Det-Tronics Instructions Multispectrum IR Flame Detector X3301
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions Multispectrum IR Flame Detector X3301 19.4 Rev: 12/13 95-8527 Table of Contents DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . oi (Optical Integrity) . . . . . . . . . . . . . . . . . Communication . . . . . . . . . . . . . . . . . . . . . Data Logging . . . . . . . . . . . . . . . . . . . . . . . Integral Wiring Compartment . . . . . . . . . . . Detector Sensitivity Levels . . . . . . . . . . . . 1 1 2 2 3 3 3 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . 16 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 17 REPLACEMENT PARTS . . . . . . . . . . . . . . . 19 Replacement Parts List . . . . . . . . . . . . . . 19 DEVICE REPAIR AND RETURN . . . . . . . . . 19 GENERAL APPLICATION INFORMATION . . 4 Response Characteristics . . . . . . . . . . . . . 4 Important Application Considerations . . . . 4 ORDERING INFORMATION . . . . . . . . . . . . . 19 Accessories . . . . . . . . . . . . . . . . . . . . . . . 19 X3301 Model Matrix . . . . . . . . . . . . . . . . . 20 IMPORTANT SAFETY NOTES . . . . . . . . . . . . 4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 5 Detector Positioning . . . . . . . . . . . . . . . . . . 5 Detector Orientation . . . . . . . . . . . . . . . . . . 5 Protection Against Moisture Damage . . . . 6 Wiring Procedure . . . . . . . . . . . . . . . . . . . . 6 Setting Device Network Addresses (EQP Model Only) . . . . . . . . . . . . . . . . . 13 APPENDIX A – FM APPROVAL AND PERFORMANCE REPORT . . . . . . . . . . . . . 21 APPENDIX B – CSA APPROVAL . . . . . . . . . 31 APPENDIX C – ATEX APPROVAL . . . . . . . . 32 APPENDIX D – IECEx APPROVAL . . . . . . . 34 APPENDIX E – EN54 APPROVALS . . . . . . . 35 STARTUP PROCEDURE . . . . . . . . . . . . . . . 14 Fire Alarm Test . . . . . . . . . . . . . . . . . . . . . 14 APPENDIX F – OFFSHORE APPROVALS . . . 36 TROUBLESHOOTING . . . . . . . . . . . . . . . . . 14 APPENDIX G – ADDITIONAL APPROVALS . . . 37 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . Cleaning Procedure . . . . . . . . . . . . . . . . . oi Plate Removal and Replacement . . . . Periodic Checkout Procedure . . . . . . . . . Clock Battery . . . . . . . . . . . . . . . . . . . . . . 15 15 15 16 16 INSTRUCTIONS Multispectrum IR Flame Detector X3301 IMPORTANT Be sure to read and understand the entire instruction manual before installing or operating the flame detection system. Any deviation from the recommendations in this manual may impair system performance and compromise safety. ATTENTION The X3301 includes the Automatic o i ® (Optical Integrity) feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. Testing with an external test lamp is not approved or required. A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Microprocessor controlled heated optics increase resistance to moisture and ice. DESCRIPTION The X3301 is a multispectrum infrared (IR) flame detector. It provides unsurpassed detection of fires from light to heavy hydrocarbon fuels combined with the highest degree of false alarm rejection. The detector has Division and Zone explosion-proof ratings and is suitable for use in indoor and outdoor applications. The X3301 housing is available in copper-free aluminum or stainless steel, with NEMA/Type 4X and IP66/IP67 rating. OUTPUTS Relays The standard detector is furnished with fire, fault and auxiliary relays. All three relays are rated 5 amperes at 30 Vdc. The X3301 contains three IR sensors with their associated signal processing circuitry. The standard output configuration includes fire, fault and auxiliary relays. Output options include: –– 0 to 20 mA output (in addition to the three relays) –– Pulse output for compatibility with existing Det-Tronics ® controller based systems (with fire and fault relays) –– Eagle Quantum Premier® (EQP) compatible model (no analog or relay outputs) –– HART communication 19.4 ©Detector Electronics Corporation 2015 The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. The Auxiliary relay has normally open / normally closed contacts, and is configurable for energized or de-energized operation, and latching or nonlatching operation. 1 Rev: 12/13 95-8527 0 to 20 mA Output LED A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions. Table  2 indicates the condition of the LED for each status. A 0 to 20 mA output is available as an option (in addition to the three relays). This option provides a 0 to 20 mA dc current output for transmitting detector status information to other devices. The circuit can be wired in either an isolated or nonisolated configuration and can drive a maximum loop resistance of 500 ohms from 18 to 19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table 1 indicates the detector status conditions represented by the various current levels. The output is calibrated at the factory, with no need for field calibration. A model with relays and 0-20 mA with HART is also available. Refer to Addendum number 95-8577 for complete details. Table 2—Detector Status Indicator Detector Status Power On/Normal Operation (no fault or fire alarm) Fault Fire (Alarm) Low Sensitivity T-Low Sensitivity Medium Sensitivity NOTE The output of the 0 to 20 mA current loop is not monitored by the fault detection circuitry of the X3301. Therefore, an open circuit on the loop will not cause the fault relay to change state or the detector status LED to indicate a fault. The status of the LED always follows the status of the relays. Very High Sensitivity oi (OPTICAL INTEGRITY) Automatic oi The X3301 includes the Automatic oi feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities. No testing with an external test lamp is required. The detector automatically performs the same test that a maintenance person with a test lamp would perform — once every minute, 60 times per hour. However, a successful Automatic oi test does not produce an alarm condition. Table 1—Detector Status Conditions Indicated by Current Level Detector Status 0 mA Power Fault 1 mA General Fault 2 mA oi Fault 3 mA High Background IR Fault 4 mA Normal Operation 20 mA Fire Alarm The X3301 signals a fault condition when less than half of the detection range remains. This is indicated by the Fault output and is evident by the yellow color of the LED on the face of the detector. The oi fault condition is self-clearing if the optical contamination is temporary. If the contamination is not automatically cleared and the oi fault remains, the detector may require cleaning or service. See the "Troubleshooting" section for further information. LON/SLC Output Magnetic oi / Manual oi The EQP model is designed for use exclusively with the Det-Tronics Eagle Quantum Premier system. The detector communicates with the system controller over a digital communication network or LON/SLC (Local Operating Network / Signaling Line Circuit). The LON/SLC is a fault tolerant, two wire digital communication network arranged in a loop configuration. Analog and relay outputs are not available on this model. 19.4 Green Yellow Red One Yellow Flash During Power-up Three Yellow Flashes During Power-up Two Yellow Flashes During Power-up Four Yellow Flashes During Power-up NOTE: See "Detector Sensitivity Levels" for additional information. An alarm condition will normally over-ride a fault condition, unless the nature of the fault condition impairs the ability of the detector to generate or maintain an alarm output, i.e. loss of operating power. Current Level (±0.3 mA) LED Indicator The detector also incorporates both Magnetic oi (Mag oi) and Manual oi (Man oi) features that provide the same calibrated test as the Automatic oi, and in addition actuates the Alarm output to verify operation for preventive maintenance requirements. These features can be performed at any time and eliminate the need for testing with a non-calibrated external test lamp. 2 95-8527 DATA LOGGING CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test. Data logging capability is also provided. Status conditions such as normal, power down, general and oi faults, fire alarm, time and temperature are recorded. Each event is time and date stamped, along with the temperature and input voltage. Event data is stored in non-volatile memory when the event becomes active, and again when the status changes. Data is accessible using the Inspector Connector accessory, RS-485, or the EQP Controller. The Mag oi test is performed by placing a magnet at the location marked "MAG OI" on the outside of the detector (see Figure 2). The Man oi test is accomplished by connecting the oi lead (terminal 22) to power supply minus via an external switch. The magnet or switch must be held in place for a minimum of 6 seconds to complete the test. Either of these test methods activates the calibrated IR emitters. If the resulting signal meets the test criteria, indicating that greater than half of the detection range remains, the alarm output changes state, the indicating LED changes to red, and the 0-20 mA current output goes to 20 mA. This condition remains until the magnet is removed or the switch is released, regardless of whether the relays are set for latching or non-latching operation. INTEGRAL WIRING COMPARTMENT All external wiring to the device is connected within the integral junction box. The detector is furnished with four conduit entries, with either 3/4 inch NPT or M25 threads. DETECTOR SENSITIVITY LEVELS There are four factory configured sensitivity levels available for the X3301 Flame Detector: If less than half of the detection range remains, no alarm is produced and a fault is generated. The fault indication can be reset by momentarily applying the Mag oi or Man oi switch. Very High, Medium, Low, and T-Low. The following criteria should be considered when choosing a sensitivity level for the intended application: NOTE Refer to Appendix A for FM verification of the o i function. • Detector placement • Speed of response based on fuel type and fire size (see Appendix A for examples of response times) • Distance between the hazard and the flame detector COMMUNICATION The X3301 is furnished with an RS-485 interface for communicating status and other information with external devices. The RS-485 supports MODBUS protocol, with the detector configured as a slave device. Additional information on X3301 Flame Detector performance results and sensitivities can be found in Appendix A, the FM Approval and Performance Report. For HART communication, connect a HART communicator across a 250 ohm resistor in the 0-20 mA loop. NOTE T h e E Q P m o d e l u s e s LO N / S L C communication. RS-485 and HART communication are not available on the EQP model. 19.4 Consult the factory with any questions on how to choose the optimum sensitivity level for the intended application. 3 95-8527 GENERAL APPLICATION INFORMATION Non-Carbon Fires The X3301 is a multiple spectrum IR device with detection limited to carbonaceous fuels. It should not be used to detect fires from fuels that do not contain carbon, such as hydrogen, sulfur, and burning metals. RESPONSE CHARACTERISTICS Response is dependent on the detector's sensitivity setting, distance, type of fuel, temperature of the fuel, and time required for the fire to come to equilibrium. As with all fire tests, results must be interpreted according to an individual application. IMPORTANT SAFETY NOTES WARNING Do not open the detector assembly in a hazardous area when power is applied. The detector contains limited serviceable components and should never be opened. Doing so could disturb critical optical alignment and calibration parameters, possibly causing serious damage. See Appendix A for third-party approved fire test results. Additional fire test results are available from Det-Tronics. IMPORTANT APPLICATION CONSIDERATIONS In applying any type of sensing device as a fire detector, it is important to know of any conditions that can prevent the device from responding to fire, and also to know what other sources besides fire can cause the device to respond. CAUTION The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local ordinances. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person. Welding Arc welding should not be performed within 40 feet (12.2 m) of the detector configured to very high sensitivity, within 10 feet (3.0 m) at medium sensitivity, within 5 feet (1.5 m) at T-Low sensitivity, or within 5 feet (1.5 m) at Low sensitivity. It is recommended that the system be bypassed during welding operations in situations where the possibility of a false alarm cannot be tolerated. Gas welding mandates system bypass, since the gas torch is an actual fire. Arc welding rods can contain organic binder materials in the flux that burn during the welding operation and are detectable by the X3301. Welding rods with clay binders do not burn and will not be detected by the X3301. However, system bypass is always recommended, since the material being welded may be contaminated with organic substances (paint, oil, etc.) that will burn and possibly cause the X3301 to alarm. CAUTION To prevent unwanted actuation or alarm, extinguishing devices must be disabled prior to per forming system tests or maintenance. CAUTION The multispectrum IR flame detectors are to be installed in places where the risk of mechanical damage is low. Artificial Lighting The X3301 should not be located within 3 feet (0.9 m) of artificial lights. Excess heating of the detector could occur due to heat radiating from the lights. ATTENTION Remove the protective cap from the front of the detector before activating the system. ATTENTION O b s e rv e p re ca u t i o n s fo r h a n d l i n g electrostatic sensitive devices. EMI/RFI Interference The X3301 is resistant to interference by EMI and RFI, and is EMC Directive compliant. It will not respond to a 5 watt walkie-talkie at distances greater than 1 foot (0.3 m). Do not operate a walkie-talkie within 1 foot (0.3 m) of the X3301. 19.4 4 95-8527 INSTALLATION • Dense fog, rain or ice can absorb IR radiation and reduce the sensitivity of the detector. To ensure optimum performance, be certain that the internal optical heater is enabled on detectors that are used in applications where snow, ice, and/condensation are likely to occur. • Although IR detectors are less affected by smoke than other detectors, the X3301 should not be placed where rising combustion products can obscure its vision. If smoke is expected before fire, smoke or other alternative detectors should be used in conjunction with the X3301. For indoor applications, if dense smoke is expected to accumulate at the onset of a fire, mount the detector on a side wall at least a few feet (approximately 1 meter) down from the ceiling. • If possible, fire tests can be conducted to verify correct detector positioning and coverage. • For ATEX installations, the X3301 Flame Detector housing must be electrically connected to earth ground. NOTE The recommended lubricant for threads and O-rings is a silicone free grease (p/n 005003-001) available from Det-Tronics. Under no circumstances should a lubricant containing silicone be used. DETECTOR POSITIONING Detectors should be positioned to provide the best unobstructed view of the area to be protected. The following factors should also be taken into consideration: • Identify all high risk fire ignition sources. • Be sure that enough detectors are used to adequately cover the hazardous area. • Be sure that the unit is easily accessible for cleaning and other periodic servicing. • Verify that all detectors in the system are properly located and positioned so that any fire hazards are within both the Field of View (FOV) and detection range of the detector. The Q1201C Laser Aimer is recommended for establishing the detector's FOV. Refer to Appendix A for specific information regarding detector range and FOV. • The detector should be aimed downward at least 10 to 20 degrees to allow lens openings to drain. See Figure 1. The detector should be positioned so that its FOV does not cover areas outside the hazardous area. This will minimize the possibility of false alarms caused by activities outside the area requiring protection. • The detector must be mounted on a rigid surface in a low vibration area. DETECTOR ORIENTATION Refer to Figure  2 and ensure that the oi plate will be oriented as shown when the X3301 is mounted and sighted. This will ensure proper operation of the oi system and will also minimize the accumulation of moisture and contaminants between the oi plate and the viewing windows. IMPORTANT If removed, the o i plate must be securely tightened to ensure proper operation of the o i system (40 oz./inches [28.2 N . cm] recommended). oi PLATE CENTER AXIS OF DETECTOR FIELD OF VIEW PLACE MAGNET HERE TO INITIATE MAGNETIC oi VIEWING WINDOW (3) INCORRECT oi MAGNET F2068 DETECTOR STATUS INDICATOR Figure 2—Front View of the X3301 CENTER AXIS OF DETECTOR FIELD OF VIEW CORRECT D1974 NOTE: DETECTOR MUST ALWAYS BE AIMED DOWNWARD AT LEAST 10 TO 20 DEGREES. Figure 1—Detector Orientation Relative to Horizon 19.4 5 95-8527 PROTECTION AGAINST MOISTURE DAMAGE NOTE Refer to “Power Consumption” in the “Specifications” section of this manual. It is important to take proper precautions during installation to ensure that moisture will not come in contact with the electrical connections or components of the system. The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer. The use of shielded cable is required to protect against interference caused by EMI and RFI. When using cables with shields, terminate the shields as shown in Figures 7 through 12, and Figure 15. Consult the factory if not using shielded cable. If conduit is used, we recommend installing drains, according to local codes, at water collection points to automatically drain accumulated moisture. It is also recommended to install at least one breather, according to local codes, at upper locations to provide ventilation and allow water vapor to escape. In applications where the wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical equipment. If disconnection of power is required, separate disconnect capability must be provided. Conduit raceways should be inclined so that water will flow to low points for drainage and will not collect inside enclosures or on conduit seals. If this is not possible, install conduit drains above the seals to prevent the collection of water or install a drain loop below the detector with a conduit drain at the lowest point of the loop. CAUTION Installation of the detector and wiring should be performed only by qualified personnel. Detector Mounting Conduit seals are not required for compliance with explosion-proof installation requirements, but are highly recommended to prevent water ingress in outdoor applications. Units with M25 threads must use an IP66/IP67 washer to prevent water ingress. Install the mounting arm assembly on a rigid surface. The ideal installation surface should be free of vibration and suitable to receive 3/8 inch or M10 bolts with a length of at least 1 inch (25 mm). The surface must also have sufficient capacity to hold the detector and mounting arm weights (see "Specifications" section). Refer to the Q9033 Mounting Arm and Collar Attachment manual (958686) for additional mounting information. See Figure 3 for dimensions. WIRING PROCEDURE Wire Size and Type The system should be wired according to local codes. The wire size selected should be based on the number of detectors connected, the supply voltage and the cable length. Typically 16 AWG or 2.5 mm2 shielded cable is recommended. Wires should be stripped 3/8 inch (9 mm). A minimum input voltage of 18 Vdc must be present at the X3301. 4X ø0.42 (1.1) 3.0 (7.6) 4.0 (10.2) 13.1 (33.3) NOTE: THIS ILLUSTRATION SHOWS THE DETECTOR MOUNTED AT THE 10° MINIMUM. THESE DIMENSIONS WILL CHANGE BASED ON THE DETECTOR’S MOUNTING ANGLE. 3.0 (7.6) 4.0 (10.2) 10.6 (27.0) F2069 Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm) (See Figure 1 for Correct Detector Orientation.) 19.4 6 95-8527 Relay and 0-20 mA Output Models EOL Resistors (Not Used with EQP Model) Follow the instructions below to install the X3301. To ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors, observe the following guidelines when installing the resistors. 1. Make field connections following local ordinances and guidelines in this manual. 1. –– Figure  4 shows the wiring terminal strip located inside the detector’s integral junction box. NOTE EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. This applies to ATEX/IEC installations only. –– Figure  5 shows the wiring terminal identification for the X3301 Flame Detector. –– Figure  6 shows an EOL resistor installed within the integral wiring compartment of the detector (refer to “EOL Resistors” for details). –– Figures 7 and 8 provide examples of typical installations with a X3301 wired to a fire alarm panel. –– If the detector is equipped with a 0 to 20 mA output, refer to Figures 9 through 12. 2. Check all field wiring to be sure that the proper connections have been made. 19.4 2. Resistor leads should be cut to a length of approximately 1 1/2 inches (40 mm). 3. Bend the leads and install the EOL resistor as shown in Figure 6. 4. Maintain a 3/8 inch (10 mm) minimum gap between the resistor body and the terminal block or any other neighboring parts. NOTE The EOL resistor can only be used within the flameproof terminal compartment. Unused conduit entries shall be closed with suitable blanking elements. IMPORTANT Do not test any wiring connected to the detector with a meg-ohmmeter. Disconnect wiring at the detector before checking system wiring for continuity. 3. Required EOL resistor power rating must be 5 watts minimum. Make the final sighting adjustments and use a 14 mm hex wrench to ensure that the mounting arm assembly is tight. 7 95-8527 Figure 4—X3301 Terminal Block 9 mA + 19 mA – 29 SPARE 8 mA + REF 18 mA – REF 28 SPARE 7 COM FIRE 17 COM FIRE 27 COM AUX 6 N.O. FIRE 16 N.O. FIRE 26 N.O. AUX 5 N.C. FIRE 15 N.C. FIRE 25 N.C. AUX 4 COM FAULT 14 COM FAULT 24 RS-485 A 3 N.O. FAULT 13 N.O. FAULT 23 RS-485 B 2 24 VDC + 12 24 VDC + 22 MAN Oi 1 24 VDC – 11 24 VDC – 21 24 VDC – D2061 Figure 5—X3301 Wiring Terminal Identification 3/8 INCH (10 MM) GAP MINIMUM 19 18 17 16 15 14 13 12 11 B2126 BULKHEAD Figure 6—EOL Resistor Installation (For Ex d Wiring only) 19.4 8 95-8527 X3301 DETECTOR FIRE ALARM PANEL ALARM + 24 VDC – 9 mA + 19 mA – SPARE 29 8 mA + REF 18 mA – REF SPARE 28 7 COM FIRE2 COM FIRE 17 COM AUX 27 6 N.O. FIRE2 N.O. FIRE 16 N.O. AUX 26 5 N.C. FIRE2 N.C. FIRE 15 N.C. AUX 25 4 COM FAULT1 COM FAULT 14 RS-485 A 24 3 N.O. FAULT1 N.O. FAULT 13 RS-485 B 23 2 24 VDC + 12 24 VDC + MAN Oi 22 1 24 VDC – 11 24 VDC – 24 VDC – 21 E.O.L. DEVICE4 oi TEST 3 WIRING NOTES: C2107 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION FOR INSTALLATION DETAILS. Figure 7—Ex d Wiring Option X3301 DETECTOR FIRE ALARM PANEL EOL RESISTOR 4 9 mA + 19 mA – SPARE 29 8 mA + REF 18 mA – REF SPARE 28 ALARM 7 COM FIRE2 COM FIRE 17 COM AUX 27 ALARM 6 N.O. FIRE2 N.O. FIRE 16 N.O. AUX 26 5 N.C. FIRE2 N.C. FIRE 15 N.C. AUX 25 4 COM FAULT1 COM FAULT 14 3 N.O. FAULT1 13 N.O. FAULT 2 24 VDC + 12 1 24 VDC – 11 + 24 VDC – RS-485 A 24 RS-485 B 23 24 VDC + MAN Oi 22 24 VDC – 24 VDC – 21 oi TEST 3 D2109 WIRING NOTES: 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED. 2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT. 3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 4 EOL RESISTOR SUPPLIED BY PANEL. Figure 8—Ex d e Wiring Option 19.4 9 95-8527 X3301 IR DETECTOR 24 VDC + – PLC 9 600 Ω MAX AT 24 VDC 19 mA – mA + SPARE 29 + 8 mA + REF SPARE 28 – 7 COM FIRE COM FIRE 17 COM AUX 27 6 N.O. FIRE N.O. FIRE 16 N.O. AUX 26 5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25 4 COM FAULT COM FAULT 14 RS-485 A 24 3 N.O. FAULT 13 RS-485 B 23 2 24 VDC + 12 24 VDC + MAN Oi 22 1 24 VDC – 11 24 VDC – 24 VDC – 21 mA + 24 VDC – 18 mA – REF 9 mA + 19 mA – SPARE 29 + 8 mA + REF 18 mA – REF SPARE 28 – 7 COM FIRE COM FIRE 17 COM AUX 27 6 N.O. FIRE N.O. FIRE 16 N.O. AUX 26 5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25 4 COM FAULT COM FAULT 14 RS-485 A 24 3 N.O. FAULT 13 RS-485 B 23 2 24 VDC + 12 24 VDC + MAN Oi 22 1 24 VDC – 11 24 VDC – 24 VDC – 21 600 Ω MAX AT 24 VDC mA 24 VDC N.O. FAULT X3301 IR DETECTOR PLC + – N.O. FAULT F2063 F2065 Oi TEST1 Oi TEST1 Figure 9—X3301 Detector Wired for Non-Isolated 0 to 20 mA Current Output (Sourcing) Figure 11—X3301 Detector Wired for Isolated 0 to 20 mA Current Output (Sourcing) 24 VDC + – X3301 IR DETECTOR PLC 9 600 Ω MAX AT 24 VDC + 8 mA + REF – 7 COM FIRE mA + 24 VDC – F2064 19 mA + 18 mA – SPARE 29 SPARE 28 COM FIRE 17 COM AUX 27 N.O. AUX 26 mA – REF X3301 IR DETECTOR PLC 9 mA + 19 mA – SPARE 29 + 8 mA + REF 18 mA – REF SPARE 28 – 7 COM FIRE COM FIRE 17 COM AUX 27 6 N.O. FIRE N.O. FIRE 16 N.O. AUX 26 5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25 4 COM FAULT COM FAULT 14 RS-485 A 24 N.O. FAULT 13 RS-485 B 23 600 Ω MAX AT 24 VDC 6 N.O. FIRE N.O. FIRE 16 5 N.C. FIRE N.C. FIRE 15 N.C. AUX 25 4 COM FAULT COM FAULT 14 RS-485 A 24 3 N.O. FAULT N.O. FAULT 13 RS-485 B 23 2 24 VDC + 12 24 VDC + MAN Oi 22 3 N.O. FAULT 1 24 VDC – 11 24 VDC – 24 VDC – 21 2 24 VDC + 12 24 VDC + MAN Oi 22 1 24 VDC – 11 24 VDC – 24 VDC – 21 mA + 24 VDC – F2066 Oi TEST1 Oi TEST1 Figure 10—X3301 Detector Wired for Non-Isolated 0 to 20 mA Current Output (Sinking) NOTES: 1. 19.4 Figure 12—X3301 Detector Wired for Isolated 0 to 20 mA Current Output (Sinking) INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED. 10 95-8527 EQP Model 1. Connect external wires to the appropriate terminals inside the device junction box, shown in Figure  13. See Figure  14 for terminal identification. 2. Connect the shield of the power cable to “earth ground” at the power source. 3. Connect shields for the LON cable as indicated. See Figure 15. 5. Check all field wiring to be sure that the proper connections have been made. 6. Replace the device cover and apply input power. 7. Make the final sighting adjustments and use a 14 mm hex wrench to ensure that the mounting arm assembly is tight. NOTE Refer to the Eagle Quantum Premier system manual (95-8533) for information regarding power requirements, network communication cable requirements, and configuration. NOTE DO NOT ground any shields at the detector housing. 4. With input power disconnected, set the device network address (see the “Setting Device Network Addresses” section of this manual for switch setting procedure). Figure 13—X3301 Terminal Block (EQP Model) 6 COM SHIELD 16 COM SHIELD 5 COM 1 A 15 COM 2 A 4 COM 1 B 14 COM 2 B 3 POWER SHIELD 13 POWER SHIELD 2 24 VDC + 12 24 VDC + 1 24 VDC – 11 24 VDC – B2089 Figure 14—Wiring Terminal Identification for X3301 EQP Model 19.4 11 95-8527 19.4 P8 NC 47 FAULT NO 46 C 45 12 9 3+ RELAY 5 RELAY 6 RELAY 7 C 42 NO 43 NC 44 31 NO 32 NC NC 41 29 NC RELAY 3 30 C C 39 NO 40 28 NO NC 38 RELAY 2 27 C C 36 NO 37 26 NC NC 35 23 NC 25 NO NO 34 22 NO RELAY 1 24 C C 33 DIGITAL INPUTS 21 C P5 8– 20 A 4 C COMMON C B IN–/OUT+ B A + SUPPLY A C COMMON C B IN–/OUT+ B A + SUPPLY A C COMMON C B IN–/OUT+ B A + SUPPLY A C COMMON C B IN–/OUT+ B A + SUPPLY A P3 1 2 3 CH 3 P4 8+ 19 7– 18 7+ 17 CH 7 12 4– 11 4+ B 5 P4 SHIELD 6 COM1 1 P2 24 VDC + 4 COM2 2 24 VDC – 5 3 SHIELD 6 P1 EQP3700DCIO CH 2 10 3– 6– 16 6+ 15 5– 14 5+ 13 P3 A 56 B 55 CH 6 8 2– 7 2+ 6 1– 5 1+ P2 59 TxD 58 RxD 57 GND GND 54 P9 50 A 53 CH 5 DB-9 CONNECTION TO COM PORT OF PC TXD 3 RXD 2 GND 5 49 B 52 P6 48 SHIELD 51 COM1 1 P7 24 VDC + 3 COM2 2 24 VDC – 4 P1 CONTROLLER CH 1 CH 4 CH 8 RELAY 4 RELAY 8 95-8527 – – 24 VDC BATTERY + H N AC LINE 24 VDC SUPPLY + + + – – POWER – – DISTRIBUTION + + + – + – + – 2 B N H AC LINE 15 14 16 A B SHIELD 5 4 6 COM1 Figure 15—A Typical EQP System 4 3 1 2 P3 A 10 3 C B 11 1 BUS BAR SHIELD 12 COM2 12 24 VDC + 2 8 COM1 24 VDC + 5 COM2 11 24 VDC – 1 7 24 VDC – 3 6 SHIELD EQPX3301 13 SHIELD 4 9 EQP2100PSM 3 15 14 16 COM2 A B SHIELD 5 4 6 COM1 12 24 VDC + 2 11 24 VDC – 1 SHIELD EQPX3301 13 3 15 14 16 COM2 A B SHIELD 5 4 6 COM1 12 24 VDC + 2 11 24 VDC – 1 SHIELD EQPX3301 13 3 B A 14 15 5 4 6 COM1 SHIELD 16 COM2 12 24 VDC + 2 11 24 VDC – 1 SHIELD EQPX3301 13 A2207 ADDRESS SWITCHES SENSOR MODULE REMOVED FROM HOUSING A2191 Figure 16—Location of Address Switches The address number is binary encoded with each switch having a specific binary value with switch 1 being the LSB (Least Significant Bit), see Figure  17. The device’s LON address is equal to the added value of all closed rocker switches. All “Open” switches are ignored. SETTING DEVICE NETWORK ADDRESSES (EQP Model Only) Overview of Network Addresses Each device on the LON must be assigned a unique address. Addresses 1 to 4 are reserved for the controller. Valid addresses for field devices are from 5 to 250. Example: for node No. 5, close rocker switches 1 and 3 (binary values 1 + 4); for node No. 25, close rocker switches 1, 4 and 5 (binary values 1 + 8 + 16). IMPORTANT If the address is set to zero or an address above 250, the switch setting will be ignored. NOTE The field device sets the LON address only when power is applied to the device. Therefore, it is important to set the switches before applying power. If an address is ever changed, system power must be cycled before the new address will take effect. Duplicated addresses are not automatically detected. Modules given the same address will use the number given and report to the controller using that address. The status word will show the latest update, which could be from any of the reporting modules using that address. After setting address switches, record the address number and device type. Setting Field Device Addresses Selection of the node address is done by setting rocker switches on an 8 switch “DIP Switch Assembly” within the detector’s housing. Refer to Figure 16 for switch location. ON WARNING The network address switches are located within the detector housing. Disassembly of the detector head that contains powered electrical circuits is required to gain access to the network address switches. For hazardous areas, the area must be de-classified before attempting disassembly of the device. Always observe precautions for handling electrostatic sensitive devices. 19.4 BINARY VALUE 1 2 3 4 5 1 2 4 8 16 32 64 128 6 7 8 NODE ADDRESS EQUALS THE ADDED VALUE OF ALL CLOSED ROCKER SWITCHES OPEN = OFF CLOSED = ON A2190 Figure 17—Address Switches for X3301 13 95-8527 STARTUP PROCEDURE Table 3—Current Level Output Troubleshooting Guide When installation of the equipment is complete, perform the “Fire Alarm Test” below. FIRE ALARM TEST 1. Disable any extinguishing equipment that is connected to the system. 2. Apply input power to the system. 3. Initiate an oi test (see “Magnetic oi / Manual oi” under Optical Integrity in the Description section of this manual). 4. Repeat this test for all detectors in the system. If a unit fails the test, refer to the “Troubleshooting” section. 5. Verify that all detectors in the system are properly aimed at the area to be protected. (The Q1201C Laser Aimer is recommended for this purpose.) 6. Current Level (±0.3 mA) Status Action 0 mA Power Fault Check system wiring 1 mA 2 mA General Fault Cycle power 1 oi Fault 3 mA High Background IR Fault Clean windows2 Remove IR source or aim detector away from IR source 4 mA 20 mA Normal Operation Fire Alarm 1 If fault continues, return device to factory for repair. See “Maintenance” section for cleaning procedure. NOTE: For additional troubleshooting guides, refer to the Flame Inspector Monitor manual (95-8581). 2 Enable extinguishing equipment when the test is complete. 3. Check input power to the unit. 4. If the fire system has a logging function, check the fire panel log for output status information. See Table  3 for information regarding 0 to 20 mA output. 5. Turn off the input power to the detector and check all wiring for continuity. Important: Disconnect wiring at the detector before checking system wiring for continuity. 6. If all wiring checks out and cleaning of the oi plate/window did not correct the fault condition, check for high levels of background IR radiation by covering the detector with the factory supplied cover or aluminum foil. If the fault condition clears within 6 minutes or less, extreme background IR is present. Re-adjust the view of the detector away from the IR source or relocate the detector. TROUBLESHOOTING WARNING The sensor module (“front” half of the detector) contains no user serviceable components and should never be opened. The terminal compartment is the only part of the enclosure that should be opened by the user in the field. 1. Disable any extinguishing equipment that is connected to the unit. If none of these actions corrects the problem, return the detector to the factory for repair. 2. Inspect the viewing windows for contamination and clean as necessary. The detector is relatively insensitive to airborne contaminants, however, thick deposits of ice, dirt, or oil will reduce sensitivity. (Refer to the “Maintenance” section for complete information regarding cleaning of the detector viewing windows.) 19.4 NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. 14 95-8527 MAINTENANCE LOOSEN TWO CAPTIVE SCREWS IMPORTANT Periodic flamepath inspections are not recommended, since the product is not intended to be serviced and provides proper ingress protection to eliminate potential deterioration of the flamepaths. GRASP VISOR AND REMOVE oi PLATE WARNING The sensor module (“front” half of the detector) contains no user serviceable components and should never be opened. The terminal compartment is the only part of the enclosure that should be opened by the user in the field. NOTE Refer to the X3301 Safety manual (958582) for specific requirements and recommendations applicable to the p ro p e r i n s ta l l a t i o n , o p e ra t i o n , a n d maintenance of all SIL-Certified X3301 Flame Detectors. B2106 Figure 18—oi Plate Removal IMPORTANT When used in extreme environments, the reflective surface of the detector oi plate may eventually deteriorate, resulting in reoccurring oi faults and the need for oi plate replacement. To maintain maximum sensitivity and false alarm resistance, the viewing windows of the X3301 must be kept relatively clean. Refer to the following procedure for cleaning instructions. oi PLATE REMOVAL AND REPLACEMENT CLEANING PROCEDURE CAUTION Disable any extinguishing equipment that is connected to the unit to prevent unwanted actuation. 1. Disable any extinguishing equipment that is connected to the unit. 2. Loosen the two captive screws, then grasp the oi plate by the visor and remove it from the detector. See Figure 18. 3. Install the new (or cleaned) oi plate. NOTE When installing the stainless steel plate, ensure that the gasket is present and correctly seated to prevent moisture or contaminants from penetrating behind the plate. To ensure even seating, tighten both screws equally. To clean the windows and oi plate, use the window cleaner (p/n 001680-001) and a soft cloth, cotton swab, or tissue and refer to the following procedure: 1. Disable any extinguishing equipment that is connected to the unit. 2. Since the X3301 is less affected by contamination than other detectors, removal of the oi plate is needed only under extreme conditions. In addition, it is not necessary to achieve perfect cleanliness, because IR is not significantly absorbed by slight films of oil and/or salt. If a fault condition is still indicated after cleaning, remove and clean the oi plate using the oi Plate Removal and Replacement procedure. 4. Recalibrate the detector's oi system. Refer to the Inspector Monitor manual (958581) for instructions regarding oi plate replacement and oi system recalibration. In all environments, clean all three viewing windows and reflector surfaces thoroughly. Use a cotton swab and the Det-Tronics window cleaning solution. Use Isopropyl alcohol for contaminations that the DetTronics window cleaning solution can not remove. Recalibration of the oi system requires the use of the Inspector Connector Cable and Inspector Monitor Software. These two items are included in the oi replacement kit, or they can be purchased separately. See Ordering Information for details. 3. 19.4 CAUTION Do not replace the o i reflector plate without also recalibrating the oi system. 15 95-8527 FEATURES X3301 Reflector Plates X3301 models are supplied with either a black or a stainless steel reflector plate. These plates are not interchangeable. Order the replacement that matches the reflector plate on your X3301 Flame Detector. • Long detection range to carbonaceous fires • Unequaled false alarm rejection • Responds to a fire in the presence of modulated blackbody radiation (i.e. heaters, ovens, turbines) without false alarm • Microprocessor controlled heated optics for increased resistance to moisture and ice • Automatic, manual, or magnetic oi testing • Easily replaceable oi plate • Fire, fault and auxiliary relays standard • 0 to 20 mA isolated output (optional) • Eagle Quantum Premier LON/SLC output (optional) • HART communication (optional) • FDT/DTM capable • Multiple sensitivity levels • A tri-color LED on the detector faceplate indicates normal condition and notifies personnel of fire alarm or fault conditions • Operates under adverse weather conditions and in dirty environments • Mounting arm allows easy sighting • Integral wiring compartment for ease of installation • Explosion-proof/flame-proof detector housing. Meets FM, CSA, ATEX Directive and CE certification requirements • Class A wiring per NFPA-72 • Meets NFPA-33 response requirement for under 0.5 second (available when model selected) • 5 year warranty • RFI and EMC Directive compliant PERIODIC CHECKOUT PROCEDURE In compliance with SIL 2, a checkout of the system using the Mag oi or Man oi feature should performed regularly to ensure that the system is operating properly. Refer to Table 1 in the X3301 Safety manual (95-8582) for frequency of proof tests. To test the system, perform the “Fire Alarm Test” as described in the “Startup Procedure” section of this manual. CLOCK BATTERY The real time clock has a backup battery that will operate the clock with no external power. Return the device to the factory for battery replacement if needed. NOTE If the backup battery is depleted, there is no effect on the operation of the flame detector, but the time stamping of the data log may be affected. Associated Manuals List of X3301 related manuals: TITLE Pulse EQP SIL 2 (Safety) HART Addendum Automotive Addendum Hangar Q9033 Mounting Arm and Collar Attachment Inspector Monitor Software for X-Series Flame Detectors Q1130 Flange Mount 19.4 16 FORM NUMBER 95-8528 95-8533 95-8582 95-8577 95-8534 95-8548 95-8686 95-8581 95-8662 95-8527 SPECIFICATIONS CURRENT OUTPUT (OPTIONAL)— 0 to 20 milliampere (±0.3 mA) dc current, with a maximum loop resistance of 500 ohms from 18 to 19.9 Vdc and 600 ohms from 20 to 30 Vdc. OPERATING VOLTAGE— 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). Maximum ripple is 2 volts peak-to-peak. LON OUTPUT— Digital communication, transformer isolated (78.5 kbps). POWER CONSUMPTION— Without heater: 4 watts at 24 Vdc nominal; 5.2 watts at 24 Vdc in alarm. 4.5 watts at 30 Vdc nominal; 6.5 watts at 30 Vdc in alarm. Heater only: 8 watts maximum. Total power: 17 watts at 30 Vdc with EOL resistor installed and heater on maximum. EOL resistor must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. For HART model, refer to Addendum number 95-8577. TEMPERATURE RANGE— Operating: –40°F to +167°F (–40°C to +75°C). Storage: –67°F to +185°F (–55°C to +85°C). Hazardous location ratings from –55°C to +125°C. HUMIDITY RANGE— 0 to 95% relative humidity, can withstand 100% condensing humidity for short periods of time. CONE OF VISION— The detector has a 90° cone of vision (horizontal) with the highest sensitivity lying along the central axis. Unlike conventional detectors, the X3301 provides full coverage at a minimum of 70% of the maximum detection distance. POWER UP TIME— Fault indication clears after 0.5 second; device is ready to indicate an alarm condition after 30 seconds. Perfect cone of vision for methane fire detection — 100 feet (30.5 m) on and off axis on “very high” setting. OUTPUT RELAYS— Fire Alarm relay, Form C, 5 amperes at 30 Vdc: The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. Refer to Appendix A for FM Approved cone of vision data. Fault relay, Form A, 5 amperes at 30 Vdc: The Fault relay has redundant terminals and normally open contacts, normally energized operation, and latching or non-latching operation. RESPONSE TIME— Typical response times are under 10 seconds. Models are available that can respond to automotive paint gun fires in under 0.5 seconds. See Appendix A and “Automotive Addendum” (95-8534) for actual response times. Auxiliary relay, Form C, 5 amperes at 30 Vdc: The auxiliary relay has normally open/normally closed contacts, normally energized or deenergized operation, and latching or non-latching operation. DIMENSIONS— See Figure 19. 4.7 (11.9) B2067 10.0 (25.4) 4.8 (12.2) Figure 19—X3301 Dimensions in Inches (cm) 19.4 17 95-8527 ENCLOSURE MATERIAL— Copper-free aluminum (painted) or Stainless Steel (316/CF8M Cast). CERTIFICATION— FM ® APPROVED VIBRATION— Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW), DNV Note 2.4 (Class B). VdS WIRING— Field wiring screw terminals are UL/CSA rated for up to 14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire. Screw terminal required torque range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m). For complete approval details, refer to the appropriate Appendix: Appendix A - FM Appendix B - CSA Appendix C - ATEX Appendix D - IECEx Appendix E - EN54 Appendix F - Offshore Appendix G - Additional approvals Important: 18 Vdc minimum must be available at the detector. For ambient temperatures below –10°C (14°F) and above +60°C (140°F) use field wiring suitable for both minimum and maximum ambient temperature. THREAD SIZE— Conduit connection: Four entries, 3/4 inch NPT or M25. Conduit seal not required. SHIPPING WEIGHT (Approximate)— Aluminum: 7 pounds (3.2 kilograms). Stainless Steel: 13.8 pounds (6.3 kilograms). Mounting Arm (AL): 6 pounds (2.75 kilograms). Mounting Arm (SS): 14 pounds (6.4 kilograms). WARRANTY PERIOD— 5 years. 19.4 18 95-8527 REPLACEMENT PARTS ORDERING INFORMATION The detector is not designed to be repaired in the field. If a problem should develop, refer to the Troubleshooting section. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair. When ordering, please specify: X3301 Multispectrum IR Flame Detector Refer to the X3301 Model Matrix for details Q9033 Mounting Arm is required: –– Q9033A for aluminum detectors only –– Q9033B for aluminum and stainless steel detectors REPLACEMENT PARTS LIST Part Number 009208-001 010831-001 007307-001 010830-001 Description oi Replacement kit for X3301 (5 Black Reflector Plates) with Inspector Connector and Monitor oi Replacement kit for X3301 (5 Stainless Steel Reflector Plates) with Inspector Connector and Monitor Replacement oi Reflector Plates for X3301 with Black plate (requires Inspector Connector to calibrate) Replacement oi Reflector Plates for X3301 with Stainless Steel plate (requires Inspector Connector to calibrate) ACCESSORIES Description 000511-029 103881-001 Converter RS485 to RS232 Converter RS485 to USB W6300B1002 Serial Inspector Connector (Inspector Monitor software included) 007819-001 NOTE: Refer to instruction manual 95-8530 to determine the correct oi Replacement Plate. 007819-002 W6300B1003 USB Inspector Connector (Inspector Monitor software included) 009207-001 Flame Inspector Monitor CD 103922-001 Model 475 HART Communicator 102740-002 Magnet 008082-001 Magnet and Adapter for Extension Pole 007739-001 Magnet and Extension Pole 007240-001 Q1116A1001, Air Shield (AL) 007818-001 Q1118A1001 Aluminum Air Shield/Flange Mount (AL) Q1118S1001 Stainless Steel Air Shield/Flange 007818-002 Mount (SS) 009177-001 Q1120A1001 Paint Shield mounting ring (AL) 010857-001 Q1130A1001 Flange Mount Assembly 006097-001 Q1201 Laser Laser Battery, 3V Lithium (laser) 102871-001 007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic) 007338-001 Q2000A1001 X-Series Weather Shield (AL) 007338-010 Q2033A10R X3301/X3302 FOV Limiter 10° (AL) 007338-020 Q2033A20R X3301/X3302 FOV Limiter 20° (AL) 007338-030 Q2033A30R X3301/X3302 FOV Limiter 30° (AL) 007912-010 Spare Restrictor Plate 10° (AL) 007912-020 Spare Restrictor Plate 20° (AL) 007912-030 Spare Restrictor Plate 30° (AL) DEVICE REPAIR AND RETURN Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure. Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge. NOTE Det-Tronics reserves the right to apply a service charge for repairing returned product damaged as a result of improper packaging. Return all equipment transportation prepaid to the factory in Minneapolis. NOTE It is highly recommended that a complete spare be kept on hand for field replacement to ensure continuous protection. 19.4 Part Number 19 007290-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors 007290-002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only 011385-001 101197-001 101197-004 101197-005 101197-003 010816-001 010817-001 010818-001 010819-001 103363-001 103406-001 107427-040 005003-001 001680-001 Q9033 Collar Attachment Stop Plug, 3/4” NPT, AL Stop Plug, 3/4” NPT, SS Stop Plug, M25, AL, IP66 Stop Plug, M25, SS, IP66 Stop Plug, 20 Pack, 3/4”NPT, AL Stop Plug, 20 Pack, 3/4”NPT, SS Stop Plug, 20 Pack, M25, AL, IP66 Stop Plug, 20 Pack, M25, SS, IP66 14 mm Hex Wrench (Steel) Screwdriver O-ring - Rear Cover (Viton) 1 oz grease for detectors (non-silicon) Window cleaner (6 pack) 95-8527 X3301 MODEL MATRIX MODEL X3301 DESCRIPTION Multispectrum IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 0-20 mA 14 Eagle Quantum Premier (EQP) 15 Relay and Pulse 16 Addressable Module Only (Third Party Type)* 21 Relay-Automotive 22 EQP Automotive 23 HART, Relay and 0-20 mA TYPE APPROVALS*** B INMETRO (Brazil) K Kazakhstan R VNIIPO/VNIIFTRI (Russia) S SIL T SIL/FM/CSA/ATEX/IECEx W FM/CSA/ULC**/ATEX/IECEx Y NEPSI/CCCF (China) TYPE CLASSIFICATION 1 Division/Zone Ex d e 2 Division/Zone Ex d *The Addressable Module Only (Type 16) is not FM approved. **ULC approval applies to output types 11, 13, 15, 21, and 23. ***Type Approvals can use one or more letters to designate the approvals of the product. 19.4 20 95-8527 APPENDIX A FM APPROVAL AND PERFORMANCE REPORT THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL: • Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615. • Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615. • Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611. • Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611. • Enclosure rating NEMA/Type 4X per NEMA 250. • Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C). • Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000). Flameproof per ANSI/ISA 60079-0, -1, -7, -31 for Class I, Zone 1 AEx d e IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C) AEx d IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C) for Zone 21 AEx tb T130°C Db Tamb –40°C to +75°C Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S. The following accessories are FM approved for use with the X3301 Flame Detector: Part Number 102740-002 007739-001 010857-001 007290-001 007290-002 011385-001 Description Magnet Magnet and Extension Pole Q1130A1001 Flange Mount Assembly Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment The following performance criteria were verified: AUTOMATIC OPTICAL INTEGRITY TEST: The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector was verified to detect a fire. MANUAL OPTICAL INTEGRITY TEST: The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated. The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual, is the approved external optical test method for this detector to verify end-to-end detector function. This test replaces the function and need of a traditional external test lamp. 19.4 21 95-8527 FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS Very High Sensitivity Fuel Size Distance feet (m) Average Response Time (seconds)*** n-Heptane n-Heptane** n-Heptane n-Heptane Isopropanol Diesel** Ethanol Methanol Methanol Methanol** Methane JP-5** JP-5** JP-5** Office Paper 0.5 lb. Corrugated Panel 1 x 1 foot 1 x 1 foot 1 x 1 foot 6 in. x 6 in. 6 in. x 6 in. 1 x 1 foot 1 x 1 foot 6 in. x 6 in. 1 x 1 foot 1 x 1 foot 30 inch plume 1 x 1 foot 2 x 2 feet 2 x 2 feet 19" x 19" x 8" 18" x 36" 210 (64)* 210 (64)* 100 (30.5) 80 (24.4) 70 (21.3) 150 (45.7)* 210 (64) 40 (12.2) 150 (45.7)* 150 (45.7)* 100 (30.5) 150 (45.7)* 210 (64)* 100 (30.5) 100 (30.5) 100 (30.5) 11 6 3 3 4 14 11 3 18 7 3 2 4 2 4 8 Distance feet (m) 100 (30.5) 50 (15.2) 70 (21.3) 85 (25.9) 70 (21.3) 65 (19.8) 55 (16.8) 100 (30.5) 50 (15.2) 50 (15.2) Average Response Time (seconds)*** 12 2 4 13 10 3 2 3 6 2 Distance feet (m) 50 (15.2) 20 (6.1) 15 (4.6) Average Response Time (seconds)*** 7 5 4 * ** *** Outdoor test condition. Pre-burn from ignition. Add 2 seconds for EQP model. Medium Sensitivity Fuel n-Heptane n-Heptane Diesel** Ethanol Methanol Methane Methane JP-5** Office Paper 0.5 lb. Corrugated Panel ** *** Size 1 x 1 foot 1 x 1 foot 1 x 1 foot 1 x 1 foot 1 x 1 foot 30 inch plume 30 inch plume 2 x 2 feet 19" x 19" x 8" 18" x 36" Pre-burn from ignition. Add 2 seconds for EQP model. T-Low Sensitivity Fuel n-Heptane Methanol Methane Size 1 x 1 foot 1 x 1 foot 32 inch plume *** Add 2 seconds for EQP model. Low Sensitivity Fuel Size Distance feet (m) Average Response Time (seconds)*** n-Heptane 1 x 1 foot 50 (15.2) 10 Methanol 1 x 1 foot 20 (6.1) 10 Methane 32 inch plume 15 (4.6) 9 *** Add 2 seconds for EQP model. 19.4 22 95-8527 FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES Very High Sensitivity False Alarm Source Sunlight, direct, modulated, reflected Distance feet (m) Fire Source Distance feet (m) Average Response Time (seconds)*** — 6-inch propane 6 (1.8) < 10 N/A 3-inch propane 10.5 (3.2) < 10 1 (0.3) 3-inch propane 12 (3.7) < 10 Arc welding, #7014 40 (12.2) 1 x 1 foot n-Heptane 40 (12.2) 4 6 kw heater, modulated 80 (24.4) 1 x 1 foot n-Heptane 80 (24.4) 2 6 kw heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 80 (24.4) 3 250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4) 2 300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4) 7 500 w shielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 80 (24.4) 2 500 w unshielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 80 (24.4) 3 1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 80 (24.4) 5 Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4) 3 Distance feet (m) Fire Source Distance feet (m) Average Response Time (seconds)*** Sunlight, direct, modulated, reflected — 6-inch propane 6 (1.8) <4 Vibration* N/A N/A N/A N/A Vibration Radio frequency interference *** Add 2 seconds for EQP model. Medium Sensitivity False Alarm Source Radio frequency interference 1 (0.3) 6-inch propane 6 (1.8) <1 Arc welding, #7014 10 (3) 1 x 1 foot n-Heptane 40 (12.2) 4 60 (18.3) 1 x 1 foot n-Heptane 60 (18.3) 2 6 kw heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3) 2 250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 1 300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 1 500 w shielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3) 1 500 w unshielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3) 1 1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3) 6 Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3) 2 6 kw heater, modulated * *** 19.4 Fire was verified with very high sensitivity only. Add 2 seconds for EQP model. 23 95-8527 FM Approval and Performance Report – Continued T-Low Sensitivity Distance feet (m) Fire Source Distance feet (m) Average Response Time (seconds)*** Sunlight, direct, unmodulated, reflected* — 1 x 1 foot n-Heptane 35 (10.7) <6 Sunlight, direct, modulated, reflected* — 1 x 1 foot n-Heptane 15 (4.6) <4 Arc welding, steady, #7014 5 (1.5) 1 x 1 foot n-Heptane 50 (15.2) 10 Arc welding, modulated, #7014 5 (1.5) 1 x 1 foot n-Heptane 30 (9.1) 3 70 w sodium vapor, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 6 70 w sodium vapor, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 7 250 w vapor lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 8 250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 6 300 w incandescent lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 7 300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 8 500 w shielded quartz halogen lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 4 500 w shielded quartz halogen lamp, modulated 10 (3) 1 x 1 foot n-Heptane 50 (15.2) 5 1500 w electric radiant heater, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 5 1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 30 (9.1) 7 Two 34 w fluorescent lamps, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 5 Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 4 Distance feet (m) Fire Source Distance feet (m) Average Response Time (seconds)*** False Alarm Source * *** Outdoor test conditions. Add 2 seconds for EQP model. Low Sensitivity False Alarm Source Sunlight, direct, unmodulated, reflected* — 1 x 1 foot n-Heptane 35 (10.7) < 13 Sunlight, direct, modulated, reflected* — 1 x 1 foot n-Heptane 15 (4.6) < 14 Arc welding, steady, #7014 5 (1.5) 1 x 1 foot n-Heptane 50 (15.2) 11 Arc welding, modulated, #7014 5 (1.5) 1 x 1 foot n-Heptane 30 (9.1) 10 70 w sodium vapor, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 16 250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 18 300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 18 500 w shielded quartz halogen lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 12 500 w shielded quartz halogen lamp, modulated 10 (3) 1 x 1 foot n-Heptane 50 (15.2) 11 1500 w electric radiant heater, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 12 1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 30 (9.1) 11 Two 34 w fluorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 50 (15.2) 14 * *** 19.4 Outdoor test conditions. Add 2 seconds for EQP model. 24 95-8527 FM Approval and Performance Report – Continued FALSE ALARM IMMUNITY Very High Sensitivity False Alarm Source Sunlight, direct, reflected Vibration Radio frequency interference Distance feet (m) Modulated Response Unmodulated Response No alarm — No alarm N/A No alarm N/A 1 (0.3) No alarm (keyed) No alarm (steady) Arc welding 40 (12.2) No alarm No alarm 6 kw heater 3 (0.9) No alarm No alarm 250 w vapor lamp 3 (0.9) No alarm No alarm 300 w incandescent lamp 3 (0.9) No alarm No alarm 500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm 500 w shielded quartz halogen lamp 8 (2.4) No alarm No alarm 1500 w electric radiant heater 3 (0.9) No alarm No alarm Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm Distance feet (m) Modulated Response Unmodulated Response No alarm Medium Sensitivity False Alarm Source Sunlight, direct, reflected Vibration Radio frequency interference — No alarm N/A No alarm N/A 1 (0.3) No alarm (keyed) No alarm (steady) Arc welding 10 (3) No alarm No alarm 6 kw heater 3 (0.9) No alarm No alarm 250 w vapor lamp 3 (0.9) No alarm No alarm 300 w incandescent lamp 3 (0.9) No alarm No alarm 500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm 500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm 1500 w electric radiant heater 3 (0.9) No alarm No alarm Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm Distance feet (m) Modulated Response Unmodulated Response T-Low Sensitivity False Alarm Source Sunlight, direct, reflected — No alarm No alarm Vibration — No alarm No alarm Arc welding 5 (1.5) No alarm No alarm 6 kw heater 3 (0.9) No alarm No alarm 70 w sodium vapor 3 (0.9) No alarm No alarm 250 w vapor lamp 3 (0.9) No alarm No alarm 300 w incandescent lamp 3 (0.9) No alarm No alarm 500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm 1500 w electric radiant heater 3 (0.9) No alarm No alarm Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm 19.4 25 95-8527 FM Approval and Performance Report – Continued Low Sensitivity Distance feet (m) Modulated Response Unmodulated Response Sunlight, direct, reflected — No alarm No alarm Vibration — No alarm No alarm N/A No alarm N/A Arc welding 5 (1.5) No alarm No alarm 6 kw heater 3 (0.9) No alarm No alarm 250 w vapor lamp 3 (0.9) No alarm No alarm 300 w incandescent lamp 3 (0.9) No alarm No alarm 500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm 1500 w electric radiant heater 3 (0.9) No alarm No alarm False Alarm Source Radio frequency interference Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm FIELD OF VIEW Very High Sensitivity Fuel Size Distance feet (m) Horizontal (degrees) Avg. Horiz. Response Time (seconds)*** Vertical (degrees) Avg. Vert. Response Time (seconds)*** n-Heptane 1 x 1 foot 150* (45.7) +45 -45 12 14 +45 -30 13 5 n-Heptane 1 x 1 foot 100 (30.5) +45 -45 6 3 +45 -30 3 2 n-Heptane 6 in. x 6 in. 80 (24.4) +45 -45 5 6 +45 -30 4 4 Isopropanol 6 in. x 6 in. 70 (21.3) +45 -45 5 5 +45 -30 4 6 Diesel** 1 x 1 foot 100 (30.5) +45 -45 2 3 +45 -30 4 3 Ethanol 1 x 1 foot 150 (45.7) +45 -45 13 10 +45 -30 10 8 Methanol 6 in. x 6 in. 40 (12.2) +45 -45 4 6 +45 -30 3 3 Methanol 1 x 1 foot 110 (33.5) +45 -45 9 7 +45 -30 9 3 Methane 30 inch plume 100 (30.5) +45 -45 7 3 +45 -30 2 2 JP-5** 1 x 1 foot 100 (30.5) +45 -45 2 4 +45 -30 3 2 JP-5** 2 x 2 feet 180* (54.9) +45 -45 2 5 +45 -30 3 2 JP-5** 2 x 2 feet 90 (27.4) +45 -45 2 3 +45 -30 1 2 80 (24.4) +45 -45 4 2 +45 -30 2 1 80 (24.4) +45 -45 1 1 +45 -30 3 2 Office Paper 0.5 lb. 19" x 19" x 8" Corrugated Panel 18" x 36" * Outdoor test condition. ** Pre-burn from ignition. *** Add 2 seconds for EQP model. 19.4 26 95-8527 FM Approval and Performance Report – Continued Medium Sensitivity Fuel Size Distance feet (m) Horizontal (degrees) Avg. Horiz. Response Time (seconds)*** Vertical (degrees) Avg. Vert. Response Time (seconds)*** n-Heptane 1 x 1 foot 75 (22.9) +45 -45 9 6 +45 -30 10 7 n-Heptane 1 x 1 foot 50 (15.2) +45 -45 4 3 +45 -30 3 3 Diesel** 1 x 1 foot 60 (18.3) +45 -45 4 4 +45 -30 4 2 Ethanol 1 x 1 foot 60 (18.2) +45 -45 12 9 +45 -30 12 9 Methanol 1 x 1 foot 50 (15.2) +45 -45 9 3 +45 -30 9 1 Methane 32 inch plume 45 (13.7) +45 -45 3 3 +45 -30 7 1 JP-5** 2 x 2 feet 90 (27.4) +45 -45 4 2 +45 -30 2 2 Office Paper 0.5 lb. 19" x 19" x 8" 40 (12.2) +45 -45 2 1 +45 -30 1 1 Corrugated Panel 18" x 36" 40 (12.2) +45 -45 2 1 +45 -30 1 1 ** *** Pre-burn from ignition. Add 2 seconds for EQP model. T-Low Sensitivity *** Fuel Size Distance feet (m) Horizontal (degrees) Avg. Horiz. Response Time (seconds)*** Vertical (degrees) Avg. Vert. Response Time (seconds)*** n-Heptane 1 x 1 foot 35 (10.7) +45 -45 7 7 +45 -30 7 7 Methanol 1 x 1 foot 15 (4.6) +45 -45 5 5 +45 -30 5 5 Methane 32 inch plume 15 (4.6) +45 -45 4 4 +45 -30 4 4 Add 2 seconds for EQP model. Low Sensitivity *** 19.4 Avg. Horiz. Vertical Response (degrees) Time (seconds)*** Avg. Vert. Response Time (seconds)*** Fuel Size Distance feet (m) Horizontal (degrees) n-Heptane 1 x 1 foot 35 (10.7) +45 -45 13 13 +45 -30 9 18 Methanol 1 x 1 foot 15 (4.6) +45 -45 14 12 +45 -30 10 8 Methane 32 inch plume 15 (4.6) +45 -45 10 11 +45 -30 8 10 Add 2 seconds for EQP model. 27 95-8527 FM Approval and Performance Report – Continued HIGH RESOLUTION FIELD OF VIEW 15° 30° 0° 210 (64) 0° 15° 70 (21.3) 15° 30° 180 (54.9) 45° 30° 45° 45° 150 (45.7) 30 (9.1) 20 (6.1) 60 (18.3) 10 (3) 30 (9.1) 10 (3) 30 (9.1) 30° 20 (6.1) 30° 60 (18.3) 30 (9.1) 90 (27.4) 15° 40 (12.2) 15° 120 (36.5) 50 (15.2) 150 (45.7) 0° 180 (54.9) 15° 30° 0° 15° 80 (24.4) DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. 70 (21.3) 45° 30° 30° 60 (18.3) 15° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for Isopropanol at Very High Sensitivity (6 in. x 6 in.) 15° 70 (21.3) 45° 0° 60 (18.3) Field of View at Indicated Distance in Feet (m) for n-Heptane at Very High Sensitivity (1 x 1 foot) 30° 45° 40 (12.2) 90 (27.4) 45° 30° 50 (15.2) 120 (36.5) 210 (64) 15° 60 (18.3) 45° 45° 50 (15.2) 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) 0° 15° 150 (45.7) 15° 135 (41.2) 120 (36.6) 105 (32) 90 (27.4) 75 (22.9) 60 (18.3) 45 (13.7) 30 (9.1) 15 (4.6) 30° 45° Field of View at Indicated Distance in Feet (m) for Diesel at Very High Sensitivity (1 x 1 foot) 10 (3) 20 (6.1) 30° 30 (9.1) 40 (12.2) 15° 50 (15.2) 60 (18.3) 0° 70 (21.3) 80 (24.4) 45° 15° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for n-Heptane at Very High Sensitivity (6 in. x 6 in.) 19.4 28 95-8527 FM Approval and Performance Report – Continued 15° 30° 0° 210 (64) 15° 180 (54.9) 45° 30° 30° 45° 45° 150 (45.7) 120 (36.5) 90 (27.4) 60 (18.3) 30 (9.1) 30° 45° Field of View at Indicated Distance in Feet (m) for Methanol at Very High Sensitivity (1 x 1 foot) 30 (9.1) 30° 60 (18.3) 90 (27.4) 30° 15° 120 (36.5) 45° 150 (45.7) 0° 180 (54.9) 15° 210 (64) 45° 30° DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. Field of View at Indicated Distance in Feet (m) for Ethanol at Very High Sensitivity (1 x 1 foot) 30° 0° 15° 40 (12.2) 10 (3) 20 (6.1) 30 (9.1) 40 (12.2) 50 (15.2) 60 (18.3) 70 (21.3) 80 (24.4) 90 (27.4) 100 (30.5) 15° 30° 35 (10.7) 30 (9.1) 45° 45° 25 (7.6) 20 (6.1) 15 (4.6) 10 (3) 45° 5 (1.5) 10 (3) 30° 45° 30° 15° 0° 15° 30° 0° 15° 210 (64) 30° 30° 15 (4.6) 20 (6.1) 45° 15° 25 (7.6) DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. 180 (54.9) 150 (45.7) 15° 30° 45° 120 (36.5) 30 (9.1) 0° 35 (10.7) 40 (12.2) 45° 0° 15° 100 (30.5) 15° 90 (27.4) 80 (24.4) 70 (21.3) 60 (18.3) 50 (15.2) 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) Field of View at Indicated Distance in Feet (m) for Methane at Very High Sensitivity (30 inch plume) 5 (1.5) 15° 30° 90 (27.4) DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45° FROM HORIZONTAL. 60 (18.3) 30 (9.1) Field of View at Indicated Distance in Feet (m) for Methanol at Very High Sensitivity (6 in. x 6 in.) 19.4 0° 15° 150 (45.7) 15° 135 (41.2 120 (36.5) 105 (32) 90 (27.4) 75 (22.9) 60 (18.3) 45 (13.7) 30 (9.1) 15 (4.6) Field of View at Indicated Distance in Feet (m) for JP-5 at Very High Sensitivity (2 x 2 feet) 29 95-8527 FM Approval and Performance Report – Continued 30° 45° 0° 15° 100 (30.5) 15° 90 (27.4) 80 (24.4) 70 (21.3) 60 (18.3) 50 (15.2) 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) 30° 30° 45° 45° 0° 15° 70 (21.3) 45° 60 (18.3) 30° 45° 50 (15.2) 30 (9.1) 20 (6.1) 10 (3) Field of View at Indicated Distance in Feet (m) for Methanol at Medium Sensitivity (1 x 1 foot) 15° 30° 60 (18.3) 15° 40 (12.2) Field of View at Indicated Distance in Feet (m) for n-Heptane at Medium Sensitivity (1 x 1 foot) 30° 0° 15° 70 (21.3) 30° 45° 50 (15.2) 0° 15° 65 ( 19.8) 15° 60 (18.3) 30° 50 (15.2) 45° 45° 40 (12.2) 40 (12.2) 30 (9.1) 30 (9.1) 20 (6.1) 20 (6.1) 10 (3) 10 (3) Field of View at Indicated Distance in Feet (m) for Diesel at Medium Sensitivity (1 x 1 foot) Field of View at Indicated Distance in Feet (m) for Methane at Medium Sensitivity (30 inch plume) 30° 45° 0° 15° 85 (25.9) 80 (24.4) 75 (22.9) 65 (19.8) 55 (16.8) 45 (13.7) 35 (10.7) 25 (7.6) 15 (4.6) 5 (1.5) 15° 30° 30° 45° 45° Field of View at Indicated Distance in Feet (m) for Ethanol at Medium Sensitivity (1 x 1 foot) 0° 15° 100 (30.5) 15° 90 (27.4) 80 (24.4) 70 (21.3) 60 (18.3) 50 (15.2) 40 (12.2) 30 (9.1) 20 (6.1) 10 (3) 30° 45° Field of View at Indicated Distance in Feet (m) for JP-5 at Medium Sensitivity (2 x 2 foot) NOTE FM Approvals minimum requirements are response distance measurements at 0° (on axis) and the limits of the field of view. These high resolution field of view diagrams show the measured response distances at all the indicated angles in the horizontal plane. 19.4 30 95-8527 APPENDIX B CSA APPROVAL Multispectrum IR Flame Detector/Controller X3301 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts. Relay contacts rated 30 Vdc, 5 Amps. NOTE Hazardous location testing has been successfully completed on the Model X3301 series from an ambient temperature range of –55°C to +125°C; however, the detector label marking indicates –40°C to +75°C. The following accessories are CSA approved for use with the X3301 Flame Detector: Part Number 102740-002 007739-001 010857-001 007290-001 007290-002 011385-001 Description Magnet Magnet and Extension Pole Q1130A1001 Flange Mount Assembly Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment DIVISION CLASSIFICATION: CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A); Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C); Class III; Enclosure NEMA/Type 4X; Conduit seal not required. APPLICABLE REQUIREMENTS CSA Std C22.2 No. 25-1966 – Enclosures for use in Class II Groups E, F & G Hazardous Locations CSA Std C22.2 No. 30-M1986 – Explosion-Proof Enclosures for use in Class I Hazardous Locations CAN/CSA C22.2 No. 94-M91 – Special Purpose Enclosures CSA Std C22.2 No. 142-M1987 – Process Control Equipment CSA Std C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations ZONE CLASSIFICATION: CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Ex d e IIC T5-T6 T6 (Ta -50oC to +60oC) T5 (Ta -50oC to +75oC) Seal required adjacent to enclosure IP66/IP67. Ex d IIC T4-T6 T6 (Ta -55oC to +60oC) T5 (Ta -55oC to +75oC) T4 (Ta -55oC to +125oC) Seal required adjacent to enclosure IP66/IP67. APPLICABLE REQUIREMENTS CAN/CSA-C22.2 No. 60079-0:07 – Electrical apparatus for explosive gas atmospheres. Part 0: General requirements CAN/CSA-C22.2 No. 60079-1:11 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d" CAN/CSA-C22.2 No. 60079-7:12 – Explosive atmospheres. Part 7: Equipment protection by increased safety "e" 19.4 31 95-8527 APPENDIX C ATEX APPROVAL EC-TYPE EXAMINATION CERTIFICATE DEMKO 01 ATEX 130204X Increased Safety Model 0539 FM ® APPROVED II 2 G II 2 D Flameproof Model FM II 2 G II 2 D 0539 ® APPROVED Ex d e IIC T6–T5 Gb Ex d IIC T6–T4 Gb Ex tb IIIC T130°C Ex tb IIIC T130°C T6 (Tamb = –50°C to +60°C) T6 (Tamb = –55°C to +60°C) T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C) IP66/IP67. T4 (Tamb = –55°C to +125°C) IP66/IP67. Compliance with: EN 60079-0: 2009 EN 60079-1: 2007 EN 60079-7: 2007 EN 60079-31: 2009 EN/IEC 60529: 2001. INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from 14-24 AWG or 2.5-0.2 mm2. The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: The front window assembly contains a special cemented joint construction. In accordance with EN600791 clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector Electronics Corporation only. The EOL resistor can only be used within the flameproof terminal compartment. EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk of mechanical damage. 19.4 32 95-8527 NOTE Operational performance verified from –40°C to +75°C. NOTE An optional third party addressable module can only be used within the Ex d flameproof model unless the addressable module is component certified as Ex e for use within the Ex d e increased safety model. NOTE Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable blanking elements. NOTE For ATEX installations, the X3301 Flame Detector housing must be electrically connected to earth ground. The following accessories are ATEX approved for use with the X3301 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 19.4 33 95-8527 APPENDIX D IECEx APPROVAL IECEx CERTIFICATE OF CONFORMITY DEMKO IECEx ULD 06.0017X Ex d e IIC T6-T5 Gb Ex tb IIIC T130°C T6 (Tamb = –50°C to +60°C) T5 (Tamb = –50°C to +75°C) IP66/IP67. or Ex d IIC T6-T4 Gb Ex tb IIIC T130°C T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) T4 (Tamb = –55°C to +125°C) IP66/IP67. Compliance with: IEC 60079-0: 2007, Ed. 5 IEC 60079-1: 2007, Ed. 6 IEC 60079-7: 2006, Ed. 4 IEC 60079-31: 2008, Ed. 1 EN/IEC 60529: 2001. INSTALLATION INSTRUCTIONS The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from 14-24 AWG or 2.5-0.2 mm2. The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given by the manufacturer. The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal compartment in type of explosion protection flameproof enclosure "d" or in type of explosion protection increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed. Unused entries shall be closed with suitable certified blanking elements. The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected to earth ground. For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum ambient temperature. Special conditions for safe use: The front window assembly contains a special cemented joint construction. In accordance with IEC 60079-1 clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector Electronics Corporation only. The EOL resistor can only be used within the flameproof terminal compartment. EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts. The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk of mechanical damage. The following accessories are IECEx approved for use with the X3301 Flame Detector: Part Number Description 007290-001 007290-002 011385-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 19.4 34 95-8527 APPENDIX E EN54 APPROVALS Conventional Output AGENCY VdS – Constructive Product Directive Basis of Approval Certificate/Approval Number 0786 – CPD – 20453 EN 54-10 + A1 — — LPCB Basis of Approval G 202136 VdS 2344 VdS 2504 EN 54-10 + A1 G 212019 VdS 2344 VdS 2504 EN 54-10 + A1 EN 54-17 S 212002* VdS 2344 EN 54-13 S 212002* VdS 2344 EN 54-13 — — 0832 – CPD – 1381 EN 54-10 + A1 EN 54-17 973e/03 EN 54-10 + A1 973a/03 EN 54-10 + A1 EN 54-17 VdS BRE – Constructive Product Directive LON Output Certificate/Approval Number * Approved for use in conjunction with the EN54-13 compliant EQP System. INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM The installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view angle in this direction is <90°. The IR-flame detector configured to High or Very High sensitivity corresponds to class 1. The IR-flame detector configured to T-Low or Low sensitivity corresponds to class 2. The following accessories are EN54-10 and EN54-17 approved for use with the X3301 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only 011385-001 19.4 Q9033 Collar Attachment 35 95-8527 APPENDIX F OFFSHORE APPROVALS USCG APPROVAL Coast Guard Approval No. 161.002/49/0 The scope of this approval is for a fire detection system meeting 46 CFR 161.002, as part of the Eagle Quantum Premier System. MARINE EQUIPMENT DIRECTIVE DNV Certificate No. MED-B-8184 Is found to comply with the requirements in the following Regulations / Standards: Annex A.1, item No. A.1/3.51 and Annex B, Module B in the Directive. SOLAS 74 as amended, Regulation II-2/7 & X/3, 2000 HSC Code 7, FSS Code 9 and IMO MSC.1/Circ. 1242. The equipment are found to comply with following location / application dependent requirements (for definition of each of the location classes, see below the table): MODEL TEMPERATURE VIBRATION EMC ENCLOSURE X3301 TEM-D VIB-B EMC-B ENC-C Definition of the location classes with reference to relevant standards: Temperature TEM-D Location (–25°C-70°C) (ref. IEC 60092-504 (2001) table 1 item 6-7) Vibration VIB-D For eq. on reciprocating machines etc. (ref IEC 60092-504 (2001) table 1 item 10) EMC EMC-B Bridge and open deck zone (ref. IEC 60092-504 (2001) table 1 item 19-20) Enclosure ENC-C Open deck (IP56) (ref. IEC 60092-201 table 5) Conformity to Module D, E and F. TYPE APPROVAL DNV Certificate No. A-13151. Subject Matter of the Approval IR Flame Detector Type X3301 for use in Ships, High Speed & Light Craft, and Offshore Applications. Application Location Classes: Location classes for X3301 IR Flame Detector with Mounting Arm Q9033B / Q9033A (Shaded areas show Det-Tronics approved location classes) COLUMN 1 TYPE Temperature Humidity Vibration EMC (Electromagnetic compatibility LOCATION WITHIN MAIN AREA Inside cubicles, desks, etc. with temperature rise of 5°C or more All other locations Locations where special precautions are taken to avoid condensation All other locations On machinery such as internal combustion engines, compressors, pumps, including piping on such machinery Masts All other locations Enclosure COLUMN 2 MAIN AREAS ON BOARD Machinery Control room, Pump room, Holds, Bridge Open Deck spaces Accommodation Rooms with no heating B B B D D A A A C D A A A A A B B B B B B — — B B — A — A — A — A — A All locations within specified main areas A A B A B Submerged application Below floor plates in engine room All other locations D C B — — A — — A D — B D — C TYPE APPROVAL Lloyd's Register Certificate No. 09/00027. Models Available: Relay output, relay 0-20 mA output, and EQP LON output versions. The following accessories are offshore approved to the listed approvals, for use with the X3301 Flame Detector: Part Number Description 102740-002 007739-001 007290-001 007290-002 011385-001 Magnet Magnet and Extension Pole Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only Q9033 Collar Attachment 19.4 36 95-8527 APPENDIX G ADDITIONAL APPROVALS SIL 2 BRAZIL IEC 61508 UL-BR 12.0093X Ex d e IIC T6-T5 Gb IP66/IP67 Ex tb IIIC T130°C T6 (Tamb = –50°C to +60°C) T5 (Tamb = –50°C to +75°C). Certified SIL 2 Capable. Applies to specific models – refer to the SIL 2 Certified X3301 Safety manual (95-8582) for details. – or – Ex d IIC T6-T4 Gb IP66/IP67 Ex tb IIIC T130°C T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) T4 (Tamb = –55°C to +125°C). FRANCE AFNOR Identification No: LIR 007 A0. For specific information regarding the X3301 Flame Detector's conformity to NF EN54-10, reference Addendum number 95-8726. CHINA RUSSIA NEPSI Certification No. GYJ12.1294X Ex d e IIC T5/T6 Gb Ex d IIC T4~T6 Gb DIP A21 TA 130°C IP66/IP67. VNIIFTRI CERTIFICATE OF CONFORMITY to TP TC 012/2011 2ExdeIICT6/T5 IP66 T6 (Tamb = –50°C to +60°C) T5 (Tamb = –50°C to +75°C). CCCF Certification No. 2013081801000455 GB15631-2008, GB/T19001-2008 Applies to Output Types 11, 13, 21, and 23 only. – or – 1ExdIICT6/T5/T4 IP66 T6 (Tamb = –55°C to +60°C) T5 (Tamb = –55°C to +75°C) T4 (Tamb = –55°C to +125°C). VNIIPO CERTIFICATE OF CONFORMITY to TECHNICAL REGULATIONS, GOST R 533252009 KAZAKHSTAN MES (Ministry of Emergency Situations) Approval for use No. 18-02-02/896 19.4 37 95-8527 95-8527 FlexSonic ® Acoustic Leak Detector X3301 Multispectrum IR Flame Detector ­Corporate Office 6901 West 110 th Street Minneapolis, MN 55438 USA www.det-tronics.com PointWatch Eclipse ® IR Combustible Gas Detector Phone: 952.946.6491 Toll-free: 800.765.3473 Fax: 952.829.8750 det-tronics@det-tronics.com FlexVu ® Universal Display with GT3000 Toxic Gas Detector Eagle Quantum Premier ® Safety System All trademarks are the property of their respective owners. © 2015 Detector Electronics Corporation. All rights reserved. Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.