Det-Tronics Instructions Multispectrum IR Flame Detector X3301
Industry Manual Repository
Join the AnalyzeDetectNetwork and Read This Manual and Hundreds of Others Like It! It's Free!
Instructions
Multispectrum IR Flame Detector
X3301
19.4
Rev: 12/13
95-8527
Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . .
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
oi (Optical Integrity) . . . . . . . . . . . . . . . . .
Communication . . . . . . . . . . . . . . . . . . . . .
Data Logging . . . . . . . . . . . . . . . . . . . . . . .
Integral Wiring Compartment . . . . . . . . . . .
Detector Sensitivity Levels . . . . . . . . . . . .
1
1
2
2
3
3
3
3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 17
REPLACEMENT PARTS . . . . . . . . . . . . . . . 19
Replacement Parts List . . . . . . . . . . . . . . 19
DEVICE REPAIR AND RETURN . . . . . . . . . 19
GENERAL APPLICATION INFORMATION . . 4
Response Characteristics . . . . . . . . . . . . . 4
Important Application Considerations . . . . 4
ORDERING INFORMATION . . . . . . . . . . . . . 19
Accessories . . . . . . . . . . . . . . . . . . . . . . . 19
X3301 Model Matrix . . . . . . . . . . . . . . . . . 20
IMPORTANT SAFETY NOTES . . . . . . . . . . . . 4
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 5
Detector Positioning . . . . . . . . . . . . . . . . . . 5
Detector Orientation . . . . . . . . . . . . . . . . . . 5
Protection Against Moisture Damage . . . . 6
Wiring Procedure . . . . . . . . . . . . . . . . . . . . 6
Setting Device Network Addresses
(EQP Model Only) . . . . . . . . . . . . . . . . . 13
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT . . . . . . . . . . . . . 21
APPENDIX B – CSA APPROVAL . . . . . . . . . 31
APPENDIX C – ATEX APPROVAL . . . . . . . . 32
APPENDIX D – IECEx APPROVAL . . . . . . . 34
APPENDIX E – EN54 APPROVALS . . . . . . . 35
STARTUP PROCEDURE . . . . . . . . . . . . . . . 14
Fire Alarm Test . . . . . . . . . . . . . . . . . . . . . 14
APPENDIX F – OFFSHORE APPROVALS . . . 36
TROUBLESHOOTING . . . . . . . . . . . . . . . . . 14
APPENDIX G – ADDITIONAL APPROVALS . . . 37
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . .
Cleaning Procedure . . . . . . . . . . . . . . . . .
oi Plate Removal and Replacement . . . .
Periodic Checkout Procedure . . . . . . . . .
Clock Battery . . . . . . . . . . . . . . . . . . . . . .
15
15
15
16
16
INSTRUCTIONS
Multispectrum IR Flame Detector
X3301
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or
operating the flame detection system. Any
deviation from the recommendations in this
manual may impair system performance
and compromise safety.
ATTENTION
The X3301 includes the Automatic o i ®
(Optical Integrity) feature — a calibrated
performance test that is automatically
performed once per minute to verify
complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire
alarm or fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
DESCRIPTION
The X3301 is a multispectrum infrared (IR) flame
detector. It provides unsurpassed detection
of fires from light to heavy hydrocarbon fuels
combined with the highest degree of false alarm
rejection. The detector has Division and Zone
explosion-proof ratings and is suitable for use in
indoor and outdoor applications.
The X3301 housing is available in copper-free
aluminum or stainless steel, with NEMA/Type 4X
and IP66/IP67 rating.
OUTPUTS
Relays
The standard detector is furnished with fire, fault
and auxiliary relays. All three relays are rated 5
amperes at 30 Vdc.
The X3301 contains three IR sensors with their
associated signal processing circuitry.
The
standard output configuration includes fire, fault
and auxiliary relays. Output options include:
––
0 to 20 mA output (in addition to the three
relays)
––
Pulse output for compatibility with
existing Det-Tronics ® controller based
systems (with fire and fault relays)
––
Eagle Quantum Premier® (EQP) compatible
model (no analog or relay outputs)
––
HART communication
19.4
©Detector Electronics Corporation 2015
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
The Auxiliary relay has normally open / normally
closed contacts, and is configurable for energized
or de-energized operation, and latching or nonlatching operation.
1
Rev: 12/13
95-8527
0 to 20 mA Output
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire
alarm or fault conditions. Table 2 indicates the
condition of the LED for each status.
A 0 to 20 mA output is available as an option (in
addition to the three relays). This option provides
a 0 to 20 mA dc current output for transmitting
detector status information to other devices. The
circuit can be wired in either an isolated or nonisolated configuration and can drive a maximum
loop resistance of 500 ohms from 18 to 19.9 Vdc
and 600 ohms from 20 to 30 Vdc. Table 1 indicates
the detector status conditions represented by the
various current levels. The output is calibrated at
the factory, with no need for field calibration. A
model with relays and 0-20 mA with HART is also
available. Refer to Addendum number 95-8577
for complete details.
Table 2—Detector Status Indicator
Detector Status
Power On/Normal Operation
(no fault or fire alarm)
Fault
Fire (Alarm)
Low Sensitivity
T-Low Sensitivity
Medium Sensitivity
NOTE
The output of the 0 to 20 mA current loop is
not monitored by the fault detection circuitry
of the X3301. Therefore, an open circuit on
the loop will not cause the fault relay to
change state or the detector status LED
to indicate a fault. The status of the LED
always follows the status of the relays.
Very High Sensitivity
oi (OPTICAL INTEGRITY)
Automatic oi
The X3301 includes the Automatic oi feature — a
calibrated performance test that is automatically
performed once per minute to verify complete
detector operation capabilities. No testing with
an external test lamp is required. The detector
automatically performs the same test that a
maintenance person with a test lamp would
perform — once every minute, 60 times per hour.
However, a successful Automatic oi test does not
produce an alarm condition.
Table 1—Detector Status Conditions Indicated by Current Level
Detector Status
0 mA
Power Fault
1 mA
General Fault
2 mA
oi Fault
3 mA
High Background IR Fault
4 mA
Normal Operation
20 mA
Fire Alarm
The X3301 signals a fault condition when less
than half of the detection range remains. This is
indicated by the Fault output and is evident by the
yellow color of the LED on the face of the detector.
The oi fault condition is self-clearing if the optical
contamination is temporary. If the contamination
is not automatically cleared and the oi fault
remains, the detector may require cleaning or
service. See the "Troubleshooting" section for
further information.
LON/SLC Output
Magnetic oi / Manual oi
The EQP model is designed for use exclusively
with the Det-Tronics Eagle Quantum Premier
system. The detector communicates with the
system controller over a digital communication
network or LON/SLC (Local Operating Network
/ Signaling Line Circuit). The LON/SLC is a fault
tolerant, two wire digital communication network
arranged in a loop configuration. Analog and
relay outputs are not available on this model.
19.4
Green
Yellow
Red
One Yellow Flash
During Power-up
Three Yellow Flashes
During Power-up
Two Yellow Flashes
During Power-up
Four Yellow Flashes
During Power-up
NOTE: See "Detector Sensitivity Levels" for additional information.
An alarm condition will normally over-ride a fault
condition, unless the nature of the fault condition
impairs the ability of the detector to generate or
maintain an alarm output, i.e. loss of operating
power.
Current Level (±0.3 mA)
LED Indicator
The detector also incorporates both Magnetic
oi (Mag oi) and Manual oi (Man oi) features
that provide the same calibrated test as the
Automatic oi, and in addition actuates the
Alarm output to verify operation for preventive
maintenance requirements. These features can
be performed at any time and eliminate the need
for testing with a non-calibrated external test
lamp.
2
95-8527
DATA LOGGING
CAUTION
These tests require disabling of all
extinguishing devices to avoid release
resulting from a successful test.
Data logging capability is also provided. Status
conditions such as normal, power down, general
and oi faults, fire alarm, time and temperature are
recorded. Each event is time and date stamped,
along with the temperature and input voltage.
Event data is stored in non-volatile memory when
the event becomes active, and again when the
status changes. Data is accessible using the
Inspector Connector accessory, RS-485, or the
EQP Controller.
The Mag oi test is performed by placing a magnet
at the location marked "MAG OI" on the outside
of the detector (see Figure 2). The Man oi test is
accomplished by connecting the oi lead (terminal
22) to power supply minus via an external switch.
The magnet or switch must be held in place for a
minimum of 6 seconds to complete the test. Either
of these test methods activates the calibrated
IR emitters. If the resulting signal meets the
test criteria, indicating that greater than half of
the detection range remains, the alarm output
changes state, the indicating LED changes to red,
and the 0-20 mA current output goes to 20 mA.
This condition remains until the magnet is removed
or the switch is released, regardless of whether the
relays are set for latching or non-latching operation.
INTEGRAL WIRING COMPARTMENT
All external wiring to the device is connected
within the integral junction box. The detector is
furnished with four conduit entries, with either 3/4
inch NPT or M25 threads.
DETECTOR SENSITIVITY LEVELS
There are four factory configured sensitivity levels
available for the X3301 Flame Detector:
If less than half of the detection range remains,
no alarm is produced and a fault is generated.
The fault indication can be reset by momentarily
applying the Mag oi or Man oi switch.
Very High, Medium, Low, and T-Low.
The following criteria should be considered
when choosing a sensitivity level for the intended
application:
NOTE
Refer to Appendix A for FM verification
of the o i function.
• Detector placement
• Speed of response based on fuel type and
fire size (see Appendix A for examples of
response times)
• Distance between the hazard and the flame
detector
COMMUNICATION
The X3301 is furnished with an RS-485 interface
for communicating status and other information
with external devices. The RS-485 supports
MODBUS protocol, with the detector configured
as a slave device.
Additional information on X3301 Flame Detector
performance results and sensitivities can be
found in Appendix A, the FM Approval and
Performance Report.
For HART communication, connect a HART
communicator across a 250 ohm resistor in the
0-20 mA loop.
NOTE
T h e E Q P m o d e l u s e s LO N / S L C
communication. RS-485 and HART
communication are not available on the
EQP model.
19.4
Consult the factory with any questions on how
to choose the optimum sensitivity level for the
intended application.
3
95-8527
GENERAL APPLICATION
INFORMATION
Non-Carbon Fires
The X3301 is a multiple spectrum IR device
with detection limited to carbonaceous fuels.
It should not be used to detect fires from fuels
that do not contain carbon, such as hydrogen,
sulfur, and burning metals.
RESPONSE CHARACTERISTICS
Response is dependent on the detector's
sensitivity setting, distance, type of fuel,
temperature of the fuel, and time required for
the fire to come to equilibrium. As with all fire
tests, results must be interpreted according to an
individual application.
IMPORTANT SAFETY NOTES
WARNING
Do not open the detector assembly in a
hazardous area when power is applied.
The detector contains limited serviceable
components and should never be opened.
Doing so could disturb critical optical
alignment and calibration parameters,
possibly causing serious damage.
See Appendix A for third-party approved fire test
results. Additional fire test results are available
from Det-Tronics.
IMPORTANT APPLICATION CONSIDERATIONS
In applying any type of sensing device as
a fire detector, it is important to know of any
conditions that can prevent the device from
responding to fire, and also to know what other
sources besides fire can cause the device to
respond.
CAUTION
The wiring procedures in this manual are
intended to ensure proper functioning of the
device under normal conditions. However,
because of the many variations in wiring
codes and regulations, total compliance to
these ordinances cannot be guaranteed.
Be certain that all wiring complies with
the NEC as well as all local ordinances.
If in doubt, consult the authority having
jurisdiction before wiring the system.
Installation must be done by a properly
trained person.
Welding
Arc welding should not be performed within
40 feet (12.2 m) of the detector configured
to very high sensitivity, within 10 feet (3.0 m)
at medium sensitivity, within 5 feet (1.5 m)
at T-Low sensitivity, or within 5 feet (1.5 m)
at Low sensitivity. It is recommended that
the system be bypassed during welding
operations in situations where the possibility
of a false alarm cannot be tolerated. Gas
welding mandates system bypass, since the
gas torch is an actual fire. Arc welding rods
can contain organic binder materials in the flux
that burn during the welding operation and are
detectable by the X3301. Welding rods with clay
binders do not burn and will not be detected by
the X3301. However, system bypass is always
recommended, since the material being welded
may be contaminated with organic substances
(paint, oil, etc.) that will burn and possibly cause
the X3301 to alarm.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled
prior to per forming system tests or
maintenance.
CAUTION
The multispectrum IR flame detectors are
to be installed in places where the risk of
mechanical damage is low.
Artificial Lighting
The X3301 should not be located within 3 feet
(0.9 m) of artificial lights. Excess heating of the
detector could occur due to heat radiating from
the lights.
ATTENTION
Remove the protective cap from the front of
the detector before activating the system.
ATTENTION
O b s e rv e p re ca u t i o n s fo r h a n d l i n g
electrostatic sensitive devices.
EMI/RFI Interference
The X3301 is resistant to interference by EMI
and RFI, and is EMC Directive compliant. It will
not respond to a 5 watt walkie-talkie at distances
greater than 1 foot (0.3 m). Do not operate a
walkie-talkie within 1 foot (0.3 m) of the X3301.
19.4
4
95-8527
INSTALLATION
• Dense fog, rain or ice can absorb IR radiation
and reduce the sensitivity of the detector. To
ensure optimum performance, be certain that the
internal optical heater is enabled on detectors
that are used in applications where snow, ice,
and/condensation are likely to occur.
• Although IR detectors are less affected by
smoke than other detectors, the X3301 should
not be placed where rising combustion products
can obscure its vision. If smoke is expected
before fire, smoke or other alternative detectors
should be used in conjunction with the X3301.
For indoor applications, if dense smoke is
expected to accumulate at the onset of a fire,
mount the detector on a side wall at least a
few feet (approximately 1 meter) down from the
ceiling.
• If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
• For ATEX installations, the X3301 Flame Detector
housing must be electrically connected to earth
ground.
NOTE
The recommended lubricant for threads
and O-rings is a silicone free grease (p/n
005003-001) available from Det-Tronics.
Under no circumstances should a lubricant
containing silicone be used.
DETECTOR POSITIONING
Detectors should be positioned to provide
the best unobstructed view of the area to be
protected. The following factors should also be
taken into consideration:
• Identify all high risk fire ignition sources.
• Be sure that enough detectors are used to
adequately cover the hazardous area.
• Be sure that the unit is easily accessible for
cleaning and other periodic servicing.
• Verify that all detectors in the system are
properly located and positioned so that any
fire hazards are within both the Field of View
(FOV) and detection range of the detector.
The Q1201C Laser Aimer is recommended
for establishing the detector's FOV. Refer to
Appendix A for specific information regarding
detector range and FOV.
• The detector should be aimed downward at
least 10 to 20 degrees to allow lens openings
to drain. See Figure 1. The detector should
be positioned so that its FOV does not
cover areas outside the hazardous area.
This will minimize the possibility of false alarms
caused by activities outside the area requiring
protection.
• The detector must be mounted on a rigid
surface in a low vibration area.
DETECTOR ORIENTATION
Refer to Figure 2 and ensure that the oi plate
will be oriented as shown when the X3301 is
mounted and sighted. This will ensure proper
operation of the oi system and will also minimize
the accumulation of moisture and contaminants
between the oi plate and the viewing windows.
IMPORTANT
If removed, the o i plate must be securely
tightened to ensure proper operation of
the o i system (40 oz./inches [28.2 N . cm]
recommended).
oi PLATE
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
VIEWING WINDOW (3)
INCORRECT
oi MAGNET
F2068
DETECTOR
STATUS INDICATOR
Figure 2—Front View of the X3301
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CORRECT
D1974
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
Figure 1—Detector Orientation Relative to Horizon
19.4
5
95-8527
PROTECTION AGAINST MOISTURE DAMAGE
NOTE
Refer to “Power Consumption” in the
“Specifications” section of this manual.
It is important to take proper precautions during
installation to ensure that moisture will not come
in contact with the electrical connections or
components of the system. The integrity of
the system regarding moisture protection must
be maintained for proper operation and is the
responsibility of the installer.
The use of shielded cable is required to protect
against interference caused by EMI and RFI.
When using cables with shields, terminate
the shields as shown in Figures 7 through 12,
and Figure 15. Consult the factory if not using
shielded cable.
If conduit is used, we recommend installing drains,
according to local codes, at water collection
points to automatically drain accumulated
moisture. It is also recommended to install at least
one breather, according to local codes, at upper
locations to provide ventilation and allow water
vapor to escape.
In applications where the wiring cable is installed
in conduit, the conduit must not be used for wiring
to other electrical equipment.
If disconnection of power is required, separate
disconnect capability must be provided.
Conduit raceways should be inclined so that
water will flow to low points for drainage and
will not collect inside enclosures or on conduit
seals. If this is not possible, install conduit drains
above the seals to prevent the collection of water
or install a drain loop below the detector with a
conduit drain at the lowest point of the loop.
CAUTION
Installation of the detector and wiring should
be performed only by qualified personnel.
Detector Mounting
Conduit seals are not required for compliance
with explosion-proof installation requirements, but
are highly recommended to prevent water ingress
in outdoor applications. Units with M25 threads
must use an IP66/IP67 washer to prevent water
ingress.
Install the mounting arm assembly on a rigid
surface. The ideal installation surface should be
free of vibration and suitable to receive 3/8 inch or
M10 bolts with a length of at least 1 inch (25 mm).
The surface must also have sufficient capacity
to hold the detector and mounting arm weights
(see "Specifications" section). Refer to the Q9033
Mounting Arm and Collar Attachment manual (958686) for additional mounting information. See
Figure 3 for dimensions.
WIRING PROCEDURE
Wire Size and Type
The system should be wired according to local
codes. The wire size selected should be based
on the number of detectors connected, the supply
voltage and the cable length. Typically 16 AWG
or 2.5 mm2 shielded cable is recommended.
Wires should be stripped 3/8 inch (9 mm). A
minimum input voltage of 18 Vdc must be present
at the X3301.
4X ø0.42
(1.1)
3.0
(7.6)
4.0
(10.2)
13.1
(33.3)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
3.0
(7.6)
4.0
(10.2)
10.6
(27.0)
F2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
19.4
6
95-8527
Relay and 0-20 mA Output Models
EOL Resistors (Not Used with EQP Model)
Follow the instructions below to install the
X3301.
To ensure that the insulating material of the
wiring terminal block will not be affected by
the heat generated by EOL resistors, observe
the following guidelines when installing the
resistors.
1.
Make field connections following local
ordinances and guidelines in this manual.
1.
–– Figure 4 shows the wiring terminal strip
located inside the detector’s integral
junction box.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual
power dissipation not to exceed 2.5 watts.
This applies to ATEX/IEC installations only.
–– Figure 5 shows the wiring terminal
identification for the X3301 Flame
Detector.
–– Figure 6 shows an EOL resistor installed
within the integral wiring compartment of
the detector (refer to “EOL Resistors” for
details).
–– Figures 7 and 8 provide examples of
typical installations with a X3301 wired to
a fire alarm panel.
–– If the detector is equipped with a 0 to
20 mA output, refer to Figures 9 through
12.
2.
Check all field wiring to be sure that the
proper connections have been made.
19.4
2.
Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3.
Bend the leads and install the EOL resistor
as shown in Figure 6.
4.
Maintain a 3/8 inch (10 mm) minimum gap
between the resistor body and the terminal
block or any other neighboring parts.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused
conduit entries shall be closed with suitable
blanking elements.
IMPORTANT
Do not test any wiring connected to the
detector with a meg-ohmmeter. Disconnect
wiring at the detector before checking
system wiring for continuity.
3.
Required EOL resistor power rating must be
5 watts minimum.
Make the final sighting adjustments and
use a 14 mm hex wrench to ensure that the
mounting arm assembly is tight.
7
95-8527
Figure 4—X3301 Terminal Block
9
mA +
19
mA –
29
SPARE
8
mA + REF
18
mA – REF
28
SPARE
7
COM FIRE
17
COM FIRE
27
COM AUX
6
N.O. FIRE
16
N.O. FIRE
26
N.O. AUX
5
N.C. FIRE
15
N.C. FIRE
25
N.C. AUX
4
COM FAULT
14
COM FAULT
24
RS-485 A
3
N.O. FAULT
13
N.O. FAULT
23
RS-485 B
2
24 VDC +
12
24 VDC +
22
MAN Oi
1
24 VDC –
11
24 VDC –
21
24 VDC –
D2061
Figure 5—X3301 Wiring Terminal Identification
3/8 INCH (10 MM) GAP MINIMUM
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
Figure 6—EOL Resistor Installation (For Ex d Wiring only)
19.4
8
95-8527
X3301 DETECTOR
FIRE ALARM PANEL
ALARM
+
24 VDC
–
9
mA +
19
mA –
SPARE
29
8
mA + REF
18
mA – REF
SPARE
28
7
COM FIRE2
COM FIRE
17
COM AUX
27
6
N.O. FIRE2
N.O. FIRE
16
N.O. AUX
26
5
N.C. FIRE2
N.C. FIRE
15
N.C. AUX
25
4
COM FAULT1
COM FAULT
14
RS-485 A
24
3
N.O. FAULT1
N.O. FAULT
13
RS-485 B
23
2
24 VDC +
12
24 VDC +
MAN Oi
22
1
24 VDC –
11
24 VDC –
24 VDC –
21
E.O.L.
DEVICE4
oi TEST 3
WIRING NOTES:
C2107
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
Figure 7—Ex d Wiring Option
X3301 DETECTOR
FIRE ALARM PANEL
EOL
RESISTOR 4
9
mA +
19
mA –
SPARE
29
8
mA + REF
18
mA – REF
SPARE
28
ALARM
7
COM FIRE2
COM FIRE
17
COM AUX
27
ALARM
6
N.O. FIRE2
N.O. FIRE
16
N.O. AUX
26
5
N.C. FIRE2
N.C. FIRE
15
N.C. AUX
25
4
COM FAULT1
COM FAULT
14
3
N.O. FAULT1
13
N.O. FAULT
2
24 VDC +
12
1
24 VDC –
11
+
24 VDC
–
RS-485 A
24
RS-485 B
23
24 VDC +
MAN Oi
22
24 VDC –
24 VDC –
21
oi TEST 3
D2109
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 EOL RESISTOR SUPPLIED BY PANEL.
Figure 8—Ex d e Wiring Option
19.4
9
95-8527
X3301 IR DETECTOR
24 VDC
+
–
PLC
9
600 Ω MAX
AT 24 VDC
19 mA –
mA +
SPARE
29
+
8
mA + REF
SPARE
28
–
7
COM FIRE
COM FIRE
17
COM AUX
27
6
N.O. FIRE
N.O. FIRE
16
N.O. AUX
26
5
N.C. FIRE
N.C. FIRE
15
N.C. AUX
25
4
COM FAULT COM FAULT
14
RS-485 A
24
3
N.O. FAULT
13
RS-485 B
23
2
24 VDC +
12
24 VDC +
MAN Oi
22
1
24 VDC –
11
24 VDC –
24 VDC –
21
mA
+
24 VDC
–
18
mA – REF
9
mA +
19
mA –
SPARE
29
+
8
mA + REF
18
mA – REF
SPARE
28
–
7
COM FIRE
COM FIRE
17
COM AUX
27
6
N.O. FIRE
N.O. FIRE
16
N.O. AUX
26
5
N.C. FIRE
N.C. FIRE
15
N.C. AUX
25
4
COM FAULT COM FAULT
14
RS-485 A
24
3
N.O. FAULT
13
RS-485 B
23
2
24 VDC +
12
24 VDC +
MAN Oi
22
1
24 VDC –
11
24 VDC –
24 VDC –
21
600 Ω MAX
AT 24 VDC
mA
24 VDC
N.O. FAULT
X3301 IR DETECTOR
PLC
+
–
N.O. FAULT
F2063
F2065
Oi TEST1
Oi TEST1
Figure 9—X3301 Detector Wired for Non-Isolated 0 to 20 mA
Current Output (Sourcing)
Figure 11—X3301 Detector Wired for Isolated 0 to 20 mA
Current Output (Sourcing)
24 VDC
+
–
X3301 IR DETECTOR
PLC
9
600 Ω MAX
AT 24 VDC
+
8
mA + REF
–
7
COM FIRE
mA
+
24 VDC
–
F2064
19
mA +
18
mA –
SPARE
29
SPARE
28
COM FIRE
17
COM AUX
27
N.O. AUX
26
mA – REF
X3301 IR DETECTOR
PLC
9
mA +
19
mA –
SPARE
29
+
8
mA + REF
18
mA – REF
SPARE
28
–
7
COM FIRE
COM FIRE
17
COM AUX
27
6
N.O. FIRE
N.O. FIRE
16
N.O. AUX
26
5
N.C. FIRE
N.C. FIRE
15
N.C. AUX
25
4
COM FAULT COM FAULT
14
RS-485 A
24
N.O. FAULT
13
RS-485 B
23
600 Ω MAX
AT 24 VDC
6
N.O. FIRE
N.O. FIRE
16
5
N.C. FIRE
N.C. FIRE
15
N.C. AUX
25
4
COM FAULT COM FAULT
14
RS-485 A
24
3
N.O. FAULT
N.O. FAULT
13
RS-485 B
23
2
24 VDC +
12
24 VDC +
MAN Oi
22
3
N.O. FAULT
1
24 VDC –
11
24 VDC –
24 VDC –
21
2
24 VDC +
12
24 VDC +
MAN Oi
22
1
24 VDC –
11
24 VDC –
24 VDC –
21
mA
+
24 VDC
–
F2066
Oi TEST1
Oi TEST1
Figure 10—X3301 Detector Wired for Non-Isolated 0 to 20 mA
Current Output (Sinking)
NOTES: 1.
19.4
Figure 12—X3301 Detector Wired for Isolated 0 to 20 mA
Current Output (Sinking)
INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE
INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.
10
95-8527
EQP Model
1.
Connect external wires to the appropriate
terminals inside the device junction box,
shown in Figure 13. See Figure 14 for
terminal identification.
2.
Connect the shield of the power cable to
“earth ground” at the power source.
3.
Connect shields for the LON cable as
indicated. See Figure 15.
5.
Check all field wiring to be sure that the
proper connections have been made.
6.
Replace the device cover and apply input
power.
7.
Make the final sighting adjustments and
use a 14 mm hex wrench to ensure that the
mounting arm assembly is tight.
NOTE
Refer to the Eagle Quantum Premier
system manual (95-8533) for information
regarding power requirements, network
communication cable requirements, and
configuration.
NOTE
DO NOT ground any shields at the detector
housing.
4.
With input power disconnected, set the
device network address (see the “Setting
Device Network Addresses” section of this
manual for switch setting procedure).
Figure 13—X3301 Terminal Block (EQP Model)
6
COM SHIELD
16
COM SHIELD
5
COM 1 A
15
COM 2 A
4
COM 1 B
14
COM 2 B
3
POWER SHIELD
13
POWER SHIELD
2
24 VDC +
12
24 VDC +
1
24 VDC –
11
24 VDC –
B2089
Figure 14—Wiring Terminal Identification for X3301 EQP Model
19.4
11
95-8527
19.4
P8
NC 47
FAULT NO 46
C 45
12
9 3+
RELAY 5
RELAY 6
RELAY 7
C 42
NO 43
NC 44
31 NO
32 NC
NC 41
29 NC
RELAY 3
30 C
C 39
NO 40
28 NO
NC 38
RELAY 2
27 C
C 36
NO 37
26 NC
NC 35
23 NC
25 NO
NO 34
22 NO
RELAY 1
24 C
C 33
DIGITAL INPUTS
21 C
P5
8– 20
A
4
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
C COMMON C
B IN–/OUT+ B
A + SUPPLY A
P3
1
2
3
CH 3
P4
8+ 19
7– 18
7+ 17
CH 7
12 4–
11 4+
B
5
P4
SHIELD
6
COM1
1
P2
24 VDC +
4
COM2
2
24 VDC –
5
3
SHIELD
6
P1
EQP3700DCIO
CH 2
10 3–
6– 16
6+ 15
5– 14
5+ 13
P3
A 56
B 55
CH 6
8 2–
7 2+
6 1–
5 1+
P2
59 TxD
58 RxD
57 GND GND 54
P9
50
A
53
CH 5
DB-9
CONNECTION
TO COM PORT
OF PC
TXD 3
RXD 2
GND 5
49
B
52
P6
48
SHIELD
51
COM1
1
P7
24 VDC +
3
COM2
2
24 VDC –
4
P1
CONTROLLER
CH 1
CH 4
CH 8
RELAY 4
RELAY 8
95-8527
–
–
24 VDC
BATTERY
+
H
N
AC LINE
24 VDC
SUPPLY
+
+
+
–
–
POWER
–
–
DISTRIBUTION
+
+
+
–
+ –
+ –
2
B
N
H
AC LINE
15
14
16
A
B
SHIELD
5
4
6
COM1
Figure 15—A Typical EQP System
4
3
1
2
P3
A
10
3
C
B
11
1
BUS BAR
SHIELD
12
COM2
12 24 VDC + 2
8
COM1
24 VDC +
5
COM2
11 24 VDC – 1
7
24 VDC –
3
6
SHIELD
EQPX3301
13
SHIELD
4
9
EQP2100PSM
3
15
14
16
COM2
A
B
SHIELD
5
4
6
COM1
12 24 VDC + 2
11 24 VDC – 1
SHIELD
EQPX3301
13
3
15
14
16
COM2
A
B
SHIELD
5
4
6
COM1
12 24 VDC + 2
11 24 VDC – 1
SHIELD
EQPX3301
13
3
B
A
14
15
5
4
6
COM1
SHIELD
16
COM2
12 24 VDC + 2
11 24 VDC – 1
SHIELD
EQPX3301
13
A2207
ADDRESS SWITCHES
SENSOR MODULE
REMOVED FROM HOUSING
A2191
Figure 16—Location of Address Switches
The address number is binary encoded with
each switch having a specific binary value with
switch 1 being the LSB (Least Significant Bit),
see Figure 17. The device’s LON address is
equal to the added value of all closed rocker
switches. All “Open” switches are ignored.
SETTING DEVICE NETWORK ADDRESSES
(EQP Model Only)
Overview of Network Addresses
Each device on the LON must be assigned a
unique address. Addresses 1 to 4 are reserved
for the controller. Valid addresses for field
devices are from 5 to 250.
Example: for node No. 5, close rocker switches
1 and 3 (binary values 1 + 4); for node No. 25,
close rocker switches 1, 4 and 5 (binary values
1 + 8 + 16).
IMPORTANT
If the address is set to zero or an address
above 250, the switch setting will be
ignored.
NOTE
The field device sets the LON address
only when power is applied to the device.
Therefore, it is important to set the switches
before applying power. If an address is
ever changed, system power must be
cycled before the new address will take
effect.
Duplicated addresses are not automatically
detected. Modules given the same address
will use the number given and report to the
controller using that address. The status word
will show the latest update, which could be
from any of the reporting modules using that
address.
After setting address switches, record the
address number and device type.
Setting Field Device Addresses
Selection of the node address is done by
setting rocker switches on an 8 switch “DIP
Switch Assembly” within the detector’s housing.
Refer to Figure 16 for switch location.
ON
WARNING
The network address switches are located
within the detector housing. Disassembly
of the detector head that contains
powered electrical circuits is required
to gain access to the network address
switches. For hazardous areas, the area
must be de-classified before attempting
disassembly of the device. Always observe
precautions for handling electrostatic
sensitive devices.
19.4
BINARY
VALUE
1
2
3
4
5
1
2
4
8
16 32 64 128
6
7
8
NODE ADDRESS EQUALS THE ADDED VALUE
OF ALL CLOSED ROCKER SWITCHES
OPEN = OFF
CLOSED = ON
A2190
Figure 17—Address Switches for X3301
13
95-8527
STARTUP PROCEDURE
Table 3—Current Level Output Troubleshooting Guide
When installation of the equipment is complete,
perform the “Fire Alarm Test” below.
FIRE ALARM TEST
1. Disable any extinguishing equipment that is
connected to the system.
2.
Apply input power to the system.
3.
Initiate an oi test (see “Magnetic oi / Manual
oi” under Optical Integrity in the Description
section of this manual).
4.
Repeat this test for all detectors in the
system. If a unit fails the test, refer to the
“Troubleshooting” section.
5.
Verify that all detectors in the system are
properly aimed at the area to be protected.
(The Q1201C Laser Aimer is recommended
for this purpose.)
6.
Current Level
(±0.3 mA)
Status
Action
0 mA
Power Fault
Check system
wiring
1 mA
2 mA
General Fault
Cycle power 1
oi Fault
3 mA
High Background IR
Fault
Clean windows2
Remove IR source
or aim detector
away from IR
source
4 mA
20 mA
Normal Operation
Fire Alarm
1
If fault continues, return device to factory for repair.
See “Maintenance” section for cleaning procedure.
NOTE: For additional troubleshooting guides, refer to the Flame Inspector
Monitor manual (95-8581).
2
Enable extinguishing equipment when the
test is complete.
3.
Check input power to the unit.
4.
If the fire system has a logging function,
check the fire panel log for output status
information. See Table 3 for information
regarding 0 to 20 mA output.
5.
Turn off the input power to the detector and
check all wiring for continuity. Important:
Disconnect wiring at the detector before
checking system wiring for continuity.
6.
If all wiring checks out and cleaning of
the oi plate/window did not correct the
fault condition, check for high levels of
background IR radiation by covering the
detector with the factory supplied cover
or aluminum foil. If the fault condition
clears within 6 minutes or less, extreme
background IR is present. Re-adjust the
view of the detector away from the IR source
or relocate the detector.
TROUBLESHOOTING
WARNING
The sensor module (“front” half of the
detector) contains no user serviceable
components and should never be opened.
The terminal compartment is the only part of
the enclosure that should be opened by the
user in the field.
1. Disable any extinguishing equipment that is
connected to the unit.
If none of these actions corrects the problem,
return the detector to the factory for repair.
2. Inspect the viewing windows for contamination
and clean as necessary. The detector is
relatively insensitive to airborne contaminants,
however, thick deposits of ice, dirt, or oil will
reduce sensitivity. (Refer to the “Maintenance”
section for complete information regarding
cleaning of the detector viewing windows.)
19.4
NOTE
It is highly recommended that a complete
spare be kept on hand for field replacement
to ensure continuous protection.
14
95-8527
MAINTENANCE
LOOSEN TWO CAPTIVE SCREWS
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not
intended to be serviced and provides
proper ingress protection to eliminate
potential deterioration of the flamepaths.
GRASP VISOR AND
REMOVE oi PLATE
WARNING
The sensor module (“front” half of the
detector) contains no user serviceable
components and should never be opened.
The terminal compartment is the only part of
the enclosure that should be opened by the
user in the field.
NOTE
Refer to the X3301 Safety manual (958582) for specific requirements and
recommendations applicable to the
p ro p e r i n s ta l l a t i o n , o p e ra t i o n , a n d
maintenance of all SIL-Certified X3301
Flame Detectors.
B2106
Figure 18—oi Plate Removal
IMPORTANT
When used in extreme environments, the
reflective surface of the detector oi plate
may eventually deteriorate, resulting in
reoccurring oi faults and the need for oi
plate replacement.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X3301
must be kept relatively clean. Refer to the
following procedure for cleaning instructions.
oi PLATE REMOVAL AND REPLACEMENT
CLEANING PROCEDURE
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
1.
Disable any extinguishing equipment that
is connected to the unit.
2.
Loosen the two captive screws, then grasp
the oi plate by the visor and remove it from
the detector. See Figure 18.
3.
Install the new (or cleaned) oi plate.
NOTE
When installing the stainless steel plate,
ensure that the gasket is present and
correctly seated to prevent moisture or
contaminants from penetrating behind the
plate. To ensure even seating, tighten both
screws equally.
To clean the windows and oi plate, use the
window cleaner (p/n 001680-001) and a soft
cloth, cotton swab, or tissue and refer to the
following procedure:
1.
Disable any extinguishing equipment that is
connected to the unit.
2.
Since the X3301 is less affected by
contamination than other detectors, removal
of the oi plate is needed only under extreme
conditions. In addition, it is not necessary
to achieve perfect cleanliness, because IR
is not significantly absorbed by slight films
of oil and/or salt. If a fault condition is still
indicated after cleaning, remove and clean
the oi plate using the oi Plate Removal and
Replacement procedure.
4. Recalibrate the detector's oi system.
Refer to the Inspector Monitor manual (958581) for instructions regarding oi plate
replacement and oi system recalibration.
In all environments, clean all three viewing
windows and reflector surfaces thoroughly.
Use a cotton swab and the Det-Tronics
window cleaning solution. Use Isopropyl
alcohol for contaminations that the DetTronics window cleaning solution can not
remove.
Recalibration of the oi system requires the use
of the Inspector Connector Cable and Inspector
Monitor Software. These two items are included in
the oi replacement kit, or they can be purchased
separately. See Ordering Information for details.
3.
19.4
CAUTION
Do not replace the o i reflector plate
without also recalibrating the oi system.
15
95-8527
FEATURES
X3301 Reflector Plates
X3301 models are supplied with either a black or
a stainless steel reflector plate. These plates are
not interchangeable. Order the replacement that
matches the reflector plate on your X3301 Flame
Detector.
• Long detection range to carbonaceous fires
• Unequaled false alarm rejection
• Responds to a fire in the presence of
modulated blackbody radiation (i.e. heaters,
ovens, turbines) without false alarm
• Microprocessor controlled heated optics for
increased resistance to moisture and ice
• Automatic, manual, or magnetic oi testing
• Easily replaceable oi plate
• Fire, fault and auxiliary relays standard
• 0 to 20 mA isolated output (optional)
• Eagle Quantum Premier LON/SLC output
(optional)
• HART communication (optional)
• FDT/DTM capable
• Multiple sensitivity levels
• A tri-color LED on the detector faceplate
indicates normal condition and notifies
personnel of fire alarm or fault conditions
• Operates under adverse weather conditions
and in dirty environments
• Mounting arm allows easy sighting
• Integral wiring compartment for ease of
installation
• Explosion-proof/flame-proof
detector
housing. Meets FM, CSA, ATEX Directive and
CE certification requirements
• Class A wiring per NFPA-72
• Meets NFPA-33 response requirement for
under 0.5 second (available when model
selected)
• 5 year warranty
• RFI and EMC Directive compliant
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the
system using the Mag oi or Man oi feature
should performed regularly to ensure that the
system is operating properly. Refer to Table 1 in
the X3301 Safety manual (95-8582) for frequency
of proof tests. To test the system, perform the
“Fire Alarm Test” as described in the “Startup
Procedure” section of this manual.
CLOCK BATTERY
The real time clock has a backup battery that
will operate the clock with no external power.
Return the device to the factory for battery
replacement if needed.
NOTE
If the backup battery is depleted, there is no
effect on the operation of the flame detector,
but the time stamping of the data log may
be affected.
Associated Manuals
List of X3301 related manuals:
TITLE
Pulse
EQP
SIL 2 (Safety)
HART Addendum
Automotive Addendum
Hangar
Q9033 Mounting Arm
and Collar Attachment
Inspector Monitor Software for
X-Series Flame Detectors
Q1130 Flange Mount
19.4
16
FORM NUMBER
95-8528
95-8533
95-8582
95-8577
95-8534
95-8548
95-8686
95-8581
95-8662
95-8527
SPECIFICATIONS
CURRENT OUTPUT (OPTIONAL)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc
maximum).
Maximum ripple is 2 volts
peak-to-peak.
LON OUTPUT—
Digital communication, transformer isolated (78.5
kbps).
POWER CONSUMPTION—
Without heater: 4 watts at 24 Vdc nominal;
5.2 watts at 24 Vdc in alarm.
4.5 watts at 30 Vdc nominal;
6.5 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power: 17 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts.
For HART model, refer to Addendum number
95-8577.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +125°C.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
CONE OF VISION—
The detector has a 90° cone of vision (horizontal)
with the highest sensitivity lying along the central
axis. Unlike conventional detectors, the X3301
provides full coverage at a minimum of 70% of
the maximum detection distance.
POWER UP TIME—
Fault indication clears after 0.5 second; device
is ready to indicate an alarm condition after 30
seconds.
Perfect cone of vision for methane fire detection
— 100 feet (30.5 m) on and off axis on “very high”
setting.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Refer to Appendix A for FM Approved cone of
vision data.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching
operation.
RESPONSE TIME—
Typical response times are under 10 seconds.
Models are available that can respond to
automotive paint gun fires in under 0.5 seconds.
See Appendix A and “Automotive Addendum”
(95-8534) for actual response times.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open/normally
closed contacts, normally energized or deenergized operation, and latching or non-latching
operation.
DIMENSIONS—
See Figure 19.
4.7
(11.9)
B2067
10.0
(25.4)
4.8
(12.2)
Figure 19—X3301 Dimensions in Inches (cm)
19.4
17
95-8527
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless
Steel (316/CF8M Cast).
CERTIFICATION—
FM
®
APPROVED
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD
810C (Curve AW), DNV Note 2.4 (Class B).
VdS
WIRING—
Field wiring screw terminals are UL/CSA rated
for up to 14 AWG wire, and are DIN/VDE rated
for 2.5 mm2 wire. Screw terminal required torque
range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m).
For complete approval details, refer to the
appropriate Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - EN54
Appendix F - Offshore
Appendix G - Additional approvals
Important: 18 Vdc minimum must be available
at the detector. For ambient temperatures below
–10°C (14°F) and above +60°C (140°F) use field
wiring suitable for both minimum and maximum
ambient temperature.
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT
or M25.
Conduit seal not required.
SHIPPING WEIGHT (Approximate)—
Aluminum: 7 pounds (3.2 kilograms).
Stainless Steel: 13.8 pounds (6.3 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).
WARRANTY PERIOD—
5 years.
19.4
18
95-8527
REPLACEMENT PARTS
ORDERING INFORMATION
The detector is not designed to be repaired in the
field. If a problem should develop, refer to the
Troubleshooting section. If it is determined that
the problem is caused by an electronic defect,
the device must be returned to the factory for
repair.
When ordering, please specify:
X3301 Multispectrum IR Flame Detector
Refer to the X3301 Model Matrix for details
Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel
detectors
REPLACEMENT PARTS LIST
Part Number
009208-001
010831-001
007307-001
010830-001
Description
oi Replacement kit for X3301 (5 Black Reflector Plates)
with Inspector Connector and Monitor
oi Replacement kit for X3301 (5 Stainless Steel Reflector
Plates) with Inspector Connector and Monitor
Replacement oi Reflector Plates for X3301 with Black plate
(requires Inspector Connector to calibrate)
Replacement oi Reflector Plates for X3301 with Stainless
Steel plate (requires Inspector Connector to calibrate)
ACCESSORIES
Description
000511-029
103881-001
Converter RS485 to RS232
Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
007819-001
NOTE: Refer to instruction manual 95-8530 to determine the correct oi
Replacement Plate.
007819-002
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
009207-001
Flame Inspector Monitor CD
103922-001
Model 475 HART Communicator
102740-002
Magnet
008082-001
Magnet and Adapter for Extension Pole
007739-001
Magnet and Extension Pole
007240-001
Q1116A1001, Air Shield (AL)
007818-001 Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange
007818-002
Mount (SS)
009177-001
Q1120A1001 Paint Shield mounting ring (AL)
010857-001
Q1130A1001 Flange Mount Assembly
006097-001
Q1201 Laser
Laser Battery, 3V Lithium (laser)
102871-001
007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic)
007338-001
Q2000A1001 X-Series Weather Shield (AL)
007338-010 Q2033A10R X3301/X3302 FOV Limiter 10° (AL)
007338-020 Q2033A20R X3301/X3302 FOV Limiter 20° (AL)
007338-030 Q2033A30R X3301/X3302 FOV Limiter 30° (AL)
007912-010
Spare Restrictor Plate 10° (AL)
007912-020
Spare Restrictor Plate 20° (AL)
007912-030
Spare Restrictor Plate 30° (AL)
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest
local Detector Electronics office so that a Return
Material Identification (RMI) number can be
assigned. A written statement describing the
malfunction must accompany the returned
device or component to assist and expedite
finding the root cause of the failure.
Pack the unit properly. Always use sufficient
packing material. Where applicable, use an
antistatic bag as protection from electrostatic
discharge.
NOTE
Det-Tronics reserves the right to apply a
service charge for repairing returned
product damaged as a result of improper
packaging.
Return all equipment transportation prepaid to the
factory in Minneapolis.
NOTE
It is highly recommended that a complete
spare be kept on hand for field replacement
to ensure continuous protection.
19.4
Part Number
19
007290-001
Q9033B Stainless Steel Mounting Arm Assembly
is for aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for
aluminum detectors only
011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
107427-040
005003-001
001680-001
Q9033 Collar Attachment
Stop Plug, 3/4” NPT, AL
Stop Plug, 3/4” NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4”NPT, AL
Stop Plug, 20 Pack, 3/4”NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
O-ring - Rear Cover (Viton)
1 oz grease for detectors (non-silicon)
Window cleaner (6 pack)
95-8527
X3301 MODEL MATRIX
MODEL
X3301
DESCRIPTION
Multispectrum IR Flame Detector
TYPE
MATERIAL
A
Aluminum
S
Stainless Steel (316)
TYPE
THREAD TYPE
4M
4 Port, Metric M25
4N
4 Port, 3/4" NPT
TYPE
OUTPUTS
11
Relay
13
Relay and 0-20 mA
14
Eagle Quantum Premier (EQP)
15
Relay and Pulse
16
Addressable Module Only (Third Party Type)*
21
Relay-Automotive
22
EQP Automotive
23
HART, Relay and 0-20 mA
TYPE
APPROVALS***
B
INMETRO (Brazil)
K
Kazakhstan
R
VNIIPO/VNIIFTRI (Russia)
S
SIL
T
SIL/FM/CSA/ATEX/IECEx
W
FM/CSA/ULC**/ATEX/IECEx
Y
NEPSI/CCCF (China)
TYPE
CLASSIFICATION
1
Division/Zone Ex d e
2
Division/Zone Ex d
*The Addressable Module Only (Type 16) is not FM approved.
**ULC approval applies to output types 11, 13, 15, 21, and 23.
***Type Approvals can use one or more letters to designate
the approvals of the product.
19.4
20
95-8527
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:
• Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA/Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
for Class I, Zone 1 AEx d e IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
AEx d IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)
for Zone 21 AEx tb T130°C Db
Tamb –40°C to +75°C
Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S.
The following accessories are FM approved for use with the X3301 Flame Detector:
Part Number
102740-002
007739-001
010857-001
007290-001
007290-002
011385-001
Description
Magnet
Magnet and Extension Pole
Q1130A1001 Flange Mount Assembly
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of
lens surfaces resulting in a loss of approximately 50% of its detection range, verifying that the detector
performs a calibrated Automatic oi test for each sensor. Upon removal of the contamination, the
detector fault was cleared and the detector was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally
actuates the alarm relay to verify output operation. If there is a 50% loss of its detection range, an alarm
signal is not generated.
The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual,
is the approved external optical test method for this detector to verify end-to-end detector function. This
test replaces the function and need of a traditional external test lamp.
19.4
21
95-8527
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
Size
Distance feet (m)
Average Response Time (seconds)***
n-Heptane
n-Heptane**
n-Heptane
n-Heptane
Isopropanol
Diesel**
Ethanol
Methanol
Methanol
Methanol**
Methane
JP-5**
JP-5**
JP-5**
Office Paper 0.5 lb.
Corrugated Panel
1 x 1 foot
1 x 1 foot
1 x 1 foot
6 in. x 6 in.
6 in. x 6 in.
1 x 1 foot
1 x 1 foot
6 in. x 6 in.
1 x 1 foot
1 x 1 foot
30 inch plume
1 x 1 foot
2 x 2 feet
2 x 2 feet
19" x 19" x 8"
18" x 36"
210 (64)*
210 (64)*
100 (30.5)
80 (24.4)
70 (21.3)
150 (45.7)*
210 (64)
40 (12.2)
150 (45.7)*
150 (45.7)*
100 (30.5)
150 (45.7)*
210 (64)*
100 (30.5)
100 (30.5)
100 (30.5)
11
6
3
3
4
14
11
3
18
7
3
2
4
2
4
8
Distance feet (m)
100 (30.5)
50 (15.2)
70 (21.3)
85 (25.9)
70 (21.3)
65 (19.8)
55 (16.8)
100 (30.5)
50 (15.2)
50 (15.2)
Average Response Time (seconds)***
12
2
4
13
10
3
2
3
6
2
Distance feet (m)
50 (15.2)
20 (6.1)
15 (4.6)
Average Response Time (seconds)***
7
5
4
*
**
***
Outdoor test condition.
Pre-burn from ignition.
Add 2 seconds for EQP model.
Medium Sensitivity
Fuel
n-Heptane
n-Heptane
Diesel**
Ethanol
Methanol
Methane
Methane
JP-5**
Office Paper 0.5 lb.
Corrugated Panel
**
***
Size
1 x 1 foot
1 x 1 foot
1 x 1 foot
1 x 1 foot
1 x 1 foot
30 inch plume
30 inch plume
2 x 2 feet
19" x 19" x 8"
18" x 36"
Pre-burn from ignition.
Add 2 seconds for EQP model.
T-Low Sensitivity
Fuel
n-Heptane
Methanol
Methane
Size
1 x 1 foot
1 x 1 foot
32 inch plume
*** Add 2 seconds for EQP model.
Low Sensitivity
Fuel
Size
Distance feet (m)
Average Response Time (seconds)***
n-Heptane
1 x 1 foot
50 (15.2)
10
Methanol
1 x 1 foot
20 (6.1)
10
Methane
32 inch plume
15 (4.6)
9
*** Add 2 seconds for EQP model.
19.4
22
95-8527
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
Very High Sensitivity
False Alarm Source
Sunlight, direct, modulated, reflected
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response
Time (seconds)***
—
6-inch propane
6 (1.8)
< 10
N/A
3-inch propane
10.5 (3.2)
< 10
1 (0.3)
3-inch propane
12 (3.7)
< 10
Arc welding, #7014
40 (12.2)
1 x 1 foot n-Heptane
40 (12.2)
4
6 kw heater, modulated
80 (24.4)
1 x 1 foot n-Heptane
80 (24.4)
2
6 kw heater, unmodulated
10 (3)
1 x 1 foot n-Heptane
80 (24.4)
3
250 w vapor lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
80 (24.4)
2
300 w incandescent lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
80 (24.4)
7
500 w shielded quartz halogen lamp, modulated
8 (2.4)
1 x 1 foot n-Heptane
80 (24.4)
2
500 w unshielded quartz halogen lamp, modulated
8 (2.4)
1 x 1 foot n-Heptane
80 (24.4)
3
1500 w electric radiant heater, modulated
10 (3)
1 x 1 foot n-Heptane
80 (24.4)
5
Two 34 w fluorescent lamps, modulated
3 (0.9)
1 x 1 foot n-Heptane
80 (24.4)
3
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response
Time (seconds)***
Sunlight, direct, modulated, reflected
—
6-inch propane
6 (1.8)
<4
Vibration*
N/A
N/A
N/A
N/A
Vibration
Radio frequency interference
*** Add 2 seconds for EQP model.
Medium Sensitivity
False Alarm Source
Radio frequency interference
1 (0.3)
6-inch propane
6 (1.8)
<1
Arc welding, #7014
10 (3)
1 x 1 foot n-Heptane
40 (12.2)
4
60 (18.3)
1 x 1 foot n-Heptane
60 (18.3)
2
6 kw heater, unmodulated
10 (3)
1 x 1 foot n-Heptane
60 (18.3)
2
250 w vapor lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
60 (18.3)
1
300 w incandescent lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
60 (18.3)
1
500 w shielded quartz halogen lamp, modulated
8 (2.4)
1 x 1 foot n-Heptane
60 (18.3)
1
500 w unshielded quartz halogen lamp, modulated
8 (2.4)
1 x 1 foot n-Heptane
60 (18.3)
1
1500 w electric radiant heater, modulated
10 (3)
1 x 1 foot n-Heptane
60 (18.3)
6
Two 34 w fluorescent lamps, modulated
3 (0.9)
1 x 1 foot n-Heptane
60 (18.3)
2
6 kw heater, modulated
*
***
19.4
Fire was verified with very high sensitivity only.
Add 2 seconds for EQP model.
23
95-8527
FM Approval and Performance Report – Continued
T-Low Sensitivity
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response
Time (seconds)***
Sunlight, direct, unmodulated, reflected*
—
1 x 1 foot n-Heptane
35 (10.7)
<6
Sunlight, direct, modulated, reflected*
—
1 x 1 foot n-Heptane
15 (4.6)
<4
Arc welding, steady, #7014
5 (1.5)
1 x 1 foot n-Heptane
50 (15.2)
10
Arc welding, modulated, #7014
5 (1.5)
1 x 1 foot n-Heptane
30 (9.1)
3
70 w sodium vapor, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
6
70 w sodium vapor, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
7
250 w vapor lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
8
250 w vapor lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
6
300 w incandescent lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
7
300 w incandescent lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
8
500 w shielded quartz halogen lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
4
500 w shielded quartz halogen lamp, modulated
10 (3)
1 x 1 foot n-Heptane
50 (15.2)
5
1500 w electric radiant heater, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
5
1500 w electric radiant heater, modulated
10 (3)
1 x 1 foot n-Heptane
30 (9.1)
7
Two 34 w fluorescent lamps, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
5
Two 34 w fluorescent lamps, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
4
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response
Time (seconds)***
False Alarm Source
*
***
Outdoor test conditions.
Add 2 seconds for EQP model.
Low Sensitivity
False Alarm Source
Sunlight, direct, unmodulated, reflected*
—
1 x 1 foot n-Heptane
35 (10.7)
< 13
Sunlight, direct, modulated, reflected*
—
1 x 1 foot n-Heptane
15 (4.6)
< 14
Arc welding, steady, #7014
5 (1.5)
1 x 1 foot n-Heptane
50 (15.2)
11
Arc welding, modulated, #7014
5 (1.5)
1 x 1 foot n-Heptane
30 (9.1)
10
70 w sodium vapor, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
16
250 w vapor lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
18
300 w incandescent lamp, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
18
500 w shielded quartz halogen lamp, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
12
500 w shielded quartz halogen lamp, modulated
10 (3)
1 x 1 foot n-Heptane
50 (15.2)
11
1500 w electric radiant heater, unmodulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
12
1500 w electric radiant heater, modulated
10 (3)
1 x 1 foot n-Heptane
30 (9.1)
11
Two 34 w fluorescent lamps, modulated
3 (0.9)
1 x 1 foot n-Heptane
50 (15.2)
14
*
***
19.4
Outdoor test conditions.
Add 2 seconds for EQP model.
24
95-8527
FM Approval and Performance Report – Continued
FALSE ALARM IMMUNITY
Very High Sensitivity
False Alarm Source
Sunlight, direct, reflected
Vibration
Radio frequency interference
Distance
feet (m)
Modulated Response
Unmodulated Response
No alarm
—
No alarm
N/A
No alarm
N/A
1 (0.3)
No alarm (keyed)
No alarm (steady)
Arc welding
40 (12.2)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
500 w shielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Distance
feet (m)
Modulated Response
Unmodulated Response
No alarm
Medium Sensitivity
False Alarm Source
Sunlight, direct, reflected
Vibration
Radio frequency interference
—
No alarm
N/A
No alarm
N/A
1 (0.3)
No alarm (keyed)
No alarm (steady)
Arc welding
10 (3)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Distance
feet (m)
Modulated Response
Unmodulated Response
T-Low Sensitivity
False Alarm Source
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
Arc welding
5 (1.5)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
70 w sodium vapor
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
19.4
25
95-8527
FM Approval and Performance Report – Continued
Low Sensitivity
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
N/A
No alarm
N/A
Arc welding
5 (1.5)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
False Alarm Source
Radio frequency interference
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
FIELD OF VIEW
Very High Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Avg. Horiz.
Response
Time (seconds)***
Vertical
(degrees)
Avg. Vert.
Response
Time (seconds)***
n-Heptane
1 x 1 foot
150*
(45.7)
+45
-45
12
14
+45
-30
13
5
n-Heptane
1 x 1 foot
100
(30.5)
+45
-45
6
3
+45
-30
3
2
n-Heptane
6 in. x 6 in.
80
(24.4)
+45
-45
5
6
+45
-30
4
4
Isopropanol
6 in. x 6 in.
70
(21.3)
+45
-45
5
5
+45
-30
4
6
Diesel**
1 x 1 foot
100
(30.5)
+45
-45
2
3
+45
-30
4
3
Ethanol
1 x 1 foot
150
(45.7)
+45
-45
13
10
+45
-30
10
8
Methanol
6 in. x 6 in.
40
(12.2)
+45
-45
4
6
+45
-30
3
3
Methanol
1 x 1 foot
110
(33.5)
+45
-45
9
7
+45
-30
9
3
Methane
30 inch
plume
100
(30.5)
+45
-45
7
3
+45
-30
2
2
JP-5**
1 x 1 foot
100
(30.5)
+45
-45
2
4
+45
-30
3
2
JP-5**
2 x 2 feet
180*
(54.9)
+45
-45
2
5
+45
-30
3
2
JP-5**
2 x 2 feet
90
(27.4)
+45
-45
2
3
+45
-30
1
2
80
(24.4)
+45
-45
4
2
+45
-30
2
1
80
(24.4)
+45
-45
1
1
+45
-30
3
2
Office Paper 0.5 lb. 19" x 19" x 8"
Corrugated Panel
18" x 36"
*
Outdoor test condition.
** Pre-burn from ignition.
*** Add 2 seconds for EQP model.
19.4
26
95-8527
FM Approval and Performance Report – Continued
Medium Sensitivity
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Avg. Horiz.
Response
Time (seconds)***
Vertical
(degrees)
Avg. Vert.
Response
Time (seconds)***
n-Heptane
1 x 1 foot
75
(22.9)
+45
-45
9
6
+45
-30
10
7
n-Heptane
1 x 1 foot
50
(15.2)
+45
-45
4
3
+45
-30
3
3
Diesel**
1 x 1 foot
60
(18.3)
+45
-45
4
4
+45
-30
4
2
Ethanol
1 x 1 foot
60
(18.2)
+45
-45
12
9
+45
-30
12
9
Methanol
1 x 1 foot
50
(15.2)
+45
-45
9
3
+45
-30
9
1
Methane
32 inch plume
45
(13.7)
+45
-45
3
3
+45
-30
7
1
JP-5**
2 x 2 feet
90
(27.4)
+45
-45
4
2
+45
-30
2
2
Office Paper
0.5 lb.
19" x 19" x 8"
40
(12.2)
+45
-45
2
1
+45
-30
1
1
Corrugated
Panel
18" x 36"
40
(12.2)
+45
-45
2
1
+45
-30
1
1
**
***
Pre-burn from ignition.
Add 2 seconds for EQP model.
T-Low Sensitivity
***
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
Avg. Horiz.
Response
Time (seconds)***
Vertical
(degrees)
Avg. Vert.
Response
Time (seconds)***
n-Heptane
1 x 1 foot
35
(10.7)
+45
-45
7
7
+45
-30
7
7
Methanol
1 x 1 foot
15
(4.6)
+45
-45
5
5
+45
-30
5
5
Methane
32 inch
plume
15
(4.6)
+45
-45
4
4
+45
-30
4
4
Add 2 seconds for EQP model.
Low Sensitivity
***
19.4
Avg. Horiz.
Vertical
Response
(degrees)
Time (seconds)***
Avg. Vert.
Response
Time (seconds)***
Fuel
Size
Distance
feet (m)
Horizontal
(degrees)
n-Heptane
1 x 1 foot
35
(10.7)
+45
-45
13
13
+45
-30
9
18
Methanol
1 x 1 foot
15
(4.6)
+45
-45
14
12
+45
-30
10
8
Methane
32 inch
plume
15
(4.6)
+45
-45
10
11
+45
-30
8
10
Add 2 seconds for EQP model.
27
95-8527
FM Approval and Performance Report – Continued
HIGH RESOLUTION FIELD OF VIEW
15°
30°
0°
210 (64)
0°
15° 70 (21.3)
15°
30°
180 (54.9)
45°
30°
45°
45°
150 (45.7)
30 (9.1)
20 (6.1)
60 (18.3)
10 (3)
30 (9.1)
10 (3)
30 (9.1)
30°
20 (6.1)
30°
60 (18.3)
30 (9.1)
90 (27.4)
15°
40 (12.2)
15°
120 (36.5)
50 (15.2)
150 (45.7)
0°
180 (54.9)
15°
30°
0°
15° 80 (24.4)
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
70 (21.3)
45°
30°
30°
60 (18.3)
15°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Isopropanol at Very High Sensitivity (6 in. x 6 in.)
15°
70 (21.3)
45°
0°
60 (18.3)
Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (1 x 1 foot)
30°
45°
40 (12.2)
90 (27.4)
45°
30°
50 (15.2)
120 (36.5)
210 (64)
15°
60 (18.3)
45°
45°
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
0°
15° 150 (45.7) 15°
135 (41.2)
120 (36.6)
105 (32)
90 (27.4)
75 (22.9)
60 (18.3)
45 (13.7)
30 (9.1)
15 (4.6)
30°
45°
Field of View at Indicated Distance in Feet (m) for
Diesel at Very High Sensitivity (1 x 1 foot)
10 (3)
20 (6.1)
30°
30 (9.1)
40 (12.2)
15°
50 (15.2)
60 (18.3)
0°
70 (21.3)
80 (24.4)
45°
15°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (6 in. x 6 in.)
19.4
28
95-8527
FM Approval and Performance Report – Continued
15°
30°
0°
210 (64)
15°
180 (54.9)
45°
30°
30°
45°
45°
150 (45.7)
120 (36.5)
90 (27.4)
60 (18.3)
30 (9.1)
30°
45°
Field of View at Indicated Distance in Feet (m) for
Methanol at Very High Sensitivity (1 x 1 foot)
30 (9.1)
30°
60 (18.3)
90 (27.4)
30°
15°
120 (36.5)
45°
150 (45.7)
0°
180 (54.9)
15°
210 (64)
45°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Ethanol at Very High Sensitivity (1 x 1 foot)
30°
0°
15° 40 (12.2)
10 (3)
20 (6.1)
30 (9.1)
40 (12.2)
50 (15.2)
60 (18.3)
70 (21.3)
80 (24.4)
90 (27.4)
100 (30.5)
15°
30°
35 (10.7)
30 (9.1)
45°
45°
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
45°
5 (1.5)
10 (3)
30°
45°
30°
15°
0°
15°
30°
0°
15° 210 (64)
30°
30°
15 (4.6)
20 (6.1)
45°
15°
25 (7.6)
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
180 (54.9)
150 (45.7)
15°
30°
45°
120 (36.5)
30 (9.1)
0°
35 (10.7)
40 (12.2)
45°
0°
15° 100 (30.5) 15°
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
Field of View at Indicated Distance in Feet (m) for
Methane at Very High Sensitivity (30 inch plume)
5 (1.5)
15°
30°
90 (27.4)
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
60 (18.3)
30 (9.1)
Field of View at Indicated Distance in Feet (m) for
Methanol at Very High Sensitivity (6 in. x 6 in.)
19.4
0°
15° 150 (45.7) 15°
135 (41.2
120 (36.5)
105 (32)
90 (27.4)
75 (22.9)
60 (18.3)
45 (13.7)
30 (9.1)
15 (4.6)
Field of View at Indicated Distance in Feet (m) for
JP-5 at Very High Sensitivity (2 x 2 feet)
29
95-8527
FM Approval and Performance Report – Continued
30°
45°
0°
15° 100 (30.5) 15°
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
30°
30°
45°
45°
0°
15° 70 (21.3)
45°
60 (18.3)
30°
45°
50 (15.2)
30 (9.1)
20 (6.1)
10 (3)
Field of View at Indicated Distance in Feet (m) for
Methanol at Medium Sensitivity (1 x 1 foot)
15°
30°
60 (18.3)
15°
40 (12.2)
Field of View at Indicated Distance in Feet (m) for
n-Heptane at Medium Sensitivity (1 x 1 foot)
30°
0°
15° 70 (21.3)
30°
45°
50 (15.2)
0°
15° 65 ( 19.8) 15°
60 (18.3)
30°
50 (15.2)
45°
45°
40 (12.2)
40 (12.2)
30 (9.1)
30 (9.1)
20 (6.1)
20 (6.1)
10 (3)
10 (3)
Field of View at Indicated Distance in Feet (m) for
Diesel at Medium Sensitivity (1 x 1 foot)
Field of View at Indicated Distance in Feet (m) for
Methane at Medium Sensitivity (30 inch plume)
30°
45°
0°
15° 85 (25.9)
80 (24.4)
75 (22.9)
65 (19.8)
55 (16.8)
45 (13.7)
35 (10.7)
25 (7.6)
15 (4.6)
5 (1.5)
15°
30°
30°
45°
45°
Field of View at Indicated Distance in Feet (m) for
Ethanol at Medium Sensitivity (1 x 1 foot)
0°
15° 100 (30.5) 15°
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
30°
45°
Field of View at Indicated Distance in Feet (m) for
JP-5 at Medium Sensitivity (2 x 2 foot)
NOTE
FM Approvals minimum requirements
are response distance measurements at
0° (on axis) and the limits of the field of
view. These high resolution field of view
diagrams show the measured response
distances at all the indicated angles in the
horizontal plane.
19.4
30
95-8527
APPENDIX B
CSA APPROVAL
Multispectrum IR Flame Detector/Controller X3301 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts.
Relay contacts rated 30 Vdc, 5 Amps.
NOTE
Hazardous location testing has been successfully completed on the Model X3301 series from
an ambient temperature range of –55°C to +125°C; however, the detector label marking indicates
–40°C to +75°C.
The following accessories are CSA approved for use with the X3301 Flame Detector:
Part Number
102740-002
007739-001
010857-001
007290-001
007290-002
011385-001
Description
Magnet
Magnet and Extension Pole
Q1130A1001 Flange Mount Assembly
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
DIVISION CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A);
Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C);
Class III; Enclosure NEMA/Type 4X;
Conduit seal not required.
APPLICABLE REQUIREMENTS
CSA Std C22.2 No. 25-1966
–
Enclosures for use in Class II Groups E, F & G Hazardous Locations
CSA Std C22.2 No. 30-M1986
–
Explosion-Proof Enclosures for use in Class I Hazardous Locations
CAN/CSA C22.2 No. 94-M91
–
Special Purpose Enclosures
CSA Std C22.2 No. 142-M1987
–
Process Control Equipment
CSA Std C22.2 No. 213-M1987
–
Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex d e IIC T5-T6
T6 (Ta -50oC to +60oC)
T5 (Ta -50oC to +75oC)
Seal required adjacent to enclosure
IP66/IP67.
Ex d IIC T4-T6
T6 (Ta -55oC to +60oC)
T5 (Ta -55oC to +75oC)
T4 (Ta -55oC to +125oC)
Seal required adjacent to enclosure
IP66/IP67.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0:07
– Electrical apparatus for explosive gas atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1:11
– Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7:12
– Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
19.4
31
95-8527
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 01 ATEX 130204X
Increased Safety Model
0539
FM
®
APPROVED
II 2 G
II 2 D
Flameproof Model
FM
II 2 G
II 2 D
0539
®
APPROVED
Ex d e IIC T6–T5 Gb
Ex d IIC T6–T4 Gb
Ex tb IIIC T130°C
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67.
T4 (Tamb = –55°C to +125°C)
IP66/IP67.
Compliance with:
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-31: 2009
EN/IEC 60529: 2001.
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring
specifications from 14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with
the terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with EN600791 clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by
Detector Electronics Corporation only.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk
of mechanical damage.
19.4
32
95-8527
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof
model unless the addressable module is component certified as Ex e for use within the Ex d e
increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking
elements shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection
increased safety “e” or flameproof enclosure “d” (as applicable), suitable for the conditions of
use and correctly installed. They shall maintain the degree of ingress protection IP66/IP67 for
the apparatus. Unused conduit entries shall be closed with suitable blanking elements.
NOTE
For ATEX installations, the X3301 Flame Detector housing must be electrically connected to
earth ground.
The following accessories are ATEX approved for use with the X3301 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
19.4
33
95-8527
APPENDIX D
IECEx APPROVAL
IECEx CERTIFICATE OF CONFORMITY
DEMKO
IECEx ULD 06.0017X
Ex d e IIC T6-T5 Gb
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C)
IP66/IP67.
or
Ex d IIC T6-T4 Gb
Ex tb IIIC T130°C
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C)
IP66/IP67.
Compliance with:
IEC 60079-0: 2007, Ed. 5
IEC 60079-1: 2007, Ed. 6
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
EN/IEC 60529: 2001.
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring
specifications from
14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use
with the terminal compartment in type of explosion protection flameproof enclosure "d" or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e". They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with IEC 60079-1
clause 5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector
Electronics Corporation only.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed
2.5 watts.
The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk
of mechanical damage.
The following accessories are IECEx approved for use with the X3301 Flame Detector:
Part Number
Description
007290-001
007290-002
011385-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
19.4
34
95-8527
APPENDIX E
EN54 APPROVALS
Conventional Output
AGENCY
VdS –
Constructive Product Directive
Basis of Approval
Certificate/Approval
Number
0786 – CPD – 20453
EN 54-10 + A1
—
—
LPCB
Basis of Approval
G 202136
VdS 2344
VdS 2504
EN 54-10 + A1
G 212019
VdS 2344
VdS 2504
EN 54-10 + A1
EN 54-17
S 212002*
VdS 2344
EN 54-13
S 212002*
VdS 2344
EN 54-13
—
—
0832 – CPD – 1381
EN 54-10 + A1
EN 54-17
973e/03
EN 54-10 + A1
973a/03
EN 54-10 + A1
EN 54-17
VdS
BRE –
Constructive Product Directive
LON Output
Certificate/Approval
Number
* Approved for use in conjunction with the EN54-13 compliant EQP System.
INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM
The installation shall take into account, that the orientation arrow on the flame detector is directed
upwards, as the view angle in this direction is <90°.
The IR-flame detector configured to High or Very High sensitivity corresponds to class 1.
The IR-flame detector configured to T-Low or Low sensitivity corresponds to class 2.
The following accessories are EN54-10 and EN54-17 approved for use with the X3301 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
19.4
Q9033 Collar Attachment
35
95-8527
APPENDIX F
OFFSHORE APPROVALS
USCG APPROVAL
Coast Guard Approval No. 161.002/49/0
The scope of this approval is for a fire detection system meeting 46 CFR 161.002, as part of the Eagle Quantum Premier System.
MARINE EQUIPMENT DIRECTIVE
DNV Certificate No. MED-B-8184
Is found to comply with the requirements in the following Regulations / Standards:
Annex A.1, item No. A.1/3.51 and Annex B, Module B in the Directive. SOLAS 74 as amended, Regulation II-2/7 & X/3,
2000 HSC Code 7, FSS Code 9 and IMO MSC.1/Circ. 1242.
The equipment are found to comply with following location / application dependent requirements
(for definition of each of the location classes, see below the table):
MODEL
TEMPERATURE
VIBRATION
EMC
ENCLOSURE
X3301
TEM-D
VIB-B
EMC-B
ENC-C
Definition of the location classes with reference to relevant standards:
Temperature
TEM-D Location (–25°C-70°C) (ref. IEC 60092-504 (2001) table 1 item 6-7)
Vibration
VIB-D For eq. on reciprocating machines etc. (ref IEC 60092-504 (2001) table 1 item 10)
EMC
EMC-B Bridge and open deck zone (ref. IEC 60092-504 (2001) table 1 item 19-20)
Enclosure
ENC-C Open deck (IP56) (ref. IEC 60092-201 table 5)
Conformity to Module D, E and F.
TYPE APPROVAL
DNV Certificate No. A-13151.
Subject Matter of the Approval
IR Flame Detector Type X3301 for use in Ships, High Speed & Light Craft, and Offshore Applications.
Application Location Classes:
Location classes for X3301 IR Flame Detector with Mounting Arm Q9033B / Q9033A (Shaded areas show Det-Tronics approved location classes)
COLUMN 1
TYPE
Temperature
Humidity
Vibration
EMC (Electromagnetic
compatibility
LOCATION WITHIN MAIN AREA
Inside cubicles, desks, etc. with temperature rise of 5°C or more
All other locations
Locations where special precautions are taken to avoid
condensation
All other locations
On machinery such as internal combustion engines, compressors,
pumps, including piping on such machinery
Masts
All other locations
Enclosure
COLUMN 2
MAIN AREAS ON BOARD
Machinery Control room,
Pump room, Holds,
Bridge
Open Deck
spaces Accommodation
Rooms with no heating
B
B
B
D
D
A
A
A
C
D
A
A
A
A
A
B
B
B
B
B
B
—
—
B
B
—
A
—
A
—
A
—
A
—
A
All locations within specified main areas
A
A
B
A
B
Submerged application
Below floor plates in engine room
All other locations
D
C
B
—
—
A
—
—
A
D
—
B
D
—
C
TYPE APPROVAL
Lloyd's Register Certificate No. 09/00027.
Models Available: Relay output, relay 0-20 mA output, and EQP LON output versions.
The following accessories are offshore approved to the listed approvals, for use with the X3301 Flame Detector:
Part Number
Description
102740-002
007739-001
007290-001
007290-002
011385-001
Magnet
Magnet and Extension Pole
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment
19.4
36
95-8527
APPENDIX G
ADDITIONAL APPROVALS
SIL 2
BRAZIL
IEC 61508
UL-BR 12.0093X
Ex d e IIC T6-T5 Gb IP66/IP67
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C).
Certified SIL 2 Capable.
Applies to specific models – refer to the SIL 2
Certified X3301 Safety manual (95-8582) for
details.
– or –
Ex d IIC T6-T4 Gb IP66/IP67
Ex tb IIIC T130°C
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C).
FRANCE
AFNOR Identification No: LIR 007 A0.
For specific information regarding the X3301
Flame Detector's conformity to NF EN54-10,
reference Addendum number 95-8726.
CHINA
RUSSIA
NEPSI Certification No. GYJ12.1294X
Ex d e IIC T5/T6 Gb
Ex d IIC T4~T6 Gb
DIP A21 TA 130°C IP66/IP67.
VNIIFTRI
CERTIFICATE OF CONFORMITY to TP TC
012/2011
2ExdeIICT6/T5 IP66
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C).
CCCF Certification No. 2013081801000455
GB15631-2008, GB/T19001-2008
Applies to Output Types 11, 13, 21, and 23 only.
– or –
1ExdIICT6/T5/T4 IP66
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C).
VNIIPO
CERTIFICATE OF CONFORMITY to
TECHNICAL REGULATIONS, GOST R 533252009
KAZAKHSTAN
MES (Ministry of Emergency Situations)
Approval for use No. 18-02-02/896
19.4
37
95-8527
95-8527
FlexSonic ® Acoustic
Leak Detector
X3301 Multispectrum
IR Flame Detector
Corporate Office
6901 West 110 th Street
Minneapolis, MN 55438 USA
www.det-tronics.com
PointWatch Eclipse ® IR
Combustible Gas Detector
Phone: 952.946.6491
Toll-free: 800.765.3473
Fax: 952.829.8750
det-tronics@det-tronics.com
FlexVu ® Universal Display
with GT3000 Toxic Gas Detector
Eagle Quantum Premier ®
Safety System
All trademarks are the property of their respective owners.
© 2015 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001—
the world’s most recognized quality management standard.