEDs on GT3000 Gas Detector
The transmitter logs the following events with a time
and date stamp:
Magnetic Switch
The GT3000 is furnished with an internal magnetic reed
switch as part of the user interface. The magnetic switch
allows the user to initiate calibration by momentarily
placing a magnet against the housing at the designated
location. See Figure 2.
• Power-up
• Sensor change
• All Faults.
HART Communication
LEDs
The transmitter supports HART communication on the
4‑20 mA loop. This allows for configuration capability
and provides device status information, calibration, and
diagnostics capabilities. The GT3000 is compatible
with HART interface devices such as a HART handheld
communicator, the Det-Tronics UD10 or UD20 Display
Unit, or an AMS system. (See Appendix G for HART
menu structure.)
The GT3000 has one green and one yellow LED
(See Figure 3). The LEDs are used to signal normal,
calibration, and fault conditions. See Table 2.
Note
The GT3000 does not have alarm setpoints and,
therefore, does not have a red LED.
Table 2—LEDs and Analog Output
During Various Operating Conditions
MAGNETIC
SWITCH
Green LED
Yellow LED
Analog
4-20 Signal
Output
Warm-up*
Single Flash
On
3.5***
Normal
Operation
Steady On
Off
4-20
Fault
Condition
Off
On
3.5***
Calibration
Off
See Table 5
3.8**
No Power
Off
Off
0
*Warm-up time can last up to 150 seconds.
**O2 sensor generates 17.3 mA during calibration.
B2443
***2.45 for TYPE OUTPUT "29", reference GTX Model Matrix .
Figure 2—Location of Magnetic Switch on GT3000 Detector
11.1
Function
3
95-8616
specifications
6.2
(15.8)
5.6
(14.3)
sensor and transmitter
Available Sensors—
Refer to Appendix F.
2.5
(6.4)
Cross Sensitivity—
See Appendix F for Cross Sensitivity information.
B2397
calibration—
Sensors are calibrated at the factory. Gas type and
range are read by the transmitter. Field calibration is
initiated at the detector, at the UD10/UD20 Universal
Display Unit, or by some other HART interface device.
Figure 4—Dimensions of GT3000 Gas Detector in Inches (CM)
Pressure range—
Atmospheric ±10%.
Ingress Protection—
IP66.
operating voltage—
24 volts dc nominal. (12 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
If using the HART function, the installation must comply
with the HART power standard.
electro-magnetic compatibility—
EMC Directive 2004/108/EC
EN55011 (Emissions)
EN50270 (Immunity).
power consumption—
0.8 watt maximum @ 30 Vdc.
Thread options—
3/4" NPT or M25.
current output—
• 4-20 mA (Normal operating mode).
ENCLOSURE MATERIAL—
GTX Transmitter:
316 Stainless Steel
GTS Sensor Module: PPA (30% carbon filled).
• 3.8 mA indicates calibrate mode.
• 3.5 mA or less indicates a fault condition (2.45 mA
option available).
Dimensions—
See Figure 4.
maximum loop resistance—
300 ohms at 18 Vdc, 600 ohms at 24 Vdc.
WARRANTY—(For the GTX and GTS)
12 months from date of installation or 18 months from
date of shipment, whichever occurs first.
Wiring—
The transmitter has flying leads, 20” long, 600V insulation.
Colors:
Red = V+
Black = V–
Green = earth ground
Gauge:
22 AWG (red and black)
16 AWG (green).
CERTIFICATIONs—
®
Warm-up—
Warm-up time can last up to 150 seconds.
For complete approval details, refer to the appropriate
Appendix:
operating temperature—
See Appendix F.
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - Other Approvals
Storage Temperature—
Transmitter: –55°C to +75°C (–67°F to +167°F)
Sensor:
0°C to +20°C (+32°F to +68°F).
Ideal: +4°C to +10°C (+39°F to +50°F).
Humidity range—
15 to 90% RH.
11.1
4
95-8616
Important Safety Notes
Liabilities
The manufacturer’s warranty for this product is
void, and all liability for proper function of the
detector is irrevocably transferred to the owner or
operator in the event that the device is serviced or
repaired by personnel not employed or authorized
by Detector Electronics Corporation, or if the
device is used in a manner not conforming to its
intended use.
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local codes. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be
done by a properly trained person.
Caution
Observe precautions for handling electrostatic
sensitive devices.
CAUTION
This product has been tested and approved
for use in hazardous areas. However, it must
be properly installed and used only under the
conditions specified within this manual and
the specific approval certificates. Any device
modification, improper installation, or use in a
faulty or incomplete configuration will render
warranty and product certifications invalid.
NOTE
The sensor housing is made of Polyphthalamide
(PPA), 30% carbon filled (Material Manufacturer
RTP). Questions regarding chemical resistance
should be addressed to:
www.det-tronics.com
US toll free 800-468-3244 or 952-941-5665
CAUTION
The GT3000 contains no field repairable
components. User performed service is limited
to replacement of the gas sensor module.
CAUTION
Hazardous location temperature limits exceed
the product operational temperature limits. If the
sensor is exposed to temperatures beyond the
operational temperature limits listed in Appendix
F, then the sensor module (GTS) should be
replaced or a response test, as described in
the GT3000 Safety Manual (95-8685), shall be
performed.
11.1
5
95-8616
Installation
The most effective number and placement of detectors
varies depending on the conditions on site. The
individual designing the installation must often rely
on experience and common sense to determine the
detector quantity and best locations to adequately
protect the area. Note that it is typically advantageous
to locate detectors where they are accessible for
maintenance.
Locations near excessive heat or
vibration sources should be avoided if possible.
The gas detector can be installed either in a stand‑alone
configuration as a loop powered device, or it can be
connected to a UD10/UD20 Universal Display Unit.
note
The gas detector housing must be electrically
connected to earth ground. A dedicated earth
ground wire is provided on the transmitter for
connection to earth ground or to a grounded
housing.
Final suitability of possible gas detector locations
should be verified by a site survey. If any questions
arise regarding installation, please contact the factory.
The detector must always be installed per local
installation code.
Device Mounting Orientation
Before installing the gas detector, define the following
application details:
The gas detector must be mounted in a vertical position
only, with the sensor pointing down (See Figure 5).
Identification of vapor(s) to be detected
Important
The sensor should be oriented with the LEDs
facing forward so they are easily visible to
personnel within the area. To ensure correct
orientation (the LEDs are not visible when power
is off), position the GND lug on the left hand side
and the calibration notch to the front. Note that the
LEDs are located directly above the calibration
notch.
It is necessary to always identify the vapor(s) of interest
at the job site. In addition, the fire hazard properties
of the vapor, such as vapor density, flashpoint, and
vapor pressure should be identified and used to assist
in selecting the optimum detector mounting location
within the area.
Identification of detector mounting
locations
Identification of the most likely leak sources and
leak accumulation areas is typically the first step in
identifying the best detector mounting locations. In
addition, identification of air current/wind patterns
within the protected area is useful in predicting gas leak
dispersion behavior. This information should be used
to identify optimum sensor installation points.
If the vapor of interest is lighter than air, place the sensor
above the potential gas leak. Place the sensor close to
the floor for gases that are heavier than air. Note that air
currents may cause a gas that is slightly heavier than
air to rise under some conditions. Heated gases may
also exhibit the same phenomenon.
GND LUG
GREEN LED
CALIBRATION NOTCH
B2436
Figure 5—Correct Mounting Orientation for the GT3000
11.1
6
95-8616
Detector installation
SENSOR termination box
A Det-Tronics sensor termination box (Model STB)
is required for installing the sensor in a stand alone
configuration, or for installing the GT3000 remotely
from the UD10/UD20 Universal Display Unit.
3/4" NPT Models
3/4" NPT models have Tapered Threads and no Lock
Nut. Install the sensor as follows:
1. Screw the detector into the appropriate entry on
the termination box. Ensure a minimum of 5 fully
engaged threads. Use of teflon tape on NPT threads
is recommended to prevent thread damage.
When installing the GT3000 remotely from a UD10/
UD20, two‑conductor shielded cable is required to
prevent possible nuisance EMI/RFI. The maximum
cable length between the GT3000 and the UD10/UD20
is 2000 ft.
2. When the detector gets tight, note the position of the
LEDs, GND lug and calibration notch and adjust the
detector as required so that the LEDs will be easily
visible.
WIRING
power SUPPLY requirements
M25 Models
Calculate the total gas detection system power
consumption rate in watts from cold start-up. Select a
power supply with adequate capability for the calculated
load. Ensure that the selected power supply provides
sufficient regulated and filtered output power for the
entire system. If a back-up power system is required, a
float‑type battery charging system is recommended. If
an existing source of power is being utilized, verify that
system requirements are met.
M25 models have Straight Threads and a Lock Nut.
Install the detector as follows:
1. Screw the detector lock nut as far back as it will go,
then screw the detector into the appropriate entry
on the termination box. Ensure a minimum of 7 fully
engaged threads.
2. With the detector in the desired position (LEDs
visible as shown in Figure 5), tighten the lock nut
against the termination box to hold the detector
securely in place.
note
The power supply must also meet the noise
requirements for HART systems.
3. Tighten the set screws (minimum of two) to prevent
movement of the lock nut. See Figure 6.
Wiring cable requirements
Always use proper cabling type and diameter for input
power as well as output signal wiring. 22 to 14 AWG
shielded stranded copper wire is recommended.
Always install a properly sized, master power fuse or
breaker on the system power circuit.
note
The use of shielded cable in conduit or shielded
armored cable is highly recommended.
In
applications where the wiring is installed in
conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and
non‑signaling conductors to prevent nuisance
EMI problems.
Set Screws
caution
The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent
water ingress and/or maintain the explosion-proof
rating.
Figure 6—Location of Lock Nut and Set Screws
(Metric Models Only)
11.1
7
95-8616
Intrinsic SafeTy Barriers
Guidelines for Intrinsic Safety Wiring
When the GT3000 is used in an intrinsically safe
installation, care must be taken when selecting an I.S.
barrier to ensure proper function of the device. The
GT3000 has been tested with the types of barriers listed
in Tables 3 and 4.
Intrinsically safe systems must be installed in
accordance with the approved control drawings for
the field equipment and the intrinsic safety barriers.
Capacitance and inductance of interconnecting wiring
must always be included in wiring calculations.
Shielded twisted pair cables with at least 18 AWG
conductors are recommended to ensure circuit
performance.
Table 3 lists zener barriers. The third column gives the
range of input voltage to the barrier. The upper limit is
set by the barrier. The lower limit is limited by voltage
drops in the 4-20 mA loop with a maximum of 10 Ohms
of resistance in each leg of the loop.
The intrinsically safe conductors must be separated
from all other wiring by placing them in separate
conduits or raceways, or by an airspace of at least 2
inches (50 mm). When located within an enclosure, the
conductors can be separated by a grounded metal or
insulated partition. Wires must be tied down to prevent
loosening and/or shorting.
Table 4 lists isolating barriers that provide a wider range
of input power supply voltages and are less dependent
on voltage drops in the loop. Input voltage to the barrier
is specified by the barrier manufacturer.
Intrinsically safe wiring must be identified. Raceways,
cable trays, open wiring, and terminal boxes must be
labeled as Intrinsically Safe. Intrinsically safe wiring
may be light blue in color when no other conductors
colored light blue are used.
For additional information regarding proper IS
installation, refer to the Control Drawings in Appendix
H of this manual.
Wiring enclosures should be located as close as
possible to the hazardous area to minimize cable runs
and reduce total capacitance of the wiring.
A high quality intrinsic safety ground is required. Some
general rules for grounding intrinsically safe systems are:
Table 3—Acceptable Intrinsic Safety Barriers
for use with GT3000 – Zener Barriers
Manufacturer
P/N
Turck
MZB87PX
MTL
MTL7787P+
Pepperl & Fuchs
Z787.h
• The maximum impedance of the grounding
conductor between the barrier ground terminal and
the main ground point must be less than 1 ohm.
• The grounding conductor must be a minimum of 12
AWG.
• Redundant grounding conductors are recommended
to facilitate testing of the ground connection.
• The grounding conductor should be insulated and
protected from the possibility of mechanical damage.
Wiring Procedure
Table 4—Acceptable Intrinsic Safety Barriers
for use with GT3000 – Isolating Barriers
11.1
Manufacturer
P/N
Turck
IM33-11Ex-Hi
MTL
5541
Pepperl & Fuchs
KCD2-STC-Ex1
Stahl
9160/13-10-11
Wire the transmitter as shown in Figures 7 through 12.
Caution
If ripple on the main power source causes
interference with the HART function, the use
of an isolated power source (Figure 12) is
recommended for best HART performance.
8
95-8616
SENSOR TERMINATION BOX
GREEN
+
RED
24 VDC
AC
K
RE
D
BLACK
RED
BL
SEE NOTES 2 & 3
–
SEE NOTE 1
BLACK
NOTE 1
GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
NOTE 2
250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3
EXTERNAL HART COMMUNICATION DEVICES
CAN BE CONNECTED ACROSS THE 250 OHM
RESISTOR OR ACROSS THE GT3000.
NOTE 4
JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
GT3000
GAS DETECTOR
A2502
Figure 7—GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Explosion-Proof)
HAZARDOUS LOCATION
NON-HAZARDOUS LOCATION
GREEN
INTRINSIC
SAFETY
BARRIER
SENSOR TERMINATION BOX
AC
K
BLACK
+
24 VDC
SEE NOTES 2 & 3
–
RED
BL
RE
D
RED
SEE NOTE 1
BLACK
NOTE 1
GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
NOTE 2
250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3
EXTERNAL HART COMMUNICATION DEVICES
CAN BE CONNECTED ACROSS THE 250 OHM
RESISTOR OR ACROSS THE GT3000.
NOTE 4
JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
GT3000
GAS DETECTOR
A2530
Figure 8— GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Intrinsically Safe)
11.1
9
95-8616
UD20 DISPLAY UNIT
+
+
J2-6
–
J2-5
SHIELD
J2-4
POWER
LOOP
24 VDC
SEE NOTES 2 & 3
–
SEE NOTE 5
RED
BLACK
GREEN
J2-3
+
J2-2
–
J2-1
SHIELD
SENSOR
LOOP
SEE NOTE 1
J2
GT3000
GAS DETECTOR
NOTE 1
CONNECT THE GREEN DETECTOR LEAD TO THE
CHASSIS GROUND LUG ON THE INSIDE BOTTOM
OF THE UD20 DISPLAY UNIT ENCLOSURE.
NOTE 2
250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3
EXTERNAL HART COMMUNICATION DEVICES CAN BE
CONNECTED ACROSS THE 250 OHM RESISTOR,
ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.
NOTE 4
JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
NOTE 5
GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
B2478
Figure 9—GT3000 Wired Directly to UD20 Display Unit (Explosion-Proof)
UD20 DISPLAY UNIT
+
J2-6
+
–
J2-5
–
24 VDC
POWER
LOOP
SEE NOTES 2 & 3
SENSOR TERMINATION BOX
SHIELD
J2-4
SEE NOTE 1
SEE NOTE 1
GREEN
RED
RE
D
BL
AC
K
RED
J2-3
+
J2-2
–
J2-1
SHIELD
BLACK
BLACK
SENSOR
LOOP
J2
NOTE 1
GROUND THE SHIELD AT THE POWER SOURCE
END ONLY.
NOTE 2
250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3
EXTERNAL HART COMMUNICATION DEVICES CAN BE
CONNECTED ACROSS THE 250 OHM RESISTOR,
ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.
NOTE 4
JUNCTION BOXES MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
GT3000
GAS DETECTOR
D2408
Figure 10—GT3000 with Sensor Termination Box Wired to UD20 Display Unit (Explosion-Proof)
11.1
10
95-8616
NON-HAZARDOUS LOCATION
HAZARDOUS LOCATION
BLACK
RED
UD10
DISPLAY UNIT
GREEN
J3-2
J3-3
J3-4
J3-5
24 VDC –
4-20 mA
24 VDC +
4-20 mA –
J3-1
4-20 mA +
P1-2
J3
SEE NOTE 1
HIGH ALARM COM
J4-1
SHIELD
P1-1
HIGH ALARM NC
J4-2
HIGH ALARM NO
J4-3
AUX ALARM COM
J4-4
AUX ALARM NC
J4-5
AUX ALARM NO
J4-6
LOW ALARM COM
J4-7
LOW ALARM NC
J4-8
LOW ALARM NO
J4-9
FAULT COM
J4-10
P1
24 VDC +
SHIELD
P2-1
P12
P2-2
+
24 VDC –
MODBUS
Connector
P2-3
RS485 B
SHIELD
24 VDC
RS485 A
J2-1
P2-4
250
OHMS
MINIMUM
J2-2
24 VDC –
–
24 VDC +
4-20 mA
COM
P2-5
INPUT
J2-3
P2-6
J2
FAULT NC
J4-11
FAULT NO
J4-12
Relay Connector
PLC 4-20 mA INPUT CARD
P1-3
SHIELD
Output Loop
Connector
CALIBRATE
Sensor Connector
GT3000
GAS DETECTOR
J4
P2
Power Supply Connector
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum
for HART communication.
NOTE 1
CONNECT THE GREEN DETECTOR LEAD
TO THE CHASSIS GROUND LUG ON THE
INSIDE BOTTOM OF THE DISPLAY UNIT
ENCLOSURE.
NOTE 2
JUNCTION BOXES MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
C2453
Figure 11—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Non-Isolated Sourcing Output
HAZARDOUS LOCATION
NON-HAZARDOUS LOCATION
BLACK
RED
UD10
DISPLAY UNIT
GREEN
J3-3
J3-4
J3-5
4-20 mA
24 VDC +
SHIELD
24 VDC –
P1-1
J3-2
4-20 mA –
J3-1
4-20 mA +
P1-2
P1
J2
J4-4
AUX ALARM NC
J4-5
AUX ALARM NO
J4-6
LOW ALARM COM
J4-7
LOW ALARM NC
J4-8
LOW ALARM NO
J4-9
24 VDC +
SHIELD
P2-2
P2-1
P12
24 VDC –
MODBUS
Connector
P2-3
FAULT COM
SHIELD
RS485 B
J4-3
AUX ALARM COM
P2-4
+
RS485 A
J2-1
J4-2
24 VDC –
24 VDC
J2-2
HIGH ALARM NC
HIGH ALARM NO
24 VDC +
250
OHMS
MINIMUM
–
J4-1
P2-5
4-20 mA
COM
SEE NOTE 1
HIGH ALARM COM
P2-6
INPUT
J2-3
J3
Power Supply Connector
Notes: Resistor may be external if voltage input card is used.
Sinking resistance at PLC must be 250 ohms minimum
for HART communication.
C2479
24 VDC
–
+
Relay Connector
PLC 4-20 mA INPUT CARD
P1-3
SHIELD
Output Loop
Connector
CALIBRATE
Sensor Connector
GT3000
GAS DETECTOR
J4-10
FAULT NC
J4-11
FAULT NO
J4-12
J4
P2
NOTE 1
CONNECT THE GREEN DETECTOR
LEAD TO THE CHASSIS GROUND
LUG ON THE INSIDE BOTTOM OF
THE DISPLAY UNIT ENCLOSURE.
NOTE 2
JUNCTION BOXES MUST BE
ELECTRICALLY CONNECTED
TO EARTH GROUND.
Figure 12—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Isolated Sourcing Output
11.1
11
95-8616
Calibration
The calibration process proceeds automatically after
initiation. Onboard LEDs signal the operator when to
apply the calibration gas and inform of the progress.
GT3000 Calibration
The GT3000 supports one person calibration, which
can be initiated locally using a calibration magnet, or
remotely with a command from the HART interface.
The calibration process is automatic, with the exception
of gas delivery. LEDs on the transmitter guide the
operator when to apply and remove the calibration gas
See Table 5.
The calibration can be aborted by activating the
magnetic switch or with a command from the HART
communication device in lieu of applying the calibration
gas.
note
The HART interface allows the operator to adjust
the calibration gas concentration within the range
of 30 to 90% full scale. The default value for all
gas sensors except oxygen is 50% full scale.
Oxygen sensors use a default value of 20.9%.
If the calibration sequence is aborted or not completed
successfully, the detector reverts back to the previous
calibration values and signals a calibration fault. The
calibration fault can be cleared by activating the
magnetic switch for one second or by performing a
successful calibration.
All GT3000 gas detectors require a two-point
calibration — zero and span. The calibration process
can be initiated using the magnetic switch or through a
HART interface, such as the UD10/UD20. All sensors,
including oxygen, should be in clean air (20.9% oxygen)
when the calibration sequence is initiated.
The calibration process can fail for the following
causes:
If the calibration process takes longer than 10 minutes,
the detector will time-out and signal a calibration fault.
• Zero is out of range
• Span is out of range
• Time-Out.
The time and date of calibration events are logged in
non‑volatile memory along with the calibration outcome.
Possible calibration scenarios include the following:
Table 5— LEDs During Calibration
11.1
Calibration Step
Yellow LED
Waiting for Zero
Steady
Waiting for Gas
Blinking
Waiting for Span
Blinking
Remove Cal Gas
Off
• Successful Calibration
• Aborted Calibration
• Failed Calibration and the Cause
The Sensor Module stores calibration data in non‑volatile
memory to allow the sensor to be calibrated off‑site and
installed in the field without the need for re‑calibration.
12
95-8616
Calibration Procedure
NOTE
The calibration procedure must be completed
within a ten minute period. If the calibration is not
completed, a calibration fault will be generated
and the transmitter will continue to use the
previous calibration data.
note
When attaching or removing the calibration cup,
push or pull the cup with a slight clockwise twist.
Turning counterclockwise can cause the filter
assembly on the GT3000 to loosen. If the filter
assembly is inadvertently loosened, tighten it by
hand (no tools required).
NOTE
To ensure reliable detection performance,
calibration should be performed at regularly
scheduled intervals.
Various factors affect
the time interval between periodic calibrations
(typically 30, 60, or 90 day intervals, depending
on the ambient conditions).
Toxic and Hydrogen Sensors
1. Clean air must be present at the GT3000 sensor
module prior to initiating calibration. The use of
bottled air is recommended.
note
Calibration of ammonia sensor is recommended
any time the sensor has been exposed to 90 ppm
ammonia.
2. Initiate calibration by momentarily holding the
calibration magnet against the designated location
on the sensor module (see Figure 13) until the
green LED turns off and the yellow LED turns on
steady (approximately one second).
Remove
the magnet when the green LED turns off. The
detector immediately begins taking zero readings.
Calibration can also be initiated via HART interface
(see Appendix G) or the UD10 (see manual number
95-8618).
Oxygen Sensor
1. Using the magnet, activate the magnetic calibration
switch on the GT3000. The green LED turns off and
the yellow LED turns on steady.
2. The device
calibration.
3. When the zero calibration is complete, the yellow
LED changes from steady to blinking. Apply the
calibration gas to the sensor.
automatically
performs
the
zero
3. When the yellow LED on the GT3000 flashes, the
device automatically performs the span calculation.
If using bottled 20.9% oxygen, apply immediately.
4. When the yellow LED turns off, remove the calibration
gas. The gas level at the sensor gradually returns to
zero. The green LED turns on steady to indicate that
the device has returned to normal operation, using
the new calibration data.
4. After successful calibration, the yellow LED turns off
and the green LED turns on steady to indicate that
the device has returned to normal operation, using
the new calibration data. Remove calibration gas (if
used).
LED
PLACE MAGNET HERE
TO ACTIVATE INTERNAL
MAGNETIC SWITCH
B2452
Figure 13—Location of Magnetic Switch on GT3000 Detector
11.1
13
95-8616
Maintenance
Important
Always exercise caution when working in
combustible gas areas. Follow replacement
instructions explicitly.
note
Refer to the GT3000 Safety Manual (number
9 5 - 8 6 8 5 ) fo r s p e c i fi c re q u i re m e n t s a n d
recommendations applicable to the proper
installation, operation, and maintenance of all
SIL‑Certified GT3000 gas detectors.
note
Removing the sensor module with power applied
will result in a fault condition until a new sensor
module of the same type is installed. When
replacing an oxygen sensor, this action will result
in an alarm condition as the decreasing 4-20 mA
signal passes through the alarm range. Inhibit
response devices to prevent unwanted actuation.
Routine Inspection
The gas inlet to the sensor should be inspected
periodically, or during scheduled maintenance, to
ensure that external obstructions such as plastic bags,
litter, heavy oil and tar, paint, mud, snow, or other
materials do not block the flow of gas to the sensor,
thereby impairing the performance of the device.
NOTE
Oxygen (O2) electrochemical sensors contain
lead (Pb). Observe all local waste management
requirements when disposing of exhausted O2
electrochemical sensors.
To replace a dirty or damaged filter, simply grasp the
filter assembly and twist counterclockwise to remove.
Screw the new filter in place on the sensor module. Do
not overtighten. See Figure 14.
note
Electrochemical sensors are highly sensitive to
antiseptic wipes and/or cleaning products that
contain alcohol and antibacterial/antiviral agents.
Antiseptic products should be removed from
areas where sensors are stored, handled, or
used. If antiseptic products are being used on
workers' hands, sufficient time should be allowed
for the alcohol to evaporate before handling
sensors.
To ensure reliable protection, it is important to check and
calibrate the detection system on a regularly scheduled
basis. The frequency of these checks is determined by
the requirements of the particular installation – typically
30, 60, or 90 day intervals, depending on the ambient
conditions.
Sensor module replacement
(Live Maintenance)
The hot swappable, intrinsically safe sensor module
can be replaced in the field without removing power or
de‑classifying the hazardous area.
To replace the sensor module, locate the three captive
screws on the front of the module as shown in Figure
15. Loosen these screws and remove the old sensor
module. Install the new sensor module onto the
transmitter, and tighten the screws. To ensure proper
moisture ingress protection and grounding of the plastic
nosepiece, tighten the screws to 70-100 oz-in (0.5-0.7
N-m).
TURN FILTER COUNTERCLOCKWISE
TO REMOVE. NO TOOLS REQUIRED.
LOOSEN CAPTIVE PHILLIPS
SCREWS (3) TO REMOVE
SENSOR MODULE.
B2451
A2481
Figure 15—Location of Screws for Sensor Module Replacement
Figure 14—GT3000 with Replaceable Filter Removed
11.1
14
95-8616
DEVICE REPAIR AND RETURN
Calibration Kits for Gas Sensors
Part Number
Gas / Concentration
010274-001 H2S / 10 ppm
010274-002 H2S / 25 ppm
010274-003 H2S / 50 ppm
010274-008 H2 / 500 ppm
010274-009 O2 / 20.9%
010274-010
CO / 50 ppm
010274-011
CO / 250 ppm
010274-005
NH3 / 50 ppm
010274-006
NH3 / 250 ppm
010274-013 SO2 / 10 ppm
010274-014 SO2 / 50 ppm
010274-004 Cl2 / 5 ppm
010274-016
NO2 / 10 ppm
Replacement gas cylinders for all calibration kits are
available.
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure.
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
note
Inadequate packaging that ultimately causes
damage to the returned device during shipment
will result in a service charge to repair the damage
incurred during shipment.
Parts & Accessories
Return all equipment transportation prepaid to the
factory in Minneapolis.
Part Number
009700-001
009737-001
107427-059
101678-007
162552-001
009640-001
012509-001
012509-002
010780-003
010783-001
012513-XXX*
012514-XXX*
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
ORDERING INFORMATION
Sensor module (GTS) and transmitter (GTX) must be
ordered separately. Refer to the Transmitter and Sensor
Model Matrix on next page for ordering details.
Description
Magnetic Tool
Calibration Cup
Calibration Cup O-ring
3 Foot Tubing
Regulator, 1 LPM
Replacement Filter
Q312 Sample Draw without Fittings
Q312 Sample Draw with Fittings
GT3000 Remote Calibration Adaptor
GT3000 Remote Calibration Filter
Q912 Duct Mount Enclosure, M25
Q912 Duct Mount Enclosure, 3/4"
*Refer to the Product Catalog for a list of options.
GTS Gas Sensors
Gas Concentration
Hydrogen Sulfide (H2S)
0-20 ppm
Hydrogen Sulfide (H2S)
0-50 ppm
Hydrogen Sulfide (H2S)
0-100 ppm
Oxygen (O2)*
0-25% V/V
Carbon Monoxide (CO)
0-100 ppm
Carbon Monoxide (CO)
0-500 ppm
Ammonia (NH3)
0-100, or 0-500 ppm
Sulfur Dioxide (SO2)
0-20 ppm
Sulfur Dioxide (SO2)
0-100 ppm
Chlorine (Cl2)
0-10 ppm
Hydrogen (H2)
0-1000 ppm
Nitrogen Dioxide (NO2)
0-20 ppm
Assistance
For assistance in ordering a system to meet the needs
of a specific application, contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.det-tronics.com
E-mail: det-tronics@det-tronics.com
*Oxygen detector for O2 depletion (< 21% V/V) only.
11.1
15
95-8616
GTS Sensor Model Matrix
MODEL
GTS
DESCRIPTION
Gas Sensor Module
TYPE
H2S
H2S+
CL2
GAS / RANGE
Hydrogen Sulfide
20P
0 - 20 PPM
50P
0 - 50 PPM
100P
0 - 100 PPM
Hydrogen Sulfide
20P
0 - 20 PPM
50P
0 - 50 PPM
100P
0 - 100 PPM
Chlorine
10P
NH3
H2
0 - 10 PPM
Ammonia
100P
0 - 100 PPM
500P
0 - 500 PPM
Hydrogen
1000P
O2
0 - 1000 PPM
Oxygen
25V
CO
SO2+
NO2
0 - 25 % by Vol
Carbon Monoxide
100P
0 - 100 PPM
500P
0 - 500 PPM
Sulfur Dioxide
20P
0 - 20 PPM
100P
0 - 100 PPM
Nitrogen Dioxide
20P
0 - 20 PPM
TYPE
APPROVAL*
B
INMETRO (Brazil)
C
CSA
D
DNV
R
Russia
S
SIL
T
SIL/FM/CSA/ATEX/CE/IECEx
W
FM/CSA/ATEX/CE/IECEx
* Type Approval can use one or more letters to
designate the Approvals on the product.
11.1
16
95-8616
GTX Transmitter Model Matrix
MODEL
DESCRIPTION
GTX
Gas Transmitter
TYPE
S
MATERIAL
Stainless Steel (316)
TYPE
THREAD SIZE
N
3/4" NPT
M
Metric M25
TYPE
OUTPUTS
26
4-20 mA, HART (3.5 mA FAULT)
29
4-20 mA, HART (2.45 mA FAULT)
TYPE
APPROVALS
B
INMETRO (Brazil)
R
Russia
W
FM/CSA/ATEX/CE/IECEx
TYPE
CLASSIFICATION (Division/Zone)
4
Intrinsically Safe
5
Explosion-Proof
Note: Approvals Type W and B are SIL 2 Capable when used with an H2S or O2 GTS sensor module.
11.1
17
95-8616
Appendix A
FM Approval Description
The following items, functions and options describe the FM approval.
Approval
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
Class I, Div. 1, Groups A, B, C, & D (T4).
Class I, Div. 2, Groups A, B, C, & D (T4).
Class I, Zone 1, AEx d mb [ia Ga] IIC T4.
IP66.
Conduit seal not required.
Acidic atmospheres excluded.
note
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of
installation to provide protection for the flying leads.
Intrinsically Safe Model
IS Class I, Div. 1, Groups A, B, C, & D (T4).
Class I, Zone 0, AEx ia IIC (T4).
IP66.
NOTE
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an
approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding
proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
Performance verified per ANSI/ISA 92.00.01, FM6340/41 and EN50104.
11.1
18
95-8616
Approved Accessories
11.1
Part Number
Description
010274-001
Gas Calibration Kit, 10 ppm H2S
010274-002
Gas Calibration Kit, 25 ppm H2S
010274-003
Gas Calibration Kit, 50 ppm H2S
010274-008
Gas Calibration Kit, 500 ppm H2
010274-009
Gas Calibration Kit, 20.9% O2
010274-010
Gas Calibration Kit, 50 ppm CO
010274-011
Gas Calibration Kit, 250 ppm CO
010274-005
Gas Calibration Kit, 50 ppm NH3
010274-006
Gas Calibration Kit, 250 ppm NH3
010274-013
Gas Calibration Kit, 10 ppm SO2
010274-014
Gas Calibration Kit, 50 ppm SO2
010274-004
Gas Calibration Kit, 5 ppm Cl2
010274-016
Gas Calibration Kit, 10 ppm NO2
009700-001
Magnetic Tool
009737-001
Calibration Cup
107427-059
Calibration Cup O-ring
101678-007
3 Foot Tubing
162552-001
Regulator, 1 LPM
009640-001
Replaceable Filter
19
95-8616
Appendix B
CSA certification Description
The following items, functions and options describe the CSA approval.
Approval
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
Class I, Div. 1, Groups A, B, C, & D (T4).
Class I, Div. 2, Groups A, B, C, & D (T4).
Class I, Zone 1, AEx d mb [ia Ga] IIC T4.
IP66.
Conduit seal not required.
Acidic atmospheres excluded.
note
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of
installation to provide protection for the flying leads.
Intrinsically Safe Model
Class I, Div. 1 & 2, Groups A, B, C, & D (T4).
IP66.
NOTE
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an
approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding
proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
11.1
20
95-8616
Appendix C
ATEX Approval Description
The following items, functions and options describe the ATEX approval.
Approval
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
0539
II 2(1)G.
Ex d mb [ia Ga] IIC T4 Gb IP66.
FM10ATEX0009X.
FM
®
APPROVED
note
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of
installation to provide protection for the flying leads.
Intrinsically Safe Model
0539
II 1 G Ex ia IIC T4 Ga IP66.
FM08ATEX0045X.
FM
®
APPROVED
NOTE
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an
approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding
proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
11.1
21
95-8616
Appendix D
IECEx Approval Description
The following items, functions and options describe the IECEx approval.
Approval
Electrochemical Gas Detector, GT3000 Series.
Explosion Proof Model
Ex d mb [ia Ga] IIC T4 Gb IP66.
IECEx FMG 10.0003X.
note
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of
installation to provide protection for the flying leads.
Intrinsically Safe Model
Ex ia IIC T4 Ga IP66.
IECEx FMG 08.0005X.
NOTE
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an
approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding
proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
11.1
22
95-8616
Appendix E
Other Approvals
The following items, functions and options describe various other approvals applicable to the GT3000.
SIL Approval
IEC 61508
Certified SIL 2 Capable.
SIL Certification includes H2S and O2 GTS models only. For specific information regarding SIL models, refer to the
GT3000 Safety Reference Manual, form 95-8685.
INMetro (Brazil)
Explosion Proof Model
UL-BR 15.0752X
Ex d mb [ia Ga] IIC T4 Gb IP66
Tamb –40°C to +50°C (H2S)
Tamb –20°C to +50°C (other)
note
The GTX Gas Transmitter module shall be connected directly to a junction box suitable for the area of
installation to provide protection for the flying leads.
NOTE
Consideration must be given to overall Gas System Performance Requirements.
Intrinsically Safe Model
UL-BR 15.0404X
Ex ia IIC T4 Ga IP66
Tamb –40°C to +50°C
NOTE
In order to maintain the intrinsically safe rating of the transmitter, the device must be powered through an
approved I.S. barrier.
For a list of recommended barrier models, refer to Tables 3 and 4. For additional information regarding
proper I.S. installation, refer to the Control Drawings in Appendix H of this manual.
DNV
Type Approval Certificate No. A-12358.
MED
Certificate No. MED-B-6708.
Russia / Kazakhstan / India
Contact Det-Tronics for details.
11.1
23
95-8616
Appendix F
declaration of conformity
For a copy of the original document, please contact the factory.
11.1
24
95-8616
Appendix G
Sensor comparison/Cross Sensitivity
Electrochemical Gas Sensors
Accuracy of
Reading
Operating
Temperature Range
Zero Drift
Performance
Approved Standard
±2 ppm or
±10% of Reading
–40°C to +50°C
± 1 ppm/Mo.
ISA 92.00.014
T20 = ≤4 Sec
T50 = ≤7 Sec.
T90 = ≤16 Sec.
±2 ppm or
±10% of Reading
–40°C to +50°C
± 1 ppm/Mo.
ISA 92.00.014
0-100 PPM
T20 = ≤5 Sec
T50 = ≤8 Sec.
T90 = ≤21 Sec.
±2 ppm or
±10% of Reading
–40°C to +50°C
± 2 ppm/Mo.
ISA 92.00.014
Hydrogen Sulfide+
(H2S+)
0-20 PPM
T20 = ≤10 Sec
T50 = ≤13 Sec.
T90 = ≤23 Sec.
±2 ppm or
±10% of Reading
–40°C to +55°C
± 1 ppm/Mo.
ISA 92.00.014
Hydrogen Sulfide+
(H2S+)
0-50 PPM
T20 = ≤6 Sec
T50 = ≤9 Sec.
T90 = ≤15 Sec.
±2 ppm or
±10% of Reading
–40°C to +55°C
± 1 ppm/Mo.
ISA 92.00.014
Hydrogen Sulfide+
(H2S+)
0-100 PPM
T20 = ≤6 Sec
T50 = ≤8 Sec.
T90 = ≤15 Sec.
±2 ppm or
±10% of Reading
–40°C to +55°C
± 2 ppm/Mo.
ISA 92.00.014
Ammonia (NH3)
0-100 PPM2
T50 = 24 Sec.
T90 = 65 Sec.
±4 ppm or
±10% of Reading
–20°C to +40°C
± 2 ppm/Mo.
FM63404
Ammonia (NH3)
0-500 PPM2
T50 = 30 Sec.
T90 = 120 Sec.
±4 ppm or
±10% of Reading
–20°C to +40°C
± 10 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Oxygen (O2)
0-25% V/V3
T20 = 7 Sec.
T90 = 30 Sec.
< 0.5% V/V
–20°C to +50°C
< 2 %/Mo.
BS EN 501044
Carbon
Monoxide (CO)
0-100 PPM
T50 = 15 Sec.
T90 = 40 Sec.
±5 ppm or
±10% of Reading
–20°C to +50°C
± 2 ppm/Mo.
ISA 92.00.014
Carbon
Monoxide (CO)
0-500 PPM
T50 = 12 Sec.
T90 = 25 Sec.
±5 ppm or
±10% of Reading
–20°C to +50°C
± 9 ppm/Mo.
ISA 92.00.014
Sulfur Dioxide+
(SO2+)
0-20 PPM
T50 = 12 Sec.
T90 = 30 Sec.
±0.6 ppm or
±10% of Reading
–40°C to +55°C
± 0.4 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Sulfur Dioxide+
(SO2+)
0-100 PPM
T50 = 15 Sec.
T90 = 35 Sec.
±0.6 ppm or
±10% of Reading
–40°C to +55°C
± 0.4 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Chlorine
(Cl2)
0-10 PPM
T50 = ≤14 Sec.
T90 = ≤34 Sec.
±0.6 ppm or
±10% of Reading
–20°C to +50°C
< 0.2 ppm/Mo.
FM63404
Hydrogen
(H2)
0-1,000 PPM
T50 = 8 Sec.
T90 = 60 Sec.
±50 ppm or
±10% of Reading
–20°C to +40°C
± 20 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Nitrogen Dioxide
(NO2)
0-20 PPM
T50 = 7 Sec.
T90 = 31 Sec.
±2 ppm or
±10% of Reading
–20°C to +40°C
± 0.1 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Gas
Range
Response
Time1
Hydrogen Sulfide
(H2S)
0-20 PPM
T20 = ≤7 Sec
T50 = ≤10 Sec.
T90 = ≤16 Sec.
Hydrogen Sulfide
(H2S)
0-50 PPM
Hydrogen Sulfide
(H2S)
(Whichever
is Greater)
1 Time to reach percentage of final reading when gas concentration equal to full scale is applied to sensor.
2 Background concentrations of ammonia may shorten lifetime of sensor.
3 Sensor approved for oxygen depletion (< 21% V/V) only.
4 Factory Mutual Performance Approved.
11.1
25
95-8616
Typical Cross Sensitivity of H2S Sensor (0-20 ppm / 0-50 ppm / 0-100 ppm)
Gas
Concentration
Carbon monoxide
300 ppm
H2S+
≤ 2 ppm
≤ 2 ppm
Sulfur dioxide
5 ppm
~ 1 ppm
~ 0 ppm
Nitric oxide
35 ppm
< 0.7 ppm
~ 0 ppm
Hydrogen
10000 ppm
≤ 10 ppm
Ammonia
50 ppm
Nitrogen dioxide
5 ppm
~ –1 ppm
~ 0 ppm
Methanol
200 ppm
~ 0 ppm
~ 0 ppm
Concentration
Reading
~ 0 ppm
Typical Cross Sensitivity of NH3 Sensor (0-500 ppm)
Typical Cross Sensitivity of NH3 Sensor (0-100 ppm)
Gas
Reading
H2S
Gas
Concentration
Reading
Alcohols
1000 ppm
0 ppm
Alcohols
1000 ppm
0 ppm
Carbon dioxide
5000 ppm
0 ppm
Carbon monoxide
100 ppm
0 ppm
Carbon monoxide
100 ppm
0 ppm
Chlorine
5 ppm
0 ppm
Hydrocarbons
% Range
0 ppm
Nitrogen dioxide
10 ppm
0 ppm
Hydrogen
10000 ppm
0 ppm
Sulfur dioxide
20 ppm
–40 ppm
Hydrogen sulfide
20 ppm
~ 2 ppm1
Hydrogen
3000 ppm
0 ppm
Hydrogen sulfide
20 ppm
2 ppm
1 Short
time gas exposure in minute range.
Typical Cross Sensitivity of SO2 Sensor (0-20 ppm / 0-100 ppm)
Typical Cross Sensitivity of CO Sensor (0-100 ppm / 0-500 ppm)
Gas
Concentration
Hydrogen sulfide
15 ppm
Reading
Gas
Concentration
Reading
CO
Carbon monoxide
300 ppm
< 1 ppm
~ 45 ppm
Nitric oxide
50 ppm
0-5 ppm
6 ppm
< –10 ppm
25 ppm
< 0.1 ppm
Sulfur dioxide
5 ppm
~ 2.5 ppm
Nitrogen dioxide
Nitric oxide
35 ppm
~ 10 ppm
Hydrogen Sulfide
Chlorine
1 ppm
–1 ppm
Chlorine
5 ppm
< –2 ppm
Hydrogen
100 ppm
< 40 ppm
Ammonia
20 ppm
0 ppm
Nitrogen dioxide
5 ppm
~ –3 ppm
Typical Cross Sensitivity of Cl2 Sensor (0-10 ppm)
Hydrogen
400 ppm
< 1 ppm
Hydrogen Cyanide
10 ppm
< 5 ppm
Acetylene
10 ppm
< 30 ppm
Ethene
50 ppm
< 45 ppm
Typical Cross Sensitivity of NO2 Sensor (0-20 ppm)
Gas
Concentration
Reading
Gas
Concentration
Reading
Carbon monoxide
300 ppm
0 ppm
Alcohols
1000 ppm
0 ppm
Hydrogen sulfide
15 ppm
~ –7.5 ppm
Carbon dioxide
5000 ppm
0 ppm
Sulfur dioxide
5 ppm
0 ppm
Chlorine
1 ppm
≤ 1 ppm
Nitric oxide
35 ppm
0 ppm
Nitric oxide
100 ppm
0.4 ppm
Sulfur dioxide
20 ppm
5 ppm
Hydrogen
3000 ppm
0 ppm
For details on other interfering gases, please contact Detector Electronics Corp.
11.1
26
95-8616
Appendix H
HART Communication
HART MENU STRUCTURE
This section displays the menu tree for the GT3000. The menu tree shows the primary commands and options
available when using menu selections of a HART handheld communicator.
11.1
27
95-8616
11.1
28
95-8616
GT3000 Root Menu
1) Process Menu
2) Status Menu
3) Setup Menu
4) Calibration Menu
5) Test Menu
xxxxx
xx yy
xx yy
xx yy
xx yy
xx yy
xx yy
1) Self Test
2) Response Test
3) Reset
4) Reset min-max Temps
5) Loop Test
6) D/A Trim
Test Menu
1) Cal Gas Concentraton xx
2) Sensor Calibration
3) Response Factor
xxx
4) Snsr Cal Point Zero
xxx
5) Snsr Cal Point Span
xxx
6) Change Gas Sensor Type
Calibration Menu
1) Write Protect
Yes/No
2) Write Protect Menu
3) Hart Option Menu
4) RTC Menu
5) Clear Configuration
Setup Menu
1) General Info
2) Fault/Status Info
3) Device Information
4) Sensor Information
5) History Info
6) Debug Menu
Status Menu
1) Gas Name
2) PV
3) PV AO
4) PV URV
5) PV LRV
6) SV
7) TV
Process Menu
Write Protect Menu
1) Seconds
2) Minutes
3) Hours
4) Day
5) Month
6) Year
RTC Menu
1) Tag
xxxxx
2) Descriptor
xxxxx
3) Message
xxxxx
4) Poll Adrs
xxxxx
5) Date
xxxxx
6) Final asmbly num xxxx
Hart Option Menu
1) Change Write Protect
2) Write Protect
xxxxx
Disable
Enable
Change Password
Select Option
xxxxxxxx
Enter Password
Fault/Status Info
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
1) Debug Hart Err Cntr xxxx
2) Debug Modbus Err Cntr
3) DD Build Version
Debug Menu
1) Snsr History
2) Tx History
3) Read Calibration Log
4) Read Event Log
History Info
1) Sensor Sensitivity xxxxx
2) Sensor Type
xxxxx
3) Snsr Serial Num
xxxxx
4) Snsr Revision
xxxxx
5) PV USL
xxxxx
6) PV LSL
xxxxx
7) Snsr Hardware Rev
8) Snsr Firmware Rev
9) Snsr Run Hours
xxxxx
Snsr PPM Hours
xxxxx
Sensor Information
1) RTC Menu
2) Write Protect
3) Universal rev
4) Fld dev rev
5) Software rev
6) Tx Serial Number
7) Tx Hardware Rev
8) Tx Firmware Rev
9) Tx Running Hrs
Tx Temperature
Device Information
1) Op Mode
xxxxx
2) Cal State
xxxxx
3) Snsr Status Byte1 xxxxx
4) Snsr Status Byte2 xxxxx
5) Tx Status Byte 1
xxxxx
6) Tx Status Byte 2
xxxxx
7) Snsr Fault Byte 1
xxxxx
8) Snsr Fault Byte 2
xxxxx
9) Tx Fault Byte 1
xxxxx
Tx Fault Byte 2
xxxxx
GTX Firmware Version 1.04
DD Version 0.10
Change Password
xxxxxxxx
Change the device write
protect setting.
General Info
1) Manufacturer
2) Model
3) Tag
4) Descriptor
5) Message
6) Final asmbly num
7) Dev id
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxx
xx-xx-xx
xx:xx:xx
xx
xx
xx
xxxx
xx-xx-xx
xx:xx:xx
xx
xx.xx
xxxxxx
GT3000
HART
March 16,2009
Detector Electronics
GT3000 DD
Build Version:
Build Date:
DD Build Version
Event Log:
Index
DD-MM-YY
hh:mm:ss
Event Code
Event Log
Cal Log:
Index
DD-MM-YY
hh:mm:ss
Cal Code
Zero Value
Span Value
Cal Log
1) Tx Running Hrs xxxx
2) Tx Max Temp
xxxxx
3) Max Temp Time
4) Tx Min Temp
xxxxx
5) Min Temp Time
Tx History
1) Snsr Run Hours xxxx
2) Sensor Max Temp xxxx
3) Max Temp Time
4) Sensor Min Temp xxxx
5) Min Temp Time
6) Snsr Hi Temp Rst xxxx
7) Snsr Lo Temp Rst xxxx
Sensor History
1) Seconds
2) Minutes
3) Hours
4) Day
5) Month
6) Year
RTC Menu
DET-TRONICS
Appendix I
Intrinsic safety ConTrol Drawing — FM
009803-001 Rev. D
11.1
29
95-8616
Intrinsic safety ConTrol Drawing — CSA
009803-002 Rev. B
11.1
30
95-8616
Explosion proof ConTrol Drawing — FM
012555-001 Rev. A
11.1
31
95-8616
95-8616
FlexSonicTM Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2015 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.