Open Path Gas Detection
How the LELm Reading is Calculated
L.E.L.metre
TRANSMITTER
RECEIVER
The OPGD’s measure the total quantity of hydrocarbons in the beam.
•The Measurement is expressed as the length of the gas cloud in the beam (metres)
multiplied by the gas concentration in the traditional units of Lower Explosive Limit (LEL)
producing a measuring scale in LEL.metres.
•In the example above, the length of the cloud is 5 metres; the average concentration of gas
within it is 20% avgLEL. Therefore 5m x 20%LEL = 100%LELm = 1 LEL.metre
Open Path Gas Detection
How the LELm Reading is Calculated
1m
100% LEL
Absorption
(dB)
OUTPUT = 1LELM
1
2
3
LELm
34 | 77
Polytron Pulsar OPGD| Dow Chemical |
4
5
Open Path Gas Detection
How the LELm Reading is Calculated
2m
50% LEL
Absorption
(dB)
OUTPUT = 1LELM
1
2
3
LELm
35 | 77
Polytron Pulsar OPGD| Dow Chemical |
4
5
Open Path Gas Detection
How the LELm Reading is Calculated
Does the open path detector know the concentration of gas and size of cloud in its
beam path?
– No
So how can it give a reading based on the two units of LEL and metres?
– During factory calibration a number of gas cells of a known size, filled with a
known concentration of gas are introduced into the beam path of each
detector. The different levels of IR absorption are then recorded into the
memory of each Receiver.
36 | 77
Polytron Pulsar OPGD| Dow Chemical |
Open Path Gas Detection
LELm Output
When the Receiver unit detects absorption of the IR signal wavelength. A check
of its memory verifies the level of gas present and the unit outputs a reading in mA
to a control system.
A Hydrocarbon gas is built up of CH molecules, the more gas present the more
molecules present. This could be in the form of a large concentration over a small
area or large volumetric amount with low concentration.
The open path gas detector does not differentiate between a small cloud of high
concentration, or a large cloud of low concentration.
37 | 77