Honeywell Searchline Excel Infrared Gas Detectors Installation and Operation Manual
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Technical Handbook
Searchline Excel
Infrared Gas Detectors
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
SAFETY
Ensure that you read and understand these instructions BEFORE operating the equipment.
Please pay particular attention to the Safety Warnings.
WARNINGS
1.
The Searchline Excel gas detector is certified for and intended for use in potentially
hazardous areas. Install and use the Searchline Excel gas detector in accordance
with the latest regulations.
2.
For installations in the UK, the Code of Practice SELECTION, INSTALLATION
AND MAINTENANCE OF ELECTRICAL APPARATUS FOR USE IN
POTENTIALLY EXPLOSIVE ATMOSPHERES should be strictly observed. General
recommendations are given in BS EN 60079-14:2008 & IEC 60079-14:2007. Refer
to BS EN 60079-29-2:2007 & IEC 60079-29-2:2007 in the UK or the appropriate
local or national regulations.
3.
For installations in North America, the national Electrical Code (NFPA 70 - 1990) or
later issues should be strictly observed.
4.
Elsewhere, the appropriate local or national regulations should be used.
5.
The Searchline Excel gas detector must be properly earthed to protect against
electrical shock and minimise electrical interference. For electrical installation design
considerations refer to Section 3.
6. Operators must be fully aware of the action to be taken if the gas concentration
exceeds an alarm level.
7. Dismantling or repair of equipment should be carried out in the safe area only.
8.
Test gases may be toxic and/or combustible. Refer to Material Safety Sheets for
appropriate warnings.
9.
Do not drill holes in any housing as this will invalidate the explosion protection.
10. In order to maintain electrical safety, the unit must not be operated in atmospheres
with more than 21% oxygen.
11. Ensure that the bolts which secure flameproof enclosures are fully tightened. The
securing bolts used are made from a special certified grade of steel. Only bolts
supplied by Honeywell Analytics should be fitted for this purpose.
12. Do not open the enclosure in the presence of an explosive atmosphere.
13. The transmitter unit contains high voltages when operational. These are discharged
when the unit is removed from its enclosure.
14. The conduit and cable glands fitted to Searchline Excel should not be modified. If,
however, it becomes necessary to make modifications they must comply with the
relevant national Codes of Practice.
15. The energy emitted by the Searchline Excel is less than 20mW/mm2.
2
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
SAFETY
CAUTIONS
1.
Use only approved parts and accessories with the Searchline Excel gas detector.
2.
To maintain safety standards, commissioning and regular maintenance of the Searchline
Excel gas detector should only be performed by qualified personnel.
IMPORTANT NOTICES
1.
Honeywell Analytics Limited can take no responsibility for installation and/or use of its
equipment if this is not done in accordance with the appropriate issue and/or amendment
of the manual.
2. The user of this manual should ensure that it is appropriate in all details to the exact
equipment to be installed and/or operated. If in doubt, the user should contact Honeywell
Analytics Limited for advice.
3.
Effect of explosive atmosphere on materials.
Searchline Excel is made from materials which exhibit good resistance to corrosive and
solvative substances. The Exd enclosures are made from 316 stainless steel and the
explosion protected windows are made from toughened soda lime glass. Honeywell
Analytics are not aware of any significant effects of explosive atmospheres upon these
materials. Contact Honeywell Analytics or one of their agents for specific queries.
Honeywell Analytics Limited reserve the right to change or revise the information supplied in
this document without notice and without obligation to notify any person or organisation of such
revision or change.
If further details are required that do not appear in this manual, contact Honeywell Analytics
Limited or one of their agents.
3
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
CONTENTS
SAFETY 2
1. INTRODUCTION
6
2. OVERVIEW
2.1 Introduction
2.2 Transmitter
2.3 Receiver
2.4 Adjustable Mountings
8
8
9
10
12
3. INSTALLATION AND OPERATION
3.1 Introduction
3.2 Siting and Mounting
3.3 Electrical connections
3.4 Power supply
3.5 Unpacking
3.6 Installation procedure
3.7 Alignment and commissioning
3.8 System Controller calibration
3.9 Installation Checks/Tests
13
13
14
18
23
24
27
33
48
49
4. MAINTENANCE
4.1 Inspection and Cleaning
4.2 Functional Testing (Plastic Test Filters)
4.3 Calibration Check using the Gassing Cell
4.4 Display Gas Reading
4.5 Alignment Telescope
4.6 Operational Maintenance (FM)
55
55
55
57
58
59
59
5. PROBLEM SOLVING
61
6. SPECIFICATIONS
6.1 System
6.2 Detectable gases
66
66
67
7. CERTIFICATION
7.1 General
7.2 ATEX & IECEx
7.3 UL
7.4 CSA/FM
68
68
69
73
76
4
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
CONTENTS
APPENDIX A - HANDHELD INTERROGATOR
A.1 Introduction
A.2 Overview
A.3 Connection to System
A.4 Basic User Tasks
A.5 Menus
A.6 Problem Solving
A.7 specification
81
81
81
82
83
84
98
99
APPENDIX B - GLOSSARY
B.1 Terminology
B.2 Measurement Units
B.3 Abbreviations
101
101
101
102
APPENDIX C - ACCESSORIES & SPARE PARTS
C.1 System Units
C.2 General
103
103
104
5
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
1. INTRODUCTION
Searchline Excel is a hydrocarbon gas detection system that is available in two versions:
•
Searchline Excel Open-Path Gas Detector
•
Searchline Excel Cross-Duct Gas Detector
For information regarding the Cross-Duct Excel contact Honeywell Analytics.
Searchline Excel Open-Path Gas Detector (OPGD) consists of a Transmitter unit that sends an
infrared beam to a Receiver unit up to 200 metres away, and can be located where a flammable
hydrocarbon gas cloud is likely to occur.
The detector operates on the principle of infrared (IR) absorption. Gases absorb light at specific
wavelengths depending on their molecular composition. Hydrocarbon gases absorb in the
infrared region of the spectrum. If a cloud of hydrocarbon gas is present, part of the infrared
light is absorbed by the gas, causing a reduction in the signal received that is proportional to
the amount of gas in the beam.
The Searchline Excel Transmitter unit produces the infrared light, and the Receiver unit features
optical detectors and signal processing electronics. Each unit is housed in a robust stainless
steel housing. The Receiver produces a 4 - 20mA analogue output equivalent to 0 - 5 LEL.m
(Lower Explosive Limit metres) of gas.
NOTE:
THE INFRARED BEAM IS INVISIBLE AND EYE SAFE
Searchline Excel is designed for use in the most demanding environments/applications and
provides a sensitive, fast and reliable response. The sophisticated open-path technology
provides immunity to sunlight and minimises the effects of environmental factors such as rain,
fog, ice, snow and condensation.
The Transmitter and Receiver units incorporate heated optics designed to minimise the build
up of humidity, condensation, snow or ice on the glass windows, that could obscure the optics
in extreme conditions.
The system is microprocessor controlled with integral self-diagnostics and fault finding
facilities.
Local communication between an operator/technician and the gas detector system is made
via an associated Handheld Interrogator that uses the Receiver’s inbuilt RS485 serial link.
The interrogator provides the user with a menu-style interface to select and invoke commands
for commissioning and configuring the system, and for viewing the system state and
measurements.
The interrogator is connected to the Receiver via one of Honeywell Analytics' DX/DVC100
(M) series types of Termination Unit, or via other types of junction box using the optional SHC
Protection Device. The DX/DVC100(M) Termination Units feature an active digital interface
that allows a remotely located control centre to monitor the gas detector's signal output and
perform basic commands using the Modbus Remote Terminal Unit (RTU) protocol over an
RS485 link.
6
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
1. INTRODUCTION
This handbook consists of the following parts:
•
Chapter 1
Introduction
•
Chapter 2
System Description
•
Chapter 3
Installation And Operation
•
Chapter 4
Maintenance
•
Chapter 5
Problem Solving
•
Chapter 6
Specifications
•
Chapter 7
Certification
•
Appendix A
Handheld Interrogator
•
Appendix B
Glossary
•
Appendix C
Accessories & Spare Parts
Information notices
The types of information notices used throughout this handbook are as follows:
WARNING
Indicates hazardous or unsafe practice that could result in severe injury
or death to personnel.
Caution: Indicates hazardous or unsafe practice which could result in minor injury to
personnel, or product or property damage.
Note: Provides useful/helpful/additional information.
If more information beyond the scope of this technical handbook is required please contact
Honeywell Analytics.
Associated Documents
Searchline Excel Open-Path Infrared Gas Detector
Basic Installation Guide
Part No: 2104M0510
Searchline Excel Cross-Duct Infrared Gas Detector
Basic Installation Guide
Part No: 2104M0511
DX100 Series Termination Units Technical Handbook
Part No: 2104M0701
DVC100 (M) MK2 Termination Unit Installation Guide
Part No: 2104M0409
7
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
2. OVERVIEW
2.1
INTRODUCTION
Each type of Searchline Excel gas detector consists of two units, a Transmitter and a Receiver.
This separate Transmitter/Receiver configuration provides the most reliable basis for open path
gas detection.
DVC100(M) MK2 or DX100(M)
(or other junction box)
Mounting plate
Mounting bracket
Honeywell Analytics
Junction Box
00780-A-0100 (or
other junction box)
Pivot block
Receiver
Transmitter
Flexible conduit
Monitored
path
5 - 200 m
8
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
2. OVERVIEW
There are three ranges of Searchline Excel gas detector. These are:
Open-Path
Short Range
Medium Range
Long Range
5 – 40m (15ft – 130ft)
20 – 120m (65ft – 390ft)
120 – 200m (390ft – 650ft)
When designing an installation for Searchline Excel it is important that the correct range of the
gas detector for each path to be monitored is selected and specified.
The Transmitter and Receiver are each mounted upon robust, adjustable mounting brackets.
These brackets bolt to a mounting plate, which is designed to accommodate a variety of junction
boxes, accessories and mechanical mounting configurations. The small size and flexibility of
Searchline Excel and its mounting arrangements are intended to make correct installation
design as simple as possible. Installation details are given in Chapter 3.
2.2
TRANSMITTER
The Searchline Excel Transmitter produces an intense, collimated infrared beam which is
produced by a Xenon arc flashlamp.
The flashlamp’s infrared output is collimated using mirrors which enables a more uniform beam
(no chromatic aberrations) to be produced and hence reduces alignment sensitivity. In order
to prevent annoying visible flashes, the visible emissions from the flashlamp are blocked by a
filter.
The Transmitter’s flashlamp is pulsed at precisely 4Hz, each pulse lasting for approximately
one microsecond. The precise timing and extremely short duration of these pulses give the
Transmitter a very distinctive signature. This distinctive signature makes it easy for the Receiver
to distinguish Searchline Excel Transmitter pulses from both natural and artificial sources of
infrared radiation.
NOTE:
THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
The medium and long range Transmitters contain a higher power flashlamp and larger optics
than the standard short range unit. The resulting infrared beam is many times brighter which
allows for a considerable increase in operating range.
9
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
2. OVERVIEW
160mm (SR)
211 (MR/LR)
Approximately
300mm
291mm (SR)
353 (MR/LR)
417mm (SR)
433 (MR/LR)
The Transmitter window is heated to minimise condensation, frosting and the build up of snow.
During particularly cold operating conditions, the heating of the Transmitter window is increased
to turbo levels. The turbo mode can be disabled if not required.
Electrical connections to the Transmitter are made via wires which run through the protective,
flexible conduit. There are three Transmitter wires, red (+24V), black (0V) and greenIyellow
(GND).
2.3 RECEIVER
The Searchline Excel Receiver collects infrared radiation from the Transmitter and performs
measurements to enable hydrocarbon gases in the beam path to be detected.
Infrared radiation is collected by a single, silicon lens, which is common to both the sample and
reference measurement channels. This radiation is divided by a beamsplitter and fed to two
filtered detectors, sample and reference.
The sample detector input is filtered at wavelengths where strong infrared absorption is exhibited
by the target gas. The reference detector input is filtered at nearby wavelengths, where strong
infrared absorption is not exhibited by the target gas. By calculating the ratio of the sample to
reference signal it is possible to measure the quantity of gas in the beam, whilst compensating
for the effects of rain, fog, dirt etc.
10
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
2. OVERVIEW
160mm
Approximately
300mm
291mm
417mm (SR)
The solid state, photovoltaic detectors used in Searchline Excel provide an exceptional dynamic
range and superb temperature and long term stability. These features contribute strongly to the
solar immunity and stability of Searchline Excel.
The Receiver contains all of the electronics necessary to amplify, condition and process the
signals received by the infrared detectors. The advanced signal processing of Searchline Excel
employs two microprocessors.
One microprocessor, the Digital Signal Processor (DSP), is used to perform the necessary
intensive signal processing calculations.
The other microprocessor, the microcontroller, controls the overall function of the unit and
performs the final calculations to determine the correct gas reading and output state.
The primary output of the Receiver is a signal in the range 4 - 20mA and is available as either
source or sink options. For most applications, the output is calibrated for a range of 0 to 5 LEL.
m. (See Appendix B for the explanation of LEL.m and other terms)
The Receiver also features an RS485 output which is used to communicate with the associated
SHC1 Handheld Interrogator. The SHC1 is used to perform final alignment, commissioning,
functional testing and diagnostic procedures.
The Receiver window is heated to minimise condensation, frosting and the buildup of snow.
The level of heating applied is controlled by the microcontroller and is adjusted from zero to
maximum depending on the window temperature.
Electrical connections to the Receiver are made via wires which run through the protective
flexible conduit. There are six Receiver wires, red (+24V), black (0V), white (4 - 20mA), orange
(RS485 A), blue (RS485 B) and green / yellow (GND).
11
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
2. OVERVIEW
2.4
ADJUSTABLE MOUNTINGS
The adjustable mountings are:
•
Purpose-built for Transmitter and Receiver.
•
Robust.
•
Rigid and stable.
•
Made from stainless steel.
•
Fully adjustable for alignment
Coarse and fine settings in both horizontal and vertical planes.
Adjustment range:
Vertical
±45o
Horizontal
±90o
Alignment details are given in Chapter 3.
Clamp nut
Mounting bracket
adjusting screw (2 off)
Adjustment clamp
lock screw (2 off)
Clamp nut
Pivot block
adjusting screw
Adjustment clamp
lock screw (2 off)
12
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.1 INTRODUCTION
WARNING
The national Code of Practice regarding selection, Installation and maintenance of
electrical apparatus for use in potentially explosive atmospheres must be complied
with at all times.
Searchline Excel has been designed, engineered and customer tested to be the most robust,
reliable Open-Path Gas Detector (OPGD) available to date.
The design and technology employed in Searchline Excel makes it far more resistant to the
adverse effects of the operating environment and non-ideal installation engineering than previous
generations of OPGDs.
With careful consideration of the intended operating environment and the installation design,
the installer/operator can maximise the reliability, availability and performance achieved with
Searchline Excel.
Before designing or specifying an installation for Searchline Excel, it is strongly recommended
that the installation design authority reads all of this chapter and considers how the information
and recommendations provided can be applied to their installation(s).
If you have any queries concerning your installation design, contact Honeywell Analytics or
your local agents.
Honeywell Analytics is committed to ensuring that customers achieve reliable operation of their
Searchline Excel Gas Detectors. For this reason, Searchline Excel should only be installed
by fully trained personnel (trained by Honeywell Analytics or a Honeywell Analytics authorised
trainer).
This training will provide the installer with a clear understanding of the Searchline Excel product
and the associated accessories and tools. It will also provide familiarity with the installation,
alignment and commissioning procedures, plus installation assessment skills to identify potential
problem areas.
For each installation, an installation check sheet should be completed and returned to
Honeywell Analytics or their agents. Details of this check sheet are given at the end of this
chapter.
NOTE:
THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
13
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.2 SITING AND MOUNTING
3.2.1 General
When designing an installation for a Searchline Excel gas detector it is important to give
consideration to where it is to be located, what potential sources of problems may be encountered
in this location and how the unit is to be mounted and supported.
3.2.2 Location for Best Coverage
Guidance on the positioning of gas detectors to provide the best detection coverage is contained
in BS EN 60079-29-2:2007 & IEC 60079-29-2:2007 and other national Codes of Practice. It is
recommended that the installation designer consults these Codes of Practice when determining
where detectors are to be located. In general, the following positions usually provide the best
results:
•
•
•
•
Below potential leak sources for gases that are heavier than air.
Above potential leak sources for gases that are lighter than air.
Near to leak sources, along the expected leak trajectory, taking account of the
prevailing wind direction and any other factors which will influence propagation
of the leak.
Between possible leak sources and any potential sources of ignition.
Location to Maximise Reliability and Availability
Care in choosing the location of Excel detectors can contribute significantly to the overall
reliability and availability.
When locating units, attempt to avoid areas where they may be adversely affected by the
following:
Vibration - Angular vibration of the structure to which Excel units are attached should be kept
to less than +/- 0.5°. Where possible, avoid locations where high levels of vibration will be
directly induced into the mounting structure. If close proximity to significant sources of vibration
is unavoidable, take steps to reduce coupling of this vibration and maximise the rigidity of the
mounting structure.
Intense Heat - Excel is certified and specified for operation in environments up to
+65°C. If sources of intense heat (flarestacks, intense sunlight, etc.) are present, a
sunshade (Part No: 2104B2323) or similar shield should be fitted to the unit to protect it
from excessive heating.
Sources of Heavy Contamination - Avoid locations where high levels of contaminants will
persistently be blown onto the unit’s windows. Potential sources of heavy contamination include
generator/turbine exhausts, flarestacks, drilling equipment, process vents/chimneys etc. If
sources of heavy contamination cannot be avoided, consider fitting extra shielding and/or
providing good access for more routine cleaning.
Snow and Ice in Ambients Below -20°C - The heated optics on Excel units will melt snow or
ice on the windows in ambient temperatures down to approximately -20°C.
14
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Below this temperature, snow or ice blown onto the window will not be melted until the ambient
temperature rises. If long-term, outdoor operation in very cold climates is intended, it is
recommended that extra shielding/covers are employed to prevent snow/ice from being blown
onto the windows and building up.
Note: The heated optics have not been evaluated as part of the performance testing relating
to the FM approval and therefore are not considered part of the performance approval.
Deluge and Flooding - Searchline Excel is rated IP66/67 and as such will not be damaged
by occasional deluge or flooding. However, during such instances the unit will completely lose
its IR signal and will enter the BEAM-BLOCK/FAULT state. Also, when the deluge/flooding
subsides, there is the possibility that contaminants will be left on the windows. Therefore, it
is recommended that Excel units be located away from areas particularly prone to deluge or
flooding.
Areas Prone to Subsidence and Settling - Where possible, it is recommended that Excel units
are not mounted on structures located where problems with subsidence, settling or thawing
of permafrost are known to cause significant movement. If such locations cannot be avoided,
the foundations of the mounting structure should be engineered to minimise any angular
movements.
Areas Prone to Earthquakes - In locations prone to earthquakes, there is a chance that during
or after an earthquake, the units of an Excel gas detector will become misaligned with respect
to each other. Provided that the Excel units do not suffer from direct mechanical impact damage
during an earthquake, they should remain undamaged by such events. Anti-vibration mounts are
unlikely to be of any benefit and are not recommended. After an earthquake it is recommended
that Excel gas detectors are visited and their alignment be checked.
Accidental Impact - Locations where there is a significant likelihood of equipment, personnel
or moving objects accidentally knocking Excel units out of alignment should where possible
be avoided. If such locations cannot be avoided, measures including improved mechanical
protection and warning notices should be considered.
Intense Electromagnetic Fields - Searchline Excel complies with EN61000-6-3:2007 and
EN61000-6-2:2005 (Industrial levels) and as such is well protected from interference by
electromagnetic fields. However, locations in close proximity to radio/radar transmitters, heavy
electrical plant and high voltage power cables may experience field strengths in excess of those
specified in EN61000-6-3:2007 and EN61000-6-2:2005. Where possible, such locations should
be avoided or units should be installed as far as possible from the source of the electromagnetic
field. Measures including additional screening, filtering and transient suppression may also be
of benefit in such locations.
3.2.3 Beam Path
The Transmitter and Receiver units windows should face each other across the area to be
protected and, depending on the range of the Transmitter in use, should be the following
distance apart:
15
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Excel Gas Detector type
Short Range
Medium Range
Long Range
Path length between units
5 - 40m
(15 - 130ft)
20 - 120m
(65 - 390ft)
120 - 200m
(390 - 650ft)
The beam path and immediate surrounds should be kept free of obstructions that might hinder
the free movement of air in the protected area or block the infrared beam. A clear beam path of
20cm diameter or greater is recommended. In particular, for optimum availability, avoid areas
affected by the following.
a.
Steam vents and plumes
b.
Smoke stacks and chimneys
c.
Walkways and personnel areas
d.
Splash and spray, e.g. from moving equipment, cooling towers, etc.
e.
Parking, loading, cranes, vehicle temporary stops, e.g. bus stops,
road junctions, etc.
f.
Vegetation, e.g. shrubs, bushes, branches, etc. - if currently clear, movement
due to weather and future growth or planting must be considered
Note: Where c. and d. cannot be avoided, consider indicating the beam by marking the walkway
or road with paint.
Unit cowl
Telescope
clearance arc
- radius more
than 50cm
Beam
clearance arc
- radius more
than 10cm
Notes:
1.
In order to fit the alignment telescope, used during the alignment process, a clear
accessible arc of at least 50cm radius is required close to the unit’s cowling as shown.
2.
A clear beam path of at least 10cm radius or greater is recommended.
16
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.2.4 Supporting Structure
The Transmitter and Receiver units should be fixed to a stable supporting structure using the
mounting plates supplied.
Note: The maximum movement of the supporting structure under all anticipated operating
conditions must be ±0.5o.
If either unit is to be free standing and not mounted to existing supports or structures, and the height
above the ground is no more than 3m, the supporting structure shown is recommended:
150mm dia. steel pipe,
nominal 6mm wall thickness
Excel mounting
plate
U-bolts
8mm dia.
166mm
centres
Up to
3m
500mm
minimum
500mm
minimum
500mm
minimum
Concrete
foundation
Note: The pipe can be filled with concrete to provide extra robustness if necessary.
3.2.5 Orientation
Searchline Excel is solar immune and therefore there is no need to take account of the sun’s
movement when considering orientation.
When positioning the units do not install them with the optical axis at an angle greater than 45o
to the horizontal. This is to avoid dirt/water buildup on the windows.
17
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.3 ELECTRICAL CONNECTIONS
3.3.1 General
All ranges of Searchline Excel comply with the EMC requirements EN50270. In order to
maintain compliance with these standards it is essential that the electrical installation of Excel
is engineered correctly.
Electrical installation standards vary for different countries, companies and applications and it
is the responsibility of the installation design authority to determine the applicable standards
and ensure compliance with them. When designing electrical installations for Excel, Honeywell
Analytics recommend that the installation design authority considers the following:
a.
The unit cases should not, if possible, be connected to electrically noisy (dirty) metalwork
or conductors. Preferably, the case (internally connected to the green/yellow GND wire)
should be connected to a low noise instrument (clean) earth. See also para e. below. In
order to facilitate electrical isolation of the Searchline Excel from a noisy earth an isolation
kit is supplied. This kit should be fitted as standard unless local regulations forbid this.
b.
The entire length of the field cabling connected to each unit should be fully shielded. This
should be connected to a low noise (clean) earth.
c.
The low noise instrument (clean) earth system should only be connected to safety earth
(usually dirty) at a single point on the entire site/installation. This connection should be
made in such a manner that it does not introduce noise onto the low noise instrument
earth. Star earthing arrangements minimise earth current crosstalk.
d.
The shields of the field cabling should not be connected such that earth loops are
produced, or in a manner that will result in the shields carrying large currents from heavy
plant or equipment.
e.
Ideally, the field cable shield should be connected to the unit’s green/yellow GND wire,
providing a single, continuous earth shield. This connection must not be allowed to
complete an earth loop.
f.
The earth bonding arrangement must ensure that the maximum peak voltage between
the unit case earth and any field cable conductor is less than 350V. Voltages in excess
of this can cause permanent damage to the unit’s RFI protection filters.
g.
The use of a single, screened cable for each gas detector ensures maximum screening
and minimum crosstalk. Cabling arrangements which use a single cable for connecting
a number of field devices compromise screening, increase the potential for crosstalk and
prevent implementation of true star earthing.
h.
Any electrical interference induced onto the 4 - 20mA loop conductors by the installation
must be kept below the levels necessary to comply with the general requirements of
EN 60079-29-1:2007 &, IEC 60079-29-1:2007. In practice, this means that peak noise
currents induced on the current loop should be no greater than ± 0.25mA
j.
The 0V rail of the control card/control system is directly connected to one side of the 4
- 20mA current sensing resistor. Electrical noise on this rail is therefore directly connected
to the 4 - 20mA input. In order to avoid additional noise being induced on the 0V rail, it
should not be commoned with the safety earth/ground, which frequently carries a high
level of electrical noise.
18
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
k.
All electrical equipment connected to the gas detector should comply with EN61000-63:2007 and EN61000-6-2:2005.
l.
The 24V supply should be free from large transients and fluctuations.
m.
The field cabling conductors should have sufficient cross sectional area to ensure that
the minimum supply voltage applied to the gas detector is 18V at a current of 420mA.
This corresponds to a maximum round loop impedance of 14 ohms for a nominal 24V
system supply.
n.
Receivers should not be installed in close proximity to the antennae of high powered
radio, radar and satellite communication equipment.
The following diagrams show typical earth bonding arrangements for various installations.
3.3.2 Receiver Connections via DVC100(M) MK2
The earth bonding arrangement must ensure
that the maximum peak voltage between the unit
case earth and any field cable conductor is less
than 350V. Voltages in excess of this can cause
permanent damage to the unit's RFI protection
filters.
Field Wiring
+24VDC IN (Terminal 1)
0V (Terminal 3)
4-20mA (Terminal 5)
Earth Terminal
MOD BUS Drain (Terminal 9)
MOD BUS A (Terminal 10)
MOD BUS B (Terminal 11)
Excel Receiver
Wiring
Earth Terminal
+24VDC (Red) (Terminal 2)
0V (Black) (Terminal 4)
4-20mA (White) (Terminal 6)
RS485 (A) (Orange) (Terminal 7)
RS485 (B) (Blue) (Terminal 8)
Note: Using metal cable glands will connect the screen of the cable to the Excel Body.
19
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.3.3 Receiver Connections via DX100(M)
CONTROL
CONTROL
CABINET
CABINET
CONNECTIONS
CONNECTIONS
CABLE
CABLESCREEN
SCREEN
The earth bonding arrangement must ensure
that the maximum peak voltage between the unit
case earth and any field cable conductor is less
than 350V. Voltages in excess of this can cause
permanent damage to the unit's RFI protection
filters.
Modbus
(TB1/6)
Modbus
AA
(TB1/6)
Modbus
B (TB1/5)
Modbus
B (TB1/5)
Modbus
ModbusDrain
Drain
CABLE
SCREEN
CABLE SCREEN
+24V(TB2/2)
(TB2/2)
+24V
4-20mA
OUT(TB2/3)
(TB2/3)
4-20mA
OUT
Note: The Dx100(M) is housed in a metal
enclosure.
(TB2/6)
0V0V
(TB2/6)
EXCEL RECEIVER WIRING
INSTRUMENT
INSTRUMENT(CLEAN)
(CLEAN)
EARTHSTAR-POINT
STAR-POINT
EARTH
WHITE(4-20mA)
(4-20mA)TB2/3
TB2/3
WHITE
GREEN/YELLOW
GREEN/YELLOW(EARTH)
(EARTH)
Same
body
and
conduit.
Samepotential
potentialasasExcel
Excel
body
and
conduit
BLACK(0V)
(0V)TB2/5
TB2/5
BLACK
RED(+24Vdc)
(+24Vdc)TB2/1
TB2/1
RED
BLUE(B)
(B)TB1/3
TB1/2
BLUE
ORANGE
ORANGE(A)
(A)TB1/2
TB1/3
SAFETY
/ PROTECTIVE GROUND
SAFETY/PROTECTIVE
GROUND
Where the DX 100(M) is not bonded
Where
thesafety/protective
DX100(M) is not bonded
to a local
earth then
to
local safety/
protective earth
anaexternal
safety/protective
earth
then an external safety / protective
needs to be made as shown.
earth needs to be made as shown.
3.3.4 Transmitter Connections
EXCEL
EXCEL
TRANSMITTER
TRANSMITTER
WIRING
WIRING
CONTROL
CONTROL
CABINET
CABINET
CONNECTIONS
CONNECTIONS
Honeywell Analytics Junction Box
JUNCTION
BOX
00780-A-0100
CABLE
CABLESCREEN
SCREEN
GREEN/YELLOW (EARTH)
(EARTH)
GREEN/YELLOW
Same
potential
Excelbody
bodyand
andconduit
conduit
Same
potential
asasExcel
EARTH
EARTH
+24V
0V
0V
RED (+24V)
BLACK (0V)
INSTRUMENT (CLEAN)
(CLEAN)
INSTRUMENT
EARTH STAR-POINT
STAR-POINT
EARTH
The earth bonding arrangement must ensure
that the maximum peak voltage between the unit
case earth and any field cable conductor is less
than 350V. Voltages in excess of this can cause
permanent damage to the unit's RFI protection
filters.
Note: Using metal cable glands will connect the
screen of the cable to the Excel Body.
20
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.3.5 Remote Installations
For remote or difficult-to-access installations, the DVC100(M) MK2 or DX100(M) can be
positioned in a convenient location by using an intervening junction box (e.g. Hawke/Bartec)
attached to the receiver's mounting plate. Alternatively an SHC Calibrator Connector System
(part number 2104B6250) can be used that enables connection of the SHC1 up to 10 meters
from the receiver.
A maximum cable length of 1km between the unit and the DVC100(M) MK2 or DX100(M) is
permissible (RS485 compliant).
The connections are as follows.
Wiring with DVC100(M) MK2
LOCAL JUNCTION
JUNCTION BOX
BOX
(mounted on Receiver
Recievermounting
mountingplate)
plate)
EXCEL
EXCEL
RECEIVER
RECEIVER
CABLESCREEN
SCREEN
CABLE
GREEN/YELLOW
GREEN / YELLOW (EARTH)
(EARTH)
Same
Samepotential
potentialas
asExcel
Excelbody
body and
and conduit
conduit
ORANGE
(A)
ORANGE (A)
BLUE
BLUE (B)
RED
RED +24V
+24V
WHITE
WHITE(4-20mA)
(4-20mA)
BLACK
BLACK (0V)
DVC100(M) JUNCTION BOX
(mounted in a convenient and accessible position)
DVC100(M) MK2 JUNCTION BOX
(mounted in a convenient and accessible position)
Field Wiring
+24VDC IN (Terminal 1)
0V (Terminal 3)
4-20mA (Terminal 5)
Earth Terminal
MOD BUS Drain (Terminal 9)
MOD BUS A (Terminal 10)
MOD BUS B (Terminal 11)
Excel Receiver
Wiring
The earth bonding arrangement must
ensure that the maximum peak voltage
between the unit case earth and any
field cable conductor is less than 350V.
Voltages in excess of this can cause
permanent damage to the unit's RFI
protection filters.
CABLE SCREEN
SCREEN
Earth Terminal
GREEN/YELLOW
(EARTH)
+24VDC
(Red)
ORANGE
(A)(Terminal
TB1/3 2)
0V (Black)
(Terminal 4)
BLUE
(B) TB1/2
4-20mA
(White)
(Terminal 6)
RED
(+24V)
TB2/1
RS485 (A)
(Orange)TB2/3
(Terminal 7)
WHITE
(4-20mA)
RS485 (B)
(Blue)
(Terminal 8)
BLACK
(0V)
TB2/5
21
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Wiring with DX100(M)
See also DX100 Termination Unit's technical Handbook.
LOCAL JUNCTION BOX
(mounted on Receiver mounting plate)
EXCEL
EXCEL
RECEIVER
RECEIVER
CABLE SCREEN
GREEN/YELLOW (EARTH)
Same potential as Excel body and conduit
Use isolating glands where necessary
ORANGE (A)
BLUE (B)
RED +24V
BLACK (0V)
WHITE (4-20mA)
DX100(M)
JUNCTION
BOXBOX
DX100(M)
JUNCTION
(mounted
in a convenient
and accessible
position)
(mounted
in a convenient
and accessible
position)
CONTROL
CONTROL
CABINET
CABINET
CONNECTIONS
CONNECTIONS
CABLE
CABLESCREEN
SCREEN
Modbus
(TB1/6)
Modbus
AA
(TB1/6)
Modbus
B (TB1/5)
Modbus
B (TB1/5)
Modbus
ModbusDrain
Drain
CABLE
SCREEN
CABLE SCREEN
+24V(TB2/2)
(TB2/2)
+24V
4-20mA
OUT(TB2/3)
(TB2/3)
4-20mA
OUT
(TB2/6)
0V0V
(TB2/6)
INSTRUMENT
INSTRUMENT(CLEAN)
(CLEAN)
EARTHSTAR-POINT
STAR-POINT
EARTH
CABLE SCREEN
SCREEN
CABLE
GREEN/YELLOW (EARTH)
ORANGE (A) TB1/2
The earth bonding arrangement
must ensure that the maximum
peak voltage between the unit
case earth and any field cable
conductor is less than 350V.
Voltages in excess of this can
cause permanent damage to the
unit's RFI protection filters.
BLUE (B) TB1/3
RED
(+24V)TB2/1
TB2/1
RED (+24V)
BLACK
(0V)TB2/5
TB2/5
BLACK (0V)
WHITE
(4-20mA)TB2/3
TB2/3
WHITE (4-20mA)
22
SAFETY
/ PROTECTIVE GROUND
SAFETY/PROTECTIVE
GROUND
Where the DX 100(M) is not bonded
Where
the DX100(M)
is not bonded
to a local
safety/protective
earth then
toan
a local
safety/
protective earthearth
external
safety/protective
then
an
external
safety
protective
needs to be made as /shown.
earth needs to be made as shown.
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.4 POWER SUPPLY
3.4.1 General
The Searchline Excel gas detector is designed to be operated from a nominal 24V DC supply.
The supply voltage at the terminals must be within the range 18 to 32V.
The unit maximum power consumption and cable lengths are as follows:
Maximum Power Maximum Cable Length Maximum Cable Length
Consumption (W)
(m) with 1.5mm2
(m) with 2.5mm2
Unit Type
Conductors (12 ohms/km) Conductors (7.6 ohms/km)
Receiver (All ranges)
8
550
900
SR Transmitter,
(Turbo heating enabled)
5
900
1,400
SR Transmitter,
(Turbo heating disabled)
3.5
1,300
2,000
MR/LR Transmitter,
(Turbo heating enabled)
7.5
600
950
MR/LR Transmitter,
(Turbo heating disabled)
5.5
820
1,300
Notes:
1.
Control room supply voltage assumed to be +24V.
2.
Standard configuration of the Transmitter is with turbo heating enabled.
Terminal sizes: DVC100(M) MK2
DX100(M)
Honeywell Analytics
Junction Box 00780-A-0100
0.5mm2 - 4mm2 (20AWG - 12AWG)
0.5mm2 - 4mm2 (20AWG - 12AWG)
0.5mm2 - 6mm2 (20AWG - 10AWG)
3.4.2 Power Supply Connections - Turbo heating Disabled
When connected as shown in section 3.3.4 Transmitter Connections all ranges of Transmitter
have turbo heating mode enabled.
This means that during conditions of low ambient temperature, additional heating power is
applied to the unit’s window to minimise condensation, frosting and snow buildup.
If the application/installation does not require turbo heating, reduced power consumption can
be achieved by disabling this mode.
The turbo heating is disabled by reversing the power supply connections to the Transmitter as
shown in the following diagram. All other connections remain the same.
23
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
EXCEL
EXCEL
TRANSMITTER
TRANSMITTER
WIRING
WIRING
CONTROL
CONTROL
CABINET
CABINET
CONNECTIONS
CONNECTIONS
Honeywell Analytics Junction Box
part JUNCTION
number 00780-A-0100
BOX
CABLE
CABLESCREEN
SCREEN
GREEN/YELLOW
GREEN/YELLOW (EARTH)
(EARTH)
Same
Samepotential
potentialas
asExcel
Excelbody
body and
and conduit
conduit
EARTH
EARTH
+24V
+24V
0V
0V
BLACK
BLACK(0V)
(0V)
RED
RED(+24V)
(+24V)
Shows wires reversed to
disable turbo heating
INSTRUMENT (CLEAN)
(CLEAN)
INSTRUMENT
EARTHSTAR-POINT
STAR-POINT
EARTH
The earth bonding arrangement must ensure that the maximum peak voltage between the
unit case earth and any field cable conductor is less than 350V. Voltages in excess of this
can cause permanent damage to the unit's RFI protection filters.
Notes:
1.
Only Transmitters have turbo mode heating which can be disabled. The Receiver uses
proportional heating, which cannot be disabled.
2.
Even with turbo mode heating disabled the Transmitter window still receives standard
levels of heating.
3.
Do not reverse the Receiver power supply connections. This will not damage the unit,
but the unit will not function.
3.5 UNPACKING
(1)
Carefully unpack the equipment, observing any instructions that may be printed on or
contained within the packaging.
(2)
Check the contents for damage and against the packing note for deficiencies.
In the event of damage or loss in transit, notify the carrier and Honeywell Analytics or
your local agent immediately.
The gas detector consists of the following items:
Where alternative component sizes are given the size depends on the version of unit,
i.e.mid/long range version or short range version.
1 x Receiver Unit
25
24
1 x Transmitter Unit
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
2 x Mounting Plates
2 x Mounting Brackets
(with grub screws)
2 x Pivot Blocks
(with grub screws)
4 x Adjustment Clamps
(with grub screws)
4 x Nuts
6 x Mounting Bracket
Fixing Bolts , Internal Lock
Washers and Plain Washers
(M10 or M12)
8 x Junction box Mounting Bolts
2 x Isolation Kits
4 x Spring Washers (M12 or M16)
25
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Se
arc
hli
ne
Ex
basic installation guide
ce
l
NS
SIO
EN
DIM
IT
UN:
0
0
4
.1
5
3
)
(1
idth (1
m
in
W 1 in
m
0
.9
5.5 )
52
)
(1
m
t:5
m
m igh
m
in
8
70
He )
.9
(2
:5 h
m
m pth wit 3in
t
.6
Deigh 10
O2
r:
e
o
H ns
ith 0
4
) w
se
m in (1
m 1
82
(2 d5.5
3in fitte
50
)
.1
(1
m
11 sor
in
m
n
0
.9
se )
52
)
(1
m
t:5
m
m igh
m
in
8
70
He )
.9
m th:5 ith in (2
m p
3
t w .6
Deigh 10
O2
r:
Henso
ith
) w
se
m
m
82
(2
3in fitt
.1
11 sor
n
se
3.1
W UN
id
5.5 th: IT D
IM
m 1 in
EN
m
(1
He )
SIO
40
m igh
NS
m t:5
De )
.9
0
Hepth
in
:5
(1
se igh .98
50
ns t w
or: ith in (1
10
52
.6
m
3in
m
)
(2
11
70
.1
m
se 3in
m
)
m nso (28
m
r fi
He )
tte 2mm
d5
m igh
.5 ) wit
m t:5
1
De )
.9
in h O
0
p
(1
He th
in
402
:5
(1
se igh .98
50
t
ns
or:with in (1
10
52
.6
m
3in
m
)
(2
11
70
.1
m
se 3in
m
ns
)
or (28
fitt 2m
m
) w
ith
O
S
ON
SI
EN
M
DI
T
NI
1Uh:
40
50
3.
)
(1
idt in (1
m
in
W
m
0
51
.9
52
5. )
)
(1
t:5
m
m
m igh
m
in
70
98
He )
(2
5.
m
m pth: with63in
t
Deigh :10.
O2
Hensor
th
) wi 40
se
m in (1
m
82 51
5.
(2
3in fitted
50
)
.1
(1
m
or
11
in
m
ns
0
.9
52
se )
)
(1
t:5
m
m
m igh
m
in
70
98
He )
(2
5.
m
m pth: with63in
t
Deigh :10.
O2
Hensor
th
) wi
se
m
m
82
(2
3in fitt
.1
or
11
ns
se
S
ON
SI
EN
M
DI
T
NI
1Uh:
40
50
3.
)
(1
idt in (1
m
in
W
m
0
51
.9
52
5. )
)
(1
t:5
m
m
m igh
m
in
70
98
He )
(2
5.
m
m pth: with63in
t
Deigh :10.
O2
Hensor
th
) wi 40
se
m in (1
m
82 51
5.
(2
3in fitted
50
)
.1
(1
m
or
11
in
m
ns
0
.9
52
se )
)
(1
t:5
m
m
m igh
m
in
70
98
He )
(2
5.
m
m pth: with63in
t
Deigh :10.
O2
Hensor
th
) wi
se
m
m
82
(2
3in fitt
.1
or
11
ns
se
2
Basic Installation Guide
2 x Allen (Hex) Keys (3mm)
(3)
Ensure that the installer/end user of the equipment receives the technical documentation
(operating instructions, manuals, etc.) contained in the packaging.
26
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.6 INSTALLATION PROCEDURE
3.6.1 General
Searchline Excel is designed to allow installation and alignment to be performed by a single
technician.
The installation procedure is split into mechanical installation and electrical installation. Each
unit needs to be mounted to a supporting structure before making the electrical connections.
3.6.2 Mechanical Installation
The mechanical installation procedure applies to both the Receiver and the Transmitter.
(1)
Ensure that the gas detector equipment supplied is compatible with the required application
(i.e. short, medium or long range).
(2)
Fit the mounting bracket and isolation kit to the mounting plate for the unit as shown:
Mounting plate
Mounting bracket
Isolation kit
(3)
Fit the mounting plate to the supporting structure.
The plate can be fitted in one of the following ways:
a.
With bolts directly to a flat surface.
b.
With U-bolts (2 off) to a single 150mm diameter pipe or pole.
c.
With U-bolts (4 off) to two 55mm diameter pipes or poles, 166mm apart.
Identify the required mounting holes from the following drawing and table:
27
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
B
A
B
A
D
D1
G
C
G
E
J
G
F
224
209
K
Always mount
plate this way up
B
A
D1
C
E
B
A
F
J
H
H
G
K
H
J
C
E
C
D
B
B
A
A
B
A
B
15
A
E
D
15
60x45° 2 POSNS
49
83
133.2
181
215
249
6mm thick
stainless steel
plate
299.2
380
Notes:
1.
Drawing is not to scale.
2.
Mounting plate fixing holes are clear. Searchline Excel gas detector component mounting
holes are tapped.
3.
The mounting plate fixings are not supplied.
Identity
Quantity
Size Used For
A
8
7.5mm
B
8
9.5mm
C
4
M6 tapped
28
Dual 2'' pipe or pole mounting,
flat surface mounting.
Single 6'' pole, flat surface
mounting, Dual 2.5'' ID pipe.
00780-A-0100 junction box mounting
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
D
3
M6 tapped
DVC100(M) junction box mounting.
D1
2
M6 tapped
DVC100 (M) MK2 junction box (used in
conjunction with bottom two D holes)
E
4
M10 tapped
DX100(M) junction box mounting.
F
2
M6 tapped
Killark/Akron junction box mounting.
G
4
M6 tapped
Sun/heat shade mounting.
H
3
M8 tapped
Short range Transmitter and all Receiver
brackets.
J
3
M10 tapped
Medium/Long range Transmitter mounting
bracket.
K
2
M10 tapped
XNX Universal Transmitter
The following drawings show typical mountings:
M8 mounting bolt - 4-off
(not supplied) using B holes
Mounting Plate Fixed to Flat Surface
6in. U-bolt - 2-off
(not supplied) using
B holes
Mounting Plate Fixed to Single Pipe/Pole
29
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
2.5in. U-bolt - 4-off
(not supplied) using
A holes
Mounting Plate Fixed to Twin Pipes/Poles
(4)
Fit an adjustment clamp to the unit’s pivot block mounting stud so that it sits on the stud’s
shoulder. The correct orientation for the pivot blocks and clamps is as follows:
Mounting stud
Pivot block
Adjustment clamp
(5)
Tighten the adjustment clamp's grubscrews until they just grip the unthreaded part of
the stud.
(6)
Fit the pivot block to the mounting bracket using a clamp nut and washer (M12 or M16).
The correct orientation for the pivot blocks and mounting brackets is as follows:
Clamp nut and
washer
Mounting
bracket
Mounting bracket
grubscrew
Do not fully tighten the nut (Refer to 3.73).
30
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Ensure that the adjustment clamp's stub lever is approximately centrally positioned
between the mounting bracket’s grubscrews. Adjust the screws if required.
(7)
Fit an adjustment clamp to the unit’s mounting stud so that it sits on the stud’s shoulder.
The correct orientation for the adjustment clamp is as follows:
Stub lever
Adjustment clamp
Mounting stud
(8)
Tighten the adjustment clamp's grubscrews until they just grip the unthreaded part of
the unit’s mounting stud.
(9)
Fit the unit to the pivot block using a clamp nut and washer (M12 or M16).
Do not fully tighten the nut (Refer to 3.73).
At this point position the units on their mountings so that their optical windows face each
other as shown:
Ensure that the adjustment clamp's stub lever is approximately centrally positioned
between the pivot block's grub screws. Adjust the screws if required.
(10) Fit a suitable junction box, e.g. DVC100(M) MK2 or DX100(M) or other suitable type
of junction box, to the mounting plate. A typical installation with junction boxes is as
follows:
31
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Receiver
Transmitter
Note: For information about alternative types of junction box see section 3.6.2 Electrical
Installation.
(11) Measure and record the distance (in metres) between the Transmitter and Receiver
units.
This distance is required later in the alignment procedures.
3.6.2 Electrical Installation
(1)
Isolate all associated power supplies and ensure that they remain OFF until the instruction
in the commissioning procedure to apply power.
See section 3.7 Alignment and Commissioning. If the units are to be installed with
junction boxes other than DVC/DX100(M) types, ensure that the boxes have:
a.
b.
M20 cable gland entries for ATEX/IECEx units, or 3/4 NPT for UL and CSA
terminals for five wires and an earth.
(2)
Remove the M20 blanking plugs (if fitted) and attach the Searchline Excel Transmitter
and Receiver cables to their junction box.
Fit the locking rings (if supplied) before terminating the cables in the junction box.
(3)
Fit approved cable glands to the junction box cable entries.
Use sealing washers where necessary to maintain the ingress protection rating.
(4)
Fit approved blanking plugs to all unused cable entries.
(5)
Make electrical connections.
See section 3.3.
32
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.7 ALIGNMENT AND COMMISSIONING
WARNING
Do not attempt to view the Sun through the optical telescope.
3.7.1 General
In order to avoid unnecessary problems, alignment and commissioning of Searchline Excel gas
detectors should only be performed by personnel trained by Honeywell Analytics.
To ensure optimum performance the gas detector Transmitter and Receiver units must be
accurately aligned with a clear line of sight between them.
The Transmitter unit is first aligned with the Receiver using a telescope attached to the body of
the unit. A telescope is then fitted to the Receiver and the alignment procedure repeated.
The Handheld Interrogator is then attached to the Receiver to finally commission the equipment
and, depending on the type of Receiver, may need to be used to assist in fine-tuning the
alignment.
The procedure can be performed by a single technician.
Each gas detector unit features a mounting assembly that allow both coarse and fine mechanical
adjustment in the horizontal and vertical directions as shown in the subsequent diagram.
Clamp nuts
Mounting bracket
adjusting screw (2 off)
Adjustment clamp
lock screw (2 off)
Pivot block
adjusting screw
(2 off)
Clamp nuts
Mounting bracket
adjusting screw (2 off)
Adjustment clamp
lock screw (2 off)
Adjustment clamp
lock screw
(2 off)
Pivot block
adjusting screw
(2 off)
Initial coarse mechanical adjustment is first carried out by means of large clamping nuts and
with the help of an alignment telescope.
33
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Fine adjustment is then achieved by means of mounting bracket and pivot block grubscrews
which move levers on the adjustment clamps, fitted to the pivot block and unit studs, and hence
the unit.
After initial mechanical setup the units are powered up and the mechanical alignment can be
optimised and verified electronically by means of the associated Handheld Interrogator linked
to the Receiver.
By entering the operating range of the gas detector the Interrogator then provides reassurance
that the alignment has been performed successfully. The gas detector cannot be put into service
until it is.
The following equipment is used to carry out the alignment and commissioning:
•
Alignment Telescope(s) suitable for the distance between the units (see
Appendix C ‑ Accessories & Spare Parts).
•
SHC1 Handheld Interrogator (see Appendix C - Spare Parts).
•
Optional SHC Protection Device (see Appendix C - Accessories & Spare Parts) see Note 8.
•
Appropriate plastic test filters (see Chapter 5, section 5.1.2).
•
3mm hex (Allen) key.
•
19mm spanner (with additional 24mm spanner for mid/long range gas detectors).
Notes:
1.
Ideally, carry out the alignment procedure on a clear day.
2.
Get familiar with the workings of the adjustable parts of the gas detector before proceeding
with the alignment procedure, see section 3.7.4.
3.
The alignment telescopes use the same datum used when the unit was aligned in the
factory to ensure precise field alignment.
4.
The telescopes incorporate eye relief adjustment for comfortable viewing.
5.
Keep telescope mirrors and optics clean.
6.
Do not try to adjust the cross-hairs using the telescope's elevation and windage adjusters
as they have been factory set.
7.
If a telescope is damaged or misaligned it will need to be returned to the factory for repair
or realignment.
8.
The SHC Protection Device is only required if connecting the SHC1 Handheld Interrogator
via a junction box other than a DVC100(M) MK2 or DX100(M).
34
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
3.7.2 Alignment Procedure
The following summarises the alignment procedure:
•
Basic gas detector alignment, see section 3.7.3.
•
Accurate alignment of Transmitter and Receiver using the appropriate
alignment telescope, see section 3.7.4.
•
Power-up and verify alignment using SHC1 Handheld Interrogator linked to
the Receiver, see section 3.7.5.
3.7.3 Basic Gas Detector Alignment
The basic procedure for aligning the Transmitter and Receiver units is the same.
(1)
Loosen the two clamping nuts and four adjustment clamp screws on the Transmitter and
Receiver units until the units move freely in all axes.
(2)
Point the Transmitter and Receiver units so that they face each other across the area to
be protected.
(3)
Tighten the clamping nuts and adjustment clamp grubscrews on each unit until the unit
cannot be moved by hand.
This is the last time that these clamp nuts and grubscrews should need to be tightened.
Further tightening later on will affect the fine adjustment and should be avoided.
Note: The unit can still be moved by the adjustment screws.
3.7.4 Accurate Alignment
The procedure for accurately aligning the Transmitter and Receiver units is the same.
Before making any adjustments consult the following table to ensure that the correct type of
telescope is used with the Excel units that are to be aligned.
Excel Type
Type of Trident telescope that
can be used
SHC1 Handheld Interrogator
required to finalise alignment?
Trident Excel
Latch-type
Bayonet-type
No
No
Non-Trident Excel
Latch-type
Yes
To tell the difference between the two types of Excel look at the front face of the units. The Tridenttype Excel units have three small pads on their front face, the non-Trident types do not.
These pads provide three contact points (hence the term Trident) for the alignment telescope
assembly datum mount to ensure accurate fixing of the telescope so that subsequent alignment
of the gas detector units is precise.
The following diagrams illustrate the differences.
35
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Excel unit
Excel unit
Alignment
telescope assembly
mounting pad (3 off)
Trident-type
Non-Trident-type
After deciding from the table which alignment telescope to use for the Excel units being aligned
the telescope assembly must be fitted to each of the units in turn starting with the Transmitter.
There are two ways of attaching the telescope to the Excel units - using latches or using a
bayonet fitting. Depending on the type supplied refer to the relevant procedure described
subsequently.
The bayonet style telescope is used on both the Transmitter and Receiver of the short range
Excel. The bayonet-style telescope is also used on the Receiver of the medium and long range
Excels. The latch-style telescope is used on the medium and long range Excel Transmitters.
Latch-style telescope assembly
This telescope assembly consists of a telescope and mirror assembly attached to a datum
mount that features a latching mechanism. It can be used with either the Trident or non-Trident
types of Excel units.
When used with the non-Trident Excel the alignment may also need to be fine-tuned and then
verified using the SHC1 Handheld Interrogator.
The latches are used to lock the whole assembly onto the body of the Excel unit.
Before securing the latches the telescope can be rotated to a convenient viewing position.
To remove the telescope assembly reverse the following fitting procedure.
(a)
Fit the datum mount of the alignment telescope securely over the cowl of the
unit as shown so that the face of the mirror is visible.
Ensure the datum mount is fully home on the cowling.
(b)
Undo the latches on the alignment telescope's mounting latch assembly and
rotate the assembly so that the parallel support bar fits underneath the unit
as indicated by arrow 2.
36
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Telescope
viewfinder
Alignment
telescope
Datum
mount
Cowl
Mirror
assembly
Excel unit
Mounting
latch assembly
Latch (2 off)
(c)
Locate the latch mounting hooks behind the back of the unit.
3
2
3
(d)
Rotate the telescope to a comfortable viewing position, and then secure the
latches as indicated by arrow 3.
A horizontal viewing position is the easiest to interpret.
Now align the units by continuing with step 5.
Note: Take care when undoing the latches to remove the alignment telescope not to touch
the springs.
37
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Bayonet-style Trident-type telescope assembly
Caution: This type of telescope assembly must only be used with Trident-type Excel
units.
This type of telescope assembly consists of a telescope and mirror attached to a datum mount.
The mount features a bayonet fitting for attaching the assembly to the Excel unit.
The datum mount has a handle for rotating and locking the whole assembly over the cowl and
onto the Excel unit's body.
Before tightening the datum mount the telescope can be rotated to a convenient viewing
position.
To remove the telescope assembly reverse the following mounting procedure.
(a)
Align the telescope's two datum mount bayonet slots with the two locating pins
on the cowl of the unit as shown.
Excel Unit
Bayonet locating
pin (2 off)
Bayonet slot
(2 off)
Datum mount
Mirror assembly
Telescope
viewfinder
Alignment telescope
Locking handle
(b)
Push the telescope datum mount fully home onto the two pins on the cowl.
(c)
Without disturbing the datum mount use one hand to rotate the telescope to a
comfortable viewing position and hold it in that position.
A horizontal viewing position is the easiest to interpret.
38
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
(d)
With the other hand use the datum mount's locking handle to rotate the
bayonet fitting in a clockwise direction until it is securely locked onto the cowl.
The fitting is held tightly against the face of the cowl by means of hidden
compression springs.
After attaching the telescope assembly align the units by continuing with step 5.
(5)
Align the Excel unit using the two sets of assembly adjustment screws so that the
cross-hairs viewed through the alignment telescope are centred on the window of the
other Excel unit.
Mirror
Distant Excel
unit
Telescope
viewfinder
Cross-hairs
Before alignment
View the image with the eye placed approximately 3 inches from the viewfinder.
Approximately
3 inches
or 7.5cm
39
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Use a viewing position that ensures that the full circular view is in sight. An ellipse will
appear when slightly off axis.
Off-axis view
Off-axis view
Caution: Do not try to adjust the cross-hairs using the telescope's elevation and windage
adjusters as they have been factory set.
Clamp nuts
Mounting bracket
adjusting screw (2 off)
Adjustment clamp
lock screw (2 off)
Pivot block
adjusting screw
(2 off)
Clamp nuts
Mounting bracket
adjusting screw (2 off)
Adjustment clamp
lock screw (2 off)
Adjustment clamp
lock screw
(2 off)
Pivot block
adjusting screw
(2 off)
(6)
Tighten and loosen each pair of adjustment screws sequentially in the horizontal and
vertical directions until the setting is correct.
(7)
When correctly adjusted, tighten both adjustment screws simultaneously.
Ensure there is minimum movement whilst locking the assembly.
(8)
Check alignment and repeat steps 5 to 7 as necessary.
(9)
Remove the telescope assembly from the unit by reversing the fitting instructions.
(10) Carry out the final commissioning procedures described in the next sub-section.
40
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Distant Excel
unit
Cross-hairs
After alignment
3.7.5 Commissioning the Gas Detector
This process consists of the following steps:
•
•
•
•
•
Connect the Handheld Interrogator to the gas detector
Power-up the gas detector and check/set the mode of the Interrogator for
operation with the installed Excel gas detector
Set the gas detector real-time clock
Complete the alignment process
Finish up
Connecting the Interrogator
Connect the SHC1 Handheld Interrogator to the gas detector in one of the following ways:
•
via a Honeywell Analytics DVC100(M) MK2 or DX100(M) Junction Box - connect the
Interrogator directly to the junction box via its IS socket, e.g.
Calibrator
Type SHC1
ESC
41
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
•
via another type of junction box, e.g. Honeywell Analytics Junction Box Part
Number 00780-A-0100 - using the SHC Protection Device.
See the following diagram and description and Appendix C - Spare Parts.
IS connector
Flying lead
Notes:
1.
The protection device must always be used for this type of connection.
2.
A hot work permit may be required for this procedure.
Carry out the following procedure to connect using the protection device.:
(1)
Isolate all power supplies.
(2)
Remove the cover of the junction box.
(3)
Hard wire the flying lead of the SHC Protection Device to the communications
link terminals in the box as shown:
Junction Box
To Receiver
(4)
Blue
Brown
Blue
B
Orange A
Black
0V
White
4-20
Red +24V
Green/ GND
Yellow
SHC Protection
Device flying
lead
Connect the Interrogator to the IS connector on the end of the SHC Protection
Device.
Powering Up
(1)
Apply power to the Excel Transmitter and Receiver units.
(2)
Press and hold the
(Enter) key on the Interrogator keypad for at least two seconds.
42
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Calibrator
Type SHC1
This section is only relevant to handheld software versions 4VO and greater.
This switches on the unit.
Z - SHC1 EXCEL
Interrogator 4V0
Note:
Full details of the SHC1 Handheld Interrogator can be
found in Appendix A.
ESC
The Interrogator displays the following start-up message for approximately three seconds:
Z - SHC1 EXCEL
Interrogator
(3)
Quickly check the type of connected detector shown on the top line of the message.
The display shows Excel or Optima+ or Optima.
(4)
If the unit displays Optima+ or Optima immediately press the ESC key on the
keypad.
The ESC key must be pressed within 3 seconds to have any effect. Also see Appendix A,
section 5.6.
This toggles the Interrogator mode between Excel, Optima Plus and Optima.
The start-up message is updated and displayed again for 3 seconds then the unit
displays the Main menu, which is the top level of its Interrogator's menu style interface,
as follows:
>
>
Main
Display
The first line of the display shows the current level in the menu tree and the second line
displays a sub-menu title, action or data.
Setting the Real-Time Clock
The gas detector clock needs to be initially set so that faults, events, etc., can be accurately
recorded and tracked for diagnostic purposes.
(1) Select Calibrate from the Main menu by pressing the
keypad to navigate through the menu options.
(2) Press
(up) and
(down) keys on the
(Enter) on the Interrogator keypad to display the Calibrate menu.
(3) Select Set Time/Date from the Calibrate menu.
43
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
(4) Press Enter on the keypad and an initial set time display similar to the following
appears:
>
>
Time 09:26
09
The top line shows the current time and the second line shows the new hours setting.
(5)
Set the hour using the up and down keys on the keypad.
(6) Press Enter on the keypad and the new minutes setting is now displayed on the second
line.
>
(7)
>
Time 09:26
09:26
Set the minutes using the up and down keys on the keypad.
(8) Press Enter on the keypad and the display for setting the date now appears as
follows:
>
>
Date 20APR03
20
The second line shows the new day setting.
(9)
Set the day using the up and down keys on the keypad.
(10) Press Enter on the keypad and the new month setting is then displayed.
(11) Repeat the procedure to set the month and year.
(12) When complete press Enter on the keypad to return to the Calibrate menu.
Notes:
1.
The time and date will not be updated unless both are entered and accepted without
error.
2.
Pressing ESC on the keypad at any time, aborts the current setting immediately and
returns to the previous setting or menu option.
Complete the alignment process
In this part of the procedure details about the gas detector must be entered so that the Interrogator
can then complete the commissioning of the gas detector using the correct data.
(1) Select Calibrate from the Main menu.
Press the up and down keys on the keypad to navigate through the menu options.
(2) Press Enter on the Interrogator keypad.
This displays the Calibrate menu.
(3) Select Install from the Calibrate menu.
(4) Press Enter on the keypad.
44
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
The following is displayed:
System Type
Shrt Range
The second line shows the current gas detector type:
Short Range
5 - 40m
(15 - 130ft)
Medium Range
20 - 120m
(65 - 390ft)
Long Range
120 - 200m
(390 - 650ft)
(6) Press Enter on the keypad.
The current path length setting in metres similar to the following is now displayed.
(7)
>
>
Path Length
nnnn
Set the actual path distance (measured in metres) between the Transmitter and Receiver
units, using the up and down keys on the keypad.
The minimum and maximum path length entry options for each gas detector are:
System Type
Minimum Range (m)
Short Range
5
40 1
Medium Range
20
120 1
Long Range
120
200 1
Duct Mount
0.5
5 0.1
(9)
Maximum Range (m)
Step Size (m)
When finished press Enter on the keypad.
A self-test routine is started and the display shows the following message:
Self Test
Please Wait
When the test is successfully finished the following message is displayed for at least
three seconds:
Checks Passed
The screen then changes to show a display similar to the following.
SIG:
TGT:
Note: If this screen shows a numerical value the alignment is not sufficient. Refer back
to 3.72.
The first line of the display shows the magnitude of the current signal level as a horizontal
bar graph - SIG:
45
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
The second line of the display shows the magnitude of the current target signal level as
a horizontal bar graph - TGT:
Important Notes:
1)
The overall objective of alignment is to maximise the SIG level. Maximised SIG corresponds
to optimal alignment.
2)
The Instrument Assisted Alignment (IAA) system only allows Excel to be initialised if the
SIG level is greater than or equal to the TGT level when Enter is pressed.
3)
The smallest TGT signal level that is initially set will be equivalent to 70% (0.700) of the
signal expected for the installation’s path length.
4)
The TGT level will increase gradually if the current SIG level is larger than the TGT level.
The TGT signal level only ever increases. If the current SIG level falls below the TGT
level, TGT will remain at its previous highest value. In order to initialise the gas detector
the SIG level must be brought back above the TGT level.
5)
If the SIG level is less than 50% of the expected level, the bar graphs are not displayed.
Instead both SIG and TGT levels are displayed as numbers.
(10) Now carry out one of the procedures described under Options.
Options
The next procedure to be followed depends on the type of alignment telescope and mounting
initially used to set up the Excel gas detector.
Bayonet-style Trident-type telescope assembly
If this type of alignment telescope was used with a Trident-type Excel gas detector, there is no
need to further optimise the alignment using the SHC1 Handheld Interrogator.
When the SIG and TGT bar graphs are displayed on the SHC1 screen, SIG will always be
greater than TGT and installation can proceed to the next stage by pressing Enter and following
step 12.
Latch-style Trident-type telescope assembly
If this type of alignment telescope was used with a Trident-type Excel gas detector, there is no
need to further optimise the alignment using the SHC1 Handheld Interrogator.
If this type of alignment telescope was used with a non-Trident Excel it may be necessary to
further optimise the alignment in the following way in order to achieve best performance.
(a)
After the SIG and TGT bar graphs are displayed on the SHC1 screen as previously
described, let the TGT level reach its initial maximum by waiting for approximately
10 seconds.
During this time the TGT level will move up towards the current SIG level.
(b)
(c)
Whilst watching the SIG level closely, make a small mechanical adjustment in either
the horizontal or vertical alignment and note whether the SIG level goes up
or down.
If the SIG level goes up, make another small mechanical adjustment in the same
direction as before.
46
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
(d)
If the SIG level goes down, change the direction of adjustment.
Maximise the SIG level by making small adjustments in only one plane at a
time.
(e)
When the SIG level has been maximised in one plane, make small adjustments
in the other plane until SIG has been maximised in this plane.
(f)
Repeat steps (b) to (e) until the SIG level has been maximised in both planes.
At this point, SIG must be bigger than the initial TGT level and any adjustment
either side of the current alignment must result in a reduction in signal level.
If not, repeat steps (b) to (e) until these requirements have been met.
(g)
Lock off the alignment by placing a hex (Allen) key in the pair of grub-screws
which control adjustment in a particular plane and simultaneously rotating them
in opposite directions.
(h)
Repeat this for the other pair of grub-screws.
(i) Press Enter and the signal levels are checked.
With the SIG level is greater than the TGT level, the signal check should
pass and the screen should display the following message:
Signals OK
Notes:
1. If SIG is less than the TGT value the following message is displayed:
Low Signal
Enter to Retry
2. If SIG is more than the TGT value the screen shows the bar graph screen again.
(12) When the following message is displayed press Enter:
Signals OK
The display changes to show the following instruction:
Ensure Zero Gas
Then Press Enter
Ensure there is a gas-free atmosphere.
(13) Press Enter on the keypad.
The following message is displayed for three seconds:
Zero Calibration
OK
47
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
The following message is displayed for three seconds:
Installation
Complete
The following message is then displayed:
Press Enter to
Release 4-20
(14) Press Enter on the keypad.
The following message is displayed for three seconds:
4-20 Released
The display then changes to show the Calibrate menu. The Searchline Excel gas detector
is now on-line .
This completes the final part of the gas detector alignment procedure.
3.7.6 Finishing Up
To finish the alignment process carry out the following procedure:
(1) Select Power Off from the Interrogator Main menu.
(2) Press
(Enter) on the keypad.
Alternatively press the
and ESC buttons simultaneously for a fast power off.
Notes:
1.
The SHC1 Handheld Interrogator powers down automatically after five minutes of nonuse.
2.
Fast power off and auto power off are disabled when any menu option is selected that
modifies the unit’s configuration.
(3) Disconnect the Interrogator from the gas detector, reversing the process described at
the beginning of section 3.7.5.
3.8 SYSTEM CONTROLLER CALIBRATION
This procedure is used to set up the system controller using the Searchline Excel gas detector.
A chosen fixed output signal is sent from the Excel gas detector to the system controller allowing
calibration of the 0 - 100% scale of the controller without having to use gas. The steps use
procedures described in the previous section.
To calibrate the controller carry out the following procedure:
(1)
Connect the Interrogator to the gas detector.
See Connecting the Interrogator to Searchline Excel Gas Detector.
(2) Turn on the Interrogator.
See Powering Up.
(3) Select Calibrate from the main menu.
Press the up and down keys on the keypad to navigate through the menu options.
48
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
(4) Press Enter on the Interrogator keypad and the Calibrate menu is displayed.
(5) Select Force 4-20 from the Calibrate menu.
(6) Press Enter on the keypad and a display similar to the following appears:
>
(7)
>
4-20 current
4.5 mA
Use the up and down keys on the keypad to set the displayed output current to the desired
value.
The values can be changed in steps of 0.1mA in the range 1mA to 21mA.
(8) Press Enter on the keypad.
This selects the currently displayed value and forces the gas detector to output that
current. Once complete a display similar to the following appears:
Fixed:4-20 mA
Press Enter
(9)
Carry out checks on the controller by following the instructions in the controller
documentation.
(10) When checks are complete press
on the Interrogator keypad and the following display
appears:
Press Enter To
Release 4-20
(11) Press Enter on the keypad.
The following message is displayed:
4-20 Released
The fixed output is released and the gas detector returns to normal operation.
(12) Turn off the Interrogator and disconnect it from the gas detector.
3.9 INSTALLATION CHECKS/TESTS
The following information is for the guidance of personnel carrying out installation checks/tests
on Searchline Excel. In general it should be noted that:
•
Searchline Excel should only be installed by fully trained personnel, trained by
Honeywell Analytics or an authorised Honeywell Analytics trainer.
•
Detailed information concerning installation, alignment and commissioning is
provided in this Technical Handbook.
•
Searchline Excel is explosion protected by a certified, flameproof enclosure.
Carefully read the safety warnings, cautions and certification details in this
handbook and the Basic Installation Guide.
Ensure that they have been complied with, before and during the installation.
•
A copy of the subsequent Installation Check Sheet should be completed
for each Searchline Excel gas detector installed. In order to help Honeywell
Analytics to provide efficient assistance/service in the event of problems,
the sheet should be returned to Honeywell Analytics or to one of their agents.
49
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
SEARCHLINE EXCEL: INSTALLATION CHECK LIST
2104P1003
CUSTOMER/OPERATOR
SITE/FACILITY
SYSTEM TYPE:
SR
MR
LR
OPERATING RANGE
GAS TABLE:
METHANE
ETHANE
PROPANE
BUTANE
PENTANE
PROPYLENE OTHER
ETHYLENE
PROPYLENE
BUTADIENE
DETECTOR LOCATION:
TAG NO. (RX):
TAG NO. (TX):
SER NO. (RX):
SER NO. (TX):
MOD STATE (RX):
MOD STATE (TX)
CHECK/TEST
CERTIFICATION:
RECIEVER
CHECK/TEST
TRANSMITTER
Mount Rigidity
Mount Rigidity
Vibration:
Vibration:
Excess Heat:
Excess Heat:
Supply Voltage:
Supply Voltage:
Earthing:
Earthing:
RFI/EMC:
RFI/EMC:
Contaminants:
Contaminants:
BEAM OBSTRUCTIONS / BLOCKS:
(cont.)
TEST FILTER:
Response:
Pass:
Fail:
4-20mA LOOP INTEGRITY
Pass:
Fail:
Untested:
FAULT / WARNING LOG:
Clear:
Faults/Warnings:
(cont.)
INSTALLATION SATISFACTORY:
Yes:
No:
INSTALLED BY (PRINT)
Signed:
DATE:
IF INSTALLATION UNSATISFACTORY, REASONS
RECOMMENDATIONS
CUSTOMER NOTIFIED:
SYSTEM STATUS:
Operational:
Nonoperational:
50
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
The following notes are to help the installer enter the correct information onto the check
sheet.
Site/Facility
Enter the name and geographical location of the site/facility, e.g.
NAM F3 Platform, North Sea
Operating Range
Enter the distance (preferably in metres), between the Transmitter and the Receiver.
Detector Location
Enter the location/position of the detector, e.g.
West Corridor, HIVAC Building1
Tag No
Enter the Tag No, or equivalent, that has been allocated to the Excel Receiver and
Transmitter units.
Mod State
Enter the Mod State of the units as indicated on their certification/product labels.
Certification
Enter the certification of the units, e.g.
ATEX, UL, CSA, FM, IECEx
Mount Rigidity
Check that the units have been mounted securely to the supporting structure. Check that the
supporting structure is sufficiently rigid to maintain alignment in the anticipated operating
conditions. A maximum angular movement of ±0.5o is allowable.
As an approximate guideline, a sufficiently rigid mount/supporting structure will only move a
few millimetres (not more than ±6mm) when leaning body weight against it.
When pushed hard and released, the mount/supporting structure should return quickly to its
original position and should not wobble or sway. If the mount/ support is unacceptable, briefly
describe the problem, e.g.
Mount wobbles unacceptably,
Mounting pole too thin
Vibration
Check the installation and its close surrounds for potential or existing sources of excessive
vibration. Such sources could include heavy plant/machinery, turbines, generators etc.
51
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
If there is the possibility that such vibration sources could or are causing unacceptable
movement,
enter a brief description, e.g.
Turbine nearby,
Below conveyor
Excess Heat
Check the installation and its surrounds for potential sources of excessive heat. The unit is
specified up to +65oC. Potential sources of excessive heat include direct sunlight in hot
climates, flare-stacks, generator/turbine exhausts and steam vents.
Enter a brief description, e.g.
Direct sun, Kuwait,
Flare-stack 2 metres away
Supply Voltage
Check that the supply voltage applied to the unit is within the specified 18V to 32V range and
is stable. Enter the supply voltage and stability, e.g.
22.5V, stable,
19V, ±2V fluctuation
Earthing
Inspect the earth connections to the units. If the unit is connected to local metalwork or the
safety/general use earth, enter 'Local Safety. If the unit has been isolated from local
metalwork/ earths and is connected to a clean, instrument earth, enter Instrument earth.
(See section 3.3, Electrical Connections).
RFI/EMC
Assess the installation, cabling and its close surrounds for known/potential sources of
excessive RF/Electromagnetic Interference. Such sources could include radio/radar
transmission antennae, high voltage switch-gear, large electrical generators/motors etc.
Searchline Excel is extremely immune to RFI/EMI, complying with the most stringent
requirements specified in EN50270. It is therefore more likely that the field cabling will pick
up interference directly on the 4 - 20mA and 0V connections and that this will affect the
reading received at the control room.
Enter brief details of known/potential EMI sources that are within five metres of the gas
detector and/or its cabling. If cable is unscreened or inadequately protected, note concerns.
Examples of the sort of information to enter are:
10m cable, unscreened, Radar, 2m from Receiver,
Cable routed over 400kW generator
(See section 3.3 Electrical Connections).
52
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Contaminants
Assess the installation and its surrounds for sources of contaminants that could build up on
the unit’s windows. Such contaminants could include oil mist, heavy sea spray, drilling mud,
dirty exhaust fumes, wave splash etc.
If there is a realistic possibility that such contaminants could cause a significant problem,
enter a brief description, e.g.
Drilling mud spray,
Diesel generator exhaust
Beam Obstruction/Blocks
Ideally, a clear path of at least 20cm diameter should be provided between the Transmitter
and the Receiver. Enter any obstructions which encroach into this path, e.g.
Process pipes,
Tree branches
Assess the installation and the beam path for potential sources of beam blockage. These
could include personnel walking in the beam, parking vehicles, moving machinery/plant,
growing vegetation etc.
If there is a realistic possibility that they could cause a significant problem, enter a brief
description, e.g.
Personnel in corridor,
Loading bay vehicles
Test Filter
After completing the installation procedure, enter the DISPLAY mode and test the gas
detector response with a plastic test filter. Enter the nominal value of the test filter, the unit’s
displayed response and mark the Pass or Fail box.
The acceptable responses to test filters for different gas tables are detailed in section 5.1.2.
4 - 20mA Loop Integrity
Test the 4 - 20mA loop integrity by forcing the unit to output a known current and monitoring
this at the control room or with a multimeter inserted into the loop. Mark the appropriate box.
Fault/Warning Log
Check the fault/warning log. In order for the unit to complete installation satisfactorily, the
ACTIVE FAULTS log must be CLEAR. Use the Handheld Interrogator to diagnose and
remedy all ACTIVE FAULT.
Wherever possible, it is recommended to CLEAR any ACTIVE WARNINGS, since these
may lead to faults in the future.
53
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
3. INSTALLATION AND OPERATION
Faults/Warning
Enter any ACTIVE FAULTS or ACTIVE WARNINGS that could not be cleared from the log,
e.g.
BEAM BLOCK,
E_ZERO_NOT_CALIBRATED
Installation Satisfactory
Only fully trained personnel trained by Honeywell Analytics or Honeywell Analytics authorised
trainers can declare an installation satisfactory. Mark the YES box and sign the form if:
a. having completed the installation and testing, the unit is operating correctly, and
b. in the trained installer's opinion, the unit should continue to operate reliably in this
installation/ operating environment providing that nothing significant about the
installation/environment is changed.
If the unit is not operating correctly or there are aspects of the installation/operating
environment which in the trained installer's opinion could or will result in unreliable operation,
mark the NO box.
Reasons for declaring an installation unsatisfactory could include:
excessive movement/vibration of unit’s mounting,
received signal levels too low,
supply voltage too low,
4 - 20mA loop integrity faults,
unclearable active faults,
any prevailing or probable condition which is known to unacceptably reduce
reliability or availability
If Installation is Unsatisfactory, Reasons
Briefly state the principal reasons why the installation is unsatisfactory, e.g.
Unit mounted on single scaffold pole. Excessive movement,
Beam path obscured by pipes, insufficient received signal levels,
Unit overheated by intense Kuwaiti sunlight
Recommendations
Briefly describe the recommended actions which need to be performed in order to make the
installation satisfactory, e.g.
Mounting pole requires bracing/stiffening,
Pipes obscuring beam to be moved, or detector relocated.
Provide correct supply voltage
Customer Notified
Make sure that the relevant customer/operator is notified of the installation problem(s).
Mark box accordingly.
System Status
Upon leaving, note the gas detectors status, i.e. operational or nonoperational.
54
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
4. MAINTENANCE
The Searchline Excel Open-Path Gas Detector requires little maintenance other than occasional
cleaning.
Depending on the local regulations and site conditions, cleaning and functional testing of the
gas detector can be carried as described in the following sub-sections. The gas detector should
remain powered during these procedures.
Caution: Searchline Excel does not contain any user serviceable parts. Do not open
either the Transmitter or Receiver unit. The warranty of units which have been
opened is invalidated.
NOTE:
THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
4.1 INSPECTION AND CLEANING
Caution: Do not use solvents or abrasives on the Searchline Excel units.
(1) Inspect the Searchline Excel units, junction box and cabling for signs of physical
damage.
(2) Using the SHC1 Handheld Interrogator inhibit the Searchline Excel signal output.
Since the signal output may vary during cleaning, due to the optical path being disturbed,
it is important to inhibit the analogue output. The quickest way to inhibit the Excel output
is to select DISPLAY from the Calibration menu.
(3) Clean any dust or dirt from the Searchline Excel windows using soapy water and a soft
cloth.
(4) Using the SHC1 Handheld Interrogator release the Searchline Excel signal output.
The output can be released by pressing ESC followed by
on the keyboard.
(5) Using the SHC1 Handheld Interrogator re-zero the unit.
See Appendix A for details about how to use the Interrogator.
4.2 FUNCTIONAL TESTING (Plastic Test Filters)
From January 2004 onwards, a new range of plastic test filters has been available for performing
functional testing on Searchline Excel. They are lettered from A to H, with the reading a filter
produces increasing in alphabetical order.
Whilst the new filters can be used with all Mod states of Searchline Excel units, they have been
specifically designed to work with open path Excel units of Mod state 7 (or higher).
The part number for the new test filter set is 2104N2999.
Testing of Mod state 6 (or lower) open path Excel units should continue to be performed using
the original plastic test filters, with the results to be anticipated detailed in Issue 8/9 of the
Technical Handbook, 2104M0506.
For information on testing Mod state 6 (or lower) Excel units refer to addendum 2104M0523
available from haexpert@honeywell.com.
55
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
4. MAINTENANCE
The procedures for using these functional test filters on Mod state 7 or higher Excel units are
detailed as follows:1)
2)
3)
4)
5)
Ensure the area is free from gas.
Connect the SHC-1 Handheld Interrogator to the unit to be tested.
Select DISPLAY from the Calibration menu.
For new units, refer to supplied test certificate for factory response to test filter
recommended.
For other units, slide a suitable functional test filter (see tables below) into the cowling
at the front of the receiver.
Receiver Gas Calibration Low Test Filter
Response
High Test Filter
Response
Methane
C or D
0.5 – 1.1 LEL.m
F
1.5 – 2.8 LEL.m
Ethane
C or D
0.6 – 1.3 LEL.m
F
1.5 – 2.7 LEL.m
Propane
B or C
0.5 – 1.2 LEL.m
F
1.6 – 2.9 LEL.m
Butane
B or C
0.6– 1.4 LEL.m
E
1.4 – 2.6 LEL.m
Pentane
A
0.6 – 1.1 LEL.m
D
1.2 – 2.2 LEL.m
Hexane
B or C
0.6 – 1.5 LEL.m
E
1.4 – 2.7 LEL.m
Ethylene
B or C
0.5 – 1.3 LEL.m
F
1.8 – 3.4 LEL.m
Propylene
A
0.5 – 1.0 LEL.m
D
1.0 – 1.9 LEL.m
Butadiene
A
0.5 – 1.0 LEL.m
D
1.0 – 1.9 LEL.m
Methanol
D
0.5 – 0.9 LEL.m
E
1.0 – 1.9 LEL.m
Ethanol
B or C
0.6 – 1.4 LEL.m
E
1.5 – 2.8 LEL.m
6)
7)
8)
9)
10)
11)
12)
13)
If this is the first time that the unit has been tested with this particular test filter, record
the gas reading that is produced. This reading should be used to verify correct operation
in the future.
If this is not the first time that the unit has been tested with this particular filter, note the
gas reading it produces and compare it to the original value recorded for this unit when
tested with this filter. Provided that the reading is within ±0.5 LEL.m of the original value,
the unit is working correctly. If the unit is working correctly, proceed to step 15.
If the gas reading is not within the expected range it is possible that the unit needs
cleaning or re-zeroing.
Remove the test filter from the cowling.
Using a damp, lint-free cloth, clean the windows of the transmitter and the receiver.
Using the SHC-1 in CALIBRATE menu, re-zero the unit.
Re-insert the chosen test filter into the cowling in front of the receiver.
Verify that the reading produced by the test filter is now within ±0.5 LEL.m of the reading
originally obtained with this filter. If the gas reading is still not within the expected range,
check the system alignment (see section 3 of the Excel manual, 2104M0506) and repeat
the test in step 7.
56
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
4. MAINTENANCE
14)
15)
16)
Remove the test filter from the cowling.
Release the unit under test from INHIBIT by selecting the MAIN menu option.
Disconnect the SHC-1 Handheld from the unit being tested.
4.3 CALIBRATION CHECK USING THE GASSING CELL
The gassing cell is designed to allow easy calibration checking using a high concentration test
gas as opposed to the standard plastic test filters. The integrated LEL.m reading of the gas
concentration in the cell can be calculated using the following formula:
Int(lel.m)xl = Lcell * (Concgas / LELgas)
where:
Int(lel.m)xl = Integrated LEL.m reading output by Searchline Excel in LEL.m.
Lcell
= Length of cell in metres.
Concgas
= Gas concentration in %v/v.
LELgas
= Lower Explosion Limit of the gas in %v/v.
The test gas must be the same as the test gas used during the factory calibration of the
Searchline Excel unit and ideally the concentration should be between 2 and 5 LEL.m and
never below 1 LEL.m.
Note: Where a different test gas is used, the typical value for cross-sensitivity is not sufficiently
precise to enable valid calibration checks to be performed using the Gassing Cell,
however, response tests can be easily performed with the plastic Test Filters as described
in section 5.1.2.
WARNING
Take the necessary precaution to ensure safety when dealing with these
high concentration gasses.
The gassing cell supplied by Honeywell Analytics (Part No: 2104B2326) is 0.15m long and the
following table outlines the response expected when using this gassing cell:
Gas type
LEL
Concentration
of the gas
applied
Calculated
response with
0.15m gas cell.
Methane
5.0 %v/v
100 %v/v
3 LEL.m
13.6mA
Ethane
3.0 %v/v
50 %v/v
2.5 LEL.m
12mA
Propane
2.0 %v/v
50 %v/v
3.75 LEL.m
16mA
Butane
1.5 %v/v
50 %v/v
5 LEL.m
20mA
57
4-20mA output
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
4. MAINTENANCE
For the Ethylene version of Excel, the following gas concentrations are suggested
Gas type
LEL
Concentration
Calculated
4-20mA output
applied Response
Ethylene
2.7% 54% 3 LELm 13.6mA
Propylene
2.0% 50% 3.75 LELm 16mA
Butadiene
2.1% 42% 3 LELm 13.6mA
WARNING
These gases are flammable and/or toxic.
Take appropriate precautions when handling.
To get the best accuracy when using the gassing cell:
(1)
Connect the gassing cell to the Searchline Excel.
(2)
Zero Searchline Excel with the empty gassing cell.
(3)
Apply the test gas to the gassing cell and allow sufficient time to fully flush the cell without
pressurising it and check that the Searchline Excel output stabilises.
(4)
Check the Searchline Excel output is as indicated in the above table ±5% fsd.
(5)
Remove the gassing cell.
(6)
Re-zero Searchline Excel.
Note: Pentane cannot be used with the gassing cell. At normal temperatures, these substances
do not vapourise sufficiently to give a useful signal in the short path of the gassing cell.
4.4 DISPLAY GAS READING
This procedure displays details about the current gas/gas table. Carry out the following
procedure:
(1)
Connect the SHC1 Handheld Interrogator to the gas detector.
See Connecting the Interrogator to the Searchline Excel Gas Detector in section
3.7.6.
(2) Switch on the SHC1 Handheld Interrogator.
See Powering Up in section 3.7.6.
(3) Select DISPLAY from the Main menu by pressing the (up) and
(down) keys on the
keypad to navigate through the menu options.
(4) Press
on the Interrogator keypad to display the Display menu.
(5) Select GAS READING from the Display menu.
(6) Press
on the keypad.
A display similar to the following is now displayed.
58
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
4. MAINTENANCE
Gas Type
Status character
Current Reading
The first line of the display shows the name of the gas or its identifier in a special gas
table.
The second line shows the gas reading and measurement units along with a gas detector
status indicator.
The status character at the end of the second line indicates one of the following:
/ -
Normal Operation
A spinning line shows the unit is in the fully active state.
-
Inactive State
A stationary line shows the unit is in the inactive state.
w
-
Active Warning
F
-
Active Fault
B
-
Beam Blocked
(7)
Switch off the Interrogator (see section 3.7.7 Finishing Up) and disconnect it from the
gas detector.
4.5 ALIGNMENT TELESCOPE
To clean the telescope lens/mirror:
(1)
Moisten the surface of the lens/mirror by breathing on it.
(2)
Using a soft tissue or lens cloth, lightly wipe the lens/mirror dry with a minimum number
of strokes.
The wiping material may be slightly dampened with a lens cleaning fluid as sold in any
camera store.
4.6 OPERATIONAL MAINTENANCE (FM)
As required as a criterion for the FM Performance Approval, routine operational verification is
recommended once within a three month period and is required once within a six month period
using one of the following methods.
WARNING
The following procedure will indicate a gas reading. Ensure all required
personal have been notified prior to starting and completing the procedure.
59
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
4. MAINTENANCE
•
Following the procedure described in section 5.1.2 insert a known test filter in the beam
path. Record the response to the test filter and verify that the response is within the
tolerance for stability and repeatability.
•
Following the procedure described in section 5.1.3, test the unit’s response to high %V/V
gas in a gassing cell. Verify that the response is within the tolerance for stability and
repeatability.
60
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
5. PROBLEM SOLVING
The majority of gas detector problems/faults can be diagnosed and corrected using the
installation and alignment kit.
The alignment kit includes:
•
•
•
SHC1 Handheld Interrogator
alignment telescope
set of functional test filters
An electrical multimeter is also useful when diagnosing electrical/wiring problems.
Refer to the troubleshooting tables in this chapter for a list of problems, possible causes and
actions.
Caution: Searchline Excel does not contain any user serviceable parts. Do not open either
the Transmitter or Receiver unit. The warranty of units which have been opened is
invalidated.
NOTE:
THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
RS485 Modbus signal errors may occur when Excel is connected via a DVC100(M) MK2 or
DX100(M) Termination Unit and is interrogated/commanded from a network control centre.
For troubleshooting these issues refer to the DX100 Series Termination Units Technical
Handbook.
If, after following the recommendations in this section, the problem persists, please make
available the following information before contacting Honeywell Analytics:
•
Installation Check Sheet
See Chapter 3.
•
Any error message
Displayed on the Handheld Interrogator screen.
•
Any error code
Displayed on the Handheld Interrogator screen.
Fault/Problem Causes
Remedies
Output is 0mA Unit is in FAULT Connect the SHC1 Interrogator to the unit and use its
condition
DIAGNOSTIC menu options to ascertain the reason for the
FAULT report.
Beam block
Check that beam path is clear from the Transmitter to
the Receiver. Remove any obstruction if present.
Transmitter
1)
or Receiver
misaligned
2)
3)
4)
Connect the SHC1 Handheld Interrogator to the
unit and check the signal levels.
If signal levels are low, use the telescope and
Interrogator to optimise Receiver alignment.
If signal levels remain low after re-aligning
Receiver, check the Transmitter alignment using telescope.
Re-zero the unit after alignment. See Appendix A.5.3.4.
61
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
5. PROBLEM SOLVING
Fault/Problem Causes
Remedies
Electrical installation
1) Check that the +24V supply is reaching the unit.
problem
Voltage at the unit should be between +18V and +32V.
2) Check cables and connections to the unit, especially
the 4‑20mA loop connections.
3) Check that the unit has the correct type of 4-20mA
output for use with the controller that it is connected to.
Heavy contamination of
Check the Transmitter and Receiver windows for
optics
build up of contamination. Clean the windows if
required. Re-zero unit.
Very low visibility along
1) Check that the Transmitter can be seen from the
beam path due to dense
Receiver. If Transmitter can be seen, even with some
fog, blizzard or
difficulty, low visibility is unlikely to be the problem.
sand-storm
2) If the Transmitter cannot be seen from the Receiver,
conditions
very low visibility could be the problem. Wait until
visibility improves and verify that the unit then returns
to operational status.
Output is 2.5mA. Beam path is blocked
Check that the beam path is clear from the Transmitter
(BEAM BLOCK)
to Receiver. Remove any obstruction if present.
Transmitter or Receiver
1) Connect SHC1 Interrogator to unit and check signal
misaligned levels.
2) If signal levels are low, use the telescope and SHC1
Interrogator to optimise Receiver alignment.
3) If signal levels remain low after re-aligning
Receiver, check the Transmitter alignment using
the telescope.
4) Re-zero the unit after alignment. See Appendix
A.5.3.4.
Output is 3mA Heavy contamination of
Check the Transmitter and Receiver windows for
(LOW SIGNAL) optics
build up of contamination. Clean windows if required.
Re-zero the unit.
Transmitter or Receiver
1) Use the telescope and Interrogator to optimise
misaligned
Receiver alignment.
2) If signal levels remain low after re-aligning
Receiver, check the Transmitter alignment using
the telescope.
3) Re-zero the unit after alignment. See Appendix
A.5.3.4.
Output is 2mA Unit has been inhibited by Release output from INHIBIT state using SHC1
(INHIBIT)
the Interrogator Interrogator.
Unit executing power-up 1) Wait for 1 minute. When power-up routine is
routine
completed satisfactorily the unit’s output should
exit the INHIBIT state.
2) If unit remains in INHIBIT, check the +24V supply
is reaching the unit. If the voltage is below +18V or
is fluctuating above and below +18V, the unit may
be being prevented from completing power-up.
(This is an electrical installation problem.)
62
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
5. PROBLEM SOLVING
Fault/Problem Causes
Remedies
Comms Error
Wrong communication mode 1) Select Change Mode option on the Interrogator.
reported by
selected on the Interrogator 2) Change the communication mode to Excel.
Interrogator
software
Interrogator software version Version 1V00 Interrogator software to be Excels
is incompatible running 1V0 software.
with Excel software version Version 2V0 Interrogator software can be used with
Excels running 2V0 software or higher.
Version 3V0 and 3V1 Interrogator software can be
used with Excels running 3V0 software or higher.
The latest version of Interrogator software is
greater than 4V0. This version works with 3V0 and
higher Excels, Optima and Optima Plus. CSA
versions of the SHC-1 are programmed with
version 4V1 of the interrogator software, which
displays the units of measurement for the
Cross-Duct version as %LEL/m.
Incorrect communication 1) Check that Interrogator is correctly plugged
connection into the IS socket on the DVC100(M) or DX100(M)
junction box.
2) Check that the RS485 A and B wires from the
Excel unit have been connected to the correct
terminals inside the DVC100(M) or DX100(M)
junction box.
Excel unit is not powered up Check that the +24V supply is reaching Excel
unit correctly. The Supply voltage at unit should be
between +18V and +32V.
Interrogator battery low Check the Interrogator battery and replace if low.
See Appendix A. Section A.4.3.
Interrogator
The installation has failed to 1) Check that the signal levels reaching the
Installation
meet the acceptable criteria Receiver are greater than 0.7 and less than 2.0.
Failed message of the Instrument Assisted 2) Check that the correct range has been entered for
when attempting Alignment (IAA) check
the installed path length.
initialisation
3) Check that the alignment of the Receiver has been
fully optimised.
The received signals must be peaked up to the
maximum achievable. Adjusting the alignment until the
signals are just above the minimum signal threshold
and then leaving it at that is poor practice and will not
always result in an installation that passes the IAA
check criteria.
4) Check the alignment of the Transmitter.
5) Check that there are no objects obscuring part or all
of the beam path.
6) Check that the windows of both the Receiver and
the Transmitter are clean.
7) Check that the structures that the Transmitter and
Receiver are mounted on are stable and free from
significant angular movement/vibration.
8) Check that there is no gas in the beam - which
prevents successful zeroing.
9) Installation will fail in conditions of low visibility or
fluctuating atmospheric transmission - which degrade
signal quality. Do not attempt installation during
conditions of heavy rain, snow or fog.
63
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
5. PROBLEM SOLVING
Fault/Problem Causes
Remedies
No signal or
Receiver misaligned
Re-align the Receiver, first using the
very low signal
telescope and then using the Interrogator.
at Receiver
Transmitter misaligned
Re-align the Transmitter using the telescope.
The beam path has become
Check that the beam path is clear from
obscured
Transmitter to Receiver.
Remove any obstruction if present.
No output from Transmitter
1) Check that the Transmitter is flashing.
Alternatively, listen for a distinct ticking
sound when the lamp flashes.
Note: The infrared beam is invisible and eye
safe.
2) If the Transmitter is not flashing, check
that the +24V supply is reaching the
Transmitter correctly.
Unit does not
Plastic test filters are only
Searchline Excel units are calibrated on
respond exactly
an approximate simulation of gas real gas. This results in a variation of the
as expected to
response test filters of different Excel
units to plastic test filters. See section
5.1.2.
1) Check that the response to the test
filters is within the limits stated in this
handbook. See section 5.1.2.
2) Check that the value being used for
response testing corresponds correctly to the
target gas that the unit has been calibrated for.
Receiver misaligned
1) Use the telescope and Interrogator to
optimise Receiver alignment.
2) Re-zero unit.
Contamination of windows
1) Check the Transmitter and Receiver
windows for build up of contamination.
Clean windows if required. See Chapter 5.
2) Re-zero unit.
Drift of unit’s zero position
1) Verify that there is no gas in the beam path.
2) Re-zero the unit.
Unit appears to
Misinterpretation of INHIBIT,
Searchline Excel does not report
be reporting a
BEAM-BLOCK or LOW
negative gas readings on the 4-20mA.
negative gas
SIGNALcurrents that are
1) Configure controller/PLC to interpret
reading on the
output on the 4-20mA
and present currents below 4mA correctly,
4-20mA
or,
2) Familiarise operators with the
interpretation of sub-4mA output currents
from Excel as follows:
FAULT
0mA
INHIBIT
2mA
BEAM-BLOCK 2.5mA*
LOW SIGNAL 3mA*
or,
3) Reconfigure the INHIBIT, BEAM-BLOCK
and LOW SIGNAL currents output by the
Excel unit.
64
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
5. PROBLEM SOLVING
Fault/Problem Causes
Diagnostics
Receiver misaligned
report
Neg Gas
Reading
Remedies
1) Re-align the Receiver, first using the
telescope and then using the Interrogator.
2) Re-zero the unit.
1) Check the Transmitter and Receiver
windows for build up of contamination.
Clean windows if required.
See Chapter 5.
2) Re-zero the unit.
Re-zero the unit.
Contamination of windows
Negative drift of unit’s zero
position
Diagnostics
Receiver misaligned
report
Baseline Drift
Contamination of windows
Drift of unit’s baseline
Diagnostics
Unit has been operated
report
at a temperature outside
Bad
its specified and certified range
Temperature
Diagnostics
Incorrect supply voltage
report
reaching unit
Supply Fault
Diagnostics
Fault on the unit's digital
report
PCB
DSP Fault
Diagnostics
A fault has been detected in
report
the NV-RAM
NV-RAM Fault
Diagnostics
The time and date record
report
being stored by the Real
RTC Fault
Time Clock (RTC) has been
lost
Diagnostics
Voltage reference fault
report
detected
Volt Ref Fault
65
1) Re-align the Receiver, first using the
telescope and then using the Interrogator.
2) Re-zero the unit.
1) Check the Transmitter and Receiver
windows for build up of contamination.
Clean windows if required.
2) Re-zero the unit.
Re-zero the unit
1) When Ex certified equipment is
operated outside its certified range, its
type approval certification is invalidated
along with its warranty.
Such equipment should be removed from
service in potentially explosive
atmospheres.
2) Investigate the cause of the excessive
temperature excursion and take steps to
prevent recurrence. (e.g. fit sunshade or
heat-shield, or relocate detector, etc.)
1) Check that the +24V supply voltage is
reaching the unit
(it should be between +18V and +32V).
2) Identify the cause of incorrect supply
voltage reaching the unit and rectify.
If this fault is displayed when the unit is
interrogated, it cannot be remedied
in the field.
If this fault is displayed when the unit is
interrogated, it cannot be remedied
in the field.
1) Re-enter the time and date using the
Interrogator.
2) Cycle the power applied to the unit.
3) Verify that the time and date record was
maintained after cycling the power.
If this fault is displayed when the unit is
interrogated, it cannot be remedied in the
field.
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
6. SPECIFICATIONS
6.1 SYSTEM
SHORT RANGE
Available Gases
OPEN-PATH
MEDIUM RANGE LONG RANGE
All: Methane, Ethane, Propane, Butane, Pentane, Ethylene, Propylene, Butadiene.
Range
0 - 5 LELm
0 - 5 LELm
0 - 5 LELm
Recommended
Alarm Setting
Low 1 LELm
High 3 LELm
Low 1 LELm
High 3 LELm
Low 1 LELm
High 3 LELm
Minimum Alarm
0.5LELm 0.5LELm 0.5LELm
Setting
Path Length
5 - 40m
(15 - 130ft)
40 - 120m
(130 - 390ft)
120 - 200m
(390 - 650ft)
Speed of
Response
T90 less
than 3seconds
T90 less
than 3seconds
T90 less
than 3seconds
Output signal
4 – 20mA
Normal operation
(0 – 5LELm)
4 – 20mA
Normal operation
(0 – 5LELm)
4 – 20mA
Normal operation
(0 – 5LELm)
Operating Temp.
All: -40°C to +65°C (-40°F to +150°F)
Humidity
Pressure
All: 0 – 99%RH Non-condensing
All: 91.5kPa – 105.5kPa (915 – 1055mBar, non-compensated)
Repeatability ±0.4LELm ±0.4LELm ±0.4LELm
Temperature
Drift (-40°C to+65°C)
±0.2LEL.m @ zero ±0.2LEL.m @ zero ±0.2LEL.m @ zero ±10%LEL (%LEL/m) @ zero
±0.5LEL.m @3LEL.m ±0.5LEL.m @3LEL.m ±0.5LEL.m @3LEL.m ±15%LEL (%LEL/m) @ 60%LEL
Warm-up Time
All: less than 5 minutes (operational), Less than 1 hour (fully stabilised)
Power Supply
All: 18 to 32V
Power Consumption * Turbo heating activated (below 0°C)
Transmitter
Receiver
3.5/5* W max
8W maximum
5.5/7.5* W max.
8W maximum
Enclosure Material
5.5/7.5* W max.
8W maximum
All: 316 Stainless Steel
Weight
Transmitter
3.5kg 7.0kg 7.0kg
Receiver 3.5kg 3.5kg 3.5kg
Vibration
All: 2 – 60Hz, maximum peak to peak amplitude 1mm.
Divergence/
±0.5°
Misalignment (~±35cm
Tolerance
at 40m)
±0.5°
±0.5°
(~±105cm (~±175cm
at 120m)
at 200m)
IP rating
All: IP66/67
66
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
6. SPECIFICATIONS
6.2 DETECTABLE GASES
The Searchline Excel Open-Path gas detector (short, medium and long range) will detect the
following hydrocarbon gases, individually or in a mixture, in the range 0-5%LEL.m:
Methane
CH4
Ethane C2H6
Propane
C 3H 8
Butane C4H10
Pentane
C5H12
Ethylene
C 2H 4
Propylene
C 3H 6
Butadiene
C 4H 6.
Searchline Excel Raw Gas Response Before Linearity Correction
Methanol
Relative Response
Ethane
Propane
Butane
Methane
Ethylene
Hexane
Ethanol
Propylene
Butadiene
Pentane
LEL.m
Cross-sensitivity to other gases
67
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.1 GENERAL
The Searchline Excel system is certified to Ex d and has the following major ATEX, IECEx, UL
and CSA approvals for worldwide acceptance:
ATEX & IECEx
II 2G, Ex d IIC T5 (Tamb -40 to +65oC) Gb
Ex d IIC T6 (Tamb -40 to +40oC)
Certificate Numbers:
Open Path Short Range Transmitter, and Receivers: BAS98ATEX2165X.
Open Path Long Range/Mid Range Transmitters:BAS98ATEX2299X.
Open Path Short Range Transmitter, and Receivers: IECEx BAS 09.0100X
Open Path Long Range/Mid Range Transmitters: IECEx BAS 09.0101X
UL
Class 1 Groups B, C, D
Class 1 Zone 1 AEx d IIB + Hydrogen (Amb -40oC to +65oC)
File No. E91044
CSA FM
Class 1 Div 1 groups B, C, D, T5 and
Class I Div 1 groups B, C, D & T5
Exd IIC T5 (Amb -40 to +65oC)
(Tamb -40 to +65oC)
File No. LR 48148-38
The Searchline Excel system has been designed, built and tested to meet the latest European
standards for Radio Frequency Immunity (RFI).
It has been tested and approved to the following British Standards Institute (BSI) regulations:
EN50270:2006.
68
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.2 ATEX & IECEx
7.2.1 Transmitter Details
Open-Path
Transmitter
M25 gland
Ex d IIC T5 (-40 to +65 ° C) Gb
Ex
e,
Ex d, IECEx d
Ex d IIC T6 (-40 to +40 ° C)
&
IECEx
d Certified.
II 2G
(customer supply)
V max. = 32V
Note: Later units
will be 1/2" NPT
Standard Junction Box
Ex e, Ex d, IECEx d
& IECEx d Certified.
M20 gland
Ex e, Ex d, IECEx d
& IECEx d Certified.
Flexible Conduit 900mm long
Ex e, Ex d, IECEx d & IECEx d Certified.
(see table of Conduit Technical Characteristics)
7.2.2 Receiver Details
Open-Path
DVC100 Termination Unit
DVC100(M)
MK2
Unit
EEx ia
e mTermination
IIC
Certified M25
SHC1 Handheld
o IIC
II
2G
Ex
ia
e
m
T6 (-40 to +65 C)
blank fitted
T5 (-40 to +65°C)
Interrogator
Receiver
V max. = 50V,
V
max.
=
32V
Ex ia IIC
Ex d IIC T5 (-40 to +65 °C) Gb
I max. = 5A
Cable
glands
M20/M25
T4
(-40
to +40oC)
Ex d IIC T6 (-40 to +40 °C)
Cable glands M20/M25
II 2G
V max. = 32V
Note:
Later units 1/2" NPT gland
1
/2" NPT
M20 gland Ex e
(customer supply)
Flexible Conduit 900mm long
M20 gland
(see table of Conduit
Ex
e,
Ex d, IECEx d
Technical Characteristics)
& IECEx d Certified.
69
Certified M20
IS Cable
blank fitted Length 15m max.
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.2.3 Conduit Technical Characteristics
Ingress Protection
IP66 and 67.
Temperature Rating
-40 to +105oC.
Construction
A helically wound galvanised steel core with cotton packing
and enhanced oil resistant PVC covering. Covering material
displays good resistance to dilute acids, alkalis and
hydrocarbon products.
Colour Grey
Electrical Flash Voltage
More than 24kV.
Insulation Resistance
More than 100M ohms.
Connector Pull off Classification
FRG04: Heavy.
Conductor Crush Classification
FRG04: Heavy.
Flame Propagation
Flame dies in less than 30 seconds after ignition source is
removed.
Approvals
Bureau Veritas.
7.2.4
Certification Labels Receiver and Short Range Transmitter
Identification
number of ATEX
notified body
Product name
and part number
CE mark
Conforms to all
applicable
European directives
Certified ambient
temperature
Explosion protection
mark and equipment
group and category
Modification status
Serial number
Warning
Certification
numbers
Certification code as
EN60079-0:2006 and
EN60079-1:2004
70
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
Certification Label - Mid Range Transmitter
Certification Label - Long Range Transmitter
71
72
ANY SUITABLE ATEX/IECEx
APPROVED SENSOR/DETECTOR
SENSOR/
DETECTOR
SENSOR ENTRY
ANY SUITABLE ATEX/IECEx
APPROVED SENSOR/DETECTOR
OPTIONAL
TRANSMITTER/
SENSOR
TRANSMITTER/SENSOR ENTRY
HANDHELD
CALIBRATOR
TYPE SCH 1
Baseefa03ATEX0073
IECEx BAS 09.0120
OPTIONAL
SUPPLY ENTRY
COMMUNICATIONS
FIXED SOCKET I.S.
OUTPUT TO CALIBRATOR
(FACTORY FITTED)
TERMINATION UNIT
DVC100 (M) MK2
Baseefa 03ATEX0261
IECEx BAS 09.0125
HAZARDOUS AREA
APPARATUS WHICH IS UNSPECIFIED EXCEPT THAT
IT MUST NOT BE SUPPLIED FROM, NOR CONTAIN
IN NORMAL OR ABNORMAL CONDITIONS, A
SOURCE OF POTENTIAL WITH RESPECT TO EARTH
IN EXCESS OF 250V rms OR 250V d.c.
INSTALL IN COMPLIANCE WITH IEC 60079-14
ENTRIES: ANY SUITABLY APPROVED Ex e, Ex d,
IECEx e & IECEx d CABLE GLAND/CABLE.
ENTRIES MUST BE SEALED TO PROVIDE A DEGREE
OF PROTECTION OF AT LEAST IP54.
SENSOR ENTRY: EITHER DIRECTLY CONNECTED
OR VIA SUITABLE GLAND - SEE NOTE 3.
1.
2.
3.
4.
5.
NOTES:
CONTROL
EQUIPMENT
NOTE 1
SAFE AREA
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.2.5 System Diagram
73
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.2.6 ATEX Special Conditions of Safe Use
7.2.6.1 Receiver and Short Range Transmitter
The integral supply cables must be mechanically protected and terminated in a suitable terminal
or junction facility.
The cover fixing screws shall be grade 12.9 minimum.
7.2.6.2 Mid and Long Range Transmitters
The integral supply cables must be mechanically protected and terminated in a suitable terminal
or junction facility.
74
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.3 UL
7.3.1 Transmitters
Open-Path
Transmitter
Class I Div 1 Groups B, C & D and
Class I Zone 1 AEx d IIB +
H2 (Tamb -40 to +65 C)
UL approved explosion
proof junction box
Conduit seal
required
(see OEM J/B
details)
UL approved M20/
½ NPT adaptor
Note: Later units
1
/2" NPT threaded
without adaptor
Flexible conduit (customer supplied)
- must conform with the relevant US
installation codes of practice
7.3.2 Receivers
Open-Path
Receiver
Class I Div 1 Groups B, C, D
Class I Zone 1 AEx d IIB + H2
(Tamb -40 to +65 C)
DX100/DX100 (M) UL
Termination Unit
Class I Div 1
Groups B, C, D
(Tamb -25 to +40oC)
SHC1 Handheld
Interrogator
Class I Div 1
Groups B, C, D
(Tamb -50 to +40 C)
UL approved
M20/0.5in. NPT adaptor
Note: Later units 1/2" NPT
threaded without adaptor
Flexible conduit (customer supplied)
- must conform with the relevant US
installation codes of practice
(see Control Drawing 2104E0045)
75
IS Cable
Length 15m max.
Conduit
seal
required
within 6"
of enclosure
(see OEM
details
for J/B)
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.3.3 System Diagram
With DX100 Termination Unit
76
77
ANY SUITABLE UL LISTED
OR CLASSIFIED EXPLOSION
PROOF APPARATUS.
SENSOR
SENSOR ENTRY
(CONDUIT CONNECTION
REQUIRED WITH SEAL)
OPTIONAL TRANSMITTER
SEARCHLINE EXCEL FILE
No. E91044
COMMUNICATIONS
FIXED SOCKET I.S.
OUTPUT TO CALIBRATOR.
(FACTORY FITTED)
TERMINATION
UNIT DX100 (M)
UL FILE E136193
TRANSMITTER ENTRYP(CONDUIT
CONNECTIONPREQUIRED WITH SEAL)
HAZARDOUS (CLASSIFIED) LOCATION
CLASS 1 DIV. 1 GROUPS B,C,D.
HANDHELD
CALIBRATOR
TYPE SHC 1
UL FILE E136193
SUPPLY ENTRY (CONDUIT
CONNECTION REQUIRED
WITH SEAL)
NOTE 2
APPARATUS WHICH IS UNSPECIFIED EXCEPT THAT IT
MUST NOT BE SUPPLIED FROM, NOR CONTAIN IN NORMAL
OR ABNORMAL CONDITIONS A SOURCE OF POTENTIAL
WITH RESPECT TO EARTH IN EXCESS OF 250V rms
OR 250V d.c.
WIRING FROM THE HANDHELD CALIBRATOR (SHC1) TO
THE TERMINATION UNIT (DX100) IS NOT TO EXCEED
15 METRES MAX.
INSTALL EQUIPMENT INCLUDING FIELD WIRING IN
ACCORDANCE WITH ARTICLES OF THE NATIONAL
ELECTRICAL CODE FOR DIVISION 1HAZARDOUS
LOCATIONS.
1.
2.
3.
NOTES:
CONTROL
EQUIPMENT
NOTE 1
NON HAZARDOUS AREA
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
With DX100 (M) Termination Unit
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
7.4 CSA/FM
7.4.1 Transmitters
CSA Transmitter:
Class 1 Div 1 Groups B, C & D T5
and Exd 11C T5 (Tamb -40 to -40 to +65oC)
FM Transmitter:
Class 1 Div 1, Groups B, C & D (-40 to -40 to +65oC)
CSA/FM approved
explosion proof
junction box
CSA approved
M20/ 1/2 NPT threaded
without adaptor
Note: Later units 1/2" NPT
threaded without adaptor
7.4.2 Receivers
Conduit seal
Flexible conduit (customer supplied) required
must conform with the relevant US
(see OEM J/B details)
and Canadian installation codes of
practice (conduit seal required within
30" of transmitter)
Handheld
SHC1 SHC1
Handheld
DX100/DX100(M) CSA
Receiver
CSA Receiver:
Interrogator
CSA/FM
Interrogator
Termination
Unit
DX100/DX100(M)
CSA/FM
I DivB,
1 Groups
B, C, D
Class 1 DivClass
1 Groups
C,
ClassClass
I Div 11 Div 1
Class
I DivI 1Div 1
Termination Unit
Class
D, T5 & Exd 11CT5
T5and Exd IIC T5
Groups
B, C, D
Groups
B, C, D
Groups
B,
C,
D
o
B, C, D (Tamb -40oto +65oC)
o
o
(Tamb
C)
(Tamb -40 to +65
C) -40 to +65Groups
(Tamb -55
to +40
(Tamb -55 to +40 C)
(Tamb
-40C)to +65oC)
FM Receiver:
Class 1 Div 1
Groups
B, C & D
(-40 to +65oCSA
C) approved
M20/0.5in. NPT adaptor
CSA approved
M20/0.5in. NPT adaptor
Conduit
seal
required
within
6" of enclosure
(see OEM
J/B details)
1
/2" NPTconduit (customer supplied) Note: Later unitsFlexible
threaded withoutmust
adaptor
Flexible
(customer supplied) - IS Cable
conform
with conduit
the relevant
15m max.
conform
withofthe
relevant US Length
and
Canadian must
installation
codes
practice
Canadian
codes of practise
(see Control
Drawinginstallation
2104E0097)
IS Cable
(conduit seal required within 30" of transmitter)
Length
15m max.
78
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
SHC1 Handheld
SHC1 Handheld
DX100/DX100(M) CSA
CSA Receiver:
Interrogator CSA/FM
Receiver
Interrogator
Termination
Unit
Class 1 Div
1
Groups
B,
C,
D
DX100/DX100(M)
CSA/FM
Class 1 Div 1
Class I Div 1 Groups B, C, D
Class
I Div 1
Class
I
Div
1
Class 1 Zone 1
IIB +IIC
H2T5 Termination Unit Class I Div 1
Groups B, C, D
T5AEx
anddExd
Groups B, C, D
Groups
B, C, D
(Tamb -40 to (Tamb
+65oC)-40 to +65oC)Groups B,
C, D (Tamb
-25 to +40oC)
(Tamb -50 to +40oC)
(Tamb -55 to +40oC)
(Tamb -55 to +40oC)
FM Receiver:
Class 1 Div 1
Groups
B, C & D
(-40 to +65oC)
CSA approved
M20/0.5in.
NPT adaptor
UL approved
M20/0.5in. NPT adaptor
Note: Later units 1/2" NPT
Flexible
conduit (customer supplied) threaded without
adaptor
IS Cable
must conform Solid
with the
relevant
conduit
(customer supplied) Length 15m max.
Canadian installation
codes of
practice
must conform
with
the relevant US and
(see Control Drawing
2104E0097)
Canadian
installation codes of practice
(conduit seal required within 30" of transmitter)
79
Conduit
seal
required
within 6"
of enclosure
(see OEM
details
for J/B)
IS Cable
Length
15m max.
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
CSA/FM Certification Label
Standard Transmitter
Standard Receiver
Long-Range Transmitter
80
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
81
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
7. CERTIFICATION
With DX100 (M) Termination Unit
82
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
A.1 INTRODUCTION
This appendix provides reference information about the SHC1 Handheld Interrogator.
The interrogator provides the user end of a two-way communication link between the Excel
system and the operator.
It features facilities which let the operator configure, align, functionally test and diagnose faults
in the system.
The appendix gives:
•
an overview of the interrogator features
•
information about how to connect the interrogator to the Excel systems
•
basic user tasks, including switching on/off and changing the battery
•
a detailed description of the menus which the interrogator provides
•
problem solving information if trouble occurs when using the interrogator
Details of how to use the interrogator for different tasks with the system are given Chapter 3
and Chapter 4 of this handbook.
A.2 OVERVIEW
The interrogator consists of an LCD screen and four keypad buttons. It links to the Excel
Receiver unit via an IS connector on the end of a flexible cable connected to the associated
junction box.
LCD screen
Up key
Escape key
Enter key
Down key
SHC1 Handheld Interrogator Main Features
83
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
The interrogator is powered by a standard 9V battery and has a management system which
reduces power consumption by placing the unit in an idle mode when it is waiting for user input
or for a communication operation to complete.
The interrogator also features a 2k byte non-volatile RAM (NV-RAM) split into two sections.
These sections are used to store the current operating mode and a backup copy.
Liquid Crystal Display Screen
This screen consists of a two-line, 16-character dot-matrix liquid crystal display (LCD). The
screen displays messages which communicate information from/to the user.
It displays a menu system that enables the user to select the command mode for the system,
and can also display information about the system configuration and its settings, plus any error
messages.
Keypad Buttons
The four keypad buttons are used to provide operator input in response to messages shown
on the display.
This includes menu option selections and changing parameter values. The four buttons are:
Up
Move to the previous menu option, list item, or increase a displayed data value.
Down Move to the next menu option, list item, or decrease a displayed data value.
ESC Escape Quit the current menu level or operation and return to the previous menu, e.g.
stop displaying a list, abort a command. No change if already at the top level.
Enter Select, i.e. Invoke/accept, the currently displayed menu option, list item, data
value, or configuration change.
Note: If the and keys are used to advance beyond the end of a list a wrap around to the
other end of the list occurs.
A.3 CONNECTION TO SYSTEM
Details of how to connect the interrogator to the Searchline Open-Path system are given in
Chapter 3. The diagram shows a typical example.
Calibrator
Type SHC1
ESC
Note: If not connecting to a DVC100 series or DX100 series termination unit the SHC Protection
Device must be used.
84
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
A.4 BASIC USER TASKS
Switching On
(1) Press
for two seconds.
The unit recalls its previously set operating mode, i.e. EXCEL, OPTIMA or OPTIMA
PLUS, and displays the following message for approximately three seconds:
Z - SHC1 EXCEL
Interrogator 4V0
The unit then displays the top level of the menu style interface in the following way:
>
>
Main
Display
During use the first line of the display shows the current level in the menu tree.
The second line displays the sub menu title, action to be invoked, or data value to be
checked/changed.
Note: To change the operating mode at switch-on, e.g. from OPTIMA to EXCEL, press the
ESC key whilst the initial message is displayed. This changes the mode and re‑displays
the message.
Switching Off
(1)
Select the Power Off option from the Main Menu,
Alternatively press the
and ESC buttons simultaneously for a fast power off.
Notes:
1.
The unit powers down automatically after five minutes of non-use.
2.
The fast power off facility and auto power off are disabled when a menu option is selected
that modifies the interrogator’s configuration.
CAUTION
Only use batteries specified below.
Replace the battery only in a Safe Area.
To replace the battery in the Hand-Held Interrogator SHC-1 proceed as follows:
OLDER ATEX VERSIONS CERT. NO. Baseefa03ATEX0073X, IECEx BAS 09.0120
ONLY USE DURACELL MN1604 TYPE 6LR61
(1)
Remove the Interrogator from its protective pouch.
(2)
Using a 2.5mm allen hexagonal key, loosen the four screws on the rear cover of the
Interrogator.
85
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
3)
Carefully lift the front half of the Interrogator away from the rear cover, ensuring the
flexible connector connecting the keypad to the electronics module is not damaged.
(4)
Unclip the old battery and fit the new battery in position (Re-use protective sleeve.
(5)
Carefully replace the front half of the Interrogator back into the rear cover, ensuring the
flexible connector lies flat.
(6)
Using a 2.5mm allen hexagonal key, tighten the four screws on the rear cover of the
Interrogator.
A.5 MENUS
The interrogator top level menu structure and menu choices are as follows.
All menu options are implemented by pressing the keypad
are shown in the diagram:
86
key. The menu options and types
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
where:
a single set of data is displayed.
D
DL a list of data is displayed - use the and keys to navigate the entries in the list.
Sub another menu of options is displayed when this choice is selected - use the
and
keys to navigate the sub menu choices.
Sw the displayed option is immediately activated.
Tog the displayed option is toggled between three choices using the and keys.
Chapter 3 and Chapter 4 of this handbook describe how the Interrogator and menus are used
when the system is being installed/in use.
A.5.1 Main Menu
This menu consists of the following sub menu options:
Display
Display gas and other unit readings.
Calibrate
Install and calibrate the system, force the analogue output,
show the calibration coefficients or show the instrument
status.
Diagnose
Inspect the fault and warning logs, perform a self-test or
perform a soft reset.
Config
Read the configuration parameters of the unit, update the
user configuration parameters.
Chg Mode
Toggle the operating mode of the interrogator.
Power Off
Switch the interrogator off.
A.5.2 Display Menu
This sub menu displays gas and other unit readings. It has the following options:
Gas Reading
Display the gas type and system status.
Signal magnitude
Show the level of the sample and reference signals.
Dynamic Reserve
Shows the acceptable drop in signal level before beam block
occurs as a percentage of the current signal level.
S/W Version
Displays the system software version and the current time and
date.
Gas Reading
Display the gas type and system status. The display is in the following format:
Excel gggggggg
rrrrrr uuuu /
where:
gggggggg Gas name. For a special gas table this shows where
nnn is the identifier.
87
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
rrrrrr
Gas reading.
uuuu Measurement units.
/
This is a status character which indicates one of the following:
/
-
A spinning line shows the system is operating
normally
i.e. in a fully active state.
|
-
A stationery line shows the system is in an inactive
state.
W
-
Active Warning.
F
-
Active Fault.
B
-
Beam Block.
A
- Alarm
Signal Magnitude
Show the level of the sample and reference signals.The display is in the following format:
Sample: aaaaaaa
Ref:
bbbbbbb
where:
aaaaaaa
bbbbbbb
Signal magnitude for the sample channel.
Signal magnitude for the reference channel.
Dynamic Reserve
Shows the acceptable drop in signal level before beam block occurs as a percentage of the
current signal level.The display is in the following format:
Dynamic Reserve:
xxx.xx %
where: xxx.xx
The acceptable drop in signal level before beam block measured as a
percentage of the current signal level.
S/W Version
Displays the system software version and the current time and date. The display is in the
following format:
Excel S/W vvVvv
hh:mm dd/mm/yy
where:
vvVvv
hh.mm
dd/mm/yy
Version number of the Excel system software.
System time as hours and minutes.
System date as day of the month, month number and the last two
digits of the year.
Note: The year 2000 is displayed as 00.
88
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
A.5.3 Calibrate Menu
This sub menu is used when installing and calibrating the system. It has the following
options:
Display
Display system readings.*
Install
Direct the alignment and initialisation of the system.*
Set Time
Set the system real time clock time and date.
Cal Sensor
Calibrate the system zero.*
Force mA
Fix the 4-20mA analogue output at a selected level.
Normal mA
Restore the analogue output to its normal output state.
Show Status
Show the calibration and configuration status of the system.
The options marked with an asterisk, (*), require the system’s analogue 4-20mA output to be
inhibited during their operation. Where this occurs then the following sequence is automatically
added to the affected operation.
Before the selected sub menu operation is started the following message is displayed for at
least three seconds:
Inhibiting 4-20
Please Wait
The analogue output is inhibited and the chosen sub menu operation proceeds. After the sub
menu operation is completed, or aborted by pressing the ESC key, the following message is
displayed:
Press Enter To
Release 4-20
Press
to release the 4-20 receiver output and the following message will be displayed for
three seconds:
4-20 Released
Display
Display system readings. This choice is the same as the GAS READING DISPLAY option on
the DISPLAY MENU.
Notes:
1.
The 4-20 output is inhibited during the display. See the earlier description.
2. No spinning line is displayed as the receiver is not in a fully activated state.
Install
This choice is used to complete the alignment and commissioning operations after the system
is mechanically and electrically installed. It provides a sequential set of operations to:
89
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
•
view the system type
•
set the system path length
•
perform a system self test
•
check system alignment
•
initialise the system and make it live
Note: The 4-20 output is inhibited during this procedure. See the earlier description.
System Type
The initial display after Install is chosen is in the following format:
where: tttttttt
>
>
System Type
tttttttt
System type. The system type displayed is one of the following:
Display Text
System Type
Short Range
40m range system
Medium Range
120m range system
Long Range
200m range system
Duct Mount
0.5 - 5m range system
Note: It is not possible to change the system type. This is set during calibration and configuration
of the unit at the factory.
Path Length
The following message is displayed:
Path Length
nnnn
where: nnnn
The path length in metres.
The following ranges of path length can be entered for the system types:
System Type
Minimum Range (m)
Maximum Range (m)
Short Range
5
40 1
Medium Range
20
120 1
Long Range
120
200 1
Duct Mount
0.5
5 0.1
90
Step Size (m)
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Self Test
This starts the system self test process.
The following message is displayed:
Press Enter to
Perform checks
This message is displayed during the self test process after pressing Enter.
Processing Data
Please Wait
This message is displayed for three seconds at the end of a successful self test process.
Checks Passed
Alignment
This starts the alignment process.
The following message is displayed:
Press Enter to
Align Unit
This message displays the system output and reference signal values.
SIG:
MAX:
where:
A bar graph representing the current signal magnitude - SIG:
A bar graph representing the target signal - TGT:
Important Notes:
1)
2)
3)
4)
5)
The overall objective of alignment is to maximise the SIG level. Maximised SIG corresponds
to optimal alignment.
The Instrument Assisted Alignment (IAA) system only allows Excel to be initialised if the
SIG level is greater than or equal to the TGT level when Enter is pressed.
The smallest TGT signal level that is initially set will be equivalent to 70% (0.700) of the
signal expected for the installation’s path length.
The TGT level will increase gradually if the current SIG level is larger than the TGT level.
The TGT signal level only ever increases. If the current SIG level falls below the TGT
level, TGT will remain at its previous highest value. In order to initialise the gas detector
the SIG level must be brought back above the TGT level.
If the SIG level is less than 50% of the expected level, the bar graphs are not displayed.
Instead both SIG and TGT levels are displayed as numbers.
91
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Options
The approach to mechanical alignment depends on the type of alignment telescope and mounting
initially used to set up the Excel gas detector, also see Chapter 3.
Bayonet-style Trident-type telescope assembly
If this type of alignment telescope was used with a Trident-type Excel gas detector, there is no
need to further optimise the alignment using the SHC1 Handheld Interrogator.
When the SIG and TGT bar graphs are displayed on the SHC1 screen, SIG will always be
greater than TGT and installation can proceed to the next stage by pressing Enter and following
step 12.
Latch-style telescope assembly
If this type of alignment telescope was used with a Trident-type Excel gas detector, there is no
need to further optimise the alignment using the SHC1 Handheld Interrogator.
If this type of alignment telescope was used with a non-Trident Excel it may be necessary to
further optimise the alignment in the following way in order to achieve best performance.
(a)
After the SIG and TGT bar graphs are displayed on the SHC1 screen as previously
described, let the TGT level reach its initial maximum by waiting for approximately
10 seconds.
During this time the TGT level will move up towards the current SIG level.
(b)
Whilst watching the SIG level closely, make a small mechanical adjustment in either
the horizontal or vertical alignment and note whether the SIG level goes up
or down.
(c)
If the SIG level goes up, make another small mechanical adjustment in the same
direction as before.
(d)
If the SIG level goes down, change the direction of adjustment.
Maximise the SIG level by making small adjustments in only one plane at
a time.
(e)
When the SIG level has been maximised in one plane, make small adjustments in
the other plane until SIG has been maximised in this plane.
(f)
Repeat steps (b) to (e) until the SIG level has been maximised in both planes.
At this point, SIG must be bigger than the initial TGT level and any adjustment either
side of the current alignment must result in a reduction in signal level.
If not, repeat steps (b) to (e) until these requirements have been met.
(g)
Lock off the alignment by placing a hex (Allen) key in the pair of grub-screws
which control adjustment in a particular plane and simultaneously rotating them
in opposite directions.
(h)
Repeat this for the other pair of grub-screws.
(i) Press Enter and the signal levels are checked.
Provided that the SIG level is greater than the TGT level, the signal check should pass on to
the next stage of installation.
92
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Initialisation
This starts the initialisation process. The following message is displayed:
Press Enter to
Initialise Unit
This message is displayed during the initialisation process after pressing Enter.
Processing Data
Please Wait
This message is displayed for three seconds at the end of a successful initialisation process.
Unit Initialised
Note: The Searchline Excel system is live after a successful initialisation.
Set Time
This option lets you set the system’s time and date.
The initial display after SET Time is chosen is in the following format:
where:
hh
mm
>
>
Time HH:MM
hh:mm
Hours.
Minutes.
When first displayed only the current hour is shown.
All settings are adjusted by means of the
and
keys on the keypad.
After setting the hour the minutes are displayed.
After the time has been entered then the same process is used to set the date which is displayed
in the following format:
where:
dd
mm
yy
>
>
Date DD/MM/YY
dd/mm/yy
Day.
Month.
Last two digits of the year.
Notes:
1.
The time and date will not be updated unless both are entered and accepted without
error.
2.
The year 2000 is displayed as 00.
93
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Cal Sensor
This menu option zeros the system.
Notes:
1.
The 4-20 output is inhibited during this procedure. See the earlier description.
2.
There must be no gas in the system beam path whilst this procedure is carried out.
The following message is displayed:
Ensure Zero Gas
Press Enter
The following message is displayed while the calibration operation is being performed:
Processing Data
Please Wait...
If the calibration is successful, the following message is displayed for a period of three
seconds:
Zero Calibrated
Force mA
This option allows the system’s analogue output signal to be adjusted to a fixed level, e.g. when
setting up a system controller. The following message is displayed:
where:
>
>
O/P current mA
mmmmm
mmmmm Current to output.
This is adjusted using the
and
keys over the range 1mA to 21mA in steps of 0.1mA.
After adjustment the output is forced to the set level and the following message is displayed:
Fixed: mmmmm mA
Press Enter
where: mmmmm Analogue output current previously set.
Normal mA
This menu option returns the system to its normal analogue output state, irrespective of its
previous state. If successful, the following message is displayed for three seconds:
4-20mA Released
94
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Show Status
This menu option displays the calibration and configuration status of the system. The status
information is displayed in the following format:
cccccccccccccccc
ssssssss
where: cccccccc...
Title of the calibration status field.
sssssssss
Current state of calibration.
The different settings from the list are selected using the
and
keys on the keypad.
The calibration status fields and values are given below:
Calibration Status Fields
Display Text
False State
True State
Temperature Cal.
Temp Sensor
Uncalibrated Calibrated
Zero Calibration
Zero Ratio
Uncalibrated Calibrated
Span Calibration
Span Sensitivity
Uncalibrated Calibrated
4-20mA Calibration
Analogue Output
Uncalibrated Calibrated
Det. Temp. Comp.
T Compensation
Uncalibrated Calibrated
Det. Sens. Comp.
Det Sensitivity Uncalibrated Calibrated
Installation Installation
Required Complete
Valid Date Time
Date and Time
Estimated Set
Loop Test Analogue Check
Failed Passed
A.5.4 Diagnose Menu
This sub menu has the following options:
Active Faults
Display the active faults in the system.
Active Warns
Display the active warnings in the system.
Self Test
Soft Reset
Perform a diagnostic system self test.
Reset the system.
Active Faults
This menu option displays operational faults when the system is in service.
If there are one or more faults present, then the faults are displayed one at a time.
Use the
and
keys to navigate the list.
If no active faults are present the display shows the following for three seconds:
None Present
The Diagnose sub menu is then displayed.
95
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
If there are one or more faults present, the display shows:
F-hh:mm DD/MM/YY
eeeeeeeeeeeeeeee
where:
F
Indicates that the message displayed is a fault.
hh:mm
Time the fault occurred.
DD/MM/YY Date the fault occurred.
eeeeeee...Fault description. See the following table for a list of error
messages.
See also Chapter 5, Problem Solving.
Display Text
Bad 4-20mA Loop
DSP Fault
Hardware Fault
NV-RAM Fault
RTC Fault
Fault Description
ERR_EXCEL_LOOP_FAULT
ERR_EXCEL_DSP_FAULT
ERR_EXCEL_HW_FAULT
ERR_EXCEL_FRAM_FAULT
ERR_EXCEL_RTC_FAULT
Meaning
A fault has occurred in the 4-20mA signal loop.
Fault on the gas detector’s digital PCB.
A hardware fault has occurred.
A fault has been detected in the unit's NV‑RAM.
The time and date record stored by the RealTime
Clock (RTC) has been lost.
Software Fault
Supply Fault
ERR_EXCEL_SW_FAULT
ERR_EXCEL_SUPPLY_FAULT
An gas detector software error has occurred.
Incorrect supply voltage reaching the gas
detector.
Active Warns
This menu option displays the active warnings in the system. They are displayed in the same
way as described for Active Faults except that a W is displayed instead of F on the first line
of the display.
Display Text
Fault Description
Meaning
Alarm
ERR_EXCEL_LOG_ALARM
The Excel log has become damaged.
Bad Temperature ERR_EXCEL_TEMPERATURE_LIMIT Unit has been operated at a temperature
outside its specified and certified range.
Baseline Drift
ERR EXCEL_DRIFT_LIMIT
Beam Blocked
ERR_EXCEL_BEAM_BLOCKED
Neg Gas Reading ERR_EXCEL_NEGATIVE_DRIFT
Not Installation
ERR_EXCEL_BAD_INSTALLATION
Overrange
ERR_EXCEL_OVERRANGE
Power Failed
ERR EXCEL_LOG_POWER_FAIL
Reset Occurred
ERR_EXCEL_RESET
Time Adjusted
ERR_EXCEL_LOG_TIME_ADJUST
Uncalibrated
ERR_EXCEL_UNCALIBRATED
Volt Ref Fault
ERR_EXCEL_VOLTAGE_REF_FAIL
96
Drift of unit’s baseline.
The infrared beam between the Transmitter
and Receiver has become blocked.
Negative drift of gas detector’s zero position.
Incorrect gas detector installation has
occurred.
An overrange signal has occurred.
The gas detector has suffered an internal
power failure.
A gas detector reset has occurred.
The Excel log time has been changed.
The gas detector requires calibration.
Voltage reference fault detected.
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Self Test
This option lets you start a system diagnostic self test.
The following message is displayed during the self test process:
Processing Data
Please Wait
The following message is displayed for three seconds at the end of a successful self test
process.
Checks Passed
Soft Reset
This option lets you reset the system.
This message is displayed during the reset process:
Processing Data
Please Wait
The following message is displayed for three seconds when the process is completed:
Unit Reset
A.5.5 Config Menu
This sub menu lets you check the configuration parameters of the unit and update the user
configuration parameters. It has the following options:
Show Gas
Show the gas related configuration parameters.
Show Config
Show the user related configuration parameters.
Show Install
Show the installation related configuration parameters.
Show Gas
This option displays the useful gas table configuration parameters in the following way:
cccccccccccccccc
vvvvvvvv
where:
ccccccc... Title of the configuration setting.
vvvvvvvv
Setting value.
Note: The settings are not field configurable:
97
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Gas Configuration Parameters Display Text
Step Size
Min Value
Max Value
Gas ID
Gas Ident
0 255 1
1 = Methane
2 = Ethane
3 = Propane
4 = Butane
5 = Pentane
6 = Hexane
7 = Methane (%UEGm)
8 = Ethane (%UEGm)
9 = Propane (%UEGm)
10 = Butane (%UEGm)
11 = Pentane (%UEGm)
12 = Hexane (%UEGm)
20 = Methane
21 = Ethane
22 = Propane
23 = Butane
24 = Pentane
25 = Hexane
26 = Ethylene
27 = Propylene
28 = Butadiene
29 = Ethanol
30 = Methanol
31 = Methane (%UEGm)
32 = Ethane (%UEGm)
33 = Propane (%UEGm)
34 = Butane (%UEGm)
35 = Pentane (%UEGm)
36 = Hexane (%UEGm)
37 = Ethylene (%UEGm)
38 = Propylene (%UEGm)
39 = Butadiene (%UEGm)
40 = Ethanol (%UEGm)
41 = Methanol (%UEGm)
Gas Units
Gas Units LELm,
PPMm,
UEGm, or
VVm
%LEL (Cross-Duct only)
Effective Full Scale
Gas Full Scale 0.1 100000 0.05
98
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
Show Config
This option displays the configuration parameters the user can set in the same way as for the
Show Gas option. The configurable settings and values are shown in the following table:
Configuration Parameters Display Text
Min Value Max Value Step Size Default Values
Protocol Address
Digital Address
0 255
1 0
Time to Block
Block Warn Time
5s 600s
5s 30
Time to Fault
Block Fault Time
0s 600s
5s 120
Max Response
Maximum T90
1s 60s 1s 60
Analogue Style
Analogue Mode
Inhibit Current
Inhibit mA
0mA
3mA
0.05mA 2.0
Block Current
Blocked mA
0mA
4mA
0.05mA 2.5
Low Signal Current
Low Signal mA
0mA
4mA
0.05mA 3.0
Low Signal Level
Low Signal %
0% 90% 1% 33%
Alarm Threshold
Alarm Threshold
10% 100% 1% 20%
Alarm or Continuous
Report fault due to blockage RPRT Blocked Fault
Enable or Disable
C
E
Show Install
This option displays the installation configuration parameters in the same way as for the
Show Gas option. The configurable settings and values are shown below:
Installation Configuration
Display Text
Description
Parameters
System Type System Type
Short Range
Medium Range
Long Range
Duct Mount
Path Length
Path Length
5m min.
200m max.
0.5m min.
5m max.
1m step
0.1m step
A.5.6 Chg Mode
This menu option toggles the operating mode of the interrogator between Excel, Optima and
Optima Plus to match the gas detector it is attached to. When invoked the mode is displayed
in the identification banner (the same as the one displayed when the unit is switched on) for
three seconds as follows:
Z - SHC1 aaaaaa
Interrogator 4V0
where:
aaaaaa
The type of gas detector that the interrogator is currently set to, i.e. Excel,
OPTIMA or OPTIMA PLUS.
99
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
A.5.7 Power Off
This menu option switches the interrogator off.
Alternatively press the
and ESC buttons simultaneously for a fast power off.
Notes:
1.
The unit powers down automatically after five minutes of non-use.
2.
The fast power off facility and auto power off are disabled when a menu option is selected
that modifies the unit’s configuration.
A.6 PROBLEM SOLVING
Interrogator problems that occur during communication with the system or as a result of a
command failure will be displayed in the following format:
Error: eee
ssssssssssssssss
where:
eee
Error code.
ssssssss... Textual description of the error.
If an error message of this kind is displayed note down the error code and text description and
contact Honeywell Analytics.
100
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
A.7 SPECIFICATION
A.7.1 HAND-HELD INTEROGATOR SHC-1 SPECIFICATION
CERTIFICATION:
ATEX & IECEx: EN60079-0:2006, EN60079-1:2004,
IEC60079-0:2004 Ed.4 and
IEC60079-11 Ed.5.
ATEX: Baseefa03ATEX0073.
IECEx: BAS 09.0120
II 2G Ex ia IIC T4
T4 amb -40°C to +40°C
OPERATING TEMPERATURE RANGE:
0°C to +40°C
(DMT evaluated: -25°C to +55°C)
STORAGE TEMPERATURE RANGE:
-10°C to +40°C
OPERATING HUMIDITY:
0 to 99% RH
DIMENSIONS: Long:
190mm
Depth:
40mm
Width:
80mm
WEIGHT: 0.5kg
MATERIAL: Stainless Steel ANSI 316
101
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX A - HANDHELD INTERROGATOR
A.7.2 SHC PROTECTION DEVICE
WARNING
Not Certified for use in hazardous areas.
Not DMT evaluated.
OPERATING TEMPERATURE RANGE: -
40°C to +65°C
OPERATING HUMIDITY:
0 to 99% RH
DIMENSIONS:
Lead Length: Long: 670mm
Box Dimensions: Long: 78mm
Depth: 39mm
Width: 59mm
WEIGHT: 0.2kg
MATERIAL: High Impact ABS
A.7.3 TERMINATION UNIT DVC100M MK2 SPECIFICATION
CERTIFICATION:
ATEX & IECEx:
EN60079-0, EN60079-7, EN60079-11,
EN61241-18, IEC60079-0:2004 Ed.4,
IEC60079-11:2006 Ed.5, IEC60079-18:2004
Ed.2 AND IEC60079-7:2001 Ed.3.
EEx ia IIC T6 amb -40°C to +65°C
OPERATING TEMPERATURE RANGE:
STORAGE TEMPERATURE:
-40°C to +65°C
(DMT evaluated: -25°C to +55°C)
-10°C to +40°C
OPERATING HUMIDITY:
0 to 99% RH
(DMT evaluated: 5% to 90% RH)
DIMENSIONS: Long: 160mm
Depth: 90mm
Width: 160mm
WEIGHT: 2.0kg
MATERIAL: DMC reinforced polyester
EMC COMPLIANCE: EN50270, susceptibility to 20V/m
(DMT evaluated up to 3V/m)
102
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX B - GLOSSARY
B.1 TERMINOLOGY
Ex d
Flame proof or explosion proof within the confines of European standards EN60079-0 and
EN60079-1. An enclosure that can withstand the pressure developed during the internal
explosion of an explosive mixture and that prevents transmission of the explosion to the
explosive atmosphere surrounding the enclosure.
Ex e
Increased safety within the confines of European standards EN60079-0 and EN60079-7
applied to electrical apparatus that does not produce arcs or sparks in normal service, in
which additional measures are applied so as to give increased security against the possibility
of excessive temperatures.
Instrument Assisted Alignment (IAA)
A method of commissioning the Excel system using the associated electronic Handheld
Interrogator device. The process will not allow the Excel system to initialise unless the
alignment of the Receiver and Transmitter is correct and the signal strength is correct.
IS
Intrinsically safe, apparatus in which the circuits themselves are incapable of causing ignition
of a flammable gas.
Lower Explosive Limit (LEL)
The volume of flammable gas or vapour in air below which an explosive gas atmosphere will
not be formed.
RS485
An industry-wide serial communication link protocol.
Turbo heating
Increased Transmitter window heating at low operating temperatures.
B.2 MEASUREMENT UNITS
LEL.m
Lower Explosive Limit metres. Open path detectors measure the amount of gas present in
the beam. However, they cannot discriminate between a low concentration gas cloud over
a large area and a high concentration gas cloud in a small area. % LEL has little meaning in
this situation and so gas readings of LEL.m are used. LEL.m is calculated by multiplying the
size of a gas cloud by its concentration.
103
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX B - GLOSSARY
An open path alarm set at 1 LEL.m would be triggered by any of the situations shown below:
100% 50%
LEL LEL
1m
10%LEL
2m
10m
LEL.m monitoring is particularly beneficial while the Excel gas detector is protecting the perimeter
of a plant or process, often reducing the quantity of point detectors required. The open path
LEL.m system has the ability to detect leaks that point detectors may miss due to prevailing
or changing wind directions, and can provide early warning of a dilute gas cloud when point
detectors may not register any gas presence.
B.3 ABBREVIATIONS
ATEX
European Hazadous Area Approval
CSA
Canadian Standards Association
DSP
Digital Signal Processor
EMC
Electro-Magnetic Compatibility
IAA
Instrument Assisted Alignment
IECEx International Hazadous Area Approval
IP Ingress Protection
IR Infrared
IS Intrinsically Safe
FM Factory Mutual
LEL Lower Explosive Limit
LR Long Range
MR Medium Range
NPT National Pipe Thread
RFI Radio Frequency Interference
SHC Sieger Handheld Calibrator
SR Short Range
UL Underwriters Laboratories
104
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX C - ACCESSORIES & SPARE PARTS
C.1 SYSTEM UNITS
The following table lists the different types of system units and provides the part numbers for
the various certification options.
All types of Transmitters and Receivers include conduit and glands. Open-Path Transmitters
and Receivers do not include mounting plates and brackets.
Instrument
Searchline Excel Short Range 5m – 40m (15ft - 130ft)
Part Number
Description
02104-N-4011
Short range system 5m to 40m ATEX complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, 1 DVC100M MK2 digital junction
box, 1 junction box Current Source
02104-N-4041
Short range system 5m to 40m ATEX complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, 1 DVC100M MK2 digital junction
box, 1 junction box Current Sink
02104-N-5012
Short range system 5m to 40m UL complete TXR and RXR system, fully wired with flexible
conduit, SS316 mounting plates, brackets, DX100M and Junction Box, Current Source
02104-N-5042
Short range system 5m to 40m UL complete TXR and RXR system, fully wired with flexible
conduit, SS316 mounting plates, brackets, DX100M and Junction Box, Current Sink
02104-N-6012
Short range system 5m to 40m CSA complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates, brackets, DX100M and Junction Box, Current
Source
02104-N-6042
Short range system 5m to 40m CSA complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates, brackets, DX100M and Junction Box, Current Sink
Searchline Excel Medium Range 40m – 120m (130ft - 390ft)
02104-N-4021
Medium range system 40m to 120m ATEX complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, 1 DVC100M MK2 digital junction
box, 1 junction box Current Source
02104-N-4051
Medium range system 40m to 120m ATEX complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, 1 DVC100M MK2 digital junction
box, 1 junction box Current Sink
02104-N-5022
Medium range system 40m to 120m UL complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current
Source
02104-N-5052
Medium range system 40m to 120m UL complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current Sink
02104-N-6022
Medium range system 40m to 120m CSA complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current
Source
105
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX C - ACCESSORIES & SPARE PARTS
02104-N-6052
Medium range system 40m to 120m CSA complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current Sink
Searchline Excel Long Range 120m – 200m (390ft - 650ft)
02104-N-4031
Long range system 120m to 200m ATEX complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, 1 DVC100M MK2 digital junction
box, 1 junction box Current Source
02104-N-4061
Long range system 120m to 200m ATEX complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, 1 DVC100M MK2 digital junction
box, 1 junction box Current Sink
02104-N-5032
Long range system 120m to 200m UL complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current
Source
02104-N-5062
Long range system 120m to 200m UL complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current Sink
02104-N-6032
Long range system 120m to 200m CSA complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current
Source
02104-N-6062
Long range system 120m to 200m CSA complete TXR and RXR system, fully wired with
flexible conduit, SS316 mounting plates and brackets, DX100M, Junction Box. Current Sink
Alternate Calibrations
Excel calibration gas table. Additional costs for non standard calibrations
2104D5001
METHANE / LELM
2104D5002
ETHANE / LELM
2104D5003
PROPANE / LELM
2104D5004
BUTANE / LELM
2104D5005
PENTANE / LELM
2104D5021
ETHYLENE / LELM
2104D5022
PROPYLENE / LELM
2104D5023
BUTADIENE / LELM
Alignment Kits
02104-N-4006
Short range alignment and conformity kit including handheld interrogator, telescope, carry
case and test filters for ATEX approved systems
02104-N-4007
Long and medium range alignment and conformity kit including handheld interrogator,
telescope, carry case and test filters for ATEX approved systems
02104-N-5006
Short range alignment and conformity kit including handheld interrogator, telescope, carry
case and test filters for UL approved systems
02104-N-5007
Long and medium range alignment and conformity kit including handheld interrogator,
telescope, carry case and test filters for UL approved systems
02104-N-6006
Short range alignment and conformity kit including handheld interrogator, telescope, carry
case and test filters for CSA approved systems
106
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX C - ACCESSORIES & SPARE PARTS
02104-N-6007
Long and medium range alignment and conformity kit including handheld interrogator,
telescope, carry case and test filters for CSA approved systems
Accessories
Handheld Interrogator and accessories
04230-A-1001
Hand Held Interrogator ATEX Certified (4V0 software) for Optima, Optima Plus and Excel
2104B2351
Hand Held Interrogator UL Certified (4V0 software) for Optima, Optima Plus and Excel
2104B2354
Hand Held Interrogator CSA Certified (4V0 software) for Optima, Optima Plus and Excel
2108B1455
Hand Held EEPROM upgrade (4V0)
04320-A-1025
SHC Protection Device Module and Lead
2104B6250
SHC Calibrator Connector System 10m
DVC/DX Interfaces
2104B6212
DVC100M MK2 Termination Unit ATEX with MODBUS capability
2104B2382
DX100M XP Termination Unit UL with MODBUS capability
Installation Accessories
2104D0295
Sun/Heat Shade (Deluge Cover)
210-190-045
Killark Junction Box (excludes terminals)
2992A0071
Conduit Assembly for Excel UL certified
0230-0069
Stainless Steel enclosure NEMA 4X 3/4" NPT UL
02104-N-9880
Upgrade to Nickel Plated Glands
Gas Test Equipment
2104N2999
Excel Test filters kit & Manual
2104B2326
Gassing Cell
Spares
2104B2391
Short Range Telescope (bayonet fitting)
2104B2322
Medium / Long Range Telescope (callipers)
210-190-003
Short Range Alignment Case
2104B0300
Searchline Excel Isolation Kit Short Range
2104B0310
Searchline Excel Isolation Kit Medium/Long Range
2104B2301
Mounting Bracket Short Range & Insul. Kit
2104B2302
Mounting Bracket Long Range & Insul. Kit
2104D0237
Mounting Plate
2104B2071
Short Range Transmitter Incl Conduit ATEX
2104B2081
Med Range Transmitter Incl Conduit ATEX
2104B2091
Long Range Transmitter Incl Conduit ATEX
2104B2111
Receiver Std Version Short Range ATEX
2104B2112
Short Range Receiver Sink ATEX
107
MAN0530 Issue 11 - 05/11
2104M0506
Searchline Excel
APPENDIX C - ACCESSORIES & SPARE PARTS
2104B2131
Medium Range Receiver Source ATEX
2104B2132
Medium Range Receiver Sink ATEX
2104B2151
Receiver Standard Version Long Range ATEX
2104B2152
Long Range Receiver Sink ATEX
2104B3001
Short Range Transmitter Incl Approved Adaptor UL
2104B3011
Medium Range Transmitter UL
2104B3021
Long Range Transmitter UL
2104B3101
Receiver Standard Version Short Range UL
2104B3102
Short Range Receiver Sink UL
2104B3111
Medium Range Receiver Source UL
2104B3112
Medium Range Receiver Sink UL
2104B3121
Long Range Receiver Source UL
2104B3122
Long Range Receiver Sink UL
2104B3201
Short Range Transmitter CSA
2104B3211
Medium Range Transmitter CSA
2104B3221
Long Range Transmitter CSA
2104B3301
Short Range Receiver Source CSA
2104B3302
Short Range Receiver Sink CSA
2104B3311
Medium Range Receiver Source CSA
2104B3312
Medium Range Receiver Sink CSA
2104B3321
Long Range Receiver Source CSA
2104B3322
Long Range Receiver Sink CSA
Manuals (Hard Copy)
Note: Electronic copies of the manuals are supplied on CD with each instrument
2104M0506
Searchline Excel and Cross Duct Technical Handbook (English)
2104M0510
Searchline Excel Installation Guide (English)
2104M0409
DVC100(M) MK2 Termination Unit Quick Start Guide Guide (English)
2104M0701
DX100 Series Termination Units Technical Handbook (English)
2104M0523
Searchline Excel Test Filter Leaflet (English)
108
Find out more
www.honeywellanalytics.com
Contact Honeywell Analytics:
Europe, Middle East, Africa, India
Life Safety Distribution AG
Weiherallee 11a
CH-8610 Uster
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
gasdetection@honeywell.com
Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honeywell.com
Technical Services
EMEAI: HAexpert@honeywell.com
US:
ha.us.service@honeywell.com
AP:
ha.ap.service@honeywell.com
www.honeywell.com
Please Note:
While every effort has been made to ensure accuracy in this publication,
no responsibility can be accepted for errors or omissions. Data may change,
as well as legislation and you are strongly advised to obtain copies of the most
recently issued regulations, standards and guidelines. This publication is not
intended to form the basis of a contract.
Issue 11 05/2011
H_MAN0530_ 2104M0506
ECO_A03523
© 2011 Honeywell Analytics
11065
Asia Pacific
Honeywell Analytics Asia Pacific
#508, Kolon Science Valley (I)
187-10 Guro-Dong, Guro-Gu
Seoul, 152-050
Korea
Tel: +82 (0)2 6909 0300
Fax: +82 (0)2 2025 0329
analytics.ap@honeywell.com