Det-Tronics Instructions UVIR Flame Detector with Pulse Output X5200
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
UVIR Flame Detector with Pulse Output
X5200
9.1
Rev: 11/15
95-8547
Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . 17
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . 18
oi Plate Removal and Replacement . . . . . . . . . 18
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Periodic Checkout Procedure . . . . . . . . . . . . . . 18
Integral Wiring Compartment . . . . . . . . . . . . . . . 3
Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
SIGNAL PROCESSING OPTIONS . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
IR Detector Options . . . . . . . . . . . . . . . . . . . . . . . 3
UV Detector Options . . . . . . . . . . . . . . . . . . . . . . 4
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 19
GENERAL APPLICATION INFORMATION . . . . . . . . 4
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 21
Response Characteristics . . . . . . . . . . . . . . . . . . 4
False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 5
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . . 21
Factors Inhibiting Detector Response . . . . . . . . . 5
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 21
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
X5200 Model Matrix . . . . . . . . . . . . . . . . . . . . . 22
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 7
Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 7
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 23
Protection Against Moisture Damage . . . . . . . . . 8
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 8
APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 28
EOL Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . 16
APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 29
STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 16
Manual oi Test (Output to Controller) . . . . . . . . 16
Count Test Mode (Output to Controller) . . . . . . . . 16
Fire Alarm Test (Pulse Output to Fire Alarm Panel) . 17
APPENDIX D – IECEx APPROVAL . . . . . . . . . . . . . 31
INSTRUCTIONS
UVIR Flame Detector
with Pulse Output
X5200
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X5200 includes the Automatic oi ® (Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
DESCRIPTION
When used as a field replacement, all operating features
of the current controller are retained in addition to gaining
the advanced features of the X5200 Flame Detector. In
typical applications, the four wire X5200 can use all
existing system wiring.
The evolution continues with the new X5200 UVIR
Flame Detector. The X5200 meets the most stringent
requirements worldwide with advanced detection
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
mounting arrangement allows the UV and IR sensors to
monitor the same hazardous location with a 90 degree
cone of vision. When both sensors simultaneously detect
the presence of a flame, an alarm signal is generated.
The detector has Division and Zone explosion-proof
ratings and is suitable for use in indoor and outdoor
applications. The X5200 housing is available in copperfree aluminum or stainless steel, with NEMA/Type 4X and
IP66/IP67 rating.
The X5200 with pulse/relay output is designed for use
in controller based systems. In addition to use in new
systems, it can serve as a direct field replacement
for Detector Electronics Corporation’s (Det-Tronics)
controller based flame detectors that generate a pulse
output (not compatible with R7484 and R7409B/C).
9.1
©Detector Electronics Corporation 2016
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
1
Rev: 11/15
95-8547
OUTPUTS
ATTENTION
The X5200 contains a source tube that is filled
with a gas mixture containing Krypton 85 (Kr85),
a radioactive material. Radioactive materials are
subject to regulation under U.S. and international
law.
Relays
The detector is furnished with fire and fault relays. The
relays are rated 5 amperes at 30 Vdc.
The Fire Alarm relay has redundant terminals and normally
open / normally closed contacts, normally de-energized
operation, and latching or non-latching operation.
oi (OPTICAL INTEGRITY)
Automatic oi
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
The X5200 includes the Automatic oi feature — a
calibrated performance test that is automatically
performed once per minute to verify complete detector
operation capabilities. No testing with an external test
lamp is required. The detector automatically performs
the same test that a maintenance person with a test
lamp would perform — once every minute. However, a
successful Automatic oi test does not produce an alarm
condition.
Latching relays can be reset by removing input power
(0.1 second minimum).
An alarm condition will normally override a fault condition,
unless the nature of the fault condition impairs the ability
of the detector to generate or maintain an alarm output,
i.e., loss of operating power.
The detector signals a fault condition when less than half
of the detection range remains. This is indicated by the
fault relay and is evident by the yellow color of the LED
on the face of the detector. See the “Troubleshooting”
section for further information.
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions. Table 1 indicates the condition of the
LED for each status.
Magnetic oi / Manual oi
CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
Table 1—Detector Status Indicator
Detector Status
Power On/Normal Auto oi
(no fault or fire alarm)
Power On/Normal Man oi
Fault
UV Alarm only
IR Alarm only
Pre-Alarm
Fire (Alarm)
LED Indicator
Green
Green, flashing off for
0.5 sec. every 5 sec.
Yellow
Red, flashing on for 5 sec. and
off for 5 sec.
Red, flashing on for 0.25 sec.
and off for 0.25 sec.
Red, flashing on for 1 sec. and
off for 1 sec.
Steady Red
The detector incorporates both Magnetic oi (Mag oi)
and Manual oi (Man oi) test capabilities. These tests
provide pulses (80 to 100 CPS) to the controller (R7404
or R7494) when the detector is not in fault. If the test
is successful, the controller indicates a fire and the
appropriate zone output is active.
NOTE
If the detector is in a fault condition, a successful
Mag oi or Man oi test cannot be performed.
On Power-Up, The LED Flashes in Sequence as Follows,
Indicating Sensitivity and Signal Processing Status
Low UV Sensitivity
Medium UV Sensitivity
High UV Sensitivity
Very High UV Sensitivity
One Red Flash
Two Red Flashes
Three Red Flashes
Four Red Flashes
Stand. UV Signal Process.
Arc Rej. UV Signal Process.
One Yellow Flash
Two Yellow Flashes
Low IR Sensitivity
Medium IR Sensitivity
High IR Sensitivity
Very High IR Sensitivity
Quick Fire/TDSA IR Signal
TDSA only IR Signal
9.1
One Green Flash
Two Green Flashes
Three Green Flashes
Four Green Flashes
One Yellow Flash
Two Yellow Flashes
2
95-8547
The Mag oi test is performed by placing a magnet by
the location marked “MAG OI” on the outside of the
detector (see Figure 2). This action causes the detector
to immediately send pulses to the controller. Controller
response is as follows:
•
The Zone LED blinks.
•
The digital display indicates which zone is in alarm.
•
The status indicator shows “6” (fire).
DATA LOGGING
Data logging capability is also provided. Status conditions
such as normal, power down, general and oi faults, prealarm, fire alarm, time and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active,
and again when the status changes. Data is accessible
using the Inspector Connector accessory or RS-485.
INTEGRAL WIRING COMPARTMENT
IMPORTANT
Mag oi can be performed with the controller’s
(R7404/R7494) keylock switch in either the
NORMAL or TEST position. In NORMAL, the
controller goes into alarm and activates its outputs.
If no controller alarm output is desired, place
the keylock switch in the TEST position before
touching the magnet to the outside of the detector.
Man oi operates only with the keylock switch in
the TEST position.
All external wiring to the device is connected within
the integral junction box. The detector is furnished with
four conduit entries, with either 3/4 inch NPT or M25
threads.
SIGNAL PROCESSING OPTIONS
The X5200 features signal processing options for both
the UV and IR sensor. These options determine the type
of logic that the detector will use for processing fire
signals to customize the X5200 to the application.
During the entire test, the detector gives no indication
of alarm.
IR DETECTOR OPTIONS
To reset the controller status and alarms, place the
keylock switch in RESET. Return the keylock switch to
NORMAL when testing is complete.
The IR detector in the X5200 can be programmed for:
The Man oi test is nearly identical to the Mag oi test,
except for the manner in which the test is initiated:
•
Press the SELECT button to select the appropriate
detector for test.
•
Press the TEST/ACCEPT button to initiate the test.
TDSA enabled
––
Both TDSA and Quick Fire enabled (either initiates
fire alarm).
Time Domain Signal Analysis (TDSA)
Place the keylock switch on the controller (R7404/
R7494) in the TEST position.
•
––
The TDSA signal processing technique analyzes the
input signal in real time, requiring the IR signal to flicker
randomly to recognize it as a fire condition.
Using TDSA signal processing, the X5200 ignores
regularly chopped blackbody sources (occurring in areas
where moving conveyors and hot objects in proximity
to one another result in a regularly chopped IR signal),
because it looks for a less uniform signal. However, in
the presence of a regularly chopped signal, the unit is
more susceptible to false alarms due to sporadic IR that
functions as a trigger when occurring in conjunction with
the regularly chopped signal.
Controller and detector responses are identical to the
Mag oi test described above.
To reset the controller status and alarms, place the
keylock switch in RESET. Return the keylock switch to
NORMAL when testing is complete.
NOTE
Refer to Appendix A for FM verification of the
o i function.
COMMUNICATION
The X5200 is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 uses Modbus protocol, with the
detector configured as a slave device.
9.1
3
95-8547
GENERAL APPLICATION
INFORMATION
Quick Fire (High Speed)
The Quick Fire (High Speed) feature can be used in
conjunction with the TDSA signal processing method.
This method overrides TDSA requirements in the event
of an intense signal. When Quick Fire is activated, the
detector is capable of responding to an intense fire signal
in less than 30 milliseconds (0.030 seconds). Using
the Quick Fire feature in conjunction with TDSA signal
processing allows the detector to provide a high speed
response to a large, non-flickering fire (such as in high
pressure gas applications) while maintaining an ability to
respond to smaller fires.
RESPONSE CHARACTERISTICS
Response is dependent on the detector’s sensitivity
setting, arc rejection, and time delay settings. Other
factors include distance, type of fuel, temperature of the
fuel, and time required for the fire to come to equilibrium.
As with all fire tests, results must be interpreted according
to an individual application.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics.
UV DETECTOR OPTIONS
Welding
The UV detector in the X5200 can be programmed for:
––
Arc Rejection
––
Standard
Electric arc welding is a source of intense ultraviolet
radiation. UV radiation from arc welding readily scatters
and can deflect across significant distances, even when
direct obstructions exist. Any open door or window can
allow nuisance UV radiation from arc welding to enter an
enclosed area.
Arc Rejection (Recommended Factory Setting)
The Arc Rejection mode enables the detector to
prevent nuisance fire alarms caused by UV from shortduration electrical arcs or electrostatic discharge, while
maintaining the ability to reliably detect the UV given
off by a flame. Typical applications that benefit from arc
rejection logic include electrostatic coating processes
and uncontrolled environments where transient UV
sources can be present, such as many typical outdoor
applications. Most false alarm sources have short
transient UV signatures, while fire creates a long UV
signature over many seconds. Most fires are detected in
a few seconds (see response times in Appendix A).
It is recommended that the system be bypassed during
welding operations in situations where the possibility of a
false alarm cannot be tolerated. Gas welding mandates
system bypass, since the gas torch is an actual fire. Arc
welding rods can contain organic binder materials in
the flux that burn during the welding operation and are
detectable by the X5200. Welding rods with clay binders
do not burn and will not be detected by the X5200.
However, system bypass is always recommended, since
the material being welded may be contaminated with
organic substances (paint, oil, etc.) that will burn and
possibly cause the X5200 to alarm.
Standard Signal Processing
Standard signal processing is recommended for
high-speed suppression systems only. To allow for
high-speed operation, the standard processing mode
does not incorporate the arc rejection programming.
This mode should only be used in a controlled, indoor
environment.
Artificial Lighting
The X5200 should not be located within 3 feet (0.9m)
of artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
EMI/RFI Interference
The X5200 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE Marked. It will
not respond to a 5 watt walkie-talkie at distances greater
than 1 foot (0.3m).
Non-Carbon Fires
The response of the X5200 is limited to carbonaceous
fuels. It should not be used to detect fires from fuels that
do not contain carbon, such as hydrogen, sulfur and
burning metals.
9.1
4
95-8547
FALSE ALARM SOURCES
FACTORS INHIBITING DETECTOR RESPONSE
UV: The UV sensor is solar blind to the ultraviolet
component of solar radiation. However, it will
respond to sources of UV besides fire, such as
electric arc welding, lightning, high voltage corona,
x-rays, and gamma radiation.
Windows
Glass and Plexiglas windows significantly attenuate
radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Det-Tronics for recommendations regarding window
materials that will not attenuate radiation.
NOTE
Radiation generated by false alarm sources such
as periodic lightning or sparks in the area can be
effectively ignored by the detector using the arc
rejection feature or time delay.
Obstructions
Radiation must be able to reach the detector in order
for it to respond. Care must be taken to keep physical
obstructions out of the line of view of the detector. In
addition, UV or IR absorbing gases or vapors must not
be allowed to accumulate between the detector and
the protected hazard. See Table 2 for a list of these
substances.
IR: The detector has been designed to ignore steady
state infrared sources that do not have a flicker
frequency characteristic of a fire, however, it
should be noted that if these steady state infrared
sources are hot enough to emit adequate amounts
of infrared radiation in the response range of the
IR sensor and if this radiation becomes interrupted
from the view of the detector in a pattern
characteristic of a flickering flame, the IR sensor
can respond.
9.1
Smoke
Smoke will absorb radiation. If accumulations of
dense smoke can be expected to precede the
presence of a flame, then detectors that are used
in enclosed areas should be mounted on the wall
approximately 3 feet (0.9m) from the ceiling where
the accumulation of smoke is reduced.
Any object having a temperature greater than
0° Kelvin (–273°C) emits infrared radiation. The
hotter the object, the greater the intensity of the
emitted radiation. The closer the infrared source is
to the detector, the greater the potential for a false
alarm. The IR sensor can respond to IR radiation
sources that can meet the amplitude and flicker
requirements of the detector such as vibrating hot
objects.
Detector Viewing Windows
It is important to keep the detector viewing windows as
free of contaminants as possible to maintain maximum
sensitivity. Commonly encountered substances that can
significantly attenuate UV and/or IR radiation include, but
are certainly not limited to, the following:
Although the detector is designed to reduce
false actuations, certain combinations of ambient
radiation must be avoided. For example, if IR
radiation with an intensity that exceeds the fire
threshold of the IR sensor should reach the detector
as a flickering signal, and if at the same time
an electric arc welding signal also reaches the
detector, an alarm output will be generated.
5
––
Silicones
––
Oils and greases
––
Dust and dirt buildup
––
Paint overspray
––
Water and ice
95-8547
IMPORTANT SAFETY NOTES
Table 2— UV and IR Absorbing Gases and Vapors
The following is a partial list of compounds that exhibit
significant UV absorption characteristics. These are
also usually hazardous vapors. While generally of little
consequence in small amounts, these gases can restrict
UV detection if they are in the atmosphere in heavy
concentrations. It should also be determined whether or
not large amounts of these gases may be released as a
result of a fire-causing occurrence.
WARNING
Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage. This type of damage
could be undetected and could result in failure to
see a fire and/or false alarm.
Acetaldehyde
Methyl Methacrylate
Acetone Alpha-Methylstyrene
Acrylonitrile Naphthalene
Ethyl Acrylate
Nitroethane
Methyl Acrylate
Nitrobenzene
Ethanol Nitromethane
Ammonia 1-Nitropropane
Aniline 2-Nitropropane
Benzene 2-Pentanone
1,3 Butadiene
Phenol
2—Butanone Pyridine
Butylamine
Hydrogen Sulfide
Chlorobenzene Styrene
1-Chloro-1-Nitropropane Tetrachloroethylene
Chloroprene Toluene
Cumene Trichloroethylene
Cyclopentadiene
Vinyl Toluene
O-Dichlorobenzene Xylene
P-Dichlorobenzene
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be done
by a properly trained person.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing detection system tests or maintenance.
If UV-absorbing gases may be a factor in a given application,
precautionary measures should be taken. Detectors can
be placed closer to the potential hazard area, and/or
the sensitivity of the detection system can be increased.
Contact the factory for further details.
CAUTION
The UVIR flame detectors are to be installed in
places where the risk of mechanical damages is low.
Substances such as methane, propane, butane, hexane,
camphor, and octane are not UV absorbing.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
Absorption of infrared radiation in the range of 4.2 to 4.7
microns is not a significant problem with most organic
vapors, with the exception of those compounds that
have triple bonds such as acetylene, nitriles, silane, or
isocyanates. Carbon dioxide concentrations higher than
normally present in the atmosphere can also cause
substantial loss of fire detection sensitivity.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.
ATTENTION
The source tube is a flame-sealed gas tube
containing Neon, Hydrogen, and a trace amount
of Krypton 85 (Kr85), a radioactive material. The
total volume of gas within the tube is 0.6 ml per
tube, making the gas mixture inside the tube
nonflammable. If the gas envelope is broken, it
will not produce a flammable mixture, and the gas
immediately disperses into the air and is unlikely
to present any type of hazard. Krypton gas and its
radioactive isotope are inert and are not absorbed
by the body. No special handling measure or
personal protection equipment is needed for the
UVIR detectors.
9.1
6
95-8547
INSTALLATION
NOTE
The recommended lubricant for threads and
O-rings is a silicone free grease (p/n 005003001) available from Det-Tronics. Under no
circumstances should a lubricant containing
silicone be used.
•
Dense fog, rain, as well as certain gases and vapors
(see Table 2) can absorb UV and IR radiation and
reduce the sensitivity of the detector.
•
If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
•
For ATEX/IECEx installations, the X5200 detector
housing must be electrically connected to earth
ground.
DETECTOR POSITIONING
DETECTOR ORIENTATION
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:
•
Identify all high risk fire ignition sources.
•
Be sure that enough detectors are used to adequately
cover the hazardous area.
•
Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
•
Verify that all detectors in the system are properly
located and positioned so that any fire hazards are
within both the Field of View (FOV) and detection
range of the detector. The Q1201C Laser Aimer
is recommended for establishing the detector’s
FOV. Refer to Appendix A for specific information
regarding detector range and FOV.
•
•
Refer to Figure 2 and ensure that the oi plate will
be oriented as shown when the X5200 is mounted
and sighted. This will ensure proper operation of the
oi system and will also minimize the accumulation of
moisture and contaminants between the oi plate and the
viewing windows.
IMPORTANT
If removed, the oi plate must be securely
tightened to ensure proper operation of
the oi system (40 oz./inches [28.2 N . cm]
recommended).
oi PLATE
The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain (see
Figure 1). The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
IR VIEWING WINDOW
UV VIEWING WINDOW
oi MAGNET
The detector must be mounted on a rigid surface in
a low vibration area.
B2134
DETECTOR STATUS INDICATOR
Figure 2—Front View of the X5200
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
INCORRECT
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
D1974
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon
9.1
7
95-8547
PROTECTION AGAINST MOISTURE DAMAGE
IMPORTANT
A minimum input voltage of 18 Vdc must be
present at the X5200.
It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
operation and is the responsibility of the installer.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures
6 through 10. Consult the factory if not using shielded
cable.
If conduit is used, we recommend installing drains,
according to local codes, at water collection points
to automatically drain accumulated moisture. It is
also recommended to install at least one breather,
according to local codes, at upper locations to provide
ventilation and allow water vapor to escape.
The “B” (pulse output) and “D” (oi driver) leads
from each detector should be shielded from the “B”
and “D” leads of all other detectors to prevent false
alarms resulting from crosstalk between zones. It
is recommended that the “A” and “C” leads also be
shielded to provide maximum immunity to EMI/RFI.
(See Figures 6 to 10.)
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
In applications where the wiring cable is installed in
conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate disconnect
capability must be provided.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are
highly recommended to prevent water ingress in
outdoor applications. Units with M25 threads must use
an IP66/IP67 washer to prevent water ingress.
WARNING
All entries must contain appropriately rated plugs
or fittings. It is required that each plug or fitting
be wrench-tightened to an appropriate installation
torque and meet the minimum thread engagement
requirements per the applicable local standards,
codes, and practices to retain the defined ratings.
PTFE sealant or equivalent should be used on
NPT threads.
WIRING PROCEDURE
Wire Size and Type
The system should be wired according to local codes.
The wire size selected should be based on the number
of detectors connected, the supply voltage, and the
cable length. Typically 16 AWG or 2.5 mm2 shielded
cable is recommended. Wires should be stripped
3/8 inch (9 mm). In some cases where the X5200 is
replacing existing pulse output detectors, the wiring
and power supplies may not be adequate. Consult the
factory for assistance.
4X ø0.42
(1.1)
3.0
(7.6)
IMPORTANT
Devices certified for hazardous locations shall be
installed in accordance with EN/IEC 60079-14 and
NEC 505.
CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.
4.0
(10.2)
13.1
(33.4)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
3.0
(7.6)
4.0
(10.2)
10.6
(27.0)
E2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
9.1
8
95-8547
Detector Installation
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 inch or M10 bolts with a length
of at least 1 inch (25 mm). The surface must also have
sufficient capacity to hold the detector and mounting arm
weights (see “Specifications” section). Refer to the Q9033
Mounting Arm manual, number 95-8686, for additional
installation information. See Figure 3 for dimensions.
Detector Wiring
IMPORTANT
If installing an X5200 in place of an existing
detector, be sure to move the “A” Lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source. Do not apply 290 Vdc to
the X5200.
1. Make field connections following local ordinances
and guidelines in this manual.
Figure 4—X5200 Terminal Block
Figure 4 shows the wiring terminal strip located
inside the detector’s integral junction box.
Figure 5 shows the wiring terminal identification for
the X5200 detector with pulse output.
9
19
8
18
PULSE OUT
29
SPARE
28
SPARE
Leave the shield open at the detector end and
permanently isolate it from accidental contact with
the case and/or other conductors. At the controller/
fire panel end, connect the shield and power minus
(–) to chassis (earth) ground either directly or
through a 0.47 µF 400 Volt non-polarized capacitor
(not supplied). (Refer to Figures 6 through 10.)
7
COM FIRE
17
COM FIRE
27
6
N.O. FIRE
16
N.O. FIRE
26
5
N.C. FIRE
15
N.C. FIRE
25
4
COM FAULT
14
COM FAULT
24
RS-485 A
3
N.O. FAULT
13
N.O. FAULT
23
RS-485 B
Figures 11 and 12 provide examples of typical
installations with a X5200 wired to a fire alarm
panel.
2
+ Vin
12
+ Vin
22
MAN Oi
1
– Vin
11
– Vin
21
– Vin
D2070
Figure 13 shows an EOL resistor installed within the
integral wiring compartment of the detector (refer to
“EOL Resistors” for details).
Figure 5—X5200 Pulse Wiring Terminal Identification
2. Check all field wiring to be sure that the proper
connections have been made.
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
3. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
9.1
9
95-8547
NOTE: DO NOT CONNECT THE X5200 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X5200
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
DETECTOR 5
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-9
J1-17
DETECTOR 6
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-10
J1-18
DETECTOR 7
X5200
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
–
2
+
–
3
J2
R7404 CONTROLLER
} 10 TO 38 VDC
ZONE OUTPUT 1
33
ZONE OUTPUT 2
34
(A) +290 VDC
ZONE OUTPUT 3
35
4
B - INPUT 1
ZONE OUTPUT 4
36
5
B - INPUT 2
ZONE OUTPUT 5
37
6
B - INPUT 3
ZONE OUTPUT 6
38
7
B - INPUT 4
ZONE OUTPUT 7
39
8
B - INPUT 5
ZONE OUTPUT 8
40
9
B - INPUT 6
FIRE LOGIC “A”
41
10
B - INPUT 7
FIRE LOGIC “B”
42
11
B - INPUT 8
ALARM OUTPUT
43
12
D1-1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D1-2 oi DRIVER
OUTPUTS INHIBITED
45
14
D1-3 oi DRIVER
FAULT OUTPUT
46
15
D1-4 oi DRIVER
EXTERNAL ACCEPT
47
16
D1-5 oi DRIVER
STATUS & DET. OUTPUT S1
48
17
D1-6 oi DRIVER
STATUS & DET. OUTPUT S2
49
18
D1-7 oi DRIVER
STATUS & DET. OUTPUT S3
50
19
D1-8 oi DRIVER
STATUS & DET. OUTPUT S4
51
20
D2-1 oi DRIVER
STATUS & DET. OUTPUT S5
52
21
D2-2 oi DRIVER
STATUS & DET. OUTPUT S6
53
22
D2-3 oi DRIVER
STATUS & DET. OUTPUT S7
54
23
D2-4 oi DRIVER
STATUS & DET. OUTPUT S8
55
24
D2-5 oi DRIVER
DATA BUS 0
56
25
D2-6 oi DRIVER
DATA BUS 1
57
26
D2-7 oi DRIVER
DATA BUS 2
58
27
D2-8 oi DRIVER
DATA BUS 3
59
28
DMA OUT AVAILABLE
DATA BUS 4
60
29
DMA OUT
DATA BUS 5
61
30
DMA IN
DATA BUS 6
62
31
DATA STROBE
DATA BUS 7
63
32
DMA IN AVAILABLE
CHASSIS (EARTH) GND
64
A2143
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X5200
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
62
63
0.47 µF / 400 VDC
NON-POLARIZED
64
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 6—A Typical System, X5200 Detectors Wired to R7404 Controller
9.1
10
95-8547
NOTE: DO NOT CONNECT THE X5200 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
X5200
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
#2
#1
#19
#22
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+290 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
STATUS & DET. OUTPUT S3
50
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
DATA BUS 5
61
DATA BUS 6
62
DATA BUS 7
63
17
18
#2
#1
#19
#22
21
22
23
24
25
J1-9
J1-17
26
27
28
#2
#1
#19
#22
#2
#1
#19
#22
29
30
J1-10
J1-18
DETECTOR 7
X5200
1
20
DETECTOR 6
X5200
J1
+
19
DETECTOR 5
X5200
24
VDC
31
32
J2
R7404 STAR LOGIC CONTROLLER
D7 oi DRIVER
D8 oi DRIVER
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED
EARTH GROUND
64
A2144
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X5200
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
62
63
0.47 µF / 400 VDC
NON-POLARIZED
64
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 7—A Typical System, X5200 Detectors Wired to R7404 Star Logic Controller
9.1
11
95-8547
X5200
#2
#1
#19
#22
#2
#1
#19
#22
DETECTOR 1
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-5
J1-13
DETECTOR 2
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-6
J1-14
DETECTOR 3
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-7
J1-15
DETECTOR 4
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J1-8
J1-16
+24 VDC
ZONE OUTPUT 1
33
–
2
CIRCUIT GROUND
ZONE OUTPUT 2
34
3
+24 VDC
ZONE OUTPUT 3
35
4
B1 - INPUT SIGNAL
ZONE OUTPUT 4
36
5
B2 - INPUT SIGNAL
ZONE OUTPUT 5
37
6
B3 - INPUT SIGNAL
ZONE OUTPUT 6
38
7
B4 - INPUT SIGNAL
ZONE OUTPUT 7
39
8
B5 - INPUT SIGNAL
ZONE OUTPUT 8
40
9
B6 - INPUT SIGNAL
FIRE LOGIC “A”
41
10
B7 - INPUT SIGNAL
FIRE LOGIC “B”
42
11
B8 - INPUT SIGNAL
ALARM OUTPUT
43
12
D1 oi DRIVER
EXTERNAL RESET/INHIBIT
44
13
D2 oi DRIVER
OUTPUTS INHIBITED
45
14
D3 oi DRIVER
FAULT OUTPUT
46
15
D4 oi DRIVER
EXTERNAL ACCEPT
47
16
D5 oi DRIVER
STATUS & DET. OUTPUT S1
48
D6 oi DRIVER
STATUS & DET. OUTPUT S2
49
STATUS & DET. OUTPUT S3
50
STATUS & DET. OUTPUT S4
51
STATUS & DET. OUTPUT S5
52
STATUS & DET. OUTPUT S6
53
STATUS & DET. OUTPUT S7
54
STATUS & DET. OUTPUT S8
55
DATA BUS 0
56
DATA BUS 1
57
DATA BUS 2
58
DATA BUS 3
59
DATA BUS 4
60
DATA BUS 5
61
DATA BUS 6
62
DATA BUS 7
63
17
18
#2
#1
#19
#22
#2
#1
#19
#22
21
22
23
24
25
J1-9
J1-17
26
27
28
#2
#1
#19
#22
#2
#1
#19
#22
29
30
J1-10
J1-18
DETECTOR 7
X5200
1
20
DETECTOR 6
X5200
J1
+
19
DETECTOR 5
X5200
24
VDC
31
32
J2
R7494 CONTROLLER
D7 oi DRIVER
D8 oi DRIVER
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED
EARTH GROUND
64
A2145
#2
#1
#19
#22
#2
#1
#19
#22
J1-11
J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X5200
WITH PULSE OUTPUT.
TERMINAL NO.
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
FUNCTION
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
62
63
0.47 µF / 400 VDC
NON-POLARIZED
64
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 8—A Typical System, X5200 Detectors Wired to R7494 Controller
9.1
12
95-8547
R7495 CONTROLLER
(NOT FM APPROVED)
X5200
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X5200
#2
#1
#19
#22
#2
#1
#19
#22
33
34
J2-45
J2-37
DETECTOR 3
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-46
J2-38
DETECTOR 4
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
DETECTOR 6
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-50
J2-42
DETECTOR 8
47
B5
48
B6
49
B7
50
B8
A2146
TO J1-2
TERMINAL IDENTIFICATION FOR X5200
WITH PULSE OUTPUT.
TERMINAL NO.
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
FUNCTION
3
4
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
0.47 µF / 400 VDC
NON-POLARIZED
5
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 9—A Typical System, X5200 Detectors Wired to R7495 Controller
9.1
13
95-8547
NOTE: DO NOT CONNECT THE X5200 "A" LEAD (#2/12) TO
TERMINAL J2-34 (290 VDC).
R7405 CONTROLLER
(NOT FM APPROVED)
X5200
#2
#1
#19
#22
#2
#1
#19
#22
24
VDC
J1
+
1
+24 VDC
–
2
GROUND
3
DETECTOR 1
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-44
J2-36
4
J2
5
31
32
DETECTOR 2
X5200
#2
#1
#19
#22
#2
#1
#19
#22
33
J2-45
J2-37
DETECTOR 3
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-46
J2-38
DETECTOR 4
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-47
J2-39
DETECTOR 5
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-48
J2-40
34
+290 VDC
35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
47
B5
48
B6
49
B7
50
B8
DETECTOR 6
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-49
J2-41
DETECTOR 7
X5200
#2
#1
#19
#22
#2
#1
#19
#22
J2-50
J2-42
DETECTOR 8
A2147
TO J1-2
TERMINAL IDENTIFICATION FOR X5200
WITH PULSE OUTPUT.
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi ("D" LEAD)
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.
3
4
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
0.47 µF / 400 VDC
NON-POLARIZED
5
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
Figure 10—A Typical System, X5200 Detectors Wired to R7405 Controller
9.1
14
95-8547
X5200 DETECTOR
FIRE ALARM PANEL
9
19
8
18
COM FIRE2
7
ALARM
N.O. FAULT1
3
+
24 VDC
+ Vin
2
–
26
END OF
LINE DEVICE 4
25
14
RS-485 A
24
13
RS-485 B
23
MAN Oi
22
12
– Vin
1
28
27
15
COM FAULT1
4
29
SPARE
16
N.C. FIRE2
5
SPARE
17
N.O. FIRE2
6
PULSE OUT
– Vin
11
21
oi TEST 3
WIRING NOTES:
C2148
1
IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2
ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3
INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
4
REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5
PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6
SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 11—Ex d Wiring Option
X5200 DETECTOR
FIRE ALARM PANEL
9
19
8
ALARM
EOL
DEVICE 4
7
ALARM
6
5
4
3
+
24 VDC
2
–
1
PULSE OUT
18
COM FIRE2
N.O. FIRE2
N.C. FIRE2
COM FAULT1
N.O. FAULT1
+ Vin
– Vin
SPARE
29
SPARE
28
17
27
16
26
15
25
14
RS-485 A
24
13
RS-485 B
23
12
MAN Oi
22
11
– Vin
21
oi TEST 3
C2149
WIRING NOTES:
1
IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2
ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3
INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
4
EOL RESISTOR SUPPLIED BY PANEL.
5
PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6
SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure 12—Ex e Wiring Option
9.1
15
95-8547
STARTUP PROCEDURE
EOL RESISTORS
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
by EOL resistors, observe the following guidelines when
installing the resistors.
When installation of the equipment is complete, apply
power and allow 20 to 30 minutes for the detector’s
heated optics to reach equilibrium. Then perform one or
more of the following tests:
1. Required EOL resistor power rating must be 5 watts
minimum.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies to
ATEX/IECEx installations only.
•
Man oi Test — Tests detector output and wiring,
without generating a fire alarm.
•
Count Test Mode — Measures actual detector output
to controller (cps), without generating a fire alarm.
•
Fire Alarm Test — For complete system test including
detector relays. Generates fire alarm output.
MANUAL oi TEST (Output to Controller)
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
1. Place the keylock switch in the TEST position.
2. Press the SELECT button to display the desired
zone on the ZONE indicator on the front panel of the
controller.
3. Bend the leads and install the EOL resistor as shown
in Figure 13.
3/8 INCH (10 MM) GAP MINIMUM
3. Press and hold the TEST button. The ZONE OUTPUT
LED for the tested zone flashes and the SYSTEM
STATUS display indicates a “6” (fire condition) if the
test is successful.
4. Release the TEST button. The ZONE OUTPUT LED
for the tested zone should remain on steadily.
5. Return to step 2 to test the next detector.
If the system responds differently than indicated above,
proceed with the count test for the problem zone to verify
detector and wiring operation.
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
COUNT TEST MODE (Output to Controller)
When in the Count Test mode, the frequency of the digital
pulses from the detector is displayed on the ZONE
and DETECTOR indicators on the controller faceplate.
The Count Test mode may be used to check the signal
(cps) from a test fire or false alarm source. This can be
useful during system set-up for sensitivity and time delay
settings. This test is performed in the following manner:
Figure 13—EOL Resistor Installation
4. Maintain a 3/8 inch (10 mm) minimum gap between
the resistor body and the terminal block or any other
neighboring parts.
1. Place the keylock switch in the TEST position.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused
apertures shall be closed with suitable blanking
elements.
9.1
2. Simultaneously press and release the SELECT and
TEST buttons. The Status display will change from
a “1” to an “8” indicating that the controller is in the
Count Test mode of operation.
16
95-8547
TROUBLESHOOTING
3. Press the SELECT button until the desired zone is
displayed on the ZONE indicator on the controller
front panel.
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
4. Press and hold the TEST button. The DETECTOR/
ZONE display indicates the counts per second (cps)
received from the detector. If the counts per second
exceeds 99, the FIRE LOGIC LEDs are illuminated to
indicate that the number shown on the display must
be multiplied by 10. The normal reading for an oi
test is 80 to 110 cps. For a live fire test, 270 - 330
cps will be generated.
1. Disable any extinguishing
connected to the unit.
equipment
that
is
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
A zero reading may indicate a dirty window, oi problem,
faulty detector, or defective wiring.
3. Check input power to the unit.
Release the TEST button, the ZONE and DETECTOR
display should drop to a reading of 0 to 1 counts per
second.
4. Check system and detector logs.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
FIRE ALARM TEST (Pulse Output to Fire Alarm Panel)
1. Disable any extinguishing equipment that is
connected to the system.
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check
for high levels of background UV or IR radiation
by covering the detector with the factory supplied
cover or aluminum foil. If the fault condition clears,
extreme background UV or IR radiation is present.
Re-adjust the view of the detector away from the UV
or IR source or relocate the detector.
2. Apply input power to the system.
3. Initiate a live fire test or a Mag oi test. (See “Magnetic
oi / Manual oi” under “Optical Integrity” in the
“Description” section of this manual.)
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
If none of these actions corrects the problem, return the
detector to the factory for repair.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Q1201C
Laser Aimer is recommended for this purpose.)
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
6. Enable extinguishing equipment when the test is
complete.
NOTE
For additional troubleshooting guides, refer to the
Flame Inspector Monitor manual, number 95-8581.
9.1
17
95-8547
MAINTENANCE
LOOSEN TWO CAPTIVE SCREWS
IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
GRASP VISOR AND
REMOVE oi PLATE
WARNING
To avoid a potential electrostatic discharge (ESD),
the painted surface of the detector should only be
cleaned with a damp cloth.
C2135
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
Figure 14—oi Plate Removal
oi PLATE REMOVAL AND REPLACEMENT
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X5200 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.
1. Disable any extinguishing equipment that is
connected to the unit.
2. Loosen the two captive screws, then grasp the oi
plate by the visor and remove it from the detector.
See Figure 14.
CLEANING PROCEDURE
3. Install the new (or cleaned) oi plate.
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
4. Recalibrate the detector’s oi system. Refer to the
Inspector Monitor Manual, number 95-8581, for
instructions regarding oi plate replacement and oi
system recalibration.
To clean the windows and oi plate, use the window
cleaner (p/n 001680-001) with a soft cloth, cotton swab,
or tissue, and refer to the following procedure:
CAUTION
Do not replace the oi reflector plate without also
recalibrating the oi system.
1. Disable any extinguishing equipment that is
connected to the unit.
Recalibration of the oi system requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.
PERIODIC CHECKOUT PROCEDURE
A checkout of the system using the Mag oi or Man oi
feature should be performed on a regularly scheduled
basis to ensure that the system is operating properly. To
test the system, perform the “Manual oi Test,” “Count Test
Mode” or “Fire Alarm Test” as described in the “Startup
Procedure” section of this manual.
2. Clean the viewing window and reflective surfaces
of the oi plate using a clean cloth, cotton swab,
or tissue with the window cleaning solution. Use
Isopropyl alcohol for contaminations that the DetTronics window cleaning solution can not remove.
If a fault condition is still indicated after cleaning,
remove and clean the oi plate using the oi Plate
Removal and Replacement procedure.
CLOCK BATTERY
The real time clock has a backup battery that will operate
the clock with no external power for nominally 10 years.
It is recommended that the battery be replaced every
7 years. Return the device to the factory for battery
replacement.
IMPORTANT
When used in extreme environments, the
reflective surface of the detector oi plate may
eventually deteriorate, resulting in reoccurring oi
faults and the need for oi plate replacement.
9.1
18
95-8547
SPECIFICATIONS
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
FEATURES
•
Responds to a fire in the presence of modulated
blackbody radiation (i.e., heaters, ovens, turbines)
without false alarm
•
High speed capability
•
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms)
•
Pulse output for compatibility with controller based
systems
•
Microprocessor controlled heated optics
increased resistance to moisture and ice
•
Automatic, manual or magnetic oi testing
•
Easily replaceable oi plate
•
Fire and fault relays
•
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
•
Operates under adverse weather conditions
•
Mounting arm allows easy sighting
•
Integral wiring compartment for ease of installation
•
Explosion-proof/flame-proof
detector
housing.
Meets FM, CSA, ATEX, and IECEx certification
requirements
•
Class A wiring per NFPA-72 (relay connections).
(Pulse output is equivalent to class A when detectors
are installed in a redundant configuration.)
•
3 year warranty
•
Advanced signal processing (ARC/TDSA)
•
RFI and EMC Directive Compliant
or CSA compliance, the power source must use
F
a SELV (Safety Extra Low Voltage) or Class 2 style
power supply.
POWER CONSUMPTION—
Without heater: 2.8 watts at 24 Vdc nominal;
4.8 watts at 24 Vdc in alarm.
3.1 watts at 30 Vdc nominal;
5.4 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power:
17.5 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
for
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or nonlatching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
9.1
19
95-8547
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 15.
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
VIEWING ANGLE
15°
30°
0°
100
15°
90
30°
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
80
45°
45°
70
60
DETECTION
DISTANCE
(PERCENT)
SHIPPING WEIGHT (Approximate)—
Aluminum:
7 pounds (3.2 kilograms).
Stainless Steel:
14.6 pounds (6.7 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).
50
40
30
20
10
WARRANTY PERIOD—
3 years
A1288
Figure 15—Detector Cone of Vision
CERTIFICATION—
®
RESPONSE TIME—
32 inch methane plume: < 10 seconds.
1 foot x 1 foot n-Heptane: < 15 seconds.
(See Appendix A for details.)
For complete approval details, refer to the appropriate
Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
SOURCE TUBE—
Contains radioactive isotope Krypton 85 (Kr85)
Calculated Activity: 14,800 Becquerels (0.4μCi).
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMENSIONS—
See Figure 16
4.7
(11.9)
B2223
10.2
(25.9)
4.8
(12.2)
Figure 16—Dimensions in Inches (cm)
9.1
20
95-8547
REPLACEMENT PARTS
NOTE
Radioactive material is subject to regulation.
All products containing a source tube meet
the definition of an “excepted package” for
radioactive material under the US Department of
Transportation (DOT), the International Air Transport
Association (IATA), the International Civil Aviation
Organization (ICAO), the International Maritime
Dangerous Goods Code (IMDG), and any other
specific hazardous material regulations from
the country of source of return (TDG, RID, ADR,
etc.). These units are classified as “UN2911,
Radioactive Material, Excepted Package – Article.”
The detector is not designed to be repaired in the field. If
a problem should develop, refer to the “Troubleshooting”
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the
factory for repair.
REPLACEMENT PARTS LIST
Part Number
Description
009208-002
oi Replacement kit for X52/X22/X98 (5 Reflector Plates)
with Inspector Connector and Monitor
Replacement oi Reflector Plate for X52/X22/X98
(requires Inspector Connector to calibrate)
007307-002
DEVICE REPAIR AND RETURN
ORDERING INFORMATION
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure. When items are being returned, please note:
When ordering, please specify:
X5200 UVIR Flame Detector with Pulse Output
Refer to the X5200 Model Matrix below for details
Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel detectors
NOTE
Shipping personnel must be hazmat trained to
pack, mark, and label the return package. Please
consult your country-specific regulations.
ACCESSORIES
Description
000511-029
103881-001
Converter RS485 to RS232
Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
Flame Inspector Monitor CD
Model 475 HART Communicator
Magnet
Magnet and Adapter for Extension Pole
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
Q1120A1001 Paint Shield mounting ring (AL)
Q1201 Laser
Laser Battery, 3V Lithium (laser)
Q1201C1001 X-Series Laser Holder (AL/Plastic)
Q2000A1001 X-Series Weather Shield (AL)
Q9033B Stainless Steel Mounting Arm Assembly is for
aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum
detectors only
Q9033 Collar Attachment
Stop Plug, 3/4” NPT, AL
Stop Plug, 3/4” NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4”NPT, AL
Stop Plug, 20 Pack, 3/4”NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
Window cleaner (6 pack)
O-ring - Rear Cover (Viton) - black or brown
1 oz grease for detectors (silicone-free)
O-ring - Rear Cover (Fluorosilicone) - blue
1 oz PTFE silicone-free lubricant
007819-001
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
007819-002
009207-001
103922-001
102740-002
008082-001
007739-001
007240-001
007818-001
007818-002
009177-001
006097-001
102871-001
007255-001
007338-001
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.
Return all equipment transportation prepaid to the factory
in Minneapolis.
007290-001
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
9.1
Part Number
007290-002
011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
001680-001
107427-040
005003-001
104346-154
012549-001
21
95-8547
X5200 MODEL MATRIX
MODEL DESCRIPTION
X5200
UV/IR Flame Detector
X5200M UV/IR Flame Detector with Molybdenum Tube
TYPE
A
S
MATERIAL
Aluminum
Stainless Steel (316)
TYPE THREAD TYPE
4M
4 PORT, METRIC M25
4N
4 PORT, 3/4" NPT
TYPE
15
OUTPUTS
Relay and Pulse
TYPE
APPROVALS
B
INMETRO (Brazil)
W
FM/CSA/ATEX/IECEx
TYPE
9.1
CLASSIFICATION
1
Division/Zone Ex d e
2
Division/Zone Ex d
22
95-8547
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS, AND OPTIONS DESCRIBE THE FM APPROVAL:
•
Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615.
•
Dust-ignition proof for Class II/III, Div. 1, Groups E, F ,and G (T5) Hazardous (Classified) Locations per FM 3615.
•
Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611.
•
Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
•
Enclosure rating NEMA Type 4X per NEMA 250.
•
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
•
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
CL I, ZONE 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
CL I, ZONE 1, AEx db IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
ZONE 21, AEx tb IIIC T80°C
Tamb –40°C to +75°C
IP66/IP67
The following accessories are FM approved for use with the X5200 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector
was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
The oi test procedure, as described in the “Magnetic oi / Manual oi” section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.
9.1
23
95-8547
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
High Sensitivity UV & IR, Hi Arc, TDSA On, Quick Fire Off
Fuel
n-Heptane
Methane
Size
1 x 1 foot
32 inch plume
Distance feet (m)
50 (15.2)
35 (10.7)
Typical Response Time (seconds)
7
3.5
High Sensitivity UV & IR, Very Hi Arc, TDSA On, Quick Fire Off
Fuel
n-Heptane
Size
1 x 1 foot
Distance feet (m)
50 (15.2)
Typical Response Time (seconds)
8
High Sensitivity UV & IR, Very Hi Arc, TDSA On, Quick Fire On
Fuel
n-Heptane
Size
1 x 1 foot
Distance feet (m)
50 (15.2)
Typical Response Time (seconds)
8
High Sensitivity UV, Low Sens. IR, Hi Arc, TDSA On, Quick Fire Off
Fuel
n-Heptane
Size
1 x 1 foot
Distance feet (m)
15 (4.6)
Typical Response Time (seconds)
9
High Sensitivity UV, Very High Sens. IR, Arc Off, TDSA On, Quick Fire On
Fuel
Size
Distance feet (m)
Typical Response Time (seconds)
Methane
32 inch plume
15 (4.6)
0.12
High Sensitivity UV, Very High Sens. IR, Hi Arc, TDSA On, Quick Fire On
Fuel
Size
Distance feet (m)
Typical Response Time (seconds)
Methane
32 inch plume
15 (4.6)
0.3
Very High Sensitivity UV & IR, Low Arc, TDSA On, Quick Fire On
Fuel
Size
Distance feet (m)
Typical Response Time (seconds)
n-Heptane
Methane
1 x 1 foot
32 inch plume
85 (25.9)
65 (19.8)
14
5
High Sensitivity UV, Very High Sensitivity IR, Hi Arc, TDSA On, Quick Fire Off
Fuel
Size
Distance feet (m)
Typical Response Time (seconds)
n-Heptane
Methane
1 x 1 foot
32 inch plume
60 (18.3)
65 (19.8)
6
9
Medium Sensitivity UV, High Sensitivity IR, Hi Arc, TDSA On, Quick Fire On
Fuel
Size
Distance feet (m)
Typical Response Time (seconds)
n-Heptane
Methane
1 x 1 foot
32 inch plume
50 (15.2)
60 (18.3)
5
5
9.1
24
95-8547
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
High Sensitivity, Hi Arc, TDSA On, Quick Fire Off
False Alarm Source
Sunlight, direct, modulated/unmodulated
Sunlight, reflected, modulated/unmodulated
70 w sodium vapor lamp, unmodulated
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response Time
(seconds)
—
2 inch dia Heptane
10 (3)
< 30
—
2 inch dia Heptane
10 (3)
< 30
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
70 w sodium vapor lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
250 w mercury vapor lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
250 w mercury vapor lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
300 w incandescent lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
4
300 w incandescent lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
3
500 w shielded quartz halogen lamp, unmodulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
500 w shielded quartz halogen lamp, modulated
5 (1.5)
2 inch dia Heptane
5 (1.5)
2
1500 w electric quartz heater, unmodulated
10 (3)
2 inch dia Heptane
5 (1.5)
3
1500 w electric quartz heater, modulated
10 (3)
2 inch dia Heptane
3 (0.9)
11
Two 34 w fluorescent lamps, unmodulated
3 (0.9)
2 inch dia Heptane
10 (3)
3
Two 34 w fluorescent lamps, modulated
3 (0.9)
2 inch dia Heptane
10 (3)
5
Arc welding
15 (4.6)
2 inch dia Heptane
5 (1.5)
N/A
FALSE ALARM IMMUNITY
High Sensitivity, Hi Arc, TDSA On, Quick Fire Off
False Alarm Source
Sunlight, direct, reflected
Vibration
Arc welding
Distance feet (m)
Modulated Response
Unmodulated Response
—
No alarm
No alarm
N/A
No alarm
No alarm
15 (4.6)
No alarm
No alarm
70 w sodium vapor lamp
3 (0.9)
No alarm
No alarm
250 w mercury vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric quartz heater
10 (3)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
9.1
25
95-8547
FM Approval and Performance Report – Continued
FIELD OF VIEW
High Sensitivity UV & IR, Hi Arc, TDSA On, Quick Fire Off
Fuel
Size
n-Heptane
1 x 1 foot
Methane
32 inch plume
Distance
feet (m)
25
(7.6)
17.5
(5.3)
Horizontal
(degrees)
+45
–45
+45
–45
Typical Horz. Response
Time (seconds)
5
8
3
4
Vertical
(degrees)
+45
–30
+45
–30
Typical Vert. Response
Time (seconds)
4
8
4
4
Vertical
(degrees)
+45
–30
Typical Vert. Response
Time (seconds)
13
6
Vertical
(degrees)
+45
–30
Typical Vert. Response
Time (seconds)
9
6
High Sensitivity UV & IR, Very Hi Arc, TDSA On, Quick Fire On
Fuel
Size
n-Heptane
1 x 1 foot
Distance
feet (m)
25
(7.6)
Horizontal
(degrees)
+45
–45
Typical Horz. Response
Time (seconds)
12
9
High Sensitivity UV, Low Sensitivity IR, Hi Arc, TDSA On, Quick Fire Off
Fuel
Size
n-Heptane
1 x 1 foot
Distance
feet (m)
7.5
(2.2)
Horizontal
(degrees)
+45
–45
Typical Horz. Response
Time (seconds)
6
6
High Sensitivity UV, Very High Sensitivity IR, Arc Off, TDSA On, Quick Fire On
Fuel
Size
Methane
32 inch plume
Distance
feet (m)
7.5
(2.2)
Horizontal
(degrees)
+45
–45
Typical Horz. Response
Time (seconds)
0.9
0.2
Vertical
(degrees)
+45
–30
Typical Vert. Response
Time (seconds)
0.1
0.1
Vertical
(degrees)
+45
–30
+45
–30
Typical Vert. Response
Time (seconds)
11
13
6
6
Very High Sensitivity UV & IR, Low Arc, TDSA On, Quick Fire On
Fuel
Size
n-Heptane
1 x 1 foot
Methane
32 inch plume
Distance
feet (m)
42.5
(13)
32.5
(9.9)
Horizontal
(degrees)
+45
–45
+45
–45
Typical Horz. Response
Time (seconds)
12
14
5
7
High Sensitivity UV, Very High Sensitivity IR, Hi Arc, TDSA On, Quick Fire Off
Fuel
Size
n-Heptane
1 x 1 foot
Methane
32 inch plume
Distance
feet (m)
30
(9.1)
32.5
(9.9)
Horizontal
(degrees)
+45
–45
+45
–45
Typical Horz. Response
Time (seconds)
8
8
4
5
Vertical
(degrees)
+45
–30
+45
–30
Typical Vert. Response
Time (seconds)
10
7
5
5
Medium Sensitivity UV, High Sensitivity IR, Hi Arc, TDSA On, Quick Fire On
Fuel
Size
n-Heptane
1 x 1 foot
Methane
32 inch plume
9.1
Distance
feet (m)
25
(7.6)
30
(9.1)
Horizontal
(degrees)
+45
–45
+45
–45
Typical Horz. Response
Time (seconds)
15
7
8
6
26
Vertical
(degrees)
+45
–30
+45
–30
Typical Vert. Response
Time (seconds)
7
9
8
12
95-8547
FM Approval and Performance Report – Continued
MODEL X5200M
The X5200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with
unusual chemistry such as black powder. Consult factory for usage recommendations.
X5200M RESPONSE CHARACTERISTICS
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)
Black Powder
40 grams
10 (3)
0.12
X5200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
False Alarm Source
Sunlight, direct, reflected, modulated & unmodulated
Distance
feet (m)
Fire Source
Distance
feet (m)
Typical Response Time
(seconds)
—
2 inch dia Heptane
10 (3)
< 15
70 w sodium vapor lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
5
70 w sodium vapor lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
<1
250 w vapor lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
11
250 w vapor lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
<1
300 w incandescent lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
7
300 w incandescent lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
6
500 w halogen lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
<1
500 w halogen lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
11
1500 w electric radiant heater, unmodulated
10 (3)
1 x 1 foot n-Heptane
40 (12)
<1
1500 w electric radiant heater, modulated
10 (3)
1 x 1 foot n-Heptane
40 (12)
<1
2-34 w fluorescent lamps , unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
15
2-34 w fluorescent lamps , modulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
<1
X5200M FALSE ALARM IMMUNITY
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Distance
feet (m)
Modulated Response
Unodulated Response
—
No alarm
No alarm
Arc welding
15 (4.6)
No alarm
No alarm
70 w sodium vapor lamp
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
2-34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
False Alarm Source
Sunlight, direct, reflected
X5200M FIELD OF VIEW
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Fuel
Size
Distance
feet (m)
Black Powder
40 grams
5
(1.5)
9.1
Horizontal
(degrees)
+45
–45
Typical Horz. Response
Time (seconds)
Vertical
(degrees)
Typical Horz. Response
Time (seconds)
0.1
0.1
+45
–30
0.1
0.1
27
95-8547
APPENDIX B
CSA APPROVAL
DIVISION CLASSIFICATION:
Ultraviolet Infrared Flame Detector/Controller X5200 series, rated 18-30 Vdc, 2.8 Watts to 17.5 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);
Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3);
Class III; Enclosure NEMA/Type 4X;
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91
–
General requirements - Canadian Electrical Code, Part II
CAN/CSA-C22.2 No. 25-1966
–
Enclosures for use in Class II Groups E, F & G Hazardous Locations
CAN/CSA-C22.2 No. 30-M1986
–
Explosion-Proof Enclosures for Use in Class I Hazardous Locations
CAN/CSA-C22.2 No. 94-M91
–
Special Purpose Enclosures
CAN/CSA-C22.2 No. 142-M1987
–
Process Control Equipment
CAN/CSA-C22.2 No. 213-M1987
–
Nonincendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex db eb IIC T6...T5
T6 (Tamb = -50°C to +60°C)
T5 (Tamb = -50°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -50°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
Ex db IIC T6...T5
T6 (Tamb = -55°C to +60°C)
T5 (Tamb = -55°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -55°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0: 2007
–
Electrical apparatus for explosive atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1: 2011
–
Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7: 2012
–
Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
CAN/CSA-C22.2 No. 60079-31: 2012
–
Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure "t"
The following accessories are CSA approved for use with the X5200 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
9.1
28
95-8547
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 02 ATEX 132195X
Increased Safety Model
Flameproof Model
II 2 G
II 2 G
0539
II 2 D
II 2 D
Ex db eb IIC T6...T5
Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
0539
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-31: 2009
EN 60529: 1991+A1:2000+A2:2013
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X5200UVIR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d,” or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e.” They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Ultraviolet Infrared (UVIR) flame detector type X5200 must be electrically connected to earth
ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Ultraviolet Infrared (UVIR) flame detector type X5200 is to be installed in places where there is a low risk of
mechanical damage.
•
See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of this manual for
more information on conducting repairs.
9.1
29
95-8547
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.
NOTE
For ATEX installations, the X5200 detector housing must be electrically connected to earth ground.
The following accessories are ATEX approved for use with the X5200 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
9.1
30
95-8547
APPENDIX D
IECEx APPROVAL
CERTIFICATE OF CONFORMITY
IECEx ULD 06.0018X
Ex db eb IIC T6...T5 Ex db IIC T6...T5
Ex tb IIIC T80°C
Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C)
or
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb =–55°C to +75°C)
IP66/IP67. IP66/IP67.
Compliance with:
IEC 60079-0: 2011, Ed. 6
IEC 60079-1: 2014, Ed. 7
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
IEC 60529: 2013, Ed. 2.2
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X5200UVIR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d,” or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e.” They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Ultraviolet Infrared (UVIR) flame detector type X5200 must be electrically connected to earth
ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
•
The EOL resistor can only be used within the flameproof terminal compartment.
•
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
•
The Ultraviolet Infrared (UVIR) flame detector type X5200 is to be installed in places where there is a low risk of
mechanical damage.
•
See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge.
•
Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of this manual for
more information on conducting repairs.
The following accessories are IECEx approved for use with the X5200 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
9.1
31
95-8547
95-8547
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2016 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.